1/2
APPLICATION
The Det-Tronics DMC (Detector Multi-Channel) is a
weatherproof, multi-sensor process monitor that deliversreliable protection. The DMC accommodates up to36 channels of toxic/combustible gas and/or flame
monitoring, and offers panel selectable configuration ofsensor type, range, and alarm output level. Weighing
less than 9 pounds, the wall-mounted DMC enclosure iseasy to install and commission, and delivers exceptional
protection for a wide range of industrial applications.A number of system options are available including apreinstalled 24 Vdc power supply, special programming,
and communication protocols.
DESCRIPTION
The DMC system is an integrated programmable logic
controller (PLC), operator interface, I/O and networkingpackage. It utilizes a ladder-logic based control engineand features an Intel processor with speed comparable
to most mid-sized PLCs. The control unit uses a stackedinput/output module design that supports up to four I/O
modules in a single unit.
A DIN rail mounted interposing terminal strip is provided forall operating power, input, and output wiring connections.Internal power and I/O circuitry is distributed to the wiring
terminals. Fuse protection is provided on the main powerinput and all signal inputs. The DMC is compatible with
any 2 or 3-wire device that generates a 4-20 milliampereanalog signal. Alarm outputs are normally open SPST
contacts, rated 4.0 amps at 30 vdc or 250 vac (non-inductive).
The DMC system is field configured using the onboardkeypad and LCD display. Selectable detector types
include Combustibles, Cl2, ClO2, CO, H2S, HCN, NH3,
O2, PH3, SO2 and flame. A number of full scalemeasurement ranges per gas type are selectable. Highand Low Alarm levels are selectable for each channel.
An optional Flame detector channel designator is alsoselectable. Special channel designations are availableupon request.
Standard common alarm (OR-Gate) logic is provided for
the high alarm, low alarm, fault, horn, and strobe outputs.The horn and strobe outputs are driven by any low or
high level alarm. The horn can be immediately silenced
using the Silence Alarm key. Special logic programmingis available upon request. Logical cause/effect diagrams
are required prior to quotation.
Each DMC system is shipped with a system instructionand operations manual that includes mechanical andelectrical drawings showing all wiring terminations.
FEATURES
Standard models are available or up to 4, 12, 24 or 36
detection points
Accepts 4-20 mA inputs rom a wide variety o detector
types and measurement ranges
Password protected feld confguration o gas typesranges, alarm levels, and channels-in-service
Standard models provide common Low, HighFault, Horn and Strobe dry relay contact outputs
(5 total)
Rugged NEMA 4X/IP66 fberglass housing with clear
latching door
Available with or without 24 VDC power supply; our
dierent 24 VDC power supply options available
DIN rail mounted, use protected power distribution and
screw terminals or feld wiring connections
Backlit 2 line x 16 large character LCD display; time
tagging and logging o all alarms and aults provided
Two communication ports provided: RS-232 serial por
supporting MODBUS RTU slave or serial CsCANnetworks, and a CAN network supporting either
DeviceNet or CsCAN. Ethernet communicationoption is also available.
SPECIFICATION DATA
DMC (Detector Multi-Channel)
Process Monitor
1.1 Detector Electronics Corporation 2009 5/09 90-118
8/7/2019 90-1180-1.1_DMC
2/2
SPECIFICATIONS
MECHANICAL
MAXIMUM WEIGHT
19 lbs. (8.7 kg).
ENCLOSURE
NEMA 4X,IP66.
ENCLOSURE MATERIAL
Corrosion resistant fiberglass reinforced with polyesterwith transparent Lexan window.
TEMPERATURE RANGEOperating: +32F to +140F (0C to +60C).
Storage: +14F to +158F (10C to +70C).
HUMIDITY RATING5 to 95 % (non-condensing).
DIMENSIONSInches (Centimeters)
ELECTRICAL
INPUT POWER
AC Models: 100-120 VAC 2.5 A maximum
JumperSelectable: 200-240 VAC 1.5 A maximum
DC Models: 24 VDC power provided by customer
at sufficient current to enable propersystem operation (model specific).
POWER CONSUMPTION
NOTE
No gas detector power requirements are includ ed in above table. Total system
consumption must be calculated by adding
power consumption of The DMC and power
consumption of all installed gas detectors.
DMC Model Number Current Required
DMC-04-A-0-FN
DMC-12-A-0-FN
DMC-24-A-0-FN
DMC-36-A-0-FN
0.2 A
0.4 A
0.8 A
1.2 A
DMC Model Gas Detector Supply Current Available
DMC-04-A-1-FN
DMC-12-A-2-FN
DMC-24-A-3-FN
1.1 A
3.8 A
3.4 A
Models with internal 24 VDC power supply:
Models without internal 24 VDC power supply(DMC input voltage = 18 30 VDC):
10.0
(25.4)
6.6
(16.8)
12.8
(32.4)
14.75
(37.5)
15.5
(39.4)
0.32 DIA. x 4
A2213
Detector Electronics Corporation6901 West 110th Street Minneapolis, Minnesota 55438 USA
Operator: (952) 941-5665 or (800) 765-FIRE
Customer Service: (952) 946-6491 Fax (952) 829-8750
http://www.det-tronics.com E-mail: [email protected]
Specications subject to change without notice.
Det-Tronics the DET-TRONICS logo, and Eagle Quantum Premier are
registered trademarks or trademarks of Detector Electronics Corporation in
the United States, other countries, or both. Other company, product, or service
names may be trademarks or service marks of others.
Copyright Detector Electronics Corporation 2009. All rights reserved.
REGISTE
REDBYUL AN
DBS
I
NO.A2305NO.2582
6
ISO 9001REGISTEREDFIR
M
REG
ISTEREDF
IRM