ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing. Bulletin 1102C 400A Vacuum Contactor Vacuum Interrupter Phase Assembly Replacement Instructions (Cat 1102-VB4) Vacuum Interrupter Phase Assembly Replacement (Used with Vacuum Contactors: 1102C-COA93, -COB93, -COD93, -COG93, -COH93, -CON93) Cover Coil Leads Control-Pak Control-Pak Disconnect Coil Wires from Control-Pak Disconnect Coil Wires from Auxiliary Auxiliary VACUUM CONTACTOR 1. Disconnect all power cables (or bus work) and all control wiring to the contactor. 2. Remove the contactor from its mounted location. The contactor is best serviced in the tabletop position. 3. Remove the cover attachment hardware from the contactor and remove the cover (Figure 1). 4. Disconnect the coil wire leads from the Control-Pak or Auxiliary (Figure 2B). 5. Remove the Control-Pak from the contactor by first rotating the retainer to release the top tab of the Control- Pak. Then pull out the top of the Control-Pak (the tab must clear the notch) and then push Control-Pak slightly downward to release lower tab that holds the Control-Pak to the housing (Figures 2A & 2B). This tab must clear notch prior to pushing Control-Pak downward. Rotate retainer to release Control-Pak Figure 2A Figure 2B AC Coil (With Control-Pak) Figure 1 DC Coil (With Auxiliary 1195C-N5) VACUUM CONTACTOR Note: The following instructions pertaining to the removal and reinstallation of the Control-Pak are applicable to the Auxiliary.

A Bulletin 1102C 400A Vacuum Contactor Vacuum Interrupter ... · Vacuum Interrupter Phase Assembly Replacement (Cont'd) 6. Locate the replacement Interrupter Phase Assembly that needs

  • Upload
    others

  • View
    17

  • Download
    0

Embed Size (px)

Citation preview

Page 1: A Bulletin 1102C 400A Vacuum Contactor Vacuum Interrupter ... · Vacuum Interrupter Phase Assembly Replacement (Cont'd) 6. Locate the replacement Interrupter Phase Assembly that needs

ATTENTION: To prevent electrical shock, disconnect from power source before installing or servicing.

42052-094G. Ushakow

N/A

N/A

N/A42052

10064901

INSTRUCTION SHEETBULLETIN 1102C 400A VACUUM CONTACTORVACUUM INTERRUPTER PHASE ASSEMBLY

REPLACEMENT

2-19-04

Mark Jutz 2-19-04

D. Josef 2-19-04

1 2

42052-104

REVISION AUTHORIZATION

DIMENSIONS APPLY BEFORESURFACE TREATMENT

H

A

B

C

D

E

F

G

(DIMENSIONS IN INCHES)TOLERANCES UNLESSOTHERWISE SPECIFIED

REFERENCE

SHEET OFDWG.

B

DR.

CHKD.

APPD.

DATE

DATE

DATE±

±

±

ANGLES:

.XXX:

.XX:

THIS DRAWING IS THE PROPERTY OF THE ALLEN-BRADLEY CO. INC.

AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE EXCEPT

AS AUTHORIZED IN WRITING BY THE ALLEN-BRADLEY CO. INC.

LOCATION : MILWAUKEE, WISCONSIN U.S.A.

SIZE

1 2 3 4 5 6 7 8

E - DOC

Bulletin 1102C 400A Vacuum Contactor Vacuum Interrupter Phase Assembly Replacement Instructions(Cat 1102-VB4)

Vacuum Interrupter Phase Assembly Replacement (Used with Vacuum Contactors: 1102C-COA93,-COB93, -COD93, -COG93, -COH93, -CON93)

Cover

Coil Leads

Control-Pak

Control-Pak

Disconnect Coil Wires from Control-Pak Disconnect Coil Wires

from Auxiliary

Auxiliary

VACUUM CONTACTOR

1. Disconnect all power cables (or bus work) and all control wiring to the contactor.

2. Remove the contactor from its mounted location. The contactor is best serviced in the tabletop position.

3. Remove the cover attachment hardware from the contactor and remove the cover (Figure 1).

4. Disconnect the coil wire leads from the Control-Pak or Auxiliary (Figure 2B).

5. Remove the Control-Pak from the contactor by first rotating the retainer to release the top tab of the Control-Pak. Then pull out the top of the Control-Pak (the tab must clear the notch) and then push Control-Pak slightly downward to release lower tab that holds the Control-Pak to the housing (Figures 2A & 2B).

