 s  SIMOREG DC Master 6RA70 Series Operating Instructions Microprocessor-Based Converters from 6kW to 2500kW for Variable-Speed DC Drives Edition 10 Order-No.: 6RX1700-0AD76

6RA70 Operating Instruction_Total-Rev10

Embed Size (px)

Citation preview

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    1/726

    s

    SIMOREG DC Master

    6RA70 Series

    Operating Instructions

    Microprocessor-Based Converters from 6kW to 2500kW

    for Variable-Speed DC Drives

    Edition 10 Order-No.: 6RX1700-0AD76

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    2/726

    General 01.04

    Siemens AG 1998 - 2004 All rights reserved

    These Operating Instructions are available in the following languages:

    Language German French Spanish Italian

    Order No. 6RX1700-0AD00 6RX1700-0AD77 6RX1700-0AD78 6RX1700-0AD72

    Converter software version:

    As these Operating Instructions went to print, SIMOREG DC Master converters were being delivered from the

    factory with software version 2.1 installed.

    These Operating Instructions also apply to other software versions.

    Earlier software versions: Some parameters described in this document might not be stored in the software(i.e. the corresponding functionality is not available on the converter) or someparameters will have a restricted setting range. If this is the case, however,appropriate reference to this status will be made in the Parameter List.

    Later software versions: Additional parameters might be available on the SIMOREG DC Master (i.e. extrafunctions might be available which are not described in these OperatingInstructions) or some parameters might have an extended setting range. In thiscase, leave the relevant parameters at their factory setting, or do not set anyparameter values which are not described in these Instructions !

    The software version of the SIMOREG DC Master can be read in parameters r060 and r065.

    The latest software version is available at the following Internet site:

    http://www4.ad.siemens.de/view/cs/en/8479576

    The reproduction, transmission or use of this document or contents is

    not permitted without express written authority. Offenders will be liable

    for damages. All rights, including rights created by patent grant or

    registration of a utility model or design, are reserved.

    We have checked that the contents of this publication agree with the

    hardware and software described herein. Nonetheless, differences

    might exist and therefore we cannot guarantee that they are completely

    identical. The information given in this publication is reviewed at regular

    intervals and any corrections that might be necessary are made in the

    subsequent printings. Suggestions for improvement are welcome at all

    times. SIMOREG is a registered trademark of Siemens

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    3/726

    01.04 Contents

    Siemens AG 6RX1700-0AD76 0-1SIMOREG DC Master Operating Instructions

    0 Contents

    Page

    1 Safety information

    2 Type spectrum

    2.1 Converter order number code 2-4

    2.2 Rating plate 2-5

    2.3 Packaging label 2-5

    2.4 Ordering information for options using codes 2-6

    3 Description

    3.1 Applications 3-1

    3.2 Design 3-1

    3.2.1 Special features of devices with 460V rated connection voltage 3-2

    3.2.2 Installation of SIMOREG devices in cabinets in accordance with UL508C standards 3-2

    3.3 Mode of operation 3-2

    3.4 Technical data 3-3

    3.4.1 Load types 3-3

    3.4.1.1 Load cycles for 1Q applications 3-4

    3.4.1.2 Load cycles for 4Q applications 3-53.4.2 Converters 3AC 400V, 30A to 125A, 1Q 3-7

    3.4.3 Converters 3AC 400V, 210A to 600A, 1Q 3-8

    3.4.4 Converters 3AC 400V, 850A to 2000A, 1Q 3-9

    3.4.5 Converters 3AC 460V, 30A to 125A, 1Q 3-10

    3.4.6 Converters 3AC 460V, 210A to 600A, 1Q 3-11

    3.4.7 Converters 3AC 460V, 850A to 1200A, 1Q 3-12

    3.4.8 Converters 3AC 575V, 60A to 600A, 1Q 3-13

    3.4.9 Converters 3AC 575V, 800A to 2200A, 1Q 3-14

    3.4.10 Converters 3AC 690V, 720A to 2000A, 1Q 3-15

    3.4.11 Converters 3AC 830V, 900A to 1900A, 1Q 3-16

    3.4.12 Converters 3AC 400V, 15A to 125A, 4Q 3-17

    3.4.13 Converters 3AC 400V, 210A to 600A, 4Q 3-18

    3.4.14 Converters 3AC 400V, 850A to 2000A, 4Q 3-19

    3.4.15 Converters 3AC 460V, 30A to 125A, 4Q 3-20

    3.4.16 Converters 3AC 460V, 210A to 600A, 4Q 3-21

    3.4.17 Converters 3AC 460V, 850A to 1200A, 4Q 3-22

    3.4.18 Converters 3AC 575V, 60A to 600A, 4Q 3-233.4.19 Converters 3AC 575V, 850A to 2200A, 4Q 3-24

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    4/726

    Contents 01.04

    0-2 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    Page

    3.4.20 Converters 3AC 690V, 760A to 2000A, 4Q 3-25

    3.4.21 Converters 3AC 830V, 950A to 1900A, 4Q 3-26

    3.4.22 Converters 3AC 400V, 3000A, 1Q / 4Q 3-27

    3.4.23 Converters 3AC 575V, 2800A, 1Q / 4Q 3-28

    3.4.24 Converters 3AC 690V, 2600A, 1Q / 4Q 3-29

    3.4.25 Converters 3AC 950V, 2200A, 1Q / 4Q 3-30

    3.5 Applicable standards 3-32

    3.6 Certification 3-33

    3.7 Abbreviations 3-33

    4 Shipment, unpacking

    4.1 Remove the transportation protection for devices with 1500A to 2200A rated DC 4-1

    5 Installation

    5.1 Dimension diagrams for standard devices 5-3

    5.1.1 Converters: 3AC 400V and 460V, 30A, 1Q 5-3

    5.1.2 Converters: 3AC 400V and 575V, 60A to 280A, 1Q 5-4

    5.1.3 Converters: 3AC 400V and 575V, 400A, 1Q 5-5

    5.1.4 Converters: 3AC 400V and 575V, 600A, 1Q 5-6

    5.1.5 Converters: 3AC 400V, 575V and 690V, 720A to 850A, 1Q 5-7

    5.1.6 Converters: 3AC 400V,460V, 575V, 690V and 830V, 900A to 1200A, 1Q 5-8

    5.1.7 Converters: 3AC 400V, 575V, 690V, and 830V, 1500A to 2000A, 575V/2200A 1Q 5-95.1.8 Converters: 3AC 400V / 3000A, 3AC 575V / 2800A, 3AC 690V / 2600A,

    3AC 950V / 2200A 1Q 5-10

    5.1.9 Converters: 3AC 400V and 460V, 15A to 30A, 4Q 5-11

    5.1.10 Converters: 3AC 400V and 575V, 60A to 280A, 4Q 5-12

    5.1.11 Converters: 3AC 400V and 575V, 400A to 600A, 4Q 5-13

    5.1.12 Converters: 3AC 400V, 575V and 690V, 760A to 850A, 4Q 5-14

    5.1.13 Converters: 3AC 400V, 460V, 575V, 690V and 830V, 950A to 1200A, 4Q 5-15

    5.1.14 Converters: 3AC 400V, 575V, 690V, and 830V, 1500A to 2000A, 575V/2200A 4Q 5-16

    5.1.15 Converters: 3AC 400V / 3000A, 3AC 575V / 2800A, 3AC 690V / 2600A,3AC 950V / 2200A 4Q 5-17

    5.2 Dimension diagrams of the devices with additional cable connectionson the top of the device 5-18

    5.2.1 Converters: 3AC 460V, 60A to 125A, 1Q 5-18

    5.2.2 Converters: 3AC 460V, 210A to 280A, 1Q 5-19

    5.2.3 Converters: 3AC 460V, 450A to 600A, 1Q 5-20

    5.2.4 Converters: 3AC 460V, 850A, 1Q 5-21

    5.2.5 Converters: 3AC 460V, 60A to 125A, 4Q 5-22

    5.2.6 Converters: 3AC 460V, 210A to 280A, 4Q 5-23

    5.2.7 Converters: 3AC 460V, 450A to 600A, 4Q 5-24

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    5/726

    01.04 Contents

    Siemens AG 6RX1700-0AD76 0-3SIMOREG DC Master Operating Instructions

    Page

    5.2.8 Converters: 3AC 460V, 850A, 4Q 5-25

    5.3 Mounting options 5-26

    5.3.1 Terminal expansion board CUD2 5-26

    5.3.2 Optional supplementary boards 5-27

    5.3.2.1 Local bus adapter (LBA) for mounting optional supplementary boards 5-27

    5.3.2.2 Mounting of optional supplementary boards 5-27

    6 Connections

    6.1 Installation instructions for proper EMC installation of drives 6-2

    6.1.1 Fundamental principles of EMC 6-2

    6.1.1.1 What is EMC 6-2

    6.1.1.2 Noise radiation and noise immunity 6-2

    6.1.1.3 Limit values 6-2

    6.1.1.4 SIMOREG converters in industrial applications 6-3

    6.1.1.5 Non-grounded supply systems 6-3

    6.1.1.6 EMC planning 6-3

    6.1.2 Proper EMC installation of drives (installation instructions) 6-4

    6.1.2.1 General 6-4

    6.1.2.2 Rules for proper EMC installation 6-4

    6.1.2.3 Converter component arrangement 6-13

    6.1.2.4 List of the recommended radio interference suppression filters 6-14

    6.1.3 Information on line-side harmonics generated by converters in afully-controlled three-phase bridge circuit configuration 6-15

