80
5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALLATION MANUAL ZL SERIES 7.5- 12.5 Ton 60 Hertz R-410A

7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

5830280-UIM-A-0220

Revision: A-0220

2020-02-01

Johnson Controls Ducted Systems

INSTALLATION MANUAL ZL SERIES7.5- 12.5 Ton 60 Hertz R-410A

Page 2: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL
Page 3: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

ContentsContentsGeneral........................................................................... 3

Safety Considerations............................................. 3

Inspection................................................................ 4

Reference................................................................. 4

Renewal Parts.......................................................... 4

Approvals................................................................. 4

Nomenclature................................................................ 6

Installation..................................................................... 7

Installation Safety Information............................. 7

Preceding Installation............................................. 7

Limitations.................................................................... 9

Location.................................................................. 10

Clearances.................................................................. 10

Rigging And Handling.......................................... 10

ZL08-14 Unit Weights............................................ 12

Ductwork................................................................ 15

Duct Covers................................................................ 15

Condensate Drain................................................. 17

Compressors.......................................................... 17

Filters...................................................................... 17

Power And Control Wiring................................... 17

Thermostat Wiring.................................................... 18

Typical Field Power and Control Wiring................... 19

Typical Power Wiring............................................ 19

Electrical Data ZL08-14 Static IndoorBlowers - Without Powered ConvenienceOutlet........................................................................... 21Electrical Data ZLE 08-14 Standard IndoorBlower - With Powered Convenience Outlet........... 23Electrical Data ZLE08-14 Medium IndoorBlower - Without Powered ConvenienceOutlet........................................................................... 25Electrical Data ZLE08-14 Medium IndoorBlower - With Powered Convenience Outlet........... 27Electrical Data ZLE08-14 High Indoor Blower- Without Powered Convenience Outlet.................. 29Electrical Data ZLE08-14 High Indoor Blower- With Powered Convenience Outlet........................ 31Physical Data.............................................................. 33Optional Gas Heat..................................................... 41Gas Piping.................................................................. 41Gas Connection......................................................... 41

Combustion Air and Flue Exhaust........................... 42

Options/Accessories............................................. 43

Economizer................................................................. 43Power Exhaust........................................................... 43Rain Hood................................................................... 43

Blower Phasing...................................................... 43

Blower Rotation......................................................... 43Belt Tension................................................................ 44Altitude and Temperature Correction forCFM, Static Pressure and Power............................... 44

Airflow Performance............................................. 47

ZL 08-14 Side Duct Application (Belt Drive)............ 49ZL 08-14 Bottom Duct Application (BeltDrive)............................................................................ 51Supply Air Drive Adjustment.................................... 53

Operation..................................................................... 58

Cooling Operation................................................. 58

Free cooling operation with economizer........... 59

Economizer with single enthalpy sensor........... 59

Economizer with dual enthalpy sensors............ 59

Economizer with power exhaust......................... 59

Motorized outdoor air dampers.......................... 59

High-pressure limit switch................................... 60

Low-pressure limit switch.................................... 60

Evaporator low limit.............................................. 60

Low ambient cooling............................................ 60

Safety controls....................................................... 60

Compressor protection........................................ 61

Gas Heating Operation......................................... 61

Gas Heat Ignition Control Board Function............... 61

Ignition Control Board on Standby..................... 61

Call for heat........................................................... 61

Pressure switch proving....................................... 61

Pre-purge............................................................... 62

Ignition trial period............................................... 62

Flame stabilization period.................................... 62

Main Burner operation......................................... 62

Post Purge.............................................................. 62

Lockout................................................................... 62

High temperature limit switch............................ 63

Johnson Controls Ducted Systems

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A i

Page 4: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Roll-out switch................................................................ 63

Power interruptions....................................................... 63

Flame present with Gas off........................................... 63

Welded gas valve relay response................................. 63

Cooling start-up................................................................... 63

Prestart Check List......................................................... 63

Cooling operating instructions..................................... 63

Post Start Check List...................................................... 64

Gas heat start-up................................................................. 64

Pre-Start Check List........................................................ 64

Gas heat operating instructions.................................. 64

Lighting The Main Burners........................................... 64

Post Start Checklist........................................................ 64

Shut Down...................................................................... 64

Checking Gas Heat Input.................................................... 64

Two Stage Gas Heat....................................................... 64

Manifold Gas Pressure Adjustment............................. 66

Two Stage........................................................................ 66

Adjustment Of Temperature Rise................................ 66

Burners/Orifices Inspection/Servicing........................ 66

Troubleshooting................................................................... 67

Flash Codes for the Gas Heat Ignition ControlBoard................................................................................ 68

ZL08-14 Charging Tables............................................... 70

Smart Equipment™ Control Board NavigationComponents.......................................................................... 72

Start-Up Sheet...................................................................... 73

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410Aii

Johnson Controls Ducted Systems

Page 5: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

GeneralZL units are single package air conditionerswith optional gas heating designed for outdoorinstallation on a rooftop or slab and for non-residential use.These units are completely assembled on rigid,permanently attached base rails. All piping,refrigerant charge, and electrical wiring isfactory installed and tested. The units requireelectric power, gas supply (where applicable),and duct connections.

Safety Considerations

This is a safety alert symbol. When you seethis symbol on labels or in manuals, be alert tothe potential for personal injury.Understand and pay particular attention thesignal words DANGER, WARNING or CAUTION.DANGER indicates an imminently hazardoussituation, which, if not avoided, will result indeath or serious injury.WARNING indicates a potentially hazardoussituation, which, if not avoided, could result indeath or serious injury.CAUTION indicates a potentially hazardoussituation, which, if not avoided may resultin minor or moderate injury. It is also usedto alert against unsafe practices and hazardsinvolving only property damage.

 WARNING

Improper installation may create a conditionwhere the operation of the product could causepersonal injury or property damage. Improperinstallation, adjustment, alteration, service ormaintenance can cause injury or property dam-age. Refer to this manual for assistance or foradditional information, consult a qualified con-tractor, installer or service agency.

 CAUTION

This product must be installed in strict compli-ance with the installation instructions and anyapplicable local, state and national codes includ-ing, but not limited to building, electrical, and me-chanical codes.

 WARNING

Before performing service or maintenance oper-ations on unit, turn off main power switch to unit.Electrical shock could cause personal injury. Im-proper installation, adjustment, alteration, ser-vice or maintenance can cause injury or proper-ty damage. Refer to this manual. For assistanceor additional information consult a qualified in-staller, service agency or the gas supplier.

 CAUTION

This system uses R-410A Refrigerant whichoperates at higher pressures than R-22. Noother refrigerant may be used in this system.Gauge sets, hoses, refrigerant containersand recovery systems must be designed tohandle R-410A. If you are unsure, consult theequipment manufacturer. Failure to use R-410Acompatible servicing equipment may result inproperty damage or injury.

 WARNING

FIRE OR EXPLOSION HAZARDIf the information in this manual is not followedexactly, a fire or explosion may result causingproperty damage, personal injury or loss of life.Do not store or use gasoline or other flammablevapors and liquids in the vicinity of this or anyother appliance.WHAT TO DO IF YOU SMELL GAS:• Do not try to light any appliance.• Do not touch any electrical switch• Do not use any phone in your building.• Immediately call your gas supplier from aneighbor’s phone. Follow the gas supplier’s in-structions.• If you cannot reach your gas supplier, call thefire department.Installation and service must be performed by aqualified installer, service agency or the gas sup-plier.

3INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A

Johnson Controls Ducted Systems

Page 6: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

 WARNING

ELECTRICAL SHOCK, FIRE OR EXPLOSIONHAZARD

Failure to follow safety warnings exactly could result indangerous operation, serious injury, death or propertydamage.Improper servicing could result in dangerousoperation, serious injury, death or property damage.• Before servicing, disconnect all electrical power tofurnace.• When servicing controls, label all wires prior to dis-connecting. Reconnect wires correctly.• Verify proper operation after servicing.

Due to system pressure, moving parts, and electricalcomponents, installation and servicing of airconditioning equipment can be hazardous. Onlyqualified, trained service personnel should install,repair, or service this equipment. Untrainedpersonnel can perform basic maintenance functionsof cleaning coils and filters and replacing filters.Observe all precautions in the literature, labels,and tags accompanying the equipment wheneverworking on air conditioning equipment. Theinstallation must conform with local building codesor, in the absence of local codes, with the NationalFuel Gas Code, ANSI Z223.1/NFPA 54, and/or theNational Gas and Propane Installation Code, CSAB149.1.Wear safety glasses and work gloves. Usequenching cloth and have a fire extinguisheravailable during brazing operations.

InspectionAs soon as a unit is received, it should be inspectedfor possible damage during transit. If damage isevident, the extent of the damage should be notedon the carrier’s freight bill. A separate request forinspection by the carrier’s agent should be made inwriting.

 CAUTION

This product must be installed in strict compliancewith the enclosed installation instructions and anyapplicable local, state and national codes including,but not limited to, building, electrical, and mechani-cal codes.The furnace and its individual shut-off valvemust be disconnected from the gas supply piping sys-tem during any pressure testing at pressures in ex-cess of 1/2 PSIG.Pressures greater than 1/2 PSIGwill cause gas valve damage resulting in a hazardouscondition. If it is subjected to a pressure greater than1/2 PSIG, the gas valve must be replaced.The furnacemust be isolated from the gas supply piping systemby closing its individual manual shut-off valve duringany pressure testing of the gas supply piping systemat test pressures equal to or less than 1/2 PSIG

ReferenceAdditional information is available in the followingreference forms:

• Technical Guide - ZX/ZQ/ZY/ZL 04-14 1068152

• General Installation - ZL08-14 5830280

• Economizer Accessory -• Vertical Flow Dry Bulb Economizer Field

Installed

Horizontal Flow Dry Bulb Economizer FieldInstalled

• Power Exhaust -• Vertical Flow Dry Bulb Economizer Field

Installed

Horizontal Flow Dry Bulb Economizer FieldInstalled

Renewal PartsContact your local UP parts distribution center forauthorized replacement parts.

ApprovalsDesign certified by CSA as follows:

1. For use as a cooling only unit, cooling unit witha forced air furnace.

2. For outdoor installation only.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A4

Johnson Controls Ducted Systems

Page 7: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

3. For installation on combustible material andmay be installed directly on combustibleflooring or, in the U.S., on wood flooringor Class A, Class B or Class C roof coveringmaterials.

4. For use with natural gas.

 CAUTION

This product must be installed in strict compliancewith the enclosed installation instructions and any ap-plicable local, state, and national codes including,but not limited to, building, electrical, and mechanicalcodes.

 WARNING

Improper installation may create a condition where theoperation of the product could cause personal injuryor property damage.

 CAUTION

This system uses R-410A Refrigerant which operatesat higher pressures than R-22. No other refrigerantmay be used in this system.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 5

Johnson Controls Ducted Systems

Page 8: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Nomenclature

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A6

Johnson Controls Ducted Systems

Page 9: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Installation

Installation Safety InformationRead these instructions before continuingthis appliance installation. This is an outdoorcombination heating and cooling unit. The installermust assure that these instructions are madeavailable to the consumer and with instructions toretain them for future reference.

1. Refer to the unit rating plate for the approvedtype of gas for this product.

2. Install this unit only in a location and positionas specified in the Location section.

3. Never test for gas leaks with an open flame.Use commercially available soap solution madespecifically for the detection of leaks whenchecking all connections.

4. Always install furnace to operate within thefurnace's intended temperature-rise rangewith the duct system and within the allowableexternal static pressure range, as specified onthe unit name/rating plate, specified in PhysicalData of these instructions.

5. This equipment is not to be used for temporaryheating of buildings or structures underconstruction.

 WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warning exactly could re-sult in serious injury, death or property damage. Nevertest for gas leaks with an open flame. Use a commer-cially available soap solution made specifically for thedetection of leaks to check all connections. A fire orexplosion may result causing property damage, per-sonal injury or loss of life.

Preceding Installation

1. Remove the two screws that hold the bracketsin the fork-lift slots on the side of the unit.

Figure 1: Unit shipping bracket

A Bracket screwsB Bracket

2. Turn each bracket toward the ground. Theprotective plywood covering drops to theground.

3. Remove the protective covering from thecondenser coil prior to operation.

Figure 2: Protective condenser covering

4. If a factory option convenience outlet isinstalled, you must install the weatherproofoutlet cover in the field. The cover is locatedbehind the filter access panel.

a. Remove the shipping label that coversthe convenience outlet.

b. Follow the instructions on the back of thecover box.

c. Attach the cover to the unit with the fourscrews provided.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 7

Johnson Controls Ducted Systems

Page 10: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

 CAUTION

208/230-3-60 and units with factory installedPowered Convenience Outlet Option are wiredfor 230v power supply. Change tap on trans-former for 208-3-60 operation. See unit wiring di-agram.

5. For gas heating models, you must movethe supply air temperature (SAT) sensor tothe working position to ensure proper SATreadings. The SAT sensor is shipped in thesupply air compartment.

a. Move the SAT sensor to the inside of thesupply air duct. See item A in Figure 5.

b. Use the excess wire available to its fulllength to drop or mount the SAT sensorin the duct. Avoid close contact with thegas heat exchanger.

c. You can use the shipping bracket to holdthe SAT sensor in the supply air stream.See Figure 3 for the factory SAT sensorlocation and Figure 5 for the sensorrelocation.

Figure 3: Supply air temperature sensor

6. For units equipped with an economizer ormotorized OD air damper, you must movethe return air temperature (RAT) sensor tothe working position to ensure proper RATreadings. See item B in Figure 5.

a. Move the RAT sensor to the inside of thereturn air duct.

b. Use the excess wire available to its fulllength to drop or mount the RAT sensorin the duct.

c. You can use the shipping bracket to holdthe RAT sensor in the return air stream.See Figure 4 for the factory RAT sensorlocation and Figure 5 for the sensorrelocation.

Figure 4: Return air temperature sensor

A Filter Rack and filtersB RAT sensor

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A8

Johnson Controls Ducted Systems

Page 11: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Figure 5: Supply and return air ducts

A Supply air ductB Return air duct

7. If an optional return air smoke detector isinstalled, you must move the return air sensorfrom the factory shipped position (upsidedown) to the working position (right side up)See Figure 6. Then slide the flex tube over thestub and tighten, see Figure 7.

Figure 6: Return air smoke detector - shippedposition

A Flex tube securedto the bracket C Controller

B Return air sensor D Wire tie

Figure 7: Return air smoke detector - workingposition

A ControllerB Return air sensor

C Flex tube in theworking position

LimitationsThese units must be installed in accordance with thefollowing:In U.S.A.:

• National Electrical Code, ANSI/NFPA No. 70 -Latest Edition

• National Fuel Gas Code, ANSI Z223.1 - LatestEdition

• Gas-Fired Central Furnace Standard, ANSIZ21.47a. - Latest Edition

• Local building codes, and

• Local gas utility requirements

In Canada:

• Canadian Electrical Code, CSA C22.1

• Installation Codes, CSA - B149.1.

• Local plumbing and waste water codes, and

• Other applicable local codes.

Refer to unit application data found in thisdocument.After installation, gas fired units must be adjusted toobtain a temperature rise within the range specifiedon the unit rating plate.If components are to be added to a unit to meetlocal codes, they are to be installed at the dealer’sand/or customer’s expense.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 9

Johnson Controls Ducted Systems

Page 12: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Size of unit for proposed installation should bebased on heat loss/heat gain calculation madeaccording to the methods of Air ConditioningContractors of America (ACCA).This furnace is not to be used for temporary heatingof buildings or structures under construction.Table 1: ZL08-14 Unit Limitations

Unit Limitations

Applied VoltageOutdoorDB Temp

Model Size(Tons) Unit Voltage

SCCR(kVA)

Min Max Max (°F)208/230-3-60 5 187 252 125

460-3-60 5 432 504 125ZL 08 (7.5)575-3-60 5 540 630 125

208/230-3-60 5 187 252 125460-3-60 5 432 504 125ZL 09 (8.5)575-3-60 5 540 630 125

208/230-3-60 5 187 252 125460-3-60 5 432 504 125ZL 12 (10)575-3-60 5 540 630 125

208/230-3-60 5 187 252 125460-3-60 5 432 504 125ZL 14 (12.5)575-3-60 5 540 630 125

LocationUse the following guidelines to select a suitablelocation for these units:

1. Unit is designed for outdoor installation only.

2. Condenser coils must have an unlimited supplyof air. Where a choice of location is possible,position the unit on either north or east side ofbuilding.

3. Suitable for mounting on roof curb.

4. For ground level installation, use a levelconcrete slab with a minimum thickness of 4inches. The length and width should be at least6 inches greater than the unit base rails. Do nottie slab to the building foundation.

5. Roof structures must be able to support theweight of the unit and its options/accessories.Unit must be installed on a solid, level roof curbor appropriate angle iron frame.

6. Maintain level tolerance to ½ in. across theentire width and length of unit.

 WARNING

Excessive exposure of this furnace to contaminatedcombustion air will result in safety and performancerelated problems. Typical contaminates include:permanent wave solution, chlorinated waxes andcleaners, chlorine based swimming pool chemicals,water softening chemicals, de-icing salts or chemicals,carbon tetrachloride, Halogen type refrigerants,cleaning solvents (e.g. perchloroethylene), printinginks, paint removers, varnishes, hydrochloric acid,cements and glues, anti-static fabric softeners forclothes dryers, masonry acid washing materials.

ClearancesAll units require particular clearances for properoperation and service. Installer must makeprovisions for adequate combustion and ventilationair in accordance with section 5.3 of Air forCombustion and Ventilation of the National FuelGas Code, ANSI Z223.1 – Latest Edition (in U.S.A.),or Sections 7.2, 7.3, or 7.4 of Gas Installation Codes,CSA-B149.1 (in Canada) - Latest Edition, and/orapplicable provisions of the local building codes.Refer to Table 4 and Table 5 for clearances requiredfor combustible construction, servicing, and properunit operation.

 WARNING

Do not permit overhanging structures or shrubs to ob-struct condenser air discharge outlet, combustion airinlet or vent outlets.

Rigging And HandlingExercise care when moving the unit. Do not removeany packaging until the unit is near the place ofinstallation. Rig the unit by attaching chain or cableslings to the lifting holes provided in the base rails.Spreader bars, whose length exceeds the largestdimension across the unit, MUST be used across thetop of the unit.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A10

Johnson Controls Ducted Systems

Page 13: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

 CAUTION

If a unit is to be installed on a roof curb other than aDucted Systems roof curb, gasketing must be appliedto all surfaces that come in contact with the unit un-derside.

 CAUTION

Before lifting, make sure the unit weight is distributedequally on the rigging cables so it will lift evenly.

Units may be moved or lifted with a forklift. Slottedopenings in the base rails are provided for thispurpose.LENGTH OF FORKS MUST BE A MINIMUM OF 60INCHES.

 CAUTION

All panels must be secured in place when the unit islifted.The condenser coils should be protected fromrigging cable damage with plywood or other suitablematerial.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 11

Johnson Controls Ducted Systems

Page 14: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

ZL08-14 Unit Weights

Figure 8: Unit 4 Point Load Weight Figure 9: Unit 6 Point Load Weight

Figure 10: Center of Gravity

Table 2: ZL08-14 Corner WeightsWeight (lb.) Center of Gravity 4 Point Load Location (lb.) 6 Point Load Location (lb.)

Model Size(Tons) Shipping Operating X Y A B C D A B C D E F

ZLE 08 (7.5) 925 920 45 37 262 282 195 181 173 181 191 131 125 119ZLE 09 (8.5) 930 925 46 36 258 284 201 182 169 180 192 136 128 120ZLE 12 (10) 960 955 46 35 258 287 216 194 169 181 195 146 136 127ZLE 14 (12.5) 985 980 44 35 277 283 213 208 184 186 189 142 140 138ZLG 08 (7.5) 1045 1040 44 37 304 312 215 210 202 205 209 144 141 139ZLG 09 (8.5) 1035 1030 45 36 294 309 219 208 194 201 208 147 142 138ZLG 12 (10) 1055 1050 45 36 299 313 224 214 198 204 210 151 146 142ZLG 14 (12.5) 1075 1070 44 36 309 316 225 220 205 208 211 151 148 146

Table 3: ZL08-14 Unit Accessory WeightsUnit Accessory Weights (lb.)Powered Convenience Outlet Factory installed 35Non-Powered Convenience Outlet Factory Installed 10Vertical Flow Dry Bulb Economizer Large Footprint 96Horizontal Flow Dry Bulb Economizer LargeFootprint Tall

102

Power Exhaust Vert Flow Large Footprint 39Power Exhaust Horiz Flow Large Footprint 39Hail Guard Kit Large Tall Factory Installed 50Flue Extension Kit (1FE0416) 19Curb Rigid 14 in. Large Footprint 135Curb Rigid 24 in. Large Footprint 135

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A12

Johnson Controls Ducted Systems

Page 15: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Figure 11: ZL 08 to ZL 09 Unit Dimensions

Table 4: ZL08-14 Unit ClearancesDirection Distance (in.) Direction Distance (in.)

1Top1 72 Right 18

Front 48 Left 12

Rear 21823/363 4Bottom4 1

1 Units must be installed outdoors. Over hanging structure orshrubs should not obscure condenser air discharge outlet.

2 Units without economizer or power exhaust.3 Units equipped with an Economizer or Power Exhaust. Flue

products must not be discharged within 10 Feet of the rearof the unit.

4 Units may be installed on combustible floors made fromwood or class A, B or C roof covering materials.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 13

Johnson Controls Ducted Systems

Page 16: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Figure 12: ZL 12 to ZL 14 Unit Dimensions

Table 5: ZL08-14 Unit ClearancesDirection Distance (in.) Direction Distance (in.)

1Top1 72 Right 18

Front 48 Left 12

Rear 21823/363 4Bottom4 1

1 Units must be installed outdoors. Over hanging structure orshrubs should not obscure condenser air discharge outlet.

2 Units without economizer or power exhaust.3 Units equipped with an Economizer or Power Exhaust. Flue

products must not be discharged within 10 Feet of the rearof the unit.

4 Units may be installed on combustible floors made fromwood or class A, B or C roof covering materials.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A14

Johnson Controls Ducted Systems

Page 17: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Figure 13: 1RC0457, 1RC0459 Roof Curb Dimensions

DuctworkDuctwork should be designed and sized accordingto the methods in Manual D of the Air ConditioningContractors of America (ACCA) or as recommendedby any other recognized authority such as ASHRAEor SMACNA.A closed return duct system should be used. Thiswill not preclude use of economizers or outdoorfresh air intake. The supply and return air ductconnections at the unit should be made with flexiblejoints to minimize noise.The supply and return air duct systems shouldbe designed for the CFM and static pressurerequirements of the job. They should NOT be sizedto match the dimensions of the duct connections onthe unit.Refer to Figure 11 and Figure 12 for bottom and sideair duct openings.

Duct CoversUnits are shipped with the side duct openingscovered and a covering over the bottom of the unit.For bottom duct application, ZL Models requirea filler plate to be removed from the return airopening, for all other models no other changes arenecessary. For side duct application, remove theside duct covers and install over the bottom ductopenings. The panels removed from the side ductconnections are designed to be reused by securingeach panel to its respective bottom duct opening.But keep in mind that the supply and return panelsare installed with the painted surface DOWN,facing the bottom duct opening. The gasket mustbe removed from the insulation side of the ductcover so it is not directly exposed to the heatingelements. The panels are secured by sliding theminto slots in the back of the duct openings andscrewing them to the base of the unit with screws(Use screws removed from original panel location.).Seals around duct openings must be tight.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 15

Johnson Controls Ducted Systems

Page 18: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

 CAUTION

When fastening ductwork to side duct flanges on unit,insert screws through duct flanges only. DO NOT in-sert screws through casing. Outdoor ductwork mustbe insulated and water-proofed.

Figure 14: Side Duct Cover Panels

Note: Shown with duct connection cover panelas shipped.

Figure 15: Bottom Return Opening For Side DuctConversion

Figure 16: Bottom Supply Opening For Side DuctConversion

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A16

Johnson Controls Ducted Systems

Page 19: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Condensate DrainA side condensate drain is provided to facilitatecondensate piping. A condensate drain connectionis available through the base pan for piping insidethe roof curb. Trap the connection per Figure 17.The trap and drain lines should be protected fromfreezing.Plumbing must conform to local codes. Use asealing compound on male pipe threads. Installcondensate drain line from the 3/4 inch NPT femaleconnection on the unit to an open drain.

Figure 17: Condensate Drain

CompressorsThe compressor used in this product is specificallydesigned to operate with R-410A Refrigerant andcannot be interchanged.

 CAUTION

This system uses R-410A Refrigerant which operatesat higher pressures than R-22. No other refrigerantmay be used in this system.

The compressor also uses a refrigerant oil that isextremely hygroscopic, meaning it absorbs waterreadily. They can absorb 15 times as much water asother oils designed for HCFC and CFC refrigerants.Take all necessary precautions to avoid exposure ofthe oil to the atmosphere.

 CAUTION

Do not leave the system open to the atmosphere. Unitdamage could occur due to moisture being absorbedby the refrigerant in the system. This type of oil ishighly susceptible to moisture absorption.

R-410A compressor lubricants are known to causelong term damage to some synthetic roofingmaterials.

