ABB Photovoltaic Disconnectors

  • Upload
    bog-pen

  • View
    216

  • Download
    0

Embed Size (px)

Citation preview

  • 7/27/2019 ABB Photovoltaic Disconnectors

    1/618 | ABB solutions for solar energy - Low Voltage Products

    ProductsSwitch-disconnectors S800PV-M

    S800PV-M switch-disconnectors can be used in networks up to 1200 V

    DC S800PV-M was specially designed for the use in PV applications as

    it safely switches DC arcs. Disconnector features are:

    -compact design

    -derating-free up to 60C

    -safe disconnection of all poles

    -polartity independent

    -wide range of accessories

    -remote controllable with S800-RSU remote switching unit

    Main technical specifications S800PV-M

    Reference Standards IEC EN 60947-3

    Rated current A 32, 63, 125

    Number of poles 2, 3, 4

    Rated voltage Ue

    (DC) 2 poles*

    (DC) 3 poles*

    (DC) 4 poles*

    V

    V

    V

    800

    1200

    1200

    Rated short-time withstand current Icu

    (DC) 2 poles * 800 V

    (DC) 3 poles * 1200 V

    (DC) 4 poles * 1200 V

    kA

    kA

    kA

    1.5

    1.5

    1.5

    Rated insulation voltage V 1500

    Class of use DC-21 A

    Operating temperature C -25+60

    Mounting on DIN rail EN 60715

    (35 mm) by means of fast

    clip device

    Accessories shunt opening re leases,

    undervoltage releases,

    signal / auxiliary contacts,

    rotary drive adapter and

    rotary handle remote

    switching unit

    * Please refer to the wiring diagrams

    Earthed network

    Non-earthed network

    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

    http://www.clrwtr.com/ABB-Photovoltaic.htmhttp://www.clrwtr.com/ABB-Photovoltaic.htm
  • 7/27/2019 ABB Photovoltaic Disconnectors

    2/6ABB solutions for solar energy - Low Voltage Products | 19

    ProductsSwitch-disconnectors OT

    OT switch-disconnectors are available from 16 A to 600 A up to

    1000 V DC. OT series from 16 to 40 A are an ideal solution for string

    boxes in residential applications and/or residential inverters where

    reliable isolation is required and safety is a must.

    OT series from 200 to 630 A are a cost-effective solution either for string

    boxes in commercial/large-scale installations or inside central inverters

    where they provide reliable isolation while simplifying maintenance and

    improving overall safety.

    Main features include:-Reliable position indication

    -Contact opening non-dependent on speed of operation

    -Wide range of accesories

    Main technical specifications OT (16-40) OT (200-630)

    Reference Standards IEC EN 60947-3 IEC EN 60947-3

    Rated Current I n A 16* , 25 , 32 200, 315, 400, 600

    Number of poles in series 6 8 5 6

    Rated voltage Ue V 550 750 800 1000

    Utilization category DC 21 A DC 21 B

    Operating temperature C -25+45 -25+45

    * OT16F8 can reach 16 A at 800 V DC

    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

  • 7/27/2019 ABB Photovoltaic Disconnectors

    3/6

    Product noteTmax PV: photovoltaic rangeT Generation

    Tmax PVincludes all the advantages of the T Generation:

    excellent performance-dimensions

    vast and complete range of accessories for all requirements

    complete remote control

    The average generating capacity of photovoltaic installa tions

    is increasing every day, in all parts of the world.

    When it comes to large photovoltaic production installations

    (over 200 kWp), the power installed has continued to increaseat an incredible pace over the last period, and at a higher rate

    than that of small and medium-sized installations.

    When the power generated by a photovoltaic production sys-

    tem exceeds a certain level and use of a low voltage switch-

    disconnector is required, Tmax PVmoulded-case switch-

    disconnectors are suitable for the purpose.

    Tmax PVis the latest T Generation product: from 0 to 1600

    A , up to 1100 V DC.Tmax PVpossesses IEC 60947-3 certification.

    Tmax PVincludes 6 different sizes: from the compact T1(which can be mounted on DIN rail) to the high-performance

    T7, avai lable in the two versions, wi th lever operating mecha-

    nism and motor operator.