    6.2 Block diagrams with recommended connection 6-17

    6.2.1 Converters: 15A to 125A 6-17

    6.2.2 Converters: 210A to 280A 6-18

    6.2.3 Converters: 400A to 3000A with a 3-phase fan 6-19

    6.2.4 Converters: 450A to 850A with a 1-phase fan 6-20

    6.3 Parallel connection of converters 6-21

    6.3.1 Circuit diagram showing parallel connection of SIMOREG converters 6-21

    6.3.2 Parameterization of SIMOREG converters for parallel connection 6-22

    6.3.2.1 Standard operating mode 6-22

    6.3.2.2 Operating mode "N+1 mode" (redundancy mode) 6-23

    6.4 Power connections 6-25

    6.4.1 Converters: 30A, 1Q 6-25

    6.4.2 Converters: 60A, 1Q 6-26

    6.4.3 Converters: 90A to 280A, 1Q 6-27

    6.4.4 Converters: 400A to 600A, 1Q 6-28

    6.4.5 Converters: 720A, 1Q 6-29

    6.4.6 Converters: 800 to 850A, 1Q 6-30

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    6/726

    Contents 01.04

    0-4 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    Page

    6.4.7 Converters: 900A to 950A, 1Q 6-31

    6.4.8 Converters: 1000 to 1200A, 1Q 6-32

    6.4.9 Converters: 1500 to 2000A, 575V/2200A, 1Q 6-33

    6.4.10 Converters: 400V/3000A, 575V/2800A, 690V/2600A, 950V/2200A 1Q 6-35

    6.4.11 Converters: 15 to 30A, 4Q 6-37

    6.4.12 Converters: 60A, 4Q 6-38

    6.4.13 Converters: 90A to 210A, 4Q 6-39

    6.4.14 Converters: 280A, 4Q 6-40

    6.4.15 Converters: 400A, 4Q 6-41

    6.4.16 Converters: 450A to 600A, 4Q 6-42

    6.4.17 Converters: 760A, 4Q 6-43

    6.4.18 Converters: 850A, 4Q 6-44

    6.4.19 Converters: 950A to 1000A, 4Q 6-45

    6.4.20 Converters: 1100 to 1200A, 4Q 6-46

    6.4.21 Converters: 1500 to 2000A, 575V/2200A, 4Q 6-47

    6.4.22 Converters: 400V/3000A, 575V/2800A, 690V/2600A, 950V/2200A 4Q 6-49

    6.5 Field supply 6-51

    6.6 Fuses and commutating reactors 6-54

    6.6.1 Commutating reactors 6-54

    6.6.2 Fuses 6-54

    6.6.2.1 Recommended fuses for field circuit 6-54

    6.6.2.2 Fuses for armature circuit 6-54

    6.6.2.2.1 Converters 1Q: 400V, 575V, 690V, 830V and 950V 6-54

    6.6.2.2.2 Converters 1Q: 460V 6-55

    6.6.2.2.3 Converters 4Q: 400V, 575V, 690V, 830V and 950V 6-56

    6.6.2.2.4 Converters 4Q: 460V 6-57

    6.6.2.3 F1 and F2 fuses in the power interface 6-57

    6.7 Terminal arrangement 6-58

    6.8 Terminal assignments 6-61

    7 Start-up

    7.1 General safety information 7-1

    7.2 Operator control panels 7-3

    7.2.1 Simple operator control panel (PMU) 7-3

    7.2.2 User-friendly operator control panel (OP1S) 7-4

    7.3 Parameterization procedure 7-6

    7.3.1 Parameter types 7-6

    7.3.2 Parameteratization on simple operator control panel 7-6

    7.4 Reset to default value and adjust offset 7-87.5 Start-up procedure 7-9

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    7/726

    01.04 Contents

    Siemens AG 6RX1700-0AD76 0-5SIMOREG DC Master Operating Instructions

    Page

    7.6 Manual optimization (if necessary) 7-18

    7.6.1 Manual setting of armature resistance RA (P110) andarmature inductance LA (P111) 7-18

    7.6.2 Manual setting of field resistance RF (P112) 7-19

    7.7 Starting up optional supplementary boards 7-207.7.1 Procedure for starting up technology boards (T100, T300, T400) 7-20

    7.7.2 Sequence of operations for starting up PROFIBUS boards (CBP2) 7-22

    7.7.2.1 Mechanisms for processing parameters via the PROFIBUS 7-24

    7.7.2.2 Diagnostic tools 7-25

    7.7.3 Sequence of operations for starting up CAN bus boards (CBC) 7-29

    7.7.3.1 Description of CBC with CAN Layer 2 7-30

    7.7.3.2 Description of CBC with CANopen 7-34

    7.7.3.2.1 Introduction to CANopen 7-34

    7.7.3.2.2 Functionality of CBC with CANopen 7-35

    7.7.3.2.3 Requirements for operating the CBC with CANopen 7-36

    7.7.3.3 Diagnostic tools 7-36

    7.7.4 Procedure for starting up SIMOLINK boards (SLB) 7-40

    7.7.5 Procedure for staring up expansion boards (EB1 and EB2) 7-44

    7.7.6 Procedure for starting up the pulse encoder board (SBP) 7-45

    7.7.7 Sequence of operations for starting up DeviceNet boards (CBD) 7-46

    7.7.7.1 Diagnostic tools 7-52

    7.7.8 Sequence of operations for starting up the serial I/O board (SCB1) 7-54

    7.7.8.1 Diagnostic tools 7-56

    7.7.9 Structure of request/response telegrams 7-57

    7.7.10 Transmission of double-word connectors for technology and communication modules 7-60

    8 Function diagrams

    9 Function descriptions

    9.1 General explanations of terms and functionality 9-1

    9.2 Computation cycles, time delay 9-69.3 Switch-on, shutdown, enabling 9-7

    9.3.1 OFF2 (voltage disconnection) - control word 1, bit 1 9-7

    9.3.2 OFF3 (Fast stop) - control word 1, bit 2 9-7

    9.3.3 Switch-on / shutdown (ON / OFF) terminal 37 - control word 1, bit 0 9-8

    9.3.4 Operating enable (enable) terminal 38 - control word 1, bit 3 9-11

    9.4 Ramp-function generator 9-11

    9.4.1 Definitions 9-12

    9.4.2 Operating principle of ramp-function generator 9-12

    9.4.3 Control signals for ramp-function generator 9-13

    9.4.4 Ramp-function generator settings 1, 2 and 3 9-13

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    8/726

    Contents 01.04

    0-6 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    Page

    9.4.5 Ramp-up integrator 9-14

    9.4.6 Ramp-function generator tracking 9-14

    9.4.7 Limitation after ramp-function generator 9-15

    9.4.8 Velocity signal dv/dt (K0191) 9-15

    9.5 Inching 9-15

    9.6 Crawling 9-16

    9.7 Fixed setpoint 9-16

    9.8 Safety shutdown (E-Stop) 9-17

    9.9 Activation command for holding or operating brake (low active) 9-18

    9.10 Switch on auxiliaries 9-21

    9.11 Switch over parameter sets 9-21

    9.12 Speed controller 9-22

    9.13 Serial interfaces 9-23

    9.13.1 Serial interfaces with USS protocol 9-24

    9.13.2 Serial interfaces with peer-to-peer protocol 9-27

    9.14 Thermal overload protection of DC motor(I2t monitoring of motor) 9-31

    9.15 Dynamic overload capability of power section 9-34

    9.15.1 Overview of functions 9-34

    9.15.2 Configuring for dynamic overload capability 9-35

    9.15.3 Characteristics for determining the dynamic overload capabilityfor intermittent overload operation 9-37

    9.16 Speed-dependent current limitation 9-72

    9.16.1 Setting the speed-dependent current limitation for motorswith commutation transition 9-73

    9.16.2 Setting of speed-dependent current limitation for motorswithout commutation transition 9-74

    9.17 Automatic restart 9-75

    9.18 Field reversal 9-75

    9.18.1 Direction of rotation reversal using field reversal 9-76

    9.18.2 Braking with field reversal 9-77

    9.19 Status description of some bits of status word ZSW1 9-79

    10 Faults / Alarms

    10.1 Fault messages 10-2

    10.1.1 General information about faults 10-2

    10.1.2 List of fault messages 10-2

    10.2 Alarms 10-25

    11 Parameter list

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    9/726

    01.04 Contents

    Siemens AG 6RX1700-0AD76 0-7SIMOREG DC Master Operating Instructions

    Page

    12 List of connectors and binectors

    12.1 Connector list 12-1

    12.2 Binector list 12-27

    13 Maintenance

    13.1 Procedure for updating software (upgrading to a new software version) 13-2

    13.2 Replacement of components 13-3

    13.2.1 Replacement of fan 13-3

    13.2.2 Replacement of PCBs 13-7

    13.2.3 Replacement of thyristor modules on converters up to 1200A 13-8

    13.2.4 Replacement of fuses and thyristor assemblies on converters of 1500A and above 13-9

    14 Servicing

    14.1 Technical Support 14-1

    14.1.1 Time zone Europe and Africa 14-1

    14.1.2 Time zone America 14-1

    14.1.3 Time zone Asia / Australia 14-1

    14.2 Spare parts 14-2

    14.3 Repairs 14-2

    14.4 On-site servicing 14-2

    15 DriveMonitor

    15.1 Scope of delivery 15-1

    15.2 Installing the software 15-1

    15.3 Connecting the SIMOREG to the PC 15-1

    15.4 Setting up an online link to the SIMOREG 15-2

    15.5 Further information 15-2

    16 Environmental compatibility

    17 Applications

    18 Appendix

    18.1 Additional documentation 18-1

    Sheet for customer feedback 18-3

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    10/726

    Contents 01.04

    0-8 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    11/726

    01.04 Safety Information

    SIEMENS AG 6RX1700-0AD76 1-1SIMOREG DC Master Operating Instructions

    1 Safety information

    WARNING

    Hazardous voltages and rotating parts (fans) are present in this electrical equipment duringoperation. Non-observance of the safety instructions can result in death, severe personal injuryor substantial property damage.

    Only qualified personnel should work on or around the equipment after first becomingthoroughly familiar with all warning and safety notices and maintenance procedures containedherein. The successful and safe operation of this equipment is dependent on proper handling,installation, operation and maintenance.

    Definitions:

    QUALIFIED PERSONNEL

    For the purpose of this Instruction Manual and product labels, a "Qualified person" is someonewho is familiar with the installation, construction and operation of the equipment and the hazardsinvolved. He or she must have the following qualifications:

    1. Trained and authorized to energize, de-energize, clear, ground and tag circuits andequipment in accordance with established safety procedures.

    2. Trained in the proper care and use of protective equipment in accordance with establishedsafety procedures.

    3. Trained in rendering first aid.

    VDANGER

    indicates an imminently hazardous situation which, if not avoided, will result in death or serious

    injury.

