Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 132 Catalog No. 535-20054 Printed in U.S.A. Form 52C,P-2W Pg 1 4-03 Replaces: 52C,P-1WBook 1 4
Tab 9a 11a
Wiring DiagramsINDEX
LEGEND
UNIT TYPEVOLTAGE
(1 Ph-60 Hz)FIGURE NO. LABEL DIAGRAM
Heat Pump Units
52CQ, PQ
AA,CP208/230,
2651 52CQ501184
RC,RP208/230,
2652 52CQ501204
Heat/Cool Units
52CE, PE
AA,CP208/230,
2653 52CQ501184
RC,RP208/230,
2654 52CQ501204
Cooling Only Units
52PCAA,CP
208/230,265
5 52CQ501184
RC,RP 6 52CQ501514
ITEM PART NO. FIGURE NO. LABEL DIAGRAM
Accessory
Energy Management (EM) Kit EM-KIT 7 52CQ501512
AA Standard ChassisCP Corrosion ProtectionRC Wall Thermostat Control (Standard Chassis)RP Wall Thermostat Control (with Corrosion Protection)
52C,PPackage Terminal
Air Conditioners and Heat Pumps
CAP CapacitorCOMP Compressor MotorCON (2) Circuit Plug CapCR Compressor RelayFCS Fan Cycle SwitchFGT Freeze Guard ThermostatFM Fan MotorFR Fan RelayGND GroundHR1 Heater RelayHR2 Heater RelayHTR HeaterIFT Indoor Frost ThermistorIT Indoor ThermostatNEC National Electrical CodeOFT Outdoor Frost ThermostatOL OverloadPCBD Printed Circuit BoardPLS Primary Limit SwitchPRI PrimaryPR Primary RelayRVR Reversing Valve RelayRVS Reversing Valve Solenoid
SEC SecondarySLS Secondary Limit SwitchSSS Speed Selector SwitchST Start ThermistorSW SwitchTRANS Transformer
Component Connection (Marked)
Component Connection (Unmarked)
Terminal Board Connection
Field Splice
Splice (Marked)
7/30/2019 Ac Wiring Diagram
2/82
Fig. 1 52CQ, PQ 208/230-1-60 and 265-1-60 Standard Units
7/30/2019 Ac Wiring Diagram
3/83
Fig. 2 52CQ, PQ 208/230-1-60 and 265-1-60 Units with Wall Thermostat Control
TYPICAL THERMOSTAT INTERFACE
1. If W is ON, then FR is forced ON (regardless of G) & CR is forced OFF.2. If Y is ON, then FR is forced ON (regardless of G).3. If IFT (indoor coil) is < 20 F, then CR is forced OFF until IFT is > 50 F.
TSTAT OUTPUT: RC CONTROLER OUTPUT: UNIT OPERATION:
G 24 VACG 0 VAC
FR LINE VACFR 0 VAC FAN
Y 24 VACO 0 VAC
HR1 & HR2 LINE VACRVR LINE VAC
HEATING
W 24 VAC HR1 & HR2 LINE VAC HEATING
Y 24 VACO 24 VAC
CR LINE VACRVR 0 VAC
COOLING
R 24 VACC COMMON
R 24 VAC OUTPUTC COMMON
POWER TO WALLTHERMOSTAT
7/30/2019 Ac Wiring Diagram
4/84
Fig. 3 52CE, PE 208/230-1-60 and 265-1-60 Standard Units
7/30/2019 Ac Wiring Diagram
5/85
Fig. 4 52CE, PE 208/230-1-60 and 265-1-60 Units with Wall Thermostat Control
TYPICAL THERMOSTAT INTERFACE
1. If W is ON, then FR is forced ON (regardless of G) & CR is forced OFF.2. If Y is ON, then FR is forced ON (regardless of G).3. If IFT (indoor coil) is < 20 F, then CR is forced OFF until IFT is > 50 F.
TSTAT OUTPUT: RC CONTROLER OUTPUT: UNIT OPERATION:
G 24 VAC
G 0 VAC
FR LINE VAC
FR 0 VAC FANW 24 VACW 0 VAC
HR1 & HR2 LINE VACHR1 & HR2 0 VAC
HEATING
Y 24 VACY 0 VAC
CR LINE VACCR 0 VAC
COOLING
R 24 VACC COMMON
R 24 VAC OUTPUTC COMMON
POWER TO WALLTHERMOSTAT
7/30/2019 Ac Wiring Diagram
6/86
Fig. 5 52PC 208/230-1-60 and 265-1-60 Cooling Only Units
7/30/2019 Ac Wiring Diagram
7/87
Fig. 6 52PC 208/230-1-60 and 265-1-60 Cooling Only Units with Wall Thermostat Control
TYPICAL THERMOSTAT INTERFACE
1. If W is ON, then FR is forced ON (regardless of G) & CR is forced OFF.2. If Y is ON, then FR is forced ON (regardless of G).3. If IFT (indoor coil) is < 20 F, then CR is forced OFF until IFT is > 50 F.
TSTAT OUTPUT: RC CONTROLER OUTPUT: UNIT OPERATION:
G 24 VACG 0 VAC
FR LINE VACFR 0 VAC
FAN
Y 24 VACY 0 VAC
CR LINE VACCR 0 VAC
COOLING
R 24 VACC COMMON
R 24 VAC OUTPUTC COMMON
POWER TO WALLTHERMOSTAT
7/30/2019 Ac Wiring Diagram
8/8
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
PC 132 Catalog No. 535-20054 Printed in U.S.A. Form 52C,P-2W Pg 8 4-03 Replaces: 52C,P-1WBook 1 4
Tab 9a 11a
Copyright 2003 Carrier Corporation
Fig. 7 Energy Management Kit All Models