Upload
vuhanh
View
246
Download
2
Embed Size (px)
Citation preview
730N Series
Torque Wrench
Procedures Manual
730N Series
Operational
Principles and
Guidelines
Beam at rest on Cam.
Ramp. The ramp is what is adjusted to
calibrate the wrench. No disassembly required to cal a
wrench.
“Tip Block” as the cam
moves up the ramp the block angle is increased making it more difficult for the small
triangle to “click” past.Interface. Where the
“click” occurs.
Lever. This is how the insert heads connect to the
torque mechanism. In this mode the lever contacts the mechanism to pull torque. If the wrench is used as a “Breaker bar” the Lever falls off the mechanism and against the torque wrench housing. Voila! No damage!
Evolution of a proven design.
The 730N series evolves from the proven 730 series wrenches. 730 wrenches built their reputation for accuracy and durability in the harshest industrial conditions on oil platforms, remote wind turbine facilities, MRO operations, OEM’s and deployed military units.
Accurate Setting with “Quick Select.”
New to the 730N “Quick Select” allows for very accurate setting of torque values. This is done quickly and easily with or without gloves in virtually any lighting conditions. Even adjust one handed!
Easy to Read Scale.
The easy to read dual scale (in.lb & ft.lb or Nm & ft.lb) allows technicians unprecedented accuracy. Set accurately to 2 in.lb. increments. Simply pull out the dial and rotate to the desired value then press dial in to lock.
Durable & Cost E!ective.
The 730N does not use a spring
in the mechanism. (see diagram ).
Proven advantages:
• No need to Zero the wrench after use. (Nothing under compression.)
• Full use of scale is possible. No loss of top or bottom %.
• Limited Lifetime warranty on non-synthetic components.
• North American 3 year
accuracy warranty.
• Same accuracy clockwise and counterclockwise. +/-3%.
• Sealed against dust & dirt.
• Interchangeable insert
heads. Maximum flexibility out of one torque wrench. Simply insert the head necessary for the task. Fewer wrenches are needed.
• No need to disassemble to adjust or calibrate. 2mm hex key is all that is needed.
• Traceable to national standards. DIN, NIST, ISO
Superior Longevity and Cost E!ective Design.
Stahlwille 730N series torque tools
set the standard for accuracy and
long life.
Because of the unique proven design,
key components manufactured in
house and uncompromising quality it
is not uncommon for Stahlwille
mechanical torque wrenches to see
over 400,000 activations before
replacement.
That is a 20 year service life at
maximum activations (5,000) each
year. DIN EN ISO6789 compliant.
730Na Model in.lb. range ft.lb. range
730 Na/2 20 - 180 1.5 - 15
730 Na/5 90 - 450 7 - 37
730 Na/10 180 - 900 15 - 75
730 Na/20 350 - 1800 30 - 150
730 Na/40 800 - 3600 60 - 300
730N Model Nm range ft.lb. range
730 N/2 2 - 20 Nm 20 - 180 in.lb.
730 N/5 10 - 50 Nm 7 - 37
730 N/10 20 - 100 Nm 15 - 75
730 N/12 25 - 130 Nm 20 - 95
730 N/20 40-200 Nm 30 - 150
730 N/40 80 - 400 Nm 60 - 300
730 N/65 130 - 650 Nm 100 - 480All 730N series torque wrenches
SHARE THE SAME COMPONENTS. Scale ranges vary.
Serial NumberSince 1992 every Stahlwille Torque Wrench has left the factory with a unique 9 digit
serial number. The serial number is not random but indicates where and when the
wrench was manufactured and tested.
The following example illustrates how to interpret a Stahlwille generated serial
number. We’ll use the wrench number above to illustrate.
Example: 607015002
607015002 The first digit refers to the factory calibration station.
607015002 The second and third digit position reveal the year of
! ! ! manufacture. (2007)
607015002 The 4th thru 6th digit position reveal the date of
! ! ! manufacture. (15th day of 2007 or January 15, 2007)
607015002 The 7th thru 9th digits reveal the daily production
! ! ! number of the wrench. (2nd wrench produced 01.15. 2007)
Switching Group/Machined Beam & ISO info.
Switching Group
Stahlwille Tools North America provides a 3 year accuracy warranty on the switching group. In addition there are special warranty considerations for military customers and OEM’s who meet certain requirements. Please talk to your representative or call Stahlwille Tools North America for more information.
