90-1180-1.1_DMC

Embed Size (px)

Citation preview

  • 8/7/2019 90-1180-1.1_DMC

    1/2

    APPLICATION

    The Det-Tronics DMC (Detector Multi-Channel) is a

    weatherproof, multi-sensor process monitor that deliversreliable protection. The DMC accommodates up to36 channels of toxic/combustible gas and/or flame

    monitoring, and offers panel selectable configuration ofsensor type, range, and alarm output level. Weighing

    less than 9 pounds, the wall-mounted DMC enclosure iseasy to install and commission, and delivers exceptional

    protection for a wide range of industrial applications.A number of system options are available including apreinstalled 24 Vdc power supply, special programming,

    and communication protocols.

    DESCRIPTION

    The DMC system is an integrated programmable logic

    controller (PLC), operator interface, I/O and networkingpackage. It utilizes a ladder-logic based control engineand features an Intel processor with speed comparable

    to most mid-sized PLCs. The control unit uses a stackedinput/output module design that supports up to four I/O

    modules in a single unit.

    A DIN rail mounted interposing terminal strip is provided forall operating power, input, and output wiring connections.Internal power and I/O circuitry is distributed to the wiring

    terminals. Fuse protection is provided on the main powerinput and all signal inputs. The DMC is compatible with

    any 2 or 3-wire device that generates a 4-20 milliampereanalog signal. Alarm outputs are normally open SPST

    contacts, rated 4.0 amps at 30 vdc or 250 vac (non-inductive).

    The DMC system is field configured using the onboardkeypad and LCD display. Selectable detector types

    include Combustibles, Cl2, ClO2, CO, H2S, HCN, NH3,

    O2, PH3, SO2 and flame. A number of full scalemeasurement ranges per gas type are selectable. Highand Low Alarm levels are selectable for each channel.

    An optional Flame detector channel designator is alsoselectable. Special channel designations are availableupon request.

    Standard common alarm (OR-Gate) logic is provided for

    the high alarm, low alarm, fault, horn, and strobe outputs.The horn and strobe outputs are driven by any low or

    high level alarm. The horn can be immediately silenced

    using the Silence Alarm key. Special logic programmingis available upon request. Logical cause/effect diagrams

    are required prior to quotation.

    Each DMC system is shipped with a system instructionand operations manual that includes mechanical andelectrical drawings showing all wiring terminations.

    FEATURES

    Standard models are available or up to 4, 12, 24 or 36

    detection points

    Accepts 4-20 mA inputs rom a wide variety o detector

    types and measurement ranges

    Password protected feld confguration o gas typesranges, alarm levels, and channels-in-service

    Standard models provide common Low, HighFault, Horn and Strobe dry relay contact outputs

    (5 total)

    Rugged NEMA 4X/IP66 fberglass housing with clear

    latching door

    Available with or without 24 VDC power supply; our

    dierent 24 VDC power supply options available

    DIN rail mounted, use protected power distribution and

    screw terminals or feld wiring connections

    Backlit 2 line x 16 large character LCD display; time

    tagging and logging o all alarms and aults provided

    Two communication ports provided: RS-232 serial por

    supporting MODBUS RTU slave or serial CsCANnetworks, and a CAN network supporting either

    DeviceNet or CsCAN. Ethernet communicationoption is also available.

    SPECIFICATION DATA

    DMC (Detector Multi-Channel)

    Process Monitor

    1.1 Detector Electronics Corporation 2009 5/09 90-118

  • 8/7/2019 90-1180-1.1_DMC

    2/2

    SPECIFICATIONS

    MECHANICAL

    MAXIMUM WEIGHT

    19 lbs. (8.7 kg).

    ENCLOSURE

    NEMA 4X,IP66.

    ENCLOSURE MATERIAL

    Corrosion resistant fiberglass reinforced with polyesterwith transparent Lexan window.

    TEMPERATURE RANGEOperating: +32F to +140F (0C to +60C).

    Storage: +14F to +158F (10C to +70C).

    HUMIDITY RATING5 to 95 % (non-condensing).

    DIMENSIONSInches (Centimeters)

    ELECTRICAL

    INPUT POWER

    AC Models: 100-120 VAC 2.5 A maximum

    JumperSelectable: 200-240 VAC 1.5 A maximum

    DC Models: 24 VDC power provided by customer

    at sufficient current to enable propersystem operation (model specific).

    POWER CONSUMPTION

    NOTE

    No gas detector power requirements are includ ed in above table. Total system

    consumption must be calculated by adding

    power consumption of The DMC and power

    consumption of all installed gas detectors.

    DMC Model Number Current Required

    DMC-04-A-0-FN

    DMC-12-A-0-FN

    DMC-24-A-0-FN

    DMC-36-A-0-FN

    0.2 A

    0.4 A

    0.8 A

    1.2 A

    DMC Model Gas Detector Supply Current Available

    DMC-04-A-1-FN

    DMC-12-A-2-FN

    DMC-24-A-3-FN

    1.1 A

    3.8 A

    3.4 A

    Models with internal 24 VDC power supply:

    Models without internal 24 VDC power supply(DMC input voltage = 18 30 VDC):

    10.0

    (25.4)

    6.6

    (16.8)

    12.8

    (32.4)

    14.75

    (37.5)

    15.5

    (39.4)

    0.32 DIA. x 4

    A2213

    Detector Electronics Corporation6901 West 110th Street Minneapolis, Minnesota 55438 USA

    Operator: (952) 941-5665 or (800) 765-FIRE

    Customer Service: (952) 946-6491 Fax (952) 829-8750

    http://www.det-tronics.com E-mail: [email protected]

    Specications subject to change without notice.

    Det-Tronics the DET-TRONICS logo, and Eagle Quantum Premier are

    registered trademarks or trademarks of Detector Electronics Corporation in

    the United States, other countries, or both. Other company, product, or service

    names may be trademarks or service marks of others.

    Copyright Detector Electronics Corporation 2009. All rights reserved.

    REGISTE

    REDBYUL AN

    DBS

    I

    NO.A2305NO.2582

    6

    ISO 9001REGISTEREDFIR

    M

    REG

    ISTEREDF

    IRM