Advanced Differential Protection

Embed Size (px)

Citation preview

  • 7/26/2019 Advanced Differential Protection

    1/8

    VIII Seminrio Tcnico de Proteo e Controle28 de Junho a 1ode Julho de 2005

    Rio de Janeiro RJ

    Artigo: ST-3

    ADVANCED POWER TRANSFORMER DIFFERENTIAL

    PROTECTION

    Zoran Gaji, Ivo Brni, Birger [email protected],[email protected],[email protected]

    ABB Power Technologies AB, Vsters, Sweden

    1. ABSTRACT

    Three most typical weaknesses of the analogue

    differential protection relays for power transformersand autotransformers have been:

    1) Long operating time in case of heavy internalfaults followed by main CT saturation. Longdelays for heavy internal faultsthey can be of the

    order of several tens of milliseconds are aconsequence of the harmonic distortion of the faultcurrents as they are seen by the differential relay.

    The harmonic distortion is due to initial heavysaturation of the current transformers under faultconditions. Harmonic restrain criterion preventsimmediate operation of the differential protection.

    2) Unwanted operations for external faults andtransformer inrush. Analogue differentialprotection relays for power transformers show atendency to unwanted operations for faults external

    to the protected zone with the power transformerparticularly for external earth faults.

    3) Bad sensitivity for low-level internal faults,

    such as winding turn-to-turn faults. The low-level turn-to-turn faults typically cannot be detectedwith differential relay due to limited sensitivity ofthe relay operaterestraint characteristic. Even therelatively high sensitivity in the first section of the

    differential relay characteristic of typically 30%may not be enough to detect a minor turn-to-turnfault, which initially only causes a differential

    current of 10%, until it evolves into a more severefault with higher differential currents.

    All these weaknesses can be successfully avoided if

    the position of the fault (i.e. internal or external to

    the differential protection zone) is quickly andcorrectly determined for all cases. The newprotection principle is based on the theory of

    symmetrical components [1] and [2], or more exact,on the negative-sequence current theory.

    Key Words: Protection, Transformer Protection,Differential Algorithm.

    2. INTRODUCTION

    The above-described problems can be effectivelysolved by the application of directional comparisonprinciple between the negative sequence currents

    from all power transformer sides. Existence ofrelatively high negative-sequence currents is initself a proof of a disturbance on the power system,possibly a fault in the power transformer. Thenegative-sequence currents are measurableindications of abnormal conditions, similar to the

    zero-sequence currents. One of the severaladvantages of the negative-sequence currentscompared to the zero-sequence currents is however

    that they provide coverage for phase-to-phase andpower transformer turn-to-turn faults [4] as well,not only for earth-faults. Theoretically the negative

    sequence currents do not exist during symmetrical

    three-phase faults, however they do appear duringinitial stage of such faults [3] for long enough timefor the differential relay to make the properdecision. Further, the negative sequence currentsare not stopped at a power transformer of the Yd, or

    Dy connection. The negative sequence currents arealways properly transformed to the other side ofany power transformer for any external disturbance.

    Finally, the negative sequence currents are typicallynot affected by through-load currents.

    The new algorithm for the internal/external fault

    discriminator is based on the theory of symmetrical

    components, or more exact, on the negative-sequence currents. Already in 1933, Wagner andEvans [1] stated that:

    mailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]
  • 7/26/2019 Advanced Differential Protection

    2/8

    1) Source of the negative-sequence currents is atthe point of fault, (ENS= -INS* ZNS)

    2)

    Negative-sequence currents distribute throughthe negative-sequence network

    3)

    Negative-sequence currents obey the first

    Kirchhoff's law

    Similar statements are as well re-confirmed inreference [2].

    The internal/external fault discriminator simplydetermines the position of the source of the

    negative sequence currents with respect to theprotected zone. If the source of the negativesequence currents is found to be outside the zone,then the fault is external. If the source is found to be

    inside the zone, the fault is internal.

