I n t ro t o Convent i ona l Fi re Ala rm Syst em s
1
I n t r o du ct i on t o
ConventionalFire Alarm Systems
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
2/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
2
Course Descriptionu This two-hour introductory course is forindividuals with little or no experience in the firealarm industry. The course covers the basic buildingblocks of modern conventional and addressable firealarm systems.
u It covers the primary and secondary functions ofa fire alarm control panel, various initiating and
notification devices, digital communicators,waterflow alarm and sprinkler monitoring.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
3/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
3
Course Contentsu Basic Elements of a Fire Alarm System
u Supplementary Functions
u Physical Elements of Fire
u Initiating Devices
u Notification Appliances
u Water Flow and Sprinkler Monitoring
u Types of Control Panels
u Design Issues
u Notification Appliance Circuit (NACs)
u Supplementary Circuit Wiring
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
4/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
4
Life Safety!
What is t he
pu rp ose o f a Fi re
Alarm Syst em ?
Detect, Alert and Evacuate.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
5/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
5
Basic Fire
Lets examine the
components that make abasic Fire AlarmControl System.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
6/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
6
Main Controlleru The brains of the system.
u
Provides power to thesystem, monitors inputs andcontrols outputs through
various circuits.
u Performs other functions asrequired by the appropriatecode.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
7/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7
Elements of a Control PanelMain Controller, Power, Inputs and Outputs
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
8/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
8
Primary (AC)
Secondary (DC)
Re q u i r e s t w o Po w e r So u r ce s
Elements of a Control Panel
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
9/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
9
Smoke Detector
Manual Pull Station
A fire alarmsystem can havea variety ofinput devices.
Elements of a Control PanelI n p u t s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
10/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
10
Inputs
u Initiating Device A system component that
originates transmission of a change of statecondition, such as a smoke detector, manual firealarm box, supervisory switch, etc....
u Initiating Device Circuit (IDC)A circuit towhich automatic or manual initiating devices areconnected where the signal received does notidentify the individual device operated.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
11/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
11
Horns
Strobes
Elements of a Control PanelO u t p u t s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
12/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
12
Outputs
u Notification Appliance A fire alarm systemcomponent such as a bell, horn, speaker, light,or text display that provides audible, tactile, orvisible output, or any combination thereof.
u Notification Appliance Circuit A circuit orpath directly connected to a notificationappliance.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
13/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
13
The Basic System
Secondary (DC)
Primary (AC)
Outputs
Inputs
Main Controller
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
14/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
14
Supplementary Operationsu Elevator Capture
u Equipment Shutdown
uAir Handling Shutdownu Damper Control
u Extinguishing SystemInterface
u Event Printing
u Display Monitor Interface
u Door Holding Devices
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
15/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
15
Supplementary Operationsu Remote Signal Annunciation - Provides
critical system status and basic control capabilityfrom a more convenient location than where thecontrol panel might be located.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
16/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
16
Remote AnnunciatorsRZA-5X
Remote Zone
Annunciator
LCD-80F LiquidCrystal Display
Graphic
Annunciator
(Custom)
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
17/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
17
DACTsUDACT Universal
Digital Communicator
Transmitter
Dedicated DACT
"daughterboard"411UD Slave/Stand
Alone DACT
Integral Onboard DACT
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
18/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
18
Basic Fire Alarm TechnologySignal Initiation & Initiating Devices
What i s
t h e
t h r ea t ?
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
19/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
19
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
20/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
20
Automatic Fire
Detectors
How do w e det e ct t h e t h r ea t ?