    Technical Characteristics

    Tmax PV switch-disconnectors in compliance with theIEC60947-3

    T1D PV T3D PV T4D PV T5D PV T6D PV T7D PV

    Conventional thermal current, Ith [A] 160 250 250 630 800 1600

    Rated service current in category DC22 B, Ie [A] 160 200 250 500 800 1600

    Rated service voltage, Ue [V] 1100 V DC 1100 V DC 1100 V DC 1100 V DC 1100 V DC 1100 V DC

    Rated impulse withstand voltage, Uimp [kV] 8 8 8 8 8 8

    Rated insulation voltage, Ui [V] 1150 V DC 1150 V DC 1150 V DC 1150 V DC 1150 V DC 1150 V DC

    Test voltage at industr ial f requency for 1 minute [V] 3500 3500 3500 3500 3500 3500

    Rated short-circuit making capacity,switch-disconnector only, Icm [kA] 1.5 2.4 3 6 9.6 19.2

    Rated short-time withstand current for 1s, Icw [kA] 1.5 2.4 3 6 9.6 19.2

    Versions F F F F F F

    Terminals FC Cu FC Cu FC Cu FC Cu FC CuAl FC CuAl

    Mechanical life [No. operations] 25000 25000 20000 20000 20000 10000

    Mechanical life [No. Hourly operations] 120 120 120 120 120 60

    Tmax PVreaches a rated insulation voltage up to 1150 V DC.

    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

  • 7/27/2019 ABB Photovoltaic Disconnectors

    4/6

    Tmax PVoperating devices are the first moulded-caseswitch-disconnectors for high direct voltage available on the

    market.

    They are of certa in interest for all types of photovol taic instal-

    lation, where they are the ideal answer for every disconnect-

    ing requiremen.

    Tmax PVmoulded-case switch-disconnectors can be used in

    both parallel switchgears and inverter switchgears.

    When used in inverter switchgears, Tmax PVmakes it abso-lutely simple to coordinate the direct side and the alternate

    side: the same circuit-breaker can be used for both the DC

    and AC sides.

    Moreover, Tmax PVequipment, which are manufactured

    and tested in accordance with Standard IEC 60947-3, can

    be used for mixed resistive-inductive loads in all low voltage

    installations with 1100 V DC and 1600 A rated current.

    Tmax PV: photovoltaic range

    T Generation

    The widest choice, thanks to Tmax PVfordisconnecting the DC side of the inverter, fromjust a few Amperes to 1600 A rated current.ABB is already a partner of some of the mostimportant inverter manufacturers in the world.

    T1D PV

    First level:string protection

    Second level:parallel switchgear

    Third level:

    inverter disconnectionon the DC side

    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

  • 7/27/2019 ABB Photovoltaic Disconnectors

    5/6

    Examples of other applications in which Tmax PVswitch-

    disconnectors can be efficiently used:

    Electric traction

    at the present time, public urban transport vehicles (trolley-

    buses, streetcars, subway trains) often run on DC power at

    600 to 1000 V voltage ratings

    UPS applications

    use of uninterruptible power suppliers is becoming more

    Since it is small in size, T1D PVcan be

    easily installed in the parallel switchgear(also called combiner box).

    T1D PV

    From T1D PV to T7D PVUp to 1100 V DC

    Inverter

    From T1 to T7(also with residual current protection)

    Transformer

    and more widespread in various types of installation: hospi-

    tals, for emergencies (lights, alarms), servers, data cent-

    ers...

    Special industrial applications

    such as: electric arc furnaces, electric welding systems,

    metal refining plants (aluminium, zinc)

    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

  • 7/27/2019 ABB Photovoltaic Disconnectors

    6/6

    The order codes for TMAX PV are listed in the table

    below:

    As described, the switch-disconnectors are always sup-

    plied with front terminal clamps for copper cables or copper/

    aluminium cables: moreover, depending on the size, they are

    also complete with accessories, such as insulating plates,

    terminal covers or phase separators.

    Valid for T1D PV, T3D PV, T6D PV and

    T7D PV

    Valid fo r T4D PV and T5D PV Valid for al l Tmax PV s izes

    L O A D

    L O A D L O A D

    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]

    Code Code description Version/Poles

    1SDA066881R1 T1D 160 PV 4p F FC Cu 1100 V DC Fixed / 4p

    1SDA066882R1 T3D 200 PV 4p F FC Cu 1100 V DC Fixed / 4p

    1SDA066883R1 T4D 250 PV 4p F FC Cu 1100 V DC Fixed / 4p

    1SDA066884R1 T5D 500 PV 4p F FC Cu 1100 V DC Fixed / 4p

    1SDA066885R1 T6D 800 PV 4p F FC CuAl 1100 V DC Fixed / 4p

    1SDA066886R1 T7D 1600 PV 4p F FC CuAl 1100 V DC Fixed / 4p1SDA066887R1 T7D1600 PV 4p F FC CuAl M 1100 V DC Fixed / 4p