33
Additional agenda for 130 th OCC meeting 23. Observance of High Voltage in the Grid: As part of winter preparedness, for controlling high voltages in the grid, following were decided in OCC meetings as well as during special meeting: a. Switching off the capacitors: Though all states have confirmed during the meeting that all capacitor banks have been switched off but proper monitoring of the same is yet to be put in place. b. Availability and utilization of all bus reactors and line reactors. c. Availability and utilization of all the tertiary reactors. d. Utilization of line reactors as bus reactors after opening of line for voltage regulation. List of Bus reactor, line reactor, Tertiary reactor and Line reactor that can be used as Bus reactor is enclosed in AnnexI. It has been observed that Out of 36 tertiary reactor in NR, only 7 nos has been reported operational. Line reactor in NR as per latest information is 253 nos, out of which only 124 nos of line reactor reportedly can be used as bus reactor. Two line reactors are damaged, 3 bus reactors are damaged and 5 nos of bus reactor are under long outage. e. Transformer tap optimization List of tap changed is enclosed in AnnexII. f. Synchronous Condenser operation Chamera (NHPC) has suggested trial operation in last week of Dec’16. Testing confirmation from RSD, Larji is still awaited. Confirmation from Uttarakhand regarding capability of new gas station is yet to come. g. Monitoring of all 400/220 kV ICTs and taking actions wherein Var flows are observed from 220 kV to 400 kV side. In this respect reactive energy accounts could also be monitored. As per NRPC reactive energy account for week of 21 st Nov 2016, net payable are Punjab, Delhi and Jammu & Kashmir. MVAr injection at particular nodes on HV is given below: State control area MVAr Injection at 400kV on High voltage as per NRPC REA for week of 21st Nov 2016 Punjab Ganguwal, Gobindgarh,Jamsher,Mohali, Ropar, Amritsar, MogaPG, Patiala & Sarna Haryana Rohtak Road, Bahadurgarh, Fatehbad, Gurgaon,Kaithal Rajasthan Hissar, Khetri, Bhinmal,Chittorgarh, Heerapura, jaipur South, kankroli & Sikar

Additional agenda for 130th OCC meeting 23. … agenda for 130th OCC meeting 23. Observance of High Voltage in ... Synchronous Condenser ... Hydro generator those are not providing

Embed Size (px)

Citation preview

Additional agenda for 130th OCC meeting 

23. Observance of High Voltage in the Grid: 

 

As part of winter preparedness, for controlling high voltages in the grid, following were decided 

in OCC meetings as well as during special meeting:  

a. Switching off the capacitors: Though all states have confirmed during the meeting that all 

capacitor banks have been switched off but proper monitoring of the same  is yet to be 

put in place.  

b. Availability and utilization of all bus reactors and line reactors. 

c. Availability and utilization of all the tertiary reactors. 

d. Utilization of line reactors as bus reactors after opening of line for voltage regulation. 

 

List of Bus reactor, line reactor, Tertiary reactor and Line reactor that can be used as Bus 

reactor is enclosed in Annex‐I. It has been observed that Out of 36 tertiary reactor in NR, 

only 7 nos has been reported operational. Line reactor in NR as per latest information is 

253 nos, out of which only 124 nos of line reactor reportedly can be used as bus reactor. 

Two line reactors are damaged, 3 bus reactors are damaged and 5 nos of bus reactor are 

under long outage. 

 

e. Transformer tap optimization 

 

List of tap changed is enclosed in Annex‐II. 

 

f. Synchronous Condenser operation 

Chamera (NHPC) has suggested trial operation  in  last week of Dec’16. Testing confirmation from 

RSD, Larji is still awaited. Confirmation from Uttarakhand regarding capability of new gas station is 

yet to come.   

g. Monitoring  of  all  400/220  kV  ICTs  and  taking  actions wherein Var  flows  are  observed 

from  220  kV  to  400  kV  side.  In  this  respect  reactive  energy  accounts  could  also  be 

monitored.  

 

As per NRPC reactive energy account for week of 21st Nov 2016, net payable are Punjab, 

Delhi and Jammu & Kashmir. MVAr injection at particular nodes on HV is given below: 

State control area MVAr Injection at 400kV on High voltage as per NRPC REA for week of 21st Nov 2016 

Punjab Ganguwal, Gobindgarh,Jamsher,Mohali, Ropar, Amritsar, Moga‐PG, Patiala & Sarna 

Haryana  Rohtak Road, Bahadurgarh, Fatehbad, Gurgaon,Kaithal 

Rajasthan Hissar, Khetri, Bhinmal,Chittorgarh, Heerapura, jaipur South, kankroli & Sikar 

Delhi  BTPS, Narela,Bamnoli, Bawana, Maharanibagh, Mundka 

Uttar Pradesh  Anpara, Atrauli, Mainpuri 

Uttarakhand  ‐ 

Himachal Pradesh  ‐ 

Jammu & Kashmir  ‐ 

Chandigarh  ‐ 

 

 

h. Opening of transmission lines keeping reliability in focus 

i. Absorption of reactive power by generating units.  

 

All the SLDCs were advised to monitor the generating stations in respective control areas for such 

absorption and were also advised to correct the MVAr telemetry if any issue is being observed.  

 

Observations regarding some of the generators at NRLDC  (Plots of MVAr (X‐axis) Vs Voltage (Y‐

axis) for 15‐Dec 2016 to 09‐Dec‐2016) are as given below:  

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Scatter plots of  ISGS stations are also given below.    In  last OCC meeting, NTPC assured to  look  into 

the generating station MVAr absorption capability and provide feedback accordingly.  

 

  

 

 

 

Members  may  like  to  discuss  area/location/station  wise  along  with  action  plan  for  further 

optimization. 

  

24. Response of SVC at Ludhiana:  

+600/‐400 MVAr SVC at Ludhiana has been commissioned on 29th November 2016. Apart  from 

above the bus reactor at Jallandhar which was out since 7th Oct 2016, has been re‐commissioned 

on  28th  Nov  2016.  This  has  resulted  in  substantial  improvement  in  voltage  profile  around 

Ludhiana. The SVC performance is given below:  

 

  

                                                                          

Scatter plot for 25th Nov 2016 to 9th Dec 2016 

is  shown  here.    Though  telemetry  of  Vref  is 

available at NRLDC,  the  telemetry of mode of 

operation,  Slope  as well  as  dead  band would 

also be further useful. An operational write‐up 

would  also  be  helpful  in  better  utilization  of 

this  resource. 

25. Hydro generation during peak and off‐peak hours 

In winter,  load duration curve of NR have a wide gap between peak and off‐peak demand. The 

ramp,  ramp  rate of peaking demand  required  to be  commensurate with  appropriate  ramp of 

hydro  generation  to  avoid  the mismatch  between  load  and  generation  and  subsequently  to 

maintain  the  frequency  of  the  grid within  the  prescribed  band.  Therefore,  Hydro  generation 

optimization become very useful and thus  its generation should be dispatched prudently as per 

the system requirement.  

Date

MVAr 

kV 

MVAr 

kV 

It has been observed that peak and offpeak load of NR has a difference of ~ 15‐16 GW while peak 

hydro generation (regional entities) remains in range of ~ 8‐9 GW and off‐peak  hydro generation 

is ~ 1 GW. Hydro generator those are not providing full capacity as per hydro availability during 

peak hours are Karcham, Salal, Dehar, Uri‐I & II, AD Hydro etc and some of the generator that are 

generating  other  than  peak  hours  are  AD  Hydro,  Bhakra,  Pong,  Uri‐I&II,  Salal,  Tanakpur, 

Koteshwar  etc.    During  winter  months  it  is  desirable  that  hydro  generators  especially  with 

pondage/reservoir based shall restrict the generation during off peak hours so as to utilize same 

during the peaking hours.  

