F.V/Time 10min 15min 30min 1h 2h 3h 5h 8h 10h
1.85V/cell 1,014.0 973.0 853.0 723.5 482.0 374.9 259.4 194.9 166.9
1.80V/cell 1,226.0 1,162.0 984.0 809.6 527.1 406.4 278.3 208.3 178.1
1.75V/cell 1,425.0 1,282.0 1,038.0 837.9 538.7 413.7 283.5 211.7 180.3
1.70V/cell 1,571.0 1,379.0 1,142.4 888.8 565.9 432.0 294.8 213.9 182.6
1.67V/cell 1,657.0 1,435.0 1,176.0 908.3 574.6 438.5 298.1 216.2 183.7
1.60V/cell 1,701.0 1,464.0 1,193.9 918.0 578.9 441.7 300.2 216.2 184.8
F.V/Time 10min 15min 30min 1h 2h 3h 5h 8h 10h
1.85V/cell 545.0 518.0 446.0 373.8 247.8 192.2 132.3 98.3 83.9
1.80V/cell 671.0 627.0 520.0 421.1 272.0 209.0 141.8 105.3 89.6
1.75V/cell 794.0 702.0 554.0 438.9 280.4 213.2 144.9 107.1 91.1
1.70V/cell 891.0 766.0 616.4 468.7 294.8 223.6 151.2 108.4 92.1
1.67V/cell 956.0 809.0 640.5 481.7 301.3 227.9 153.4 109.8 93.0
1.60V/cell 1,001.0 838.0 657.3 490.3 305.6 231.1 155.5 110.7 93.6
8 OPzV800 (2V,800AH)
Tubular GEL Battery
Maintence-free Sealed Lead-acid GEL BatterySELED LEAD BATTERY MUST BE RECYCLED OR
DISPOSED OF PROPERLYLEOCH BATTERY CO.,LTD.
MADE IN CHINA
896.0Ah
191mm(7.52 in.)
210mm(8.27 in.)
646mm(25.43 in.)
681mm(26.81 in.)
2V
Specification
Specifications subject to change without notice.
o oConstant Power Discharge (Watts/cell) at 25 C (77 F )
o oConstant Current Discharge (Amperes) at 25 C (77 F )
65.1Kg (143.52 Ibs)
6400A (5s)
Approx 0.43 mΩ
o o o o25 C±3 C (77 F±5 F)
ABS
M8
o≤3% per month at 25 C
≤200.0A
2.35V~2.40V
o o o o-20 C~55 C (-4 F~131 F)o o o o 0 C~40 C (32 F~104 F)o o o o-20 C~50 C (-4 F~122 F)
Length
Width
Container Height
Total Height (with Terminal)
Discharge
Charge
Storage
2.25Vo -3mV/cell/ C
Charging Voltage
Temp. Coefficient
Charging Current ≤200.0A
Nominal Voltage
Dimension
Approx Weight
Nominal Operating Temp. Range
Self Discharge
Terminal
Container Material
oCycle Use(25 C)
oStandby Use (25 C)
Max. Discharge Current
Operating Temp.Range
Internal Resistance
8 OPzV800 8 OPzV800 8 OPzV800
9.7
21
5.7
M8108±1210±1
19
1±
1
80±
16
46±
26
63±
26
81±
2
Ø18
Charging Current
Charging Voltage
Rated Capacity (C ,1.80V/cell)10
896 Ah
724.5 Ah
639.6 Ah
481.7 Ah
(10hr,89.6A,1.80V/cell)
(5hr,144.9A,1.75V/cell)
(3hr,213.2A,1.75V/cell)
(1hr,481.7A,1.67V/cell)
Capacity
Layout
Sales Offices Worldwide
19751 Descartes
Foothill Ranch, CA 92610, USA
Tel: 949-588-5853
Fax: 949-588-5966
E-mail: [email protected]
5th Floor, Xinbaohui Bldg., Nanhai Blvd.,
Nanshan, Shenzhen, China. 518052
Tel: +86-755-86036060 (100 lines)
Fax: +86-755-26067269
E-mail:[email protected]
North America Sales Office
China Sales Office
Workshop C, 33/F, TML Tower, No. 3 Hoi Shing Road,
Tsuen Wan, New Territories, Hong Kong
Tel: +852 35786666
Fax: +44 1452 690125
E-mail: [email protected]
9B Wheatstone Court. Waterwells, Business Park,
Gloucester, GL2-2AQ, UK United Kingdom
Tel: +44(0) 1452 729428 / 1452 729696