    VWARNING

    indicates a potentially hazardous situation which, if not avoided, could result in death or seriousinjury.

    VCAUTION

    used with the safety alert symbol indicates a potentially hazardous situation which, if notavoided, may result in minor or moderate injury.

    CAUTIONused without the safety alert symbol indicates a potentially hazardous situation which, if notavoided, may result in property damage.

    NOTICE

    NOTICE used without the safety alert symbol indicates a potentially situation which, if notavoided, may result in an undesirable result or state.

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    12/726

    Safety Information 01.04

    1-2 SIEMENS AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    NOTE

    These operating instructions do not purport to cover all details or variations in equipment, nor toprovide for every possible contingency to be met in connection with installation, operation ormaintenance.

    Should further information be desired or should particular problems arise which are not coveredsufficiently for the purchaser's purposes, the matter should be referred to the local SiemensSales Office.

    The contents of these operating instructions shall not become part or modify any prior or existingagreement, commitment or relationship. The Sales Contract contains the entire obligations ofSiemens. The warranty contained in the contract between the parties is the sole warranty ofSiemens. Any statements contained herein do not create new warranties or modify the existingwarranty.

    DANGER

    Converters contain hazardous electrical voltages, Death, severe bodily injury or significantmaterial damage can occur if the safety measures are not followed.

    1. Only qualified personnel, who are knowledgeable about the converters and the providedinformation, can install, start up, operate, troubleshoot or repair the converters.

    2. The converters must be installed in accordance with all relevant safety regulations (e.g. DINVDE) as well as all other national or local regulations. Operational safety and reliability mustbe ensured by correct grounding, cable dimensioning and appropriate short-circuitprotection.

    3. All panels and doors must be kept closed during normal operation.

    4. Before carrying out visual checks and maintenance work, ensure that the AC power supply

    is disconnected and locked out. Before the AC supply is disconnected, both converters andmotors have hazardous voltage levels. Even when the converter contactor is open,hazardous voltages are still present.

    5. When making measurements with the power supply switched on, electrical connectionsmust not be touched under any circumstances. Remove all jewelry from wrists and fingers.Ensure that the test equipment is in good conditions and operationally safe.

    6. When working on units which are switched on, stand on an insulating surface, i.e. ensurethat you are not grounded.

    7. Carefully follow the relevant instructions and observe all danger, warning and cautionaryinstructions.

    8. This does not represent a full listing of all the measures necessary for safe operation of the

    equipment. If you require other information or if certain problems occur which are nothandled in enough detail in the information provided in the Instruction Manual, pleasecontact your local Siemens office.

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    13/726

    01.04 Safety Information

    SIEMENS AG 6RX1700-0AD76 1-3SIMOREG DC Master Operating Instructions

    CAUTION

    Electrostatically sensitive devicesThe converter contains electrostatically sensitive devices. These can easily be destroyed if they are nothandled correctly. If, however, it is absolutely essential for you to work on electronic modules, please pay

    careful attention to the following instructions:

    Electronic modules (PCBs) should not be touched unless work has to be carried out on them.

    Before touching a PCB, the person carrying out the work must himself be electrostatically discharged.The simplest way of doing this is to touch an electrically conductive earthed object, e.g. socket outletearth contact.

    PCBs must not be allowed to come into contact with electrically insulating materials plastic foil,

    insulating table tops or clothing made of synthetic fibers

    PCBs may only be set down or stored on electrically conducting surfaces.

    When carrying out soldering jobs on PCBs, make sure that the soldering tip has been earthed.

    PCBs and electronic components should generally be packed in electrically conducting containers (suchas metallized-plastic boxes or metal cans) before being stored or shipped.

    If the use of non-conducting packing containers cannot be avoided, PCBs must be wrapped in aconducting material before being put in them. Examples of such materials include electrically conductingfoam rubber or household aluminium foil.

    For easy reference, the protective measures necessary when dealing with sensitive electronic componentsare illustrated in the sketches below.

    a = Conductive flooring d = Anti-static overall

    b = Anti-static table e = Anti-static chain

    c = Anti-static footwear f = Earthing connections of cabinets

    a

    b

    e

    d

    f f f

    d

    ac

    e

    d

    f f

    b

    ca

    Seated workstation Standing workstation Standing/seated workstation

    WARNING

    Hazardous voltages and rotating parts (fans) are present in this electrical equipment duringoperation.

    Non-observance of the safety instructions can result in death, severe personal injury orsubstantial property damage.

    Only qualified personnel should work on or around the equipment after first becomingthoroughly familiar with all warning and safety notices and maintenance procedures containedherein.

    The successful and safe operation of this equipment is dependent on proper handling,installation, operation and maintenance.

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    14/726

    Safety Information 01.04

    1-4 SIEMENS AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    15/726

    01.04 Type spectrum

    Siemens AG 6RX1700-0AD76 2-1SIMOREG DC Master Operating Instructions

    2 Type spectrum

    600A converters 1200A converter 2200A, 3000A converter 850A converters

    60A converters

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    16/726

    Type spectrum 01.04

    2-2 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    Converter order no. Type designation

    6RA7018 - 6DS22 - 0 D485 / 30 Mre - GeE6S226RA7025 - 6DS22 - 0 D485 / 60 Mre - GeE6S226RA7028 - 6DS22 - 0 D485 / 90 Mre - GeE6S226RA7031 - 6DS22 - 0 D485 / 125 Mre - GeE6S22

    6RA7075 - 6DS22 - 0 D485 / 210 Mre - GeEF6S226RA7078 - 6DS22 - 0 D485 / 280 Mre - GeEF6S226RA7081 - 6DS22 - 0 D485 / 400 Mre - GeEF6S226RA7085 - 6DS22 - 0 D485 / 600 Mre - GeEF6S226RA7087 - 6DS22 - 0 D485 / 850 Mre - GeEF6S226RA7091 - 6DS22 - 0 D485 / 1200 Mre - GeEF6S22

    6RA7093 - 4DS22 - 0 D485 / 1600 Mre - GeEF4S226RA7095 - 4DS22 - 0 D485 / 2000 Mre - GeEF4S226RA7098 - 4DS22 - 0 D485 / 3000 Mre - GeEF4S22

    6RA7018 - 6FS22 - 0 D550 / 30 Mre - GeE6S226RA7025 - 6FS22 - 0 D550 / 60 Mre - GeE6S226RA7028 - 6FS22 - 0 D550 / 90 Mre - GeE6S22

    6RA7031 - 6FS22 - 0 D550 / 125 Mre - GeE6S22

    6RA7075 - 6FS22 - 0 D550 / 210 Mre - GeEF6S226RA7078 - 6FS22 - 0 D550 / 280 Mre - GeEF6S226RA7082 - 6FS22 - 0 D550 / 450 Mre - GeEF6S226RA7085 - 6FS22 - 0 D550 / 600 Mre - GeEF6S226RA7087 - 6FS22 - 0 D550 / 850 Mre - GeEF6S226RA7091 - 6FS22 - 0 D550 / 1200 Mre - GeEF6S22

    6RA7025 - 6GS22 - 0 D690 / 60 Mre - GeE6S226RA7031 - 6GS22 - 0 D690 / 125 Mre - GeE6S22

    6RA7075 - 6GS22 - 0 D690 / 210 Mre - GeEF6S22

    6RA7081 - 6GS22 - 0 D690 / 400 Mre - GeEF6S226RA7085 - 6GS22 - 0 D690 / 600 Mre - GeEF6S226RA7087 - 6GS22 - 0 D690 / 800 Mre - GeEF6S226RA7090 - 6GS22 - 0 D690 / 1000 Mre - GeEF6S22

    6RA7093 - 4GS22 - 0 D690 / 1600 Mre - GeEF4S226RA7095 - 4GS22 - 0 D690 / 2000 Mre - GeEF4S226RA7096 - 4GS22 - 0 D690 / 2200 Mre - GeEF4S226RA7097 - 4GS22 - 0 D690 / 2800 Mre - GeEF4S22

    6RA7086 - 6KS22 - 0 D830 / 720 Mre - GeEF6S226RA7088 - 6KS22 - 0 D830 / 950 Mre - GeEF6S22

    6RA7093 - 4KS22 - 0 D830 / 1500 Mre - GeEF4S226RA7095 - 4KS22 - 0 D830 / 2000 Mre - GeEF4S226RA7097 - 4KS22 - 0 D830 / 2600 Mre - GeEF4S22

    6RA7088 - 6LS22 - 0 D1000 / 900 Mre - GeEF6S22

    6RA7093 - 4LS22 - 0 D1000 / 1500 Mre - GeEF4S226RA7095 - 4LS22 - 0 D1000 / 1900 Mre - GeEF4S22

    6RA7096 - 4MS22 - 0 D1140 / 2200 Mre - GeEF4S22

    Rated Rated

    DC voltage DC current

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    17/726

    01.04 Type spectrum

    Siemens AG 6RX1700-0AD76 2-3SIMOREG DC Master Operating Instructions

    Converter order no. Type designation

    6RA7013 - 6DV62 - 0 D420 / 15 Mreq - GeG6V626RA7018 - 6DV62 - 0 D420 / 30 Mreq - GeG6V626RA7025 - 6DV62 - 0 D420 / 60 Mreq - GeG6V626RA7028 - 6DV62 - 0 D420 / 90 Mreq - GeG6V626RA7031 - 6DV62 - 0 D420 / 125 Mreq - GeG6V62

    6RA7075 - 6DV62 - 0 D420 / 210 Mreq - GeGF6V626RA7078 - 6DV62 - 0 D420 / 280 Mreq - GeGF6V626RA7081 - 6DV62 - 0 D420 / 400 Mreq - GeGF6V626RA7085 - 6DV62 - 0 D420 / 600 Mreq - GeGF6V626RA7087 - 6DV62 - 0 D420 / 850 Mreq - GeGF6V626RA7091 - 6DV62 - 0 D420 / 1200 Mreq - GeGF6V62

    6RA7093 - 4DV62 - 0 D420 / 1600 Mreq - GeGF4V626RA7095 - 4DV62 - 0 D420 / 2000 Mreq - GeGF4V626RA7098 - 4DV62 - 0 D420 / 3000 Mreq - GeGF4V62