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
21/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
21
Automatic Fire Detectors
u Spot Detectors provide detection concentrationin a particular location - Heat & Smoke Detectors.
u Line Detectors provide continuous detectionalong a path - Thermal Cable & Beam Detectors.
u Air Sampling Systems draw air through pipes toan enclosed chamber for testing. - (VESDA & DuctDetectors.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
22/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
22
u Photoelectric
u Light-Scattering (Reflective)u Light-Obscuring (Beam)
u Ionization
u Thermal (heat)
u Duct
Automatic Fire Detectors
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
23/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
23
Photoelectric Smoke DetectorsLight-Scattering Type
u These detectors use a Light-Emitting Diode
(LED) that sends a beam of light into a darkchamber. A photo diode sits on the other side of apartition within the chamber.
u Smoke particles entering the chamber deflect
some of the light rays into the photocell. The photocell generates a current when exposed to light, andif the current reaches a certain level, the smokedetector alarms.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
24/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
24
Light Scattering PrincipalSensing Chamber
LightEmitting
Diode
Photo
Diode
Partition
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
25/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
25
Light Scattering Principal
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
26/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
26
u In a projected BeamDetector, alarms are
generated by diffusing theprojected light beam by a
specified percentage ofobscuration. Total beamblockage generally resultsin a trouble signal.
Photoelectric Smoke DetectorsLight Obscuration Type
u Wire the receiver unit as a 4-wire detector (separatepower and sensing connections to the control panel).
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
27/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
27
Projected Beam Principal
Transmitter Receiver
Smoke from the
fire in the protected
area diffuses the
intensity of the beam at the receiver
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
28/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
28
Ionization Smoke Detectors
u These detectors contain a small amount ofradioactive material encapsulated in a metalchamber. Ionizing radiation develops a low, butsteady electrical current. Smoke particles enteringthe chamber disrupt the current and trigger the
detector's alarm.
u Ion detectors react more quickly to fast flaming
fires that give off little smoke.
u Spot-type Detectors.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
29/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
29
DuctDetectors
u Photoelectric detector mounted in housingoutside the ductwork that has probes that
extend into the duct to sample the air insidethe duct.
u Primarily used as a smoke control device tocontrol the flow of air in ductwork.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
30/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
30
The i3 series is based on three guiding principles:Installation ease, Intelligence, and Instantinspection.
uPlug-In Head/Base combination.uSmoothing algorithms
uDrift compensation (automatically adjusts fordust accumulation, reducing nuisance alarms)
uOptional Sensitivity Reader
The i3 SeriesThis line of photoelectric smokedetectors by System Sensor consists of2- and 4-wire detectors, offered with or
without a fixed 135
temperaturethermal sensor.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
31/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
31
Manual Initiating DevicesThe Manual Fire Alarm Pull Station
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
32/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
32
Initiating DevicesManual Fire Alarm Stations
u Manually operated device used to
initiate an alarm signal.u Single Action Stations require a single
operation to activate it. Generally a pullingdown action.
u
Dual Action Stations require two distinctoperations. A set-up and an activating action.
u Breakglass Stations have an inhibit devicethat must be damaged to activate the station(non-ADA compliant).
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
33/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
33
Initiating DevicesManual Fire Alarm Stations
u Optional Features
u With and without key locks or hex key locks
u Weatherproof models with special backboxes
u With auxiliary contacts
u Multiple languages, even dual languages.
u With a pre-signal featureu With screw-terminal or pigtail connections
u Conventional and Addressable
u Metal or Polycarbonate
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
34/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
34
Single-Action Manual StationSpring-loaded
releasing
switch
Reset
Key
Actuation
Handle
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
35/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
35
Dual-Action Manual Station
Initial
Pre-Actuator
Actuator
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
36/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
36
Non Alarm Pull Stations
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
37/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
37
Heat DetectorsHeat detectors are the oldest type of automaticfire detection device. Not considered direct LifeSafety devices, these detectors do contributeto the detection of a fire.
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
38/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
38
Heat Detectorsu Fixed Detectors alarm when the sensing elementreaches a certain set point. Two common ones have135 and 200-degrees F range. The Fixed element isgenerally a non-restorable type, and when activated, must bereplaced.
u Rate-of-Rise Detectors respond when the rate oftemperature increase is greater than an allowable limit(15 degrees in 60 secs.) (placement in a stableenvironment) (e.g.. ovens, heating vents, etc.). The
Rate-of-Rise element is restorable when conditions return tonormal.
u Rate Compensation will respond regardless of therate of temperature rise.
