Upload
kyna
View
82
Download
9
Embed Size (px)
DESCRIPTION
AC Interference. Columbia Gas of Ohio/Kentucky Tim Jenkins Corrosion Front Line Leader. Objectives. Develop a basic understanding of the principles and components of AC Develop an understanding of the different types and effects of AC Influence Develop methods of mitigation - PowerPoint PPT Presentation
Citation preview
AC InterferenceAC InterferenceAC InterferenceAC Interference
Columbia Gas of Ohio/Kentucky
Tim JenkinsCorrosion Front Line Leader
ObjectivesObjectivesObjectivesObjectives Develop a basic understanding of Develop a basic understanding of
the principles and components of ACthe principles and components of AC Develop an understanding of the Develop an understanding of the
different types and effects of AC different types and effects of AC Influence Influence
Develop methods of mitigation Develop methods of mitigation Understand safety protocols Understand safety protocols Cover AC calculationsCover AC calculations
Basic Electric - ACBasic Electric - ACBasic Electric - ACBasic Electric - AC
0
Half Cycle
Half Cycle
Peak of positive side of cycle.
Peak of negative side of cycle
00
AC - alternating current will reverse in polarity 120 times per second. A full cycle is considered one hertz. Typical AC has 60 hz per second.
SINE WAVESINE WAVE
Single PhaseSingle Phase
Basic Electric - ACBasic Electric - ACBasic Electric - ACBasic Electric - AC
0
Half Cycle
Half Cycle
Peak of positive side of cycle.
Peak of negative side of cycle
00
AC – Three Phase, each conductor has the same amount of current and are 120 degrees out of phase
SINE WAVESINE WAVE
Three PhaseThree Phase
If any of the AC waveforms are to get of frequency with each other greater than or less than 120°, then a possible fault current can occur.
Fault currents are large magnitude of current that can occur in brief amount of time (normally in milliseconds, typically .1 second) Normally electrical towers or structure has
grounding and protection devices for this situation that limits the fault current to a brief amount of time
Fault CurrentsFault CurrentsFault CurrentsFault Currents
It’s not possible to know whenn, how or how or wherewhere fault currents will occur, in which makes it difficult to predict the effects of the fault and the mitigation required to protect both the pipeline and personnel
Need to calculate locations of more acceptable for fault currents to occur, such as – Electrical storms, ice storms, & high winds Distance from the Power lines Information provided from the electric
company
Fault CurrentsFault CurrentsFault CurrentsFault Currents
Even though the fault current is brief, it still presents a danger to personnel and the pipeline Coating damage can occur Pipeline failure due to melting or
cracking of the pipeline wall Discuss more in Conductive
coupling
Fault CurrentsFault CurrentsFault CurrentsFault Currents
Three Phase –
Three conductorsShielded wiresCounterpoise Lines – Counterpoise Lines –
Used for the grounding Used for the grounding system, normally system, normally buried and above buried and above connected to each connected to each tower to provide tower to provide groundinggrounding
Counterpoise Lines – Counterpoise Lines – Used for the grounding Used for the grounding system, normally system, normally buried and above buried and above connected to each connected to each tower to provide tower to provide groundinggrounding
Method of measuring AC voltage on Structures Connect to ground with one lead and measure
the AC volts onto the structure with the other lead.