 CAUTION

Exposure, even if immediately cleaned up, may causeembrittlement (leading to cracking) to occur in oneyear or more. When performing any service that mayrisk exposure of compressor oil to the roof, take pre-cautions to protect roofing.

Procedures which risk oil leakage include, but arenot limited to, compressor replacement, repairingrefrigerant leaks, replacing refrigerant componentssuch as filter drier, pressure switch, metering deviceor coil.Units are shipped with compressor mountingswhich are factory-adjusted and ready for operation.

 CAUTION

Do not loosen compressor mounting bolts.

FiltersTwo-inch filters are supplied with each unit. Four-inch filters may be used with no modification to thefilter racks. Filters must always be installed ahead ofevaporator coil and must be kept clean or replacedwith same size and type. Dirty filters reduce thecapacity of the unit and result in frosted coils orsafety shutdown. Refer to physical data tables, forthe number and size of filters needed for the unit.The unit should not be operated without filtersproperly installed.

Power And Control WiringField wiring to the unit, fuses, and disconnects mustconform to provisions of National Electrical Code(NEC), ANSI/NFPA No. 70 – Latest Edition (in U.S.A.),current Canadian Electrical Code C221, and/or local

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 17

Johnson Controls Ducted Systems

Page 20: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

ordinances. The unit must be electrically groundedin accordance with NEC and CEC as specified aboveand/or local codes.Voltage tolerances which must be maintained at thecompressor terminals during starting and runningconditions are indicated on the unit Rating Plate andTable 1.

 CAUTION

208/230-3-60 and 208/230-1-60 units control trans-formers are factory wired for 230v. Change tap ontransformer for 208v operation. See unit wiring dia-gram.

The internal wiring harnesses furnished with thisunit are an integral part of the design certifiedunit. Field alteration to comply with electrical codesshould not be required. If any of the wire suppliedwith the unit must be replaced, replacement wiremust be of the type shown on the wiring diagramand the same minimum gauge as the replaced wire.A disconnect must be utilized for these units.Factory installed disconnects are available. Ifinstalling a disconnect (field supplied), refer toFigure 11 thru Figure 12 for the recommendedmounting location.

 CAUTION

Avoid damage to internal components if drilling holesfor disconnect mounting.

Note: Since not all local codes allow themounting of a disconnect on the unit, pleaseconfirm compliance with local code beforemounting a disconnect on the unit.

Electrical line must be sized properly to carry theload. USE COPPER CONDUCTORS ONLY. Each unitmust be wired with a separate branch circuit feddirectly from the meter panel and properly fused.

 CAUTION

When connecting electrical power and control wiringto the unit, water-proof connectors must be used sothat water or moisture cannot be drawn into the unitduring normal operation. The above water-proofingconditions will also apply when installing a field sup-plied disconnect switch.

 CAUTION

When installing equipment in a facility with a 3 phasehigh-leg delta power supply, care must be taken toensure that the high-leg conductor is not attachedto either of the two legs of the (single phase, directdrive) X13 or ECM motors. Failure to do so can re-sult in the motor acting erratically or not running atall.Check for the high leg conductor by checking volt-age of each phase to ground.Example: A or L1 phaseto ground, voltage reading is 120V. B or L2 phase toground, voltage reading is 195 to 208V. C or L3 phaseto ground, voltage reading is 120V. Therefore B orL2 phase is the high Leg. The high should alwaysbe wired to the center or B or L2 tap. Note: Checkall three phase motors and compressors for properrotation after making a change. If it is necessary tochange 3 phase motor rotation, swap A or L1 and C orL3 only.

Thermostat WiringInstall the thermostat on an inside wallapproximately 56 inches above the floor. Thethermostat must not be subject to drafts, sunexposure, or heat from electrical fixtures orappliances.Follow the manufacturer's instructions enclosedwith thermostat for general installation procedure.Use color-coded, insulated wires to connect thethermostat to the unit. See Table 6 for control wiresizing and maximum length.Table 6: Control Wire Sizes

Wire Size 1Maximum Length1

18 AWG 150 Feet

1 From the unit to the thermostat and back to the unit.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A18

Johnson Controls Ducted Systems

Page 21: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Typical Field Power and Control Wiring

Typical Power Wiring

Figure 18: Typical Smart Equipment™ Control Wiring

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 19

Johnson Controls Ducted Systems

Page 22: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Figure 19: Field Wiring Disconnect

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A20

Johnson Controls Ducted Systems

Page 23: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Electrical Data ZL08-14 Static Indoor Blowers - Without Powered ConvenienceOutlet

Table 7: ZL08-14 Standard Static Indoor Blower - Without Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ect R

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCC

OD

Fan

Mot

ors

(eac

h)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

Max

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

FLA LRA

MCA

1 w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 42.6 45 50 45 241 44.8 45 50 47 24611725 12 1 33.3 50.4 60 60 46 241 53.1 60 60 49 24612525 18.6 1 51.6 73.3 80 80 67 241 76 80 80 70 24613225 24 1 66.6 92 100 100 85 241 94.8 100 100 87 246

208-3-60 14 83.1 22 13.5 88 21 2.3 7 1.1

14225 31.8 2 88.3 119.1 125 125 110 241 121.9 125 125 112 246None - - - 42.8 45 50 45 243 44.8 45 50 47 24811725 16 1 38.5 57.1 60 60 53 243 59.6 60 60 55 24812525 24.8 1 59.7 83.6 90 90 77 243 86.1 90 90 79 24813225 32 1 77 105.3 110 110 97 243 107.8 110 110 99 248

230-3-60 14 83.1 22 13.5 88 21 2.3 7.2 1

14225 42.4 2 102 136.5 150 150 126 243 139 150 150 128 248None - - - 20.2 25 25 21 122 21.2 25 25 23 12411746 16.5 1 19.8 29.3 30 30 27 122 30.5 35 35 28 12412846 27.8 1 33.4 46.3 50 50 43 122 47.5 50 50 44 12413346 33 1 39.7 54.1 60 60 50 122 55.4 60 60 51 124

460-3-60 6.4 41 10 6 44 9 1.3 3.6 0.5

14246 41.7 2 50.2 67.3 70 70 62 122 68.5 70 70 63 124None - - - 15.4 20 20 16 89 16.2 20 20 17 9111758 17 1 16.4 23.6 25 25 22 89 24.6 25 25 23 91

08(7.5)

575-3-60 4.6 33 7 4.9 34 8 1.1 2.5 0.413458 34 1 32.7 44 45 45 40 89 45 45 45 41 91None - - - 42.8 45 50 45 236 45 45 50 48 24111725 12 1 33.3 50.4 60 60 46 236 53.1 60 60 49 24112525 18.6 1 51.6 73.3 80 80 67 236 76 80 80 70 24113225 24 1 66.6 92 100 100 85 236 94.8 100 100 87 241

208-3-60 14 83.1 22 13.7 83.1 21 2.3 7 1.1

14225 31.8 2 88.3 119.1 125 125 110 236 121.9 125 125 112 241None - - - 43 45 50 45 238 45 45 50 48 24311725 16 1 38.5 57.1 60 60 53 238 59.6 60 60 55 24312525 24.8 1 59.7 83.6 90 90 77 238 86.1 90 90 79 24313225 32 1 77 105.3 110 110 97 238 107.8 110 110 99 243

230-3-60 14 83.1 22 13.7 83.1 21 2.3 7.2 1

14225 42.4 2 102 136.5 150 150 126 238 139 150 150 128 243None - - - 20.4 25 25 22 119 21.4 25 25 23 12111746 16.5 1 19.8 29.3 30 30 27 119 30.5 35 35 28 12112846 27.8 1 33.4 46.3 50 50 43 119 47.5 50 50 44 12113346 33 1 39.7 54.1 60 60 50 119 55.4 60 60 51 121

460-3-60 6.4 41 10 6.2 41 10 1.3 3.6 0.5

14246 41.7 2 50.2 67.3 70 70 62 119 68.5 70 70 63 121None - - - 15.3 20 20 16 88 16.1 20 20 17 9011758 17 1 16.4 23.6 25 25 22 88 24.6 25 25 23 90

09(8.5)

575-3-60 4.6 33 7 4.8 33 8 1.1 2.5 0.413458 34 1 32.7 44 45 45 40 88 45 45 45 41 90

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 21

Johnson Controls Ducted Systems

Page 24: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 7: ZL08-14 Standard Static Indoor Blower - Without Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ect R

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCCO

D F

an M

otor

s (e

ach)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

Max

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

FLA LRA

MCA

1 w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 49.4 50 60 52 302 51.6 60 60 55 30711725 12 1 33.3 50.4 60 60 52 302 53.1 60 60 55 30712525 18.6 1 51.6 73.3 80 80 67 302 76 80 80 70 30713225 24 1 66.6 92 100 100 85 302 94.8 100 100 87 307

208-3-60 16.5 110 26 16 110 25 5.8 7 1.1

14225 31.8 2 88.3 119.1 125 125 110 302 121.9 125 125 112 307None - - - 49 50 60 52 301 51 60 60 54 30511725 16 1 38.5 57.1 60 60 53 301 59.6 60 60 55 30512525 24.8 1 59.7 83.6 90 90 77 301 86.1 90 90 79 30513225 32 1 77 105.3 110 110 97 301 107.8 110 110 99 305

230-3-60 16.5 110 26 16 110 25 5.2 7.2 1

14225 42.4 2 102 136.5 150 150 126 301 139 150 150 128 305None - - - 23.5 25 30 25 146 24.5 25 30 26 14811746 16.5 1 19.8 29.3 30 30 27 146 30.5 35 35 28 14812846 27.8 1 33.4 46.3 50 50 43 146 47.5 50 50 44 14813346 33 1 39.7 54.1 60 60 50 146 55.4 60 60 51 148

460-3-60 7.2 52 11 7.8 52 12 2.9 3.6 0.5

14246 41.7 2 50.2 67.3 70 70 62 146 68.5 70 70 63 148None - - - 17.5 20 20 19 112 18.3 20 20 19 11411758 17 1 16.4 23.6 25 25 22 112 24.6 25 25 23 114

12 (10)

575-3-60 5.7 43.8 9 5.7 38.9 9 2.2 2.5 0.413458 34 1 32.7 44 45 45 40 112 45 45 45 41 114None - - - 57.8 60 70 61 384 57.8 60 70 61 38411725 12 1 33.3 57.8 60 70 61 384 57.8 60 70 61 38412525 18.6 1 51.6 75.6 80 80 70 384 75.6 80 80 70 38413225 24 1 66.6 94.4 100 100 87 384 94.4 100 100 87 384

208-3-60 18.6 149 29 19.6 136 31 5.8 8.9 0

14225 31.8 2 88.3 121.5 125 125 112 384 121.5 125 125 112 384None - - - 56.5 60 70 59 383 56.5 60 70 59 38311725 16 1 38.5 58.4 60 70 59 383 58.4 60 70 59 38312525 24.8 1 59.7 84.9 90 90 78 383 84.9 90 90 78 38313225 32 1 77 106.5 110 110 98 383 106.5 110 110 98 383

230-3-60 18.6 149 29 19.6 136 31 5.2 8.2 0

14225 42.4 2 102 137.8 150 150 127 383 137.8 150 150 127 383None - - - 26.5 30 35 28 173 26.5 30 35 28 17311746 16.5 1 19.8 29.9 30 35 27 173 29.9 30 35 27 17312846 27.8 1 33.4 46.9 50 50 43 173 46.9 50 50 43 17313346 33 1 39.7 54.8 60 60 50 173 54.8 60 60 50 173

460-3-60 9 60.9 14 8.2 66.1 13 2.9 4.1 0

14246 41.7 2 50.2 67.9 70 70 62 173 67.9 70 70 62 173None - - - 20.9 25 25 22 149 20.9 25 25 22 14911758 17 1 16.4 24.5 25 25 23 149 24.5 25 25 23 149

14(12.5)

575-3-60 7.1 56 11 6.6 55.3 10 2.2 3.2 013458 34 1 32.7 44.9 45 45 41 149 44.9 45 45 41 149

1 Minimum Circuit Ampacity.2 Dual Element, Time Delay Type.3 HACR type per NEC.4 Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field

installed electric heat kits may exceed the factory installed disconnect amperage rating.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A22

Johnson Controls Ducted Systems

Page 25: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Electrical Data ZLE 08-14 Standard Indoor Blower - With Powered ConvenienceOutlet

Table 8: Electrical Data ZL08-14 Standard Indoor Blower - With Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ect R

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCC

OD

Fan

Mot

ors

(eac

h)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e2 /Bre

aker

3 Siz

e (A

mps

)

Max

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

FLA LRA

MCA

w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 46.9 50 60 50 245 49.1 50 60 52 25011725 12 1 33.3 55.8 60 60 51 245 58.5 60 60 54 25012525 18.6 1 51.6 78.6 80 80 72 245 81.4 90 90 75 25013225 24 1 66.6 97.4 100 100 90 245 100.1 110 110 92 250

208-3-60 14 83.1 22 13.5 88 21 2.3 7 1.1 8.6

14225 31.8 2 88.3 124.5 125 125 115 245 127.3 150 150 117 250None - - - 47.1 50 60 50 247 49.1 50 60 52 25211725 16 1 38.5 62.5 70 70 58 247 65 70 70 60 25212525 24.8 1 59.7 89 90 90 82 247 91.5 100 100 84 25213225 32 1 77 110.6 125 125 102 247 113.1 125 125 104 252

230-3-60 14 83.1 22 13.5 88 21 2.3 7.2 1 8.6

14225 42.4 2 102 141.9 150 150 131 247 144.4 150 150 133 252None - - - 22.4 25 25 24 124 23.4 25 25 25 12611746 16.5 1 19.8 31.9 35 35 29 124 33.2 35 35 31 12612846 27.8 1 33.4 48.9 50 50 45 124 50.2 60 60 46 12613346 33 1 39.7 56.8 60 60 52 124 58.1 60 60 53 126

460-3-60 6.4 41 10 6 44 9 1.3 3.6 0.5 8.6

14246 41.7 2 50.2 69.9 70 70 64 124 71.2 80 80 65 126None - - - 17.1 20 20 18 91 17.9 20 20 19 9313458 34 1 32.7 46.2 50 50 42 91 47.2 50 50 43 93

08(7.5)

575-3-60 4.6 33 7 4.9 34 8 1.1 2.5 0.4 8.611758 17 1 16.4 25.8 30 30 24 91 26.8 30 30 25 93None - - - 47.1 50 60 50 240 49.3 50 60 53 24511725 12 1 33.3 55.8 60 60 51 240 58.5 60 60 54 24512525 18.6 1 51.6 78.6 80 80 72 240 81.4 90 90 75 24513225 24 1 66.6 97.4 100 100 90 240 100.1 110 110 92 245

208-3-60 14 83.1 22 13.7 83.1 21 2.3 7 1.1 8.6

14225 31.8 2 88.3 124.5 125 125 115 240 127.3 150 150 117 245None - - - 47.3 50 60 50 242 49.3 50 60 53 24711725 16 1 38.5 62.5 70 70 58 242 65 70 70 60 24712525 24.8 1 59.7 89 90 90 82 242 91.5 100 100 84 24713225 32 1 77 110.6 125 125 102 242 113.1 125 125 104 247

230-3-60 14 83.1 22 13.7 83.1 21 2.3 7.2 1 8.6

14225 42.4 2 102 141.9 150 150 131 242 144.4 150 150 133 247None - - - 22.6 25 25 24 121 23.6 25 25 25 12311746 16.5 1 19.8 31.9 35 35 29 121 33.2 35 35 31 12312846 27.8 1 33.4 48.9 50 50 45 121 50.2 60 60 46 12313346 33 1 39.7 56.8 60 60 52 121 58.1 60 60 53 123

460-3-60 6.4 41 10 6.2 41 10 1.3 3.6 0.5 8.6

14246 41.7 2 50.2 69.9 70 70 64 121 71.2 80 80 65 123None - - - 17 20 20 18 90 17.8 20 20 19 9211758 17 1 16.4 25.8 30 30 24 90 26.8 30 30 25 92

09(8.5)

575-3-60 4.6 33 7 4.8 33 8 1.1 2.5 0.4 8.613458 34 1 32.7 46.2 50 50 42 90 47.2 50 50 43 92

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 23

Johnson Controls Ducted Systems

Page 26: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 8: Electrical Data ZL08-14 Standard Indoor Blower - With Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ect R

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCCO

D F

an M

otor

s (e

ach)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e2 /Bre

aker

3 Siz

e (A

mps

)

Max

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

FLA LRA

MCA

w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 53.7 60 70 57 306 55.9 60 70 60 31111725 12 1 33.3 55.8 60 70 57 306 58.5 60 70 60 31112525 18.6 1 51.6 78.6 80 80 72 306 81.4 90 90 75 31113225 24 1 66.6 97.4 100 100 90 306 100.1 110 110 92 311

208-3-60 16.5 110 26 16 110 25 5.8 7 1.1 8.6

14225 31.8 2 88.3 124.5 125 125 115 306 127.3 150 150 117 311None - - - 53.3 60 60 57 305 55.3 60 70 59 31011725 16 1 38.5 62.5 70 70 58 305 65 70 70 60 31012525 24.8 1 59.7 89 90 90 82 305 91.5 100 100 84 31013225 32 1 77 110.6 125 125 102 305 113.1 125 125 104 310

230-3-60 16.5 110 26 16 110 25 5.2 7.2 1 8.6

14225 42.4 2 102 141.9 150 150 131 305 144.4 150 150 133 310None - - - 25.7 30 30 27 148 26.7 30 30 28 15011746 16.5 1 19.8 31.9 35 35 29 148 33.2 35 35 31 15012846 27.8 1 33.4 48.9 50 50 45 148 50.2 60 60 46 15013346 33 1 39.7 56.8 60 60 52 148 58.1 60 60 53 150

460-3-60 7.2 52 11 7.8 52 12 2.9 3.6 0.5 8.6

14246 41.7 2 50.2 69.9 70 70 64 148 71.2 80 80 65 150None - - - 19.2 20 20 20 113 20 20 20 21 11511758 17 1 16.4 25.8 30 30 24 113 26.8 30 30 25 115

12 (10)

575-3-60 5.7 43.8 9 5.7 38.9 9 2.2 2.5 0.4 8.613458 34 1 32.7 46.2 50 50 42 113 47.2 50 50 43 115None - - - 62.1 70 80 66 388 62.1 70 80 66 38811725 12 1 33.3 62.1 70 80 66 388 62.1 70 80 66 38812525 18.6 1 51.6 81 90 90 75 388 81 90 90 75 38813225 24 1 66.6 99.8 100 100 92 388 99.8 100 100 92 388

208-3-60 18.6 149 29 19.6 136 31 5.8 8.9 0 8.6

14225 31.8 2 88.3 126.9 150 150 117 388 126.9 150 150 117 388None - - - 60.8 70 80 64 387 60.8 70 80 64 38711725 16 1 38.5 63.8 70 80 64 387 63.8 70 80 64 38712525 24.8 1 59.7 90.3 100 100 83 387 90.3 100 100 83 38713225 32 1 77 111.9 125 125 103 387 111.9 125 125 103 387

230-3-60 18.6 149 29 19.6 136 31 5.2 8.2 0 8.6

14225 42.4 2 102 143.1 150 150 132 387 143.1 150 150 132 387None - - - 28.7 30 35 30 175 28.7 30 35 30 17511746 16.5 1 19.8 32.6 35 35 30 175 32.6 35 35 30 17512846 27.8 1 33.4 49.6 50 50 46 175 49.6 50 50 46 17513346 33 1 39.7 57.4 60 60 53 175 57.4 60 60 53 175

460-3-60 9 60.9 14 8.2 66.1 13 2.9 4.1 0 8.6

14246 41.7 2 50.2 70.6 80 80 65 175 70.6 80 80 65 175None - - - 22.6 25 25 24 150 22.6 25 25 24 15011758 17 1 16.4 26.7 30 30 25 150 26.7 30 30 25 150

14(12.5)

575-3-60 7.1 56 11 6.6 55.3 10 2.2 3.2 0 8.613458 34 1 32.7 47 50 50 43 150 47 50 50 43 150

1 Minimum Circuit Ampacity.2 Dual Element, Time Delay Type.3 HACR type per NEC.4 Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field

installed electric heat kits may exceed the factory installed disconnect amperage rating.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A24

Johnson Controls Ducted Systems

Page 27: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Electrical Data ZLE08-14 Medium Indoor Blower - Without Powered ConvenienceOutlet

Table 9: Electrical Data ZL08-14 Medium Indoor Blower - Without Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ectR

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCC

OD

Fan

Mot

ors

(eac

h)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e2 /Bre

aker

3 Siz

e (A

mps

)

Max

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

FLA LRA

MCA

1 w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 42.6 45 50 45 241 44.8 45 50 47 24611725 12 1 33.3 50.4 60 60 46 241 53.1 60 60 49 24612525 18.6 1 51.6 73.3 80 80 67 241 76 80 80 70 24613225 24 1 66.6 92 100 100 85 241 94.8 100 100 87 246

208-3-60 14 83.1 22 13.5 88 21 2.3 7 1.1

14225 31.8 2 88.3 119.1 125 125 110 241 121.9 125 125 112 246None - - - 42.8 45 50 45 243 44.8 45 50 47 24811725 16 1 38.5 57.1 60 60 53 243 59.6 60 60 55 24812525 24.8 1 59.7 83.6 90 90 77 243 86.1 90 90 79 24813225 32 1 77 105.3 110 110 97 243 107.8 110 110 99 248

230-3-60 14 83.1 22 13.5 88 21 2.3 7.2 1

14225 42.4 2 102 136.5 150 150 126 243 139 150 150 128 248None - - - 20.2 25 25 21 122 21.2 25 25 23 12411746 16.5 1 19.8 29.3 30 30 27 122 30.5 35 35 28 12412846 27.8 1 33.4 46.3 50 50 43 122 47.5 50 50 44 12413346 33 1 39.7 54.1 60 60 50 122 55.4 60 60 51 124

460-3-60 6.4 41 10 6 44 9 1.3 3.6 0.5

14246 41.7 2 50.2 67.3 70 70 62 122 68.5 70 70 63 124None - - - 15.4 20 20 16 89 16.2 20 20 17 9111758 17 1 16.4 23.6 25 25 22 89 24.6 25 25 23 91

08(7.5)

575-3-60 4.6 33 7 4.9 34 8 1.1 2.5 0.413458 34 1 32.7 44 45 45 40 89 45 45 45 41 91None - - - 42.8 45 50 45 236 45 45 50 48 24111725 12 1 33.3 50.4 60 60 46 236 53.1 60 60 49 24112525 18.6 1 51.6 73.3 80 80 67 236 76 80 80 70 24113225 24 1 66.6 92 100 100 85 236 94.8 100 100 87 241

208-3-60 14 83.1 22 13.7 83.1 21 2.3 7 1.1

14225 31.8 2 88.3 119.1 125 125 110 236 121.9 125 125 112 241None - - - 43 45 50 45 238 45 45 50 48 24311725 16 1 38.5 57.1 60 60 53 238 59.6 60 60 55 24312525 24.8 1 59.7 83.6 90 90 77 238 86.1 90 90 79 24313225 32 1 77 105.3 110 110 97 238 107.8 110 110 99 243

230-3-60 14 83.1 22 13.7 83.1 21 2.3 7.2 1

14225 42.4 2 102 136.5 150 150 126 238 139 150 150 128 243None - - - 20.4 25 25 22 119 21.4 25 25 23 12111746 16.5 1 19.8 29.3 30 30 27 119 30.5 35 35 28 12112846 27.8 1 33.4 46.3 50 50 43 119 47.5 50 50 44 12113346 33 1 39.7 54.1 60 60 50 119 55.4 60 60 51 121

460-3-60 6.4 41 10 6.2 41 10 1.3 3.6 0.5

14246 41.7 2 50.2 67.3 70 70 62 119 68.5 70 70 63 121None - - - 15.3 20 20 16 88 16.1 20 20 17 9011758 17 1 16.4 23.6 25 25 22 88 24.6 25 25 23 90

09(8.5)

575-3-60 4.6 33 7 4.8 33 8 1.1 2.5 0.413458 34 1 32.7 44 45 45 40 88 45 45 45 41 90

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 25

Johnson Controls Ducted Systems

Page 28: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 9: Electrical Data ZL08-14 Medium Indoor Blower - Without Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ectR

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCCO

D F

an M

otor

s (e

ach)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e2 /Bre

aker

3 Siz

e (A

mps

)

Max

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

FLA LRA

MCA

1 w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 52.3 60 60 55 315 54.5 60 60 58 32011725 12 1 33.3 54 60 60 55 315 56.8 60 60 58 32012525 18.6 1 51.6 76.9 80 80 71 315 79.6 80 80 73 32013225 24 1 66.6 95.6 100 100 88 315 98.4 100 100 91 320

208-3-60 16.5 110 26 16 110 25 5.8 9.9 1.1

14225 31.8 2 88.3 122.8 125 125 113 315 125.5 150 150 115 320None - - - 51.2 60 60 54 320 53.2 60 60 56 32411725 16 1 38.5 59.9 60 60 55 320 62.4 70 70 57 32412525 24.8 1 59.7 86.4 90 90 79 320 88.9 90 90 82 32413225 32 1 77 108 110 110 99 320 110.5 125 125 102 324