    The internal/external fault discriminator only worksif the protected power transformer is connected tosome load, so that currents can flow through the

    protected power transformer, or at least through twowindings in case of a three-winding powertransformer. Thus, at an initial current inrush, theinternal/external fault discriminator algorithm

    declares neither internal, nor external fault.

    3. PRINCIPLES OF OPERATION

    In order to avoid misunderstandings about what ismeant by the same direction and opposite

    direction, an explanation of relay internally usedCT reference directions is shown in Figure 1.

    Relay

    E1S1

    Z1S1

    E1S2

    Z1S2

    IW1

    IW2

    IW1

    IW2

    Figure 1: Used reference connections of CTs, anddefinition of positive direction of currents

    As shown in Figure 1 relay will always measure theprimary currents on all sides of the powertransformer with the same reference direction

    towards the power transformer windings.

    For an external fault the fictitious negativesequence source will be located outside thedifferential protection zone at the fault point. Thusthe negative sequence currents will enter the

    healthy power transformer on the fault side, andleave it on the other side, properly transformed.According to the current direction definitions in

    Figure 1, the negative sequence currents on therespective power transformer sides will have

    opposite directions. In other words, the

    internal/external fault discriminator sees thesecurrents as having a relative phase displacement ofexactly 180oas shown in Figure 2.

    Relay

    ENS

    ZNSS1

    ZNSS2

    Yy0; 1:1INS

    S1 INS

    S1 INS

    S2

    INSS1

    INSS1

    Negative Sequence

    Zero Potential

    Figure 2:Flow of negative sequence currents forpower transformer external fault

    For an internal fault (with the fictitious negativesequence source within protected power

    transformer) the negative sequence currents willflow out of the faulty power transformer on both

    sides. According to the definitions in Figure 1, thenegative sequence currents on the respective powertransformer sides will have the same direction. Inother words, the internal/external fault

    discriminator sees these currents as having arelative phase displacement of zero electricaldegrees, as shown in Figure 3. In reality, for aninternal fault, there might be some small phase shiftbetween these two currents due to possible differentnegative sequence impedance angles of the source

    equivalent circuits on the two power transformersides.

    Relay

    ENS

    Yy0; 1:1

    ZNSS1

    ZNSS2

    INSS2

    INSS1

    INSS2INSS1

    Negative Sequence

    Zero Potential

    Figure 3: Flow of negative sequence currents for

    power transformer internal fault

    3.1 Negative sequence differential current

    Modern numerical transformer differential relaysuse matrix equations to automatically compensatefor any power transformer vector group and turnsratio [6]. This compensation is done automaticallyin the on-line process of calculating the traditional

    differential currents. It can be shown, that thenegative-sequence differential currents can be

    calculated by using exactly the same matrixequations, which are used to calculate thetraditional differential currents. However, the sameequation shall be fed by the negative-sequence

    currents from the two power transformer sidesinstead of individual phase currents, as shown in

    the following matrix equation for a case of two-winding, Yd5 power transformer.

  • 7/26/2019 Advanced Differential Protection

    3/8

    2 2

    _ 1 _ 2 1 1 _ 1 0 1 _

    1 _ 1_ 2 _ 1 2 1 _ 1 1 0 _

    3 _ 3_ 3 _ 1 1 2 _ 0 1 1 _

    Id L N S IH V N S IL V N S

    U r L V

    Id L N S a IH V N S a IL V N S

    U r H V

    Id L N S a IH V N S a IL V N S

    (0.1)

    where:

    Id_L1_NS is the negative sequence differentialcurrent in phase L1 (in HV side primary amperes).IHV_NS is HV side negative sequence current in

    HV side primary amperes (phase L1 reference).ILV_NS is LV side negative sequence current inLV side primary amperes (phase L1 reference).

    Ur_HV is transformer rated phase-to-phase voltageon HV side (setting parameter).Ur_LV is transformer rated phase-to-phase voltageon LV side (setting parameter).

    a is the well-known complex operator for sequence

    quantities; a=0,5+j*0,866.

