FC501

www.fireclass.net

Addressable Fire Control Panels

User Manual

Page 2: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

This Fire Control panel can be programmed only usingthe Software FireClass Console release 1.0 or higher.

Control panel FW ver. 1.0 or higher.

TYCO and BENTEL SECURITYsrl shall not assumethe responsibility for damage arising from improper ap-plication or use. This Control panel has been designedand manufactured to the highest standards of qualityand performance. Installation of this Control panel mustbe carried out strictly in accordance with the instruc-tions described in this manual, and in compliance withthe local laws and bylaws in force.

The FC501 Fire Control panel complies with the essen-tial requirements of standards EN54-2: 1997+A1:2006;

EN54-4: 1997+A1:2002+A2:2006; EN 54-21.

The manufacturer reserves the right to change the tech-nical specifications of these products without prior no-tice.

Recycling information

The manufacturer recommends that customers dis-pose of their used equipment (panels, detectors, sirens,and other devices) in an environmentally sound man-ner. Potential methods include reuse of parts or wholeproducts and recycling of products, components,and/or materials.

Waste Electrical and Electronic Equipment (WEEE)

Directive

In the European Union, this label indicates thatthis product should NOT be disposed of with householdwaste. It should be deposited at an appropriate facilityto enable recovery and recycling.

NOTE- The FC501 Fire control panel can support several

addressable devices (Detectors, Modules, Manual call

Points, etc). The present manual includes the instructions

for their programming, but for further information on those

devices and their accessories, please visits:

www.fireclass.net.

� Maintenance

To ensure that the system continues to operate nor-mally it must be maintained with regular testing by theuser and periodic maintenance by the installer in accor-dance with local laws.

�For the maintenance of other devices such as de-

tectors, modules, etc. follow the dedicated instruc-

tions for the devices.

The following operations must be carried out regularly.

A Using a damp cloth (DO NOT USE SOLVENTS OFANY KIND), remove dust from the Control panel cabi-net.

B Using the Lamp Test key, check that the LEDs andbuzzer are functioning properly.

C Ensure that the batteries are sufficiently charged andfunctioning properly. If not, replace them immediately.

D Ensure that all cables and connections are intact.

E Ensure that there are no unrelated objects inside theControl panel case.

F Ensure that the control panel is capable of process-ing a fire alarm and if a siren (sounder) is present in thesystem, it is activated in consequence of this alarm. Ifthere is a facility for transmission of fire alarm signals toa Central Station, it should also be ensured that the sig-nal is correctly received.

G Also verify the actual functionality of the circuit for thedetection of earth fault. The procedure is as follows:

� connect one of the SH terminals of the loop to thepanel ground (earth);

� verify that the fault is reported correctly by the FirePanel;

� remove the connection previously made.Points A and B may be carried out by users.Points C, D, E, F and G must be carried out by qualifiedpersons only.

Page 3: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

TABLE OF CONTENTS

INTRODUCTION 5FC501 Fire Control Panel 5

Accessory items 5

User Access Level 5

USER INTERFACE 6Description of Keys 6

Panel Command keys description (Table n.1) 6

Silence/Resound/Sounders 6

Reset 6

Key Help 6

Signalling 7

The status LEDs 7

Buzzer (Audible Signals) 7

Description of the Repeater FC500REP LEDs 7

DISPLAY 7

START-UP PAGE 7

FRONT PAGE 9

MAIN PAGE 9

Diagnostic pages 10

MENU page 10

The EVENT DRIVEN pages 10

WARNING STATUS 10

PREALARM STATUS (Delay to Alarm) 11

ALARM STATUS 12

FAULT STATUS 13

Locate loop break pages 14

Locate the not addressed devices 14

VIEW-LOG-PARAMETERS 15View parameters 15

1 KEY - View Loop 16

View of Loop Details 16

2 KEY - View Devices 16

Select the Loop 16

Select the device 16

View device data on the Loop 17

3 KEY- View SW Zone 18

4 KEY- View Output 18

5 KEY- View NETWORK 19

6 KEY- COMMUNICATORS 19

7 KEY- View Option 20

8 KEY - View Log 20

View Log 20

9 Key - View FW version 21

0 Key-Panel 21View Lists (Press 4= MORE and then 2) 22

MODIFY 23MODIFY MENU 23

1 KEY -INIT MSG (Modify panel label) 23

2 KEY - User Password 24Insert or Modify Password 24

3 KEY-DAY/NIGHT 24

Day/Night Mode 24

4 Key-Time and Date 25

5 Key- Clear LOG 256 KEY- Zone WALK TEST 26

SW zone in WALK TEST 26

DISABLE 271 Key - Disable list 282 Key - Devices (Disable) 28

Select the Loop 28

Select the Device 28

Disable device on the Loop 28

3 Key - SW zone 29

Select SW zone 29

Disable SW Zone 30

4 Key - Outputs 30Select the Output 30

Disable Output 30

5 Key - Network 30

Select the Network device 30

Disable Network device 31

6 Key - COMMUNIC. (Disable) 31

Select the COMMUNIC. device 31

Disable COMMUNIC. device ��

7 Key-Password (Disable) 32

Select the Password ��

Disable Password ��

8 Key -Fire Relay 32

Repeater FC500REP Signalling 33

Description of command Keys 33

LCD DISPLAY DESCRIPTION 33

EVENT DRIVEN page description 33

Description of Status LED 33

Page 4: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

4 Addressable Fire Control Panel FC501

Page 5: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

INTRODUCTION

FC501 Fire Control Panel

The FC501 is available in the following models:� FC501-L - Addressable Control Panel with 3 different

and isolated loops, that can support up to 128 ad-dressable devices and 32 zones.Power Supply: BENTEL Switching power supplyBAQ35T24 (1.5 A @ 27.6 V).Suitable Batteries: 2 * 12 V/ 7Ah

2 * 12 V/ 12Ah.� FC501-H - Addressable Control Panel with 3 differ-

ent and isolated loops, that can support up to 128 ad-dressable devices and 32 zones.Power Supply: BENTEL Switching power supplyBAQ60T24 (2,5 A @ 27,6 V).Suitable Batteries: 2 * 12 V/ 12Ah

2 * 12 V/ 38Ah.

�In this manual the term FC501 is used to describe

the characteristics common to all versions while

the version name is used to describe the differ-

ences between the versions listed above

FC501 The FC501 control panel is a modular system.The configuration of the FC501 system depends on thesize and requirements of the application, therefore,some of the described devices and functions may notbe present on your system.The FC501 system consists of:one FC501 control panel,max 4 FC500REP Repeaters,max 4 FC500MFI Multifunction Modules,max 128 devices in three different loops or 128 max in a

single loop only.The FC501 control panel allows users to manage thefunctions of the Fire control system up to 2000 m (Loop)with shielded cable 2 cores 2x2.5 csa.

� Accessory items

FC500REP Repeater Repeaters are peripherals thatprovide all the system status information, emit audiblesignals and allow users to control the functions of theFC501 system (up to 1000 m, with double twist shieldedcable).

FC500-MFI FC500-MFI is a Programmable Multi func-tional Module for connection of a real time event printer;furthermore, thanks to the terminal blocks, it is also pos-sible to connect a “standard interface” to remotely con-trol and manage a set of Inputs and Outputs to controlthe panel.

Software FireClass Console This user-friendly soft-ware application (Microsoft Windows XP & above) of-fers a quick and easy way to program the Control paneland provides event log and print-out functions.

User Access Level

L1= Access level 1: Viewing: everybody can view theControl panel status. In detail:-ANALYZE shows the status of the: 1- LOOP, 2- DEVICE, 3-SW ZONES, 4- OUTPUTS, 5- NETWORK, 6- COMMUNIC.,7- OPTIONS, 8- LOG and 9- FW Vers, 0-Panel.;-VIEW LOG shows the LOG;-VIEW LISTS shows the lists of: 1- DIS. ZONES, 2- DIS.DEVICES, 3- DIS. PARTS, 4- WALK TEST, 5-FAULTS, 6- WARNINGS and 7- DEV. in TEST.L2= Access level 2 or User Level: Operating the sys-tem (Access Code entered : ONLY Access Code canoperate the system). At this Level, all the operations ataccess LEVEL 1 are available and in addition:-MODIFY for: 1- INIT. MSG, 2-USER PASSWORD, 3-DAY/NIGHT, 4- TIME and DATE, 5- Clear LOG, 6-ZONE WALK TEST.-DISABLE for: 1- Dis.LISTS, 2- DEVICES, 3- SWZONES, 4- OUTPUTS, 5- NETWORK, 6-COMMUNIC., 7- PASSWORD, 8- FIRE relay.

INTRODUCTION 5

ZONE

1

ZONE

2

ZONE

3

ZONE

4

ZONE

5

ZONE

6

ZONE

7

ZONE

8

1

2

3

4

GENERAL FAULT MORE INFO

SYSTEM FAULTSOUNDERS

SILENCED

FIRE SIGNAL

FAULT

FIRE SIGNAL

ON

POWER SUPPLY

FAULT

SOUNDERS

FAULTS/DIS

EARTH FAULT DISABLED

BATTERY

TROUBLETEST

POWER ON DAY MODE ON

CONTROLS

ON

SILENCE BUZZER

SILENCE/RESOUND

SOUNDERSRESET

INVESTIGATION

DELAY

LAMP TESTEVAC

FIRE

MSACMNEEFC501D0.0

2 3

A

D

B C

E F

ABC1 DEF GHI

JKL MNO PQR4 5 6

STU VWX YZ7 8 9

0 ?ESC ]

Figure 1 User interface View

Page 6: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

USER INTERFACE

Description of Keys

To manage the panel from the User interface the follow-ing controls are used:� the Alphanumeric keypad;� the Cursors Keys UP ( ), DOWN ( ), RIGHT ( )

and LEFT ( );� ESC Key;� ENTER Key ( );

� The Help button to open the Help pages on thedisplay (see example in Figure 2).

� The Command Keys.

�The Cursors Keys UP, DOWN, RIGHT and LEFT

and the Command Keys LAMP TEST and

SILENCE BUZZER are used to enter the charac-

ters A,B,C,D,E,F respectively, to quickly enter hex-

adecimal numbers (future use).

The function of the Cursors Keys, ESC key, ENTERKey and Command Keys is different in every LCD dis-play and is fully described in the following pages. Alsothe pressure time of the keys will have a different use infunction of the different LCD display. Use the Help keyfor explanations.

� Panel Command keys description (Table n.1)

�Only the Lamp Test, Silence Buzzer and Evacu-

ate Command buttons can be operated without the

access code (access level L1), all the other Com-

mand buttons can be operated after the access

code is entered (access level L2 and L3)

� Silence/Resound/Sounders

The control panel can operate in DAY or NIGHT Mode.If the system is silenced during DAY Mode, SILENCEstatus will be held until the system is unsilenced (i.e. un-less new alarms or faults occur). If the system is si-lenced during NIGHT Mode, SILENCE status will beheld until the Night Mode Silence time expires (refer to“Silence” ). On power up (at default) the system will setto DAY Mode. During this operating mode, silencedalarms/faults will not be unsilenced automatically.

�This Control panel will generate an Instant Alarm if

alarm conditions are detected during Night Mode

or if an alarm is triggered from a Callpoint.

� Reset

RESET will stop Alarm, Prealarm, Warning and FAULTconditions. Access to this command is limited to autho-rized personnel only (installer or user access code).The system will reprocess any alarm, prealarm, warningor fault signal which is not cleared by RESET operations.Command keys cannot be used when RESET is running.The repeaters can be RESET by the installer or useraccess code.

Key Help

To explain the information on the LCD display in the differentpages, an embedded help feature is present on thepanel LCD display. For each User Interface page active,when the help key is pressed the full text in memory willbe scrolled, line by line, in the window of the Help page.

6 Addressable Fire Control Panel FC501

Key Icon DESCRIPTION

Lamp Test This key can be used to test the buzzer , the LEDs and LCD module . If this key is pressed

(when the Control panel is functioning as intended), all the LEDs will glow and the buzzer

will emit a continuous beep.

Silence/

Resound/

Sounders

This key can be used to restore the Silenceable outputs to standby status. Silence status

will be held until the Silence key is pressed again in Day Mode, or if the Control panel is

operating in Night Mode, until the Night mode Silence time expires or until a new

Alarm/Trouble condition is detected.