The accuracy warranty states that Stahlwille Tools North America guarantees that at each calibration period, not to exceed 1 year and at the customers expense, the 730N series wrenches will calibrate back to the factory
specification of +/-3%. If the wrench cannot be adjusted to +/-3% Stahlwille Tools North America will replace the switching group with a new version which will then carry 3 years of warranty forward.
Machined Beam
Stahlwille introduced a new machined beam in 2007 designed to offer even greater accuracy and repeatability. These beams are identified by a black coating. The new beam reduces friction, enhances corrosion resistance and provides calibration accuracy of +/-1% achievable by the customer Metrology lab or calibration provider.
ISO 6789
All procedures outlined in this manual are based upon but do not override the procedures and specifications found in the current ISO 6789 and related international and national guidelines. (DKD or NIST)
As the ISO 6789 is a copyrighted publication it cannot be copied or distributed without permission. It can be purchased in electronic format at:
http://www.2din.de/index.php?lang=eng and enter ISO 6789 in the search window.
Switching or “Vector” Group
Machined Beam. The “Spring”
730N Series
Calibration
ATTENTIONStahlwille makes a very popular Quick Release ratcheting insert.
If your customer ordered these inserts please note: These inserts will not calibrate correctly (Exception is the 1/4” QR) as a
factor must be applied to compensate for the added length of the insert. All Stahlwille Torque Wrenches are calibrated at the factory to the
standard insert center point.
730N Series Torque Wrench Factory Calibrated
Center Point
Insert Size
730N/2, 730N/5, 730N/10, 730Na/2, 730Na/5, 730Na/10
17.5mm 9 x 12
730N/12, 730N/20, 730N/40, 730N/65, 730Na/20, 730Na/40
25mm 14 x 18
Complete details on all inserts and center point data is available in the
Stahlwille Programme catalog or Aerospace catalog in Section 5..
Center Point Information
Regarding Inserts & Calibration
25mm17.5mm
Note! This is how to achieve the correct tightening torque -even if you are using inserts with an extension
When you tighten fasteners using inserts whose extension length S deviates from the standard length SF' it is necessary to recalculate the setting/display value for the torque wrench in use. Caution! If adapters are combined with inserts or special tools, use the sum of the extensions =J;S. Where the special tool is angled to the side, WK will have to be determined empirically.
Normal situation
WK = MAxLF
Lk
[NmxmmJ
mm
Torque wrench No 730N/1O combined with
square drive insert tool No 734/5 and socket size 13 mm. Required tightening torque for the screw MA = 40 N m
MAxLF Dimension table for torque wrenches: LF = 336 mm, SF = 175 mm Dimension table for square drive insert tools: S = 175 mm
WK = LF-SF+S (or LSj
MA = desired tightening torque S extension of STAHLWILLE ,dh inserts or special tools W = reading/setting W= MA (see dimension table
WK = adjusted reading for inserts) SF
or setting value WK" MA SF = standard extension (see dimension table for LF = functional length torque wrenches) (see dimension table No adjustment to sening value required on torque wrench.
for torque wrenches) IS = total of all extensions of the attached inserts
= adjusted functional length Sadapl", + Sinsen + .,
LK = LF - SF +S(or 1:S) Example 2: adjusted reading (Insert tool and adapter)
Torque wrench No 71/2 combined with
square drive insert tool No 734/5 and adapter No 447 size 10 mm Required tightening torque for the screw MA = 25 N mExample 1: adjusted setting value (1 insert tool)
Torque wrench No 730N/20 combined with Dimension table for torque wrenches: LF = 250 mm, SF = 175 mm
ring insert tool No 732/40 size 36 mm Dimension table for square drive insert tools: S = 175 mm
Required tightening torque for the screw MA = 190 N m Dimension table for adapters: S = 50.8 mm
Dimension table for torque wrenches: LF = 424.5 mm, SF = 25 mm Dimension table for ring insert tools: S=28mm LF
LF
M. S
MAX LF 190 N m x 424.5 mm 190 N m x 424.5 mm MAxLF 25Nmx250mm 25Nmx250mm WK = = ------- wK = = ---------
LF -5F +5 424.5mm-25mm +28 mm 427.5mm LF -5F +1:5 250mm-17.5mm+17.5mm+50.8mm 300.8mm
Adjusted sening value WK = 188.7 N m value to set = 189 N m Adjusted reading WK = 20.8 Nm
... and this is what it looks like in the catalogue.
h L LF s" Fine scale $/ b
mm mmmmmmmmmm•. n "Wl 23 275 228
9x 12 28 225 "1ninJb 02Nm 23 280.5 25 ,339x 12 28025Nm 336I Tun 386 5822.