I C i l Fi Al S
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
39/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
39
Heat DetectorsRate Compensation Type
u Detector responds when the temperature of the
surrounding air reaches a predetermined level,regardless of the rate oftemperature rise.
u The system compensates for Thermal Lag.
u During a slow rate of temperature rise there ismore time for heat to penetrate the inner element,which inhibits contact closure until the total devicereaches the rated temperature level.
u During fast rate of increase, there is less time forheat to penetrate the inner element, which exertsless inhibiting effect, so contact closure is still
obtained at the rated temperature.
I t t C t i l Fi Al S t
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
40/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
40
Heat Detectors
u DONT Paint Heat Detectors!!!
u Why? Because Thermal Lag occurswhen the physical properties of the Heat
detector cause it to lag behind the alarmcondition of the surrounding air.
I t t C t i l Fi Al S t
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
41/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
41
Heat Detectorsu Exhibit the lowest false alarm rate of all
automatic fire detector devices,
u Slowest-responding fire detection devices.
u Best used in applications where
u Fast-developing, large fires are expected.
u Environment won't allow the use of other
fire detection devices.u The speed of detection is not a prime
consideration.
I t t C t i l Fi Al S t
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
42/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
42
Heat DetectorsHeat Sensitive Cable
u A line-type initiating device whose sensing elementcomprises, in one type, two current-carrying wires
held separated by heat-sensitive insulation whichsoftens at the rated temperature, thus allowing thewires to make electrical contact.
u Installed at the exact point of risk to provide rapidlocalized detection of abnormal temperature rises(overloaded or short-circuited high voltage powerwiring).
I t t C t i l Fi Al S t
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
43/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
43
Heat DetectorHeat Sensitive Cable
Actuators
Outer Insulation
Protective Tape
Heat Sensitive
Material
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
44/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
44
Notification Appliances Types
uAudible - Horns, Bells, Sounders,
Sirens, Chimes, Speakers.
uVisual - Strobes
u Physical - Bed shakers
u Olfactory - Smell
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
45/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
45
Audible Devicesu Bells: Only used if they are only for
fire, or have a distinctive sound fromother bell signaling devices. Often
used as an external gong to indicatethe flow of water in the sprinklersystem.
u Horns: Loud and distinctive output.Often used in high-noiseenvironments, such as manufacturingplants.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
46/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
46
Audible Devicesu Sounders: Electronic or mechanical
audible devices, which are capable ofproducing a variety of tones. Often, thetone is selectable during installation ofthe device.
u Chimes: Soft-toned appliances usedwhere loud noises could be disruptive toother operations. Generally used wherequalified personnel are continuously inattendance.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
47/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
47
Audible Devices
u Sirens: Extremely loud devicesgenerally limited in use to outdoor
or heavy industrial areas.
u Speakers: Audible devices used inconjunction with voice evacuation
messages. Life-Safety speakers arenot generally associated with Muzak
systems.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
48/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
48
Audible Codesu Coded outputs are required in many applications.
This can be accomplished by pulsing tones for
different areas of the building, or zoning the outputs(floor above - floor below).
u General alarm codes commonly used are MarchTime (110-120 ppm) or Temporal code (ANSIEvacuation Code 3).
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
49/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
49
VisualSignaling
Appliances
Visual signaling appliances are used in high-noiseenvironments, in areas occupied by hearing-impaired individuals, or in areas where audibledevices may not be desired.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
50/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
50
VisualDevices
Speaker/Strobe
Chime/Strobe
Horn/Strobe
Strobe
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
51/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
51
Selectable-OutputVisual Devices
u Selectable Candela Output (15 - 30 - 60 -75 - 110)
u Selectable Operating Voltage (12 or 24 volts)
u Offered in Strobe and
Horn/Strobe combinations
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
52/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
52
Types of Power
u For powering the various devices connected to a fire
alarm system, control panels supply auxiliary power.There are two main types of power that you MUST be
aware of:u Full-Wave Rectified (Special Purpose) Power - Unregulated
output directly. High ripple voltage. Do n ot use for Sm oke Detec tors !Only use NAC devices listed for use with thistype of power.
u Filtered Regulated Power - Most stable output. Minimal ripplevoltage. Used for Smoke Detectors, and some remotesupplementary devices.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
53/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
53
Full-Wave Rectified Power
24v
0v
42v
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
54/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
54
Filtered Regulated Power
24v
0v
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
55/117
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
55
Secondary Power
u Direct Current - Clean, absolute filtered power
u Supplies the system with operating power underthe loss of primary (AC) for at least 24 hours ofstandby (quiescence) followed by 5 minutes in
alarm. Voice systems require 15 minutes in alarm.u Rated in AMP-HOURS (AH).
u Must be calculated!