    In reality only the first negative sequence

    differential current, e.g. Id_L1_NS, needs to becalculated, because the negative sequence currentsalways form the symmetrical three phase current

    system on each transformer side. Consequentlythree negative sequence differential currents willalways have the same magnitude and be phase

    displaced for 120 electrical degrees from eachother.

    As marked in matrix equation, the first term on theright hand side of the equation, represents the totalcontribution of the negative sequence current from

    HV side compensated for eventual powertransformer phase shift. The second term on theright hand side of the equation, represents the totalcontribution of the negative sequence current from

    LV side compensated for eventual powertransformer phase shift and transferred to the powertransformer HV side.

    When above compensation is made, then the 0-180

    degree rule is again valid between negativesequence current contributions from the two sides.For example, for any unsymmetrical external fault,the respective negative sequence current

    contributions from the HV and LV powertransformer sides will be exactly 180 degrees apart

    and equal in magnitude, regardless the powertransformer turns ratio and phase displacement, asin example shown in Figure 4.

    0.1 kA

    30

    210

    60

    240

    90

    270

    150

    330

    180 0

    Contribution to neg. seq. differential current from HV side

    Contribution to neg. seq. differential current from LV side

    0.2 kA0.3 kA

    0.4 kA

    "steady state"

    for HV side

    neg. seq. phasor

    "steady state"

    for LV side

    neg. seq. phasor

    10ms

    10ms

    Figure 4: Trajectories of Negative SequenceCurrent Contributions from HV and LV sides of

    Yd5 power transformer during external fault

    Figure 4 shows trajectories of the two separate

    phasors representing the negative-sequence currentcontributions from HV and LV sides of an Yd5power transformer (e.g. after the compensation of

    the transformer turns ratio and phase displacementby using previous matrix equation) for anunsymmetrical external fault. Observe that the

    relative phase angle between these two phasors is180 electrical degrees at any point in time. There isnot any current transformer saturation for this case.

    3.2 Internal / external fault discriminator

    The internal/external fault discriminator is based onthe above-explained facts. Its operation is based onthe relative position of the two phasors representing

    HV and LV negative-sequence currentcontributions, defined by matrix expression. Itpractically performs directional comparisonbetween these two phasors. First, the LV sidephasors is positioned along the zero degree line.After that the relevant position of the HV side

    phasor in the complex plain is determined. Theoverall directional characteristic of theinternal/external fault discriminator is shown in

    Figure 5.

    Figure 5: Operating characteristic of theinternal/external fault discriminator

    Neg. Seq. currentcontribution from

    HV side

    Neg. Seq. currentcontribution from

    LV side

  • 7/26/2019 Advanced Differential Protection

    4/8

    In order to perform directional comparison of the

    two phasors their magnitudes must be high enoughso that one can be sure that they are due to a fault.On the other hand, in order to guarantee a goodsensitivity of the internal/external fault

    discriminator, the value of this minimum limit must

    not be too high. Therefore this limit value, calledIminNegSeq, is settable in the range from 1% to

    20% of the differential protections base current,which is in our case the power transformer HV side

    rated current. The default value is 4%. Only ifmagnitudes of both negative sequence currentcontributions are above the set limit, the relative

    position between these two phasors is checked. Ifeither of the negative sequence currentcontributions, which should be compared, is toosmall (less than the set value for IminNegSeq), no

    directional comparison is made in order to avoid thepossibility to produce a wrong decision. This

    magnitude check, as well guarantee stability of thealgorithm, when power transformer is energized.

    The setting NegSeqROA represents the so-calledRelay Operate Angle, which determines theboundary between the internal and external faultregions. It can be selected in the range from 30

    degrees to 90 degrees, with a step of 1 degree. Thedefault value is 60 degrees. The default settingsomewhat favours security in comparison to

    dependability.

