5/21/2018 99077475 SV POWER Lightning Protection Calculation Sheet T G Building
1/11
PROJECT : -
CLIENT :-
CLIENT'S CONSULTANT :-
E-BOP CONTRACTOR :-
i) Input Data :-a) Dimensions of Building / Structure
Length of the Building L = 60.00 m
Width of the Building W = 28.00 m
Height of the Building H = 23.00 m
b) Lightning Flash Density & Weighing FactorsNumber of Thunderstorm Days / Year N = 100 No. of Days / Year
Li htnin Flash Densit (Flashes to Ground /km2/ ear) Ng = 9.2 Nos./km
2/ ear
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
Weighting Factor B ( Type of Construction ) B ( Refer Table 1B of IS 2309 ) = 0.8
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
Overall Multiplying Factor = AxBxCxDxE = 0.096000
= 0.006526
ie 6.5260E-03
iii) Maximum Acceptable Overall Risk Factor:-
= 0.000001
ie 1.000E-06
iv) Result / Conclusion :-
>
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = = 1680 Meter2Perimeter of Structure P = = 176 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
= = 6 Nos
c) Based on Parimeter of Structure:-
= = 6 Nos.
Hence, Required Number of Down Conductors = 6 Nos.
Rev. Date Drg/Doc. No. Reviewed ApprovedR0 12.10.2009 KVP KVP
Probable Number of Strikes to Building / Structure per Year (
Refer Clause 8.1.2 of IS 2309 )
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
( REFERENCE : IS 2309 )
= 0.067979 Times per year
Collection Area ( Refer Clause 8.1.2 of IS 2309 )
P
=(L x W) + 2 (L x H) +
2(W x H) + 3.14 H2=
1+(Ab-100)/300
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Rf-C
Rf-AMaximum Acceptable Overall Risk Factor( Refer Clauses 8.1.3 &
8.1.6 of IS 2309 )
Hence, Lightning Protection is Required.
Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor
HK
7389.06 Meter2
Description / Parameter
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
Ac
Symbol / Formulae /
References
For Ab < 100m2
Number of Down Conductors Required
Overall Multiplying
Factor x P
( Refer Fig. 1 of IS 2309 )
Ac x Ng x 10-6
times/year
=
P/30
LIGHTNING PROTECTION CALCULATION FOR TG BLDG.AB-BC BAY
Overall Risk Factor Calculated
( L x W )2(L+W)
Number of Down Conductors Required
REVISION
DETAILS
3VYN855200
Value
=
Prepared
( Refer Clause 8.1.2 of
( Refer the Relevant Layout
Drawings of the Building /
Structure )
RemarksFirst Submission
1x 63 MW TPP AT KORBA,CHATTISGARH
S V POWER PVT LTD
DESEIN PVT LTD
ABB LTD,FARIDABAD
Unit
5/21/2018 99077475 SV POWER Lightning Protection Calculation Sheet T G Building
2/11
PROJECT : -
CLIENT :-
CONSULTANT :-
BOP CONTRACTOR :-
i) Input Data :-a) Dimensions of Building / Structure
Length of the Building L = 43.62 m
Width of the Building W = 12.20 m
Height of the Building H = 17.53 m
b) Lightning Flash Density & Weighing FactorsNumber of Thunderstorm Days / Year N = 27 No. of Days / Year
Li htnin Flash Densit (Flashes to Ground /km2/ ear) Ng = 5 Nos./km
2/ ear
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
Weighting Factor B ( Type of Construction ) B ( Refer Table 1B of IS 2309 ) = 0.2
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
Overall Multiplying Factor = AxBxCxDxE = 0.024000
= 0.000414
ie 4.1434E-04
iii) Maximum Acceptable Overall Risk Factor:-
= 0.000001
ie 1.000E-06
iv) Result / Conclusion :-
>
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = = 532.10 Meter2Perimeter of Structure P = = 111.63 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
= = 2 Nos
c) Based on Parimeter of Structure:-
= = 4 Nos.
Hence, Required Number of Down Conductors = 2 Nos.