    6RA7018 - 6FV62 - 0 D480 / 30 Mreq - GeG6V626RA7025 - 6FV62 - 0 D480 / 60 Mreq - GeG6V62

    6RA7028 - 6FV62 - 0 D480 / 90 Mreq - GeG6V626RA7031 - 6FV62 - 0 D480 / 125 Mreq - GeG6V62

    6RA7075 - 6FV62 - 0 D480 / 210 Mreq - GeGF6V626RA7078 - 6FV62 - 0 D480 / 280 Mreq - GeGF6V626RA7082 - 6FV62 - 0 D480 / 450 Mreq - GeGF6V626RA7085 - 6FV62 - 0 D480 / 600 Mreq - GeGF6V626RA7087 - 6FV62 - 0 D480 / 850 Mreq - GeGF6V626RA7091 - 6FV62 - 0 D480 / 1200 Mreq - GeGF6V62

    6RA7025 - 6GV62 - 0 D600 / 60 Mreq - GeG6V626RA7031 - 6GV62 - 0 D600 / 125 Mreq - GeG6V62

    6RA7075 - 6GV62 - 0 D600 / 210 Mreq - GeGF6V626RA7081 - 6GV62 - 0 D600 / 400 Mreq - GeGF6V626RA7085 - 6GV62 - 0 D600 / 600 Mreq - GeGF6V626RA7087 - 6GV62 - 0 D600 / 850 Mreq - GeGF6V626RA7090 - 6GV62 - 0 D600 / 1100 Mreq - GeGF6V62

    6RA7093 - 4GV62 - 0 D600 / 1600 Mreq - GeGF4V626RA7095 - 4GV62 - 0 D600 / 2000 Mreq - GeGF4V626RA7096 - 4GV62 - 0 D600 / 2200 Mreq - GeGF4V626RA7097 - 4GV62 - 0 D600 / 2800 Mreq - GeGF4V62

    6RA7086 - 6KV62 - 0 D725 / 760 Mreq - GeGF6V626RA7090 - 6KV62 - 0 D725 / 1000 Mreq - GeGF6V62

    6RA7093 - 4KV62 - 0 D725 / 1500 Mreq - GeGF4V626RA7095 - 4KV62 - 0 D725 / 2000 Mreq - GeGF4V626RA7097 - 4KV62 - 0 D725 / 2600 Mreq - GeGF4V62

    6RA7088 - 6LV62 - 0 D875 / 950 Mreq - GeGF6V62

    6RA7093 - 4LV62 - 0 D875 /1500 Mreq - GeGF4V626RA7095 - 4LV62 - 0 D875 /1900 Mreq - GeGF4V62

    6RA7096 - 4MV62 - 0 D1000 /2200 Mreq - GeGF4V62

    Rated RatedDC voltage DC current

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    18/726

    Type spectrum 01.04

    2-4 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    2.1 Converter order number code

    6 R A - - 0 -

    Code letters defined acc. Options:to general MLFB guidelines: Z: With option

    Converter model: Innovation23: SIMOREG Comp. 4th Gen.24: SIMOREG Comp. 4th Gen. Digital Closed-loop control:70: SIMOREG DC Master 1: Uncontrolled field

    2: Controlled field

    Closed-loop control:Rated DC currents and cooling: 1: 1Q analogNatural cooling: Separate cooling 2: 1Q digital

    Ambient temp. Ambient temp.+45C +35C / +40C on 6RA70 7: 4Q analog

    6: 4Q digital00: 5001: 3.6.......

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    19/726

    01.04 Type spectrum

    Siemens AG 6RX1700-0AD76 2-5SIMOREG DC Master Operating Instructions

    2.2 Rating plate

    SIMOREGs DC - CONVERTER

    1)

    Order No. / Type 1P 6RA70 . . - . . . . . - 0 2)

    3)

    4)

    Serial No. S Q6 . . . . . . . . . .

    ARMATURE

    Input 3AC . . . V . . . A 50/60HzSuitable for use on a circuit capable of delivering not morethan . . . kA rms symmetrical amperes , . . . V maximum.

    Output (DC-Rating) DC . . . V . . . AOutput (US-Rating) DC . . . V . . . A

    FIELD SUPPLYInput 2AC . . . V . . . A 50/60HzOutput DC . . . V . . . A

    Prod. State 5)

    Cooling

    6)EN 60146

    Made in Austria

    1) Bar code for order number (MLFB)

    2) A -Z is affixed after the MLFB foroptions

    3) Code for options (order-specific)

    4) Bar code, serial number (order-specific)

    5) Product version

    6) Space for other symbol

    e.g.:

    2.3 Packaging label

    DC - CONVERTER sStromrichter

    Static Converter

    Variateur

    D . . . / . . . . M . . . -GeE . . . . 2

    6RA70 . . - . . . . . - 0 1)EN 60146

    1P6RA70 . . - . . . . . - 0 . . . , . . . , . . . , . . . , . . . , . . . 2)

    S Q6 . . . . . . . . . . QTY 1

    SW - STAND E - STAND

    Q . . . . . . (Version) (Version)

    - - - - - -Made in Austria

    1) Space for othersymbol

    e.g.:

    2) A -Z is affixed tothe MLFB foroptions,followed by thecode for therelevant option(order-specific)

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    20/726

    Type spectrum 01.04

    2-6 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    2.4 Ordering information for options using codes

    SIMOREG converter order no. withsuffix Z and

    codes (several codes together)and/or

    plaintext (if required)

    Options Codes Order No.

    Technology software in the basic converter ("Free functionblocks")

    S00 6RX1700-0AS00

    Module terminal expansion (CUD2) K00 6RX1700-0AK00

    DriveMonitor PC - PMU (RS232) connecting cable, 3m 6SX7005-0AB00

    User-friendly operator control panel (OP1S) 6SE7090-0XX84-2FK0

    AOP1 adapter for mounting OP1A in cubicle door, including

    5 m connecting cable

    6SX7010-0AA00

    PMU-OP1S connecting cable, 3m 6SX7010-0AB03

    PMU-OP1S connecting cable, 5m 6SX7010-0AB05

    LBA Local bus adapter for the electronics boxLBA is always needed to install supplementary boards(see Section 5.3.2)

    K11 6SE7090-0XX84-4HA0

    ADB Adapter boardADB is always needed to install CBC, CBP, EB1, EB2,SBP and SLB boards

    K01, K02 5) 6SE7090-0XX84-0KA0

    SBP Pulse encoder evaluation board 1) 2)3)

    (miniature-format board; ADB required)C14, C15C16, C17 5)

    6SX7010-0FA00

    EB1 Terminal expansion board 3)(miniature-format board; ADB required)

    G64, G65G66, G67 5)

    6SE7090-0XX84-0KB0

    EB2 Terminal expansion board 3)(miniature-format board; ADB required)

    G74, G75G76, G77 5)

    6SE7090-0XX84-0KC0

    SLB SIMOLINK board 1) 3)

    (miniature-format board; ADB required)G44, G45G46, G47 5)

    6SX7010-0FJ00

    CBP2 Communications board with interface for SINEC- L2-DP, (PROFIBUS) 1) 3)

    (miniature-format board; ADB required)

    G94, G95G96, G97 5)

    6SX7010-0FF05

    CBC Communications board with interface for CAN protocol1) 3)

    (miniature-format board; ADB required)

    G24, G25G26, G27 5)

    6SX7010-0FG00

    CBD Communications board with interface for DeviceNetprotocol 1) 3)

    (miniature-format board; ADB required)

    G54, G55G56, G57 5)

    6SX7010-0FK00

    SCB1 Serial Communication Board 1 (Master for SCI1 andSCI2 with FO link) 3) 4)

    6SE7090-0XX84-0BC0

    SCI1 Serial Communication Interface 1(terminal expansion with FO link to SCB1) forattachment to DIN EN 50022 rail 4)

    6SE7090-0XX84-3EA0

    6 R A 7 00 Z

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    21/726

    01.04 Type spectrum

    Siemens AG 6RX1700-0AD76 2-7SIMOREG DC Master Operating Instructions

    Options Codes Order No.

    SCI2 Serial Communication Interface 2(terminal expansion with FO link to SCB1) forattachment to DIN EN 50022 rail 4)

    6SE7090-0XX84-3EF0

    T100 module incl. hardware operating instructions withoutsoftware module) 3)

    6SE7090-0XX87-0BB0

    Hardware operating instructions for T100 6SE7080-0CX87-0BB0

    MS100 "Universal Drive software module for T100 (EPROM)without manual

    6SE7098-0XX84-0BB0

    Manual for MS100 "Universal Drive" software module

    German 6SE7080-0CX84-0BB1

    English 6SE7087-6CX84-0BB1

    French 6SE7087-7CX84-0BB1

    Spanish 6SE7087-8CX84-0BB1

    Italian 6SE7087-2CX84-0BB1

    T300 technology board with 2 connecting leads, SC58 andSC60, terminal block SE300 and hardware operatinginstructions 3)

    6SE7090-0XX84-0AH0

    T400 technology board (incl. short description) 3)

    T400 hardware and configuring manual

    6DD1606-0AD0

    6DD1903-0EA0

    Operating instructions for SIMOREG DC Master

    Operating instructions in German D00 6RX1700-0AD00

    Operating instructions in Italian D72 6RX1700-0AD72

    Operating instructions in English D76 6RX1700-0AD76

    Operating instructions in French D77 6RX1700-0AD77

    Operating instructions in Spanish D78 6RX1700-0AD78

    Operating instructions and DriveMonitor in all the abovelanguages available on CD-ROM

    D64 6RX1700-0AD64

    No description D99

    1) These boards can be ordered under two different numbers, i.e.

    under the order number of the board without accessories (such as connectors and Short Guide)

    as a retrofit kit: Board with connectors and Short Guide

    Board Order number of board (w/o accessories) Order number of retrofit kit

    ADB 6SE7090-0XX84-0KA0 6SE7010-0KA00

    SBP 6SE7090-0XX84-0FA0 6SE7010-0FA00

    EB1 6SE7090-0XX84-0KB0 6SE7010-0KB00

    EB2 6SE7090-0XX84-0KC0 6SE7010-0KC00

    SLB 6SE7090-0XX84-0FJ0 6SE7010-0FJ00

    CBP2 6SE7090-0XX84-0FF5 6SE7010-0FF05

    CBC 6SE7090-0XX84-0FG0 6SE7010-0FG00

    CBD 6SE7090-0XX84-0FK0 6SE7010-0FK00

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    22/726

    Type spectrum 01.04

    2-8 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    The retrofit kit must be ordered to install boards in the SMOREG converter so that the correct connectorsfor system cabling and the Short Guide are also available.