230-3-60 16.5 110 26 16 110 25 5.2 9.4 1

14225 42.4 2 102 139.3 150 150 128 320 141.8 150 150 130 324None - - - 24.6 25 30 26 155 25.6 30 30 27 15811746 16.5 1 19.8 30.6 35 35 28 155 31.9 35 35 29 15812846 27.8 1 33.4 47.6 50 50 44 155 48.9 50 50 45 15813346 33 1 39.7 55.5 60 60 51 155 56.8 60 60 52 158

460-3-60 7.2 52 11 7.8 52 12 2.9 4.7 0.5

14246 41.7 2 50.2 68.6 70 70 63 155 69.9 70 70 64 158None - - - 19.3 20 25 21 134 20.1 25 25 22 13611758 17 1 16.4 25.9 30 30 24 134 26.9 30 30 25 136

12 (10)

575-3-60 5.7 43.8 9 5.7 38.9 9 2.2 4.3 0.413458 34 1 32.7 46.3 50 50 43 134 47.3 50 50 43 136None - - - 58.8 60 70 62 380 58.8 60 70 62 38011725 12 1 33.3 58.8 60 70 62 380 58.8 60 70 62 38012525 18.6 1 51.6 76.9 80 80 71 380 76.9 80 80 71 38013225 24 1 66.6 95.6 100 100 88 380 95.6 100 100 88 380

208-3-60 18.6 149 29 19.6 136 31 5.8 9.9 0

14225 31.8 2 88.3 122.8 125 125 113 380 122.8 125 125 113 380None - - - 57.7 60 70 61 385 57.7 60 70 61 38511725 16 1 38.5 59.9 60 70 61 385 59.9 60 70 61 38512525 24.8 1 59.7 86.4 90 90 79 385 86.4 90 90 79 38513225 32 1 77 108 110 110 99 385 108 110 110 99 385

230-3-60 18.6 149 29 19.6 136 31 5.2 9.4 0

14225 42.4 2 102 139.3 150 150 128 385 139.3 150 150 128 385None - - - 27.1 30 35 29 178 27.1 30 35 29 17811746 16.5 1 19.8 30.6 35 35 28 178 30.6 35 35 28 17812846 27.8 1 33.4 47.6 50 50 44 178 47.6 50 50 44 17813346 33 1 39.7 55.5 60 60 51 178 55.5 60 60 51 178

460-3-60 9 60.9 14 8.2 66.1 13 2.9 4.7 0

14246 41.7 2 50.2 68.6 70 70 63 178 68.6 70 70 63 178None - - - 22 25 25 23 163 22 25 25 23 16311758 17 1 16.4 25.9 30 30 24 163 25.9 30 30 24 163

14(12.5)

575-3-60 7.1 56 11 6.6 55.3 10 2.2 4.3 013458 34 1 32.7 46.3 50 50 43 163 46.3 50 50 43 163

1 Minimum Circuit Ampacity.2 Dual Element, Time Delay Type.3 HACR type per NEC.4 Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field

installed electric heat kits may exceed the factory installed disconnect amperage rating.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A26

Johnson Controls Ducted Systems

Page 29: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Electrical Data ZLE08-14 Medium Indoor Blower - With Powered ConvenienceOutlet

Table 10: ZLE08-14 Medium Indoor Blower - With Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ect R

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCC

OD

Fan

Mot

ors

(eac

h)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e 2 / B

reak

er3 S

ize

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

FLA LRA

MCA

1 w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 46.9 50 60 50 245 49.1 50 60 52 25011725 12 1 33.3 55.8 60 60 51 245 58.5 60 60 54 25012525 18.6 1 51.6 78.6 80 80 72 245 81.4 90 90 75 25013225 24 1 66.6 97.4 100 100 90 245 100.1 110 110 92 250

208-3-60 14 83.1 22 13.5 88 21 2.3 7 1.1 8.6

14225 31.8 2 88.3 124.5 125 125 115 245 127.3 150 150 117 250None - - - 47.1 50 60 50 247 49.1 50 60 52 25211725 16 1 38.5 62.5 70 70 58 247 65 70 70 60 25212525 24.8 1 59.7 89 90 90 82 247 91.5 100 100 84 25213225 32 1 77 110.6 125 125 102 247 113.1 125 125 104 252

230-3-60 14 83.1 22 13.5 88 21 2.3 7.2 1 8.6

14225 42.4 2 102 141.9 150 150 131 247 144.4 150 150 133 252None - - - 22.4 25 25 24 124 23.4 25 25 25 12611746 16.5 1 19.8 31.9 35 35 29 124 33.2 35 35 31 12612846 27.8 1 33.4 48.9 50 50 45 124 50.2 60 60 46 12613346 33 1 39.7 56.8 60 60 52 124 58.1 60 60 53 126

460-3-60 6.4 41 10 6 44 9 1.3 3.6 0.5 8.6

14246 41.7 2 50.2 69.9 70 70 64 124 71.2 80 80 65 126None - - - 17.1 20 20 18 91 17.9 20 20 19 9311758 17 1 16.4 25.8 30 30 24 91 26.8 30 30 25 93

08(7.5)

575-3-60 4.6 33 7 4.9 34 8 1.1 2.5 0.4 8.613458 34 1 32.7 46.2 50 50 42 91 47.2 50 50 43 93None - - - 47.1 50 60 50 240 49.3 50 60 53 24511725 12 1 33.3 55.8 60 60 51 240 58.5 60 60 54 24512525 18.6 1 51.6 78.6 80 80 72 240 81.4 90 90 75 24513225 24 1 66.6 97.4 100 100 90 240 100.1 110 110 92 245

208-3-60 14 83.1 22 13.7 83.1 21 2.3 7 1.1 8.6

14225 31.8 2 88.3 124.5 125 125 115 240 127.3 150 150 117 245None - - - 47.3 50 60 50 242 49.3 50 60 53 24711725 16 1 38.5 62.5 70 70 58 242 65 70 70 60 24712525 24.8 1 59.7 89 90 90 82 242 91.5 100 100 84 24713225 32 1 77 110.6 125 125 102 242 113.1 125 125 104 247

230-3-60 14 83.1 22 13.7 83.1 21 2.3 7.2 1 8.6

14225 42.4 2 102 141.9 150 150 131 242 144.4 150 150 133 247None - - - 22.6 25 25 24 121 23.6 25 25 25 12311746 16.5 1 19.8 31.9 35 35 29 121 33.2 35 35 31 12312846 27.8 1 33.4 48.9 50 50 45 121 50.2 60 60 46 12313346 33 1 39.7 56.8 60 60 52 121 58.1 60 60 53 123

460-3-60 6.4 41 10 6.2 41 10 1.3 3.6 0.5 8.6

14246 41.7 2 50.2 69.9 70 70 64 121 71.2 80 80 65 123None - - - 17 20 20 18 90 17.8 20 20 19 9211758 17 1 16.4 25.8 30 30 24 90 26.8 30 30 25 92

09(8.5)

575-3-60 4.6 33 7 4.8 33 8 1.1 2.5 0.4 8.613458 34 1 32.7 46.2 50 50 42 90 47.2 50 50 43 92

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 27

Johnson Controls Ducted Systems

Page 30: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 10: ZLE08-14 Medium Indoor Blower - With Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ect R

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCCO

D F

an M

otor

s (e

ach)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e 2 / B

reak

er3 S

ize

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

FLA LRA

MCA

1 w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 56.6 60 70 60 319 58.8 60 70 63 32411725 12 1 33.3 59.4 60 70 60 319 62.1 70 70 63 32412525 18.6 1 51.6 82.3 90 90 76 319 85 90 90 78 32413225 24 1 66.6 101 110 110 93 319 103.8 110 110 95 324

208-3-60 16.5 110 26 16 110 25 5.8 9.9 1.1 8.6

14225 31.8 2 88.3 128.1 150 150 118 319 130.9 150 150 120 324None - - - 55.5 60 70 59 324 57.5 60 70 61 32911725 16 1 38.5 65.3 70 70 60 324 67.8 70 70 62 32912525 24.8 1 59.7 91.8 100 100 84 324 94.3 100 100 87 32913225 32 1 77 113.4 125 125 104 324 115.9 125 125 107 329

230-3-60 16.5 110 26 16 110 25 5.2 9.4 1 8.6

14225 42.4 2 102 144.6 150 150 133 324 147.1 150 150 135 329None - - - 26.8 30 30 29 157 27.8 30 30 30 16011746 16.5 1 19.8 33.3 35 35 31 157 34.6 35 35 32 16012846 27.8 1 33.4 50.3 60 60 46 157 51.6 60 60 47 16013346 33 1 39.7 58.2 60 60 54 157 59.4 60 60 55 160

460-3-60 7.2 52 11 7.8 52 12 2.9 4.7 0.5 8.6

14246 41.7 2 50.2 71.3 80 80 66 157 72.6 80 80 67 160None - - - 21 25 25 23 136 21.8 25 25 23 13811758 17 1 16.4 28 30 30 26 136 29 30 30 27 138

12 (10)

575-3-60 5.7 43.8 9 5.7 38.9 9 2.2 4.3 0.4 8.613458 34 1 32.7 48.4 50 50 45 136 49.4 50 50 45 138None - - - 63.1 70 80 67 384 63.1 70 80 67 38411725 12 1 33.3 63.1 70 80 67 384 63.1 70 80 67 38412525 18.6 1 51.6 82.3 90 90 76 384 82.3 90 90 76 38413225 24 1 66.6 101 110 110 93 384 101 110 110 93 384

208-3-60 18.6 149 29 19.6 136 31 5.8 9.9 0 8.6

14225 31.8 2 88.3 128.1 150 150 118 384 128.1 150 150 118 384None - - - 62 70 80 66 389 62 70 80 66 38911725 16 1 38.5 65.3 70 80 66 389 65.3 70 80 66 38912525 24.8 1 59.7 91.8 100 100 84 389 91.8 100 100 84 38913225 32 1 77 113.4 125 125 104 389 113.4 125 125 104 389

230-3-60 18.6 149 29 19.6 136 31 5.2 9.4 0 8.6

14225 42.4 2 102 144.6 150 150 133 389 144.6 150 150 133 389None - - - 29.3 30 35 31 180 29.3 30 35 31 18011746 16.5 1 19.8 33.3 35 35 31 180 33.3 35 35 31 18012846 27.8 1 33.4 50.3 60 60 46 180 50.3 60 60 46 18013346 33 1 39.7 58.2 60 60 54 180 58.2 60 60 54 180

460-3-60 9 60.9 14 8.2 66.1 13 2.9 4.7 0 8.6

14246 41.7 2 50.2 71.3 80 80 66 180 71.3 80 80 66 180None - - - 23.7 25 30 25 164 23.7 25 30 25 16411758 17 1 16.4 28 30 30 26 164 28 30 30 26 164

14(12.5)

575-3-60 7.1 56 11 6.6 55.3 10 2.2 4.3 0 8.613458 34 1 32.7 48.4 50 50 45 164 48.4 50 50 45 164

1 Minimum Circuit Ampacity.2 Dual Element, Time Delay Type.3 HACR type per NEC.4 Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field

installed electric heat kits may exceed the factory installed disconnect amperage rating.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A28

Johnson Controls Ducted Systems

Page 31: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Electrical Data ZLE08-14 High Indoor Blower - Without Powered ConvenienceOutlet

Table 11: ZLE08-14 High Indoor Blower - Without Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ectR

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCC

OD

Fan

Mot

ors

(eac

h)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e 2 /B

reak

er3 S

ize

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

FLA LRA

MCA

1 w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 45.5 50 50 48 253 47.7 50 60 51 25811725 12 1 33.3 54 60 60 50 253 56.8 60 60 52 25812525 18.6 1 51.6 76.9 80 80 71 253 79.6 80 80 73 25813225 24 1 66.6 95.6 100 100 88 253 98.4 100 100 91 258

208-3-60 14 83.1 22 13.5 88 21 2.3 9.9 1.1

14225 31.8 2 88.3 122.8 125 125 113 253 125.5 150 150 115 258None - - - 45 45 50 48 262 47 50 60 50 26611725 16 1 38.5 59.9 60 60 55 262 62.4 70 70 57 26612525 24.8 1 59.7 86.4 90 90 79 262 88.9 90 90 82 26613225 32 1 77 108 110 110 99 262 110.5 125 125 102 266

230-3-60 14 83.1 22 13.5 88 21 2.3 9.4 1

14225 42.4 2 102 139.3 150 150 128 262 141.8 150 150 130 266None - - - 21.3 25 25 23 131 22.3 25 25 24 13311746 16.5 1 19.8 30.6 35 35 28 131 31.9 35 35 29 13312846 27.8 1 33.4 47.6 50 50 44 131 48.9 50 50 45 13313346 33 1 39.7 55.5 60 60 51 131 56.8 60 60 52 133

460-3-60 6.4 41 10 6 44 9 1.3 4.7 0.5

14246 41.7 2 50.2 68.6 70 70 63 131 69.9 70 70 64 133None - - - 17.2 20 20 18 112 18 20 20 19 11411758 17 1 16.4 25.9 30 30 24 112 26.9 30 30 25 114

08(7.5)

575-3-60 4.6 33 7 4.9 34 8 1.1 4.3 0.413458 34 1 32.7 46.3 50 50 43 112 47.3 50 50 43 114None - - - 45.7 50 50 49 248 47.9 50 60 51 25311725 12 1 33.3 54 60 60 50 248 56.8 60 60 52 25312525 18.6 1 51.6 76.9 80 80 71 248 79.6 80 80 73 25313225 24 1 66.6 95.6 100 100 88 248 98.4 100 100 91 253

208-3-60 14 83.1 22 13.7 83.1 21 2.3 9.9 1.1

14225 31.8 2 88.3 122.8 125 125 113 248 125.5 150 150 115 253None - - - 45.2 50 50 48 257 47.2 50 60 50 26111725 16 1 38.5 59.9 60 60 55 257 62.4 70 70 57 26112525 24.8 1 59.7 86.4 90 90 79 257 88.9 90 90 82 26113225 32 1 77 108 110 110 99 257 110.5 125 125 102 261

230-3-60 14 83.1 22 13.7 83.1 21 2.3 9.4 1

14225 42.4 2 102 139.3 150 150 128 257 141.8 150 150 130 261None - - - 21.5 25 25 23 128 22.5 25 25 24 13011746 16.5 1 19.8 30.6 35 35 28 128 31.9 35 35 29 13012846 27.8 1 33.4 47.6 50 50 44 128 48.9 50 50 45 13013346 33 1 39.7 55.5 60 60 51 128 56.8 60 60 52 130

460-3-60 6.4 41 10 6.2 41 10 1.3 4.7 0.5

14246 41.7 2 50.2 68.6 70 70 63 128 69.9 70 70 64 130None - - - 17.1 20 20 18 111 17.9 20 20 19 11311758 17 1 16.4 25.9 30 30 24 111 26.9 30 30 25 113

09(8.5)

575-3-60 4.6 33 7 4.8 33 8 1.1 4.3 0.413458 34 1 32.7 46.3 50 50 43 111 47.3 50 50 43 113

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 29

Johnson Controls Ducted Systems

Page 32: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 11: ZLE08-14 High Indoor Blower - Without Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ectR

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCCO

D F

an M

otor

s (e

ach)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e 2 /B

reak

er3 S

ize

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e (A

mps

)

FLA LRA

MCA

1 w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 55.9 60 70 60 345 58.1 60 70 62 35011725 12 1 33.3 58.5 60 70 60 345 61.3 70 70 62 35012525 18.6 1 51.6 81.4 90 90 75 345 84.1 90 90 77 35013225 24 1 66.6 100.1 110 110 92 345 102.9 110 110 95 350

208-3-60 16.5 110 26 16 110 25 5.8 13.5 1.1

14225 31.8 2 88.3 127.3 150 150 117 345 130 150 150 120 350None - - - 55.2 60 70 59 341 57.2 60 70 61 34611725 16 1 38.5 64.9 70 70 60 341 67.4 70 70 62 34612525 24.8 1 59.7 91.4 100 100 84 341 93.9 100 100 86 34613225 32 1 77 113 125 125 104 341 115.5 125 125 106 346

230-3-60 16.5 110 26 16 110 25 5.2 13.4 1

14225 42.4 2 102 144.3 150 150 133 341 146.8 150 150 135 346None - - - 26.6 30 30 28 166 27.6 30 30 29 16811746 16.5 1 19.8 33.1 35 35 30 166 34.4 35 35 32 16812846 27.8 1 33.4 50.1 60 60 46 166 51.4 60 60 47 16813346 33 1 39.7 58 60 60 53 166 59.3 60 60 55 168

460-3-60 7.2 52 11 7.8 52 12 2.9 6.7 0.5

14246 41.7 2 50.2 71.1 80 80 65 166 72.4 80 80 67 168None - - - 20.4 25 25 22 134 21.2 25 25 23 13611758 17 1 16.4 27.3 30 30 25 134 28.3 30 30 26 136

12 (10)

575-3-60 5.7 43.8 9 5.7 38.9 9 2.2 5.4 0.413458 34 1 32.7 47.6 50 50 44 134 48.6 50 50 45 136None - - - 62.4 70 80 66 410 62.4 70 80 66 41011725 12 1 33.3 62.4 70 80 66 410 62.4 70 80 66 41012525 18.6 1 51.6 81.4 90 90 75 410 81.4 90 90 75 41013225 24 1 66.6 100.1 110 110 92 410 100.1 110 110 92 410

208-3-60 18.6 149 29 19.6 136 31 5.8 13.5 0

14225 31.8 2 88.3 127.3 150 150 117 410 127.3 150 150 117 410None - - - 61.7 70 80 65 406 61.7 70 80 65 40611725 16 1 38.5 64.9 70 80 65 406 64.9 70 80 65 40612525 24.8 1 59.7 91.4 100 100 84 406 91.4 100 100 84 40613225 32 1 77 113 125 125 104 406 113 125 125 104 406

230-3-60 18.6 149 29 19.6 136 31 5.2 13.4 0

14225 42.4 2 102 144.3 150 150 133 406 144.3 150 150 133 406None - - - 29.1 30 35 31 189 29.1 30 35 31 18911746 16.5 1 19.8 33.1 35 35 30 189 33.1 35 35 30 18912846 27.8 1 33.4 50.1 60 60 46 189 50.1 60 60 46 18913346 33 1 39.7 58 60 60 53 189 58 60 60 53 189

460-3-60 9 60.9 14 8.2 66.1 13 2.9 6.7 0

14246 41.7 2 50.2 71.1 80 80 65 189 71.1 80 80 65 189None - - - 23.1 25 30 24 163 23.1 25 30 24 16311758 17 1 16.4 27.3 30 30 25 163 27.3 30 30 25 163

14(12.5)

575-3-60 7.1 56 11 6.6 55.3 10 2.2 5.4 013458 34 1 32.7 47.6 50 50 44 163 47.6 50 50 44 163

1 Minimum Circuit Ampacity.2 Dual Element, Time Delay Type.3 HACR type per NEC.4 Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field

installed electric heat kits may exceed the factory installed disconnect amperage rating.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A30

Johnson Controls Ducted Systems

Page 33: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Electrical Data ZLE08-14 High Indoor Blower - With Powered Convenience Outlet

Table 12: ZLE08-14 High Indoor Blower - With Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ect R

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCC

OD

Fan

Mot

ors

(eac

h)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e 2 / B

reak

er3 S

ize

(Am

ps)

Max

Fus

e 2 / B

reak

er3 S

ize

(Am

ps)

FLA LRA

MCA

1 w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 49.8 50 60 53 258 52 60 60 56 26311725 12 1 33.3 59.4 60 60 55 258 62.1 70 70 57 26312525 18.6 1 51.6 82.3 90 90 76 258 85 90 90 78 26313225 24 1 66.6 101 110 110 93 258 103.8 110 110 95 263

208-3-60 14 83.1 22 13.5 88 21 2.3 9.9 1.1 8.6

14225 31.8 2 88.3 128.1 150 150 118 258 130.9 150 150 120 263None - - - 49.3 50 60 53 266 51.3 60 60 55 27111725 16 1 38.5 65.3 70 70 60 266 67.8 70 70 62 27112525 24.8 1 59.7 91.8 100 100 84 266 94.3 100 100 87 27113225 32 1 77 113.4 125 125 104 266 115.9 125 125 107 271

230-3-60 14 83.1 22 13.5 88 21 2.3 9.4 1 8.6

14225 42.4 2 102 144.6 150 150 133 266 147.1 150 150 135 271None - - - 23.5 25 25 25 133 24.5 25 25 26 13511746 16.5 1 19.8 33.3 35 35 31 133 34.6 35 35 32 13512846 27.8 1 33.4 50.3 60 60 46 133 51.6 60 60 47 13513346 33 1 39.7 58.2 60 60 54 133 59.4 60 60 55 135

460-3-60 6.4 41 10 6 44 9 1.3 4.7 0.5 8.6

14246 41.7 2 50.2 71.3 80 80 66 133 72.6 80 80 67 135None - - - 18.9 20 20 20 113 19.7 20 20 21 11511758 17 1 16.4 28 30 30 26 113 29 30 30 27 115

08(7.5)

575-3-60 4.6 33 7 4.9 34 8 1.1 4.3 0.4 8.613458 34 1 32.7 48.4 50 50 45 113 49.4 50 50 45 115None - - - 50 50 60 53 253 52.2 60 60 56 25811725 12 1 33.3 59.4 60 60 55 253 62.1 70 70 57 25812525 18.6 1 51.6 82.3 90 90 76 253 85 90 90 78 25813225 24 1 66.6 101 110 110 93 253 103.8 110 110 95 258

208-3-60 14 83.1 22 13.7 83.1 21 2.3 9.9 1.1 8.6

14225 31.8 2 88.3 128.1 150 150 118 253 130.9 150 150 120 258None - - - 49.5 50 60 53 261 51.5 60 60 55 26611725 16 1 38.5 65.3 70 70 60 261 67.8 70 70 62 26612525 24.8 1 59.7 91.8 100 100 84 261 94.3 100 100 87 26613225 32 1 77 113.4 125 125 104 261 115.9 125 125 107 266

230-3-60 14 83.1 22 13.7 83.1 21 2.3 9.4 1 8.6

14225 42.4 2 102 144.6 150 150 133 261 147.1 150 150 135 266None - - - 23.7 25 30 25 130 24.7 25 30 27 13211746 16.5 1 19.8 33.3 35 35 31 130 34.6 35 35 32 13212846 27.8 1 33.4 50.3 60 60 46 130 51.6 60 60 47 13213346 33 1 39.7 58.2 60 60 54 130 59.4 60 60 55 132

460-3-60 6.4 41 10 6.2 41 10 1.3 4.7 0.5 8.6

14246 41.7 2 50.2 71.3 80 80 66 130 72.6 80 80 67 132None - - - 18.8 20 20 20 112 19.6 20 20 21 11411758 17 1 16.4 28 30 30 26 112 29 30 30 27 114

09(8.5)

575-3-60 4.6 33 7 4.8 33 8 1.1 4.3 0.4 8.613458 34 1 32.7 48.4 50 50 45 112 49.4 50 50 45 114

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 31

Johnson Controls Ducted Systems

Page 34: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 12: ZLE08-14 High Indoor Blower - With Powered Convenience Outlet

Compressor 1 Compressor 2Electric Heat Field

Installed Kit 2EK045*

4 Min

Dis

conn

ect R

atin

g4

Min

Dis

conn

ect R

atin

g4 / Pw

r Exh

Size

(Ton

s)

Nom

inal

Uni

t Vol

tage

RLA LRA MCC RLA LRA MCCO

D F

an M

otor

s (e

ach)

Supp

ly B

low

er M

otor

Pwr E

xh M

otor

Pwr C

onv

Out

let

Model kW Stages Amps1 M

CA1 (A

mps

)

2, 3 Min

Fus

e 2 / B

reak

er3 S

ize

(Am

ps)

Max

Fus

e 2 / B

reak

er3 S

ize

(Am

ps)

FLA LRA

MCA

1 w/P

wr E

xh (A

mps

)

Min

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

Max

Fus

e2 / Bre

aker

3 Siz

e w

/ Pw

r Exh

(Am

ps)

FLA LRANone - - - 60.2 70 70 65 349 62.4 70 70 67 35411725 12 1 33.3 63.9 70 70 65 349 66.6 70 70 67 35412525 18.6 1 51.6 86.8 90 90 80 349 89.5 90 90 82 35413225 24 1 66.6 105.5 110 110 97 349 108.3 110 110 100 354

208-3-60 16.5 110 26 16 110 25 5.8 13.5 1.1 8.6

14225 31.8 2 88.3 132.6 150 150 122 349 135.4 150 150 125 354None - - - 59.5 60 70 64 345 61.5 70 70 66 35011725 16 1 38.5 70.3 80 80 65 345 72.8 80 80 67 35012525 24.8 1 59.7 96.8 100 100 89 345 99.3 100 100 91 35013225 32 1 77 118.4 125 125 109 345 120.9 125 125 111 350

230-3-60 16.5 110 26 16 110 25 5.2 13.4 1 8.6

14225 42.4 2 102 149.6 150 150 138 345 152.1 175 175 140 350None - - - 28.8 30 35 31 168 29.8 30 35 32 17011746 16.5 1 19.8 35.8 40 40 33 168 37.1 40 40 34 17012846 27.8 1 33.4 52.8 60 60 49 168 54.1 60 60 50 17013346 33 1 39.7 60.7 70 70 56 168 61.9 70 70 57 170