4013 40 \3 :1.3 " 25.
nt:;;Nm 9x 12 28 23 \35421 379 5822. 14 24 " 14 x 18 28 23
O.5Nm 4014 \342.5 tUb 4245 5822. 25,5 \2 25
46714x 18 28 23 4015 25 ,38
StUb t Nm 23 flJ7 5822. ,214x 18 28 4016 \AA
IUll_IO 2Nm 30.6 25.6 890 5822. 17 '3 25
__ 'L 'll:;. ..... m 14 x '8 4017 5 25 ,.5
275 2 inJb \539x 12 28 23 5822. 4016 30 '3 25
O.5tt.lb 3,30 17.5 5822. 33'59x 12 28 23 4019 25 ,62
1 tt.lb 2.5 in.lb 28 23· 386,..336 17.5 5822. ' 21 34 5 ,5 25
&""JllJb 5in.lb 9x 12 23 <167 424.5 25 5822.40222. 22. 37' 5 ,5 25
\75 ...... ,... tn inlb 14x 18 28
pi:J7 564.5 25 40 \B214 x 18 28 2523 5822. 4i,5 ,7
4024 ,B'5822. 26 45.5 ,9 4027 25 2\0
!lOSll040
/// 28: 203
5822. 47.5 '9 2B·Required tightefling lORlue fat" the screw MA '1190 N m 5822.4030 3A 52 '-' 240
40325822. 403A 3& 54 19
Required setting value WK se22. 3&'" - 20 40 nell
5822.404 ' AI 60 • 1110,11",,0 'ol\il1QS "" ""e
(1,,\"1 \0 nole oooage ,92\ ------ ,9 30"
ExtJmp.le 1 (see
W _ 18
B:1Nm Torque wrench 730N/20, combined wilh insert tool 732/40, size 36 mm. IC ReqUired lightening torque for the screw M. = 190 N m
Adjusted sef1ing value on lORlue wrench No 730N/20: 189 N m Dimension table for torque wrenches: LF = 424.5mm; SF = 25mm
Dimension table for ;nser1 toofs: S = 28 mm196
OJ II
121 ,23 ,ZB
5
25 25
h'i c9
\1
MAX LF
WK = LF-SF + S
Torque Wrench Calibration & Procedures
Stahlwille Manoskop 730N & Na series.
All calibration procedures whether detailed in this document or elsewhere are to be
performed in accordance with the current DIN ISO 6789 standard.
A calibration device with a certified accuracy of +/-1% of all values to be measured is
required to complete adjustment / calibration or re-calibration tasks.
When the wrench is being loaded for test the following procedures are to be followed:
! Load must be applied to the middle of the handle at the point of the mark on
the handle. (Whether in a fixture or by hand). The embossed arrow and or other
markings are not intended for use as reference points.
! Apply load evenly and ensure that the load from approx. 80% of the target
torque value is applied uniformly and results in a trigger within a timeframe
from .5 to 4 seconds.
Step 1: Load and work in
! Load the wrench until it triggers at 100% value (the highest setting on
scale), release load and back off the wrench several degrees to allow a
reset.
! Repeat this a total of 5 times. This will “work in” the switching elements
in preparation for calibration.
Step 2: Check 20%
! Set the wrench to 20% of the scales value (ie. If maximum value of the
scale is 100Nm then 20% would be 20 Nm) .
! Check and record the value at which the wrench triggered. Please ensure
that the value recorded is the “first peak” which is not necessarily the
highest value obtained.
Step 3: Check 100%
! Set the wrench to 100% of the scales value (ie. If maximum value of the
scale is 100Nm then 100% would be 100 Nm) .
! Check and record the value at which the wrench triggered. Please ensure
that the value recorded is the “first peak” which is not necessarily the
highest value obtained.
Step 4: Check accuracy to determine whether to calibrate or adjust
! If the accuracy of the wrench at 20% and 100% is not within the required
tolerance (from +4.14 to -3.85%) adjustment may be required. Proceed
to steps 9 through 11 for adjustment instructions.
Step 5: Calibrate 20%
! Set the wrench to 20% of the scales value (ie. If maximum value of the
scale is 100Nm then 20% would be 20 Nm) .