Fax:+44 1452 690125
E-mail: [email protected]
HongKong Sales Office
UK Sales Office
No. 1 Tech Park Crescent,
Singapore 638131
Tel: +65 68636078
Fax: +65 6863 6079
Email: [email protected]
1 Deligiorgi St., 121 31 Athens,
Greece
Tel: +30 210 5760318 (2 lines)
E-mail: [email protected]
Singapore Sales Office
Europe/MEA Sales Office
2 /29 Tarlington Place, Smithfield. NSW 2164
Australia
Tel: 02 9756 0950
E-mail: [email protected]
Shed no.A-53(b), 2nd Stage of Peenya Industrial Area,
Bangalore North Taluk, Bangalore-560058, India
Tel: +91-80-23440018/23440019
Fax: +91-80-23440017
E-mail: [email protected]
Australia Sales Office
India Sales Office
Publication No.:LB-8OPzV800-PD-EN-V1.0-201710
© 2017 LEOCH. All rights reserved.
Trademarks and logos are the property of LEOCH and its affiliates unless otherwise noted.
Subject to revisions without prior notice.
Http://www.leoch.com
Http://www.leoch.us
Classified as “Very Long Life” according to •
Eurobat
UL Certified•
Manufactured in Leoch®•
TS16949,ISO 9001 and ISO 14001
certified production facilities
• IEC 60896Certified• Telecommunications
• Radio and cellular telephone relay stations
• Power stations,Conventional power stations,alternative pwer(solar,wind)
Railway signaling•
• Emergency lighting systems
• Process and control engineering
• Buoy lighting
• Better recovery performance
Wide working temperature range (-20~50)℃•
No electrolyte stratification provides longer • service life.
High recombination efficient.•
Pasted negative plate special grid design • increase the active material.availablity large current discharge and charge ability.
Tubuler type positive plate (polyester tube) • prevent the active material from falling. Muti metal alloy pressed positive grid increase the anti corrosion ablity and service life.
Applications General Features Standards
Large UPS and computer • back-up
Maritime standby power on• ships and ashore
• Standby power
Build in copper core based in lead will carry • large current Separator imported form AMER-SIL high • porosity.PVC-SiO and low resistance.2
Float Life
2.50
2.45
2.40
2.35
2.30
2.25
2.20
2.15
2.10-20 -10 0 10 20 30 40 50
Temperature 0( C)
Equaling charge voltage for max. 16 hours
Float voltage +/- 1%
Ch
arg
e v
olt
ag
e (
V/c
ell
)
For continuous charging we recommend a voltage of 2.25 V.
The charging voltage must be compensated to the curve for
acontinuously different battery ambient temperature.
Cycle Life
Number of Cycles
Flo
at
life
(year)
5
10
15
20
020 25 30 35 40 45
oF
oC68 77 86 95 104 113
Charge voltage vs ambient temperature curve
DO
D(%
)
Temperature Effects in Relation to Battery Capacity
Temperature
Cap
acit
y(%
)
0.1CA
0.25CA
0.65CA
1CA
oF
oC
120
100
80
60
40
20
30-20 -10 0 10 20 40
86-4 -14 32 50 68 104
1500 2000 2500 3000 3500 4000 4500 5000
100
90
80
70
60
50
40
30
20
10