    The LBA local bus adapter and ADB adapter board must be ordered as additional components forinstalling supplementary boards in the SIMOREG converter. These adapters are available under separateorder numbers.

    2) A pulse encoder evaluation circuit is a standard component of the basic SIMOREG converter. The SBPneed therefore be ordered only in configurations requiring evaluation of a second pulse encoder.

    3) An LBA local bus adapter is required to install this board in a SIMOREG converter. The adapter isavailable under a separate order number.

    4) Supplied packed separately, including 10 m fiber-optic cable.

    5) The last figure in the order code identifies the module location or slot of the electronic box (see Section5.3.2):

    1 . . . Board location 2

    2 . . . Board location 3

    4 . . . Slot D

    5 . . . Slot E6 . . . Slot F

    7 . . . Slot G

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    23/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-1SIMOREG DC Master Operating Instructions

    3 Description

    3.1 Applications

    Series 6RA70 SIMOREG DC MASTER converters are fully digital, compact units for three-phasesupply which supply the armature and field of variable-speed DC drives with rated armaturecurrents of between 15A and 3000A. The compact converters can be connected in parallel tosupply currents of up to 12000A. The field circuit can be supplied with currents of up to 85A (currentlevels depend on the armature rated current).

    3.2 Design

    Series 6RA70 SIMOREG DC MASTER converters are characterized by their compact, space-saving construction. Their compact design makes them particularly easy to service and maintainsince individual components are readily accessible. The electronics box contains the basicelectronic circuitry as well as any supplementary boards.

    All SIMOREG DC MASTER units are equipped with a PMU simple operator panel mounted in theconverter door. The panel consists of a five-digit, seven-segment display, three LEDs as statusindicators and three parameterization keys. The PMU also features connector X300 with a USSinterface in accordance with the RS232 or RS485 standard.The panel provides all the facilities for making adjustments or settings and displaying measuredvalues required to start up the converter.

    The OP1S optional converter operator panel can be mounted either in the converter door orexternally, e.g. in the cubicle door. For this purpose, it can be connected up by means of a 5 m longcable. Cables of up to 200 m in length can be used if a separate 5 V supply is available. The OP1Sis connected to the SIMOREG via connector X300. The OP1S can be installed as an economicalternative to control cubicle measuring instruments which display physical measured quantities.The OP1S features an LCD with 4 x 16 characters for displaying parameter names in plaintext.German, English, French, Spanish and Italian can be selected as the display languages.

    The OP1S can store parameter sets for easy downloading to other devices.

    The converter can also be parameterized on a standard PC with appropriate software connected tothe serial interface on the basic unit. This PC interface is used during start-up, for maintenanceduring shutdown and for diagnosis in operation. Furthermore, converter software upgrades can beloaded via this interface for storage in a Flash memory.

    On single-quadrant converters, the armature is supplied via a fully controlled three-phase bridgeB6C and, on four-quadrant devices, via two fully controlled three-phase bridges in circulating-current-free, inverse-parallel connection (B6)A(B6)C.The field is supplied via a single-phase, branch-pair half-controlled 2-pulse bridge connectionB2HZ.The frequencies of the armature and field supply voltages may be different (in a range from 45 to65 Hz). Operation in the extended frequency range between 23 Hz and 110 Hz is available on

    request. The armature circuit supply phase sequence is insignificant.

    For converters with 15A to 850A (1200A at 400V supply voltage) rated DC current, the powersection for armature and field is constructed of isolated thyristor modules. The heat sink is thuselectrically isolated. On devices with a higher rated DC current, the power section for the armaturecircuit is constructed of disk thyristors and heat sinks (thyristor assemblies) at voltage potential. Thehousing and terminal covers on power connections provide protection against accidental contact foroperators working in the vicinity. All connecting terminals are accessible from the front.

    The power section cooling system is monitored by means of temperature sensors.

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    24/726

    Description 01.04

    3-2 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    3.2.1 Special features of devices with 460V rated connection voltage

    This device series is available with rated direct currents of 30A to 1200A.

    Devices with rated direct currents of 450A to 1200A are equipped with a 1-phase fan.

    On devices with rated direct currents of 60A to 850A, the power terminals are located on theunderside and on the top of the device.

    3.2.2 Installation of SIMOREG devices in cabinets in accordance with UL 508 Cstandards

    When the drive is provided in a panel (enclosure), the panel is ventilated and designated"Type 1".

    The minimum size panel (enclosure) to be used with the drive is 600 mm length, 600 mm width,2200 mm height.

    3.3 Mode of operation

    All open-loop and closed-loop drive control and communication functions are performed by twopowerful microprocessors. Drive control functions are implemented in the software as programmodules which can be "wired up" by parameters.

    The rated DC currents (continuous DC currents), load class , specified on the rated plate can beexceeded by 180%, the permissible overload during being dependent on individual converters. Themicroprocessor calculates the current I2t value of the power section cyclically to ensure that thethyristors are not damaged in overload operation.

    A selection table for overload operation can be found in Section 9 Description of functions".

    Converters self-adapt to the frequency of the available supply voltage in the range from 45 to 65 Hz(armature and field are independent).

    Operation in the extended frequency range between 23 Hz and 110 Hz is available on request.

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    25/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-3SIMOREG DC Master Operating Instructions

    3.4 Technical data

    3.4.1 Load types

    To adapt the SIMOREG DC Master to the load profile of the working machine as efficiently aspossible, you can dimension it using the load cycle.

    The setting on the SIMOREG DC Master is made in parameter P067.

    Load class Load for converter Load cycle

    DC I

    (P067=1)

    IDC I continuous (IdN)100%

    DC II

    (P067=2)IDC II for 15 min and 1.5 x IDC II for 60 s

    100%150%

    15min

    DC III

    (P067=3)

    IDC III for 15 min and 1.5 x IDC III for 120 s100%

    150%

    15min

    DC IV

    (P067=4)

    IDC IV for 15 min and 2 x IDC IV for 10 s

    100%200%

    15min

    US rating

    (P067=5)

    IUS for 15 min and 1.5 x IUS for 60 s

    Note:In this setting, an ambient or coolanttemperature of 45C is permissible for alldevice types.

    100%150%

    15min

    NOTICE

    If you set a value of > 1 in P067, you must ensure that the "Dynamic overload capability of powermodule is enabled, i.e. a value of > 0 must be set in parameter P075.

    The SIMOREG DC Master does not monitor for compliance with the criteria of the load class setin parameter P067. If permitted by the power module, the unit can operate for overload periodsin excess of those defined by the load class. The actual permissible overload period for theinstalled power module is always longer than the overload period defined for the load class. TheSIMOREG DC Master does monitor the actual permissible overload period for the powermodule. See Section 9.15.

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    26/726

    Description 01.04

    3-4 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    3.4.1.1 Load cycles for 1Q applications