    If the above condition concerning magnitudes is

    fulfilled, the internal/external fault discriminatorcompares the relative phase angle between thenegative sequence current contributions from the

    HV side and LV side of the power transformerusing the following two rules:

    If the negative sequence currents contributionsfrom HV and LV sides are in phase, the fault isinternal (i.e. both phasors are within internal fault

    region)

    If the negative sequence currents contributionsfrom HV and LV sides are 180 degrees out of

    phase, the fault is external (i.e. HV phasors isoutside internal fault region)

    Therefore, under all external fault condition, therelative angle is theoretically equal to 180 degrees.

    During internal fault, the angle shall ideally be 0degrees, but due to possible different negativesequence source impedance angles on HV and LV

    side of power transformer, it may differ somewhatfrom the ideal zero value. However, during heavyfaults, CT saturation might cause the measured

    phase angle to differ from 180 degrees for external,and from about 0 degrees for internal fault. See

    Figure 6 for an example of a heavy internal faultwith transient CT saturation.

    0.5 kA

    30

    210

    60

    240

    90

    270

    120

    300

    150

    330

    180 0

    HV side contribution t o the t otal negative sequence differential current in kA

    Directional limit (within the region delimited by 60 degrees is internal fault)

    1 .0 kA

    1 .5 kA

    definitely

    an internal

    fault

    Internal

    fault

    declared

    7 ms after

    internal

    fault

    occurred

    trip command

    in 12 ms

    excursion

    from 0 degrees

    due to

    CT saturation

    external

    fault

    region

    35 ms

    Directional Comparison Criterion: Internal fault as seen from the HV s ide

    Figure 6:Operation of the internal/external faultdiscriminator for internal fault with CT saturation

    4. IMPROVEMENT OF THE PROTECTION

    The internal/external fault discriminator is a verypowerful and reliable supplementary criterion to thetraditional power transformer differential

    protection. It detects even minor faults, with a highsensitivity and a high speed, and at the same timediscriminates with a high degree of dependability

    between internal and external faults. When goodproperties of traditional power transformerdifferential protection are combined together with

    advanced features of internal/external faultdiscriminator a high performance differential

    protection for power transformers andautotransformers is achieved.

    4.1 No extra delays at heavy internal faults

    As the newly introduced internal/external faultdiscriminator has proved to be very reliable, it has

    been given a great power. If, for example, a faulthas been detected, i.e. start signals set by ordinarydifferential protection, and at the same time the

    internal/external fault discriminator characterisedthis fault as internal, then any eventual blocksignals produced by either the harmonic or the

    waveform restraints, are ignored. This assures theresponse times of the new and advanced differentialprotection below one power system cycle (i.e.below 20ms for 50Hz system) for all internal faults.Even for heavy internal faults with severelysaturated current transformers new differential

    protection operates well below one cycle becausethe harmonic distortions in the differential currentsdo not slow down the differential protection

    operation. Practically, an unrestrained operation isachieved for all internal faults.

    4.2 Stability against external faults

    External faults happen ten to hundred times moreoften than internal ones. Many power transformer

  • 7/26/2019 Advanced Differential Protection

    5/8

    differential protection relays have a rather poor

    stability against external faults. If a disturbance hasbeen detected and the internal/external faultdiscriminator characterised this fault as externalfault, the additional criteria are posed on the

    differential relay before its trip is allowed. This

    assures high stability against external faults.However, in the same time the differential relay is

    still capable to trip for evolving faults. Example ofsuch evolving fault is shown in Figure 7.

    0.2

    0.4 kA

    30

    210

    60

    240

    90

    270

    120

    300

    150

    330

    180 0

    Magnitude of contribution from the HV (Y) side (in kA)

    Directional limit (within 60 degrees is internal fault)

    only

    ext.

    fault

    ext.

    and

    int.

    faults

    int.

    only

    internal -

    external

    fault

    boundary

    A

    B

    C

    internal

    faults

    external

    faults

    Figure 7:Operation for evolving fault

    Point A in Figure 7 corresponds to the external faultonly. Point B corresponds to simultaneous external

    and internal faults. The internal fault occurred 20msafter the external one. Point C corresponds to thesituation after the external fault has been cleared by

    some other protection in 128 ms, while the internalfault persists. The advanced differential protectionwould actually operates already at point B and

    disconnects the power transformer, in spite of thefact that the point B is deep in the external faultarea because of the more dominant (heavier)external fault.