Use an accurate volt meter, set meter on AC volts
Use rubber gloves during measurement and/or Use a rubber mat for added insulation High dielectric boots are available as well
Common method, use a copper-copper sulfate half cell with the meter set at AC volts
Must have good soil contact with half cell
Effects of AC InfluenceEffects of AC InfluenceEffects of AC InfluenceEffects of AC Influence
Two key factors to consider with Two key factors to consider with AC InfluenceAC Influence Safety Safety CorrosionCorrosion
Effects of AC InfluenceEffects of AC InfluenceEffects of AC InfluenceEffects of AC Influence
Two key factors to consider with Two key factors to consider with AC InfluenceAC Influence Safety Safety CorrosionCorrosion
SafetySafetySafetySafety
Electrical ShocksElectrical Shocks Step voltagesStep voltages Touch voltagesTouch voltages
Arcing Arcing Ignition of volatile liquids Ignition of volatile liquids
SafetySafetySafetySafety Maximum allowable AC voltage = 15
Vac Based on a typical individual is at 1000
ohms body resistance And the individual can tolerate up to 15
mA Ohms law = 15 volts Anything above 15 Vac, could cause
muscular contractions Prevents the person from letting go
SafetySafetySafetySafety Electrical Shock, such as fault currents
Can occur by physical contact or standing in the vicinity of an energize structure in contact with earth
Short time frames of electrical shocks are a concern when currents are above 50mA or greater
Can cause ventricular fibrillation Certainly occurs at body currents of
greater than 100 mA Death will occur unless De-
fibrillation is given
SafetySafetySafetySafety Electrical ShockElectrical Shock
Fault currents - passes from the structure Fault currents - passes from the structure to ground creating a voltage gradientto ground creating a voltage gradient
Step Voltage – Step Voltage – Is the potential difference between two points Is the potential difference between two points
on earth’s surface separation by a distance of on earth’s surface separation by a distance of 1 pace (approx. 1 meter) in the direction of 1 pace (approx. 1 meter) in the direction of max. potential gradientmax. potential gradient
Touch Voltage – Touch Voltage – Potential difference between the grounded Potential difference between the grounded
metallic structure and the point of earth’s metallic structure and the point of earth’s surface separated by a distance equal to the surface separated by a distance equal to the normal maximum horizontal reach (approx. 1 normal maximum horizontal reach (approx. 1 meter)meter)
SafetySafetySafetySafety
9 kV8 kV
7 kV
Potential Touch voltage = 2kV
Potential Touch voltage = 2kV
Ouch!!!
I (Fault Current)
10 kV
f
SafetySafetySafetySafety I (Fault Current)
9 kV 8 kV 7 kV
10 kV
Potential Step voltage = 1kV
Potential Step voltage = 1kV
Ouch!!!f
Safety – Safety – (Maximum Current (Maximum Current Calculation)Calculation)
Safety – Safety – (Maximum Current (Maximum Current Calculation)Calculation)
Maximum current IMaximum current IB B a human body a human body can tolerate depends on shock can tolerate depends on shock duration tduration ts s (seconds) and body weight (seconds) and body weight
calculated as follows:calculated as follows: IIBB = = 0.157/ 0.157/ ts ts ( for a 70 kg body)( for a 70 kg body) IIBB = = 0.116/ 0.116/ tsts ( for a 50 kg body) ( for a 50 kg body)
Safety – Safety – Step and Touch Voltage Step and Touch Voltage CalculationCalculation
Safety – Safety – Step and Touch Voltage Step and Touch Voltage CalculationCalculation
Maximum voltage that human body Maximum voltage that human body can tolerate by touch or step – can tolerate by touch or step –
Step formula - Step formula - VVStepStep = (1000 + 6 = (1000 + 6) 0.157/ 0.157/ ts ts ( for a 70 kg body)( for a 70 kg body) VVSSteptep = (1000 + 6 = (1000 + 6) 0.116/ 0.116/ tsts ( for a 50 kg body) ( for a 50 kg body)
Touch formula - Touch formula - VVTouchTouch = (1000 + 1.5 = (1000 + 1.5) 0.157/ 0.157/ tsts ( for a 70 kg body)( for a 70 kg body) VVTouchTouch = (1000 + 1.5 = (1000 + 1.5) 0.116/ 0.116/ tsts ( for a 50 kg body)( for a 50 kg body)
Pipe line running parallel to a power line may exhibit 500 volts for a duration of ½ second during line to ground fault
What is the tolerable touch voltage for a 50 kg individual with a soil resistivity of 50 ohms m touching the structure during the fault?