460-3-60 7.2 52 11 7.8 52 12 2.9 6.7 0.5 8.6

14246 41.7 2 50.2 73.8 80 80 68 168 75.1 80 80 69 170None - - - 22.1 25 25 24 136 22.9 25 25 25 13811758 17 1 16.4 29.4 30 30 27 136 30.4 35 35 28 138

12 (10)

575-3-60 5.7 43.8 9 5.7 38.9 9 2.2 5.4 0.4 8.613458 34 1 32.7 49.8 50 50 46 136 50.8 60 60 47 138None - - - 66.7 70 80 71 414 66.7 70 80 71 41411725 12 1 33.3 66.7 70 80 71 414 66.7 70 80 71 41412525 18.6 1 51.6 86.8 90 90 80 414 86.8 90 90 80 41413225 24 1 66.6 105.5 110 110 97 414 105.5 110 110 97 414

208-3-60 18.6 149 29 19.6 136 31 5.8 13.5 0 8.6

14225 31.8 2 88.3 132.6 150 150 122 414 132.6 150 150 122 414None - - - 66 70 80 70 410 66 70 80 70 41011725 16 1 38.5 70.3 80 80 70 410 70.3 80 80 70 41012525 24.8 1 59.7 96.8 100 100 89 410 96.8 100 100 89 41013225 32 1 77 118.4 125 125 109 410 118.4 125 125 109 410

230-3-60 18.6 149 29 19.6 136 31 5.2 13.4 0 8.6

14225 42.4 2 102 149.6 150 150 138 410 149.6 150 150 138 410None - - - 31.3 35 40 33 191 31.3 35 40 33 19111746 16.5 1 19.8 35.8 40 40 33 191 35.8 40 40 33 19112846 27.8 1 33.4 52.8 60 60 49 191 52.8 60 60 49 19113346 33 1 39.7 60.7 70 70 56 191 60.7 70 70 56 191

460-3-60 9 60.9 14 8.2 66.1 13 2.9 6.7 0 8.6

14246 41.7 2 50.2 73.8 80 80 68 191 73.8 80 80 68 191None - - - 24.8 25 30 26 164 24.8 25 30 26 16411758 17 1 16.4 29.4 30 30 27 164 29.4 30 30 27 164

14(12.5)

575-3-60 7.1 56 11 6.6 55.3 10 2.2 5.4 0 8.613458 34 1 32.7 49.8 50 50 46 164 49.8 50 50 46 164

1 Minimum Circuit Ampacity.2 Dual Element, Time Delay Type.3 HACR type per NEC.4 Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field

installed electric heat kits may exceed the factory installed disconnect amperage rating.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A32

Johnson Controls Ducted Systems

Page 35: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Physical Data

Table 13: ZL08 Physical DataModels

ComponentZLG08 ZLE08

Nominal Tonnage 7.5 7.5Gross Capacity@ AHRI A point(Btu)

93000 93000

AHRI netcapacity (Btu)

89000 89000

EER 12 12.2SEER - -IEER IntelliSpeed 15.6 15.8VAV IEER 15.2 15.4Nominal CFM 2900 2900System power(KW)

7.40 7.40

Refrigerant type R-410A R-410ARefrigerantcharge (lb-oz)System 1 6-0 6-0

AHRI COOLINGPERFORMANCE

System 2 6-6 6-6Heating Option D E F -Heating model Low Med High -1st. Stage Heatinput (K Btu)

90 125 176 -

2nd. Stage Heatinput (K Btu)

125 180 220 -

1st. Stage Heatoutput (K Btu)

72 100 141 -

2nd. Stage Heatoutput (K Btu)

100 144 176 -

Steady stateefficiency (%)

80 80 80 -

No. burners 3 4 5 -No. stages 2 2 2 -TemperatureRise Range (ºF)

25-41 36-59 43-72 -

Gas Limit Setting(ºF)

140 150 140 -

AHRI HEATINGPERFORMANCE THREEPHASE

Gas pipingconnection (in.)

3/4 3/4 3/4 -

Length 87.2 87.2Width 61.7 61.7DIMENSIONS (inches)Height 48.6 48.6

OPERATING WT. (lbs.) 1040 920

Type 2-stage Scroll/Scroll 2-stage Scroll/ScrollQuantity 2 2

COMPRESSORSUnit CapacitySteps (%)

34 / 67 /100 34 / 67 /100

Face area (Sq.Ft.)

25.5 25.5

Rows 1 1Fins per inch 23 23Tube diameter(in./MM)

1/25 1/25

CONDENSER COIL DATA

Circuitry Type 2-pass Microchannel 2-pass Microchannel

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 33

Johnson Controls Ducted Systems

Page 36: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 14: ZL08 Physical DataModels

ComponentZLG08 ZLE08

Nominal Tonnage 7.5 7.5Face area (Sq.Ft.)

11.1 11.1

Rows 4 4Fins per inch 15 15Tube diameter 0.375 0.375Circuitry Type Intertwined Intertwined

EVAPORATOR COILDATA

Refrigerantcontrol

TXV TXV

Quantity of fans 2 2Fan diameter(Inch)

22 22

Type Prop PropDrive type Direct DirectQuantity ofmotors

2 2

Motor HP each 1/2 1/2No. speeds 1 1RPM 1085 1085

CONDENSER FAN DATA

Nominal totalCFM

8600 8600

Airflow Option A B C A B CQuantity 1 1 1 1 1 1Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15Type Centrifugal CentrifugalMotor Sheave 1VL34 1VL44 1VP50 1VL34 1VL44 1VP50Blower Sheave AK74 AK74 AK74 AK74 AK74 AK74Belt A47 A48 A50 A47 A48 A50Motor Max Bhp,3 Phase

2.4 2.4 3.7 2.4 2.4 3.7

RPM 1725 1725 1725 1725 1725 1725

EVAP FAN DATA BELTDRIVE

Frame size 56Y 56Y 56HZ 56Y 56Y 56HZFILTERS Quantity - Size 4 - (20 x 20 x 2)1 4 - (20 x 20 x 2)1

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A34

Johnson Controls Ducted Systems

Page 37: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 15: ZL09 Physical DataModels

ComponentZLG09 ZLE09

Nominal Tonnage 8.5 8.5Gross Capacity @ AHRI Apoint (Btu)

101000 101000

AHRI net capacity (Btu) 98000 98000EER 12 12.2SEER - -IEER IntelliSpeed 16.1 16.3VAV IEER 15.7 15.9Nominal CFM 3000 3000System power (KW) 8.00 8.00Refrigerant type R-410A R-410A

Refrigerant charge (lb-oz)

System 1 6-4 6-4

AHRI COOLINGPERFORMANCE

System 2 6-4 6-4Heating Option D E F -Heating model Low Med High -1st. Stage Heat input (KBtu)

90 125 176 -

2nd. Stage Heat input (KBtu)

125 180 220 -

1st. Stage Heat output (KBtu)

72 100 141 -

2nd. Stage Heat output (KBtu)

100 144 176 -

Steady state efficiency(%)

80 80 80 -

No. burners 3 4 5 -No. stages 2 2 2 -Temperature Rise Range(ºF)

22-36 31-52 38-64 -

Gas Limit Setting (ºF) 140 150 140 -

AHRI HEATINGPERFORMANCE THREEPHASE

Gas piping connection(in.)

3/4 3/4 3/4 -

Length 87.2 87.2Width 61.7 61.7DIMENSIONS (inches)Height 48.6 48.6

OPERATING WT. (lbs.) 1030 925

Type 2-stage Scroll/Scroll 2-stage Scroll/ScrollQuantity 2 2COMPRESSORSUnit Capacity Steps (%) 34 / 67 /100 34 / 67 /100Face area (Sq. Ft.) 25.5 25.5Rows 1 1Fins per inch 23 23Tube diameter (in./MM) 1/25 1/25

CONDENSER COIL DATA

Circuitry Type 2-pass Microchannel 2-pass Microchannel

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 35

Johnson Controls Ducted Systems

Page 38: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 16: ZL09 Physical DataModels

ComponentZLG09 ZLE09

Nominal Tonnage 8.5 8.5Face area (Sq. Ft.) 11.1 11.1Rows 4 4Fins per inch 15 15Tube diameter 0.375 0.375Circuitry Type Intertwined Intertwined

EVAPORATOR COIL DATA

Refrigerant control TXV TXVQuantity of fans 2 2Fan diameter (Inch) 22 22Type Prop PropDrive type Direct DirectQuantity of motors 2 2Motor HP each 1/2 1/2No. speeds 1 1RPM 1085 1085

CONDENSER FAN DATA

Nominal total CFM 8600 8600Airflow Option A B C A B CQuantity 1 1 1 1 1 1Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15Type Centrifugal CentrifugalMotor Sheave 1VL34 1VL44 1VP50 1VL34 1VL44 1VP50Blower Sheave AK74 AK74 AK74 AK74 AK74 AK74Belt A47 A48 A50 A47 A48 A50Motor Max Bhp, 3 Phase 2.4 2.4 3.7 2.4 2.4 3.7RPM 1725 1725 1725 1725 1725 1725

EVAP FAN DATA BELTDRIVE

Frame size 56Y 56Y 56HZ 56Y 56Y 56HZFILTERS Quantity - Size 4 - (20 x 20 x 2)1 4 - (20 x 20 x 2)1

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A36

Johnson Controls Ducted Systems

Page 39: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 17: ZL12 Physical DataModels

ComponentZLG12 ZLE12

Nominal Tonnage 10 10Gross Capacity @ AHRI Apoint (Btu)

120200 120200

AHRI net capacity (Btu) 116000 116000EER 12 12.2SEER - -IEER IntelliSpeed 15.4 15.6VAV IEER 15.2 15.4Nominal CFM 3100 3100System power (KW) 9.60 9.60Refrigerant type R-410A R-410A

Refrigerant charge (lb-oz)

System 1 6-0 6-0

AHRI COOLINGPERFORMANCE

System 2 6-10 6-10Heating Option D E F -Heating model Low Med High -1st. Stage Heat input (KBtu)

125 176 200 -

2nd. Stage Heat input (KBtu)

180 220 250 -

1st. Stage Heat output (KBtu)

100 141 160 -

2nd. Stage Heat output (KBtu)

144 176 200 -

Steady state efficiency(%)

80 80 80 -

No. burners 4 5 5 -No. stages 2 2 2 -Temperature Rise Range(ºF)

27-44 33-54 37-62 -

Gas Limit Setting (ºF) 150 140 160 -

AHRI HEATINGPERFORMANCE THREEPHASE

Gas piping connection(in.)

3/4 3/4 3/4 -

Length 87.2 87.2Width 61.7 61.7DIMENSIONS (inches)Height 55.3 55.3

OPERATING WT. (lbs.) 1050 955

Type 2-stage Scroll/Scroll 2-stage Scroll/ScrollQuantity 2 2COMPRESSORSUnit Capacity Steps (%) 34 / 67 /100 34 / 67 /100Face area (Sq. Ft.) 24.9 24.9Rows 1 1Fins per inch 21 21Tube diameter (in./MM) 1.26/32 1.26/32

CONDENSER COIL DATA

Circuitry Type 2-pass Microchannel 2-pass Microchannel

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 37

Johnson Controls Ducted Systems

Page 40: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 18: ZL12 Physical DataModels

ComponentZLG12 ZLE12

Nominal Tonnage 10 10Face area (Sq. Ft.) 11.1 11.1Rows 4 4Fins per inch 15 15Tube diameter 0.375 0.375Circuitry Type Intertwined Intertwined

EVAPORATOR COIL DATA

Refrigerant control TXV TXVQuantity of fans 1 1Fan diameter (Inch) 30 30Type Prop PropDrive type Direct DirectQuantity of motors 1 1Motor HP each 1 1/2 1 1/2No. speeds 1 1RPM 1140 1140

CONDENSER FAN DATA

Nominal total CFM 9700 9700Airflow Option A B C A B CQuantity 1 1 1 1 1 1Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15Type CentrifugalMotor Sheave 1VL44 1VP50 1VP56 1VL44 1VP50 1VP56Blower Sheave AK79 AK79 BK85 AK79 AK79 BK85Belt A50 A50 BX52 A50 A50 BX52Motor Max Bhp, 3 Phase 2.4 3.7 5.25 2.4 3.7 5.25RPM 1725 1725 1725 1725 1725 1725

EVAP FAN DATA BELTDRIVE

Frame size 56Y 56HZ 145TY 56Y 56HZ 145TYFILTERS Quantity - Size 4 - (20 x 20 x 2)1 4 - (20 x 20 x 2)1

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A38

Johnson Controls Ducted Systems

Page 41: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 19: ZL14 Physical DataModels

ComponentZLG14 ZLE14

Nominal Tonnage 12.5 12.5Gross Capacity @ AHRI Apoint (Btu)

139500 139500

AHRI net capacity (Btu) 135000 135000EER 11.0 11.2SEER - -IEER IntelliSpeed 14.7 14.9VAV IEER 14.5 14.7Nominal CFM 3900 3900System power (KW) 11.90 11.90Refrigerant type R-410A R-410A

Refrigerant charge (lb-oz)

System 1 6-2 6-2

AHRI COOLINGPERFORMANCE

System 2 6-8 6-8Heating Option D E F -Heating model Low Med High -1st. Stage Heat input (KBtu)

125 176 200 -

2nd. Stage Heat input (KBtu)

180 220 250 -

1st. Stage Heat output (KBtu)

100 141 160 -

2nd. Stage Heat output (KBtu)

144 176 200 -

Steady state efficiency(%)

80 80 80 -

No. burners 4 5 5 -No. stages 2 2 2 -Temperature Rise Range(ºF)

21-36 26-43 30-49 -

Gas Limit Setting (ºF) 150 140 160 -

AHRI HEATINGPERFORMANCE THREEPHASE

Gas piping connection(in.)

3/4 3/4 3/4 -

Length 87.2 87.2Width 61.7 61.7DIMENSIONS (inches)Height 55.3 55.3

OPERATING WT. (lbs.) 1070 980

Type 2-stage Scroll/Scroll 2-stage Scroll/ScrollQuantity 2 2COMPRESSORSUnit Capacity Steps (%) 34 / 67 /100 34 / 67 /100Face area (Sq. Ft.) 24.9 24.9Rows 1 1Fins per inch 21 21Tube diameter (in./MM) 1.26/32 1.26/32

CONDENSER COIL DATA

Circuitry Type 2-pass Microchannel 2-pass Microchannel

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 39

Johnson Controls Ducted Systems

Page 42: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 20: ZL14 Physical DataModels

ComponentZLG14 ZLE14

Nominal Tonnage 12.5 12.5Face area (Sq. Ft.) 11.1 11.1Rows 4 4Fins per inch 15 15Tube diameter 0.375 0.375Circuitry Type Intertwined Intertwined

EVAPORATOR COIL DATA

Refrigerant control TXV TXVQuantity of fans 1 1Fan diameter (Inch) 30 30Type Prop PropDrive type Direct DirectQuantity of motors 1 1Motor HP each 1 1/2 1 1/2No. speeds 1 1RPM 1140 1140

CONDENSER FAN DATA

Nominal total CFM 9700 9700Airflow Option A B C A B CQuantity 1 1 1 1 1 1Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15Type Centrifugal CentrifugalMotor Sheave 1VL44 1VP50 1VP56 1VL44 1VP50 1VP56Blower Sheave AK79 AK79 BK85 AK79 AK79 BK85Belt A50 A50 BX54 A50 A50 BX54Motor Max Bhp, 3 Phase 2.9 3.7 5.25 2.9 3.7 5.25RPM 1750 1750 1750 1750 1750 1750

EVAP FAN DATA BELTDRIVE

Frame size 56Y 182TZ 184TZ 56Y 182TZ 184TZFILTERS Quantity - Size 4 - (20 x 20 x 2)1 4 - (20 x 20 x 2)1

1. 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value).

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A40

Johnson Controls Ducted Systems

Page 43: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Optional Gas HeatThese gas-fired heaters have aluminized-steel oroptional stainless steel, tubular heat exchangerswith spark ignition.

Gas PipingProper sizing of gas piping depends on the cubicfeet per hour of gas flow required, specific gravityof the gas and the length of run. "National FuelGas Code" Z223.1 (in U.S.A.) or the current GasInstallation Codes CSA-B149.1 (in Canada) shouldbe followed in all cases unless superseded by localcodes or gas utility requirements. Refer to the PipeSizing Table 21. The heating value of the gas maydiffer with locality. The value should be checkedwith the local gas utility.

Figure 20: Side Entry Gas Piping

Note: Routing of gas piping must not interferewith the flue or heat compartment access.

Table 21: Gas Pipe Sizing - Capacity of PipeNominal Iron Pipe Size

Length of Pipe (ft.)3/4 in. 1 in. 1-1/4 in.

10 278 520 105020 190 350 73030 152 285 59040 130 245 50050 115 215 44060 105 195 40070 96 180 37080 90 170 35090 84 160 320

100 79 150 305

Note: Maximum capacity of pipe in cubic feetof gas per hour based upon a pressure drop of0.3 inch W.C. and 0.6 specific gravity gas.

Note: There may be a local gas utilityrequirement specifying a minimum diameterfor gas piping. Units require either a 1/2 or 3/4inch pipe connection at the entrance fitting.Line should not be sized smaller than theentrance fitting size.

Table 22: Gas Heat Supply AirSupply Air (CFM)

HeatingModel(Size)

Gas HeatDescription Opt.

Min MaxLow D 2260 3700Med E 2260 3700ZL08 (7.5)High F 2260 3790Low D 2570 4210Med E 2560 4300ZL09 (8.5)High F 2550 4290Low D 3030 4940Med E 3020 4940ZL12 (10)High F 2990 5010Low D 3700 6350Med E 3790 6270ZL14 (12.5)High F 3780 6170

Gas ConnectionThe gas supply line can be routed within the spaceand roof curb, exiting through the unit’s basepan.Refer to Figure 11 thru Figure 12 for the gas pipinginlet location. Typical supply piping arrangementsare shown in Figure 20. All pipe nipples, fittings, andthe gas cock are field supplied.Gas piping recommendations:

1. A drip leg and a ground joint union must beinstalled in the gas piping.

2. Where required by local codes, a manual shut-off valve must be installed outside of the unit.

3. Use wrought iron or steel pipe for all gas lines.Pipe dope should be applied sparingly to malethreads only. If local codes allow the use of aflexible gas appliance connector, always use anew listed connector. Do not use a connectorwhich has previously serviced another gasappliance.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 41

Johnson Controls Ducted Systems

Page 44: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

 WARNING

Natural gas may contain some propane. Propane isan excellent solvent and will quickly dissolve whitelead and most standard commercial compounds. Aspecial pipe dope must be used when assemblingwrought iron or steel pipe. Shellac based compoundssuch as Gaskolac or Stalastic, and compounds suchas Rectorseal #5, Clydes’s or John Crane may beused.

4. All piping should be cleaned of dirt and scaleby hammering on the outside of the pipe andblowing out loose particles. Before initial start-up, be sure that all gas lines external to the unithave been purged of air.

5. The gas supply should be a separate line andinstalled in accordance with all safety codes asprescribed under Limitations.

6. A 1/8-inch NPT plugged tapping, accessiblefor test gauge connection, must be installedimmediately upstream of the gas supplyconnection to the unit.

7. After the gas connections have beencompleted, open the main shut-off valveadmitting normal gas pressure to the mains.Check all joints for leaks with soap solution orother material suitable for the purpose. NEVERUSE A FLAME.

 WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warning exactly could re-sult in serious injury, death or property damage.Nevertest for gas leaks with an open flame. Use a commer-cially available soap solution made specifically for thedetection of leaks to check all connections. A fire orexplosion may result causing property damage, per-sonal injury or loss of life.

 CAUTION

The furnace and its individual shut-off valve must bedisconnected from the gas supply piping system dur-ing any pressure testing at pressures in excess of 1/2PSIG. Pressures greater than 1/2 PSIG will cause gasvalve damage resulting in a hazardous condition. If itis subjected to a pressure greater than 1/2 PSIG, thegas valve must be replaced. The furnace must be iso-lated from the gas supply piping system by closing itsindividual manual shut-off valve during any pressuretesting of the gas supply piping system at test pres-sures equal to or less than 1/2 PSIG.

 WARNING

Threaded joints should be coated with a sealing com-pound that is resistant to the action of liquefied petro-leum gases. Do not use Teflon tape.

Check all connections for leaks when piping iscompleted using a soap solution. NEVER USE AFLAME.

 WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warning exactly could re-sult in serious injury, death or property damage. Nevertest for gas leaks with an open flame. Use a commer-cially available soap solution made specifically for thedetection of leaks to check all connections. A fire orexplosion may result causing property damage, per-sonal injury or loss of life.

Combustion Air and Flue ExhaustVenting slots in the heating compartment accesspanel remove the need for a combustion air hood.The gas heat flue exhaust is routed from the unitthrough a field installed exhaust hood with screen(See Figure 21 for location of hood within theunit and Figure 22 for Installation of the hood.) Ifnecessary, a flue exhaust extension may be installedat the point of installation.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A42

Johnson Controls Ducted Systems

Page 45: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Figure 21: Flue Exhaust Hood Shipping Location

Figure 22: Flue Exhaust Hood Installed

Options/Accessories

EconomizerThe Economizer can be a factory installed optionor a field installed accessory. If factory installed,refer to the instructions included with theoutdoor air hood to complete the assembly. Fieldinstalled Economizer accessories include completeinstructions for installation.There are two Economizer options. Each is specificto footprint and unit voltage:

1. Vertical Flow application with barometric reliefstandard.

2. Horizontal Flow application with barometricrelief standard.

Power ExhaustThe Power Exhaust is a field installed accessory.Field installed Power Exhaust accessories includecomplete instructions for installation.The Power Exhaust factory installed option is forDown Flow application only.There are two field installed Power Exhaustaccessories:

1. Down Flow application.

2. Horizontal Flow application that requires thepurchase of a barometric relief hood.

Rain HoodAll of the hood components, including the misteliminators, the gasketing and the hardware forassembling, are packaged and located betweenthe condenser coil section and the main unitcabinet, if the unit has factory installed options.If field installed accessories are being installed allparts necessary for the installation comes in theaccessory.

Blower PhasingZL units are properly phased at the factory. Checkfor proper blower rotation. If the blower rotatesin the wrong direction at start-up, the electricalconnection to the unit is misphased. Change thephasing of the Field Line Connection at thefactory or field supplied disconnect to obtainproper rotation.

Blower RotationCheck for proper supply air blower rotation. If theblower is rotating backwards, the line voltage at theunit point of power connection is misphased (SeeBlower Phasing).Table 23: Supply Air Limitations

Supply Air (CFM)Model (Size)

Minimum MaximumZL08 (7.5) 2250 3750ZL09 (8.5) 2550 4250ZL12 (10) 3000 5000

ZL14 (12.5) 3750 6000

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 43

Johnson Controls Ducted Systems

Page 46: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Belt TensionThe tension on the belt should be adjusted asshown in Figure 23.

Figure 23: Belt Adjustment

 CAUTION

Procedure for adjusting best tension below:

1. Loosen the three nuts (A and B on side and Con back) of motor mount slide plate. See Figure23.

2. Adjust tension by placing a flat heat screwdriverinto the belt tightening slots (1/4 in. X 1/2 in.)in the motor mount slide plate and applyingpressure against the motor mounting plate. SeeFigure 23.

3. Tighten the three loosened nuts (A, B, and C).

4. Determine the deflection distance fromnormal position, use a straight edge fromsheave to sheave as reference line. Use belttension checker to apply a perpendicular forceto the belt at the midpoint of the span asshown. Deflection distance of 4mm (5/32 in.) isobtained

5. After adjustments are completed re-tightennuts (A, B, and C).

Altitude and Temperature Correction forCFM, Static Pressure and Power.The information below should be used to assistin application of product when being applied ataltitudes at or exceeding 1000 feet above sea level.The air flow rates listed in the standard blowerperformance tables are based on standard air at sealevel. As the altitude or temperature increases, thedensity of air decreases. In order to use the indoorblower tables for high altitude applications, certaincorrections are necessary.A centrifugal fan is a "constant volume" device. Thismeans that, if the rpm remains constant, the CFMdelivered is the same regardless of the density ofthe air. However, since the air at high altitude is lessdense, less static pressure will be generated andless power will be required than a similar applicationat sea level. Air density correction factors are shownin Table 24 and Figure 24.

Table 24: Altitude/Temperature Correction FactorsAltitude (Ft.)