Some of plots are given below: 

 

In case of state hydro, Jammu & Kashmir Hydro is being dispatched during off‐peak hours in the 

range of ~ 300 MW, Rajasthan (RPS & JS) & Uttar Pradesh hydro (excluding vishnuprayag HEP) are 

also being  dispatching ~ 150‐180 MW each during off‐peak hours.  

Hydro optimization, its timing, ramp, ramp rate etc has been discussed numbers of times in OCC 

meeting  and  other  fora  and  it  is  once  again  requested  to  all  the  users  to  ensure  the  hydro 

generation optimization as per load requirement especially during winters. 

Members may deliberate for further optimization of hydro generation 

 

26. Performance of generating station during Ancillary Up and down 

 

HVDC Rihand‐Dadri Pole‐2 is under shutdown since 11‐Dec‐2016 due to oil  leakage  in converter 

transformer. Ancillary  (RRAS) down was kick up  for Rihand, Singrauli and Ancillary up  for Dadri 

thermal stations within this duration. Schedule vs. actual generation of these stations for 11th Dec 

2016  is shown below.  It has been observed that Rihand, Dadri‐Th was deviating  from schedule 

during ancillary kick up.  

 

  

27. Reliability Issues 

 

ATC/TTC of Northern region state control area is enclosed in Annex‐III. 

 

Other reliability issues 

a.  Generation Dispatch  in view of security constrained dispatch 

 

Recent  tripping  of  complete Anpara  generation  in Uttar  Pradesh  control  area, Rajpura & 

Talwandi saboo in Punjab state control area in Nov‐Dec’16 causes sudden loss of generation 

in respective state control area subsequent to frequency change of grid. 

It has been mentioned nos of times that every state control area should have a widespread 

generation  i.e. all  the generating station  that  is cheap or costly should be keep on bar so 

that  in  case  of  complete  outage  of  any  generating  complex,  other  generating  station’s 

machine that already on bar can be increase fast to match up the loss of generation due to 

Singrauli actual SCADA data is 

bit less than actual generation 

tripping. It would help in fast load generation balance in state control area and to maintain 

the grid discipline. 

 

b. Jammu & Kashmir reliability issues 

 

Kashmir valley load during winter remains in range of ~1100‐1200 MW. Load in the Kashmir 

valley area has been  increasing over  the years but  intra‐state transmission system growth 

has been slow. Present connectivity of Kashmir valley to rest of the grid is only through two 

400 kV  lines viz 400 kV Kishenpur‐Wanpoh‐Wagoora D/C and  two 220 kV  lines viz 220 kV 

Kishenpur‐Ramban‐Mirbazar‐Pampore  D/C.  During  such  high  demand  and  low  voltage 

scenario,  any  N‐1  contingency  of  the  above  400kV  or  220kV  lines  further  depletes  the 

interconnection  and  poses  reliability  threat  to  the  Kashmir Valley  system.  The  inclement 

weather during winter months (e.g. Storm/Snow fall) also increases the probability of multi 

element tripping and thus severe reduction of the reliability. 

Despite commissioning of 400/220 kV New Wanpoh substation for past few years now,  the  connectivity  of  220  kV  system  at  this  station  is  yet  to  be planned/Commissioned. This is resulting in N‐1 non‐compliance of 220 kV Wagoora‐Ziankote D/C and Wagoora‐Pampore D/C  lines apart  from very  low voltages  in the valley area.  

 

 

28. Tripping of lines on High Voltage 

 

Since  November’16,  average  ~  30  nos  of  400kV  and  above  line  is  being  opened  for  voltage 

regulation and average 10 nos of 400kv and above lines trip during fog , details is as given below:  

Date Tripping during Fog 

Multiple element tripping   Tripping on 

High Voltage Line opened on High 

Voltage Events 

Lines tripped 

11/30/2016  31  5  15  2  29 

12/1/2016  12  0  0  0  34 

12/2/2016  10  1  2  0  34 

12/3/2016  10  1  2  0  31 

12/4/2016  4  1  2  0  28 

12/5/2016  8  1  2  1  33 

12/6/2016  2  0  0  0  31 

12/7/2016  4  0  0  1  40 

12/8/2016  15  3  9  2  22 

12/9/2016  4  0  0  1  32 

12/10/2016  10  1  2  1  36 

12/11/2016  7  0  0  2  22 

12/12/2016  6  0  0  3  33 

Total  123  13  34  13  ‐ 

Average  10        1  31 

 

Further,  41  nos  of  EHV  has  been  given planned  shutdown  by NRLDC  since  30th Nov  2016  for 

Insulator replacement/ Cleaning of Insulators/ Pre‐winter Maintenance.  

 

States has also been reported nos of 220kV line tripping during fog. States control area may also 

share the preventive action being taken to avoid such tripping. 

 

29. Deviation Report 

 

The deviations from the schedule are to be minimized. Some of the violations brought out by the 

Regulations are given below:  

Violation of regulation 7 (1) of CERC (Deviation Settlement and related matters) Regulation 2014: 

(Limit on volume of deviation)  

 Period:‐01.11.2016 to 27.11.2016  

S.No.  State       O/D: Violation in Over drawl  Average No of 

Blocks per day       U/D: Violation in Underdrawl 

1  Punjab O/D  35 

U/D  8 

2  Rajasthan O/D  32 

U/D  7 

3  Uttar Pradesh  O/D  31 

U/D  28 

4  Uttarakhand O/D  17 

U/D  12 

5  Jammu & Kashmir O/D  14 

U/D  1 

6  Haryana O/D  13 

U/D  19 

7  Himachal Pradesh  O/D  12 

U/D  3 

8  Delhi O/D  9 

U/D  2 

9  Chandigarh O/D  1 

U/D  0 

 

Remarks: Violation is considered while Deviation from Schedule of a Utility is 150 MW or 12% of 

Schedule whichever is lower.  

Violation  of  regulation  7  (10)  of  CERC  (Deviation  Settlement  and  related matters)  Regulation 

2014: (Sustained deviation from schedule in one direction).  

 

Period:  01‐Nov‐16 to 27‐Nov‐16 

Chandigarh Delhi Haryana HP J&K Punjab Rajasthan UP Uttarakhand

Total No. of Violations 

126  123  111  107  102  93  59  47  37 

 

Members may like to discuss and take action to avoid such violations. It could be seen that these 

zero crossing violations are very high in numbers indicating less sensitization of the operators at 

control centers.  

In the absence of AGC controls,  it  is very  important that Area Control Error (ACE) of respective 

control areas is monitored and corrected expeditiously.   