Safety – Safety – Step and Touch Voltage Step and Touch Voltage CalculationCalculation
Safety – Safety – Step and Touch Voltage Step and Touch Voltage CalculationCalculation
VVTouchTouch = (1000 + 1.5 = (1000 + 1.5) 0.116/ 0.116/ tsts - - ( for a 50 kg body)( for a 50 kg body) VVTouchTouch = (1000 + 1.5 = (1000 + 1.5 • • 50) 0.116/ 0.116/ (.5) (.5) = 176 VAC= 176 VAC
Since the possible fault voltage is 500 V then we need to raise the soil resistance
Try 3000 Ω-m of crush stone added to the site
Now the calculation equals to 902 VAC902 VAC Which exceeds the maximum pipe to earth Which exceeds the maximum pipe to earth
voltage of voltage of 500 VAC500 VAC, the pipe is now safe, the pipe is now safe
Voltage gradient matsVoltage gradient mats could provide a higher could provide a higher earth voltage to decrease the potential difference earth voltage to decrease the potential difference between the hand or feet touching the pipebetween the hand or feet touching the pipe
Safety – Safety – Step and Touch Voltage Step and Touch Voltage CalculationCalculation
Safety – Safety – Step and Touch Voltage Step and Touch Voltage CalculationCalculation
SafetySafetySafetySafety I (Fault Current)
10 kV
10 kV
7 kV
10 kV
Potential Step voltage = 0 kV
Potential Step voltage = 0 kV
Cool !!!f
Voltage gradient Mat = 10 kV
Voltage gradient Mat = 10 kV
Gradient control Gradient control mats – Placed at mats – Placed at all test station all test station locations in the locations in the AC CorridorAC Corridor
Gradient control Gradient control mats – Placed at mats – Placed at all test station all test station locations in the locations in the AC CorridorAC Corridor
Zinc Grounding Zinc Grounding MatMatZinc Grounding Zinc Grounding MatMat
12” crushed gravel
6” Low resistance material – Coke breeze or benonite
6” Low resistance material – Coke breeze or benonite
Note : You can use the native soil, providing soil has good moisture content
Cut hole for Test station
Dimensions = 4’x4’
Zinc ribbon
Wire connected to the zinc ribbon
Zinc Grounding Zinc Grounding MatMatZinc Grounding Zinc Grounding MatMat Wire
connected to the zinc ribbon
Connected Connected to pipeline to pipeline in Test in Test station boxstation box
Connected Connected to pipeline to pipeline in Test in Test station boxstation box
Copper Copper rods rods installed installed to get to get low low resistancresistance with e with groundingrounding matg mat
Copper Copper rods rods installed installed to get to get low low resistancresistance with e with groundingrounding matg mat
One of the greatest concern in dealing with fault currents between a power line structure and the pipeline is whether or not there is enough energy available to create an electric arc through the soil.
Could result in pipeline damage
Safety Safety (Calculation for Arcing)(Calculation for Arcing)Safety Safety (Calculation for Arcing)(Calculation for Arcing)
Greatest prevention of Arcing with fault currents is to maintain safe distance between power lines and the pipeline
One must obtain information from the electric company or producer such as fault currents maximum measurements
Need to find soil resistivity in area Perform sufficient amount of testing
samples in order to accurate obtain average
Safety Safety (Calculation for Arcing)(Calculation for Arcing)Safety Safety (Calculation for Arcing)(Calculation for Arcing)
One Safe distance calculation by Sunde - for prevention of arcing
Distance r (m) over which an arc could occur, based on soil resistivity in (Ω-m) and fault magnitude If (kA).