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
56/117
t o t o Co e t o a e a Syst e s
56
Relays and Contactsu Form A - refers to a relay with contacts for common
and normally open ONLY.
u Form B - refers to a relay with contacts for commonand normally close ONLY.
u Form C - refers to a relay with contacts for common,normally open, and normally closed.
u Dry Contacts -By magnetically controlling the stateof the contacts, the control panel is electricallyisolated (and thus protected) from power connectedto the contacts..
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
57/117
y
57
Relays and Contacts
When a relay is not active,the contacts are in theirnormal position.
Normally Closed
Normally OpenCommon
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
58/117
y
58
Relays and Contacts
When the relay is activated,current passing through therelay coil magnetically
influences the common"wiper", moving it to theopposite position.
Normally Closed
Normally OpeCommon
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
59/117
y
59
Relays and Contacts
"Fail-Safe" relays areenergized during "normal"conditions. The relay isactivated by deenergizing
the coil, guaranteeingactivation of the desiredsignal during loss of allpower to the system.
Normally Closed
Normally Open
Common
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
60/117
y
60
InitiatingDevices
SprinklerSystems
Monitoring
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
61/117
61
u Wet-Pipe SprinklerSystems use a vane-activated Water Flow Device
(WFD) sized to the piping.The device reacts to a
change in flow pressure of10 psi, which is theequivalent of one sprinklerhead activating. Retarddevices inhibit falseactivation due to changes inwater supply pressure.
Fire Sprinkler Systems
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
62/117
62
WaterflowDetectors
Pressure
Gauges
TamperSwitches
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
63/117
63
u Dry-Pipe Sprinkler: An automatic sprinkler systemwhere all piping contains air under pressure. When asprinkler head opens, the air is released and waterflows into the system and through any opensprinkler heads into the fire. This type of system isused when freezing of water in the pipes is aconcern.
Fire Sprinkler Systems
u Dry-Pipe Sprinkler Systems use apressure switch. The device reacts to achange in pressure due to water fillingthe system.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
64/117
64
Sprinkler Monitoring
u Sprinkler Systems have water feed controlvalves. These control valves shut off the water supplyto the sprinkler system and render it useless. A
monitoring device should be attached to every criticalcontrol valve in the system, whether it's a gate valve,indicator valve, or butterfly valve. Whenever the valveis shut off, a supervisory alarm signal (as opposed to
a Fire or Waterflow alarm) is generated.
u The two most common types of SupervisoryTamper Switches are OSY and PIV.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
65/117
65
SprinklerMonitoringOS&Y
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
66/117
66
Sprinkler MonitoringPIV
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
67/117
67
The Systems
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
68/117
68
u Conventional (hard wired)u Fixed
u Programmable
uAddressable (multiplexed)
u Intelligent (analog data transfer)
Types ofFire Alarm Control Panels
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
69/117
69
u Simplest type of control unit.
u Generally, a single circuit board contains powersupply, control, initiating and notification circuitry.
u Some models use auxiliary circuit boards to performspecial functions.
u Input/output devices connect to dedicated circuits.
u Designated outputs occur when initiating signals are
received.u Limited special functions and capabilities.
Examples: Fire-Lite MS-2 and MS-4
Conventional Hard Wired System
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
70/117
70
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
71/117
71
AddressableSystem
u Each device (detector, pull station) has a uniquenumber assigned to it called the address for reportingalarms and troubles.
u Employs a Signaling Line Circuit (SLC) Loop along
which all addressable input and output devices areconnected to the fire alarm control panel.
u Addressable devices transmit an electronic message back tothe Control Unit representing their state (Normal, Alarm,Trouble) when polled by the Control Unit.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
72/117
72
Addressable Modules
These systems can also monitor conventionalinitiating devices using addressable monitormodules.