Investigation

Delay

This key can be used to refresh the “PreAlarm Time”; if this key is pressed during “PreA-

larm”, the remaining PreAlarm time will be increased with the programmed "Investiga-

tion delay".

Silence

Buzzer

Key to silence the local buzzer of the control panel; the buzzer will operate every time a

new event occurs.

Reset This key can be used to reset the Fire detectors and restore all outputs to standby status

(Supervised/Silenceable outputs, NON-Supervised/Non-Silenceable outputs and Alarm

zone outputs).

Evacuation Key to activate the evacuation; if this key is pressed, the system will generate an alarm.

Table 1 Command keys description (The icons are not shown on the UK panel.)

?

?

?

?

Page 7: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

A dedicated text will be present in every page of theUser interface.See the following example: key Help functions for the“Main page”. In the following the full text in memory:

1- To select Program or Analyze mode.2- To select Disable or View list mode.3- Shows the panel event log or select the Modify mode.4- Select between the function groups related to thekeys 1,2,3.ENTER: No action.ESC: Exit from the HELP to MAIN page, or event drivenpage, if any.Pressing the key for more than 3 sec. the panel will beforced to level 1.The Up and Down key: scroll HELP list.No action is related to the Right and Left key.

Signalling

The system status is indicated by the:

- control panel LEDs;- back-lighted display (40 characters on 4 lines);- buzzer.

� The status LEDs

The following table n.2 describes how the Control panelLEDs operate, and the actions that can be taken duringthe various phases signalled on the LEDs.

�During standby status, ONLY the GREEN Mains

LED and the Day mode LED (if the control panel is

in Day mode) should be On (glowing).

�The General FAULT LED and the LED relative to

the Fault, slow blinking ONLY indicates a FAULT

event in memory.

�To manage the brightness and contrast of the LCD

display see MAIN page.

� Buzzer (Audible Signals)

The control panel buzzer provides audible indication ofthe panel status. The buzzer signalling is discribed inthe Table n. 3.To test the buzzer press LAMP TEST. The buzzer can-not work when the SILENCE Buzzer is pressed .

�When an Alarm status has been silenced and a new

Fault signal has been detected, the control panel re-

starts the buzzer with the previous Alarm signal.

� Description of the Repeater FC500REP LEDs

The table on page 34 describes the function of theLEDs and Keys on the User Interface of the repeaterFC500REP.

DISPLAY

The information on the LCD display is organizedas pages. There are the following kinds of pages:START-UP PAGEFRONT PAGEMAIN PAGEDIAGNOSTIC PAGESMENU PAGEEVENTS DRIVEN PAGE

� START-UP PAGE

The START-UP page is displayed at the panel start-upif some vital informations for the User Interface are notprogrammed. These information are:� Selected language� Panel Identification number� The panel type (FC501-l/FC501-H)� The installed battery capacity (7Ah/12Ah/38Ah)The selected language is vital for the User Interface to se-lect between the two available languages in the panel.The panel Identification number is vital for the panel toname and manage the files over the USB memory stick.

�During the start-up page the panel is not fully oper-

ative and the controls keys are not working

USER INTERFACE 7

1= lev.1 : ACTIVEAnalyze

2=View lists MASTER PANEL

3=View Log SCANNING LOOP

18:50 27 - 17/10/12:4=More

Access Level

If it blinksindicates theControl paneloperating normally

Working Activity

Control panel Status

Control panel name,the user can modify it

Help for: MAIN PAGE UP/DOWN

1 To select the Analyze mode

2 To select the View list mode

?

ESC or after 30 sec. of inactivity

Figure 2 Example of the LCD display after pressing

the Help key

ALARM PAGE PRE-ALARM PAGE FAULT PAGE WARNING PAGE WALK TEST PAGE

MAIN PAGE

or wait3 sec

EVENT DRIVEN PAGES

MAIN PAGE

ESC

EVENT DRIVEN PAGES AND MAIN PAGE BASIC INTERACTIONS

MAIN PAGE, FRONT PAGE AND MENU PAGES BASIC INTERACTIONS

FRONT PAGE

ESC

Wait30 sec (*)

4JKL

1ABC 2DEF 3GHI 1ABC 2DEF 3GHI

MENU PAGES

ANALYZEMENU

VIEW LOGPAGE

VIEW LISTMENU

PROGRAMMINGMENU

DISABLEPAGE

MODIFYPAGE

ESC

(*) Only if the panel is in its normal activity

(**) No timeout for ANALYZE menu, VIEW LOG page,VIEW LIST page. The timeout is extended to 4 minutesin the programming menu during the entering of parameters

or wait60 sec (**)

Figure 3 Event driven pages and Main page basicinteractions

Page 8: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

8 Addressable Fire Control Panel FC501

LED ICON DESCRIPTION

FIRE

(Red)

Glowing indicates Alarm status. In the event of an Alarm, the Control panel will activate the

unbypassed alarm outputs.

SOFTWARE

ZONES

(Red) (1-8)

-Glowing indicates that the corresponding Software zone is in Alarm status (*)

Slow Blinking indicates that the corresponding Software zone is in Pre-Alarm status.

OFF indicates no alarms, the zone is in stand-by status

FIRE SIGNAL

ON (Red)

Glowing indicates that transmission was successful.

Slow Blinking indicates that transmission is in progress. On the display of the control pa-

nel it is possible to know the connection type: PSTN, GSM, or LAN network.

OFF indicates the communicator is in stand-by status

GENERAL

FAULT

(Amber)

Glowing indicates the presence of a Fault: the following LEDs or the screen on the display

indicates the type of the Fault.

Slow blinking indicates a fault event in memory (Reset turns OFF )

OFF indicates no Fault

SYSTEM

FAULT

(Amber)

Glowing +Buzzer (**) indicates a blocked Control Panel. IMPORTANT: Maintenance required

Slow blinking + Buzzer (***)indicates the Control Panel restart

Fast blinking + Buzzer (***) indicates that the panel programming data is corrupted

NOTE – When the Control panel is switched on for the first time, this LED will blink until a

Reset has been performed.

FIRE SIGNAL

FAULT

(Amber)

Glowing indicates the communicator has been disabled;

Slow blinking indicates that the communicator has broken down;

OFF indicates no fault relative to communicator.

SOUNDERS

FAULTS/DIS

Glowing indicates that SC 1 Output is disabled or SC2 "act as SC1" is disabled,

Slow blinking indicates that SC1 is in fault or SC2 "act as SC1" is in fault.

OFF indicates all the SC outputs function properly.

EARTH

FAULT

(Amber

Glowing indicates a Voltage leakage to Earth.

IMPORTANT: Check wiring insulation;

OFF indicates no Earth faults are present.

BATTERY

TROUBLE

(Amber)

Glowing indicates Batteries empty or faulty. If this condition persists, the batteries will be una-

ble to function as intended in the event of blackout, IMPORTANT: New batteries required.

Slow blinking indicates a fault event in memory (Reset turns OFF )

OFF indicates the batteries are healthy.

POWER

SUPPLY

FAULT

(Amber)

Glowing indicates Mains failure (230 Vac) ;

Fast blinking indicates Switching Power supply fault.

During this condition, the Control panel will be powered by the batteries.

OFF indicates the presence of the Main and the power supply functions properly

DAY MODE Glowing indicates that the Control panel is operating in DAY MODE

OFF indicates that the Control panel is operating in NIGHT MODE

DISABLED Glowing indicates the Disabled status of any bypassable entity.

OFF indicates no entity is disabled

SOUNDERS

SILENCED

(Amber)

Glowing indicates that Silenceable outputs and Loop devices have been forced to

standby by means of SOUNDER SILENCED key; in Day Mode the SILENCE will remain

until the SILENCE key is pressed again, while in Night Mode after the Silence Time expi-

res automatically the SILENCE will end.

Test Glowing indicates Test conditions on at least one zone.

OFF indicates no zone is in Test

MORE INFO

(Amber)

Glowing indicates that there is hidden information with lower priority: access to the page

View List to show the hidden information.

OFF indicates no hidden information is presents.

CONTROLS

ON (AMBER)-

Glowing indicates that the Control Panel is at least at level 2 so the Silence/Resound So-

unders, Reset and Investigation Delay Keys are enabled

POWER ON

(Green)

Glowing indicates panel is supplied with power.

OFF indicates Mains failure (both mains & battery power is lost) (Battery disconnect

threshold: 19,2 V). Mains Power must be restored before the batteries reach the discon-

nect threshold.

Table 2 Description of the status LEDs. (*) the zone outside this range (1 to 8) didn’t have a related LED, its alarm sta-

tus is displayed only by the LCD, (**)buzzer SYSTEM FAULT pattern, (***)buzzer FAULT pattern,

These icons are not shown on the UK User Interface panel.

Page 9: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

� FRONT PAGE

The FRONT page is the page normally displayed whenthe panel is in Stand-by status. It can contain an adver-tisement message set by the installer. The page con-tent, and the enablement to display it are set by theFC500Console SW.

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor keys No function is related to the UP, DOWN,RIGHT and LEFT keys.

ESC Key Exit from the FRONT page, moves theUser Interface to MAIN page or EVENT DRIVENpage, activated directly by Events: WARNING,PRE-ALARM, ALARM, FAULT or WALK TEST.

ENTER Key No function is related to the ENTER key.

�To permanently remove the FRONT PAGE, it may

be re-activated downloading into the panel a new

front page using the FireClass Console SW (see

Screen saver Menu on Installation Manual)

� MAIN PAGE

This is the first page displayed by the panel after thepower-up (see Figure 5). This page can be replaced bythe EVENT DRIVEN page.When the panel starts its normal activity and no ac-cesses to the User Interface are sensed for a period of30s, the User Interface leaves the MAIN page andreaches the FRONT page.The access level field shows the current access level ofthe panel. 10 s before leaving the present access levelthis field starts to blink.

The panel mode field displays the current panel mode,the possible values are:“ACTIVE ”, the panel is active, its normal state.A continuous panel heart beat blinking indicates thatthe panel is functioning properly.The panel activity field displays the current activity ofthe panel, the possible values are:

“RESETTING ” The panel is resetting;“LOC. PROG ” The panel is being programmed by a lo-cal access;“REM.ACCESS” The panel is remotely accessed (PCvia serial port, USB or IP);“SYS. INIT ” The panel is initializing;“SYS. VER: ” The panel is verifying itself;“CLEAR LOG ” The panel is clearing the event log;“ WAITS ” The panel is waiting to be configured;“—————” No activity;“IS SCANNING LOOP” The panel is in its normal activity.

�The date and time field blinks until the date and

time is set.

In this phase:

Alphanumeric keypad The 1 key moves the panel toProgram or Disable mode;The 2 key moves the panel to Analyze or View lists

mode;

USER INTERFACE 9

FIRECLASS 501

FireClass

www.fireclass.net

Figure 4 Display FRONT page (stand-by status)

1=Program lev.1 : ACTIVE

2=Disable MASTER PANEL

3=Modify SCANNING LOOP

18:50 27 - 17/10/12:4=More

Access Level

If blinkingcontrol panelworking properly

Current phase

Control panel status

Control Panel name(It can be modified by User)

1=Analyze lev.1 : ACTIVE

2= ew istVi L MASTER PANEL

3=View Log

18:50 27 - 17/10/12:

SCANNING LOOP

4=More

Figure 5 Display MAIN page -Access to the manage-

ment of the Panel

Condition Frequency (Hz) Sound Pause

SYSTEM FAULT (main processor fail ) 1300 2.5 s 2.8 s

GENERAL FAULT (Programming data corrupted) 660 1 s 1 s

Alarm 3300 0.2 s 0.2 s

Fault 660 1 s 1 s

Delay to alarm (Pre-alarm) 880 0.5 s 0.5 s

Warning 440 2 s 2 s

Reset No sound

Test No sound

Table 3 Buzzer Signalling

Page 10: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

The 3 key shows the panel View log or moves thepanel to the Modify mode;The 4 key selects between the function groups relatedto the keys 1,2,3.

Cursor keys The UP Key: increase the brightness ofLCD display;the Down Key: decrease the brightness of LCD display;the Right Key: increase the contrast of LCD display;the Left Key: decrease the contrast of LCD display;

ESC Key Exit from the MAIN page, moves the User In-terface to FRONT page or EVENT DRIVEN page.Pressing the key for more than 3 sec. the panel will beforced to access Level 1.