    Load cycles

    Tu DC I DC II DC III DC IVUS rating

    Tu=45C

    continuous 15min100%

    60sec150%

    15min100%

    120 sec150%

    15min100%

    10sec200%

    15min100%

    60sec150%

    Recommended

    SIMOREG DC Master

    C A A A A A A A A A

    400V, 1Q

    6RA7018-6DS22 45 30 24.9 37.4 24.2 36.3 22.4 44.8 24.9 37.4

    6RA7025-6DS22 45 60 51.4 77.1 50.2 75.3 46.4 92.8 51.4 77.1

    6RA7028-6DS22 45 90 74.4 111.6 72.8 109.2 65.4 130.8 74.4 111.6

    6RA7031-6DS22 45 125 106.1 159.2 103.4 155.1 96.3 192.6 106.1 159.2

    6RA7075-6DS22 40 210 164.9 247.4 161.4 242.1 136.5 273.0 157.5 236.3

    6RA7078-6DS22 40 280 226.8 340.2 219.3 329.0 201.0 402.0 215.8 323.7

    6RA7081-6DS22 40 400 290.6 435.9 282.6 423.9 244.4 488.8 278.4 417.6

    6RA7085-6DS22 40 600 462.6 693.9 446.3 669.5 413.2 826.4 443.4 665.1

    6RA7087-6DS22 40 850 652.3 978.5 622.4 933.6 610.1 1220.2 620.2 930.3

    6RA7091-6DS22 40 1200 879.9 1319.9 850.8 1276.2 786.6 1573.2 842.6 1263.9

    6RA7093-4DS22 40 1600 1255.5 1883.3 1213.1 1819.7 1139.9 2279.8 1190.1 1785.2

    6RA7095-4DS22 40 2000 1510.2 2265.3 1456.3 2184.5 1388.8 2777.6 1438.7 2158.1

    6RA7098-4DS22 40 3000 2288.0 3432.0 2189.1 3283.6 2164.0 4328.0 2178.6 3267.9

    460V, 1Q

    6RA7018-6FS22 45 30 24.9 37.4 24.2 36.3 22.4 44.8 15.0 22.5

    6RA7025-6FS22 45 60 51.4 77.1 50.2 75.3 46.4 92.8 30.0 45.0

    6RA7028-6FS22 45 90 74.4 111.6 72.8 109.2 65.4 130.8 60.0 90.0

    6RA7031-6FS22 45 125 106.1 159.2 103.4 155.1 96.3 192.6 100.0 150.0

    6RA7075-6FS22 40 210 164.9 247.4 161.4 242.1 136.5 273.0 140.0 210.0

    6RA7078-6FS22 40 280 226.8 340.2 219.3 329.0 201.0 402.0 210.0 315.0

    6RA7082-6FS22 40 450 320.6 480.9 311.2 466.8 274.3 548.6 255.0 382.5

    6RA7085-6FS22 40 600 462.6 693.9 446.3 669.5 413.2 826.4 430.0 645.0

    6RA7087-6FS22 40 850 652.3 978.5 622.4 933.6 610.1 1220.2 510.0 765.0

    6RA7091-6FS22 40 1200 879.9 1319.9 850.8 1276.2 786.6 1573.2 850.0 1275.0

    575V, 1Q

    6RA7025-6GS22 45 60 51.4 77.1 50.2 75.3 46.4 92.8 51.4 77.1

    6RA7031-6GS22 45 125 106.1 159.2 103.4 155.1 96.3 192.6 106.1 159.2

    6RA7075-6GS22 40 210 164.9 247.4 161.4 242.1 136.5 273.0 157.5 236.3

    6RA7081-6GS22 40 400 290.6 435.9 282.6 423.9 244.4 488.8 278.4 417.6

    6RA7085-6GS22 40 600 462.6 693.9 446.3 669.5 413.2 826.4 443.4 665.1

    6RA7087-6GS22 40 800 607.7 911.6 581.5 872.3 559.3 1118.6 578.0 867.0

    6RA7090-6GS22 40 1000 735.8 1103.7 713.4 1070.1 648.0 1296.0 700.4 1050.6

    6RA7093-4GS22 40 1600 1255.5 1883.3 1213.1 1819.7 1139.9 2279.8 1190.1 1785.2

    6RA7095-4GS22 40 2000 1663.0 2494.5 1591.2 2386.8 1568.4 3136.8 1569.5 2354.3

    6RA7096-4GS22 40 2200 1779.6 2669.4 1699.9 2549.9 1697.2 3394.4 1678.0 2517.0

    6RA7097-4GS22 40 2800 2136.6 3204.9 2044.1 3066.1 2022.1 4044.2 2024.0 3036.0

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    27/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-5SIMOREG DC Master Operating Instructions

    Load cycles

    Tu DC I DC II DC III DC IVUS rating

    Tu=45C

    continuous 15min100%

    60sec150%

    15min100%

    120 sec150%

    15min100%

    10sec200%

    15min100%

    60sec150%

    Recommended

    SIMOREG DC Master

    C A A A A A A A A A

    690V, 1Q

    6RA7086-6KS22 40 720 553.1 829.7 527.9 791.9 515.8 1031.6 525.9 788.9

    6RA7088-6KS22 40 950 700.1 1050.2 677.1 1015.7 624.4 1248.8 668.1 1002.2

    6RA7093-4KS22 40 1500 1156.9 1735.4 1118.2 1677.3 1047.0 2094.0 1101.9 1652.9

    6RA7095-4KS22 40 2000 1589.3 2384.0 1522.2 2283.3 1505.5 3011.0 1503.9 2255.9

    6RA7097-4KS22 40 2600 1992.7 2989.1 1906.3 2859.4 1887.2 3774.4 1876.9 2815.3

    830V, 1Q

    6RA7088-6LS22 40 900 663.8 995.7 642.0 963.0 592.1 1184.2 633.5 950.3

    6RA7093-4LS22 40 1500 1156.9 1735.4 1118.2 1677.3 1047.0 2094.0 1101.9 1652.9

    6RA7095-4LS22 40 1900 1485.4 2228.1 1421.6 2132.4 1396.9 2793.8 1414.2 2121.3

    950V, 1Q

    6RA7096-4MS22 40 2200 1674.3 2511.4 1603.3 2404.9 1570.7 3141.4 1588.1 2382.1

    3.4.1.2 Load cycles for 4Q applications

    Load cycles

    Tu DC I DC II DC III DC IVUS rating

    Tu=45C

    continuous 15min

    100%

    60sec

    150%

    15min

    100%

    120 sec

    150%

    15min

    100%

    10sec

    200%

    15min

    100%

    60sec

    150%

    Recommended

    SIMOREG DC Master

    C A A A A A A A A A

    400V, 4Q

    6RA7013-6DV62 45 15 13.9 20.9 13.5 20.3 12.6 25.2 13.9 20.9

    6RA7018-6DV62 45 30 24.9 37.4 24.2 36.3 22.4 44.8 24.9 37.4

    6RA7025-6DV62 45 60 53.1 79.7 51.8 77.7 47.2 94.4 53.1 79.7

    6RA7028-6DV62 45 90 78.2 117.3 76.0 114.0 72.2 144.4 78.2 117.3

    6RA7031-6DV62 45 125 106.1 159.2 103.6 155.4 95.4 190.8 106.1 159.2

    6RA7075-6DV62 40 210 164.9 247.4 161.4 242.1 136.5 273.0 157.5 236.3

    6RA7078-6DV62 40 280 226.8 340.2 219.3 329.0 201.0 402.0 215.8 323.7

    6RA7081-6DV62 40 400 300.1 450.2 292.4 438.6 247.4 494.8 285.5 428.3

    6RA7085-6DV62 40 600 470.8 706.2 453.9 680.9 410.4 820.8 450.1 675.2

    6RA7087-6DV62 40 850 658.3 987.5 634.2 951.3 579.6 1159.2 626.4 939.6

    6RA7091-6DV62 40 1200 884.1 1326.2 857.5 1286.3 768.8 1537.6 842.3 1263.5

    6RA7093-4DV62 40 1600 1255.5 1883.3 1213.1 1819.7 1139.9 2279.8 1190.1 1785.2

    6RA7095-4DV62 40 2000 1477.7 2216.6 1435.3 2153.0 1326.7 2653.4 1404.6 2106.9

    6RA7098-4DV62 40 3000 2288.0 3432.0 2189.1 3283.6 2164.0 4328.0 2178.6 3267.9

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    28/726

    Description 01.04

    3-6 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    Load cycles

    Tu DC I DC II DC III DC IVUS rating

    Tu=45C

    continuous 15min100%

    60sec150%

    15min100%

    120 sec150%

    15min100%

    10sec200%

    15min100%

    60sec150%

    Recommended

    SIMOREG DC Master

    C A A A A A A A A A

    460V, 4Q

    6RA7018-6FV62 45 30 24.9 37.4 24.2 36.3 22.4 44.8 15.0 22.5

    6RA7025-6FV62 45 60 53.1 79.7 51.8 77.7 47.2 94.4 30.0 45.0

    6RA7028-6FV62 45 90 78.2 117.3 76.0 114.0 72.2 144.4 60.0 90.0

    6RA7031-6FV62 45 125 106.1 159.2 103.6 155.4 95.4 190.8 100.0 150.0

    6RA7075-6FV62 40 210 164.9 247.4 161.4 242.1 136.5 273.0 140.0 210.0

    6RA7078-6FV62 40 280 226.8 340.2 219.3 329.0 201.0 402.0 210.0 315.0

    6RA7082-6FV62 40 450 320.6 480.9 311.2 466.8 274.3 548.6 255.0 382.5

    6RA7085-6FV62 40 600 470.8 706.2 453.9 680.9 410.4 820.8 430.0 645.0

    6RA7087-6FV62 40 850 658.3 987.5 634.2 951.3 579.6 1159.2 510.0 765.06RA7091-6FV62 40 1200 884.1 1326.2 857.5 1286.3 768.8 1537.6 850.0 1275.0

    575V, 4Q

    6RA7025-6GV62 45 60 53.1 79.7 51.8 77.7 47.2 94.4 53.1 79.7

    6RA7031-6GV62 45 125 106.1 159.2 103.6 155.4 95.4 190.8 106.1 159.2

    6RA7075-6GV62 40 210 164.9 247.4 161.4 242.1 136.5 273.0 157.5 236.3

    6RA7081-6GV62 40 400 300.1 450.2 292.4 438.6 247.4 494.8 285.5 428.3

    6RA7085-6GV62 40 600 470.8 706.2 453.9 680.9 410.4 820.8 450.1 675.2

    6RA7087-6GV62 40 850 658.3 987.5 634.2 951.3 579.6 1159.2 626.4 939.6

    6RA7090-6GV62 40 1100 804.7 1207.1 782.6 1173.9 689.6 1379.2 766.8 1150.2

    6RA7093-4GV62 40 1600 1255.5 1883.3 1213.1 1819.7 1139.9 2279.8 1190.1 1785.2

    6RA7095-4GV62 40 2000 1663.0 2494.5 1591.2 2386.8 1568.4 3136.8 1569.5 2354.3

    6RA7096-4GV62 40 2200 1779.6 2669.4 1699.9 2549.9 1697.2 3394.4 1678.0 2517.0

    6RA7097-4GV62 40 2800 2136.6 3204.9 2044.1 3066.1 2022.1 4044.2 2024.0 3036.0

    690V, 4Q

    6RA7086-6KV62 40 760 598.7 898.1 575.4 863.1 532.9 1065.8 569.3 854.0

    6RA7090-6KV62 40 1000 737.3 1106.0 715.2 1072.8 639.5 1279.0 702.3 1053.5

    6RA7093-4KV62 40 1500 1171.6 1757.4 1140.1 1710.2 1036.6 2073.2 1116.2 1674.3

    6RA7095-4KV62 40 2000 1477.7 2216.6 1435.3 2153.0 1326.7 2653.4 1404.6 2106.9

    6RA7097-4KV62 40 2600 1992.7 2989.1 1906.3 2859.4 1887.2 3774.4 1876.9 2815.3

    830V, 4Q

    6RA7088-6LV62 40 950 700.8 1051.2 679.8 1019.7 607.8 1215.6 667.6 1001.4

    6RA7093-4LV62 40 1500 1171.6 1757.4 1140.1 1710.2 1036.6 2073.2 1116.2 1674.3

    6RA7095-4LV62 40 1900 1485.4 2228.1 1421.6 2132.4 1396.9 2793.8 1414.2 2121.3

    950V, 4Q

    6RA7096-4MV62 40 2200 1674.3 2511.4 1603.3 2404.9 1570.7 3141.4 1588.1 2382.1

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    29/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-7SIMOREG DC Master Operating Instructions

    3.4.2 Converters 3AC 400V, 30A to 125A, 1Q

    Order No. 6RA70 . . 6DS22

    18 25 28 31

    Rated supply voltage armature 1) V 3AC 400 (+15% / 20%)

    Rated input current armature 2) A 25 50 75 104

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage field 1) V 2AC 400 (+15% / 20%) 7)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 485

    Rated DC current A 30 60 90 125

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 14.5 29 44 61

    Power loss at rated DC current(approx.)