    4.3 Detection of minor internal faults

    The internal/external fault discriminator has shownextreme capability to detect low-level faults such as

    winding turn-to-turn faults. For more information

    on this subject please refer to reference [4].

    5. OPERATING PRINCIPLES FOR THREE-

    WINDING TRANSFORMERS

    The principle of the internal/external faultdiscriminator can be extended to powertransformers and autotransformers with three

    windings. If all three windings are connected totheir respective networks, then three directionalcomparisons can be done, but only twocomparisons are necessary in order to positively

    determine the position of the fault with respect to

    the protected zone. The directional comparisons,which are possible, are: primary - secondary,

    primary - tertiary, and secondary - tertiary. The rule

    applied by the internal / external fault discriminator

    in case of three-winding power transformers is:

    If all comparisons indicate an internal fault,then it is an internal fault.

    If any comparison indicates an external fault,

    then it is an external fault

    If one of the windings is not connected, thealgorithm automatically reduces to the two-windingversion. Nevertheless, the whole power transformer

    is protected, inclusive the non-connected winding.

    5.1 Example of unsymmetrical internal fault for

    three-winding transformer

    An internal fault L2-L3-Ground on the secondary

    winding (d1) of a three-winding power transformer,connection group Yd1d5, has been simulated by

    ATP [7].

    0 10 20 30 40 50 60 70 80-4

    -2

    0

    2

    4

    PrimarycurrentsinkA

    iA

    iB

    iC

    iN

    0 10 20 30 40 50 60 70 80-50

    0

    50

    100

    SecondarycurrentsinkA

    ia

    ib

    ic

    0 10 20 30 40 50 60 70 80-5

    0

    5

    10

    Time in ms, internal fault at t = 13 ms

    Inst.diff.curr.in

    kA

    inst diff L1inst diff L2

    inst diff L3

    int. fault

    int. faultint. fault

    int. fault

    iB = primary (Y) line current L2

    ib = secondary (d1) line current L2

    instaneous diff. curr. L2

    Figure 8:Currents for an L2-L3-E internal fault onthe secondary winding (d1) of an Yd1d5 power

    transformer. Differential currents are in primary kA

    The currents on the primary- and secondary sides,

    and the instantaneous differential currents, areshown in Figure 8. The two directional

    comparisons, made by the internal/external faultdiscriminator on the contributions to the totalnegative sequence differential current from theprimary, secondary and tertiary are shown in Figure9 and Figure 10.

  • 7/26/2019 Advanced Differential Protection

    6/8

    Figure 9:Internal/external fault discriminator

    operation between primary and secondary windings

    Figure 10:Internal/external fault discriminatoroperation between primary and tertiary windings

    Obviously both of them steadily indicate that the

    fault is internal. Deviations of the relative phaseangle from zero degrees in Figure 9 and Figure 10were mainly due to current transformer saturation.Severe current transformer saturation is actually the

    most dangerous enemy of the internal/external faultdiscriminator. However very effective means tocounteract the negative effects of main CTsaturation have been integrated in advanceddifferential protection algorithm.

    0 10 20 30 40 50 60 70 80

    0

    2

    4

    6

    8

    10

    12

    14

    16

    18

    Time in ms, internal fault at t = 13 ms

    Binary signals of the power transformer differential protection

    fault

    start-L1

    start-L2

    start-L3

    trip

    tripRestrained

    tripUnrestrained

    tripNegSeqUnrestrained

    tripNegSeqSensitive

    blockDueToCurr2ndHarm-L1

    blockDueToCurr2ndHarm-L2

    blockDueToCurr2ndHarm-L3blockDueToCurr5thHarm-L1

    blockDueToCurr5thHarm-L2

    blockDueToCurr5thHarm-L3

    blockDueToWaveAnalysis-L1

    blockDueToWaveAnalysis-L2

    blockDueToWaveAnalysis-L3

    InternalFault

    ExternalFaultint. fault declared

    trip in 15 ms

    Figure 11: Binary output signals of the advanceddifferential protection during internal fault in 3-

    winding power transformer.