SLC Loop
24 VDCPower
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
73/117
73
Addressable Pull StationsAddressable
Module
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
74/117
74
TypicalSLC
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
75/117
75
Input-to-Output Mapping
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
76/117
76
Software Zoning
u Floor-Above/Floor Below
u Elevator Recall
u Smoke Control
u Ring-By-Zone
u Door Locks (Card Access)
u Cross Zoning
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
77/117
77
Intelligent System
uAlways an Addressable System.
u Processes detailed, analog data from
detectors about smoke levels.
u Can provide sensitivity data for eachdetector.
u Employs Drift Compensation (self calibration)
in it's detectors.
Examples: Fire-Lite MS-9200,
MS-9200UD & MS-9600.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
78/117
78
Design and Application
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
79/117
79
Design Issues
u Device Selectionu Photo vs. Ion, line versus spot.
u What is are the total costs of one type versus another?
u How does the environment affect device selection?
u Does the device meet code specifications and code?
u Placement of Devices (where do you place smokedetectors, pull stations, notification appliances)?
u Calculations (how do you calculate battery size and
NAC voltage drops?).u Programming (how will you accomplish your non-
general alarm events?).
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
80/117
80
Spot Detector Placement
u Total (complete) Coverage includes all rooms,halls, storage areas, basements attics, lofts, spaces
above suspended ceilings, and other subdivisions
and accessible spaces as well as the inside of allclosets, elevator shafts, enclosed stairways,dumbwaiter shafts and chutes.
NFPA 72 2002 Section 5.5.2.1
Exception - inaccessible areas that DO NOT containcombustible materials do not require smoke detection
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
81/117
81
Spot Detector Placement
u Partial Coverage calls for smoke detection in allcommon areas and work spaces, such as corridors,
lobbies, storage rooms, equipment rooms, and other
tenantless spaces.
The building owner must understand that a fire
alarm system may not detect a fire that developswithin any area without smoke detection until thatfire has reached proportions that may seriouslycompromise the safe evacuation of occupants andthe timely notification of fire responders.
CAUTION!
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
82/117
82
Spot Detector Placement
Smoke
Detector
30
21
Typical area
of room protection
Maximum
radius of
protectionSpot detector
placement isbased on centralmounting of adetector in a 30 X30 room. No areamay be more than
21 from thedetector.
21
30
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
83/117
83
Spot Detector Placement
SmokeDetector
10
21
Room Maximum
radius of
protectionNote that in this
application, twodetectors are notrequired becauseall areas within theroom are within 21feet of the
detector.
41
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
84/117
84
15 15
15 15
30
30
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
85/117
85
Heat Detector SpacingCeiling Height
(feet)
Percent (%) ofListed Spacing
0 -10
10-1212-14
14-16
16-18
18-20
20-22
22-24
24-26
26-28
28-30
100
9184
77
71
64
58
52
46
40
34
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
86/117
86
Initiating DevicesManual Fire Alarm Pull Stations
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
87/117
87
Manual Fire Alarm StationsMounting Locations
u Manual fire alarm stations shall be located within
5 feet of the exit doorway opening of each floor.
u Grouped openings over 40 feet in width requirepull stations on either side of the opening.
u Additional pull station will be installed no morethan 200 linear feet apart.
u Each manual fire alarm station shall beconspicuous, unobstructed, and accessible, and ofa contrasting color to the background on whichthey are mounted.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
88/117
88
Manual Fire Alarm Stations
u NFPA 72 - Mount pull station so that operable
part is 42" to 54" from the floor.
u ADA Accessibility Guidelines
u Forward reach: If access is only from aforward approach, mount 15-48.
u
Side reach: If clear space allows a parallelapproach, mount 9-54. If side reach is overan obstruction, use forward reach rules.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
89/117
89
Manual Fire Alarm Stations
The height is measured from the floor to thepoint of actuation.