AirTemp.0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000

40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.72950 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.71560 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.70170 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.68880 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.67690 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663

100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A44

Johnson Controls Ducted Systems

Page 47: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Figure 24: Altitude/Temperature Correction Factors

The examples below will assist in determining theairflow performance of the product at altitude.Example 1: What are the corrected CFM, staticpressure, and BHP at an elevation of 5,000 ft. if theairflow performance data is 3,000 CFM, 1.4 IWC and2.0 BHP?Solution: At an elevation of 5,000 ft. the indoorblower will still deliver 3,000 CFM if the rpm isunchanged. However, the Altitude correction mustbe used to determine the static pressure andBHP. Since no temperature data is given, we willassume an Air Temperature of 70°F. The Altitude/Temperature Factors show the correction factor tobe 0.832.Corrected static pressure = 1.4 x 0.832 = 1.16 IWCCorrected BHP = 2.0 x 0.832 = 1.66Example 2: A system, located at 5,000 feet ofelevation, is to deliver 3,000 CFM at a static pressureof 1.4 in. Use the unit blower tables to select theblower speed and the BHP requirement.Solution: As in the example above, no temperatureinformation is given so 70°F is assumed.The 1.4 in. static pressure given is at an elevationof 5,000 ft. The first step is to convert this staticpressure to equivalent sea level conditions.Sea level static pressure = 1.4 in. / .832 = 1.68 in.

Enter the Supply Air Blower Performance Table at3,000 CFM and static pressure of 1.68 in. The rpmlisted will be the same rpm needed at 5,000 ft.Suppose that the corresponding BHP listed inthe table is 2.0. This value must be corrected forelevation.BHP at 5,000 ft. = 2.0 x .832 = 1.66Drive Selection

1. Determine side or bottom supply ductApplication.

2. Determine desired airflow.

3. Calculate or measure the amount of externalstatic pressure.

- Add or deduct any additional staticresistance from Table 39.

4. Using the operating point determined fromsteps 1, 2, and 3, locate this point on theappropriate supply air blower performancetable. (Linear interpolation may be necessary.)

5. Noting the RPM and BHP from step 4, locate theappropriate motor and, or drive.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 45

Johnson Controls Ducted Systems

Page 48: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

6. Review the BHP compared to the motor optionsavailable. Select the appropriate motor and, ordrive.

7. Review the RPM range for the motor optionsavailable. Select the appropriate drive ifmultiple drives are available for the chosenmotor.

8. Determine turns open to obtain the desiredoperation point.

Example

1. 3400 CFM

2. 1.6 iwg

3. Using the airflow performance table below, thefollowing data point was located: 1039 RPM and2.52 BHP.

4. Using the RPM selection table below, Model ZLand Size 08 (Tons) 7.5 is found.

5. 2.59 BHP exceeds the maximum continuousBHP rating of the 1.5 HP motor. The 3 HP motoris required.

6. 1039 RPM is within the range of the 3 HP drives.

7. Using the 3 HP motor and drive, 1.5 turns openwill achieve 1039 RPM.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A46

Johnson Controls Ducted Systems

Page 49: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Airflow PerformanceTable 25: Example Supply Air Blower Performance-ZL08 (7.5 Ton) Bottom Duct

Available External Static0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0CFM

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2250 556 0.45 621 0.65 683 0.83 742 1.00 798 1.18 852 1.34 904 1.51 954 1.69 1003 1.87 1050 2.142400 567 0.53 632 0.73 694 0.91 753 1.09 809 1.26 863 1.43 914 1.60 964 1.77 1013 1.95 1060 2.142600 580 0.65 646 0.85 707 1.03 766 1.21 823 1.38 876 1.55 928 1.72 978 1.89 1027 2.07 1074 2.272800 595 0.79 660 0.99 722 1.17 780 1.35 837 1.52 890 1.69 942 1.86 992 2.03 1041 2.21 1088 2.43000 609 0.94 674 1.14 736 1.32 795 1.50 851 1.67 905 1.83 957 2.00 1007 2.18 1056 2.36 1100 2.553200 625 1.10 690 1.30 752 1.48 810 1.66 867 1.83 921 2.00 972 2.17 1022 2.34 1071 2.52 -- --3400 641 1.28 706 1.47 768 1.66 827 1.83 883 2.00 937 2.17 989 2.34 1039 2.52 1087 2.7 -- --

Standard Static Option with Motor rated at 2.4-hp

Medium Static Option with Motor rated at 2.9-hp

High Static Option with Motor rated at 3.7-hp

-- Exceeds recommended blower speed

Table 26: Example RPM Selection

Model Size (Tons)AirflowOption

Phase Max BHPBlowerSheave

MotorSheave

6 TurnsOpen

5 TurnsOpen

4 TurnsOpen

3 TurnsOpen

2 TurnsOpen

1 TurnsOpen

FullyClosed

Std. 3 2.4 AK74 1VL34 N/A 475 525 575 625 675 725Med. 3 2.4 AK74 1VL44 N/A 700 750 800 850 900 950ZL 08 (7.5)

H. Static 3 3.7 AK74 1VP50 N/A 850 900 950 1000 1050 1100

Table 27: Example Additional Static ResistanceElectric Heat kW2

Model Size (Tons) CFM1Cooling

Only12, 3Economizer2,3 4" Filters2

6/6.5 9.2/10.5/11 13.8/14/16 16/16.5/17 23 24.8/25.5/27.8 32/33/34 41.7/42.4

2200 0.04 0.11 --- --- --- --- 0.07 --- 0.09 0.10 0.122600 0.06 0.13 --- --- --- --- 0.09 --- 0.11 0.12 0.153000 0.10 0.17 --- --- --- --- 0.12 --- 0.14 0.15 0.193400 0.13 0.20 --- --- --- --- 0.15 --- 0.18 0.19 0.233800 0.16 0.25 --- --- --- --- 0.19 --- 0.22 0.23 0.274000 0.17 0.28 --- --- --- --- 0.21 --- 0.24 0.25 0.304400 0.20 0.33 --- --- --- --- 0.25 --- 0.29 0.30 0.354800 0.22 0.38 --- --- --- --- 0.30 --- 0.34 0.35 0.415200 0.24 0.43 --- --- --- --- 0.35 --- 0.39 0.41 0.475600 0.26 0.46 --- --- --- --- 0.41 --- 0.45 0.47 0.54

ZL

08 (7.5)

09 (8.5)

12 (10.0)

14 (12.5)

6000 0.28 0.50 --- --- --- --- 0.48 --- 0.52 0.54 0.60

1 Add these values to the available static resistance in the respective Blower Performance Tables.2 Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.3 The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return

air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

Table 28: RPM Selection

Model Size (Tons)AirflowOption

Phase Max BHPBlowerSheave

MotorSheave

6 TurnsOpen

5 TurnsOpen

4 TurnsOpen

3 TurnsOpen

2 TurnsOpen

1 TurnsOpen

FullyClosed

Std. 3 2.4 AK74 1VL34 N/A 475 525 575 625 675 725Med. 3 2.4 AK74 1VL44 N/A 700 750 800 850 900 950ZL 08 (7.5)

H. Static 3 3.7 AK74 1VP50 N/A 850 900 950 1000 1050 1100Std. 3 2.4 AK74 1VL34 N/A 475 525 575 625 675 725

Med. 3 2.4 AK74 1VL44 N/A 700 750 800 850 900 950ZL 09 (8.5)H. Static 3 3.7 AK74 1VP50 N/A 850 900 950 1000 1050 1100

Std. 3 2.4 AK79 1VL44 N/A 653 700 747 793 840 887Med. 3 3.7 AK79 1VP50 N/A 793 840 887 933 980 1027ZL 12 (10)

H. Static 3 5.25 BK85 1VP56 953 997 1041 1085 1130 1174 N/AStd. 3 2.9 AK79 1VL44 N/A 653 700 747 793 840 887

Med. 3 3.7 AK79 1VP50 N/A 793 840 887 933 980 1027ZL 14 (12.5)H. Static 3 5.25 BK85 1VP56 953 997 1041 1085 1130 1174 N/A

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 47

Johnson Controls Ducted Systems

Page 50: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 29: Indoor Blower SpecificationsMotor Motor Sheave Blower Sheave

Model Size (Tons)AirflowOption Phase

MAXBHP

RPM Eff. SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) ModelBelt

Std. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 7.0 1 AK74 A47Med. 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 7.0 1 AK74 A48ZL 08 (7.5)

H. Static 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 7.0 1 AK74 A50Std. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 7.0 1 AK74 A47

Med. 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 7.0 1 AK74 A48ZL 09 (8.5)H. Static 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 7.0 1 AK74 A50

Std. 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 7.5 1 AK79 A50Med. 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 7.5 1 AK79 A50ZL 12 (10)

H. Static 3 5.25 1725 0.84 1.15 145TY 4.3 - 5.3 7/8 1VP56 7.9 1 BK85 BX52Std. 3 2.9 1750 0.87 1.15 56Y 2.8 - 3.8 5/8 1VL44 7.5 1 AK79 A50

Med. 3 3.7 1750 0.90 1.15 184TZ 3.4 - 4.4 7/8 1VP50 7.5 1 AK79 A52ZL 14 (12.5)H. Static 3 5.25 1750 0.90 1.15 184TZ 4.3 - 5.3 7/8 1VP56 7.9 1 BK85 BX52

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A48

Johnson Controls Ducted Systems

Page 51: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

ZL 08-14 Side Duct Application (Belt Drive)

Table 30: ZL 08 (7.5 Ton) Side DuctAvailable External Static

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0CFMRPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2250 547 0.39 610 0.60 670 0.81 727 1.01 783 1.21 836 1.41 888 1.59 939 1.78 989 1.96 1038 2.132400 556 0.47 619 0.69 679 0.90 736 1.10 792 1.30 845 1.49 897 1.68 948 1.86 998 2.04 1047 2.222600 568 0.60 631 0.81 691 1.02 749 1.22 804 1.42 857 1.61 909 1.80 960 1.99 1010 2.17 1059 2.342800 581 0.73 644 0.95 704 1.16 762 1.36 817 1.56 871 1.75 923 1.94 973 2.13 1023 2.31 1073 2.483000 595 0.89 658 1.10 718 1.31 776 1.51 831 1.71 885 1.91 937 2.09 988 2.28 1038 2.46 1087 2.633200 610 1.05 673 1.27 733 1.48 791 1.68 846 1.88 900 2.07 952 2.26 1003 2.44 1053 2.62 -- --3400 627 1.23 689 1.45 750 1.66 807 1.86 863 2.06 916 2.25 968 2.44 1019 2.62 1069 2.80 -- --3600 644 1.42 707 1.64 767 1.85 824 2.05 880 2.25 933 2.44 985 2.63 1036 2.82 1086 3.00 -- --3750 657 1.58 720 1.79 780 2.00 838 2.20 893 2.40 947 2.60 999 2.78 1049 2.97 1099 3.15 -- --

Standard Static Option with Motor rated at 2.4-hp

Medium Static Option with Motor rated at 2.4-hp

High Static Option with Motor rated at 3.7-hp

-- Exceeds recommended blower speed

Table 31: ZL 09 (8.5 Ton) Side DuctAvailable External Static

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0CFMRPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2550 565 0.56 628 0.78 688 0.99 745 1.19 801 1.39 854 1.58 906 1.77 957 1.95 1007 2.13 1056 2.312600 568 0.60 631 0.81 691 1.02 749 1.22 804 1.42 857 1.61 909 1.80 960 1.99 1010 2.17 1059 2.342800 581 0.73 644 0.95 704 1.16 762 1.36 817 1.56 871 1.75 923 1.94 973 2.13 1023 2.31 1073 2.483000 595 0.89 658 1.10 718 1.31 776 1.51 831 1.71 885 1.91 937 2.09 988 2.28 1038 2.46 1087 2.633200 610 1.05 673 1.27 733 1.48 791 1.68 846 1.88 900 2.07 952 2.26 1003 2.44 1053 2.62 1100 2.803400 627 1.23 689 1.45 750 1.66 807 1.86 863 2.06 916 2.25 968 2.44 1019 2.62 1069 2.80 -- --3600 644 1.42 707 1.64 767 1.85 824 2.05 880 2.25 933 2.44 985 2.63 1036 2.82 1086 3.00 -- --3800 662 1.63 725 1.84 785 2.05 842 2.26 898 2.46 951 2.65 1003 2.84 1054 3.02 1100 3.20 -- --4000 681 1.85 744 2.06 804 2.27 861 2.47 917 2.67 970 2.87 1022 3.05 1073 3.24 -- -- -- --4200 701 2.08 764 2.29 824 2.50 881 2.70 937 2.90 990 3.09 1042 3.28 1093 3.47 -- -- -- --4250 706 2.14 769 2.35 829 2.56 887 2.76 942 2.96 996 3.15 1048 3.34 1098 3.53 -- -- -- --

Standard Static Option with Motor rated at 2.4-hp

Medium Static Option with Motor rated at 2.4-hp

High Static Option with Motor rated at 3.7-hp

Bold Field-supplied BK95 x 1 fixed pulley (p/n 9381) with Motor rated at 3.7-hp-- Exceeds recommended blower speed

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 49

Johnson Controls Ducted Systems

Page 52: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 32: ZL 12 (10 Ton) Side DuctAvailable External Static

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0CFMRPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3000 653 0.79 706 1.02 758 1.25 808 1.49 858 1.72 907 1.95 955 2.18 1003 2.4 1049 2.62 1095 2.823200 667 0.94 720 1.17 771 1.40 822 1.64 872 1.88 921 2.11 969 2.34 1016 2.56 1063 2.77 1109 2.973400 682 1.11 734 1.34 786 1.57 837 1.81 887 2.04 936 2.28 984 2.5 1031 2.73 1078 2.94 1124 3.143600 697 1.29 750 1.52 802 1.76 853 1.99 903 2.23 952 2.46 1000 2.69 1047 2.91 1094 3.12 1140 3.323800 714 1.50 767 1.73 819 1.96 870 2.20 920 2.43 969 2.67 1017 2.90 1064 3.12 1111 3.33 1157 3.534000 733 1.73 786 1.96 837 2.19 888 2.43 938 2.66 987 2.90 1035 3.12 1083 3.34 1129 3.56 1174 3.764200 753 1.98 806 2.21 857 2.44 908 2.68 958 2.91 1007 3.15 1055 3.37 1102 3.6 1149 3.81 -- --4400 774 2.25 827 2.48 879 2.72 930 2.95 979 3.19 1028 3.42 1076 3.65 1124 3.87 1170 4.08 -- --4600 797 2.55 850 2.78 902 3.02 952 3.25 1002 3.49 1051 3.72 1099 3.95 1147 4.17 -- -- -- --4800 822 2.88 874 3.11 926 3.34 977 3.58 1027 3.81 1076 4.05 1124 4.27 1171 4.50 -- -- -- --5000 848 3.23 901 3.46 952 3.69 1003 3.93 1053 4.16 1102 4.4 1150 4.62 -- -- -- -- -- --

Standard Static Option with Motor rated at 2.4-hp

Medium Static Option with Motor rated at 2.9-hp

High Static Option with Motor rated at 3.7-hp

-- Exceeds recommended blower speed

Table 33: ZL14 (12.5 Ton) Side DuctAvailable External Static

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0CFMRPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3750 684 1.33 741 1.56 792 1.81 840 2.07 884 2.33 927 2.60 971 2.85 1017 3.09 1066 3.30 1121 3.493800 688 1.38 745 1.61 797 1.85 844 2.12 888 2.38 932 2.65 976 2.90 1021 3.14 1071 3.35 1125 3.544000 706 1.58 763 1.81 814 2.06 861 2.32 906 2.59 949 2.85 993 3.11 1039 3.35 1088 3.56 1142 3.744200 724 1.81 781 2.04 832 2.29 879 2.55 924 2.82 967 3.08 1011 3.34 1057 3.57 1106 3.79 1160 3.974400 742 2.06 799 2.29 850 2.54 897 2.80 942 3.06 985 3.33 1029 3.58 1075 3.82 1124 4.03 1178 4.224600 760 2.32 817 2.55 869 2.80 916 3.06 960 3.33 1004 3.59 1048 3.85 1093 4.08 1143 4.30 -- --4800 779 2.60 836 2.83 888 3.08 935 3.34 979 3.61 1023 3.88 1067 4.13 1112 4.37 1162 4.58 -- --5000 799 2.91 856 3.14 907 3.39 954 3.65 999 3.91 1042 4.18 1086 4.43 1132 4.67 -- -- -- --5200 819 3.23 876 3.46 927 3.71 974 3.97 1019 4.23 1062 4.50 1106 4.75 1152 4.99 -- -- -- --5400 839 3.57 896 3.80 953 4.04 995 4.31 1039 4.57 1083 4.84 1127 5.09 -- -- -- -- -- --5600 860 3.92 917 4.15 969 4.40 1016 4.66 1060 4.93 1104 5.19 -- -- -- -- -- -- -- --5800 882 4.30 939 4.53 990 4.77 1037 5.04 -- -- -- -- -- -- -- -- -- -- -- --6000 904 4.69 961 4.92 1012 5.17 -- -- -- -- -- -- -- -- -- -- -- -- -- --

Standard Static Option with Motor rated at 2.9-hp

Medium Static Option with Motor rated at 3.7-hp

High Static Option with Motor rated at 5.25-hp

-- Exceeds recommended Blower speed

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A50

Johnson Controls Ducted Systems

Page 53: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

ZL 08-14 Bottom Duct Application (Belt Drive)Table 34: ZL08 (7.5 Ton) Bottom Duct

Available External Static0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0CFM

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP2250 556 0.45 621 0.65 683 0.83 742 1.00 798 1.18 852 1.34 904 1.51 954 1.69 1003 1.87 1050 2.062400 567 0.53 632 0.73 694 0.91 753 1.09 809 1.26 863 1.43 914 1.60 964 1.77 1013 1.95 1060 2.142600 580 0.65 646 0.85 707 1.03 766 1.21 823 1.38 876 1.55 928 1.72 978 1.89 1027 2.07 1074 2.272800 595 0.79 660 0.99 722 1.17 780 1.35 837 1.52 890 1.69 942 1.86 992 2.03 1041 2.21 1088 2.403000 609 0.94 674 1.14 736 1.32 795 1.50 851 1.67 905 1.83 957 2.00 1007 2.18 1056 2.36 1100 2.553200 625 1.10 690 1.30 752 1.48 810 1.66 867 1.83 921 2.00 972 2.17 1022 2.34 1071 2.52 -- --3400 641 1.28 706 1.47 768 1.66 827 1.83 883 2.00 937 2.17 989 2.34 1039 2.52 1087 2.70 -- --3600 658 1.47 723 1.66 785 1.85 844 2.02 900 2.19 954 2.36 1006 2.53 1056 2.70 1100 2.89 -- --3750 672 1.61 737 1.81 799 1.99 858 2.17 914 2.34 968 2.51 1019 2.68 1069 2.85 -- -- -- --

Standard Static Option with Motor rated at 2.4-hp

Medium Static Option with Motor rated at 2.9-hp

High Static Option with Motor rated at 3.7-hp

-- Exceeds recommended Blower speed

Table 35: ZL09 (8.5 Ton) Bottom DuctAvailable External Static

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0CFMRPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2550 577 0.62 642 0.82 704 1.00 763 1.18 819 1.35 873 1.52 925 1.69 975 1.86 1023 2.04 1071 2.232600 580 0.65 646 0.85 707 1.03 766 1.21 823 1.38 876 1.55 928 1.72 978 1.89 1027 2.07 1074 2.272800 595 0.79 660 0.99 722 1.17 780 1.35 837 1.52 890 1.69 942 1.86 992 2.03 1041 2.21 1088 2.403000 609 0.94 674 1.14 736 1.32 795 1.50 851 1.67 905 1.83 957 2.00 1007 2.18 1056 2.36 1103 2.553200 625 1.10 690 1.30 752 1.48 810 1.66 867 1.83 921 2.00 972 2.17 1022 2.34 1071 2.52 -- --3400 641 1.28 706 1.47 768 1.66 827 1.83 883 2.00 937 2.17 989 2.34 1039 2.52 1087 2.70 -- --3600 658 1.47 723 1.66 785 1.85 844 2.02 900 2.19 954 2.36 1006 2.53 1056 2.7 1104 2.89 -- --3800 676 1.67 742 1.86 803 2.04 862 2.22 918 2.39 972 2.56 1024 2.73 1074 2.90 -- -- -- --4000 696 1.88 761 2.07 823 2.26 882 2.43 938 2.6 992 2.77 1043 2.94 1093 3.12 -- -- -- --4200 716 2.1 781 2.29 843 2.48 902 2.65 958 2.82 1012 2.99 1064 3.16 1114 3.34 -- -- -- --4250 721 2.16 786 2.35 848 2.53 907 2.71 963 2.88 1017 3.05 1069 3.22 1119 3.39 -- -- -- --

Standard Static Option with Motor rated at 2.4-hp

Medium Static Option with Motor rated at 2.9-hp

High Static Option with Motor rated at 3.7-hp

Bold Field-supplied BK95 x 1 fixed pulley (p/n 9381) with Motor rated at 3.7-hp-- Exceeds recommended Blower speed

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 51

Johnson Controls Ducted Systems

Page 54: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 36: ZL12 (10 Ton) Bottom DuctAvailable External Static

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0CFMRPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

2600 626 0.5 679 0.73 731 0.97 782 1.20 831 1.44 880 1.67 928 1.9 976 2.12 1022 2.33 1068 2.532800 639 0.64 692 0.87 744 1.11 795 1.34 845 1.58 894 1.81 942 2.04 989 2.26 1036 2.47 1082 2.673000 653 0.79 706 1.02 758 1.25 808 1.49 858 1.72 907 1.95 955 2.18 1003 2.40 1049 2.62 1095 2.823200 667 0.94 720 1.17 771 1.40 822 1.64 872 1.88 921 2.11 969 2.34 1016 2.56 1063 2.77 1109 2.973400 682 1.11 734 1.34 786 1.57 837 1.81 887 2.04 936 2.28 984 2.50 1031 2.73 1078 2.94 1124 3.143600 697 1.29 750 1.52 802 1.76 853 1.99 903 2.23 952 2.46 1000 2.69 1047 2.91 1094 3.12 1140 3.323800 714 1.5 767 1.73 819 1.96 870 2.20 920 2.43 969 2.67 1017 2.90 1064 3.12 1111 3.33 1157 3.534000 733 1.73 786 1.96 837 2.19 888 2.43 938 2.66 987 2.90 1035 3.12 1083 3.34 1129 3.56 1175 3.764200 753 1.98 806 2.21 857 2.44 908 2.68 958 2.91 1007 3.15 1055 3.37 1102 3.6 1149 3.81 1195 4.014400 774 2.25 827 2.48 879 2.72 930 2.95 979 3.19 1028 3.42 1076 3.65 1124 3.87 1170 4.08 1216 4.284600 797 2.55 850 2.78 902 3.02 952 3.25 1002 3.49 1051 3.72 1099 3.95 1147 4.17 1193 4.38 1239 4.584800 822 2.88 874 3.11 926 3.34 977 3.58 1027 3.81 1076 4.05 1124 4.27 1171 4.5 1218 4.71 -- --5000 848 3.23 901 3.46 952 3.69 1003 3.93 1053 4.16 1102 4.40 1150 4.62 1197 4.84 1242 5.06 -- --

Standard Static Option with Motor rated at 2.4-hp

Medium Static Option with Motor rated at 3.7-hp

High Static Option with Motor rated at 5.25-hp

-- Exceeds recommended Blower speed

Table 37: ZL14 (12.5 Ton) Bottom DuctAvailable External Static

0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0CFMRPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

3750 715 1.46 762 1.68 810 1.91 858 2.13 907 2.36 957 2.58 1008 2.80 1060 3.02 1113 3.24 1167 3.463800 720 1.51 766 1.73 814 1.96 862 2.18 911 2.41 961 2.63 1012 2.85 1064 3.07 1117 3.29 1171 3.514000 737 1.72 784 1.94 832 2.17 880 2.39 929 2.62 979 2.84 1030 3.07 1082 3.29 1135 3.51 -- --4200 756 1.95 803 2.17 851 2.40 899 2.63 948 2.85 998 3.07 1049 3.30 1101 3.52 1154 3.74 -- --4400 777 2.20 824 2.42 871 2.65 920 2.87 969 3.10 1019 3.32 1069 3.55 1121 3.77 1174 3.98 -- --4600 799 2.47 846 2.69 893 2.92 941 3.14 990 3.37 1040 3.59 1091 3.81 1143 4.04 -- -- -- --4800 822 2.75 869 2.98 916 3.20 965 3.43 1014 3.65 1064 3.88 1114 4.10 1166 4.32 -- -- -- --5000 846 3.06 893 3.28 941 3.51 989 3.73 1038 3.96 1088 4.18 1139 4.41 -- -- -- -- -- --5200 872 3.39 919 3.61 966 3.83 1015 4.06 1064 4.28 1114 4.51 1164 4.73 -- -- -- -- -- --5400 899 3.73 946 3.95 993 4.18 1042 4.40 1091 4.63 1141 4.85 -- -- -- -- -- -- -- --5600 927 4.09 974 4.32 1021 4.54 1070 4.77 1119 4.99 1169 5.22 -- -- -- -- -- -- -- --5800 956 4.47 1003 4.70 1051 4.92 1099 5.15 -- -- -- -- -- -- -- -- -- -- -- --6000 987 4.87 1034 5.10 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --

Standard Static Option with Motor rated at 2.4-hp

Medium Static Option with Motor rated at 3.7-hp

High Static Option with Motor rated at 5.25-hp

-- Exceeds recommended Blower speed

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A52

Johnson Controls Ducted Systems

Page 55: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Supply Air Drive Adjustment

 CAUTION

Before making any blower speed changes reviewthe installation for any installation errors, leaks orundesirable systems effects that can result in lossof airflow.Even small changes in blower speed canresult in substantial changes in static pressure andBHP. BHP and AMP draw of the blower motor will in-crease by the cube of the blower speed. Static pres-sure will increase by the square of the blower speed.Only qualified personnel should make blower speedchanges, strictly adhering to the fan laws.