Safety -Safety -(Calculation for Arcing)(Calculation for Arcing)Safety -Safety -(Calculation for Arcing)(Calculation for Arcing)
R(m) = 0.08 Use this formula with lower resistivity
R(m) = 0.047 If • ( = > 1000-m) Use this formula with extremely high
resistivity R(m) = Distance measured in meters If = Magnitude of fault current = Soil resistivity measured in
meters
Safety -Safety -(Calculation for Arcing)(Calculation for Arcing)Safety -Safety -(Calculation for Arcing)(Calculation for Arcing)
If • ( = < 100-m)
For an example, Soil = 6700 ohms-cm = 67 ohms
-m Fault Current If =17.9 kA Use formula R(m) = 0.08 R(m) = 87.6 meters
Safety -Safety -(Calculation for Arcing)(Calculation for Arcing)Safety -Safety -(Calculation for Arcing)(Calculation for Arcing)
If • ( = < 100-m)
Pipeline
Fault Currents
Lightening
90 Meters
PipelineFault Currents
Lightening
90 Meters
Zinc Ribbon
If safe distance can not be obtain, Screening electrodes between the
pipeline and towers maybe used to intercept the fault currents
Such as zinc ribbon, or banks of sacrificial anodes
Safety -Safety -(Calculation for Arcing)(Calculation for Arcing)Safety -Safety -(Calculation for Arcing)(Calculation for Arcing)
Pipeline
Fault Currents
Lightening
Pipeline
Fault Currents
Lightening
Zinc Ribbon
Zinc
Effects of AC InfluenceEffects of AC InfluenceEffects of AC InfluenceEffects of AC Influence
Two key factors to consider with Two key factors to consider with AC InfluenceAC Influence Safety Safety CorrosionCorrosion
AC Corrosion on AC Corrosion on PipelinesPipelinesAC Corrosion on AC Corrosion on PipelinesPipelines
AC influence can cause corrosion to take AC influence can cause corrosion to take place on coated steel pipe lineplace on coated steel pipe line
Study performed in Germany, recently in Study performed in Germany, recently in the 1990’s, had determined that corrosion the 1990’s, had determined that corrosion occurs at specific occurs at specific AC current densityAC current density - - (>100 A/m(>100 A/m²²) = ) = Corrosion will resultCorrosion will result (20 A/m(20 A/m²² - 100 A/m - 100 A/m²²) = ) = Corrosion is unpredictableCorrosion is unpredictable (< 20 A/m(< 20 A/m²²)) = = Corrosion will not resultCorrosion will not result
AC Corrosion on AC Corrosion on PipelinesPipelinesAC Corrosion on AC Corrosion on PipelinesPipelines There has been documented cases of pipe
to soil potentials being above -1.170VCSE with pH samples at 11, indicating pipe being cathodically protected, but corrosion was found due to AC current density in the range of 800 A/m²
Pipe must be mitigated by dropping the AC voltage with the use of grounding devices such as zinc ribbon, copper wire, etc..