Rev. Date Drg/Doc. No. Reviewed ApprovedR0 30.06.2009 PS PAS
REVISION
DETAILS
3VYN855200
RemarksFirst Submission
Prepared
1x70 MW TPP AT KORBA,CHATTISGARH
RRVUNL
DCPL, New Delhi
( Refer Clause 8.1.2 of
( Refer the Relevant Layout
Drawings of the Building /
Structure )
( Refer Fig. 1 of IS 2309 )
(L x W) + 2 (L x H) +
2(W x H) + 3.14 H2= 3452.79
RK
CW PUMP HOUSE
Meter2
Description / Parameter
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
Ac
Symbol / Formulae /
ReferencesValue Unit
=
Indure, New Delhi
For Ab < 100m2
=
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR
= 0.017264 Times per year
Collection Area ( Refer Clause 8.1.2 of IS 2309 )
P
Overall Multiplying
Factor x POverall Risk Factor Calculated
( L x W )2(L+W)
Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor
P/30
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
Number of Down Conductors Required
Number of Down Conductors Required 1+(Ab-100)/300
= Ac x Ng x 10-6
times/yearProbable Number of Strikes to Building / Structure per Year (
Refer Clause 8.1.2 of IS 2309 )
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Rf-C
Rf-AMaximum Acceptable Overall Risk Factor( Refer Clauses 8.1.3 &
8.1.6 of IS 2309 )
Hence, Lightning Protection is Required.
5/21/2018 99077475 SV POWER Lightning Protection Calculation Sheet T G Building
3/11
PROJECT : -
CLIENT :-
CONSULTANT :-
BOP CONTRACTOR :-
i) Input Data :-a) Dimensions of Building / Structure
Length of the Building L = 40.23 m
Width of the Building W = 30.23 m
Height of the Building H = 5.00 m
b) Lightning Flash Density & Weighing FactorsNumber of Thunderstorm Days / Year N = 27 No. of Days / Year
Li htnin Flash Densit (Flashes to Ground /km2/ ear) Ng = 5 Nos./km
2/ ear
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
Weighting Factor B ( Type of Construction ) B ( Refer Table 1B of IS 2309 ) = 0.2
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
Overall Multiplying Factor = AxBxCxDxE = 0.024000
= 0.000240
ie 2.3991E-04
iii) Maximum Acceptable Overall Risk Factor:-
= 0.000001
ie 1.000E-06
iv) Result / Conclusion :-
>
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = = 1216.15 Meter2Perimeter of Structure P = = 140.92 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
= = 5 Nos
c) Based on Parimeter of Structure:-
= = 5 Nos.
Hence, Required Number of Down Conductors = 5 Nos.
Rev. Date Drg/Doc. No. Reviewed ApprovedR0 30.06.2009 PS PAS
= Ac x Ng x 10-6
times/yearProbable Number of Strikes to Building / Structure per Year (
Refer Clause 8.1.2 of IS 2309 )
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Rf-C
Rf-AMaximum Acceptable Overall Risk Factor( Refer Clauses 8.1.3 &
8.1.6 of IS 2309 )
Hence, Lightning Protection is Required.