 

30. Low Frequency Oscillation occurrence during opening of 400kV Tehri‐Koteshwar ckt‐1: 

In antecedent condition, FSC of Meerut‐ Koteshwar (Pool) ckt ‐2 at Meerut (PG) was under damage condition  from 16.07.2015 and FSC of Meerut‐ Koteshwar  (Pool)  ckt  ‐1 at Meerut  (PG) was under outage from 04.11.2016. Shutdown (Planned) code  issued for 400kV Meerut‐Koteshwar (Pool) ckt‐1 for  isolator  replacement  at  Koteshwar  (Pool)  GIS.  During  shutdown  of  the  ckt‐1,  only  one uncompensated  evacuation  line  was  available  from  Koteshwar  (Pool)  to  Meerut.  Antecedent generation in the complex was ~1150MW (1060MW at Tehri and 90MW at Koteshwar).   On 22nd Nov 2016, at 08:13hrs 400kV Meerut‐Koteshwar ckt‐1 was taken under shutdown for isolator contact replacement at Koteshwar (Pool) GIS. During opening of the  line,  low frequency oscillations observed in the power system. PMU plot of frequency and rate of change of frequency is: 

   

Salient point for low frequency oscillations on 22nd Nov 2016:  At the moment of outage of 400kV Koteswhar(Pool)‐Meerut ckt‐1, oscillation started into the 

NR system and sustained upto 47second.  Oscillations started at 08:13.34hrs and die down at 08:14:21hrs.  Oscillations were observed in Balia, Hissar, Bassi and Karcham voltage magnitude, frequency 

& angle.   Negative damping observed for 0.76Hz and 1.6Hz frequency mode.  Tehri generation was manually reduced by ~300MW within 20second.  

  

One SPS is already discussed and approved in the OCC meeting.  

Approved  SPS  of  Tehri  complex‐  “When  all  the  four machines  (i.e.  Tehri  HPS  (4  ×  250 MW)  and Koteshwar HPS (4×100 MW)) are running and any one of the 400 kV Koteshwar‐Merrut circuit trips, one unit of 250 MW of Tehri HPS should be tripped instantaneously”.  However, in actual real time grid operation on 22nd Nov 2016, oscillations observed in the system for 1150MW generation in the complex. It may be due to dynamic behavior of power system.  On  23rd  Nov  2016,  NRLDC  control  room  tried  to  increase  the  generation  in  the  complex  upto 1200MW  by  10‐20MW  block  increment.  No  oscillation  observed  in  the  system  for  1200MW generation in the complex.  SPS needs to be reviewed for considering the dynamic behavior of the system. Tripping of one unit may not be averted the oscillation  i.e. Tripping of two units needs to be planned  for proposed SPS operation of Tehri/Koteshwar generation complex.  

 Member may kindly discuss and review the planned SPS of Tehri/Koteshwar generation complex.  

31. Multiple element tripping events in Northern region since last OCC meeting: 

Following multiple tripping events took place in NR since last OCC meeting. The preliminary report of 

all the events have been issued from NRLDC.  

 

 

S.No 

Outage  Time Duration of fault (as per PMU) 

Owner / Agency 

Event (As reported) 

Category as per CEA Grid 

Standards 

Status of Preliminary report received within 24hrs (Y/N) 

Status of DR/EL  received within 24hrs (Y/N) 

Status of 

Analysis report received (Y/N)  

Date Time  (in Hrs) 

1  11‐11‐16  09:11  80ms POWERG

RID/UP 

220kV Meerut(PG)‐

Modipuram(UP) 1 & 2 tripped 

reportedly on B‐phase to earth 

fault. 

GI2  N  N  N 

2  11‐11‐16  14:16  120ms DTL/PO

WERGRID 

400kV Bahadurgarh(PG)‐

Bawana(DTL) tripped due to 

wavetrap problem and 400kV 

Bahadurgarh(PG)‐Bawana(GT) 

tripped along with this. 

GI2  N  N  N 

3  11‐11‐16  20:46 No fault 

observed Haryana 

400/220kV Nuhiyawali 315 MVA 

ICT 1 & 2 tripped on overvoltage. GI2  N  N  N 

4  17‐11‐16  09:34  80ms THDC/PO

WERGRID 

During opening of Bus‐2 isolator 

of Koteshwar Pool‐Tehri Ckt‐2, 

Bus Fault reported in “Y” phase of 

Bus‐2 (Fault Current ~ 6kA). As 

per pre‐fault condition, all lines 

were connected to Bus‐2, bus 

bar‐2 operation leads to tripping 

of all lines. 

GD1  Y  Y  N 

5  20‐11‐16  03:03 No fault 

observed 

DTL/PO

WERGRID 

400kV Maharanibagh‐

Ballabhgarh and 400kV 

Maharanibagh‐Dadri TH tripped 

on overvoltage. 

GD1  N  Y  N 

6  21‐11‐16  01:17 No fault 

observed 

DTL/PO

WERGRID 

400kV Maharanibagh‐

Ballabhgarh tripped on 

overvoltage at 01:17hrs. 220kV 

Maharanibagh‐Lodhi Road ckt‐1 

and 220kV Maharanibagh‐Truma 

centre ckt‐2 tripped along with 

this. 

GD1  N  Y  N 

7  21‐11‐16  21:17 No fault 

observed 

Punjab/B

BMB 

On bus‐bar operation at 

Rajpura(PSTCL), 400kV 

Dehar(BBMB)‐Rajpura(PSTCL), 

400kV Bhiwani(BBMB)‐

Rajpura(PSTCL), 400kV 

Rajpura(PSTCL)‐Rajpura 

TPS(PSEB) along with unit #4 at 

Dehar HEP(BBMB) tripped. 

GD1  N  Y  Y 

8  25‐11‐16  16:57  80ms  Punjab 

LA of 400kV Kanpur(765)‐Kanpur 

ckt‐1 at Kanpur(765) end blasted 

resulting complete outage of 

whole 765/400kV Kanpur(PG) 

station. 400kV Kanpur(765)‐

Kanpur ckt‐2 was under S/D. 

GI2  N  N  N 

9  27‐11‐16  10:32  80ms Rajastha

400kV Heerapura‐Merta and 

400kV Heerapura(RVPNL)‐

Phagi(RVPNL) ckt‐1 tripped 

reportedly on phase to earth 

fault. 

GI2  N  N  N 

10  28‐11‐16  10:43  80ms 

POWERG

RID/Hary

ana 

400/220kV Hissar 315MVA ICT #1 

& 3, 220kV Hisar(PG)‐Hisar‐

IA(HVPNL) ckt‐1 & 2 and 220kV 

Hisar(PG)‐Isharwal(HVPNL) 2 

tripped. Busbar protection 

operation is reported. 

GI2  N  N  N 

11  29‐11‐16  01:08 

Two 

successiv

e faults of 

80ms 

clearance 

time 

UP 

400kV Bareilly‐Unnao ckt‐1 

tripped on overvoltage and 

Bareilly‐Unnao ckt‐2 tripped on 

phase to earth fault. 

GI2  N  N  N 

12  29‐11‐16  02:10 No fault 

observed 

UP/Uttra

khand  

400kV Alaknanda HEP(UP)‐

Srinagar(UTT) ckt‐1 & 2 tripped 

reportedly on phase to earth 

fault. 

GI2  N  N  N 

13  29‐11‐16  03:37  400ms  UP 

400kV Muradnagar‐

Muzaffarnagar and 400kV 

Alaknanda HEP ‐ Muzaffarnagar 

ckt‐2 tripped reportedly on phase 

to earth fault. 

GI2  N  N  N 

14  30‐11‐16  00:18 

Two 

successiv

e faults of 

80ms 

clearance 

time 

POWERG

RID 

500kV HVDC Balia‐Bhiwadi Bipole 

tripped on  transient fault due to 

non availability of 66 KV earth 

electrode line at Bhiwadi end. 

GI2  N  Y  Y 

15  30‐11‐16  00:59  560ms UP/LPGC

765/400kV Fatehabad 765(UP) 

1500 MVA ICT 1 and 765kV 

Fatehabad 765(UP)‐Lalitpur 

TPS(LPGCL) 1 tripped. 