    W 163 240 347 400

    Rated DC voltage field 1) V max. 325

    Rated DC current field A 5 10

    Operational ambient temperature C 0 to 45 at Irated3)

    self-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 385x265x239 385x265x283

    Dimension diagram see Section 5.1.1 5.1.2

    Weight (approx.) kg 11 14 16 16

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    30/726

    Description 01.04

    3-8 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    3.4.3 Converters 3AC 400V, 210A to 600A, 1Q

    Order No. 6RA70 . . 6DS22

    75 78 81 85

    Rated supply voltage armature 1) V 3AC 400 (+15% / 20%)

    Rated input current armature 2) A 175 233 332 498

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V DC 24V internal 3AC 400 (15%) 50Hz3AC 460 (10%) 60Hz

    Fan rated current A 0.3 8)

    Air flow rate m3/h 100 570

    Fan noise level dBA 40 73

    Rated supply voltage field1)

    V 2AC 400 (+15% / 20%)7)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 485

    Rated DC current A 210 280 400 600

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 102 136 194 291

    Power loss at rated DC current(approx.)

    W 676 800 1328 1798

    Rated DC voltage field1)

    V max. 325

    Rated DC current field A 15 25

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 385x265x283 625x268x318

    Dimension diagram see Section 5.1.2 5.1.3 5.1.4

    Weight (approx.) kg 16 17 30

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    31/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-9SIMOREG DC Master Operating Instructions

    3.4.4 Converters 3AC 400V, 850A to 2000A, 1Q

    Order No. 6RA70 . . 6DS22 6RA70 . . 4DS22

    87 91 93 95

    Rated supply voltage armature 1) V 3AC 400 (+15% / 20%)

    Rated input current armature 2) A 705 995 1326 1658

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V 3AC 400 (15%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    50Hz 60Hz 50Hz 60Hz

    Fan rated current A 0.3 8) 1.0 9) 1.25 9) 1.0 9) 1.25 9)

    Air flow rate m3/h 570 1300 1300 2400 2400

    Fan noise level dBA 73 83 87 83 87

    Rated supply voltage field 1) V 2AC 400 (+15% / 20%) 7)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 485

    Rated DC current A 850 1200 1600 2000

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 412 582 776 970

    Power loss at rated DC current

    (approx.)

    W 2420 4525 5710 6810

    Rated DC voltage field 1) V max. 325

    Rated DC current field A 30 40

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation and digitalsetpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 700x268x362 780x410x362 880x450x500

    Dimension diagram see Section 5.1.5 5.1.6 5.1.7

    Weight (approx.) kg 40 80 125

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    32/726

    Description 01.04

    3-10 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    3.4.5 Converters 3AC 460V, 30A to 125A, 1Q

    Order No. 6RA70 . . 6FS22

    18 25 28 31

    Rated supply voltage armature 1) V 3AC 460 (+15% / 20%)

    Rated input current armature 2) A 25 50 75 104

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage field 1) V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 550

    Rated DC current A 30 60 90 125

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 16.5 33 49.5 68.7

    Power loss at rated DC current(approx.)

    W 172 248 363 417

    Rated DC voltage field 1) V max. 375

    Rated DC current field A 5 10

    Operational ambient temperature C 0 to 45 at Irated3)

    self-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 385x265x239 385x265x313

    Dimension diagram see Section 5.1.1 5.2.1

    Weight (approx.) kg 11 15 17 17

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    33/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-11SIMOREG DC Master Operating Instructions

    3.4.6 Converters 3AC 460V, 210A to 600A, 1Q

    Order No. 6RA70 . . 6FS22

    75 78 82 85

    Rated supply voltage armature 1) V 3AC 460 (+15% / 20%)

    Rated input current armature 2) A 175 233 374 498

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V DC 24V internal 1AC 230 (10%)

    50Hz 60Hz

    Fan rated current A 0.55 0.55

    Air flow rate m3/h 100 570 570

    Fan noise level dBA 40 73 76

    Rated supply voltage field 1) V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 550

    Rated DC current A 210 280 450 600

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 115 154 247 330

    Power loss at rated DC current(approx.)

    W 700 792 1519 1845

    Rated DC voltage field 1) V max. 375

    Rated DC current field A 15 25

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 385x265x313 625x268x318

    Dimension diagram see Section 5.2.2 5.2.3

    Weight (approx.) kg 17 18 32

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    34/726

    Description 01.04

    3-12 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    3.4.7 Converters 3AC 460V, 850A to 1200A, 1Q

    Order No. 6RA70 . . 6FS22

    87 91

    Rated supply voltage armature 1) V 3AC 460 (+15% / 20%)

    Rated input current armature 2) A 705 995

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V 1AC 230 (10%) 1AC 230 (10%)

    50Hz 60Hz 50Hz 60Hz

    Fan rated current A 0.55 0.55 2.6 3.3

    Air flow rate m3/h 570 570 1300 1300

    Fan noise level dBA 73 76 82 85

    Rated supply voltage field 1) V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 550

    Rated DC current A 850 1200

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 467 660

    Power loss at rated DC current(approx.)

    W 2514 4620

    Rated DC voltage field 1) V max. 375

    Rated DC current field A 30

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 700x268x362 780x410x362

    Dimension diagram see Section 5.2.4 5.1.6

    Weight (approx.) kg 42 80

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    35/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-13SIMOREG DC Master Operating Instructions

    3.4.8 Converters 3AC 575V, 60A to 600A, 1Q

    Order No. 6RA70 . . 6GS22

    25 31 75 81 85

    Rated supply voltage armature 1) V 3AC 575 (+10% / 20%)

    Rated input current armature 2) A 50 104 175 332 498

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V DC24Vinternal

    3AC 400 (15%) 50Hz3AC 460 (10%) 60Hz

    Fan rated current A 0.3 8)

    Air flow rate m3/h 100 570

    Fan noise level dBA 40 73

    Rated supply voltage field1)

    V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 690

    Rated DC current A 60 125 210 400 600

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 41 86 145 276 414

    Power loss at rated DC current(approx.)

    W 265 454 730 1550 1955

    Rated DC voltage field1)

    V max. 375

    Rated DC current field A 10 15 25

    Operational ambient temperature C 0 to 45 at Irated3)

    self-cooled

    0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 385x265x283 625x268x318

    Dimension diagram see Section 5.1.2 5.1.3 5.1.4

    Weight (approx.) kg 14 16 30

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    36/726

    Description 01.04

    3-14 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    3.4.9 Converters 3AC 575V, 800A to 2200A, 1Q

    Order No. 6RA70 . . 6GS22 6RA70 . . 4GS22

    87 90 93 95 96

    Rated supply voltage armature 1) V 3AC 575 (+10% / 20%)

    Rated input current armature 2) A 663 829 1326 1658 1824

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V 3AC 400 (15%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    50Hz 60Hz 50Hz 60Hz

    Fan rated current A 0.3 8) 1.0 9) 1.25 9) 1.0 9) 1.25 9)

    Air flow rate m3/h 570 1300 1300 2400 2400

    Fan noise level dBA 73 83 87 83 87

    Rated supply voltage field 1) V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 690

    Rated DC current A 800 1000 1600 2000 2200

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 552 690 1104 1380 1518

    Power loss at rated DC current

    (approx.)

    W 2638 4130 5942 7349 7400

    Rated DC voltage field 1) V max. 375

    Rated DC current field A 30 40 85

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation and digitalsetpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 700x268x362 780x410x362 880x450x500

    Dimension diagram see Section 5.1.5 5.1.6 5.1.7

    Weight (approx.) kg 40 80 125

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    37/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-15SIMOREG DC Master Operating Instructions

    3.4.10 Converters 3AC 690V, 720A to 2000A, 1Q

    Order No. 6RA70 . . 6KS22 6RA70 . . 4KS22

    86 88 93 95

    Rated supply voltage armature 1) V 3AC 690 (+10% / 20%)

    Rated input current armature 2) A 597 788 1244 1658

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V 3AC 400 (15%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    50Hz 60Hz 50Hz 60Hz

    Fan rated current A 0.3 8) 1.0 9) 1.25 9) 1.0 9) 1.25 9)

    Air flow rate m3/h 570 1300 1300 2400 2400

    Fan noise level dBA 73 83 87 83 87

    Rated supply voltage field 1) V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 830

    Rated DC current A 720 950 1500 2000

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 598 789 1245 1660

    Power loss at rated DC current

    (approx.)

    W 2720 4380 6706 8190

    Rated DC voltage field 1) V max. 375

    Rated DC current field A 30 40

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation and digitalsetpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 700x268x362 780x410x362 880x450x500

    Dimension diagram see Section 5.1.5 5.1.6 5.1.7

    Weight (approx.) kg 40 80 125

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    38/726

    Description 01.04

    3-16 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    3.4.11 Converters 3AC 830V, 900A to 1900A, 1Q

    Order No. 6RA70 . . 6LS22 6RA70 . . 4LS22

    88 93 95

    Rated supply voltage armature 1) V 3AC 830 (+10% / 20%)

    Rated input current armature 2) A 746 1244 1575

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V 3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    50Hz 60Hz 50Hz 60Hz

    Fan rated current A 1.0 9) 1.25 9) 1.0 9) 1.25 9)

    Air flow rate m3/h 1300 1300 2400 2400

    Fan noise level dBA 83 87 83 87

    Rated supply voltage field 1) V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 1000

    Rated DC current A 900 1500 1900

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 900 1500 1900

    Power loss at rated DC current

    (approx.)

    W 4638 6778 8700

    Rated DC voltage field 1) V max. 375

    Rated DC current field A 30 40

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 780x410x362 880x450x500

    Dimension diagram see Section 5.1.6 5.1.7

    Weight (approx.) kg 80 125

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    39/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-17SIMOREG DC Master Operating Instructions

    3.4.12 Converters 3AC 400V, 15A to 125A, 4Q

    Order No. 6RA70 . . 6DV62

    13 18 25 28 31

    Rated supply voltage armature 1) V 3AC 400 (+15% / 20%)

    Rated input current armature 2) A 13 25 50 75 104

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage field 1) V 2AC 400 (+15% / 20%) 7)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 420

    Rated DC current A 15 30 60 90 125

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 6.3 12.6 25 38 52.5

    Power loss at rated DC current(approx.)