ENTER Key No function is related to the ENTER key.

� Diagnostic pages

These pages allow:� To know some electrical parameters inside the panel

(Panel meter page)� To know some functional parameters related to the

loops (LOOP page)� To execute the panel keyboard test (KEYBOARD

TEST page).These pages are reached during the normal operationfrom the Main page after a long pressing of the key 4.

� MENU page

The MENU pages allows the access to the PROGRAM,ANALYZE, DISABLE and MODIFY features of thepanel. The part relating to the User will be explained inthe sections of this manual: ANALYZE, DISABLE andMODIFY. The part relative to the Installer will be ex-plained in the section PROGRAM in the Installer man-ual.

� The EVENT DRIVEN pages

The EVENT DRIVEN pages are pages that are activatedby events in the system and when they becomes activethey override the page present on the display at that time.Also an EVENT DRIVEN page may be overridden by an-other EVENT DRIVEN page that has a higher priority.The following table contains the EVENT DRIVEN pagepriority assignment.

The Event Driven pages Priority

ALARM 0 (highest)PREALARM 1

FAULT 2WARNING 3

WALK TEST 4 (Lowest)In the case of lower priority Event pages (one or more)being suppressed by the highest priority Event page,the MORE INFO LED is ON. In this condition thesuppressed EVENT pages may be manually reachedusing the View list. entry in the MAIN page.

�WARNING STATUS

The FC501 fire control panel can be programmed toprovide WARNINGS or PREALARMS status beforeALARM status.The Warning status will be signalled by the WARNINGdisplay (see Figure 6). The panel will generate a warn-ing when an input point (detector) exceeds its warningthreshold and there is risk of an alarm.WARNING STATUS will be signalled by:� Warning output points;� fire control panel Display;� intermittent audible signal on the panel buzzer;� the FC500REP repeater.In this phase:

Alphanumeric keypad 0 key: if the Warning is relatedto an item that may be disabled, the User Interfacemoves to the disabling page. In order to allow a fast dis-ablement procedure;1 key: to jump to the Zone status visualization page;2 key: if the first Warning is related to a point, jump to

10 Addressable Fire Control Panel FC501

Total :0015 Status: Warning

First : MS:Loop 1 det025 zone=078

Last : MS:Loop 1 det030 zone=080

#0011 : MS:Loop 1 det034 zone=090

Warnings Number

Stored Warningindex

Last Warning

Control panel statusFirst Warning

This symbol showsthe presence of followingblocks to be scrolled by Right cursor key,the symbol shows the presenceof previous blocks to be scrolled byLeft cursor key.

1° block:Point identification

If it blinksindicates theControl paneloperating normally

Figure 6 DISPLAY: WARNING STATUS

LOOP

A avg=096 , min=090 , max=106

B avg=170 , min=165 , max=192

C count = 0000

Panel meter

ESC ESC

KEYBOARD TEST

ESC

Figure 7 Interaction between the Diagnostic pages

Page 11: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

loop device status visualization page;3 key: if the last Warning is related to a point, jump toloop device status visualization page;4 key: to display further Warning.When a point Warning is present in the fourth row, a fur-ther 4 key press will cause the User Interface to jump tothe related loop device status visualization page.From Figure 6, in the WARNING STATUS, use theRIGHT Key to scroll the second string of data of Warn-

ing Zones; then use the RIGHT Key to scroll the thirdstring of data of Warning causes; then use the RIGHT

Key to scroll the fourth string of data of Warning Times

and Events.

�If the events are linked to the devices, the zone la-

bel alternates with the point label every 3 seconds.

If the zone has not been associated with the point,

only the point label will appear.

Cursor keys Use the UP Key to view the next event,other than the first and the last;Use the DOWN Key to view the previous event, otherthan the first and the last.Use the RIGHT Key to view the next string of data.Use the LEFT Key to view the previous string of data.

ESC Key Use ESC key to cancel the operation and tostep back to MAIN page.

ENTER Key The ENTER Key blocks/reactivates theexchange between the labels of the devices and thoseof the zones. When the block is enabled, the @ charac-ter appears in the top left-hand corner of the display.

� PREALARM STATUS (Delay to Alarm)

This status indicates that an input point (detector) hasexceeded its alarm threshold. The fire control panel willnot generate an alarm until the preset prealarm- time

ends. However, if a second input point (detector in thesame SW zone) detects alarm conditions during thePrealarm phase (and the “Double knock” option hasbeen programmed for that zone), the fire control panelwill generate an instant alarm.If the fire control panel is operating in NIGHT mode, itwill generate INSTANT ALARMS ONLY (Prealarm sta-tus will be bypassed automatically). If an alarm proce-dure is already running, the fire control panel will ignoreprealarm conditions.

�The EN54-2 requires that at the least, the first zone

in Prealarm, the most recent zone in Prealarm and

the number of zones in Prealarm will be displayed.

Besides to supply the information about the points

in Prealarm, the visualization of the Prealarm (De-

lay to Alarm) will be by zones (default) or by points.

USER INTERFACE 11

Total :0015 status:WARNING

First : zone: R-D department EVAC.

Last : zone=456zone: Air compressor n1

#0011 : zone=245zone: Boiler room

Push the right key to scrollthe second block of data

regarding the WARNING zones

Total :0015 status:WARNING

First : MS:Loop 1 mod012 zone=067

Last : MS:Loop 1 mod182 zone=456

#0011 : MS:Loop 2 det034 zone=245

Total :0015 status:WARNING

First : cause: EVAC.

Last : cause: CP820 Manual

#0011 : cause: 801PH Temp.

Total :0015 status:WARNING

First : Time: 10:46:21 - 01/01/07

Last : Time: 10:47:18 - 01/01/07

#0011 : Time: 10:47:12 - 01/01/07

Push the right key to scrollthe third block of data

regarding the WARNING causes

Push the right key to scrollthe fourth block of data

regarding the WARNING times

Figure 8 Warning status- Scrolling Right key

zones:004 / Dev:013 ALARM+DLY

First z001 det: office 3, first floor

Last z004 det: main corridor

4= : view suppressed Delay to alarm

BlinkingPoints in Prealarm counter

To view further pointsin Prealarm

Last point inPrealarm

Control panel statusFirst Point in

Prealarm

This symbolthe presence of followinginformation: point coordinate

CauseTime

shows

BY POINTS

Point labelswapped with

zone label

30 sec. or

zones:004 / Dev:013 ALARM+DLY

First z001 zone: RD dept. first floor

Last z004 zone: Warehouse

4= : view suppressed Delay to alarm

BlinkingZones in Prealarm counter

To view further zonesin Prealarm

Last zone inPrealarm

Control panel statusFirst zone in Prealarm

If blinksindicates thecontrol paneloperating normal

BY ZONE

Zone labelswapped with

point label

This symbolthe presence of followinginformation: point coordinate

CauseTime

shows

Figure 9 DISPLAY: PREALARM STATUS

Zones:004 / Dev.: 013 ALARM+DLY

First Z001 det.: office 3, south wing

Last Z001 det.: main corridor, north

4= view all

Zones:004 / Dev.: 013 ALARM+DLY

First Z001 Loop 1 mod012 zone=001

Last Z001 Loop 1 mod182 zone=001

4= view all

ALARM+DLYZones:004 / Dev.: 013

First cause: 400PH Temp.Z001

Last cause: 400PH Temp.Z001

4= view all

Zones:004 / Dev.: 013 ALARM+DLY

First Time: 10:46:21 - 01/01/07Z001

Last Time: 10:47:18 - 01/01/07Z001

4= view all

Push the right key to scrollthe second block of data

regarding the Points Coordinate

Push the right key to scrollthe third block of data

regarding the PREALARM causes

Push the right key to scrollthe fourth block of data

regarding the PREALARM times

Push the left key

Push the left key

Push the left key

Figure 10 Prealarm status- Scrolling Right key

Page 12: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

PREALARM status will also be signalled by:� on fire control panel Display;� the LED (1-8) relative the zone in Pre-alarm mode

slow blinking;� an intermittent audible signal on the control panel buzzer;� the prealarm output points.During the PREALARM phase you will be able to SI-LENCE, INVESTIGATE or RESET the system and viewthe LOG.The Display in Figure 9shows that the fire control panelis in PREALARM STATUS: in this phase:

Alphanumeric keypad For the Prealarm by ZONES

or by POINTS the use is the same:1 key: to jump to the Zone status visualization page;2 key: to jump to the first activated loop device status vi-sualization page;3 key: to jump to the last activated loop device status vi-sualization page ;4 key: to display further Points in Prealarm.When a point information is present in the fourth row, afurther 4 key press will cause the User Interface jumpthe related loop device status visualization page.

Cursor keys For the Prealarm by ZONES or byPOINTS the use is the same:the UP Key to view the next available point in Prealarm,other than the first and the last;the DOWN Key to view the previous available point inalarm, other than the first and the last.The RIGHT Key to display the next auxiliary informationabout the point (see Figure 10);The LEFT Key to display the previous auxiliary informa-tion about the point.

ESC Key ESC key to step back to the MAIN page.

ENTER Key Long press -> change between the visu-alization modes;Short press -> stops or restart the zone/point swap.

�Functional notes: the point related to the first zone

in Prealarm is the first point in the zone that be-

came active. For all other zones in Prealarm the re-

lated point is the last that became active. This

information are update in real time.

The “first point in Prealarm” field contains the infor-

mation about the first device that became active.

The “last point in Prealarm” field contains the infor-

mation about the last activated point, no matter on

which zone belong.

� ALARM STATUS

In the ALARM status, an alarm has been raised by a de-tector or manual call point.ALARM status will also be signalled by:� blinking ALARM LEDs;� message on fire control panel/Repeater Display (see

Figure 12);� an intermittent audible signal on the fire control panel;� the Alarm output points, programmed to signal the

Alarm status. In this phase:

�The EN54-2 requires that at the least, the first zone

in alarm, the most recent zone in alarm and the

number of zones in alarm will be displayed.

Besides to supply the information about the points

in alarm, the visualization of the alarm will be by

zones (default) or by points.

Alphanumeric keypad For the alarm by ZONES or byPOINTS the use is the same:1 key: to jump to the Zone status visualization page;

�In the FC500REP repeater case in addition to

press F1 key , you have to press ENTER key to vi-

sualize the zone label.

12 Addressable Fire Control Panel FC501

Zones:004 / Dev.: 013 ALARM

First Z001 det.: office 3, south wing

Last Z001 det.: main corridor, north

4= view all

Zones:004 / Dev.: 013 ALARM

First Z001 Loop 1 mod012 zone=001

Last Z001 Loop 1 mod182 zone=001

4= view all

ALARMZones:004 / Dev.: 013

First cause: 400PH Temp.Z001

Last cause: 400PH Temp.Z001

4= view all

Zones:004 / Dev.: 013 ALARM

First Time: 10:46:21 - 01/01/07Z001

Last Time: 10:47:18 - 01/01/07Z001

4= view all

Push the right key to scrollthe second block of data

regarding the Points Coordinate

Push the right key to scrollthe third block of data

regarding the ALARM causes

Push the right key to scrollthe fourth block of data

regarding the ALARM times

Push the left key

Push the left key

Push the left key

Figure 11 Alarm status- Scrolling Right key

zones:004 / Dev:013 ALARM

First z001 det: office 3, first floor

Last z004 det: main corridor

4= : view suppressed Delay to alarm

BlinkingPoints in alarm counter

To view further zonesin alarm

Last point inalarm

Control panel statusFirst Point in

alarm

This symbolthe presence of followinginformation: point coordinate

CauseTime

shows

BY POINTS

Point labelswapped with

zone label

30 sec. or

zones:004 / Dev:013 ALARM

First z001 zone: RD dept. first floor

Last z004 zone: Warehouse

4= : view suppressed Delay to alarm

BlinkingZones in alarm counter

To view further zonesin alarm

Last zone inalarm

Control panel statusFirst zone in alarm

If blinksindicates thecontrol paneloperating normal

BY ZONE

Zone labelswapped with

point label

This symbolthe presence of followinginformation: point coordinate

CauseTime

shows

Figure 12 DISPLAY: ALARM STATUS.

Page 13: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

2 key: to jump to the first activated loop device status vi-sualization page;3 key: to jump to the last activated loop device status vi-sualization page ;4 key: to display further Points in alarm.When in the fourth row is present a point information, afurther 4 key press will cause the User Interface jumpthe related loop device status visualization page.