AC Calculation for AC Calculation for Current DensityCurrent DensityAC Calculation for AC Calculation for Current DensityCurrent Density
Calculation to determine AC current density - Iac = 8◦Vac/ ••d
Iac = Current density = soil resistivity in meters d = holiday area in cm’s
AC Calculation for AC Calculation for Current DensityCurrent DensityAC Calculation for AC Calculation for Current DensityCurrent Density Calculation to determine AC current density
- Iac = 8Vac/ ••d
Resistance and area of holiday will be the key factors in determining the AC current density
For an example – 1cm² holiday found with 5 Vac in a soil resistivity of 10 Ohms m (1000 ohms CM)
= 127 amp/m² ((( Corrosive))) But below the 15 Vac
Documented cases of Documented cases of AC Corrosion Found -AC Corrosion Found -Documented cases of Documented cases of AC Corrosion Found -AC Corrosion Found -
Pipe to soil potential readings were above –1.0v CSE DC
Pipe to soil potential readings were above –1.0v CSE DC
Pipe met DOT criteria for CP – above .850- V CSE
Documented cases of Documented cases of AC Corrosion Found -AC Corrosion Found -Documented cases of Documented cases of AC Corrosion Found -AC Corrosion Found -
AC Stray Current – AC Stray Current – Interference MethodsInterference MethodsAC Stray Current – AC Stray Current – Interference MethodsInterference Methods
Electromagnetic Coupling – Inductive
Electrostatic Coupling – Capacitive
Conductive Coupling - Direct path
AC Stray Current – AC Stray Current – Interference MethodsInterference MethodsAC Stray Current – AC Stray Current – Interference MethodsInterference Methods
Electromagnetic Coupling –Electromagnetic Coupling – InductiveInductive
Electrostatic Coupling – Capacitive
Conductive Coupling Direct path
Works in the same capacity of a inductive pipeline locator – Induces an audio signal onto the
buried pipeline Or in the same capacity of a
transformer Primary coils inducing current by a
electromagnetic field to the secondary windings
Electromagnetic Electromagnetic Coupling – InductiveCoupling – Inductive
Primary characteristics include: Medium to High Voltages High induced current levels
Electromagnetic Electromagnetic Coupling - InductiveCoupling - Inductive
The level of interference decreases with increasing separation of conductors
The strength of the magnetic flux is in direct proportional to the current magnitude and inversely proportional to the distance of the conductor
Induction effects experienced during power line faults can be a hazard to personnel
Normally peaks at the point of entry of AC corridor and at the point of exit
Electromagnetic Electromagnetic Coupling - InductiveCoupling - Inductive
Installation of a low resistance grounding systems to reduce current and voltage levels Grounding mats for test stations (safety) Zinc ribbon Copper wire with the use of PCR or ISP
Achieve at least a 25 ohm impedance system Ideally one ohm system Normally deeper is better
Electromagnetic Electromagnetic Coupling - Inductive Coupling - Inductive (Remediation)(Remediation)
AC Stray Current – AC Stray Current – Interference MethodsInterference MethodsAC Stray Current – AC Stray Current – Interference MethodsInterference Methods
Electromagnetic Coupling – Inductive
Electrostatic Coupling –Electrostatic Coupling – CapacitiveCapacitive
Conductive Coupling Direct path
Electrostatic Coupling – Electrostatic Coupling – CapacitiveCapacitive
Any two conductors separated by a dielectric material (insulator) is considered a capacitor
Electrical Field Gradient between the transmission line and conductor takes place, builds up a electrical charge on the structure Such as a capacitor function
Primary characteristics include : Very High Voltage peaks on power lines
Electrostatic Coupling – Electrostatic Coupling – CapacitiveCapacitive
Conductors acceptable to capacitive coupling Pipelines suspended above ground on
skids Any above ground equipment isolated such
as vehicles or backhoes with rubber tires Electrostatic Coupling does not penetrate
the earth Long parallel exposure of buried metallic
structures to power lines
((
VAC
VAC
Ground
The voltage builds up until it has path to ground to discharge
Electromagnetic charge
Voltage Gradient – electrom-agnetic field
Voltage Gradient – electrom-agnetic field
Electrostatic Coupling – Electrostatic Coupling – CapacitiveCapacitive
((
VAC
VAC
Ground
Circuit is open, the voltage charge will build to high voltage static capacity, until a ground source is provided.
The voltage builds up until it has path to ground to discharge
Electromagnetic charge
Voltage Gradient – electrom-agnetic field
Voltage Gradient – electrom-agnetic field
Electrostatic Coupling – Electrostatic Coupling – CapacitiveCapacitive
VAC
Ground
Direct Path to ground –
You……
By touching the structure and ground at the same time.