At unit start-up, the measured CFM may be higheror lower than the required CFM. To achieve therequired CFM, the speed of the drive may haveadjusted by changing the datum diameter (DD) ofthe variable pitch motor sheave as described below:

Use the following tables and the DD calculated perthe above equation to adjust the motor variablepitch sheave.EXAMPLE NEW DATUM DIAMETERA 4 ton unit was selected to deliver 1,600 CFM with a1VL34 motor sheave, but the unit is delivering 1,350CFM. The variable pitch motor sheave is set at 4turns open.Use the equation to determine the required DD forthe new motor sheave,

Use Table 38 to locate the DD nearest to 2.48 in.Close the sheave to 2 turn open.

EXAMPLE NEW BHP

= (Speed increase)3 • Original BHP = New BHP

= (Speed increase)3 • BHP at 1,350 CFMEXAMPLE NEW MOTOR AMPS

= (Speed increase)3 • Original Amps = New Amps

= (Speed increase)3 • Amps at 1,350 CFMTable 38: Motor Sheave Datum Diameters

1VL34 1VL44 1VP50 1VP56TurnsOpen

DatumDiameter

TurnsOpen

DatumDiameter

TurnsOpen

DatumDiameter

TurnsOpen

DatumDiameter

0 2.9 0 3.8 0 4.4 0 -1/2 2.8 1/2 3.7 1/2 4.3 1/2 -1 2.7 1 3.6 1 4.2 1 5.3

1-1/2 2.6 1-1/2 3.5 1-1/2 4.1 1-1/2 5.22 2.5 2 3.4 2 4.0 2 5.1

2-1/2 2.4 2-1/2 3.3 2-1/2 3.9 2-1/2 5.03 2.3 3 3.2 3 3.8 3 4.9

3-1/2 2.2 3-1/2 3.1 3-1/2 3.7 3-1/2 4.84 2.1 4 3.0 4 3.6 4 4.7

4-1/2 2.0 4-1/2 2.9 4-1/2 3.5 4-1/2 4.65 1.9 5 2.8 5 3.4 5 4.5

5-1/2 - 5-1/2 - 5-1/2 - 5-1/2 4.46 - 6 - 6 - 6 4.3

 CAUTION

Belt drive blower systems MUST be adjusted to thespecific static and CFM requirements for the applica-tion. The Belt drive blowers are NOT set at the facto-ry for any specific static or CFM. Adjustments of theblower speed and belt tension are REQUIRED. Veri-fy proper sheave alignment; tighten blower pulley andmotor sheave set screws after these adjustments. Re-checking set screws and belt tension after 10-12 hrs.run time is recommended.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 53

Johnson Controls Ducted Systems

Page 56: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 39: Additional Static ResistanceElectric Heat kW2

Model Size (Tons) CFM1Cooling

Only12, 3Economizer 2,3 4 in. Filters2

6/6.5 9.2/10.5/11 13.8/14/16 16/16.5/17 23 24.8/25.5/27.8 32/33/34 41.7/42.42200 0.04 0.11 --- --- --- --- 0.07 --- 0.09 0.10 0.122600 0.06 0.13 --- --- --- --- 0.09 --- 0.11 0.12 0.153000 0.10 0.17 --- --- --- --- 0.12 --- 0.14 0.15 0.193400 0.13 0.20 --- --- --- --- 0.15 --- 0.18 0.19 0.233800 0.16 0.25 --- --- --- --- 0.19 --- 0.22 0.23 0.274000 0.17 0.28 --- --- --- --- 0.21 --- 0.24 0.25 0.304400 0.20 0.33 --- --- --- --- 0.25 --- 0.29 0.30 0.354800 0.22 0.38 --- --- --- --- 0.30 --- 0.34 0.35 0.415200 0.24 0.43 --- --- --- --- 0.35 --- 0.39 0.41 0.475600 0.26 0.46 --- --- --- --- 0.41 --- 0.45 0.47 0.54

ZL

08 (7.5),

09 (8.5),

12 (10.0),

14 (12.5)

6000 0.28 0.50 --- --- --- --- 0.48 --- 0.52 0.54 0.60

1 Add these values to the available static resistance in the respective Blower Performance Tables.2 Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.3 The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return

air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

Figure 25: Unit Control Board

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A54

Johnson Controls Ducted Systems

Page 57: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 40: Smart Equipment™ UCB Details(Continued)Description Function & CommentsTerminal Directional orientation: viewed with silkscreen labels uprightLimit, 24 VAC power and shutdown connections from unit wiring harness at lefton upper edge of UCB

LIMITMonitored 24 VAC inputthrough heat section limitswitch(es)

If voltage is absent, indicating theheat section is over-temperature, theUCB will bring on the indoor blower

C24 VAC, 75 VA transformerCommon referenced tocabinet ground

Connects through circuit traces tothermostat connection strip C andindoor blower VFD pin C

24V24 VAC, 75 VA transformerhot

Powers the UCB microprocessor,connects through circuit trace to theSD 24 terminal

SD 24

24 VAC hot out for factoryaccessory smoke detector,condensate overflow and/or user shutdown relayswitching in series

Connects through circuit trace tothermostat connection strip SD-24.A wiring harness jumper plugconnecting SD 24 to SD R is in place iffactory accessories for unit shutdownare not used - this jumper plugmust be removed if the switching offield-added external accessories forunit shutdown are wired betweenthermostat connection strip SD-24and R

SD R

24 VAC hot return fromfactory accessory smokedetector, condensateoverflow and user shutdownrelay switching in series

Connects through circuit trace to theR terminal on the upper left of theboard

R24 VAC hot for switchedinputs to the UCB

Connects through circuit trace tothe thermostat connection strip Rterminal, right FAN OVR pin, rightHPS1 pin, right HPS2 pin, lower DFSpin and lower APS pin

Terminal Thermostat connection strip on left edge of UCB

W11st stage heating request, 24VAC input switched from R

Not effective for cooling-only units

W22nd stage heating request, 24VAC input switched from R

Not effective for cooling-only units orunits with single-stage heat sections

Y11st stage cooling request, 24VAC input switched from R

Y22nd stage cooling request, 24VAC input switched from R

Visible in the display menu when the#ClgStgs parameter is set for 2 ormore, also effective for economizerfree cooling supply air temperaturereset when the #ClgStgs parameter isset for 1 or more

GContinuous indoor blowerrequest, 24 VAC inputswitched from R

OCCOccupancy request, 24 VACinput switched from R

Must have the OccMode parameterset for External to be effective

XHard lockout indicator,24 volt output to a lightthermostat LED

R24 VAC hot for thermostatswitching and power

If field-added external accessoriesfor unit shutdown are used, 24 VAChot return from smoke detector,condensate overflow and/or usershutdown relay switching in series

SD-24

If field-added externalaccessories for unitshutdown are used, 24 VAChot out for smoke detector,condensate over- flow and/or user shutdown relayswitching in series

Unit wiring harness jumper plugfor factory shutdown accessoriesmust be removed if the switching offield-added external accessories forunit shutdown are wired betweenthermo- stat connection strip SD-24and R

Table 40: Smart Equipment™ UCB Details(Continued)Description Function & Comments

C24 VAC common forthermostat power

LEDs on left edge of UCB

POWER Green UCB power indicatorLit indicates 24 VAC is present at Cand 24V terminals

FAULTRed hard lockout, networkingerror and firmware errorindicator

1/2 second on/off flashing indicatesone or more alarm is currentlyactive, 1/10th second on/off flashingindicates a networking error(polarity, addressing, etc.) or afirmware error (likely correctablewith re-loading from USB flash drive)

SA BUSGreen UCB SA buscommunication transmissionindicator

Lit/flickering indicates UCB SA buscommunication is currently active, offindicates the UCB is awaiting SA buscommunication

Terminal Space temperature sensor connections at center on upper edge of UCB

ST

Space Temperaturesensor input from 10KΩ@ 77°F, Type III negativetemperature coefficientthermistor

Positive of VDC circuit (3.625 VDCreading to COM with open circuit),effective if “Thermo- stat-onlyControl” parameter is set OFF, spacesensor override momentary shortsST to COM to initiate/terminatetemporary occupancy

COMCommon for ST and SSOinputs

Negative of VDC circuit for ST andSSO inputs

SSOSpace Sensor Offsetinput from 0 to 20KΩpotentiometer

Positive of VDC circuit (3.625 VDCreading to COM with open circuit),10KΩ/2.5 VDC is 0°F offset, 0Ω/0VDC is maximum above offset and20KΩ/3.4 VDC is maximum belowoffset from active space temperaturesetpoint

Pin Temperature sensor connections at right on upper edge of UCB

SAT+

Supply Air Temperaturesensor input from 10KΩ@ 77°F, Type III negativetemperature coefficientthermistor

Input required for operation; 3.625VDC reading SAT+ to SAT– with opencircuit. Used in heat/cool stagingcutouts, free cooling operation,demand ventilation operation,comfort ventilation operation,economizer loading operation, VAVcooling operation, hydronic heatoperation.

RAT+

Return Air Temperaturesensor input from 10KΩ@ 77°F, Type III negativetemperature coefficientthermistor

Input required for operation; 3.625VDC reading RAT+ to RAT– with opencircuit. Used in return air enthalpycalculation. Substitutes for spacetemperature if no other spacetemperature input is present.

OAT+

Outside Air Temperaturesensor input from 10KΩ@ 77°F, Type III negativetemperature coefficientthermistor

Input required for operation but maybe a communicated value; 3.625 VDCreading OAT+ to OAT– with opencircuit. Used in heat/cool cutouts,low ambient cooling determination,dry bulb free cooling changeover,outside air enthalpy calculation,economizer loading operation, heatpump demand defrost calculation.

CC1+

#1 refrigerant circuitCondenser Coil temperaturesensor input from 10KΩ@ 77°F, Type III negativetemperature coefficientthermistor

Input required for heat pump units,not required for A/C units; 3.625VDC reading CC1+ to CC1– with opencircuit. Used in heat pump demanddefrost calculation.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 55

Johnson Controls Ducted Systems

Page 58: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 40: Smart Equipment™ UCB Details(Continued)Description Function & Comments

EC1+

#1 refrigerant circuitEvaporator Coil temperaturesensor input from 10KΩ@ 77°F, Type III negativetemperature coefficientthermistor

Input required for operation; 3.625VDC reading EC1+ to EC1– withopen circuit. Used in suction linetemperature safety.

CC2+

#2 refrigerant circuitCondenser Coil temperaturesensor input from 10KΩ@ 77°F, Type III negativetemperature coefficientthermistor

Input required for 2-compressorheat pump units, not required for2-compressor A/C units, not activefor 1-compressor units; 3.625 VDCreading CC2+ to CC2– with opencircuit. Used in heat pump demanddefrost calculation.

EC2+

#2 refrigerant circuitEvaporator Coil temperaturesensor input from 10KΩ@ 77°F, Type III negativetemperature coefficientthermistor

Input required for operation of 2-compressor units, not active for 1-compressor units; 3.625 VDC readingEC2+ to EC2– with open circuit. Usedin suction line temperature safety.

Pinned connections on right edge of UCB

RAH+Return Air Humidity inputfrom 0-10 VDC @ 0-100% RHsensor

Input required for reheat units,optional in all other units, maybe a communicated value. Usedin return air enthalpy calculation,temperature/humidity setpoint reset,reheat operation.

DCT PRS+Supply Duct Pressure inputfrom 0-5 VDC @ 0-5” w.c.sensor

Input required for variable air volumeunits. Used in VAV indoor bloweroperation.

DFS (upper pin)24 VAC hot return from DirtyFilter Switch

Optional input; switch closure forgreater than 15 seconds duringindoor blower operation initiates anotification alarm

DFS (lower pin)24 VAC hot out for Dirty FilterSwitch

Connects through circuit trace to theR terminal

APS (upper pin)24 VAC hot return from AirProving Switch

When this optional input is enabled:the air proving switch must closewithin 30 seconds of initiation ofindoor blower operation and notopen for greater than 10 secondsduring in- door blower operationto allow heat/cool operation andprevent an “APS open” alarm; theair proving switch must open within30 seconds of termination of indoorblower operation to prevent an “APSstuck closed” notification alarm

APS (lower pin)24 VAC hot out for AirProving Switch

Connects through circuit trace to theR terminal

C Common for the VFD outputNegative of the VDC circuit for theVFD output

VFD2-10 VDC (0-100%) output forthe indoor blower VariableFrequency Drive

Output is active with indoor bloweroperation. For CV units: this outputprovides stepped IntelliSpeed controlof the indoor blower VFD based onfan-only, cooling stage and heatingstage outputs. For VAV units: thisoutput provides control of the indoorblower VFD based on supply ductstatic pressure input and setpoint.

VFDFLT24 VAC hot input from thenormally open VFD alarmcontact

The VFD alarm contact switches fromR within the unit wiring harness. 24VAC input results in unit shutdownand a “VFD fault” alarm

Terminal at lower right corner of UCB

Table 40: Smart Equipment™ UCB Details(Continued)Description Function & Comments

24V FOROUTPUTS

24 VAC hot for H1, H2, CN-FAN, AUX HGR, FAN C1 andC2 output relay contactswitching

Output relay circuitry is isolatedfrom other UCB components andthe 24 VAC hot source may be from asecond transformer in the unit

Pin Heat section connections at right on lower edge of UCB

H124 VAC hot output for heatsection stage 1

Not effective for cooling-only units.Output if demand is present andpermissions allow one stage or twostages of heat section operation

H224 VAC hot output for heatsection stage 2

Not effective for cooling-only units orunits with single-stage heat sections.Output if demand is present andpermissions allow two stages of heatsection operation

MV24 VAC hot input confirmingheat section operation

Sourced from gas valve in gas heatunits or first stage heat contactorin electric heat units. Input within 5minutes from initiation of H1 outputinitiates the “Heat On Fan Delay”timer, loss of input following thetermination of H1 output initiatesthe “Heat On Fan Delay” timer, noinput within 5 minutes from initiationof H1 output initiates an “IgnitionFailure” alarm, input for longer than5 minutes without H1 output initiatesa “Gas Valve Mis-wire” alarm

Pin Cooling and fan output connections at right on lower edge of UCB

CN-FAN24 VAC hot output for thecondenser fan contactor coil

Output with either C1 or C2 output;interrupted during defrost cycle forheat pump units

AUX HGR24 VAC hot output for hot gasreheat components

Effective only for reheat units, outputwith reheat operation

FAN24 VAC hot output for indoorblower contactor coil/indoorblower VFD enable relay coil

Output with heat/cool operation, Ginput or schedule demand

C124 VAC hot output forcompressor 1

If demand is present andpermissions allow compressor 1operation; output with compressorcooling, comfort ventilation cooling,reheat or heat pump heatingdemands

C224 VAC hot output forcompressor 2

Not effective for one stagecompressor UCBs. If demand ispresent and permissions allowcompressor 2 operation; outputwith compressor cooling, comfortventilation cooling or heat pumpheating demands

Pin Refrigerant circuit safety switch and indoor blower overload connections atcenter on lower edge of UCB

HPS1(right pin)24 VAC hot out for refrigerantcircuit 1 High Pressure Switch

Connects through circuit trace to theR terminal

HPS1(left pin)24 VAC hot return fromrefrigerant circuit 1 HighPressure Switch

Input is only considered if C1 outputis needed; input must be present toallow C1 output. Three HPS1 tripsin a two hour period cause a “HighPressure Switch 1 Lockout” and C1output is then prevented until alarmreset. Connects through circuit traceto the right LPS1 pin.

LPS1(right pin)24 VAC hot out for refrigerantcircuit 1 Low Pressure Switch

Connects through circuit trace to theleft HSP1 pin

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A56

Johnson Controls Ducted Systems

Page 59: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 40: Smart Equipment™ UCB Details(Continued)Description Function & Comments

LPS1(left pin)24 VAC hot return fromrefrigerant circuit 1 LowPressure Switch

Input is only considered after 30seconds of C1 output; afterwards,input must be present to allow C1output. Three LPS1 trips in a onehour period cause a “Low PressureSwitch 1 Lockout” and C1 output isthen prevented until alarm reset.

HPS2(right pin)24 VAC hot out for refrigerantcircuit 2 High Pressure Switch

Not effective for one stagecompressor UCBs. Connects throughcircuit trace to the R terminal

HPS2(left pin)24 VAC hot return fromrefrigerant circuit 2 HighPressure Switch

Not effective for one stagecompressor UCBs. Input is onlyconsidered if C2 output is needed;input must be present to allow C1output. Three HPS2 trips in a twohour period cause a “High PressureSwitch 1 Lockout” and C2 output isthen prevented until alarm reset.Connects through circuit trace to theright LPS2 pin.

LPS2(right pin)24 VAC hot out for refrigerantcircuit 2 Low Pressure Switch

Not effective for one stagecompressor UCBs. Connects throughcircuit trace to the left HSP2 pin

LPS2(left pin)24 VAC hot return fromrefrigerant circuit 2 LowPressure Switch

Not effective for one stagecompressor UCBs. Input is onlyconsidered after 30 seconds of C2output; afterwards, input must bepresent to allow C2 output. ThreeLPS2 trips in a one hour period causea “Low Pressure Switch 2 Lockout”and C2 output is then prevented untilalarm reset.

FAN OVR(rightpin)

24 VAC hot out for indoorblower FAN Overload relaycontact/motor protectorswitch

Connects through circuit trace to theR terminal

FAN OVR(leftpin)

24 VAC hot return fromindoor blower FAN Overloadrelay contact/motorprotector switch

Input is only considered if FANoutput is needed; input must bepresent to allow FAN output and unitoperation. One FAN OVR trip lastinglonger than 5 minutes or three FANOVR trips in a two hour period causea “Fan Overload Lockout” and unitoperation is then prevented untilalarm reset.

1Terminal SA BUS1connections on at left on lower edge and center of UCB

PWRPower for SA (“Sensor-Actuator”) BUS devices

Also incorporated in the J8 6-pinphone jack connector at the left-center of the board. Positive of the15 VDC (reading to C) circuit forpowering an optional netstat and/orMulti Touch gateway

CCommon for SA BUS powerand communication circuits

Also incorporated in the J8 6-pinphone jack connector at the left-center of the board. Negative of theSA BUS circuits

–Communication for SA BUSdevices

Also incorporated in the J8 6-pinphone jack connector at the left-center of the board. Positive of theVDC (typically, a fluctuating 1.5 to 3.5volts reading to C; at least 0.25 voltslower than +) SA BUS communicationcircuit to optional economizer board,4-stage board, fault detection &diagnostics board, netstat and/orMulti Touch gateway

Table 40: Smart Equipment™ UCB Details(Continued)Description Function & Comments

+Communication for SA BUSdevices

Also incorporated in the J8 6-pinphone jack connector at the left-center of the board. Positive ofthe VDC (typically, a fluctuating 1.5to 3.5 volts reading to C; at least0.25 volts higher than –) SA BUScommunication circuit to optionaleconomizer board, 4-stage board,fault detection & diagnostics board,netstat and/or Multi Touch gateway

J8 6-pin phone jack connector

Incorporates the SA BUS terminalsfor convenience/alternate connectionof SA BUS devices, primarily used fortemporary service connection of theMulti Touch gateway

Item Integrated user interface at lower left corner of UCB

DisplayOn-board, 2-line x 8-character back-lit display

On-board display, buttons andjoystick allow access to UCB,economizer, 4-stage and FDD boardparameters

ENTERButton for display menuacknowledgment andnavigation

CANCEL

Button for display menunavigation and zeroing ofactive compressor ASCDtimer

JOY4-way Joystick for displaymenu navigation

Item USB connector at right of UCB

J10Type A female UniversalSerial Bus connector

Used for backup, restoration, &copying of board parameters as wellas board software updating througha flash drive

J15Factory wired SA Busconnector

Optional communication sub-board at center of UCB

Terminal FC BUS1connections on left edge of the communication board

FC+FC (“Field Connected”) BUSBACnet MSTP communication

Positive of the VDC (typically, afluctuating 1.5 to 3.5 volts readingto COM; at least 0.25 volts higherthan –) FC bus BACnet MSTPcommunication circuit

FC–FC (“Field Connected”) BUSBACnet MSTP communication

Positive of the VDC (typically, afluctuating 1.5 to 3.5 volts reading toCOM; at least 0.25 volts lower than +)FC bus BACnet MSTP communicationcircuit

COMCommon for the FC (“FieldConnected”) BUS BACnetMSTP communication circuit

Negative of the VDC FC bus BACnetMSTP communication circuit

SHLDShield for the FC (“FieldConnected”) BUS BACnetMSTP communication circuit

Earth ground reference of the cableto prevent interference on the FC busBACnet MSTP communication circuit

Item Selector in red housing at left on top edge of the communication board

EOLswitchEnd Of Line selector switchfor the FC BUS BACnet MSTPcommunication circuit

ON selected only for the UCB that isthe terminus of the FC bus BACnetMSTP communication cable toprevent signal “bounce-back”

LEDs on the communication board

EOL Green End Of Line indicatorLit indicates the EOL switch isselected ON

FC BUSGreen FC bus communicationtransmission indicator

Lit/flickering indicates outgoingUCB FC bus communication iscurrently active, off indicates theUCB is awaiting incoming FC buscommunication

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 57

Johnson Controls Ducted Systems

Page 60: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 40: Smart Equipment™ UCB Details(Continued)Description Function & Comments

ISO PWRGreen communication boardIsolated Power indicator

Lit indicates the UCB is supplyingpower to the communication sub-board

1 When wiring unit and other devices using the SA Bus and FCBus, see Table 41.

Table 41: Cable for FC Buses and SA Buses inOrder of Preference

Non-PlenumApplications

Plenum ApplicationsBus and Cable Type

PartNumber

O.D. Part Number O.D.

1FC Bus: 22 AWG Stranded, 3-WireTwisted Shielded Cable1

Anixter:

CBL-22/3-FC-PVC

Belden®:B5501FE

0.138in.

Anixter:CBL-22/3-FC-PLNBelden: B6501FE

0.140in.

SA Bus (Terminal Block): 22 AWGStranded, 4-Wire, 2 Twisted-PairShielded Cable

Anixter:

CBL-22/2P-SA-PVC

Belden:B5541FE

0.209in.

Anixter:CBL-22/2P-SA-PLN

Belden: B6541FE

0.206in.

2SA Bus (Modular Jack): 26 AWG Solid6-Wire, 3 Twisted-Pair Cable2

Anixterpreassembled:CBL-NETWORK25CBL-NETWORK50CBL-NETWORK75CBL-NETWORK100

0.15 in.

FC Bus: 22 AWG Stranded, 3-WireTwisted Non-Shielded Cable

Belden:B5501UE

0.135in.

Belden: B6501UE0.131in.

SA Bus (Terminal Block): 22 AWGStranded, 4-Wire, 2 Twisted-Pair Non-Shielded Cable

Belden:B5541UE

0.206in.

Belden: B6541UE0.199in.

1 We strongly recommend 3-wire (for FC bus) and 4-wire, 2twisted-pair (for SA bus), 22 AWG stranded, shielded cable.A 22 gauge cable offers the best performance for variousbaud rates, cable distances, and number of trunk devicesprimarily due to lower conductor-to-conductor capacitance.Shielded cable offers better overall electrical noise immunitythan non-shielded cable. Observe the shield groundingrequirements.

2 We recommend 26 AWG solid, 6-wire (3 twisted pairs)cable as the best fit for fabricating modular cables with themodular jack housing assembly. Be sure the cable you usefits the modular jack housing. The preassembled cables thatare available from Anixter (Part No. CBL-NETWORKxxx) use24 gauge wire.

Operation

Cooling Operation• A Y1 call for the first stage of cooling is passed

to the unit control board (UCB). The UCB thendetermines whether the requested operationis available and if so, which components toenergize. With a Y1 call for first stage cooling, theUCB determines if a first stage cooling output isvalid as long as all safeties and time-delays allowa C1 output for cooling. The C1 relay on the UCBcloses and sends 24 volts to the M1 relay. Thisstarts compressor #1 on low and also energizesM4 for the condenser fan(s) to run at nominalspeed. The UCB energizes the VFD-equippedblower at the first stage speed as set in the SmartEquipment™.

• If a Y2 call is present, it is passed to theUCB. The UCB then determines whether therequested operation is available and if so, whichcomponents to energize. With a Y2 call for secondstage cooling, the UCB determines if a secondstage cooling output is valid as long as all safetiesand time-delays allow a C2 output for cooling. TheC2 relay on the UCB closes and sends 24 volts tothe M2 to the M2 relay which starts compressor#2 on high speed. The UCB energizes the VFD-equipped blower at the second stage speed as setin the Smart Equipment™ control.