P/30
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
Number of Down Conductors Required
Number of Down Conductors Required 1+(Ab-100)/300
Overall Risk Factor Calculated
( L x W )2(L+W)
Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor
Indure, New Delhi
For Ab < 100m2
=
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR
= 0.009996 Times per year
Collection Area ( Refer Clause 8.1.2 of IS 2309 )
P
Overall Multiplying
Factor x P
Description / Parameter
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
Ac
Symbol / Formulae /
ReferencesValue Unit
=(L x W) + 2 (L x H) +
2(W x H) + 3.14 H2= 1999.25
Prepared
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
RRVUNL
DCPL, New Delhi
( Refer Clause 8.1.2 of
( Refer the Relevant Layout
Drawings of the Building /
Structure )
( Refer Fig. 1 of IS 2309 )
RK
Meter2
CW TREATMENT AREA
REVISION
DETAILS
3VYN855200
RemarksFirst Submission
5/21/2018 99077475 SV POWER Lightning Protection Calculation Sheet T G Building
4/11
PROJECT : -
CLIENT :-
CONSULTANT :-
BOP CONTRACTOR :-
i) Input Data :-a) Dimensions of Building / Structure
Length of the Building L = 33.30 m
Width of the Building W = 8.60 m
Height of the Building H = 10.70 m
b) Lightning Flash Density & Weighing FactorsNumber of Thunderstorm Days / Year N = 27 No. of Days / Year
Li htnin Flash Densit (Flashes to Ground /km2/ ear) Ng = 5 Nos./km
2/ ear
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
Weighting Factor B ( Type of Construction ) B ( Refer Table 1B of IS 2309 ) = 0.2
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
Overall Multiplying Factor = AxBxCxDxE = 0.024000
= 0.000185
ie 1.8510E-04
iii) Maximum Acceptable Overall Risk Factor:-
= 0.000001ie 1.000E-06
iv) Result / Conclusion :-
>
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = = 286.38 Meter2Perimeter of Structure P = = 83.8 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
= = 2 Nos
c) Based on Parimeter of Structure:-
= = 3 Nos.
Hence, Required Number of Down Conductors = 2 Nos.
Rev. Date Drg/Doc. No. Reviewed ApprovedR0 30.06.2009 PS PAS
REVISION
DETAILS
3VYN855200
RemarksFirst Submission
Prepared
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
RRVUNL
DCPL, New Delhi
( Refer Clause 8.1.2 of
( Refer the Relevant Layout
Drawings of the Building /
Structure )
( Refer Fig. 1 of IS 2309 )
(L x W) + 2 (L x H) +
2(W x H) + 3.14 H2= 1542.54
RK
RAW WATER PUMP HOUSE
Meter2
Description / Parameter
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
Ac
Symbol / Formulae /
ReferencesValue Unit
=
Indure, New Delhi
For Ab < 100m2
=
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR
= 0.007713 Times per year
Collection Area ( Refer Clause 8.1.2 of IS 2309 )
P
Overall Multiplying
Factor x POverall Risk Factor Calculated
( L x W )2(L+W)
Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor
P/30
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
Number of Down Conductors Required
Number of Down Conductors Required 1+(Ab-100)/300
= Ac x Ng x 10-6
times/yearProbable Number of Strikes to Building / Structure per Year (
Refer Clause 8.1.2 of IS 2309 )
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Rf-C
Rf-AMaximum Acceptable Overall Risk Factor( Refer Clauses 8.1.3 &
8.1.6 of IS 2309 )
Hence, Lightning Protection is Required.
5/21/2018 99077475 SV POWER Lightning Protection Calculation Sheet T G Building
5/11
PROJECT : -
CLIENT :-
CONSULTANT :-
BOP CONTRACTOR :-
i) Input Data :-a) Dimensions of Building / Structure
Length of the Building L = 22.80 m
Width of the Building W = 9.81 m
Height of the Building H = 5.00 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N = 27 No. of Days / Year
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km
2/year
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
Weighting Factor B ( Type of Construction ) B ( Refer Table 1B of IS 2309 ) = 0.2
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
Overall Multiplying Factor = AxBxCxDxE = 0.024000
= 0.000075
ie 7.5392E-05
iii) Maximum Acceptable Overall Risk Factor:-
= 0.000001
ie 1.000E-06
iv) Result / Conclusion :-
>
Calculations (As per Clause 12.2.3 of IS-2309):-Base Area of Structure Ab = = 223.67 Meter2
Perimeter of Structure P = = 65.22 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
= = 1 Nos
c) Based on Parimeter of Structure:-
= = 2 Nos.
Hence, Required Number of Down Conductors = 1 Nos.
Rev. Date Drg/Doc. No. Reviewed Approved
R0 30.06.2009 PS PAS
= Ac x Ng x 10-6
times/yearProbable Number of Strikes to Building / Structure per Year (
Refer Clause 8.1.2 of IS 2309 )
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Rf-C
Rf-AMaximum Acceptable Overall Risk Factor( Refer Clauses 8.1.3 &
8.1.6 of IS 2309 )
Hence, Lightning Protection is Required.