48 Inches
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
90/117
90
Designing withNotification Appliances
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
91/117
91
ADA vs NFPA
u Conflicts exist betweenADA and
NFPA guidelines regardingrequirements for notification
appliances in fire alarm systems.u If the specifications call forADA
compliance, it is a federal law whichmust be obeyed.
u It is believed that newly-revisedADA Accessibility Guidelines willreference NFPA 72 2002.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
92/117
92
Ambient Noiseu Ambient Noise Level the level of noise
around us, or encircling us. Often referred
to as background noise.u Decibels (dB) Sound pressure is rated in
decibels, which is a unit for measuringrelative loudness.
u dBA - A dB scale referenced to theminimum pressure that can be detected bythe human ear.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
93/117
93
Ambient Noise
u 1 dBA (faintest audible sound)
Remember the hearing test?
u 50 dBA Typical conversation
u 80 dBA Alarm Clock
u 130 dBA (painful ear damage possible).
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
94/117
94
Typical Ambient Noise LevelsBusiness Occupancies 55 dBAEducational Occupancies 45 dBA
Industrial Occupancies 80 dBA
Institutional Occupancies 50 dBA
Mercantile Occupancies 40 dBAPiers and Water-Surrounded Structures 40 dBA
Places of Assembly 55 dBA
Residential Occupancies 35 dBAStorage Occupancies 30 dBA
Thoroughfares, High Density Urban 70 dBA
Thoroughfares, Medium Density Urban 55 dBAThoroughfares, Rural and Suburban 40 dBA
Tower Occupancies 35 dBAUnderground Structures and
Windowless Buildings
40 dBA
Vehicles and Vessels 50 dBA
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
95/117
95
Operating Modes
u Public Mode Audible or visible signalingto occupants or inhabitants of the areaprotected by the fire alarm system.
u Private Mode Audibleor visible signaling onlyto those persons directlyconcerned with the
implementation anddirection of emergencyaction initiation and procedure in the areaprotected by the fire alarm system.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
96/117
96
Audible Devices - Public Modeu NFPA: 15 dB above average ambient
sound level or 5 dB above maximum 60-second sound level, whichever is greater
(minimum of 75 dBA to a maximum of120 dBA).
u ADA: If provided, 15 dB above averageambient sound level or 5 dB above
maximum 60-second sound level,whichever is greater (maximum of 120dBA).
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
97/117
97
Audible Devices - Private Mode
u NFPA: Minimum of 45 dBA, maximum of120 dBA, at least 10 dB above average
ambient sound level or 5 dB abovemaximum 60-second sound level,whichever is greater.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
98/117
98
Visual Signaling Appliance
u Above 105 dbA: When the average ambientsound level is greater than 105 dbA, visualsignaling appliances are required.
u Indoor concertsu Drop forge shops
u Printing presses
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
99/117
99
Visual SignalingADA Requirements
u Americans with Disabilities Act sets provisionsfor visual appliances:
u Intensity minimum of 75 cd in non-sleeping areas,and 110 cd in sleeping areas.
u Lamp shall be a Xenon strobe type or equivalent.
u The color shall be clear or nominal white.u Pulse duration 0.2 sec. with a 40% duty cycle.
u Flash Rate 1 - 3 per second (1-3 Hz).
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
100/117
100
Wall-Mounted Appliances
NFPAu Wall mounted devicesshall have their bottoms atheights above the finishedfloor of not less than 80inches, and not greaterthan 96 inches.
u Maximum separation ofappliances shall not exceed100 feet.
ADA
u The appliance shall be placed80 inches above the highestfloor level within the space, or6 inches from the ceiling,whichever is lower.
u Devices shall be no morethan 50 ft. apart.
u
In large areas withoutobstructions 6 ft. above thefloor, devices may be spaced amaximum of 100 feet apart.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
101/117
101
Visual Device Installation
96"
80"
At least 80"
At
least
6"
NFPA
ADA 96"
80"
At least 80"
At
least
6"
NFPA
ADA
Strobe Horn/Strobe
At least 90"
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
102/117
102
Synchronization
u Visual Synchronization reduces the effect on those
who are prone to suffer seizures from Epilepsy.