The voltage discharges
Electromagnetic charge
((
VAC
Voltage Gradient – electrom-agnetic field
Voltage Gradient – electrom-agnetic field
Electrostatic Coupling – Electrostatic Coupling – CapacitiveCapacitive
Pipe suspended
500 VAC
Pipe suspended
500 VAC
Electrostatic Coupling – Electrostatic Coupling – Capacitive Capacitive (Remediation)(Remediation)
Temporary repair – Ground vehicles and equipment
Use temporary grounding rods (copper rods) normally in 3 meters in length
Use #2 Cable Use ½ in diameter rods in normal soils
Refuel away of influence area to prevent accidental ignition, bond to refueling tanks
Due to high resistance soil, you need to place multiple rods, space about 6 feet apart
Metal chains dragging from the vehicle’s bumper in High AC voltage corridors are commonly used
Pipe is Pipe is being being grounded by grounded by making making contact to contact to the soilthe soil
Pipe is Pipe is being being grounded by grounded by making making contact to contact to the soilthe soil
Electrostatic Electrostatic Interference – Interference – Capacitive Capacitive (Remediation)(Remediation)
Permanent repair – Above ground pipelines or valves
Install Zinc ribbon Install Zinc Grounding or voltage gradient Mats Grounding Rods
3 Meters in length Design cable size based on potential fault
currents Set depth until achieved a minimum of 25 ohms
impedance Lower the impedance as low as possible One ohm is desirable
Electrostatic Electrostatic Interference – Interference – Capacitive Capacitive (Remediation)(Remediation)
In most cases, the Electrostatic charge can not generate enough body current to create a shock hazard, more of a nuisance shock similar to static electricity.
AC Stray Current – AC Stray Current – Interference MethodsInterference MethodsAC Stray Current – AC Stray Current – Interference MethodsInterference Methods
Electromagnetic Coupling – Inductive
Electrostatic Coupling – Capacitive
Conductive Coupling Direct path
Conductive Coupling Occurs when line to ground shorts or faults
take place On High Voltage power lines faults normally
occur during lighting strikes Fault currents can occur by accidental
contact with other structures Such as construction equipment or cranes
Fault currents is conducted to the pipeline through its coating Higher the coating dielectric strength, the less
amount of the transfer current on the pipeline
Conductive Coupling
Occurs in milliseconds Voltage and current is higher than
steady state but happens very briefly .1 or a tenth of a second is the normal
time frame that voltage is present due to the fault protection system
Conductive Coupling
Failure to the pipeline Coating damage Cracking and melting of the pipe wall
Materials Used for AC Materials Used for AC MitigationMitigationMaterials Used for AC Materials Used for AC MitigationMitigation Two reasons for mitigation of AC
influence Prevent corrosion on the pipeline Prevent of hazardous shock from
contacting the pipeline Materials commonly used
Zinc grounding and/or voltage gradient mats
Zinc ribbon or heavy gauge copper wiring Blind face test stations Galvanic anodes PRC or Inductive capacitive coupling
Materials Used for AC Materials Used for AC MitigationMitigationMaterials Used for AC Materials Used for AC MitigationMitigation Materials –
Zinc Ribbon – to mitigate the AC currents from the pipeline to the soil
Zinc is used in some low resistivity areas as a galvanic anode to protect structures
The AC currents will take the path of less resistance to the ground
Zinc provides this path Depending of soil resistance, distance to the
tower, the location of structure to the towers and the amount of magnitude influence of the towers must be calculated in the design of the amount of Zinc ribbon needed and the location
Materials Used for AC Materials Used for AC MitigationMitigationMaterials Used for AC Materials Used for AC MitigationMitigation
Programs available to profile the pipeline for AC mitigation PRCI
Materials Used for AC Materials Used for AC MitigationMitigationMaterials Used for AC Materials Used for AC MitigationMitigation Materials –
Zinc Ribbon – Installation –
Placed below the pipeline Depending on soil resistance Place in the lowest resistance area Minimum Two feet away from the pipeline