    W 117 163 240 312 400

    Rated DC voltage field 1) V max. 325

    Rated DC current field A 3 5 10

    Operational ambient temperature C 0 to 45 at Irated3)

    self-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 385x265x239 385x265x283

    Dimension diagram see Section 5.1.9 5.1.10

    Weight (approx.) kg 11 11 14 14 16

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    40/726

    Description 01.04

    3-18 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    3.4.13 Converters 3AC 400V, 210A to 600A, 4Q

    Order No. 6RA70 . . 6DV62

    75 78 81 85

    Rated supply voltage armature 1) V 3AC 400 (+15% / 20%)

    Rated input current armature 2) A 175 233 332 498

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V DC 24V internal 3AC 400 (15%) 50Hz3AC 460 (10%) 60Hz

    Fan rated current A 0.3 8)

    Air flow rate m3/h 100 570

    Fan noise level dBA 40 73

    Rated supply voltage field1)

    V 2AC 400 (+15% / 20%)7)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 420

    Rated DC current A 210 280 400 600

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 88 118 168 252

    Power loss at rated DC current(approx.)

    W 676 800 1328 1800

    Rated DC voltage field1)

    V max. 325

    Rated DC current field A 15 25

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 385x265x283 625x268x318

    Dimension diagram see Section 5.1.10 5.1.11

    Weight (approx.) kg 16 17 30

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    41/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-19SIMOREG DC Master Operating Instructions

    3.4.14 Converters 3AC 400V, 850A to 2000A, 4Q

    Order No. 6RA70 . . 6DV62 6RA70 . . 4DV62

    87 91 93 95

    Rated supply voltage armature 1) V 3AC 400 (+15% / 20%)

    Rated input current armature 2) A 705 995 1326 1658

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V 3AC 400 (15%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    50Hz 60Hz 50Hz 60Hz

    Fan rated current A 0.3 8) 1.0 9) 1.25 9) 1.0 9) 1.25 9)

    Air flow rate m3/h 570 1300 1300 2400 2400

    Fan noise level dBA 73 83 87 83 87

    Rated supply voltage field 1) V 2AC 400 (+15% / 20%) 7)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 420

    Rated DC current A 850 1200 1600 2000

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 357 504 672 840

    Power loss at rated DC current

    (approx.)

    W 2420 4525 5708 6810

    Rated DC voltage field 1) V max. 325

    Rated DC current field A 30 40

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation and digitalsetpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 700x268x362 780x410x362 880x450x500

    Dimension diagram see Section 5.1.12 5.1.13 5.1.14

    Weight (approx.) kg 45 85 145

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    42/726

    Description 01.04

    3-20 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    3.4.15 Converters 3AC 460V, 30A to 125A, 4Q

    Order No. 6RA70 . . 6FV62

    18 25 28 31

    Rated supply voltage armature 1) V 3AC 460 (+15% / 20%)

    Rated input current armature 2) A 25 50 75 104

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage field 1) V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 480

    Rated DC current A 30 60 90 125

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 14.4 28.8 43 60

    Power loss at rated DC current(approx.)

    W 172 248 328 417

    Rated DC voltage field 1) V max. 375

    Rated DC current field A 5 10

    Operational ambient temperature C 0 to 45 at Irated3)

    self-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 385x265x239 385x265x313

    Dimension diagram see Section 5.1.9 5.2.5

    Weight (approx.) kg 11 15 15 17

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    43/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-21SIMOREG DC Master Operating Instructions

    3.4.16 Converters 3AC 460V, 210A to 600A, 4Q

    Order No. 6RA70 . . 6FV62

    75 78 82 85

    Rated supply voltage armature 1) V 3AC 460 (+15% / 20%)

    Rated input current armature 2) A 175 233 374 498

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V DC 24V internal 1AC 230 (10%)

    50Hz 60Hz

    Fan rated current A 0.55 0.55

    Air flow rate m3/h 100 570 570

    Fan noise level dBA 40 73 76

    Rated supply voltage field 1) V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 480

    Rated DC current A 210 280 450 600

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 100 134 216 288

    Power loss at rated DC current(approx.)

    W 700 792 1519 1845

    Rated DC voltage field 1) V max. 375

    Rated DC current field A 15 25

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 385x265x313 625x268x318

    Dimension diagram see Section 5.2.6 5.2.7

    Weight (approx.) kg 17 18 32

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    44/726

    Description 01.04

    3-22 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    3.4.17 Converters 3AC 460V, 850A to 1200A, 4Q

    Order No. 6RA70 . . 6FV62

    87 91

    Rated supply voltage armature 1) V 3AC 460 (+15% / 20%)

    Rated input current armature 2) A 705 995

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V 1AC 230 (10%) 1AC 230 (10%)

    50Hz 60Hz 50Hz 60Hz

    Fan rated current A 0.55 0.55 2.6 3.3

    Air flow rate m3/h 570 570 1300 1300

    Fan noise level dBA 73 76 82 85

    Rated supply voltage field 1) V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 480

    Rated DC current A 850 1200

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 408 576

    Power loss at rated DC current(approx.)

    W 2514 4620

    Rated DC voltage field 1) V max. 375

    Rated DC current field A 30

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 700x268x362 780x410x362

    Dimension diagram see Section 5.2.8 5.1.13

    Weight (approx.) kg 47 85

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    45/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-23SIMOREG DC Master Operating Instructions

    3.4.18 Converters 3AC 575V, 60A to 600A, 4Q

    Order No. 6RA70 . . 6GV62

    25 31 75 81 85

    Rated supply voltage armature 1) V 3AC 575 (+10% / 20%)

    Rated input current armature 2) A 50 104 175 332 498

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V DC24Vinternal

    3AC 400 (15%) 50Hz3AC 460 (10%) 60Hz

    Fan rated current A 0.3 8)

    Air flow rate m3/h 100 570

    Fan noise level dBA 40 73

    Rated supply voltage field1)

    V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 600

    Rated DC current A 60 125 210 400 600

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 36 75 126 240 360

    Power loss at rated DC current(approx.)

    W 265 455 730 1550 1955

    Rated DC voltage field1)

    V max. 375

    Rated DC current field A 10 15 25

    Operational ambient temperature C 0 to 45 at Irated3)

    self-cooled

    0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation anddigital setpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 385x265x283 625x268x318

    Dimension diagram see Section 5.1.10 5.1.11

    Weight (approx.) kg 14 16 30

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    46/726

    Description 01.04

    3-24 Siemens AG 6RX1700-0AD76SIMOREG DC Master Operating Instructions

    3.4.19 Converters 3AC 575V, 850A to 2200A, 4Q

    Order No. 6RA70 . . 6GV62 6RA70 . . 4GV62

    87 90 93 95 96

    Rated supply voltage armature 1) V 3AC 575 (+10% / 20%)

    Rated input current armature 2) A 705 912 1326 1658 1824

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V 3AC 400 (15%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    50Hz 60Hz 50Hz 60Hz

    Fan rated current A 0.3 8) 1.0 9) 1.25 9) 1.0 9) 1.25 9)

    Air flow rate m3/h 570 1300 1300 2400 2400

    Fan noise level dBA 73 83 87 83 87

    Rated supply voltage field 1) V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 600

    Rated DC current A 850 1100 1600 2000 2200

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 510 660 960 1200 1320

    Power loss at rated DC current

    (approx.)

    W 2780 4515 5942 7349 7400

    Rated DC voltage field 1) V max. 375

    Rated DC current field A 30 40 85

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation and digitalsetpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 700x268x362 780x410x362 880x450x500

    Dimension diagram see Section 5.1.12 5.1.13 5.1.14

    Weight (approx.) kg 45 85 145

    Explanation at end of list of tables

  • 7/21/2019 6RA70 Operating Instruction_Total-Rev10

    47/726

    01.04 Description

    Siemens AG 6RX1700-0AD76 3-25SIMOREG DC Master Operating Instructions

    3.4.20 Converters 3AC 690V, 760A to 2000A, 4Q

    Order No. 6RA70 . . 6KV62 6RA70 . . 4KV62

    86 90 93 95

    Rated supply voltage armature 1) V 3AC 690 (+10% / 20%)

    Rated input current armature 2) A 630 829 1244 1658

    Rated supply voltage electronicspower supply

    V 2AC 380 ( 25%) to 460 (+15%); In=1A or1AC 190 ( 25%) to 230 (+15%); In=2A

    ( 35% for 1min)

    Rated supply voltage fan V 3AC 400 (15%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    3AC 400 (10%) 50Hz3AC 460 (10%) 60Hz

    50Hz 60Hz 50Hz 60Hz

    Fan rated current A 0.3 8) 1.0 9) 1.25 9) 1.0 9) 1.25 9)

    Air flow rate m3/h 570 1300 1300 2400 2400

    Fan noise level dBA 73 83 87 83 87

    Rated supply voltage field 1) V 2AC 460 (+15% / 20%)

    Rated frequency Hz 45 to 65 10)

    Rated DC voltage 1) V 725

    Rated DC current A 760 1000 1500 2000

    Overload capability 6) max. 180% of rated DC current

    Rated output kW 551 725 1088 1450

    Power loss at rated DC current

    (approx.)

    W 2850 4605 6706 8190

    Rated DC voltage field 1) V max. 375

    Rated DC current field A 30 40

    Operational ambient temperature C 0 to 40 at Irated3)

    forced-cooled

    Storage and transporttemperature

    C 25 to +70

    Installation altitude above sea level 1000 m at rated DC current 4)

    Control stability n = 0.006% of the rated motor speed, valid for pulse encoder operation and digitalsetpoint

    n = 0.1% of the rated motor speed, valid for analog tacho or analogsetpoint 5)

    Environmental classDIN IEC 60 721-3-3

    3K3

    Degree of protection DIN EN 60529 IP00

    Dimensions (HxWxD) mm 700x268x362 780x410x362 880x450x500

    Di