u Required when two or more appliances are in thesame field of view.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
103/117
103
Synchronization
u Synchronization is effectedvia two means - a remotemodule or circuitry built intothe fire alarm control panel.
u Built-in control panelcircuitry is highly desirable.
u Audible Synchronization permits theproper sounding of evacuation coding.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
104/117
104
Distributed NACsu Use of a remote power supply can save previous
voltage in the run from the control panel to thestart of a Notification Appliance Circuit.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
105/117
105
Wiring Standards
u NFPA 72 establishes standards of
performance for various wiring styles forInitiation Circuits, Notification ApplianceCircuits and Signaling Line Circuit (SLC)Loop wiring.
u For Initiating Device Circuits Styles B & D.
u For Notification Appliance Circuits Styles Y & Z.u For SLC Loops Styles 4,6, & 7.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
106/117
106
u 2-wire circuit originates at the control unit,
interconnects all devices in parallel fashion
and terminates with an End-Of-LineResistor.
uA wire break results in a loss of all devices
past the break.u No branch tapping allowed.
Style B/Style Y( Class-B t yp e c ircu i t s)
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
107/117
107
Class B-Type Circuit
FACP
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
108/117
108
Style D/Style Z( Class-A t yp e c i rcu i t s )
u Wiring originates at the control unit,
interconnects all devices in parallel fashionand returns to the control unit.
u Return circuit monitors line voltage. Ifvoltage missing, return line will feed
current to devices from its connections.u No branch tapping allowed.
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
109/117
109
Class A-Type Circuit
FACP
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
110/117
110
u 4-wire Smoke Detectors are devices that receivepower from a source other than the InitiatingDevice Circuit.
u They may be wired inStyle B or Style D, andare supervised with anend-of-line power
supervision relay for lossof operating current.
4 Wire Smoke Detectors
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
111/117
111
4 Wire Detectors4-wire Smoke Detectors wired Style B
Initiating
Zone
4-Wire
Detector
Power
IDC (+)
IDC (-)
+24VDC
Common
UL Listed
PowerSupervisoryRelay
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
112/117
112
Questions?
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
113/117
113
Thank Youfor Attending!
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
114/117
114
Terminologyu FACP - Fire Alarm Control Panel.
u FACU - Fire Alarm Control Unit.
u FCC - Federal Communications Commission
u UL - Underwriters Laboratories
u NFPA - National Fire Protection Agency.u AHJ, LAHJ - Authority Having Jurisdiction, Local AHJ
u ADAAG - Americans with Disabilities Act AccessibilityGuidelines.
u PoC - Products of Combustion
u LED - Light Emitting Diode
u IDC - Initiating Device Circuit
u NAC - Notification Appliance Circuit
u ELR, EOL - End of Line Resistor
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
115/117
115
Terminologyu NEC - National Electrical Code (NFPA 70)
u NEMA - National Electrical Manufacturing Association
u EIA - Electronics Industry Association
u Cd - Candela
u dB, dBA - Decibelsu FWR - Full Wave Rectified
u ANSI - American National Standards Institute
u PIV - Post Indicator Valve
u
OS&Y - Outside Stem and Yoke Valvesu SFPE - Society for Fire Protection Engineers
u Shall - Indicates a mandatory requirement
u Should - Indicates a recommendation or advisement
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
116/117
116
References
u NFPA 70 - National Electrical Code
u NFPA 72 - National Fire Alarm Code
u NFPA 101 - Life Safety Code
u National Electrical Code Handbook, NFPA
u Life Safety Code Handbook, NFPA
u Fire Protection Handbook, NFPA
u Fire Alarm Signaling Systems, NFPA
I n t ro t o Convent i ona l Fi re Ala rm Syst em s
7/30/2019 83773741 Fire Alarm Systems El Benaa Com
117/117
Additional References
u Guide for Proper Use of System Smoke Detectors,System Sensor.
u Guide for Proper Use of Smoke Detectors in Duct
Applications, System Sensor.u Guide for Proper Use of Projected Beam Smoke
Detectors, System Sensor.
u Strobe Compliance Reference Guide, System
Sensor.