Cursor keys For the alarm by ZONES or by POINTS

the use is the same:Use the UP Key to view the next point in alarm, otherthan the first and the last;Use the DOWN Key to view the previous point in alarm ,other than the first and the last.Use the RIGHT Key to display the next auxiliary infor-mation about the point .Use the LEFT Key to display the previous auxiliary in-formation about the point.

ESC Key Use ESC key to step back to the MAIN page.

ENTER Key Long press -> change between the visual-ization modes;Short press -> stops or restart the zone/point swap.

�Functional notes: the point related to the first zone

in alarm is the first point in the zone that became

active. For all other zones in alarm the related point

is the last that became active. This information are

update in real time.

The “first point in alarm” field contains the informa-

tion about the first device that became active.

The “last point in alarm” field contains the informa-

tion about the last activated point, no matter on

which zone belong.

�For the WALK TEST status, displays and proce-

dures are similar to the FAULT status

� FAULT STATUS

FAULT status will also be signalled by:� blinking FAULT LEDs;� message on fire control panel Display;� blinking the specific FAULT LEDs, if present

(POWER SUPPLY FAULT - BATTERY TROUBLE-EARTH FAULT-SYSTEM FAULT-FIRE SIGNALFAULT- SOUNDERS FAULT/DIS);

� an intermittent audible signal on the fire control panel;� the Fault output points.

Figure 13shows the Fault status of the control panel.The SILENCE button can be used to force the FAULTSilenceable output momentarily to standby status.FAULT MEMORY will be signalled by blinking on theFAULT LEDs ONLY.The RESET key can be used to force ALL Fault outputs tostandby and clear the fault memory. The fault outputs willrestore automatically to standby when faults clear.In this phase:

Alphanumeric keypad Use the 1 key to jump to theZone status visualization page.Use the 2 key if the first fault is related to a point, jump toloop device status visualization page.If the first fault is a loop break fault, jump to the “locatethe loop break” page.If the first fault is related to an item that may be disabled,the User Interface moves to the disabling page; in orderto allow a fast disablement procedure.

�If the access level is less than L2, the password will

be required before proceed to disablement

Use the 3 key if the last fault is related to a point, jump toloop device status visualization page.If the last fault is a loop break fault, jump to the “locatethe loop break” page.If the last fault is related to an item that may be disabled,the User Interface moves to the disabling page; in orderto allow a fast disablement procedure.

�If the access level is less than L2, the password will

be required before proceed to disablement

Use the 4 key to display further faults.When a point fault is present in the fourth row, a further4 key press will cause the User Interface jump to the re-lated loop device status visualization page.When a point fault is present in the fourth row, a further

USER INTERFACE 13

If it blinksthe panel isoperating normally

Total :0004 status: FAULT

First : MS: SHORT on Sc1

Last : MS:L1 Signal Path broken

#0002 : MS:Loop 2 det191 zone=002

Last Faults

First FaultsControl panel status

Faults number

Stored Faultsindex

This symbolthe presence of followingblocks to be scrolled by Rightthe symbol

cursor key,shows the presence

of previous blocks to be scrolled byLeft cursor key.

shows1° block:

Point identification

Figure 13 DISPLAY: FAULT STATUS.

Total :0004 status:FAULT

First : MS: SHORT on SC1

Last : MS:L1 Signal Path broken

Total :0004 status: FAULT

First : zone: System Area

Last : zone: System Area

#0002 : zone: Reception

Total :0004 status: FAULT

First : cause: NO DATA

Last : cause: NO DATA

#0002 : cause: 801PH NOT RESPONDING

Total :0004 status: FAULT

First : Time: 08:34:46 - 01/01/07

Last : Time: 08:36:23 - 01/01/07

#0002 : Time: 08:36:13 - 01/01/07

#0002 : MS:Loop 2 det191 zone=002

Push the right key to scrollthe second block of data

regarding the FAULT zones

Push the right key to scrollthe third block of data

regarding the FAULT causes

Push the right key to scrollthe block of data

regarding the FAULT timesfourth

Figure 14 Fault status- Scrolling Right key

Page 14: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

4 key press will cause the User Interface jump to the “lo-cate the loop break” page. If in the fourth row is presenta fault related to an item that may be disabled, the UserInterface moves to the disabling page in order to allow afast disablement procedure.

�If the access level is less than L2, the password will

be required before proceed to disablement

From Figure 14, in the FAULT STATUS, use the RIGHT

Key to scroll the second string of data of fault Zones;after use the RIGHT Key to scroll the third string of dataof Fault causes;then use the RIGHT Key to scroll the fourth string ofdata of Fault Times and Events.

�In the case of a fault is related to a Loop device, the

faulty point label is swapped with the assigned

zone label every 3 seconds. If the zone has not

been associated with the point, only the point label

will appear.

Cursor keys Use the UP Key to view the next avail-able fault, other than the first and the last.Use the DOWN Key to view the previous available fault,other than the first and the last.Use the RIGHT Key to view the next auxiliary informa-tion about the point.Use the LEFT Key to view the previous auxiliary infor-mation about the point .

ESC Key Use the ESC key to step back to MAIN page.

ENTER Key The ENTER Key blocks/reactivates theexchange between the labels of the devices and thoseof the zones.

� Locate loop break pages

From paragraph Fault status -2 Key.These pages are used to manage the “locate loopbreak” procedure that helps to understand where theloop is broken giving as result the number of sensed de-tector on the left and on the right side of the analyzedloop.The pages sequence is depicted in figure n.15.

�Note that during the “locate loop break” procedure

all the detectors will be powered down, so at the

exit of the procedure a full loop initialization will be

executed.

�During the “locate loop break” procedure" the de-

vices not in configuration are not found.

�In the immediate future, in case of short circuit on a

loop, the control panel will indicate a fault for short

circuit on the other loops. Only later, with “locate

loop break” procedure it is possible to see which of

the three Loop occurred on short circuit.

� Locate the not addressed devices

In the case of “NOT POGRAMMED DEV.” fault it is pos-sible to locate all the not addressed devices.

To make visible all the not addressed devices that havea LED, they will be activated (steady on).

The sounders will start to sound, while the beacons willstart to flash.The following picture diplay the “locate not addresseddevice page” diagram flow.

If there are too many not addressed devices, the overallcurrent required to keep active, at the same time, all theLEDs, sounders and beacons, may be so high to triggerthe loop overcurrent protection circuit.For this reason the operator is warned about this possi-bility.

�This feature is made available only when the panel

reach its stand-by status (scanning loop).

14 Addressable Fire Control Panel FC501

Locate the loop break on: Loop 1

ESC to EXIT ENTER to EXECUTE

Loop ID

Locate the loop break on: Loop 1

IN PROGRESS

Go back toFault page

Locate the loop break on: Loop 1

XXX devices on left side

XXX devices on right side

ESC to Exit ENTER to Restart

Figure 15 Page "Locate loop break"

Total:0001 Status: FAULT

First : MS: NOT PROGRAMMED DEV.

Last :

Make visible not addressed devices

WARNING!

If too many dev. the loops may shutdown

3 GHI

2 DEF

4 JKL

ESC=Exit ENTER=Execute

To MAINpage

The notaddresseddevicesare madevisible

FAILED

Make visible not addressed devices

Devices Visible

ESC=Exit SILENCE=Stop

To MAINpage

The not addresseddevices are silenced

Make visible not addressed devices

Devices is silenced

ESC=Exit SILENCE=Excute

To MAINpage

The not addresseddevicesare made visible

Figure 16 Locate the not addressed devices pages

Page 15: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

VIEW-LOG-PARAMETERS

Read through the following section carefully, in order toget an overall view of how to use the Programming forthe Users. For details regarding the parameters of eachphase, refer to the respective paragraph in the “PRO-GRAMMING FROM A PC” chapter of the InstallationManual.

From Main Page, the User can manage without Access

code:� View parameters (Use 1=ANALYZE)� View Log (Use 3= View LOG or 1=ANALYZE and

then use 8 Key)� View Lists (Use 4= MORE and then 2)and with User Access code can manage this menu:� Modify

� Disable

� View parameters

The Display (Figure 17) shows how to manage theviewing of different parameters:

In this phase:

Alphanumeric keypad Use the Alphanumeric keypadto select the different viewing functions:1= Loop: start the procedure for selection and viewingof the loop data;2= To activate the selection and visualization sequenceof the loop devices real time data;3 = SW zone: activates the selection and display proce-dure for the data corresponding to all SW zones;4 = Output: activates the selection and viewing proce-dure for the data corresponding to an output;5= Network: start the procedure for viewing of all de-vices (Repeaters and MFI module) on the RS485 Net-work;6 = Communic: activates the viewing sequence for allcommunication units main data;

7 = Option: activates the viewing sequence for all lo-cally programmed system options;8= Log: start the procedure for viewing of Loggedevents;9= Fw ver.: start the procedure for viewing of FW ver-sion of all processors in the panel;0= Panel: start the procedure for viewing Panelinformations.

Cursor keys No function is related to the UP,Down,

Right and Left key.

ESC Key Use the ESC key to step back to MAIN page.

ENTER Key No function is related to the ENTER key.

VIEW-LOG-PARAMETERS 15

FC501 panel lev.1: ANALYZE

1=Loop 2=Device 3=SW zone 4=Output

5=Network 6=Communic. 7=Option 8=Log

9=FW ver. 0=Panel

Control panel name Access Level

Options

If it blinks the panelis operating normallyControl panel status

Figure 17 Display: View Parameters.

Page 16: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

1 KEY - View Loop

Use the 1 Key to view the Loop data (see Figure 18).

� View of Loop Details

In this phase:

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys Use the UP Key to select the next Loopdata;Use the Down Key to select the previous Loop data;No function is related to the Right Key;No function is related to the Left Key.

ESC Key Use ESC key to step back to previous page.

ENTER Key No function is related to the ENTER key.

In the Figure n. 18, the “loop=” field shows which loopdetail is displayed.

The “Detectors:” field displays the number of detectorssensed on the relevant loop.

The “Modules:” field displays the number of modulessensed on the relevant loop.

The “Status:” field displays the status of the selectedloop. The possible values are:� Working,� Fault,� Stand_by,� Disabled.The “loop=” field real time display (5s data refresh rate)the total current supplied to all three loops.

2 KEY - View Devices

Use the 2 Key to view the Loop devices (see Figure 19).In this page: Select the Loop and then the device.

� Select the Loop

In this phase:

Alphanumeric keypad 1,2,3 used to select the loop.

Cursor Keys No function is related to UP Key;No function is related to the Down Key;Use the Right Key to select the next available Loop;Use the Left Key to select the previous available Loop.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key Use the ENTER key to confirm and to dis-play the page of the selected Loop.

� Select the device

After selecting the Loop, the Loop details are shown asin Figure 20;

in this phase:

Alphanumeric keypad Use the Alphanumeric keypadto insert the device address. If the address does not ex-ist the next available device will be selected.

�If the device is in the system, the square brackets

will be shown near the address. If the address does

not exist or it is different from that selected in the

underlying bar, the arrows will be shown.

Cursor Keys No function is related to the UP Key;No function is related to the Down Key;Use the Right Key to select the next available Device;Use the Left Key to select the previous available device.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key Use the ENTER key to confirm and to dis-play the page of the selected device.

16 Addressable Fire Control Panel FC501

Loop= 01 lev.1: ANALYZE

Modules : 125

Status: Working

Loop number

ILoop=073 mA (400 ma MAX)

Current Valuein the 3 Loops

Present Statusof the Loop

Detectors: 125

Detectors Number

ModulesnumberOvercurrent that

powers OFF the Loop

If it blinks the panelis operating normally

Figure 18 DISPLAY: Viewing Loop details

FC501 Panel lev.1: ANALYZE

Master Panel

[ L1 ] L2

Control panel name Access level

Choose Panel Loop 1

Initial of the selectedControl panel

Name of the selectedControl panel

If it blinks the panelis operating normally

Control panel status

Figure 19 Display: viewing a) Loop choice, b) Loop de-

tails

Page 17: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

� View device data on the Loop

Selected the Loop and then the device, the Display willshow Figure 20.In this phase:

Alphanumeric keypad No function is related to the Al-phanumeric keypad except 0 key to disable the device(detector or module), it will required the entry of the ac-cess code if the access level is less than 2.