• If a Y3 call is present, it is passed to theUCB. The UCB then determines whether therequested operation is available and if so, whichcomponents to energize. With a Y3 call for thirdstage cooling, the UCB determines if a third stagecooling output is valid as long as all safeties andtime-delays allow a C3 output for cooling. TheC3 relay on the 4-stage board closes and sends24 volts to terminal block TB3 which energizescompressor #1 on high speed. The UCB energizesthe VFD-equipped blower at the third stage speedas set in the Smart Equipment™ control.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A58

Johnson Controls Ducted Systems

Page 61: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Free cooling operation witheconomizer• With a demand for first stage cooling either from

a thermostat or space sensor and the outsideair is suitable for free cooling, the dampers aremodulated to maintain supply air temperature towithin +/- 1 degree of the free cooling SAT uppersetpoint. If the output to the economizer actuatoris at 10 VDC and the supply air temperaturecannot be controlled to within 5 degrees of thefree cooling SAT upper setpoint, one compressoris energized. The economizer is then modulatedto maintain supply air temperature to within +/- 1degree of the free cooling SAT upper setpoint.

• If a demand for second stage cooling occurs andthe economizer is already modulating to maintainthe supply air temperature to the cooling SATupper setpoint, the setpoint is changed to thefree cooling SAT lower setpoint. Any compressorsthat are energized remain energized and theeconomizer dampers are modulated to maintainsupply air temperature to within +/- 1 degreeof the cooling SAT lower setpoint. If the outputto the economizer actuator is at 10 VDC and thesupply air temperature cannot be controlledto within 5 degrees of the cooling SAT lowersetpoint, compressor stage 2 is energized. Theeconomizer is then modulated to maintain supplyair temperature to within +/- 1 degree of thecooling SAT lower setpoint.

• If the output to the economizer actuator is atminimum position and the supply air temperaturedrops more than 5 degrees below the currenteconomizer SAT setpoint, the highest stagecompressor is de-energized as long as theminimum run time has elapsed.

Economizer with single enthalpysensorWhen the room thermostat calls for cooling, thelow voltage control circuit from R to G and Y1 iscompleted. The UCB energizes the blower motor(if the fan switch on the room thermostat is set toAUTO position) and drives the economizer dampersfrom fully closed to their minimum position. If theenthalpy of the outdoor air is below the setpoint ofthe enthalpy controller (previously determined), Y1energizes the economizer. The dampers modulateto maintain a constant supply air temperatureas monitored by the discharge air sensor. If theoutdoor air enthalpy is above the setpoint, Y1

energizes the compressor and condenser fan motoronly.When the thermostat has been satisfied, it de-energizes Y1. If the compressor has satisfied itsminimum run time, the compressor and condenserfan are de-energized. Otherwise, the unit operatesthe cooling system until the minimum run timesfor the compressor are completed. After thecompressor de-energizes, the blower is stoppedfollowing the elapse of the fan off delay for cooling,and the economizer damper goes to the closedposition. If the unit continues fan operation, theeconomizer damper goes to the min. position.

Economizer with dual enthalpysensorsThe operation with the dual enthalpy sensors isidentical to the single sensor except that a secondenthalpy sensor is mounted in the return air. Thisreturn air sensor allows the economizer to choosebetween outdoor air and return air, whichever hasthe lowest enthalpy value, to provide maximumoperating efficiency.

Economizer with power exhaustA unit equipped with an economizer (single ordual enthalpy) and a power exhaust operatesas specified above with one addition. The powerexhaust motor is energized 45 seconds after theactuator position exceeds the exhaust fan setpointon the economizer control. The R to G connectionprovides minimum position but does not providepower exhaust operation.

Motorized outdoor air dampersThis system operation is the same as the units withno outdoor air options with one exception. Whenthe R to G circuit is complete, the motorized damperdrives open to a position set by the thumbwheelon the damper motor. When the R to G circuit isopened, the damper spring returns fully closed.Each cooling system is monitored for operationoutside of the intended parameters. Errors arehandled as described below. All system errorsoverride minimum run times for compressors.

Note: The following components are neededto access the control points in the SmartEquipment™ control.

1. Local LCD on Unit Control Board.

OR

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 59

Johnson Controls Ducted Systems

Page 62: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

2. Mobile Access Portal (MAP) Gateway (Portable).

- Source 1 P/N S1-JC-MAP1810-OP

- MAP Gateway Quick Start Guide P/N24-10737-16

- MAP Gateway Instruction P/N 24-10737-8

High-pressure limit switchDuring cooling operation, if a high-pressure limitswitch opens, the UCB de-energizes the compressor,initiates the ASCD (anti-short cycle delay), and stopsthe condenser fans. If the call for cooling is stillpresent at the conclusion of the ASCD, the UCB re-energizes the halted compressor.If a high-pressure switch opens three times withintwo hours of operation, the UCB locks out thecompressor.

Low-pressure limit switchThe low-pressure limit switch is not monitoredduring the initial 30 seconds of a cooling system'soperation. For the following 30 seconds, the UCBmonitors the low-pressure switch to ensure thatit closes. If the low-pressure switch fails to closeafter the 30-second monitoring phase, the UCB de-energizes the compressor, initiates the ASCD, andstops the condenser fans.When the low-pressure switch is proven (closedduring the 30-second monitor period describedabove), the UCB monitors the low-pressure limitswitch for any openings. If the low-pressure switchopens for greater than 5 seconds, the UCB de-energizes the compressor, initiates the ASCD, andstops the condenser fans.If the call for cooling is still present at the conclusionof the ASCD, the UCB re-energizes the haltedcompressor.If a low-pressure switch opens three times withinone hour of operation, the UCB locks out thecompressor.

Evaporator low limitThe evaporator low limit sensor (EC1) is locatedon the suction line at the evaporator coil. Duringcooling operation, if the evaporator low limit sensordetects a temperature below 26°F (default), the UCBde-energizes the compressor, initiates the ASCD,and stops the condenser fans. If the call for coolingis still present at the conclusion of the ASCD, theUCB re-energizes the halted compressor.If the UCB detects the evaporator low limit sensor(EC1) falling below 26°F (default) three times within

two hours of operation, the UCB locks out thecompressor.

Low ambient coolingTo determine when to operate in low ambientmode, the UCB has an outdoor air temperaturesensor (OAT) with a low ambient setpoint at45ºF (default). When the OAT sensor senses atemperature below the low ambient setpointand the thermostat is calling for cooling, the UCBoperates in the low ambient mode.Low ambient mode operates the compressors inthis manner: 10 minutes on, 5 minutes off. Theindoor blower is operated throughout the cycle.The 5-minute off period is necessary to defrost theindoor coil.Low ambient mode always begins with compressoroperation. Compressor minimum run time mayextend the minutes of compressor operation. Theoff cycle begins immediately following the elapse ofthe minimum run time.When operating in low ambient mode, anevaporator low limit sensor (EC1) temperaturebelow 26ºF de-energizes the compressor. If thecall for cooling is still present at the end of theASCD and the evaporator temperature sensor(EC1) temperature is above 26°F, the unit resumesoperation.

Safety controlsThe unit control board monitors the following inputsfor each cooling system:

1. An evaporator low limit sensor (EC1) to protectagainst low evaporator temperatures due toa low airflow or a low return air temperature,set at 26°F. The evaporator low limit sensor islocated on the suction line at the evaporatorcoil.

2. A high-pressure switch to protect againstexcessive discharge pressures due to a blockedcondenser coil or a condenser motor failure.The switch opens at 625 ± 25 psig.

3. A low-pressure switch to protect against loss ofrefrigerant charge. the switch opens at opensat 50 ± 5 psig.

The above pressure switches are hard-solderedto the unit. The refrigeration systems areindependently monitored and controlled. On anyfault, only the associated system is affected by anysafety or preventive action.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A60

Johnson Controls Ducted Systems

Page 63: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

The UCB monitors the temperature limit switch ofelectric heat units and the temperature limit switchand the gas valve of gas furnace units.

Compressor protectionIn addition to the external pressure switches,the compressors also have inherent (internal)protection. If there is an abnormal temperature risein a compressor, the protector opens to shut downthe compressor. The UCB incorporates featuresto minimize compressor wear and damage. Ananti-short cycle delay (ASCD) is used to preventoperation of a compressor too soon after itsprevious run. Additionally, a minimum run time isimposed any time a compressor is energized.The ASCD is initiated on unit start-up and on anycompressor reset or lock-out.

Gas Heating Operation1. Heating stages are controlled by the W1

through W2 thermostat inputs. A W1 or W2input energizes a H1 or H1/H2 output.

2. When the pre-ignition process is complete theignition module energizes the gas valve andprovides a 24 V input to the MV terminal on theUCB.

3. The FAN ON HEAT DELAY timer starts as soonas 24 V is present on MV terminal. When thetimer expires the FAN output for the indoorfan operation energizes. If 24 V is not receivedon the MV terminal within 6 minutes, analarm appears and the fan output energizesimmediately and remains On until the alarmclears.

4. When the thermostat heat inputs are lost andthe 120 second Minimum Heat Run Timers haveexpired, heating outputs stage off. The FAN OFFHEAT DELAY timer starts when 24 V is removedfrom the MV terminal. When the timer expires,the FAN output for the indoor fan operation de-energizes.

Note: If 24 V is lost on the MV terminalduring the same heat cycle, an alarmappears and the fan output energizes andremains On until 24 V is present again onthe MV terminal.

Note: If 24 V is present on the MV terminalwithout a call for heat, an alarm appearsand the fan output energizes. If thiscondition occurs for 6 minutes an alarmappears, and remains, until the alarmcondition is cleared.

5. At any time, if 24 V is lost on the LIMIT terminal,the FAN output for indoor fan operation isenergized. If 24 V is lost on the LIMIT input 3times in 1 hour, an alarm appears and the FANoutput is energized. The heating H1 and H2outputs are de-energized until the alarm iscleared.

Gas Heat Ignition Control BoardFunction

Ignition Control Board on StandbyThe Ignition Control Board (ICB) has all outputs de-energized and monitors the thermostat and flamesense. The ICB resets ignition trial and flame losscounters. The ICB begins a call for heat when W1 isenergized at the Unit Control Board (UCB). The ICBignores W2 until ignition has been established.

Call for heatThe ICB checks to see if the pressure switch is open.If the pressure switch is closed, the ICB flashes "3"on the LED and waits indefinitely for it to open.When the pressure switch is sensed as open, the ICBbegins pressure switch proving period. If the call forheat is lost, the ICB goes back to Standby.

Pressure switch provingThe ICB energizes the induced draft motor andwaits for the low pressure switch to close. When thelow pressure switch closes, the control begins Pre-purge period. If the call for heat is lost, the controlde-energizes the inducer without post-purge andreturns to standby.If the low pressure switch does not close within 10seconds of inducer energizing, the control flashes"2" on the LED. If the pressure switch does not closewithin 5 minutes of inducer energizing, the controlshuts off the inducer for 30 seconds, then energizesthe inducer for another 5 minute try to close thepressure switch. This cycle continues indefinitelyuntil either the pressure switch is proved closed, orthe call for heat ends.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 61

Johnson Controls Ducted Systems

Page 64: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Pre-purgeThe ICB monitors the low pressure switch andensures it remains closed during pre-purge. If thepressure switch opens, the control goes back topressure switch proving mode. The control waitsfor a 15 second pre-purge period, then begins theignition trial.

Ignition trial periodThe ICB energizes the main gas valve, second stagegas valve and spark outputs for a 10 second Ignitiontrial. The control de-energizes the spark when flameis sensed and enters a flame stabilization period.If flame is not established within the ignition trialperiod, the control de-energizes the spark and gasvalve and checks for maximum number of ignitiontrials. The ICB has a maximum number of 3 ignitiontrials. If the control has attempted the maximumnumber of ignition trials within the same call forheat without flame, the control will lockout flashing"4" on the LED. If the control has attempted lessthan maximum ignition trials, it begins an inter-purge period before attempting another ignitiontrial.If the call for heat is lost during an ignition trialperiod, the control immediately de-energizesspark and gas. The control runs the inducer motorthrough a post purge period before de-energizing.If the pressure switch is lost during an ignition trialperiod, the control immediately de-energizes sparkand gas. The control begins pressure switch provingbefore an inter-purge and re-ignition attempt.

Flame stabilization periodIf a flame is detected during the Ignition TrialPeriod, the ICB then enters the flame stabilizationperiod. If a flame is not detected in 2 seconds, themain valve is de-energized and a retry operationbegins. The flame stabilization period lasts 10seconds. flame detection must be lost for 2 secondsduring flame stabilization for the main valve to bede-energized. When the flame stabilization periodhas ended, a loss of flame detection for 3/4 secondswill result in the main valve being de-energized.If flame is lost during the flame stabilization period,the control counts it as a flame loss and retriesignition or locks out as described in Low heatsection.

Main Burner operationHigh heat warm-upTwo stage models run high heat for the first30 seconds following flame stabilization period

regardless of W2 demand. If W2 is not energizedat the end of this 30 second period the control de-energizes the high gas output. If W2 is energizedthe control remains on high heat.Low heatThe ICB keeps the main gas valve and induced draftmotor energized while continuously monitoring thecall for heat, low pressure switch, and flame status.If the call for heat (W1) is lost, the control de-energizes the gas valve and begins post purge.If low pressure switch opens, the control de-energizes the gas valve and begins pressure switchproving mode.If flame is lost, the control de-energizes the gasvalve within 2.0 seconds and counts the flame loss.If flame has been lost more than 5 times within thesame call for heat, the control locks out flashing "5"on the LED. If flame has been lost less than 5 times,the control attempts re-ignition after a 30 secondinter-purge period.High heatThe ICB recognizes a call for 2nd stage heat whenW2 is energized. The control energizes the high gasoutput.If the call for 2nd stage heat goes away and the 1ststage call remains, the control de-energizes the highgas valve and returns to low heat operation.Response to loss of W1, low pressure switch, andflame are identical to low heat operation.

Post PurgeThe ICB runs the induced draft motor for a 5 secondpost-purge period, then de-energizes the inducer. Ifa call for heat occurs during post-purge, the controlfinishes the post-purge, drops inducer out to re-prove open pressure switch before continuing withthe heat cycle.

LockoutWhile in lockout, the ICB keeps the main gas valveand induced draft motor de-energized.Lockouts due to failed ignition or flame losses maybe reset by removing the call for heat (W1) formore than 1 second, but less than 20 seconds, orby removing power from the control for over 0.25seconds. The control will automatically reset lockoutafter 60 minutes.Lockouts due to detected internal control faults willreset after 60 minutes or power interruption.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A62

Johnson Controls Ducted Systems

Page 65: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

High temperature limit switchIf the high temperature limit switch is open thecontrol will run the inducer, de-energize the gasvalve, and flash "6" on the LED. When the hightemperature switch closes, the control will restartthe ignition sequence beginning with pre-purge.If the high temperature limit is open for more than6 minutes continuously during a call for heat, it isassumed that the main blower has failed and thecontrol shall enter a hard lockout and flash a "9"on the LED. During the hard lockout, the controlwill continue to run the inducer as long as the limitswitch is open. If the limit switch recloses in thishard lockout condition, the inducer will run a postpurge and then shutoff. The control shall remainlocked out until power is removed and shall notreset automatically.

Roll-out switchIf the roll-out switch opens for more than 0.25seconds, the ICB will run the inducer for a post-purge period, immediately de-energize the gasvalve, and flash "7" on the LED.If the roll-out switch closes, the control shall remainlocked out until power removed or "W" is removed.Rollout switch lockout shall not reset automatically.

Power interruptionsPower interruptions less than 0.80 seconds shallnot cause the ICB to interrupt the heat sequence.Power interruptions over 0.250 seconds will causethe control reset lockout and ignition trial counters.Power interruptions of any duration shall notcause lockout or any operation requiring manualintervention.

Flame present with Gas offIf flame is sensed for longer than 2.0 seconds duringa period when the gas valve should be closed, theICB will enter lockout. The control will turn on theinducer blower while the flame is present.

Welded gas valve relay responseIf either or both Main and 2nd Stage Gas valveoutputs are sensed to be off for more than 1 secondwhen commanded to be ON the ICB shuts off alloutputs and enters lockout.If the Main valve output is sensed to be energizedfor more than 1 second when commanded to be off,the control de-energizes the induced draft motor(if flame is not present) to attempt to open thepressure switch to de-energize the gas valve. If theMain gas valve is still sensed as energized after the

inducer has been off for 15 seconds, the controlre-energizes the inducer to attempt to vent theunburned gas. In either case, the control locks out.

Cooling start-up

Prestart Check ListAfter installation has been completed:

1. Check the electrical supply voltage beingsupplied. Be sure that it is the same as listed onthe unit nameplate.

2. Set the room thermostat to the off position.

3. Turn unit electrical power on.

4. Set the room thermostat fan switch to on.

5. Check indoor blower rotation.

If blower rotation is in the wrong direction,refer to Blower Phasing.

6. Check blower drive belt tension.

7. Check the unit supply air (CFM).

8. Measure evaporator fan motor's amp draw.

9. Set the room thermostat fan switch to off.

10. Turn unit electrical power off.

Cooling operating instructions1. Turn unit electrical power on.

Note: Prior to each cooling season, thecrankcase heaters where equipment mustbe energized at least 10 hours before thesystem is put into operation.

2. Set the room thermostat setting to lower thanthe room temperature.

3. First stage compressors will energize after thebuilt-in time delay (five minutes).

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 63

Johnson Controls Ducted Systems

Page 66: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Post Start Check List1. Verify proper system pressures.

2. Measure the temperature drop across theevaporator coil.

Gas heat start-up

Pre-Start Check ListComplete the following checks before starting theunit.

1. Check the type of gas being supplied. Besure that it is the same as listed on the unitnameplate.

2. Make sure that the vent outlet and combustionair inlet are free of any debris or obstruction.

Gas heat operating instructions

 CAUTION

This furnace is equipped with an automatic re-ignitionsystem. DO NOT attempt to manually light the pilot.

Lighting The Main Burners1. Turn “OFF” electric power to unit.

2. Turn room thermostat to lowest setting.

3. Turn gas valve switch to “ON” position. SeeFigure 27

4. Turn “ON” electric power to unit.

5. If thermostat set temperature is above roomtemperature, the main burners will ignite.

Post Start ChecklistAfter the entire control circuit has been energizedand the heating section is operating, make thefollowing checks:

1. Check for gas leaks in the unit piping as well asthe supply piping.

 WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warning exactly could re-sult in serious injury, death or property damage.Nevertest for gas leaks with an open flame. use a commer-cially available soap solution made specifically for thedetection of leaks to check all connections. A fire orexplosion may result causing property damage, per-sonal injury or loss of life.

2. Check for correct manifold gas pressures. (SeeChecking Gas Heat Input.)

3. Check the supply gas pressure. It mustbe within the limits shown on the ratingnameplate. Supply pressure should be checkedwith all gas appliances in the building at fullfire. At no time should the standby gas pressureexceed 10.5 in. or the operating pressuredrop below 4.5 in. for natural gas units. Ifgas pressure is outside these limits, contactthe local gas utility or propane supplier forcorrective action.

Shut Down1. Set the thermostat to the lowest temperature

setting.

2. Turn “OFF” all electric power to unit.

3. Open gas heat access panel.

4. Turn gas valve switch to “OFF” position. SeeFigure 27.

Checking Gas Heat Input

Two Stage Gas HeatThis unit has two stages of gas heat. First stageinput is considered the minimum input for thefurnace. The intended input for each furnaceis shown in Table 43. The table applies to unitsoperating on 60 Hz power only.To determine the rate of gas flow (Second Stage).

1. Turn off all other gas appliances connected tothe gas meter.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A64

Johnson Controls Ducted Systems

Page 67: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

2. Turn on the furnace and make sure thethermostat is calling for Second stage (100%input) heat.

3. Measure the time needed for one revolution ofthe hand on the lowest increment dial on themeter. A typical gas meter has a 1/2 or a 1 cubicfoot test dial.

4. Using the number of seconds it takes for onerevolution of the dial, calculate the cubic feet ofgas consumed per hour. (See example below).

5. If necessary, adjust the high pressure regulatoras discussed in the section Manifold GasPressure Adjustment. Be sure not to over-firethe furnace on second stage. If in doubt, it isbetter to leave the second stage of the furnaceslightly under-fired. Repeat Steps 1-5.

To determine the rate of gas flow (FirstStage)

6. Turn off all other gas appliances connected tothe gas meter.

7. Turn on the furnace and make sure thethermostat is calling for first stage heat.

8. Even when the thermostat is calling for firststage heat, the unit will light on second stageand will run on second stage for 1 minute.Allow this one-minute time period to expire andbe certain the unit is running on first stage.

9. Measure the time needed for one revolution ofthe hand on the lowest increment dial on themeter. A typical gas meter has a 1/2 or a 1 cubicfoot test dial.

10. Using the number of seconds it takes for onerevolution of the dial, calculate the cubic feet ofgas consumed per hour (See example below).

11. If necessary, adjust the low pressure regulatoras discussed in the section Manifold GasPressure Adjustment. Be sure not to under-fire the furnace on first stage. If in doubt, itis better to leave the first stage of the furnaceslightly over-fired (Refer to Table 42 for inputvalue). Repeat Steps 1-6.

Table 42: Gas Rate Cubic Feet Per HourSize of Test Dial

Seconds for One Rev.1/2 cu. ft. 1 cu. ft.

10 180 36012 150 30014 129 25716 113 22518 100 20020 90 18022 82 16424 75 15026 69 13828 64 12930 60 12032 56 11334 53 10636 50 10038 47 9540 45 9042 43 8644 41 8246 39 7848 37 7550 36 7252 35 6954 34 6756 32 6458 31 6260 30 60

Note: To find the Btu input, multiply thenumber of cubic feet of gas consumedper hour by the Btu content of the gas inyour particular locality (contact your gascompany for this information as it varieswidely from area to area).

EXAMPLEBy actual measurement, it takes 19 seconds for thehand on a 1 cubic foot dial to make a revolutionwith a 200,000 Btuh furnace running. To determinerotations per minute, divide 60 by 19 = 3.16. Tocalculate rotations per hour, multiply 3.16 • 60 =189.6. Multiply 189.6 • 1 (0.5 if using a 1/2 cubic footdial) = 189.6. Multiply 189.6 • (the Btu rating of thegas). For this example, assume the gas has a Bturating of 1050 Btu/ft3. The result of 199,000 Btuh iswithin 2% of the 200,000 Btuh rating of the furnace.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 65

Johnson Controls Ducted Systems

Page 68: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Manifold Gas Pressure Adjustment

Two StageThis gas furnace has two heat stages. Therefore, thegas valve has two adjustment screws located undertwo cover screws. The second stage adjustmentscrew is adjacent to the "HI" marking on the valveand the first stage adjustment screw is locatedadjacent to the "LO" marking on the valve (SeeFigure 27).Manifold pressure adjustment procedure.Adjust second stage (Refer to Table 42 for inputvalue) pressure first, then adjust first stage (Refer toTable 43 for input value) pressure.

1. Turn off all power to the unit.

2. Using the outlet pressure port on the gas valve,connect a manometer to monitor the manifoldpressure.

3. Remove cover screws covering HI and LOpressure adjustment screws.

4. Turn on power to the unit.

5. Set thermostat to call for second stage heat andstart furnace.

6. If necessary, using a screwdriver, turnthesecond stage adjustment screw (adjacentto the “HI” marking on the valve) clockwise toincrease manifold pressure or counterclockwiseto decrease manifold pressure.

7. After the high manifold pressure has beenchecked, adjust the thermostat to call for firststage heat.

8. If necessary, using a screwdriver, turn the firststage adjustment screw (adjacent to the “LO”marking on the valve) clockwise to increasemanifold pressure or counterclockwise todecrease manifold pressure.

9. Once pressure has been checked, replace thecover screws covering the HI and LO pressureadjustment screws.

Table 43: Gas Heat Stages

Model(Size)

Gas HeatDescription

Opt.# of Burner

Tubes

1st StageInput(Mbh)

2nd StageInput(Mbh)

TotalInput(Mbh)

Low D 3 90 125 125Med E 4 125 180 180ZL08 (7.5)High F 5 176 220 220Low D 3 90 125 125Med E 4 125 180 180ZL09 (8.5)High F 5 176 220 220Low D 4 125 180 180Med E 5 176 220 220ZL12 (10)High F 5 200 250 250Low D 4 125 180 180Med E 5 176 220 220ZL14 (12.5)High F 5 200 250 250

Adjustment Of Temperature RiseThe temperature rise (the difference of temperaturebetween the return air and the heated air from thefurnace) must lie within the range shown on the unitrating plate and the data in Physical Data.After the temperature rise has been determined, theCFM can be calculated as follows:

After about 20 minutes of operation, determine thefurnace temperature rise. Take readings of boththe return air and the heated air in the ducts (about6 feet from the furnace) where they will not beaffected by radiant heat. Increase the blower CFM todecrease the temperature rise; decrease the blowerCFM to increase the rise (See SUPPLY AIR DRIVEADJUSTMENT).

Note: Each gas heat exchanger size has aminimum allowable CFM. Below this CFM, thelimit will open.

Burners/Orifices Inspection/ServicingBefore checking or changing burners or orifices,CLOSE MAIN MANUAL SHUT-OFF VALVE AND SHUTOFF ALL POWER TO THE UNIT.

1. Open the union fitting just upstream of theunit gas valve and downstream from the mainmanual shut-off valve in the gas supply line.

2. Remove the screws holding each end of themanifold to the manifold supports.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A66

Johnson Controls Ducted Systems

Page 69: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

3. Disconnect wiring to the gas valve. Remove themanifold & gas valve assembly. Orifices cannow be inspected and/or replaced.