    It shall be noticed that in Figure 11 the usual

    restrained differential protection (signal namedtripRestrained) was delayed due to harmonic andwaveform block criteria. Besides, this signal wasunstable (onoffon, etc). The usual unrestraineddifferential protection limit, which had been set to10 times transformer rated current, was not

    exceeded due to heavy ct saturation, and thus nohelp from the unrestrained differential protectionwas obtained either. Only the new advanced

    differential protection was capable to quickly detectand trip the faulty power transformer in 15 ms afterthe fault inception.

    5.3 Example of two simultaneous external faults

    A case with two simultaneous external faults, the

    first one L1Ground fault on the secondary side andthe second fault L1Ground on the tertiary side of

    an Yd1d5 power transformer, is presented here.

    0.2 kA0.4 kA

    30

    210

    60

    240

    90

    270

    120

    300

    150

    330

    180 0

    Contribution to t otal neg. seq. diff. current from tertiary

    Contribution to total neg. seq. diff. current from primary

    Contribution to t otal neg. seq. diff. current from secondary

    0 .6 kA

    fromsecondary

    side

    from tertiary

    side

    Figure 12. Trajectories of the contributions to thetotal negative sequence differential current for thefirst 25 ms during two simultaneous external faults

    From Figure 12 it is obvious that the new

    internal/external fault discriminator will securely

    0.2

    0.4

    0.6 kA

    30

    210

    60

    240

    90

    270

    120

    300

    150

    180 0

    Comparison Between Contributions: Primary - Secondary

    Negative sequence differential current phasor (in kA)

    Directional limit (within 60 degrees is internal fault)

    57 ms

    after

    fault

    internal

    fault

    declared

    here

    external

    fault

    zone

    external

    fault

    zone

    0.2

    0.4

    0.6 kA

    30

    210

    60

    240

    90

    270

    120

    300

    150

    330

    180 0

    Negative sequence differential current phasor (in kA)

    Directional limit (within 60 degrees is internal fault)

    Comparison Between Contributions: Primary - Tertiary

    57 ms

    after

    fault

    trip

    external

    fault

    zone

    external

    fault

    zone

    internal

    fault

    zone

  • 7/26/2019 Advanced Differential Protection

    7/8

    declare this fault as external for this complicated

    test case.

    5.4 Example of three-phase internal fault

    The negative-sequence-current-based directional

    principle yields a fast and reliable discriminationbetween external and internal faults. This is easy to

    understand in case of unsymmetrical faults, wherethe negative sequence system is expected to exist.

    But the principle is just as efficient in case ofwholly symmetrical three-phase faults as well. Thereason is that when a (symmetrical) three-phase

    fault occurs, the negative sequence current sourceappears at the fault for a while, more exactly, untilthe dc components in the fault currents die out [3].As far as advanced power transformers differential

    algorithm is concerned, this interval of time is longenough for the directional criterion to declare either

    an internal or an external fault.

    Figure 13 shows magnitudes of the negative

    sequence differential current, and its components,for an absolutely symmetrical internal three-phasefault on the Y side of an Yd1d5 power transformeras they were calculated by the differential relay. It

    took in this example about 20 ms for currenttransformers to reach heavy saturation. Theexistence of the false negative sequence currents

    after CT saturation was not a surprise. However,much more interesting was that the negativesequence system appeared immediately following

    the inception of the internal symmetrical fault.

    Figure 14 shows that during 22 ms after the fault

    inception, both directional tests correctly indicatedan internal fault, which was long enough time todisconnect the faulty power transformer in 14 ms

    (output relay make time not included) as shown inFigure 15.