�NOTE: This feature doesn’t work in the case of

multichannel module not answering to loop poll.

Cursor Keys The UP Key, in the case of modules withseveral inputs or outputs, can scroll through them;The Down Key in the case of modules with several in-puts or outputs, can scroll through them;the Right Key: displays the status of the next device onthe same loop; the Left Key: displays the status of theprevious device on the same loop; in the case of mod-ules with several inputs or outputs, this means it is pos-sible to scroll through them.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key No function is related to the ENTER key.

The Device status field displays the current status of thedetector or module, the possible values are:

-WORKING-ACTIVE-WARNING-FAULT-ZONE DIS.-WALK TEST-STAND-BY.

The device coordinate field displays:

-the loop ID,-the device address,-the device type,-the channel ID (for the modules).

The “Device channels info area” displays:

-the channel ID S=Smoke, T=temperature, C=Carbonmonoxide (for the detector),-the current analog value in percentage,-a real time, pseudo-graphic representation of the cur-rent analog value with threshold,-the channel configuration mode or the threshold value-the channel status.

�The device info is displayed only in the case of de-

vices in WORKING state.

VIEW-LOG-PARAMETERS 17

Office Zone stat: WORKING

Add:163 Type:801PH s=07% ----|--t=60%

T=26% ---|-A2S

Device nameAddress

Sizes valuetested by detector

Functionmode

Type

Threshold

FC501 panel lev.1 : ANALYZE

Master Control panel

[ L1 ] L2

List of thepresent Loop

Loop 1

Name of theselected Loop

FC501 panel lev.1: ANALYZE

Master control Panel

D001 [d187] m250 801PHInsertedaddress

List of thepresentdevices

Loop 1

Name of theselected Loop

Add= > 123 <

Selected devicetype

Selecteddevice

This symbol shows thedevice

presence

Control panel name Access level

Control panel status if it blinks the panelis operating normally

Choose Loop

Initial of the selectedLoop

Label ofControl panel

Control panel name Access levelControl panel status

Name of theControl panel

Device status

Pattern of thecurrent value and

Threshold (if applicable)

IN THE DETECTOR CASE

Reception stat: WORKING

L1:038 800MIO inp1 MAIN door

30% - --|-C:NO|

Device nameType

Device status

Pattern of thecurrent value and

Threshold (if applicable)

IN THE MODULE CASE

WORKING

The devicecoordinate field

“ ”

Zone: 32

Assignedzone

Zone: 32

Assignedzone

Figure 20 Following displays of View devices on the

Loop (Detectors and Modules)

Page 18: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

3 KEY- View SW Zone

The 3 Key (SW Zone) option in the ANALYZE menu ac-tivates the viewing of the software zones (max 32). Dur-ing this phase (see Figure 21) the status of all the SWzones in the system is displayed in compact format. Thestatus of the SW zones will be displayed using the fol-lowing abbreviations:. : “UNUSED” Not used zone, no devices assigned to itA: “ALARM” zone in Alarm modeP: “PRE AL.” zone in Pre-alarm modeW: “WARNING” zone in Warning modeF: “FAULT” zone in Fault modeX: “DISABLED” zone Disabledt: “TEST” zone in Test modeT: “TEST ON” At least one point in the zone is active intest_: “ST-BY” zone in standby modeD: “DIRTY” At least one smoke detector in the zone isdirty.

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to UP key.No function is related to the Down key;the Right Key: selects the next SW zone, in the “Allzone status area”;(the corresponding number appears on the Left of thedisplay);the Left Key: selects the previous SW zone, in the “Allzone status area”;(the corresponding number appears on the Left of thedisplay).

ESC Key Use ESC key to cancel the operation and tostep back to previous page.

ENTER key No function is related to ENTER key.

4 KEY- View Output

The 4 key Output option in the ANALYZE menu acti-vates the viewing of the Outputs. During this phase (seeFigure 22) the status of all the Outputs in the system isdisplayed in compact format. The status of the Outputswill be displayed using the following abbreviations:-DIS: output disabled-ACT: output active-SC: output shorted-OPE: output open-_ _ : output in standby-FAU: transistor Fault

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the UP, Down,

Right and Left key.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key No function is related to the ENTER key.

18 Addressable Fire Control Panel FC501

Zone

ST-BY

011

SW zone status

[ First Floor ]

Zone Label

Zone Number ID

FA ---- --

All zones status area

Figure 21 Display view SW zone

SC1: -- --

OC:

01 02

SC1 Output

OpenCollector Output

OUTPUT STATUS

OPE --

ST-BY status

Figure 22 Display view Outputs

Page 19: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

5 KEY- View NETWORK

Use the 5 Key to view the Network devices: MFI mod-ules (max 4) and Repeaters (max4) (see Figure 23).

The field Network devices status displays the relatedoutput status using abbreviations.

The abbreviations are:

“ OK!”, the net. device is sensed as connected andworking“ Ko!”, the net. device is sensed as not connected“ FAU”, the net. device is faulty“ DIS”, the net. device is disabled“ — ”, the net. device is not configured in the network“ OLD”, the net. device has an obsolete FW version.

In this phase:

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the UP, Down,

Right, Left Key.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key No function is related to the ENTER key.

6 KEY- COMMUNICATORS

The 6 Key is used to view the Communicator connectedto the control panel, see Figure 24. In addition to theFirmware version, the FC500IP module status and theaddress will be displayed.

In this phase:

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the UP, Down,

Right, Left Key.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key No function is related to the ENTER key.

VIEW-LOG-PARAMETERS 19

MFI M1 M2 M3 M4

REPEATER R1 R2 R3 R4

-- -- -- Ko!

OK! -- -- FAU

Network typedevices Network devices status

Figure 23 Example of Display: View Network (MFI mo-

dules and Repeaters)

FW ver. Address

IP: OK! 01.00.09 255 255 255 255. . .

Type of Communic. Firmware Rev.

Communicators status

IP Address of theFC500IP module

Figure 24 Display Communicators

Page 20: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

7 KEY- View Option

The 7 Key activates, in the ANALYZE MENU, the view-ing of programmed system options, see Figure 25. Thestatus of the DAY/NIGHT MODE options will be indi-cated using the following abbreviations:-DAY: day mode-NGT: night mode-AUT: automatic mode.

In this phase:

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the Up, Down,

Right and Left Key;

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key No function is related to the ENTER key.

8 KEY - View Log

Use the 8 Key to select View LOG (see Figure 26) or di-rectly from the STANDBY status.

The option View Log of the menu View parameters

will allow you to view the stored events in the Log of thefire control panel.This Control panel can store the last 4000 occurredevents.When the Log is full, the oldest event will be deleted, sothe newest can be stored.

�Use the option CLEAR LOG of the Modify menu to

delete the Log events.

The following data will be stored in the LOG:� Event description;� Event number;� Description of the device (Panel or Repeater) that

generated the event;� Description of the item that generated the event;� Time and date of the event;� Address of the Item which generated the event.

View Log

From MAIN page directly, (see Figure 5) the User, with-out password, can arrive to View Log see Figure 26.

The Event Class field displays the class of the eventcurrently displayed, the possible values are:RESTOREALARMALARM+DLYWARNINGFAULTGENERICWALK TEST.

In this phase:

Alphanumeric keypad Used to activate the display fil-ters.1: Alarm events only, 2: Pre-alarm events only, 3:

Warning events only, 4: Walk Test events only, 5: Faultevents only, 6: Restore events only, 7: Generic eventsonly.

Cursor Keys Use the UP Key to select the previousavailable event;Use the Down Key to select the next available event;Use the Right Key to view the next available data;Use the Left Key to view the previous available data.

ESC Key Use ESC key to cancel the operation and tostep back to main page.

ENTER key No function is related to the ENTER key.

�If the events are linked to the devices, the zone la-

bel alternates with the point label every 3 seconds.

If the zone has not been associated with the point,

only the point label will appear.

�If the displayed events are filtered by type, “*” will

immediately begin to blink to the right of the event

number.

20 Addressable Fire Control Panel FC501

Options Lev.1: ANALYZE

Access Level

Mode Type

DAY ngt aut

DAY NIGHT MODE

^

Control panel status If it blinks the panelis operating normally

Master panel

Current state

DAY

Figure 25 Display: View Option.

Total :0297 status: VIEW LOG

Event :0292 RESTORE*

MS:Loop 2 det191 zone=002

08:43:11 - 01/01/07

Total stored Events

At presentstored events

This symbol: shows the presence offollowing blocks to be scrolled by RIGHT key( previous block to be scrolled by LEFT key)

1° block

EventsType

Time and dateconncted to

the event

If it blinks the panelis operating normallyControl panel status

If present, it shows the filteredview by type of events

Figure 26 Display: View LOG.

Page 21: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

9 Key - View FW version

The option Ver. FW of the View Parameters Menu al-lows you to view the Firmware version of Fire controlpanel.Use the 9 key to view the Firmware version of Fire con-trol panel (see Figure 28), in this phase:

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the Up, Down,

Right and Left Key.

ESC Key Use the ESC key to cancel the operation andto step back to MAIN page.

ENTER key No function is related to the ENTER key.

0 Key-Panel

By pressing the 0 key, in the ANALYZE menu, it is pos-sible to read:- the fire panel ID- the serial number of the Fire Panel (displays the elec-tronic board serial number composed by eighthexadecimal digits);- the version of the PCB;- the type of power supply on board;- the type of batteries on board- the presence of the auxiliary controller (see Figure 29).

In this phase:

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the Up, Down,

Right and Left Key;

ESC Key Use the ESC key to step back to ANALYZEmenu page.

ENTER key No function is related to the ENTER key.

VIEW-LOG-PARAMETERS 21

Total :0297 status: VIEW LOG

Event :0292 RESTORE

MS:Loop 2 det191 zone=002

08:43:11 - 01/01/07

Total :0297 status: VIEW LOG

Event :0292 RESTORE

Zone: Reception

08:43:11 - 01/01/07

Total :0297 status: VIEW LOG

Event :0292 RESTORE

Cause:8011H NO DATA

08:43:11 - 01/01/07

Push the right key to scrollthe second block of data

regarding the zones in the LOG

Push the right key to scrollthe third block of data

regarding the causes in the LOG

Figure 27 View LOG: scroll with RIGHT key

FIRMWARE VERSIONS

MAIN CONTROLLER ver 01.00 sv01

AUX. CONTROLLER ver 01.00 sv03

If it blinks the panelis operating normally

Figure 28 Display: Viewing FW version.

PANEL INFO ID=0001

Ser.Num. 123456789 PCB ver.0

PSU 27.6V. 1.5Ah Batteries 7Ah

Aux.Contr. PRESENT ESC to exit

Figure 29 Display: Viewing Panel info.

Page 22: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

View Lists (Press 4= MORE and then 2)

Directly from the MAIN page, press 4 =MORE Key andthen 2= View Lists.

The option View Lists allows you to view:� 1- Dis. Zone-Disabled zones� 2-Dis. Device-Disabled devices� 3-Dis. Part-Disabled Parts� 4-Walk test - Walk test Zones� 5-Faults List� 6-Warnings List� 7-Dev. in test (Devices in test).

�The lists containing data (not empty) are indicated

by the blinking of the corresponding number

In this phase:

Alphanumeric keypad Alphanumeric keypad is usedto select and access the View function (see optionsabove).

Cursor Keys No function is related to the Up, Down,Right and Left key.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key No function is related to the ENTER key.

The field “Item in the list” contains the number of itemspresent in the list at the moment of it opening;the field “Current item ID” contains the number ID of thecurrently displayed item;The field “Kind of list” replicates the name of the list pre-viously selected.

The field “Item info” displays the information about theitem currently selected. It shows the location of the SWzone and loop device or the description of a system partplus the related label.

In this phase (second Display in Figure 30):

Alphanumeric keypad To call the enablement pageto quickly enable the displayed entity.

Cursor Keys The UP Key, used to navigate the list,displays the next element;The Down Key, used to navigate the list, displays theprevious element;No function is related to the Right key;

No function is related to the Left key.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key No function is related to the ENTER key.