! Check and record the value at which the wrench triggered. Please ensure
that the value recorded is the “first peak” which is not necessarily the
highest value obtained.
! Repeat a total of 5 times, recording each value.
Step 6: Calibrate 60%
! Set the wrench to 60% of the scales value (ie. If maximum value of the
scale is 100Nm then 20% would be 20 Nm) .
! Check and record the value at which the wrench triggered. Please ensure
that the value recorded is the “first peak” which is not necessarily the
highest value obtained.
! Repeat a total of 5 times, recording each value.
Step 7: Calibrate 100%
! Set the wrench to 100% of the scales value (ie. If maximum value of the
scale is 100Nm then 100% would be 100 Nm) .
! Check and record the value at which the wrench triggered. Please ensure
that the value recorded is the “first peak” which is not necessarily the
highest value obtained.
! Repeat a total of 5 times, recording each value.
Step 8: Check Accuracy
! Check the values obtained in steps 5 to 7 for acceptable accuracy.
! If the values are within the required tolerances the appropriate
documentation should be produced.
! If the values are not inside of an acceptable tolerance proceed to steps 9
through 11 for adjustment procedures.
Step 9: Adjustment 20%
! Adjust the lower range FIRST
! Adjusting the lowest adjustment screw (closest hole to end of handle)
using a 2mm hex key. Clockwise adjustment will increase the trigger
setting, counter clockwise adjustment will lower the trigger setting.
Step 10: Adjust 100%
! Check and if required adjust the 100% setting.
! Adjust the upper range by adjusting the upper adjustment screw (the
second adjustment screw further up the wrench) using a 2mm hex key.
Clockwise adjustment will increase the trigger setting, counter
clockwise adjustment will lower the trigger setting.
! No adjustments are necessary for the 60% range. Should accuracy
deviations be present in this range they must be compensated for
altering the lower and upper ranges to bring the complete range inside of
the allowable accuracy tolerances.
Adjustment Ports. Remove White plugs to gain access. Use 2mm hex key.
Step 11: Verify for correct adjustment
! Check 20%,60%,100% for accuracy conformance by loading several
times at each value prior to calibration. This step reduces the likelihood of
having to interrupt a calibration for readjustment of the wrench.
! Please bear in mind that adjustments to either lower or upper setting will
have an effect all settings, therefore for any single adjustment 20%,60%
and 100% should be checked before starting to perform a calibration
check.
! Once verified proceed to Steps 5 through 8 for calibration instructions.
NOTE:
If after repeated attempts to adjust the wrench fail to bring the unit to an acceptable
level of accuracy factory service may be required. Please return the units in question
to Stahlwille factory authorised service centre for repair.
730N Series
Disassembly &
Reassembly
730N & Na Disassembly / Reassembly
Note:
The following is a summation of factory approved service procedures. These
procedures are issued as guidance and may be revoked or altered at any time without
prior consent. All applicable local or corporate heath and safety guidelines must be
observed and and not contained in this document.
Please note after any entry has been made to the wrench a Calibration in accordance
with ISO 6789 is mandatory.
Required Tools Possible Parts Required Consumable Materials
#7 Torx bit
#9 Torx bit
4mm drift or punch
Hammer
Bit Driver
Pocket knife
Engineer pick
1- Main scale window - 925055552
1- Micro scale window - 925055553
1- Handle part 1 - 925055543
1- Handle part 2 - 925055544
2 - Sealing Plugs - 925051549
For other parts or components please
see the attached parts lists in the
appendix.
Grease MOS2 (Molydag 49) or
equivalent.
Grease Microlube GL261 or
equivalent anti-corrosion fretting
grease.
Locktite 496
Ethyl Alcohol (for spot cleaning)
Clean lint free rags
Step 1:
Remove Torx
Screws in handle
using #7 Torx bit.
The two component
handle is Skydrol,
MEK and fuels
resistant. New
handle components
are available if
necessary. pg. 16
Step 2:
Remove the plugs
from the
adjustment holes
and discard.
Replacement plugs
are available, pg 16.
Step 3:
Remove the mylar
label. Order a new
one!
Step 4:
Using a pocket knife
split apart the two
component handles.
Step 5:
Remove the handles
and two component
material.
Alert:
Watch for the clear
plastic windows
falling out of the
handle.
Step 6:
Alert: IMPORTANT
Set the micro
adjustment to ZERO.
Alert:
Watch for any small
bb’s that might
escape when pulling
out on the
adjustment dial.