This tab must clear notch priorto pushingControl-Pak downward.

Rotate retainer torelease Control-Pak

Figure 2A Figure 2B

AC Coil (With Control-Pak) Figure 1 DC Coil (With Auxiliary 1195C-N5)

VACUUM CONTACTOR

Note: The following instructions pertaining to the removal and reinstallation of the Control-Pak are applicable to the Auxiliary.

Page 2: A Bulletin 1102C 400A Vacuum Contactor Vacuum Interrupter ... · Vacuum Interrupter Phase Assembly Replacement (Cont'd) 6. Locate the replacement Interrupter Phase Assembly that needs

42052-094G. Ushakow

N/A

N/A

N/A42052

10064901

INSTRUCTION SHEETBULLETIN 1102C 400A VACUUM CONTACTORVACUUM INTERRUPTER PHASE ASSEMBLY

REPLACEMENT

2-19-04

Mark Jutz 2-19-04

D. Josef 2-19-04

2 2

REVISION AUTHORIZATION

DIMENSIONS APPLY BEFORESURFACE TREATMENT

H

A

B

C

D

E

F

G

(DIMENSIONS IN INCHES)TOLERANCES UNLESSOTHERWISE SPECIFIED

REFERENCE

SHEET OFDWG.

B

DR.

CHKD.

APPD.

DATE

DATE

DATE±

±

±

ANGLES:

.XXX:

.XX:

THIS DRAWING IS THE PROPERTY OF THE ALLEN-BRADLEY CO. INC.

AND MAY NOT BE COPIED, USED OR DISCLOSED FOR ANY PURPOSE EXCEPT

AS AUTHORIZED IN WRITING BY THE ALLEN-BRADLEY CO. INC.

LOCATION : MILWAUKEE, WISCONSIN U.S.A.

SIZE

1 2 3 4 5 6 7 8

E - DOC

Vacuum Interrupter Phase Assembly Replacement (Cont'd)6. Locate the replacement Interrupter Phase Assembly that needs to be replaced. It is recommended that all three interrupters be replaced at the same time.

7. For the outer interrupters, remove the Retainer. While holding the Interrupter in position with the provided wrench, remove the screw from the line side terminal (Figure 3).

8. Remove the shunt screw from the load side terminal (See Section A-A). This will free the shunt. Carefully remove the interrupter assembly (Figure 4).

9. The replacement interrupter is factory set for contact gap and does not require adjustment. The flexible shunt will feed through the flexible shunt path in the molding of the contactor and the assembly can be pushed firmly back into place (See Figure 4 showing locations for applying hand pressure to snap interrupter into plastic molding), observe the adjacent phases to see precisely how this is positioned. While holding the Interrupter in position with the provided wrench, replace the line terminal screw (Figure 3). Replace the shunt connection hardware (Figure 4). Torque screw to 60 - 80 lb-inches.

10. Reinstall the Control-Pak (Figures 5A & 5B). First, insert the lower tab into the recess on the side of the contactor base. With proper installation, the Actuator will fit into the hole in the slot in the side of the contactor housing. Using a thin rod or flat blade, lift the Actuator up as necessary to insert it into the slot mentioned.

11. Reinstall the cover and secure it with the original mounting hardware. NOTE: Cover must fit under metal bracket on Control-Pak. Tighten the four screws in a diagonal pattern to 12 lb-inches. (Figure 1).

12. Reattach the coil wire leads and any auxiliary control wires to the Control-Pak (tighten to 7 lb-inches).

13. Reinstall the contactor. Torque mounting screws to 50 - 75 lb-inches.

14. Reconnect the line and load conductors and tighten the main terminal hardware and bolts to 180 - 210 lb-inches.

Figure 5A Figure 5B

42052-094-01 (1)Printed in U.S.A.

Figure 3 Figure 4

Shunt

Shunt

SECTION A-A

A

A

Special wrenchsupplied with kit

Retainer

Actuatormust fit into slot shown

Control-PakActuator

Auxiliary Control-Pak

Thin rod orflat blade

ShuntScrew

ShuntScrew

InterrupterPhase Assembly

TerminalScrew

Pressure points for interrupter installation

PARTNO. MATERIALCHG.

LTR. SIZEFLAT FOLD

-01 1ONE SIDE PRINTED

8-1/2" W x 11" HBODY STOCK WHITEBODY INK BLACK

4-1/4" W x 5-1/2" H