P/30
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
Number of Down Conductors Required
Number of Down Conductors Required 1+(Ab-100)/300
Overall Risk Factor Calculated
( L x W )
2(L+W)
Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor
Indure, New Delhi
For Ab < 100m2
=
LIGHTNING PROTECTION CALCULATION ( Reference : IS 2309 ) for
= 0.003141 Times per year
Collection Area ( Refer Clause 8.1.2 of IS 2309 )
P
Overall Multiplying Factor
x P
Description / Parameter
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
Ac
Symbol / Formulae / References Value Unit
=
(L x W) + 2 (L x H) +
2(W x H) + 3.14 H2= 628.27
Prepared
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
RRVUNL
DCPL, New Delhi
(Refer Clause 8.1.2 of IS 2309)
( Refer the Relevant Layout
Drawings of the Building /
Structure )
( Refer Fig. 1 of IS 2309 )
RK
Meter2
RWPH MCC Room
REVISION
DETAILS
3VYN855200
Remarks
First Submission
5/21/2018 99077475 SV POWER Lightning Protection Calculation Sheet T G Building
6/11
PROJECT : -
CLIENT :-
CONSULTANT :-
BOP CONTRACTOR :-
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR PRIMARY CRUSHER HOUSE
i) Input Data :-a) Dimensions of Building / Structure
Length of the Building L = 23.00 m
Width of the Building W = 21.50 m
Height of the Building H = 21.70 m
b) Lightning Flash Density & Weighing FactorsNumber of Thunderstorm Days / Year N = 27 No. of Days / Year
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km
2/year
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
Weighting Factor B ( Type of Construction ) B ( Refer Table 1B of IS 2309 ) = 0.2
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
Overall Multiplying Factor = AxBxCxDxE = 0.024000
= 0.000469
ie 4.6853E-04
iii) Maximum Acceptable Overall Risk Factor:-
= 0.000001
ie 1.000E-06
iv) Result / Conclusion :-
>
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = = 494.50 Meter2
Perimeter of Structure P = = 89 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
= = 2 Nos
c) Based on Parimeter of Structure:-
= = 3 Nos.
Hence, Required Number of Down Conductors = 2 Nos.
Rev. Date Drg/Doc. No. Reviewed ApprovedR0 30.06.2009 PS PAS
REVISION
DETAILS
3VYN855200
Remarks
First Submission
Prepared
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
RRVUNL
DCPL, New Delhi
(Refer Clause 8.1.2 of IS 2309)
( Refer the Relevant Layout
Drawings of the Building /
Structure )
( Refer Fig. 1 of IS 2309 )
Indure, New Delhi
RK
Description / Parameter
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
Ac
Symbol / Formulae / References Value Unit
=(L x W) + 2 (L x H) +
2(W x H) + 3.14 H2
Times per year
Collection Area ( Refer Clause 8.1.2 of IS 2309 )
P
Meter
2= 3904.39
= 0.019522
Overall Risk Factor Calculated
( L x W )
= Ac x Ng x 10-6
times/yearProbable Number of Strikes to Building / Structure per Year (
Refer Clause 8.1.2 of IS 2309 )
=Overall Multiplying Factor
x P
P/30
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
Number of Down Conductors Required
Number of Down Conductors Required 1+(Ab-100)/300
For Ab < 100m2
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Rf-C
Rf-AMaximum Acceptable Overall Risk Factor( Refer Clauses 8.1.3 &
8.1.6 of IS 2309 )
Hence, Lightning Protection is Required.