GI2  N  N  N 

16  30‐11‐16  03:14 

Two 

successiv

e faults of 

120ms 

clearance 

time. 

NTPC/DT

220kV Badarpur(NTPC)‐

Ballabgarh(BBMB) 2, 220kV 

Badarpur(NTPC)‐Noida sec 

20s(UP), 220kV Badarpur(NTPC)‐

Sarita vihar(DTL) 2, 220kV 

BTPS(NTPC)‐MIA Alwar(RPVNL), 

220kV Badarpur(NTPC)‐

Mahrauli(DTL) 2 and 220kV 

Badarpur(NTPC)‐Okhla(DTL) 2 

tripped. 

GD1  N  N  N 

17  30‐11‐16  03:50 

Two 

successiv

e faults of 

120ms 

clearance 

time. 

UP 400/220kV 240MVA Muradnagar 

ICT #1 & 2 tripped. GD1  N  N  N 

18  30‐11‐16  06:02   ‐  UP 

At 06:02hrs all elements 

connected from 400kV Anpara 

along with unit at Anpara, Anpara 

C & Anpara D tripped and 

resulted complete outage of 

Anpara A,B,C & D TPS. 

GD1  N  N  N 

19  30‐11‐16 

06:48 

07:24  

Two 

successiv

e faults of 

80ms & 

120ms 

clearance 

time  

Punjab 

 400kV T.Sabo‐Dhuri ckt‐1 tripped 

at 06:33hrs and ckt‐2 tripped at 

06:24hrs. 400kV T.Sabo‐Nakodar 

tripped at 06:42hrs and 400kV 

T.Sabo‐Moga tripped at 06:48hrs. 

T.Sabo unit #3 tripped at 

06:48hrs ( gen loss ~300MW0. 

400kV T.Sabo‐Muktsar ckt‐2 

along with unit #1 & 2 tripped at 

07:24hrs and further resulted in 

gen loss of 800MW. 

 GD1   Y   Y   N 

20  01‐12‐16  01:56  80ms  UP 

400kV Anpara‐Mau and 400kV 

Anpara‐Obra tripped due to 

dense fog. 

GI2  N  N  N 

21  02‐12‐16  06:00  80ms  Punjab 

400kV Nakodar ‐ Rajpura (TH) 

ckt‐1 and 2 tripped due to dense 

fog. Rajpura TH unit #2 tripped 

due to outage of lines. 

GD1   Y   Y   N 

22  03‐12‐16  03:23 

Two 

successiv

e faults of 

80ms 

clearance 

time 

POWERG

RID 

400kV Balia‐Patna ckt‐3 & 4 

tripped on Y‐N fault during high 

density fog. 

GI2  N  N  N 

23  04‐12‐16  06:29 No fault 

observed Punjab 

400kV Makhu‐Mukatsar ckt‐1 & 2 

tripped reportedly on phase to 

earth fault. 

GI2  N  N  N 

24  05‐12‐16  20:40  160ms  UP 

400kV Bareilly‐Unnao ckt‐1 

tripped on overvoltage and 

Bareilly‐Unnao ckt‐2 tripped due 

to fog. 

GI2  N  N  N 

25  08‐12‐16  02:28  80ms  Punjab 400kV Dhuri(400kV) ‐Rajpura TH 

ckt‐1 & 2 tripped due to fog. GI2  N  N  N 

26  08‐12‐16  03:08  80ms  Haryana 

In antecedent condition, 400kV 

Rajpura‐Dehar was already 

opened on High voltage.400kV 

Rajpura‐Nakodar ckt‐2 tripped at 

02:54hrs. 400kV Rajpura‐Nakodar 

ckt‐1, 400kV Rajpura‐Bhiwani  

and 400kV Rajpura‐Rajpura(Th)  

tripped at 03:08hrs due to fog. 

Due to loss of evacuation path, 

400kV Rajpura Th unit #2 

generating around 350MW 

tripped. 

GD1  N  N  N 

27  08‐12‐16  03:53  80ms  Delhi 

In antecedent condition, 400 kV  

Talwandi Sabo‐Nakodar, 400 kV  

Talwandi Sabo‐Dhuri 1 & 2 were 

already opened on over voltage. 

400 kV  Talwandi Sabo‐Moga 

tripped at 01:38hrs. 400 kV  

Talwandi Sabo‐Mukatsar 1&2 

tripped at 03:08hrs due to fog. 

Due to loss of evacuation path, 

400kV Talwandi Sabo unit #1 & 2 

generating around 650MW 

tripped. 

GD1  N  N  N 

 

It could be observed that despite persistent discussions/follow‐up  in various OCC/PCC meetings, the 

compliance of the regulations is still much below to the desired level.  

 

Member may please  impress upon  all  concerned  for providing  the Preliminary Report, DR/EL & 

Detailed Report of the events in line with the regulations and also take expeditious actions to avoid 

such tripping in future 

     Members may like to discuss. 

 

32. Details of tripping of Inter‐Regional lines from Northern Region for November’16: 

The list of tripping of inter‐regional lines in the month of November’16 is given below. The status of 

receipt of preliminary reports, DR/EL within 24hrs of the event and fault clearing time as per PMU 

data has also been mentioned  in the table. The non‐receipt of DR/EL & preliminary report within 

24hrs of  the event  is  in  violation of  various  regulations. As per  regulations,  all  the utilities  shall 

furnish  the DR/EL,  flag details & preliminary  report  to RLDC/RPC within 24hrs of the event. They 

shall also furnish the detailed investigation report within 7 days of the event if fault clearance time 

is higher than mandated by CEA (Grid Standard) Regulations. 

 

  

It could be observed from above table that the not all  information regarding the tripping  is received 

from the utilities, except in one case. 

 

Members may please note  and  advise  the  concerned  for  taking  corrective  action  as well  as  timely 

submission of the information. 

 

33. Frequency response characteristic: 

One FRC based event has occurred since last OCC meeting. The FRC has been computed by NRLDC as 

well as request was sent to state control areas along with other regional entities to compute the same 

at their end. Description of the events is as given below: 

 

FRC 

S.NO  Event Date Time (in hrs) 

Event Description Starting 

Frequency  (in Hz) 

End Frequency  (in Hz) 

Δf 

1  30‐Nov‐16  06:02 

At  06:02  Hrs  all  running  units  in 

Anpara  generation  complex  tripped 

most  likely due to tripping of 400kV 

Anpara‐Sarnath  D/C.  Generation 

loss  of  2000 MW  occurred.  At  the 

same  time  Vindhyachal  Block‐1 

tripped  due  to  DC  Over  current 

protection. 