To service burners, complete step 4.

4. Remove the heat shield on top of the manifoldsupports. Burners are now accessible forinspection and/or replacement.

Note: Reverse the above procedure toreplace the assemblies.

Make sure that burners are level and seat at the rearof the gas orifice.

Figure 26: Typical Flame

Note: installation of this furnace at altitudesabove 2000 ft (610 m) shall be in accordancewith local codes, or in the absence of localcodes, the National Fuel Gas Code, ANSIZ223.1/NFPA 54 or National Standard ofCanada, Natural Gas and Propane InstallationCode, CSA B149.1.

Figure 27: Typical two stage gas valve

Troubleshooting

 WARNING

Troubleshooting of components may require open-ing the electrical control box with the power connect-ed to the unit. Use extreme care when workingwith live circuits! Check the unit nameplate for thecorrect line voltage and set the voltmeter to the cor-rect range before making any connections with lineterminals.When not necessary, shut off all electricpower to the unit prior to any of the following mainte-nance procedures so as to prevent personal injury.

 CAUTION

Label all wires prior to disconnection when servicingcontrols. Wiring errors can cause improper and dan-gerous operation, which could cause injury to personand/or damage unit components. Verify proper opera-tion after servicing.

 WARNING

The furnace may shut down on a high temperaturecondition during the procedure. If this occurs, the UCBenergize the supply air blower motor until the hightemperature limit has reset. Caution should be usedat all times as the supply air blower may energize re-gardless of the room thermostat fan switch position.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 67

Johnson Controls Ducted Systems

Page 70: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Flash Codes for the Gas Heat IgnitionControl BoardTable 44: Flash Codes for the Gas Heat Ignition Control Board

Flash Code Description Technician Corrective ActionIgnition Control Response toFlash Code

Method for Reset

HeartbeatNormal Operation - no staus orerror information currently needsto be displayed

None.All functions available to respondto heating demand.

None.

a. No Power to the Control - Lessthan 18 VAC is present at theignition control's R (P2-2 pin) andC (P2-1 pin) connections

a. Restoration of 24VAC power to theignition control.

Steady Off b. The ignition control hascatastrophic damage that will notallow the LED display (it is likelythat there will be visible physicalevidence of the damage)

Verify line voltage is present at the primary of the 75VA transformer,verify 24 VAC is present at the secondary of the 75VA transformer.Verify 24 VAC is present from the UCB's C to SD terminals indicatingthe 3.2A control circuit breaker and phase monitor contacts are closed.Verify 24 VAC is present at the ignition control's R (P2-2 pin) and C (P2-1pin) connections indicating the unit to ignition control wiring is intact.

The output relay contacts open soinducer and gas valve operation isnot permitted.

b. None.

Steady OnThe Ignition Control'sMicroprocessor Has Not Passed itsSelf-check

Cycle power to the control to eliminate the possibility that transientvoltage conditions such as surges, brownouts, etc. have not created afalse indication. If the steady on LED indication repeats, the control willneed to be replaced and potential causes for failure, such as excessivevoltage, RF interference, etc. should be investigated.

The output relay contacts open soinducer and gas valve operation isnot permitted.

Cycling 24 VACpower to the ignitioncontrol or expirationof the 60 minute"watchdog" timer.

2 Flashes

The Induced Draft Pressure SwitchDid Not Close - 24 VAC was notreceived to the ignition control'spressure switch input (P1-8 pin)within 10 seconds of the ignitioncontrol energizing the induceddraft motor or 24 VAC was laterlost to the control's pressureswitch input while the ignitioncontrol energized the induceddraft motor

Verify that the induced draft motor is operable, the ignition control's L1to IND contacts are not open, the induced draft blower wheel is intactand there are no blockages in the combustion air / induced draft path.Verify that the induced draft pressure switch sensing tubing is intact.With an incline manometer, digital manometer or Magnehelic® gaugeteed into the pressure switch sensing line verify that the negativepressure exceeds the setting listed on the induced draft pressureswitch label and the switch's contacts correctly close at the settinglisted

Gas valve operation is notpermitted/ends when the induceddraft pressure switch input is notpresent. The ignition control's L1 toIND output relay contact will cycleclosed for 5 minutes/open for 30seconds until 24 VAC is received tothe pressure switch input or theheating demand ends.

Closure of thepressure switch (24VAC input to P1-8pin), cycling firststage heat inputor cycling 24 VACpower to the ignitioncontrol.

3 Flashes

The Induced Draft Pressure Switch isStuck Closed - 24 VAC is received tothe control's pressure switch input(P1-8 pin) at the same time as 24VAC to initiate heating operation isreceived at the control's W1 input(P2-3 pin)

Verify that the induced draft pressure switch contacts are not stuckor welded closed. Verify that the ignition control's L1 to IND contactsare not stuck or welded closed causing the induced draft motor to runcontinuously. Verify that the wiring from the ignition control's P1-3pin through the induced draft pressure switch to the ignition control'spressure switch input (P1-8 pin) is not shorted.

The output relay contacts open soinducer and gas valve operation isnot permitted.

Opening of thepressure switch (lossof 24 VAC input toP1-8 pin) then cyclingfirst stage heat inputor cycling 24 VACpower to the ignitioncontrol.

4 Flashes

Flame Could Not Be Established - Aflame signal of 0.2μa or greatercould not be established in threeconsecutive attempts for ignitionat the initiation of the heatingcycle

Verify that the unit has proper electrical grounding. Verify the 24VAC common and ignition control cabinet ground references areintact. Monitor the flame signal. Verify that combustion air openingsare without blockages and that the unit has proper clearance to thestructure and adjacent units. Verify that the burners are clean andwithout blockages that could interfere with gas flow. Verify that theignitor sparks with an ≈1/8" gap to the crossover area of the leftburner. Verify that the flame sensor is intact and positioned with an≈1/8" gap to the right burner. Verify that the gas lines have beenpurged of air and provide proper gas inlet pressure. Verify that the gasvalve is opening and adjusted to provide proper manifold pressure.Verify that the wiring to the gas valve is intact. Verify that there is nowind, rain or snow entering the heat compartment to interfere withignition or the burners. Verify that there are no conditioned air leaks orheat exchanger breaches to interfere with ignition or the burners.

Immediately after the thirdignition trial: the gas valve outputrelay contact opens so gas valveoperation is not permitted,following a 5 second inducer postpurge the induced draft outputrelay contact opens so induceroperation is not permitted.

Cycling first stageheat input, cycling24 VAC power to theignition control orexpiration of the 60minute "watchdog"timer.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A68

Johnson Controls Ducted Systems

Page 71: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 44: Flash Codes for the Gas Heat Ignition Control Board

Flash Code Description Technician Corrective ActionIgnition Control Response toFlash Code

Method for Reset

5 Flashes

Flame Loss - After beingestablished during ignition trials,flame signal dropped below 0.2μafive times during one heating cycle

Verify that the unit has proper electrical grounding. Verify the 24VAC common and ignition control cabinet ground references areintact. Monitor the flame signal. Verify that combustion air openingsare without blockages and that the unit has proper clearance to thestructure and adjacent units. Verify that the burners are clean andwithout blockages that could interfere with gas flow. Verify that theflame sensor is intact and positioned with an ≈1/8" gap to the rightburner. Verify that the gas lines have been purged of air and provideproper gas inlet pressure. Verify that the gas valve provides propermanifold pressure. Verify that the wiring to the gas valve is intact. Verifythat there is no wind, rain or snow entering the heat compartmentto interfere with ignition or the burners. Verify that there are noconditioned air leaks or heat exchanger breaches to interfere withignition or the burners.

Immediately after the fifth flameloss: the gas valve output relaycontact opens so gas valveoperation is not permitted,following a 5 second inducer postpurge the induced draft outputrelay contact opens so induceroperation is not permitted.

Cycling first stageheat input, cycling24 VAC power to theignition control orexpiration of the 60minute "watchdog"timer.

6 Flashes

Open Limit - 24 VAC has been lostto the control's limit switch input(P1-9 pin) or 24 VAC has beenlost to the control's limit switchinput (P1-9 pin) for a durationof 6 minutes or less with 24 VACpresent at the control's W1 input(P2-3 pin)

Verify proper gas manifold pressure. Correct the inadequate indoorairflow condition. Verify filters, indoor coil and blower wheel are clean.Verify that the blower belt is properly maintained and adjusted; theblower motor fuses are intact, contactor and motor are operable andwheel has the correct rotation. Verify that the ducting is not restrictive.Verify indoor air volume is at least the minimum required for the heatsection by using the Airflow Measurement Charts in the TechnicalTraining Manual or other method such as temperature rise, balometer,etc. Verify heating mode blower on/off delays are proper for the heattype and provide adequate heat section cooling at the termination ofthe heating cycle. Verify wiring for main and auxiliary limit switches isintact.

The gas valve output relay contactopens so gas valve operation is notpermitted, the induced draft outputrelay contact closes to operate theinducer.

Closure of the limitswitch(es) (24 VACinput to P1-9 pin)

7 FlashesOpen Rollout - 24 VAC has beenlost to the control's rollout switchinput (P1-6 pin)

Verify that combustion air openings are without blockages and thatthe unit has proper clearance to the structure and adjacent units.Verify that the burners are clean and without blockages that couldinterfere with gas flow. Verify that the ignitor sparks with an ≈1/8"gap to the crossover area of the left burner. Verify that the gas linesprovide proper gas inlet pressure. Verify that the gas valve is adjustedto provide proper manifold pressure. Verify that there is no wind, rainor snow entering the heat compartment to interfere with ignitionor the burners. Verify that there are no conditioned air leaks or heatexchanger breaches to interfere with ignition or the burners. Verifywiring for the rollout switch is intact.

The gas valve output relay contactopens so gas valve operation is notpermitted, following a 5 secondinducer post purge the induceddraft output relay contact opens soinducer operation is not permitted.

Closure of the rolloutswitch (24 VAC inputto P1-6 pin) thencycling first stageheat input or cycling24 VAC power to theignition control.

8 Flashes

The Gas Valve Failed To Shut Off -flame has been sensed for longerthan 2 seconds when the firststage gas valve output is off

Verify that the gas valve is not slow to shut off, leaks by or otherwisedoes not completely shut off gas flow when de-energized. Verify thegas valve wiring to is intact and not shorted in a manner that wouldimproperly allow 24 VAC from another circuit to be applied to the gasvalve.

The gas valve output relay contactopens so gas valve operation is notpermitted, the induced draft outputrelay closes to operate the inducer.

Cycling 24 VACpower to the ignitioncontrol.

9 Flashes

Indoor Airflow Failure Open Limit- 24 VAC has been lost to thecontrol's limit switch input (P1-9pin) for a duration of more than6 minutes with 24 VAC present atthe control's W1 input (P2-3 pin)

Correct the no/extremely low indoor airflow condition. Verify filters,indoor coil and blower wheel are clean. Verify that the blower belt isintact, properly maintained and adjusted; the blower motor fuses areintact, contactor and motor are operable and wheel has the correctrotation. Verify that the ducting is without blockages. Verify indoor airvolume is at least the minimum required for the heat section by usingthe Airflow Mesurement Charts in the Technical Training Manual orother method such as temperature rise, balometer, etc. Verify wiringfor main and auxiliary limit switches is intact. Verify main and auxiliarylimit switches are not failed in an open position.

The gas valve output relay contactopens so gas valve operation is notpermitted, the induced draft outputrelay contact closes to operate theinducer.

Cycling 24 VACpower to the ignitioncontrol.

a. Gas Valve Miss-wire - 24 VAC hasbeen present for longer than 1second at the first stage and/orsecond stage gas valve output(P1-7 pin and/or P1-4 pin) whenthe gas valve is commanded off bythe ignition control

10 Flashes b. Ignition Control Gas Valve RelayContact Failed to Close - 24 VAC hasnot been sensed for longer than1 second at the first stage and/or second stage gas valve output(P1-7 pin and/or P1-4 pin) whenthe gas valve is commanded on bythe ignition control

Verify gas valve wiring from the ignition control to the gas valve is intactand not shorted in a manner that would improperly allow 24 VAC fromanother circuit to be applied to the control's P1-7 and/or P1-4 gas valveoutput pins. Verify the control's gas valve output relay contacts for firststage (P1-8 to P1-7) and second stage (P1-7 to P1-4) are not shorted orfail to close when commanded on.

Initally, the output relay contactsopen. Then, if 24 VAC remainspresent at the P1-7 pin after 15seconds, the induced draft outputrelay contact closes to operate theinducer.

Cycling 24 VACpower to the ignitioncontrol.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 69

Johnson Controls Ducted Systems

Page 72: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

ZL08-14 Charging TablesTable 45: ZL08 Charging Table System 1

Air FlowIndoorDb/Wb

OutdoorDB

Suction PSuctionTemp.

LiquidP

LiquidTemp.

DeltaT Db

Compr.amps

75 133 59 276 82 26 7.685 130 56 322 90 27 8.5

300 Cfm/Ton 80/62

95 127 54 368 98 27 9.575 134 59 274 86 26 7.585 136 58 322 92 25 8.5

300 Cfm/Ton 80/67

95 138 57 369 98 24 9.575 135 59 272 89 26 7.585 142 59 321 94 24 8.5

300 Cfm/Ton 80/72

95 148 60 371 99 21 9.575 128 55 274 82 24 7.585 127 53 320 90 23 8.5

300 Cfm/Ton 75/62

95 127 52 365 99 23 9.475 138 62 279 82 24 7.685 138 60 325 90 23 8.6

400 Cfm/Ton 80/62

95 138 59 372 99 23 9.575 139 62 279 83 23 7.685 141 61 326 91 22 8.6

400 Cfm/Ton 80/67

95 143 60 373 99 21 9.575 140 62 279 84 23 7.685 144 61 326 91 21 8.6

400 Cfm/Ton 80/72

95 148 60 374 99 20 9.575 133 58 278 81 21 7.685 134 57 324 90 20 8.5

400 Cfm/Ton 75/62

95 136 56 370 99 20 9.5

Table 46: ZL08 Charging Table System 2Air FlowIndoorDb/Wb

OutdoorDB

Suction PSuctionTemp.

LiquidP

LiquidTemp.

DeltaT Db

Compr.amps

75 138 64 264 81 26 7.185 138 63 312 90 27 7.9

300 Cfm/Ton 80/62

95 139 62 359 99 27 8.875 140 65 263 83 26 7.085 144 64 309 92 25 7.8

300 Cfm/Ton 80/67

95 148 64 355 101 24 8.775 142 65 263 85 26 6.985 150 66 306 94 24 7.8

300 Cfm/Ton 80/72

95 158 66 350 103 21 8.675 133 61 262 81 24 7.085 135 61 310 90 23 7.9

300 Cfm/Ton 75/62

95 138 60 357 99 23 8.775 141 67 268 79 24 7.185 144 66 315 89 23 7.9

400 Cfm/Ton 80/62

95 147 65 363 99 23 8.875 144 67 268 81 23 7.185 148 67 314 90 22 7.9

400 Cfm/Ton 80/67

95 152 66 361 100 21 8.875 146 68 267 82 23 7.085 152 67 313 91 21 7.9

400 Cfm/Ton 80/72

95 157 67 359 100 20 8.775 137 63 266 79 21 7.185 140 63 314 89 20 7.9

400 Cfm/Ton 75/62

95 144 63 362 98 20 8.8

Table 47: ZL09 Charging Table System 1Air FlowIndoorDb/Wb

OutdoorDB

Suction PSuctionTemp.

LiquidP

LiquidTemp.

DeltaT Db

Compr.amps

75 139 66 278 84 25 7.685 140 64 322 94 26 8.5

300 Cfm/Ton 80/62

95 141 63 366 104 26 9.475 139 64 277 85 25 7.685 142 64 325 93 24 8.6

300 Cfm/Ton 80/67

95 146 64 372 100 24 9.575 139 62 276 86 25 7.685 145 64 327 92 23 8.6

300 Cfm/Ton 80/72

95 150 66 378 97 21 9.675 132 62 277 82 23 7.685 135 61 322 92 23 8.5

300 Cfm/Ton 75/62

95 138 61 367 102 22 9.475 144 68 280 84 23 7.785 147 67 327 93 23 8.6

400 Cfm/Ton 80/62

95 149 66 373 102 22 9.675 146 67 280 85 22 7.785 148 67 328 92 21 8.7

400 Cfm/Ton 80/67

95 151 66 377 100 21 9.675 147 66 280 85 21 7.785 150 67 330 92 20 8.7

400 Cfm/Ton 80/72

95 153 67 380 98 19 9.775 138 64 279 82 20 7.685 141 64 326 91 20 8.6

400 Cfm/Ton 75/62

95 144 63 373 101 19 9.6

Table 48: ZL09 Charging Table System 2Air FlowIndoorDb/Wb

OutdoorDB

Suction PSuctionTemp.

LiquidP

LiquidTemp.

DeltaT Db

Compr.amps

75 139 66 276 80 25 7.785 141 63 321 91 26 8.8

300 Cfm/Ton 80/62

95 143 59 366 102 26 9.975 140 67 274 80 25 7.885 145 64 322 91 24 8.9

300 Cfm/Ton 80/67

95 150 61 370 101 24 9.975 141 67 273 79 25 7.885 149 65 323 90 23 8.9

300 Cfm/Ton 80/72

95 156 63 373 101 21 10.075 135 61 272 81 23 7.785 138 59 319 91 23 8.8

300 Cfm/Ton 75/62

95 140 57 367 101 22 9.975 142 69 280 80 23 7.885 147 67 326 90 23 8.9

400 Cfm/Ton 80/62

95 152 64 372 101 22 10.075 144 70 281 79 22 7.985 150 67 327 90 21 8.9

400 Cfm/Ton 80/67

95 156 64 373 101 21 10.075 145 70 282 79 21 7.985 152 67 328 90 20 9.0

400 Cfm/Ton 80/72

95 159 64 375 101 19 10.075 139 64 276 80 20 7.885 143 63 324 90 20 8.9

400 Cfm/Ton 75/62

95 147 61 371 101 19 10.0

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A70

Johnson Controls Ducted Systems

Page 73: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Table 49: ZL12 Charging Table System 1Air FlowIndoorDb/Wb

OutdoorDB

Suction PSuctionTemp.

LiquidP

LiquidTemp.

DeltaT Db

Compr.amps

75 136 65 284 82 25 10.085 135 63 331 91 26 11.1

300 Cfm/Ton 80/62

95 134 61 377 100 26 12.375 135 65 283 82 25 10.085 138 64 332 91 24 11.2

300 Cfm/Ton 80/67

95 141 63 381 101 23 12.475 134 64 282 81 26 10.085 141 64 333 91 23 11.3

300 Cfm/Ton 80/72

95 148 65 384 101 20 12.575 130 62 281 82 23 9.985 131 60 329 91 23 11.1

300 Cfm/Ton 75/62

95 132 59 377 100 23 12.275 139 67 284 81 23 10.085 140 66 332 91 23 11.1

400 Cfm/Ton 80/62

95 141 64 379 100 22 12.375 140 67 285 81 22 10.085 142 66 332 91 21 11.2

400 Cfm/Ton 80/67

95 145 65 380 100 21 12.475 140 67 285 80 22 10.085 144 67 333 90 20 11.2

400 Cfm/Ton 80/72

95 149 66 381 100 19 12.475 134 64 283 81 20 9.985 136 63 331 90 20 11.1

400 Cfm/Ton 75/62

95 138 62 378 100 19 12.3

Table 50: ZL12 Charging Table System 2Air FlowIndoorDb/Wb

OutdoorDB

Suction PSuctionTemp.

LiquidP

LiquidTemp.

DeltaT Db

Compr.amps

75 141 65 275 83 25 9.585 142 62 322 93 26 10.7

300 Cfm/Ton 80/62

95 143 59 369 104 26 11.975 140 64 274 83 25 9.585 143 65 325 92 24 10.8

300 Cfm/Ton 80/67

95 146 66 376 101 23 12.175 140 63 274 83 26 9.585 144 68 328 90 23 11.0

300 Cfm/Ton 80/72

95 149 73 383 97 20 12.475 136 60 273 83 23 9.585 137 59 321 92 23 10.7

300 Cfm/Ton 75/62

95 139 59 370 102 23 11.975 143 68 275 82 23 9.585 146 66 323 92 23 10.8

400 Cfm/Ton 80/62

95 149 63 371 103 22 12.075 144 67 276 82 22 9.685 147 66 324 92 21 10.8

400 Cfm/Ton 80/67

95 151 65 373 102 21 12.175 144 67 276 81 22 9.685 149 67 325 91 20 10.8

400 Cfm/Ton 80/72

95 153 67 374 101 19 12.175 138 63 274 82 20 9.585 141 62 323 92 20 10.7

400 Cfm/Ton 75/62

95 144 61 371 102 19 12.0

Table 51: ZL14 Charging Table System 1Air FlowIndoorDb/Wb

OutdoorDB

Suction PSuctionTemp.

LiquidP

LiquidTemp.

DeltaT Db

Compr.amps

75 138 62 294 88 24 11.385 137 62 343 95 25 12.7

300 Cfm/Ton 80/62

95 135 61 391 102 25 14.175 138 62 293 89 24 11.385 139 63 343 95 23 12.7

300 Cfm/Ton 80/67

95 141 64 394 101 22 14.275 137 62 292 90 24 11.285 142 64 344 95 22 12.8

300 Cfm/Ton 80/72

95 146 66 396 101 20 14.375 131 59 292 86 22 11.285 132 58 341 94 22 12.6

300 Cfm/Ton 75/62

95 133 58 390 101 21 14.175 142 64 297 89 21 11.485 143 64 346 96 21 12.8

400 Cfm/Ton 80/62

95 144 64 395 104 21 14.375 143 64 297 89 21 11.485 144 65 346 96 20 12.8

400 Cfm/Ton 80/67

95 146 65 396 103 20 14.375 143 64 297 90 21 11.485 146 65 347 96 20 12.8

400 Cfm/Ton 80/72

95 148 66 397 103 18 14.375 136 61 295 87 19 11.385 138 61 345 95 18 12.8

400 Cfm/Ton 75/62

95 139 60 394 103 18 14.3

Table 52: ZL14 Charging Table System 2Air FlowIndoorDb/Wb

OutdoorDB

Suction PSuctionTemp.

LiquidP

LiquidTemp.

DeltaT Db

Compr.amps

75 134 61 289 81 24 11.585 134 60 341 90 25 13.1

300 Cfm/Ton 80/62

95 135 60 393 99 25 14.675 134 61 287 81 24 11.585 137 61 341 90 23 13.1

300 Cfm/Ton 80/67

95 140 61 394 98 22 14.775 133 60 285 81 24 11.485 139 62 340 90 22 13.1

300 Cfm/Ton 80/72

95 145 63 395 98 20 14.875 127 58 287 80 22 11.485 129 58 339 89 22 13.0

300 Cfm/Ton 75/62

95 132 58 392 98 21 14.675 138 63 293 82 21 11.785 140 63 345 91 21 13.2

400 Cfm/Ton 80/62

95 143 63 397 101 21 14.875 139 64 292 82 21 11.785 142 63 344 91 20 13.2

400 Cfm/Ton 80/67

95 145 63 396 100 20 14.875 140 64 291 83 21 11.685 143 63 343 91 20 13.3

400 Cfm/Ton 80/72

95 146 63 395 99 18 14.975 132 60 291 80 19 11.685 135 60 344 90 18 13.2

400 Cfm/Ton 75/62

95 138 60 396 100 18 14.7

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 71

Johnson Controls Ducted Systems

Page 74: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Smart Equipment™ Control BoardNavigation ComponentsThe following components are needed to accessthe control points in the Smart Equipment™ control.Installation and operation guides are available fromyour equipment dealer or distributor.

1. Local LCD on Unit Control Board.

2. Mobile Access Portal (MAP) Gateway (Portable).

- Source 1 P/N S1-JC-MAP1810-OP

3. MAP Gateway Quick Start Guide P/N 24-10737-16

4. MAP Gateway Instruction P/N 24-10737-8

For more information on the Smart Equipment™unit control board navigation, refer to the SmartEquipment™ Quick Start Guide.

Note: For more in-depth sequence of operationof the Smart Equipment™ control, refer tothe Smart Equipment™ Controls Sequence ofOperation Overview LIT-12011950.

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A72

Johnson Controls Ducted Systems

Page 75: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Start-Up Sheet

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 73

Johnson Controls Ducted Systems

Page 76: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A74

Johnson Controls Ducted Systems

Page 77: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 75

Johnson Controls Ducted Systems

Page 78: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A76

Johnson Controls Ducted Systems

Page 79: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

INSTALLATION MANUAL ZL SERIES 7.5‑12.5 Ton 60 Hertz R-410A 77

Johnson Controls Ducted Systems

Page 80: 7.5- 12 .5 Ton 60 Her tz R- 410A INSTALL ATION MANUAL ZL … · 2020. 1. 10. · 5830280-UIM-A-0220 Revision: A-0220 2020-02-01 Johnson Controls Ducted Systems INSTALL ATION MANUAL

Subject to change without notice. Printed in U.S.A. Copyright © 2019 by Johnson Controls. All rights reserved.

Johnson Controls Ducted Systems