2(L+W)
Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor
5/21/2018 99077475 SV POWER Lightning Protection Calculation Sheet T G Building
7/11
5/21/2018 99077475 SV POWER Lightning Protection Calculation Sheet T G Building
8/11
PROJECT : -
CLIENT :-
CONSULTANT :-
BOP CONTRACTOR :-
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR SECONDARY CRUSHER HOUSE
i) Input Data :-a) Dimensions of Building / Structure
Length of the Building L = 38.00 m
Width of the Building W = 17.40 m
Height of the Building H = 24.20 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N = 27 No. of Days / Year
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km
2/year
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
Weighting Factor B ( Type of Construction ) B ( Refer Table 1B of IS 2309 ) = 0.2
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
Overall Multiplying Factor = AxBxCxDxE = 0.024000
= 0.000622
ie 6.2178E-04
iii) Maximum Acceptable Overall Risk Factor:-
= 0.000001
ie 1.000E-06
iv) Result / Conclusion :-
>
Calculations (As per Clause 12.2.3 of IS-2309):-Base Area of Structure Ab = = 661.20 Meter
2
Perimeter of Structure P = = 110.8 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
= = 3 Nos
c) Based on Parimeter of Structure:-
= = 4 Nos.
Hence, Required Number of Down Conductors = 3 Nos.
Rev. Date Drg/Doc. No. Reviewed Approved
R0 30.06.2009 PS PAS
Since Overall Risk Factor Calculated
Overall Multiplying Factor
x P
P/30
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
Number of Down Conductors Required
Maximum Acceptable Overall Risk Factor( Refer Clauses 8.1.3 &
8.1.6 of IS 2309 )
Hence, Lightning Protection is Required.
Number of Down Conductors Required 1+(Ab-100)/300
(Refer Clause 8.1.2 of IS 2309)
0.025907 Times per year=Probable Number of Strikes to Building / Structure per Year (
Refer Clause 8.1.2 of IS 2309 )
For Ab < 100m2
=
( L x W )
2(L+W)
Maximum Acceptable Overall Risk Factor
Rf-C
Description / Parameter
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
Ac
Symbol / Formulae / References Value Unit
Collection Area ( Refer Clause 8.1.2 of IS 2309 ) 5181.47 Meter2
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
RRVUNL
DCPL, New Delhi
Indure, New Delhi
Overall Risk Factor Calculated
P = Ac x Ng x 10-6
times/year
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Rf-A
REVISION
DETAILS
3VYN855200
Remarks
First Submission
( Refer the Relevant Layout
Drawings of the Building /
Structure )
( Refer Fig. 1 of IS 2309 )
RK
Prepared
=
(L x W) + 2 (L x H) +
2(W x H) + 3.14 H2=
5/21/2018 99077475 SV POWER Lightning Protection Calculation Sheet T G Building
9/11
PROJECT : -
CLIENT :-
CONSULTANT :-
BOP CONTRACTOR :-
i) Input Data :-a) Dimensions of Building / Structure
Length of the Building L = 41.00 m
Width of the Building W = 18.00 m
Height of the Building H = 19.00 m
b) Lightning Flash Density & Weighing FactorsNumber of Thunderstorm Days / Year N = 27 No. of Days / Year
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km
2/year
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
Weighting Factor B ( Type of Construction ) B ( Refer Table 1B of IS 2309 ) = 0.8
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
Overall Multiplying Factor = AxBxCxDxE = 0.096000
= 0.001974
ie 1.9745E-03
iii) Maximum Acceptable Overall Risk Factor:-
= 0.000001ie 1.000E-06
iv) Result / Conclusion :-
>
Calculations (As per Clause 12.2.3 of IS-2309):-
Base Area of Structure Ab = = 738.00 Meter2
Perimeter of Structure P = = 118 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
= = 3 Nos
c) Based on Parimeter of Structure:-
= = 4 Nos.
Hence, Required Number of Down Conductors = 3 Nos.
Rev. Date Drg/Doc. No. Reviewed ApprovedR0 30.06.2009 PS PAS
REVISION
DETAILS
3VYN855200
RemarksFirst Submission
Prepared
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
RRVUNL
DCPL, New Delhi
(Refer Clause 8.1.2 of IS 2309)
( Refer the Relevant Layout
Drawings of the Building /
Structure )
( Refer Fig. 1 of IS 2309 )
(L x W) + 2 (L x H) +
2(W x H) + 3.14 H2= 4113.54
RK
WAGON TIPPLER AREA
Meter
2
Description / Parameter
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
Ac
Symbol / Formulae / References Value Unit
=
Indure, New Delhi
For Ab < 100m2
=
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR
= 0.020568 Times per year
Collection Area ( Refer Clause 8.1.2 of IS 2309 )
P
Overall Multiplying Factor
x POverall Risk Factor Calculated
( L x W )
2(L+W)
Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor
P/30
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
Number of Down Conductors Required
Number of Down Conductors Required 1+(Ab-100)/300
= Ac x Ng x 10-6
times/yearProbable Number of Strikes to Building / Structure per Year (
Refer Clause 8.1.2 of IS 2309 )
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Rf-C
Rf-AMaximum Acceptable Overall Risk Factor( Refer Clauses 8.1.3 &
8.1.6 of IS 2309 )
Hence, Lightning Protection is Required.