50.25  49.99  ‐0.26 

 

The Hon’ble CERC approved procedure has already been shared with all concerned during previous 

OCC meetings. FRC observed for each state control area for the events is tabulated below:   

                                                                                      

State Control Area 

FRC computed  

(Based on NR‐

SCADA data)

PUNJAB  17%

HARYANA  30%

RAJASTHAN  15%

DELHI  21%

UTTAR PRADESH  30%

UTTARAKHAND  4%

CHANDIGARH  35%

HIMACHAL PRADESH  7%

JAMMU & KASHMIR  5%

Northern Region (NR)  18% 

 

 

 

 

 

 

                                                                                

Thermal Generators  

FRC computed  

(based on NR‐

SCADA data) 

Hydro Generators  

FRC computed 

 (based on NR‐

SCADA data) 

Rihand‐3*  NA  Chamera‐1*  NA 

Unchahar*  NA  Salal*  NA 

Anta*  NA  Uri‐2*  NA 

Auraiya*  NA  Sewa‐II*  NA 

Sh. Cement*  NA  Tehri*  NA 

Faridabad*  NA  Malana‐2*  NA 

Khedar*  NA  Budhil*  NA 

Panipat*  NA  Vishnu Prayag*  NA 

Yamuna Nagar* 

NA Karcham Wangtoo* 

NA 

Suratgarh*  NA  Bairasiul  24.2% 

Chabra*  NA  Dulhasti  20.9% 

Rajwest*  NA  Koteshwar  20.5% 

Anpara*  NA  Chamera‐3  18.7% 

Anpara C*  NA  Dhauliganga  15.1% 

Tanda*  NA  Uri‐1  9.8% 

Parichha*  NA  Pong  5.0% 

Dadri ‐2  96.0%  Dehar  3.1% 

Badarpur  46.4%  Parbati‐3  0.0% 

Dadri‐1  28.5%  Bhakra  ‐2.2% 

Jhajjar  21.2%  Tanakpur  ‐4.3% 

ROSA  12.0%  Chamera‐2  ‐6.6% 

RAPS‐C  7.4%  Rampur  ‐9.5% 

NAPS  1.6%  Jhakri  ‐66.7% 

KTPS  ‐1.2% 

Rihand‐1  ‐1.7% 

Singrauli  ‐4.4% 

Rihand‐2  ‐4.6% 

CLP Jhajjar  ‐6.4% 

RAPS‐B  ‐8.7% 

Ropar  ‐11.9% 

Dadri‐Gas  ‐61.8% 

Obra  ‐106.3% 

In  line with  the decisions  taken during various OCC meetings,  the  time and date of  the FRC events 

were e‐mailed  to  respective utilities. However, FRCs  from utilities are yet  to be  submitted. Utilities 

may kindly submit the FRC of their control areas.  

UP  has  sent  FRC  of  its  control  area  generators  for  the  event  of  Lalitpur  tripping  on  19.10.16  & 

20.10.16. 

 

Members may  discuss  the  reason  for  such  poor  frequency  response  and  suggestive measures  to 

monitor it and improve it. 

Members may  discuss  and  decide  a  date  wherefrom  all  the  generators  shall  be  put  in  governor 

responsive mode.  

 

34. Mock Blackstart exercise: 

As per  Indian Electricity Grid Code  (IEGC) clause 5.8(b) “Mock trial runs of the procedure for different sub‐systems shall be carried out by the Users/ CTU/ STU at least once every six months under intimation to the RLDC”.  Schedule has been given in 127th OCC meeting for conducting mock blackstart testing in the year 2016‐

2017.The summary of the Mock Black start exercises conducted so far 2016‐17 is given below: 

 

S.No. Proposed 

Date 

Actual 

Date 

Generating 

station 

Report 

Received Remarks 

1  20‐Oct‐16  ‐  Parbati‐III HEP  ‐ Deferred by the Power station for last 

week of November. 

2  25‐Oct‐16  ‐  Budhil HEP  ‐  Deferred by the Power station. 

3  28‐Oct‐16  09‐Nov‐16  Chamera‐3 HEP  Yes Black  start  exercise  was  carried  out 

successfully. 

4  2‐Nov‐16  ‐  Sewa‐2 HEP  ‐ 

Absence  of  synchronizing  feature  in 

the existing relay at Sewa‐II. This issue 

has been taken up with M/s BHEL  i.e. 

OEM for resolving the same.  

5  7‐Nov‐16  ‐  Malana‐2 HEP  ‐ Exercise deferred due to Shutdown at 

AD Hydro. 

6  11‐Nov‐16  11‐Nov‐16  Chamera‐2 HEP  No 

During charging of 400kV Chamba‐

Jallandhar,  line  tripped  from 

Jallandhar  end  on  over  voltage

stage‐1  at  first  attempt  and  on 

fault  at  400kV  Chamera‐2(end)‐‐

Chamba  on  second  attempt.  The 

exercise  is  to  be  clubbed  with 

Mock black start activities carried out at state embedded generating units were also to be  informed 

regularly  but  till  now  no  information  is  available.  All  SLDC may  update  the  status  and  inform  the 

outcome of exercises.  

 

Member may discuss. 

 

35. Mapping of UFR & df/dt in SCADA systems of state: 

 

The Hon’ble Central Electricity Regulatory Commission (CERC), through its order dated 23rd 

December 2013 in petition no 221/MP/2012 has ordered as follows:  

 

Chamera‐1 HEP. 

7  17‐Nov‐16  ‐  Chamera‐1 HEP  ‐ Black  start  exercise  was  carried  out 

successfully. 

8  22‐Nov‐16  ‐  Bairasiul HEP  ‐  Date confirmed by station.  

9  25‐Nov‐16  ‐  Dhauliganga HEP ‐ 

Due  to minor  SF6  gas  leakage  in  line 

isolator  compartment  of  220kV 

Bareilly(UP)  line  the exercise  is  to be 

deferred for last week of December. 

10  30‐Nov‐16  07‐Dec‐16  Koteshwar HEP  ‐ 

During  synchronization  of  island  at 

Tehri,  400kV  Koteshwar  Pool‐Tehri 

line  tripped  on O/V  at  first  attempt. 

Later  on  it  was  synchronized 

successfully. 

11  9‐Dec‐16  ‐ 

Nathpa Jhakri 

HEP &  Rampur 

HEP 

‐  To be confirmed by stations. 

12  16‐Dec‐16  20‐Dec‐16 

Uri‐I, II HEP, 

Lower Jhelum 

HEP & Pampore 

GT’s 

‐  Date confirmed by Uri‐I, II. 

13  22‐Dec‐16  ‐  AD Hydro HEP  ‐ 

14  28‐Dec‐16  16‐Dec‐16 Karcham 

Wangtoo HEP ‐  Date confirmed by Karcham 

15  3‐Jan‐17  ‐  Salal HEP  ‐  Date confirmed by station. 

16  9‐Jan‐17  ‐  Tehri HEP  ‐ 

17  13‐Jan‐17  ‐  Koldam HEP  ‐ 

“(c) UFRs and df/dt  relays also be mapped on  the SCADA  system of each  state  so  that  they  can be 

monitored from SLDC/NRLDC. (d) All STUs and SLDCs to map/network the UFR and df/dt on their SCADA system.” 

 

NRLDC has taken up the issue since then and the same is also being discussed in various OCC meetings 

wherein it has also been decided that both digital and analog values, of the feeders where such relays 

have been installed, shall be monitored. NRLDC had also taken up for same again through its letter no. 

NRLDC\TS‐11\1216 dated 08/07/2016.  

 

        In 120th OCC meeting, a uniform formats for mapping of UFR & df/dt in SCADA systems for all the 

states  for  visualizing  the  feeders was  suggested by NRLDC.  These  formats have  to be  compiled by 

respective state/SLDC by co‐coordinating with respective SCADA team of SLDCs.  

 

Considering that communication from all UFR and df/dt relays  is yet not available,  it was decided  in 

124th  OCC meeting  that wherever,  such  issues  are  arising,  the  transformers  at  220kV  or  132  kV 

substations be monitored and mapped in the SCADA as alternate monitoring point. 