Step 7:
Remove the Lock
Screw with a #9
Torx bit.
Step 8:
Alert: IMPORTANT
Place a hand under
the fine adjustment
dial. Pull out
SLOWLY and catch
any bb’s or small
springs.
These provide
resistance and the
“click” during
movement.
Step 9:
Using a 4mm drift or
a press drive out
the Locking Pin.
Step 10:
Slowly remove the
entire mechanism
by pulling on the
end where the micro
dial was sitting.
(Black plastic cap).
Step 11:
As the mechanism is
being removed roll it
over so you can see
the switching group,
ramp and beam.
This will prevent the
“Click” spring from
falling on the floor.
Step 12:
Alert: IMPORTANT
DO NOT MESS with
the FINE
ADJUSTMENT DRIVE
This is key to the
calibration of the
wrench. If there are
any questions
contact Stahlwille
North America.
Step 13:
If the torque wrench
is not giving an
audible “click” when
reaching the desired
torque value the
“Click” Spring may
need to be replaced.
Simply lift off of the
Switching Group and
set in a new spring.
Step 14:
The Click Spring just
sits on the
Switching Group. It
is held in place by
the pressure of the
housing against the
spring.
Step 15:
Lubricate the
internal mechanism
of the wrench
before re-assembly.
MOS2 = Switching Group
contact points edges.
Microlube or other anti-
corrosive grease can be
applied on cam, beam &
surfaces. Wet or humid
environment coat all
internal surfaces.
Step 16:
Alert: IMPORTANT
Replace BB’s then
Small Springs and
then place a BB on
top of each spring.
Step 17:
Alert: IMPORTANT
Be sure to align
ZERO to the top of
the wrench as the
micro dial is re-
inserted.
It is highly
recommended you
do this with the
wrench as shown.
Straight up & down.
Step 18:
Alert: IMPORTANT
Press the Micro dial
down so it is
seated. MAINTAIN
PRESSURE on the
Micro dial to keep
the BB’s in place
when re-inserting
the mechanism into
the wrench housing.
Step 19:
Insert the “guts”
back into the torque
wrench tube. Lever
the insert to make
sure the “Click”
spring is seated
properly.
Alert: Remember to
keep pressure on
the Micro Dial!
Step 20:
Alert: IMPORTANT
Maintain constant
pressure on Micro
Dial and seat the
mechanism back in
the wrench.
IMPORTANT
TAPE over the micro
dial to the housing
to keep the Micro
Dial seated.
Step 21:
Drop the wrench
into a hand to help
slide the mechanism
to the proper
position.
Step 22:
A scribe can be
used to align the
locking pin hole to
the housing.
Step 23:
Insert the locking
pin and hammer into
place.
Alert: IMPORTANT
PEEN the Locking
Pin by placing the
housing on an Anvil
or vice and give it a
good WHACK!
Step 24:
Reinstall the Lock
Screw with #9 Torx
bit. Remove any
tape from the Micro
Dial being careful to
keep it seated!
Alert: IMPORTANT
Be sure ZERO is
facing the front of
the wrench!
Step 25:
Re-attach the two
component handle
making sure the
plastic windows are
in place.
Step 26:
Using the #7 Torx
bit screw together
the handle
components.
A small bit of RTV
may be placed in
the screw holes to
assure FOD security.
Step 27:
Alert: IMPORTANT
Make sure the Micro
Dial rotates freely
and clicks into
place. Note that the
scales are aligned at
top and bottom of
the range.
Zero on the micro
dial should match
the whole number
selected.
Step 28:
Make certain the
Micro Dial locks
properly when
pressed in.
Voila! Nice Job.
Any problems
simply repeat the
procedure or call
Stahlwille N.A.
•Install new sealing plugs on the adjustment holes or use a
similar anti-tamper material. (Mylar tape, putty, etc.)
•Calibration is required prior to returning the wrench to service.
Parts lists and exploded assembly diagrams in Index.
Questions or for more information:
Stahlwille North America - 719-473-3328 or [email protected]
730N Series
INDEXDiagrams & Parts Lists
730N/2 (Na/2)
730N
/2
(Na
/2
)
730N/5 (Na/5)
730N
/5
(Na
/5
)
730N/10 (Na/10) 730N
/10
(Na
/10
)
730N/12 730N
/12
730N/20 (Na/20) 730N
/20
(Na
/20
)
730N/40 (Na/40) 730N
/40
(Na
/40
)
730N/65 730N
/65