Make connection to the pipeline in a junction box or test station
Commonly used, a minimum of a no. 4 gauge wire connected to the pipeline and zinc ribbon
May need to increase size of cable due to greater magnitude of fault currents
Materials Used for AC Materials Used for AC MitigationMitigationMaterials Used for AC Materials Used for AC MitigationMitigation
Materials – Zinc Ribbon –
Installation – Placed between the pipeline and tower
To mitigate fault currents and prevent coating damage
Splice zinc ribbon by striping the zinc off the wire and crimp the connections together
Make crimp repair with epoxy resin kits, heat shrink sleeve, or electrical rubber tape
Chart for Zinc RibbonChart for Zinc RibbonChart for Zinc RibbonChart for Zinc Ribbon
Standard – ½ inch comes Standard – ½ inch comes in wooden spoolsin wooden spools
Ribbon is bonded to the Ribbon is bonded to the main in the test station main in the test station to be able to test AC to be able to test AC mitigation such as AC mitigation such as AC current density & current density & grounding system grounding system resistance resistance
Standard – ½ inch comes Standard – ½ inch comes in wooden spoolsin wooden spools
Ribbon is bonded to the Ribbon is bonded to the main in the test station main in the test station to be able to test AC to be able to test AC mitigation such as AC mitigation such as AC current density & current density & grounding system grounding system resistance resistance
Zinc ribbon is placed Zinc ribbon is placed below the pipeline below the pipeline and at least two feet and at least two feet away away
Zinc ribbon is placed Zinc ribbon is placed below the pipeline below the pipeline and at least two feet and at least two feet away away
Installed at test Installed at test station facility –station facility –
Coupon for AC Coupon for AC measurementsmeasurements
Grounding mat Grounding mat or voltage or voltage gradient mat for gradient mat for test point reader test point reader safetysafety
Zinc ribbon Zinc ribbon connectionconnection
Structure Structure connectionsconnections
Zinc Ribbon
Pipeline
AWG #4 w
hite
Zinc Ribbon
Coupon
AWG #4 w
hite
2 -AWG #
4 white
AWG # 12 Green 2-AWG #12 Blackswitch
AC Mitigation Test Station(recommendation - installationof voltage gradient mat)
Coupon
Used for AC currentdensity measurements
What's wrong with What's wrong with the next slide?the next slide?What's wrong with What's wrong with the next slide?the next slide?
Tower
Zinc ribbon
Pipe line
Zinc ribbon
Slide “A”
Slide “B”
Zinc ribbon is above Zinc ribbon is above the pipelinethe pipelineZinc ribbon is above Zinc ribbon is above the pipelinethe pipeline
Zinc Ribbon is on the Zinc Ribbon is on the wrong side of the wrong side of the pipelinepipeline
Zinc Ribbon is on the Zinc Ribbon is on the wrong side of the wrong side of the pipelinepipeline
Tower
Zinc ribbon
Pipe line
Polarization cells or Polarization cells or Insulated surge Insulated surge protections are great for protections are great for grounding the pipeline or grounding the pipeline or structure with out structure with out shorting out the DC shorting out the DC cathodic protection cathodic protection currents. It will block the currents. It will block the DC and allow the AC DC and allow the AC currents flow to ground.currents flow to ground.
Polarization cells or Polarization cells or Insulated surge Insulated surge protections are great for protections are great for grounding the pipeline or grounding the pipeline or structure with out structure with out shorting out the DC shorting out the DC cathodic protection cathodic protection currents. It will block the currents. It will block the DC and allow the AC DC and allow the AC currents flow to ground.currents flow to ground.
Dead Front Test Dead Front Test StationsStationsDead Front Test Dead Front Test StationsStations
To prevent To prevent electrical shock electrical shock in making in making contact with contact with wire connection wire connection to mainlineto mainline
To prevent To prevent electrical shock electrical shock in making in making contact with contact with wire connection wire connection to mainlineto mainline