The issue was once again discussed in 125th, 126th, 127th and 128th OCC meeting of NRPC. The status of 

UFR, df/dt SCADA displays of different states/UTs as received at NRLDC is tabulated below: 

 

 

State Remarks 

UFR SCADA display  df/dt SCADA display 

Punjab Feeders are not segregated as per respective UFR, df/dt settings 

Only one end analog data of the feeder; Digital status of CB not mapped 

Haryana 

   setting of df/dt and feeder name doesn’t match

SCADA telemetry of many feeders not availableSCADA telemetry of four out of six feeders not available 

Only one end analog data of the feeder Only one end analog data of the feeder

   Stage‐wise total load relief not mentioned

Feeder wise planned load relief not mentioned Feeder wise planned load relief not mentioned

220kV Narwana: 100MVA ICT‐1 (UFR‐49.0Hz) & ICT‐2 (UFR‐48.6Hz) are parallel ICTs but in different stages 

132kV Karnal‐Ramba ckt is mentioned in both UFR‐48.6Hz and UFR‐48.8Hz stages 

Rajasthan  Mapped UFR, df/dt SCADA displays not received at NRLDC

Delhi  UFR, df/dt feeders mapped as per areas in Delhi viz. Dadri, BTPS, Bawana, Delhi 

UP  Mapped UFR, df/dt SCADA displays not received at NRLDC

Uttarakhand  Mapped UFR, df/dt SCADA displays not received at NRLDC

HP 

Feeders are not segregated as per respective UFR, df/dt settings

Only one end analog data of the feeder

132kV Kunihar Barotiwala‐1 (49.9Hz, 0.1Hz/sec) & Barotiwala‐2 (UFR‐48.6Hz) are parallel ckts but in different stages 

132kV Giri: 132/33kV ICT‐1 (UFR‐49.0Hz) & ICT‐2 (UFR‐48.8Hz) are parallel ICTs but in different stages

J&K  Mapped UFR, df/dt SCADA displays not received at NRLDC

Chandigarh  Mapped UFR, df/dt SCADA displays not received at NRLDC

In all the displays, only one end analog data of feeders is mapped, stage based segregated load relief not mentioned and alternate feeder for telemetry not mapped 

Member may please discuss, update the status and take action accordingly. 

36. Revision of document for Reactive Power Management for Northern Region: 

Reactive Power Management document and System  restoration procedure  for Northern  region are 

due for revision. The last updated document link has already been shared with the constituents are as 

follows: 

 http://www.nrldc.org/docs/NR‐RPM‐2016.pdf  

 http://www.nrldc.org/docs/NR‐SRP‐2015.pdf 

Utilities may kindly give their feedback, suggestion & updated  information at the earliest  in order to 

revise the document. The current status of details received from the constituents is tabulated below:  

System Restoration Procedure 

Data Received from 

Data Not received from 

AD Hydro  Malana‐II  SJVN 

Delhi  Adani  HP 

APCPL  Rosa (Reliance)  J&K 

Haryana  Greenko Budhil  Malana‐I

NHPC  Punjab  JAYPEE 

Rajasthan  Railway  NPCIL 

NTPC  UP  POWERLINK

Uttarakhand  PKTCL 

BBMB  Shree Cement

Chandigarh THDC 

POWERGRID  Others… 

Karcham (JSW) 

 

 

 

Utilities may kindly give  their  feedback, suggestion & updated  information at  the earliest  in order  to 

revise the documents. 

Member may discuss. 

37. PILOT PROJECT TO DRAW POWER FROM INSULATED EARTH WIRE OF 400KV BHIWANI JIND TRANSMISSION LINE AS A R&D PROJECT(Agenda by POWERGRID):

A pilot project to draw approximate 2‐5kW power by insulating few km of one of the two earth wire of 

400kv BHIWANI JIND line and tapping the induced voltage through MV class PT, whose secondary shall 

be used  to  feed  the  load,  shall be executed by POWERGRID near BHIWANI  substation under a R&D 

project.  

 

System Restoration Procedure 

Data Received from 

Data Not received from 

AD Hydro Malana‐II  SJVN 

Greenko Budhil Adani HP 

UP* Rosa (Reliance)  J&K 

Malana‐I Delhi APCPL

NPCIL Karcham (JSW)  JAYPEE

NTPC Punjab  NHPC

Railway  POWERLINK

Haryana  PKTCL

Uttarakhand  Shree Cement

BBMB THDC

Chandigarh 

Rajasthan 

POWERGRID  Others…

The details of basic scheme are attached  for  ready reference as Annex‐IV. The outcome of success of 

this R&D project/ scheme, shall be shared with all constituents by POWERGRID. 

This is for information to all OCC members.

38. Frequently opening of NAPS lines by UPSLDC and kept open for longer duration (Agenda by NAPS):  

There are five 220 kV lines emanating from NAPS,3 out 5 lines i.e. NAPS-Khurja-1,NAPS-Harduaganj & NAPS- had been LILOed by UPPTCL at Dibai, Atrauli & Sambhal respectively. Recently, it has been observed that LILO links are opened very frequently on one and other reasons without information to NAPS as well NRLDC and kept open for week’s .Opening of these links results in weakening the grid connectivity to NAPS. Before formation of LILO in NAPS-Khurja line-1, UPPTCL Authorities ensured that the proper communication will be made with NAPS if opening of these links required. The details of opening of these links are given as below;

i) NAPS-Harduaganj line opened at Atrauli on 30/11/2016 and remained open till

10/12/2016. ii) NAPS- Moradabad line opened at Moradabad on 12/12/2016 and remained open

till 13/12/2016. iii) NAPS- Khurja line-1 also kept opened at Dibai at nos. of time recent past.

UPPTCL authorities are requested to advising their officials for effective communication and co-ordination with NAPS Control room according to available guide lines.

Annex‐I 

Operational Tirtiary Reactor 

Sl No. Utility Station_Name Installed on Rating (MVAR)

Out since and reason of outage

1  NTPC  AURIYA CCGPP  33 KV SIDE OF 315 MVA ICT ‐ 1  25    

2  NTPC  AURIYA CCGPP  33 KV SIDE OF 315 MVA ICT ‐ 2  25    

3  UPPC  BAREILY (UP)  33 KV SIDE OF 315MVA ICT ‐ 1  32    

4  UPPC  BAREILY (UP)  33 KV SIDE OF 315MVA ICT ‐ 2  32    

5  UPPC  LUCKNOW(UP)  33 KV SIDE OF 315MVA ICT ‐ 1  25    

6  UPPC  SULTANPUR  33 KV SIDE OF 240MVA ICT ‐ 1 25    

7  UPPC  SULTANPUR  33 KV SIDE OF 240MVA  ICT ‐ 2  25    

Non‐Operational Tirtiary Reactor 

Sl No. Utility Station_Name Installed on Rating (MVAR)

Out since and reason of outage

1  PGCL  MOGA(PG)  33 KV SIDE OF 315MVA ICT 1  25  Out due to fire in ICT‐2 since 2001. 

New equipment has been installed and cabelling work is 

pending 2 

PGCL  MOGA(PG)  33 KV SIDE OF 315MVA ICT 2  25 

3  UPPC  AGRA(UP)  33 KV SIDE OF 500MVA ICT ‐ 1  31.5 

315MVA ICT‐I replaced by 500MVA & tertiary kept open as per instruction of the firm. 