22 Addressable Fire Control Panel FC501

FC501 Panel lev.1 : ANALYZE

1=Dis.Zone 2=Dis. Dev. 3=Dis.Part

4=Walk Test 5=Faults 6=Warnings

7=Dev.in Test

Control panel name Acces level

Choice Options

Control panel status If it blinks the panelis operating normally

Total : 0003 VIEW LIST

Index : 0002 DIS: Zones

SW Zone 007

First Floor

For the andDis.Zone, Dis. Dev, Dis. Part Walk Test a common visualization list page s usedi

Kindof list

Info

Items in the list

Current Item ID

Figure 30 Display: View Lists

Page 23: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

MODIFY

MODIFY MENU

For the MODIFY option, from the MAIN page, press the3 key.

To access the MODIFY Menu:Enter the User Access code (11111 at default), eachdigit will be masked by * (asterisk).

The following options are available in this menu:1-Clear and update the Welcome message (Init MSG)(control panel name),2- Enter and update L2- User Password,3- Update Day/Night mode4- Update Time and Date5- Clear LOG6-Zone Walk test.

Figure 31shows the options for the MODIFY MENU af-ter inserting or modifying the password.

In this phase:

Alphanumeric keypad Use the Alphanumeric keypadto select the options of MODIFY MENU.

Cursor Keys No function is related to the UP, Down,

Right and left Key.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key No function is related to the ENTER key.

1 KEY -INIT MSG (Modify panel label)

Use the 1 Key to enter or update the Panel label.In this phase:

Alphanumeric keypad The Alphanumeric keypad isused to enter or update the panel label.

Cursor Keys Use the UP key to change the selectedletter from lower case to upper case;Use the Down Key to change the selected letter fromupper case to lower case;Use the Right Key to select the next character to bemodified;Use the Left Key to select the previous character to bemodified.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key Use the ENTER key to confirm the label.

MODIFY 23

FC501 panel lev.2 : MODIFY

1=Init MSG 2=l2-User PassWord

5=Clear LOG 6=Zone Walk Test

Access level

Options

If it blinks the panelis operating normally

Control panelStatusName of Control Panel

3=Day/Night 4=Time and Date

Figure 31 Display MODIFY MENU.

Page 24: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

2 KEY - User Password

Use the 2 key to Modify the User Password (see Figure32).

� Insert or Modify Password

Select the option MODIFY, the display will show Figure32; in this phase:

Alphanumeric keypad Use the Alphanumeric keypadto enter the last 5 digit User password.

�To avoid the use of the same password for multiple

users, as the first digit of password, the User must

enter the number corresponding to his position,

see the following.

The first digit for the User 1: is 1The first digit for the User 2: is 2The first digit for the User 3: is 3The first digit for the User 4: is 4The first digit for the User 5: is 5The first digit for the User 6: is 6The first digit for the User 7: is 7The first digit for the User 8: is 8.

Cursor Keys No function is related to the UP, Down,

Right and Left Key;

ESC Key Short press: Abort the enter password pro-cedure and exit;Long press: clear all the entered digits.

ENTER key Use the ENTER key to confirm the pass-word and start the password verification process.

�If a wrong or empty password is entered the sec-

ond page in Figure 32, will be displayed for 5s.

3 KEY-DAY/NIGHT

If the 3 Key is pressed, it is possible to change the con-trol panel operating mode: Day mode or Night mode.

The Day/Night mode will be toggled at each key 3

press.

�The Day mode indicator light will change sta-

tus.

� Day/Night Mode

The control panel can operate in DAY or NIGHT Mode.If the system is silenced during DAY Mode, SILENCEstatus will be held until the system is unsilenced (i.e. un-til new alarms or faults occur). If the system is silencedduring NIGHT Mode, SILENCE status will be held untilthe Night Mode Silence time expires. On power up (atdefault) the system will set to DAY Mode. During thisoperating mode, silenced alarms/faults will not beunsilenced automatically.

�This control panel will generate an Instant Alarm if

alarm conditions are detected during Night Mode

or if an alarm is triggered from a Callpoint.

24 Addressable Fire Control Panel FC501

FC501 Panel lev.2: MODIFY

USER#1 Enter the new password

Enter 1 as first digit

[_____]

Name of Control Panel

Field to enter the password

If it blinks the panelis operating normallyControl panel

StatusAccess Level

a)

FC501 Panel lev.2: MODIFY

USER

WRONG Password

Figure 32 Display: Modify User password

System lev. 2 : MODIFY

[--------------------]

PANEL NAME FC501 Panel

Cursor (20 characters max)

^

Access level

If it blinks the panelis operating normally

Control panelStatus

Name of Control Panel

Figure 33 Display Panel label

Page 25: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

4 Key-Time and Date

Use the 4 Key to select TIME and DATE in the MODIFYmenu to enter/change the control panel Time and Date(see Figure 34).

In this phase:

Alphanumeric keypad The alphanumeric keypad isused to enter the Time and Date values.

Cursor Keys No function is related to the UP Key;No function is related to the Down Key;Use the Right Key to select the next value to be in-serted/modified;Use the Left Key to select the previous value to be in-serted/modified;

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key Use the ENTER key to confirm the Timeand the Date.

�If you enter incorrect values a message will show

the error as shown in Figure 34a.

5 Key- Clear LOG

Use the 5 key to select Clear LOG (see Figure 35).

This option allows you to delete all stored events in thefire control panel.

�If the 5 Key is selected, confirmation of this deletion

will be requested, as all data will be lost.

In this phase:

Alphanumeric keypad No function is related to the al-phanumeric keypad.

Cursor Keys No function is related to the UP, Down,

Right and Left Key.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key Use the ENTER key to confirm the proce-dure to clear Log..

�During the Clear LOG activity the MAIN page will

be displayed with the Panel activity field loaded

with CLEAR LOG string (see Figure 35). Once the

Log has been cleared, the panel resets.

MODIFY 25

Lev 2: MODIFY

FC501 CONTROL PANEL

Enter Date and Time

Access levelControl panel status

DATE and TIME

hh.mm.ss mm.dd.yy

System

^

WRONG VALUE!

Please enter the parameter again

a)

Figure 34 Display Time and Date

Lev 2: ACTIVE

FC501 CONTROL PANEL

Control panel name

Access LevelControl panel Status

CLEAR LOG

17.00.24 - 04/02/13

WARNING!

All logged data will be lost.

Do you want to continue?ESC=NO ENTER=Yes

Figure 35 Display "Clear LOG"

Page 26: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

6 KEY- Zone WALK TEST

The Zone Walk Test option of the MODIFY menu willactivate the zone programming procedure for the Zonewalk test (see Figure 36) .

� SW zone in WALK TEST

After selecting the SW Zone, you will be able to enable ordisable the option Zone in WALK TEST (OFF) or not (off);� if the option all (ALL) is selected, all the devices as-

signed to zones in WALK TEST mode, will NOT gen-erate alarm in the case of their activation but they willreach the TEST status.

� If the option det (DET) is selected, only the detectorsassigned to zones in WALK TEST mode, will NOTgenerate alarm in the case of their activation but willreach the TEST status.

� If the option cp (CP) is selected, only the call-pointsassigned to zones in WALK TEST mode, will NOTgenerate alarm in the case of their activation but willreach the TEST status.The presence of a zone in WALK TEST mode is sig-

nalled by the TEST yellow LED on the User In-terface. More than one zone can be put in WALKTEST mode at the same time.

�In the English User Interface version, the Icons are

not presents.

Alphanumeric keypad Use to enter the SW zonenumber.

Cursor Key No function is related to the UP and Down

Keys;The Right key: selects the next: OFF-ALL-det-cp;The Left key: selects the previous: OFF-ALL-det-cp.

ESC Key The ESC key cancels the procedure and re-turns to the programming page�

ENTER key The ENTER key accepts the selectionand activates the corresponding programming page.

26 Addressable Fire Control Panel FC501

FC501 Panel lev.2: MODIFY

FC501 Panel

Enter the SW zone number

Access LevelIf it blinks the panelis operating normally

Panel status

Zona SW: 002

Name ofthe selected

panel

SW Zone Index

SW Zone lev.2: MODIFY

FC501 Panel

OFF All det cp

Access LevelPanel status

ZONE IN WALK TEST

Choose the option

a)

b)

Name ofthe selected

panel

Figure 36 Display WALK TEST option

Page 27: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

DISABLE

To access the DISABLE menu from the MAIN page,you will be asked to enter a “User PIN” password (thedefault PIN is 11111): each entered digit will be hiddenwith the * symbol.

This activates the procedure used to enable/disable:Display List of disabled devices, the loop devices (inputor output devices), the SW zones, the Outputs of thecontrol panel, the network devices, the Telecom mod-ules, the User password and the RELÈ FIRE Output;

�When at least a device is disabled, the Disable

LED will be glowing , and any Alarm or Fault,

related to the disabled device, will be ignored.

The disabled and enabled modes are as follows:

Input Devices A disabled input device (Detector, In-put module, Conventional Zone module, AddressableCall-points) will not generate ALARM or FAULT status.

� To clear ALARM status generated by an input device- RESET the fire control panel.

Output Devices ALARM or FAULT status will not acti-vate disabled output devices (Output modules, Ad-dressable Sirens).

� To stop the output devices activated by FAULT sta-tus - Disable the devices concerned.

� To stop the output devices activated by an ALARMstatus - RESET the fire control panel.

�Output devices enabled during ALARM or FAULT

status (programmed), will be activated immedi-

ately.

The Display (see Figure 37) shows how to select thedevices to Disable/Enable.

In this phase:

Alphanumeric keypad Use the Alphanumeric keypadto select the Disable/Enable options.Use the 1 key to select the Disab. List.

Use the 2 key to select the Disable option of Loop de-vices.Use the 3 key to select the Disable option of SW zones.Use the 4 key to select the Disable option of Outputs.Use the 5 key to select the Disable option of Device inthe Network.Use the 6 key to select the Disable option of Comunic.devices.Use the 7 key to select the Disable option of the UserPassword # 2.... # 8 and Installer # 2.Use the 8 key to select the Disable option of the FIRErelay output.

�The option 7 can be enabled only by the Installer

#1 password (default 00000)

Cursor Keys No function is related to the UP, Down,

Right and Left Keys.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key No function is related to the ENTER key.

DISABLE 27

FC501 panel lev.2: DISABLE

1=Dis. list 2=Device 3=SW zone

7=Password 8=FIRE Relay

Control Panel name Access Level

Options

4=Output 5=Network 6=Communic.

If it blinks the panelis operating normally

Control panelStatus

Figure 37 Display DISABLE menu

Page 28: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

1 Key - Disable list

Use 1 key, or from MAIN page use 4 key (More) and then2 to select “View List”; (see Figure 38) In this phase:

�If any of the elements have been disabled, the cor-

responding number will blink and the Disable indi-

cator light will glow. If the Communicator is

disabled, the yellow indicator light (Communicator)

will also glow.

Alphanumeric keypad Used to select list to analyze.1- To view the list of disabled zones2- To view the list of disabled loop devices3- To view the list of disabled system parts (Outputs,Communicator).

Cursor Keys No function is related to the UP, Down,

Right and Left Key;

ESC Key Use the ESC key to cancel the operation andto step back to MAIN page.

ENTER key No function is related to the ENTER key .

�See paragraph View List in the chapter “View Pa-

rameters”.

For Disabled zones, Loop devices, System parts seeFigure 38(second display). In this phase:

Alphanumeric keypad Press 1 to call the enablementpage to quickly enable the displayed entity.

Cursor Keys Use the UP key, to select previous item;Use Down key to select next item.No function is related to Right and Left Keys;

ESC Key Use the ESC key to cancel the operation andto step back to MAIN page.

ENTER key No function is related to the ENTER key.

2 Key - Devices (Disable)

Use the 2 key to select “Device” Disable; then the Loopcan be selected (see Figure 39).

� Select the Loop

In this phase:

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the UP Key;No function is related to the Down Key;Use the Right Key to select the next Loop;Use the Left Key to select the previous Loop.

ESC Key Use the ESC key to cancel the operation andto step back to main page.

ENTER key Use the ENTER key to confirm and to dis-play the page of the selected Loop.

� Select the Device

In this phase:

Alphanumeric keypad Use the Alphanumeric keypadto insert the device address.

�If the device is in the system, the square brackets

will be shown near the address. If the address does

not exist or it is different from that selected in the

underlying bar, the arrows will be shown.

Cursor Keys No function is related to the UP Key;No function is related to Down Key;Use the Right Key to select the next available Device;Use the Left Key to select the previous available device.

ESC Key Use the ESC key to cancel the operation andto step back to main page.