5/21/2018 99077475 SV POWER Lightning Protection Calculation Sheet T G Building
10/11
5/21/2018 99077475 SV POWER Lightning Protection Calculation Sheet T G Building
11/11
PROJECT : -
CLIENT :-
CONSULTANT :-
BOP CONTRACTOR :-
i) Input Data :-a) Dimensions of Building / Structure
Length of the Building L = 15.50 m
Width of the Building W = 8.50 m
Height of the Building H = 5.00 m
b) Lightning Flash Density & Weighing Factors
Number of Thunderstorm Days / Year N = 27 No. of Days / Year
Lightning Flash Density (Flashes to Ground /km2/year) Ng = 5 Nos./km
2/year
Weighting Factor A ( Use of Structure ) A ( Refer Table 1A of IS 2309 ) = 1
Weighting Factor B ( Type of Construction ) B ( Refer Table 1B of IS 2309 ) = 0.2
Weighting Factor C ( Content of Consequential Effects ) C ( Refer Table 1C of IS 2309 ) = 1
Weighting Factor D ( Degree of Isolation ) D ( Refer Table 1D of IS 2309 ) = 0.4
Weighting Factor E ( Type of Country ) E ( Refer Table 1E of IS 2309 ) = 0.3
ii) Calculations :-
Overall Multiplying Factor = AxBxCxDxE = 0.024000
= 0.000054
ie 5.4030E-05
iii) Maximum Acceptable Overall Risk Factor:-
= 0.000001
ie 1.000E-06
iv) Result / Conclusion :-
>
Calculations (As per Clause 12.2.3 of IS-2309):-Base Area of Structure Ab = = 131.75 Meter2
Perimeter of Structure P = = 48 Meter
i) For Base Area (Ab) < 100m2
a) Number of Down Conductors Required = = 1 Nos
ii) For Base Area (Ab) > 100m2
b) Based on Base Area of Structure:-
= = 1 Nos
c) Based on Parimeter of Structure:-
= = 2 Nos.
Hence, Required Number of Down Conductors = 1 Nos.
Rev. Date Drg/Doc. No. Reviewed Approved
R0 30.06.2009 PS PAS
REVISION
DETAILS
3VYN855200
Remarks
First Submission
Prepared
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV)
RRVUNL
DCPL, New Delhi
(Refer Clause 8.1.2 of IS 2309)
( Refer the Relevant Layout
Drawings of the Building /
Structure )
( Refer Fig. 1 of IS 2309 )
(L x W) + 2 (L x H) +
2(W x H) + 3.14 H2= 450.25
RK
FOR DRIVE HOUSE
Meter2
Description / Parameter
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION
Ac
Symbol / Formulae / References Value Unit
=
Indure, New Delhi
For Ab < 100m2
=
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 )
= 0.002251 Times per year
Collection Area ( Refer Clause 8.1.2 of IS 2309 )
P
Overall Multiplying Factor
x POverall Risk Factor Calculated
( L x W )
2(L+W)
Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor
P/30
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS
Number of Down Conductors Required
Number of Down Conductors Required 1+(Ab-100)/300
= Ac x Ng x 10-6
times/yearProbable Number of Strikes to Building / Structure per Year (
Refer Clause 8.1.2 of IS 2309 )
Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309)
Rf-C
Rf-AMaximum Acceptable Overall Risk Factor( Refer Clauses 8.1.3 &
8.1.6 of IS 2309 )
Hence, Lightning Protection is Required.