4  UPPC  AGRA(UP)  33 KV SIDE OF 315MVA ICT ‐ 2  31.5 LA & Capacitor unit damaged. 

5  UPPC  AZAMGARH  33 KV SIDE OF 315MVA ICT ‐ 1  31.5 CB alotted,CT&PT Not Alotted 

6  UPPC  AZAMGARH  33 KV SIDE OF 315MVA ICT ‐ 2  31.5 CB alotted,CT&PT Not Alotted 

7  UPPC  G. Noida  33 KV SIDE OF 315MVA ICT ‐ 1  31.5    

8  UPPC  G. Noida  33 KV SIDE OF 315MVA ICT ‐ 2  31.5    

9  UPPC  GORAKHPUR(UP)  33 KV SIDE OF 240MVA ICT ‐ 1  31.5    

10  UPPC  LUCKNOW(UP)  33 KV SIDE OF 315MVA ICT ‐ 2  25 

02 No. Bushing Damaged. Bushings are to be arranged  from M/s BHEL 

11  UPPC MAU (KASARA)‐400  33 KV SIDE OF 200MVA ICT ‐ 1  31.5    

12  UPPC MAU (KASARA)‐400  33 KV SIDE OF 200MVA ICT ‐ 2  31.5    

13  UPPC  MORADABAD 400  33 KV SIDE OF 315MVA ICT ‐ 1  25    

14  UPPC  MORADABAD 400  33 KV SIDE OF 315MVA ICT ‐ 2  25    

15  UPPC MURADNAGAR 400  33 KV SIDE OF315MVA ICT ‐1  25    

16  UPPC MURADNAGAR 400  33 KV SIDE OF315MVA ICT ‐2  25    

17  UPPC MUZAFFARNAGAR 400  33 KV SIDE OF315MVA ICT ‐1  31.5    

18  UPPC MUZAFFARNAGAR 400  33 KV SIDE OF315MVA ICT ‐2  31.5    

19  UPPC  OBRA‐B TPS  33 KV SIDE OF ICT ‐ 2  31.5  Out due to damage 

20  UPPC  OBRA‐B TPS  33 KV SIDE OF ICT ‐ 1 31.5  Out due to damage

21  UPPC  PANKI 400  33 KV SIDE OF 240MVA ICT ‐ 1  25 

33KV CT,PT, Surge Arrester etc damaged 

22  UPPC  PANKI 400  33 KV SIDE OF 240MVA ICT ‐ 2  25 

33KV CT,PT, Surge Arrester etc damaged 

23  UPPC  SARNATH  33 KV SIDE OF 315MVA ICT ‐ 1  31.5    

24  UPPC  SARNATH  33 KV SIDE OF 315MVA ICT ‐ 2  31.5    

25  UPPC  SARNATH  33 KV SIDE OF 500MVA ICT ‐ 3  31.5    

26  UPPC  UNNAO  33 KV SIDE OF 315MVA ICT ‐ 1  32 

02 No. Bushing Damaged. Bushing are to be arranged. 

27  UPPC  UNNAO  33 KV SIDE OF 315MVA ICT ‐ 2  32 

Tender to erect the pipe of the bay is under Process. 

28  PTCUL  RISHIKESH 400  33 KV SIDE OF ICT ‐ 1  25    

29  PTCUL  RISHIKESH 400  33 KV SIDE OF ICT ‐ 2  25    

Annexure‐ II: OCC Agenda 22 (B) 

S.No. Name of Stations 

Owner Present tap position 

*Suggested tap Position 

Date & TIME  

A. 400kV Stations    

1  Abdullapur  POWERGRID  9B  11  18:25/24.10.20165 

2  Agra UP  UPPTCL  ‐ Tap position number 

increase by one   

3 Akal 

RRVPNL  9 Tap position number increase by one 10 

19:34/26.10.2016 

4  Allahabad  POWERGRID  11  13    

5  Amritsar  POWERGRID  9B  11  19:15/24.10.2016 

6 Azamgarh 

UPPTCL  ‐ Tap position number 

increase by one    

7  Bahadurgarh  POWERGRID  7  11    

8 Bareilly UP 

UPPTCL  ‐ Tap position number 

increase by one    

9  Bawana  DTL  ‐  11    

10 Daultabad 

HVPNL  10 Tap position number increase by one 11 

12:30/26.10.2016 

11 Dehar BBMB 

BBMB  ‐ Tap position number 

increase by one    

12  Dhuri  PSTCL  9B  11  14:25/13.10.2016 

13  Fatehabad  POWERGRID  9B  11  13:26/13.10.2016 

14  Gurgaon  POWERGRID  9B  11    

15  Hamirpur  POWERGRID  9B  11  12:50/11.10.2016 

16  Hisar  POWERGRID  9B  11    

17  Jalandhar  POWERGRID  9B  11  13:35/11.10.20146 

18 Kabulpur 

HVPNL  ‐ Tap position number 

increase by one  19:35/25.10.2016 

19 Kaithal 

POWERGRID  9B Tap position number increase by one 10 

17:25/24.10.2016 

20  Kishenpur  POWERGRID  9  11  17:20/11.10.2016 

21  Ludhiana  POWERGRID  9B  11  15:45/11.10.2016 

22  Makhu  PSTCL  9B  11    

23  Malerkotla  POWERGRID  9  11  15:03/11.10.2016 

24  Mandola  POWERGRID  9B  11    

25 Meerut 

POWERGRID  9B  11 Already at 11 (no 

change) 

26  Moga  POWERGRID  9B  11  16:25/11.10.2016 

27 Moradabad 

UPPTCL  ‐ Tap position number 

increase by one    

28 Mukatsar 

PSTCL  9 b Tap position number increase by two 11  16:25/13.10.2016 

29 Mundka 

DTL  ‐ Tap position number 

increase by one    

30 Muzaffarnagar 

UPPTCL  ‐ Tap position number increase by three    

31  Nakodar  PSTCL  9B  11  16:36/13.10.2016 

32  Nalagarh  POWERGRID  9B  11  13:50/11.10.2016

33 Nuhiyanwali 

HVPNL  9B Tap position number increase by one 10 

18:00/25.10.2016 

34 Obra B 

UPPTCL  ‐ Tap position number 

increase by two    

35  Panchkula  POWERGRID  9B  11  17:28/24.10.2016 

36 Panki 

UPPTCL  ‐ Tap position number 

increase by one    

37  Patiala  POWERGRID  9B  11  13:10/11.10.2016 

38 Sarnath 

UPPTCL  ‐ Tap position number 

increase by one    

B. 765kV Stations    

39  765kV Anpara‐D  UPPTCL  14  11    

40  765kV Meerut  POWERGRID  12  11    

41  765kV Moga  POWERGRID  12  11    

42  765kV Unnao  UPPTCL  16  12    

43  765kV Bareilly  POWERGRID  12  9    

*Note: Generally, tap change control is at HV side except in case of Panipat in Northern region where tap change control is at 220kV side. Tap position number increase by one : If present tap position number is 9 , it is proposed to increase the tap position number to 10 ( By increasing the tap position number, Voltage at HV side decreases) Tap position number decrease by one : If present tap position number is 9 , it is proposed to decrease the tap position number to 8 ( By decreasing the tap position number, Voltage at HV side increases) 

Annex‐III 

ATC of state control area of Northern region 

State ATC during Summer/Monsoon (MW)

Constraints/Issues Discussion in meetings

Punjab ~6500

N-1 non-compliant at Dhuri, Amritsar, Malerkotla & Patiala ICTs.

Underlying network of Amritsar and Ludhiana.

No underlying connectivity at 400kV Patran.