ENTER key Use the ENTER key to confirm and to dis-play the page of the selected device.

� Disable device on the Loop

Selected the Loop and then the device, the Display willshow the third display in Figure 39.

The display shows the current status of the device, thepossible actions are: ENABLE or DISABLE.

In this phase:

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the UP, Down,

Right and Left Key.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

28 Addressable Fire Control Panel FC501

FC501 Panel lev.2 :DISABLE

1=Dis. Zone 2=Dis. Dev. 3=Dis. Part

Panel name Access level

If it blinks the panelis operating normally

Options to choose

Panel status

Total :0003 lev.2 :DISABLE

SW Zone 007

Kind of listIndex :0002 Zone SW Dis.

First floor

Panel statusItem in the listCurrent itemID

Item’s Info

Figure 38 Display "Dis. List" menu

Page 29: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

ENTER key Use the ENTER key to confirm and dis-able the detector. The User Interface moves to theMAIN page signaling a local programming activity fol-lowed by a panel reset.

In the case of MULTI CHANNEL MODULE, before toreach the display 3 (seeFigure 39) ENABLE/DISABLE,a channel selected display will be showed, allowing toselect the single channel to ENABLE/DISABLE, display4 (see Figure 39).

In this phase:

Alphanumeric keypad To select the desired channel1-8.

Cursor Keys No function is related to the UP, Down,

Right and Left Key.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER key Use the ENTER key to confirm; the UserInterface moves to the enabling/disabling page.

3 Key - SW zone

Use the 3 key to select “SW zone”; after the zone has beenselected the zone can be Disabled/Enabled (see Figure40).

� Select SW zone

In this phase:

Alphanumeric keypad Use the Alphanumeric keypadto select the Zone identification number.

Cursor Keys No function is related to the UP, Down

key.Use the Right key to select the next SW Zone,Use the Left Key to select the previous SW Zone;

ESC Key Use the ESC key to cancel the operation andto step back to MAIN page.

ENTER Key The ENTER key accepts the selectionand displays the next page, if the zone exists, otherwisean error message will be shown: WRONG VALUEPLEASE ENTER NEW PARAMETER.

After 5 sec. the User interface returns to the page of SWZone to select.

DISABLE 29

FC501 panel lev.2 : DISABLE

FC501 panel

[ L1 ] L2

Control panel name

Choose loop

List of the presentLoops

Loop 1

Name of theselected Loop

FC501 panel lev.2 : DISABLE

Fc501 panel

D001 [d187] m250 801PH

Control panel name

Programmingaddress

List of thepresent devices

Loop 1

Name of theselected Loop

Add= > 123 <

Type of selecteddevice

Selected device

Symbols to show thepresence of devices

FC501 panel lev.2 : DISABLE

801PH Office zone

Disable it?

ENABLED

Present Status

Device toDis./Enable

Request to Enable/Disable

If it blinks the panelis operating normally

Control panelStatusAccess level

Name of the selectedcontrol panel

Abbr. of the selectedLoop

Name of theselected

control panel

Control panelStatusAccess level

Control panelStatusAccess levelControl panel name

Panel name

Master control panel lev.2 : DISABLE

Office zone

5=o1 6=o2 7=o3 8=o4 410QIO inp1

1=i1 2=i2 3=i3 4=i4 loop 1

4)

Module type & channel ID

Select channel [1]

IN THE CASE OF MULTI CHANNEL MODULE

Selected channel

3)

2)

1)

Figure 39 Following Displays of Disable devices

FC501 Panel lev.2: DISABLE

SW zone: 097

SW zone name Index of the zoneto view

FC501 Panel lev.2: DISABLE

SW zone: 097

Disable it?

ENABLED

Present Status

SW zoneto disable

Request to Enable/Disable

If it blinks the panelis operating normallyControl Panel name Access Level

Control panelStatus

Control Panel name Access Level

Control panelStatus

Enter the SW Zone number

Figure 40 Display "Dis. SW. Zones "

Page 30: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

� Disable SW Zone

The display shows the current status of the SW Zone, thepossible actions are: ENABLE or DISABLE. In this phase:

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the UP, Down,

Right and Left Keys.

ESC Key Use the ESC key to cancel the operation andto return to previous page.

ENTER key Use the ENTER key to confirm and dis-able the SW Zone. The User Interface moves to theMAIN page signalling a local programming activity fol-lowed by a panel reset.

4 Key - Outputs

Use the 4 key to select “Output”; after the Output hasbeen selected, the Output can be Disabled/Enabled(see Figure 41).

� Select the Output

In this phase:

Alphanumeric keypad Use the Alphanumeric keypadto select the Output identification number.

Cursor Keys Use the UP Key to show the next type ofOutputs;Use the Down Key to show the previous type of Out-puts;The type of Output are: SC1 Output (NACFIRE)

SC2OC Output 1-2

No function is related to the Right and Left Key.

ESC Key Use the ESC key to cancel the operation andto step back to previous page.

ENTER Key Use the ENTER key to confirm.

� Disable Output

In this phase:

The display shows the current status of the Output, thepossible actions are: ENABLE or DISABLE.

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the UP, Down,

Right and Left Keys.

ESC Key Use the ESC key to cancel the operation andto return to previous page.

ENTER Key Use the ENTER Key to confirm. The UserInterface moves to the MAIN page followed by a panelreset.

5 Key - Network

The 5 Key is used to select the Disable Network de-vices option; after the network device has been se-lected, will be disabled/enabled accordingly (see Figure42) .

� Select the Network device

In this phase:

Alphanumeric keypad Use the Alphanumeric keypadto select the identification number of Network device.

�If the number is incorrect an error message will be

shown: WRONG VALUE

PLEASE ENTER NEW PARAMETER.

Cursor Keys Use the UP Key to show the next type ofnetwork device ;Use the Down Key to show the previous type of net-work device;The type of devices are: Repeater 1-4

MFI (1-4)RS485NET—(local network interface)

No function is related to the Right Key;No function is related to the Left Key.

ESC Key Use the ESC key to cancel the operation andto return to previous page.

ENTER Key Use the ENTER key to confirm and dis-play the next page.

30 Addressable Fire Control Panels FC501

FC501 panel lev.2: DISABLE

SC output: 001

FC501 panel lev.2: DISABLE

SC:output: 001

Disable it?

ENABLED

If it blinks the panelis operating normallyControl Panel name Access Level

Control panelStatus

Output name Identification number

Present Status

Outputto disable

Request to Enable/Disable

Control Panel name Access Level

Control panelStatus

Up or Down to select the type

Enter the SC Output number

Figure 41 Display "Dis. Outputs"

Page 31: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

� Disable Network device

In this phase:

The display shows the current status of the Netwok de-vice, the possible actions are: ENABLE or DISABLE.

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the UP, Down,

Right and Left Key.

ESC Key Use the ESC key to cancel the operation andto return to previous page.

ENTER Key Use the ENTER Key to confirm. The UserInterface moves to the MAIN page followed by a panelreset.

6 Key - COMMUNIC. (Disable)

The 6 Key is used to select the Disable Communic. de-vices option; after Communic. device has been se-lected, will be disable/enable; the correspondingTelecom module will then be disabled/enabled accord-ingly.

� Select the COMMUNIC. device

In this phase:

Alphanumeric keypad Use the Alphanumeric keypadto select the identification number of module.

�If the number is incorrect an error message will be

shown: NO ACTION TO BE DONE

Cursor Keys Use the UP Key to show the next type ofTelecom module.Use the Down Key to show the previous type ofTelecom module.

The type of Telecom module are: TEL i/f

Alarm TX

Fault TX

IP i/f

Alarm IP

Fault IP

No function is related to the Right Key;No function is related to the Left Key.

ESC Key Use the ESC key to cancel the operation andto return to previous page.

ENTER Key Use the ENTER key to confirm and dis-play the next page.

� Disable COMMUNIC. device

In this phase: the display shows the current status, thepossible actions are: ENABLE or DISABLE.

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the UP, Down,

Right and Left Keys.

ESC Key Use the ESC key to cancel the operation andto return to previous page.

ENTER Key Use the ENTER Key to confirm. The UserInterface moves to the MAIN page followed by a panelreset.

�If a module is disabled (TEL i/if or TX Alarms or TX

Fault or IP Alarm or IP Fault), the Disabled indica-

tor light will glow, as will the yellow Communicator

indicator light.

�If the TEL i/f communicator has not been enabled us-

ing software (Options page- FireClass Console ) and

you attempt to enable/disable it, the following text will

appear on the display: NO ACTION TO BE DONE

DISABLE 31

FC501 panel lev.2 : DISABLE

Repeater: 001

FC501 panel lev.2 : DISABLE

Repeater: 001 Label

Disabled?

ENABLED

Actual Status

DeviceDis./Enable

Request Enable/Disable

Up or Down to select the type

Enter the Repeater number

If it blinks the panelis operating normallyControl Panel name Access Level

Control panelStatus

Device name

Identification number

Control Panel name Access Level Control panelStatus

Figure 42 Display Disable/enable Network device

FC501 Panel lev.2 : DISABLE

TEL i/f

Communicator Type

FC501 Panel lev.2 : DISABLE

TEL i/f

Disabled it?

ENABLED

Present status

CommunicatorDis./Enable

Request Enabled/Disabled

UP or Down per to select the type

If it blinks the panelis operating normallyControl Panel name Access Level

Control panelStatus

Figure 43 Dispaly Enabled/Disabled Telecom (Com-

municator

Page 32: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

7 Key-Password (Disable)

This option is enabled only if you enter in the ControlPanel using a Master Installer PIN (Default 00000).The Key 7 is used to select the Disable Password op-tion, after the option has been selected the correspond-ing password will be disabled/enabled (Figure 44).

� Select the Password

In this phase:

Alphanumeric keypad Use the Alphanumeric keypadto select the identification number of Password.

Cursor Keys Use the UP Key to show the next type ofpassword;Use the Down Key to show the previous type of pass-word; the types of password are: User Password

Installer PasswordNo function is related to the Right and Left Keys.

ESC Key Use the ESC key to cancel the operation andto return to previous page.

ENTER Key Use the ENTER Key to confirm.

� Disable Password

In this phase: the display shows the current status of theselected Password (User or Installer), the possible ac-tions are: ENABLE or DISABLE.

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the UP, Down,

Right and Left Keys.

ESC Key Use the ESC key to cancel the operation andto return to previous page.

ENTER Key Use the ENTER Key to confirm. The UserInterface moves to the MAIN page followed by a panelreset.

8 Key -Fire Relay

Use the 8 key to select “Fire Relay”; the “Fire Relay”output can be Disabled/Enabled (see Figure 45).

The field “Current enablement status” displays the cur-rent enablement status of the selected item.

The possible status are:

“ENABLED”“DISABLED”

The Item “Action to do” contain the action that can do.

The possible actions are:

“ENABLE IT?”“DISABLE IT?”

In this phase:

Alphanumeric keypad No function is related to Al-phanumeric keypad.

Cursor Keys No function is related to the UP, Down,

Right and Left Keys;

ESC Key Use the ESC key to cancel the operation andto return to previous page.

ENTER Key Use the ENTER Key to confirm. The UserInterface moves to the MAIN page followed by a panelreset.

32 Addressable Fire Control Panels FC501

FC501 Panel lev.2 : DISABLE

User Pwd

Password Type

FC501 Panel lev.2 : DISABLE

User Pwd

Disabled it?

ENABLED

Present status

PasswordDis./Enable

Request Enabled/Disabled

UP or Down per to select the type

If it blinks the panelis operating normallyControl Panel name Access Level

Control panelStatus

Enter the User Pwd number

Figure 44 Dispaly Enabled/Disabled Password

FC501 Panel lev.2 : DISABLE

Fire Relay FIRE

DISABLE it?

ENABLED

Present status

FIRE RelayDis./Enable

Action to do

Control Panel name

If it blinks the panelis operating normallyAccess Level

Control panelStatus

Current enablementstatus field

Figure 45 Dispaly Enabled/Disabled FIRE Relay

Page 33: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

Repeater FC500REP Signalling

� Description of command Keys

�ONLY the Lamp/Buzz/Test, Silence Buzzer and

Evacuate Control keys can be activated without pass-

word (access level L1), all the others Control keys can

be activated with password (access level L2 and L3)

see Table n. 4.

� LCD DISPLAY DESCRIPTION

The information on the LCD display is organized as“pages”. There are two kinds of pages:� MAIN page� EVENT DRIVEN pages.The MAIN page is the page that allows access to thepanel information, it also shows the status of the panel.

The FC500REP MAIN page replicates the panel MAINpage with the following limitation:� Will never be overwritten by the panel front page.� Only the View list and View Log pages may be called.� The ESC long press to return to level 1 is NOT opera-

tive.� View log page description acts as in the panel.� View list page description acts as in the panel.

� EVENT DRIVEN page description

The EVENT DRIVEN pages are pages that are acti-vated by events in the system and when they becomeactive they override the page present on the display atthat time.

Also an Event driven page may be overridden by an-other Event driven page that has a higher priority.

The event driven page behavior is completely underpanel control.

The EVENT DRIVEN pages replicate the panel EVENTDRIVEN pages with the following limitations:

� Will NOT be possible to reach the device status pageusing the “F” keys.

� It is NOT possible to change the display mode In theAlarm or Pre-alarm pages .

� Description of Status LED

The Repeater status LED are described iIn the table n.5.

DISABLE 33

KEY DESCRIPTION

Lamp/Buzz

Test

This key can be used to test the buzzer and LEDs. If this key is pressed (when the Control panel is

functioning as intended), all the LEDs will glow and the buzzer will emit a continuous beep.

Silence This key can be used to restore the Silenceable outputs to standby status. Silence status will be held

until the Silence key is pressed again in Day Mode, or if the Control panel is operating in Night Mode,

until the Night mode Silence time expires or until a new Alarm/Trouble condition is detected.

Investigate This key can be used to refresh the “PreAlarm Time”: if this key is pressed during “PreAlarm”, the re-

maining PreAlarm time will be increased with the programmed "Investigation delay".

Silence

Buzzer

Key to silence the local buzzer of the control panel: the buzzer will operate every time a new event

occurs.

Reset This key can be used to reset the Fire detectors and restore all outputs to standby status (Supervi-

sed/Silenceable outputs, NON-Supervised/Non-Silenceable outputs and Alarm zone outputs)

Evacuate Key to activate the evacuation: if this key is pressed, the system will generate an alarm.

F1, F2, F3, F4 Function keys of the Display; their function varies according to different screens of display

Table 4 Description of the Repeater keys.

ALARM PAGE PREALARM

PAGEFAULT PAGE WARNING PAGE WALK TEST PAGE

MAIN PAGE

or wait30 sec

EVENT DRIVEN PAGES

MAIN Page and list pages basic intercations

MAIN PAGE

VIEW LOG PAGE VIEW LIST PAGE

Figure 46 Event driven pages and Main page basic in-

teractions.

Page 34: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

34 Addressable Fire Control Panels FC501

DESCRIPTION

FIRE Glowing indicates Alarm status. In the event of an Alarm, the Control panel will activate the

unbypassed alarm outputs.

More Alarms Glowing indicates more Alarm status.

Pre-alarms Blinking indicates Pre-alarm status.

Communicator

(Red)

Glowing indicates that transmission was successful.

Blinking indicates that transmission is in progress. On the display of the control panel it is possible

to know the connection type: PSTN, GSM, or LAN network.

FAULT Glowing indicates the presence of a Fault: the following LEDs or the screen on the display indicate

the type of the Fault. Slow blinking indicates a fault event in memory (Reset turns OFF ).

Logic Unit Glowing indicates a blocked Control panel. IMPORTANT: Maintenance required.

NOTE – When the Control panel is switched on for the first time, this LED will blink until a Reset has

been performed.

Lost Device Glowing indicates that a Loop device has disappeared (missing address).

Communicator

(Amber)

Glowing indicates the Dialer has been disabled; Slow blinking indicates that the dialer has broken

down

(SC)Nac Fire

Output

Glowing indicates that SC FIRE Output is bypassable (Disabled), Slow blinking indicates the pre-

sence of a Fault on SCFIRE Output.

Earth Glowing indicates a Voltage leakage to Earth.

IMPORTANT: Check wiring insulation

Low Battery Glowing indicates Batteries empty or faulty. If this condition persists, the batteries will be unable to

function as intended in the event of blackout, IMPORTANT: New batteries required.

NO Battery Glowing indicates Batteries empty or disconnected ; check if the connections are correct.

MAINS

(amber)

Glowing indicates Mains failure (230 Vac) or Switching Power supply fault. During this condition,

the Control panel will be powered by the batteries.

Day mode Glowing indicates that the Control panel is operating in Day Mode

OFF indicates that the Control panel is operating in Night Mode.

Disabled Glowing indicates the Disabled status of any bypassable entity.

Silence Glowing indicates that Silenceable outputs have been forced to standby by means of SILENCE key;

in Day Mode the SILENCE will remain until the SILENCE key is pressed again,

while in Night Mode the SILENCE will end automatically after the Silence Time expires.

Test Glowing indicates Test conditions on at least one zone.

MAINS

(Green)

OFF indicates Mains failure (230 Vac), both mains & battery power is lost.

IMPORTANT: Power must be restored before the batteries are discharged.

Table 5 Description of the status LEDs

F1

F2

F3

F4

FIRE

FAULT

Figure 47 Repeater FC500REP User Interface

Page 35: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

DISABLE 35

INSERT

USER

PA

SSW

ORD

CH

AN

GE

USER

PW

DPA

NEL

NA

ME

FW

VERSIO

N

DIA

SA

BLE

CLEA

RLO

GD

ATE

&TI

ME

SW

ZO

NE

DEVIC

EO

UTP

UT

LOG

OPTI

ON

TELEC

OM

INSER

PA

NEL

NA

ME

VIE

WFW

VER.

INSERT

NEW

USER

PA

SSW

ORD

SELEC

TW

HAT

ITEM

TOBE

DIS

ABLED NET

DEVIC

EO

UTP

UT

CO

MM

UN

IC.

SW

ZO

NE

DIS

ABLE

ZO

NE

CH

OO

SE

SW

ZO

NE

DIS

ABLE

CO

MU

NIC

.

CH

OO

SE

OU

TPU

T

DIS

ABLE

OU

TPU

T

CH

OO

SE

NET

EQ

UIP

MEN

T

DIS

ABLE

NET

EQ

UIP

EM

NT

DIS

ABLE

DEVIC

E

CH

OO

SE

DEVIC

E

CH

OO

SE

LOO

P

SH

OW

DEVIC

E

CH

OO

SE

DEVIC

E

CH

OO

SE

LOO

P

SH

OW

SW

ZO

NE

STA

TU

S

SH

OW

OU

TPU

TSTA

TUS

SH

OW

OPTI

ON

SVIE

WLO

G

NET

SH

OW

NET

PSTA

TUS

SELEC

TW

HAT

ITEM

TOM

OD

IFY

LOO

P

SC

AN

&SH

OW

LOO

PPA

RA

M.

MA

INPA

GE

MO

DIF

YPRO

GRA

MA

NA

LYZE

VIE

WLO

G

WRO

NG

PA

SSW

ORD

LIS

T

VIE

WLIS

T

INSERT

USER

PA

SSW

ORD

WRO

NG

PA

SSW

ORD

CH

OO

SE

INTE

RFA

CE

DIS

ABLED

DEVIC

ES

DIS

ABLED

ZO

NE

DIS

ABLED

PA

RTS

SW

ZO

NE

IN

WA

LK

TEST

FA

ULT

SLIS

T

SCA

N&

SHO

W

DIS

ABL

EDSW

ZON

ES

SCA

N&

SHO

W

DIS

ABLE

DD

EVIC

ES

SC

AN

&SH

OW

DIS

ABLED

PA

RTS

VIE

WLIS

Ts

SC

AN

&SH

OW

SW

ZO

NES

INW

ALK

TEST

ALA

RM

FA

ULT

WA

RN

ING

PRE

ALA

RM

WA

LK

TEST

12

3

4

12

3

SELEC

TW

HAT

ITEM

TOA

NA

LYZE

15

45

67

89

2

SH

OW

TELEC

OM

i/f

STA

TU

S

LOG

CLEA

RIN

G

INSERT

DATA

&TI

ME

13

42

13

42

56

7

AC

TIVE

WA

LK

TEST

WA

RN

ING

S

LIS

TS

SC

AN

&SH

OW

AC

TIVE

FA

ULT

S

SC

AN

&SH

OW

DEVIC

ES

IN

WA

LK

TEST

13

42

56

Lev.

1

Lev.

2

Lev.

2

Lev.

2

41

23

42

3

23

42

3

42

3

SC

AN

&SH

OW

AC

TIV

E

WA

RN

ING

S

PA

GE

DIR

EC

TLY

AC

TIVATE

DBY

EVEN

TS

PA

NEL

0

4VIE

WSER.N

UM

.

DAY/

NIG

HT

INSERT

DAY/N

IGH

T

MO

DE3

WA

LK

TEST

6

INSERT

ZO

NE

WA

LK

TEST

PA

SSW

ORD

FIR

ERELAY

78

CH

OO

SE

USER

orIN

STA

LLER

DIS

ABLE

PA

SSW

ORD

DIS

ABLE

FIR

ERELAY

DIS

ABLED

DEVIC

ES

DIS

ABLED

ZO

NE

DIS

ABLED

PA

RTS

SCA

N&

SHO

W

DIS

ABL

EDSW

ZON

ES

SCA

N&

SHO

W

DIS

ABLE

DD

EVIC

ES

SC

AN

&SH

OW

DIS

ABLED

PA

RTS

13

2

Lev.

1

EN

TR

YV

ALID

ON

LYF

OR

I NS

TAL

LE

R#

1(0

00

00

=D

efa

ult)

*

*

Figura 48 Structure of the User Interface operations at L1and L2 levels.

Page 36: Addressable Fire Control Panels - ALARMCENTARalarmcentar.com/downloads/FC501 User Manual.pdfControl panel case. F Ensure that the control panel is capable of process-ing a fire alarm

0051

BENTEL SECURITY s.r.l.Via Gabbiano, 22 - Zona Ind. S. Scolastica

64013 Corropoli (TE) - ITALY13

0051-CPD-0406 (FC501-L)0051-CPD-0407 (FC501-H)

EN 54-2:1997+A1:2006 EN 54-21

Control and indicating equipment for fire detection and fire alarmsystems for buildings with alarm transmission and fault warningrouting equipment.

EXPECTED OPTIONS

Fault signals from pointsDependencies on more than one alarm signal: type A and BDelays to outputsDisablement of addressable pointTest conditionOutput to fire alarm device

EN 54-2 ESSENTIAL CHARACTERISTICS

Performance under fire conditions Passed

Response delay (response time to fire) Passed

Operational reliability Passed

Durability of operational reliability, Temperature resistance Passed

Durability of operational reliability, Vibration resistance Passed

Durability of operational reliability, Electrical stability Passed

Durability of operational reliability, humidity resistance Passed

EN 54-21 ESSENTIAL CHARACTERISTICS

Performance of transmission Passed

Operational reliability Passed

Durability of operational reliability, Temperature resistance Passed

Durability of operational reliability, Vibration resistance Passed

Durability of operational reliability, Electrical stability Passed

Durability of operational reliability, humidity resistance Passed

EN 54-4 ESSENTIAL CHARACTERISTICS

Performance of power supply Passed

Operational reliability Passed

Durability of operational reliability, Temperature resistance Passed

Durability of operational reliability, Vibration resistance Passed

Durability of operational reliability, Electrical stability Passed

Durability of operational reliability, humidity resistance Passed

0051

BENTEL SECURITY s.r.l.Via Gabbiano, 22 - Zona Ind. S. Scolastica

64013 Corropoli (TE) - ITALY13

0051-CPD-0408 (FC500IP in FC501-L/FC501-H)EN 54-21

Alarm transmission and fault warning routing equipment for firealarm systems installed in buildings.

EN 54-21 ESSENTIAL CHARACTERISTICS

Performance of transmission Passed

Operational reliability Passed

Durability of operational reliability, Temperature resistance Passed

Durability of operational reliability, Vibration resistance Passed

Durability of operational reliability, Electrical stability Passed

Durability of operational reliability, humidity resistance Passed

© FireClassvia Gabbiano 22, Z. Ind. S. Scoastica64013 Corropoli (TE), Italy

Hillcrest Business Park Cinderbank Dudley West MidlandsDY2 9AP United Kingdom

www.fireclass.netISTUSFKEFC501 1.0 190613