Following are the element to be commissioned that may relief the transmission constraints as provided by Punjab SLDC: 1. Amritsar:

Erection of 220kV DC line from Makhu to 220kV Rashiana (expected date: 31.12.2016).

Erection of 220kV DC line from Makhu to 220kV Algaon (expected date: 31.05.2017).

540MW Generation at GVK Goindwal Sahib.

2. Patiala ,Dhuri & Malerkotla

400/220KV, 500MVA, 1st ICT at 400kV Dhuri (Re commissioned: 06.08.2016).

LILO of 220kV Patiala- 220kV Mandi Gobindgarh D/C line at 400kV Rajpura (31.08.2016).

LILO of 220kV Patran- 220kV Kakrala 220kV line at 400kV PGCIL Patran (expected date: 31.10.2016)

LILO of 220kV Patran –220kV Rajla 220kV line at 400kV PGCIL Patran(expected date: 31.10.2016)

Erection of 220 kV D/C line from 400kV Rajpura to 220kV Devigarh(expected date: 31.12.2016)

Commissioning of 400/220KV, 500MVA, 3rd ICT at 400kV Dhuri (expected date: 28.02.2017)

3. Ludhiana: 220kV DC line from 400kV Nakodar to

220kV Ladhowal (expected date: 31.03.2017)

LILO of 220kV Humbran - 220kV Ferozpur Rd Ludhiana line at 220kV Ladhowal (expected date: 31.12.2017).

Haryana ~6300

N-1 non-compliant at Ballabhgarh, Kaithal, Gurgaon, Dhanoda 220kV network of Hisar PG, 400kV Mahindergarh-Bhiwani D/C, 220kV Charkhi Dadri-Lula Ahir.

Isolator rating issue at 400kV Nawada & 400kV Dhanonda (constraining evacuation of HVDC Mundra-Mohindergarh) power substations.

Tower collapse at 400kV, 220 & 132 kV level

No underlying network at 400/220kV Jind, Bhiwani, Kurukshetra

All issues have been discussed since 125th to 127th OCC meeting.

400/220kV, 315MVA ICT-2 at Ballabhgarh has been replaced by 500MVA capacity (Sept’16).

As reported by HVPNL in 127th OCC meeting Isolator at Nawada has been replaced in sept’16.

Isolators at Dhanonda are expected to replace by Dec’16.

Many 400kV (~4) and 220kV (~ 12) lines were remain under breakdown for more than a month due to tower collapse, reduces the reliability & evacuation issues in the interconnected network. Breakdown of 400kV Jhajjar-Daultabad D/C constrained evacuation of Jhajjar generation.

Rajasthan

~4500

N-1 non-compliant at Bhilwara, Bassi, Jodhpur, 400kV Phagi-Bassi.

In wind pocket, Akal ICTs are overloaded and Outage of large wind generation (LVRT issues)

N-1-1 non-compliant of 765kV Anta-Phagi D/C.

Evacuation Issue of Kawai/Kalisindh/Chhabra Complex.

SPS of Kawai/Kalisindh/ Chhabra has been implemented.

In view of large generating complex and connected to Phagi/Gwalior, it was suggested to plan for N-1-1 contingency in this complex.

765/400kV Phagi ICTs are also not N-1 non-compliant.

400kV Phagi-Bassi D/C (Quad moose) loading remains in the range of ~1800-2000 MW.

Planned network at 400kV Phagi-Heerapura and Phagi-Ajmer D/C is still to be commissioned.

During thunder storm on 23rd May 2016, tripping of both 765kV Anta-Phagi (One on fault and other were manually tripped due to isolator burnt at Anta end) lead to generation loss of whole complex. Therefore, N-1-1 planning of this complex is very important for Grid security and reliability.

Kalisindh ICT is out since 4-June-2016 and Jodhpur ICT-2 is out since 10-Aug-2016

Delhi ~4500

N-1 non-compliant of Mandola, Bamnoli, Maharani Bagh.

N-1-1 security of south Delhi area around BTPS.

Open 400kV transmission ring at two places Bamnoli & Mundka S/s. in Delhi.

High loading around 220 kV Wazirabad/Geeta Colony.

Connectivity at Mundka, Harsh Vihar, 220kV Gazipur-Noida and 220kV Badarpur-Noida is out since Sep-14 due to faulty cable.

400/220kV, 315MVA ICT-1, 3 & 4 at Mandola has been replaced by 500MVA capacity each.

400/220kV, 315MVA ICT-2 & 3 at Bamnoli has been replaced by 500MVA capacity each.

Opening of Delhi ring due to tower collapse of 400kV Jhatikara-Bamnoli D/C and one ckt is charged on ERS tower and other one is still out.

Split Bus operation at Bamnoli leading to overloading of three ICTs those are on one bus.

400kV Bawana-Mundka D/C is also under shutdown since 27th Sep 2016 (tentative schedule was 15th Oct 2016, still under s/d) due to increase in height of tower (Metro construction)

400kV Bamnoli-Jhatikara is out since 22nd May

2016

New 220 kV Loni Road-Patparganj and Wazirabad to be expedited.

Uttar Pradesh

~7200-7700 depends on

own generation of

UP

N-1 non-compliant of Agra (UP),Muradnagar, Muzaffarnagar, Unnao, Mainpuri, Allahabad, Lucknow UP, Azamgarh & Sultanpur ICTs.

Evacuation network of new generating stations Anpara D, Bara and Lalitpur.

N-1-1 security of

SPS for evacuation of Anpara-D is still pending.

Third ICTs at 765/400 kV Unnao is still awaited.

Elements should be expedited as early as possible:

400kV Gr. Noida, 400kV Gr. Noida –Gr.Noida (765kV) D/C

765kV Lalitpur-Fatehabad (Agra)-2 & LILO of one ckt of 400kV Agra (PG)-Agra (UP).

765kV Bara-Mainpuri D/C.

Greater Noida/Noida area

Radial connectivity at Muradnagar (New),

No underlying connectivity at Sohawal.

765kV Anpara D-Unnao.

765/400kV, 100MVA 3rd ICT at Unnao.

Uttarakhand

~900-950

N-1 non-compliance of 400/220kV Kashipur,

N-1 non-compliance of 220kV Roorkee(PG)- Roorkee(PTCUL),

Heavy overdrawal has been observed in Uttarakhand. Loading of Kashipur ICTs also remained n-1 non-compliant most of the time. It has been discussed and highlighted in OCC meetings also. It has been observed that Gas generation at Kashipur has slightly relief the loading of Kashipur ICTs.

Himachal

Pradesh ~1000

N-1 non-compliance of Panchkula / 220kV network of Madanpur/ 220/132kV Kunihar ICTs

Overdrawal by HP and same time selling the power in STOA has been observed. Better planning has been suggested number of times. HP was suggested to banking the other arrangements for sudden hydro outages due to silt and other issues.

Jammu &

Kashmir ~1800

N-1 non-compliance of Wagoora ICT, underlying 220kv network of Wagoora, Kishenpur.

No underlying network at Samba, New Wanpoh

Any N-1 contingency in the 400kV or 220kV network in the valley lead to complete blackout of Kashmir Valley.

Full substation outage due to any maintenance because of Single Bus and transfer schemes in all the 220kV substation of Jamm & Kashmir.

Recently Gladini/Heeranagar/ was full out due to the maintenance work at 220kV Gladini/Heeranagar, whole substation has to shutdown affecting the load and reliability of Jammu area.

Note: In winter, due to change in load generation scenario and element that are expected may change the TTC/ATC of respective control area/Interconnected network.

Annex-IV