    0 10 20 30 40 50 60 70 800

    0.2

    0.4

    0.6

    0.8

    1

    1.2

    1.4The total negative sequence differential current and its three components

    CurrentsinkA

    (transformerratedcurrentI1=0.5

    23kA)

    Time in ms, internal symmetrical fault at t = 13 ms

    IdifNegSeqTotal

    IdifNegSeqContrPri

    IdifNegSeqContrSec

    IdifNegSeqContrTer

    total negative

    sequencedifferential

    current

    current transformer

    saturation sets in

    heavy ct saturation

    3-phase

    internal

    fault

    rated current

    Figure 13:Magnitudes of the negative sequencedifferential current, and its components, for an

    internal three-phase fault on an Yd1d5 transformer.

    210

    240

    90

    270

    120

    330

    150

    180

    Primary - Secondary Primary - Tertiary

    Magnitude of negative sequence differential current (in kA)

    Directional limit (within 60 degrees is internal fault)

    60

    30

    0

    300

    0

    30

    60

    90

    120

    150

    180

    210

    240270

    300

    330

    Figure 14: Directional tests for an internal three-phase fault on an Yd1d5 transformer, first 25 ms.

    0 10 20 30 40 50 60 70 80 90

    0

    2

    4

    6

    8

    10

    12

    14

    16

    18

    Time in ms, internal fault occured at t = 13 ms

    Binary output signals of the differential protection for 3-phase internal fault

    fault

    start-L1

    start-L2

    start-L3

    trip

    tripRestrained

    tripUnrestrained

    tripNegSeqUnrestrained

    tripNegSeqSensitive

    blockDueToCurr2ndHarm-L1blockDueToCurr2ndHarm-L2

    blockDueToCurr2ndHarm-L3

    blockDueToCurr5thHarm-L1

    blockDueToCurr5thHarm-L2

    blockDueToCurr5thHarm-L3

    blockDueToWaveAnalysis-L1

    blockDueToWaveAnalysis-L2

    blockDueToWaveAnalysis-L3

    InternalFault

    ExternalFaultint. fault found, 9 ms

    trip in 14 ms

    12 ms

    Figure 15: Output signals for an internal whollysymmetrical three-phase fault.

    As shown in Figure 15 the internal fault was

    declared in 9 ms, the negative sequence differentialprotection issued a trip request after 12 ms, and the

    final trip command to the power transformer circuitbreakers was given in 14 ms after the faultinception by the advanced differential protection.

    6. CONCLUSIONS

    This paper shows, that by using advanced

    numerical technology, it is now possible to protectpower transformers with advanced differentialprotection principle, which has much higheroperation speed, security and sensitivity thantraditional transformer differential protection.

    Operation of new internal/external faultdiscriminator for power transformers has been

    successfully tested, by using simulation filesproduced by ATP [7], disturbance recording filescaptured during independent transformerdifferential protection testing on the analogue

    network simulator [5] and finally from thedisturbance recordings captured in the field. Allthese tests indicate excellent performance of the

    internal/external fault discriminator for power

    transformers and autotransformers. It detects evenminor faults, with a high sensitivity and a highspeed, and at the same time discriminates with a

  • 7/26/2019 Advanced Differential Protection

    8/8

    high degree of dependability between internal and

    external faults. The only shortcomings of this newdirectional comparison algorithm are that it onlyoperates when power transformer is loaded and itdoes not provide indication of the faulty phase(s).

    However, for internal faults power transformers are

    always tripped three-phase, while from the captureddisturbance record at the moment of tripping the

    faulty phase(s) can be identified.

    7. REFERENCES

    [1] C.F. Wagner, R.D. Evans, Book:Symmetrical Components", McGraw-Hill,New York & London, 1933

    [2] J.L. Blackburn, Book: SymmetricalComponents for Power System Engineering,

    Marcel Dekker, New York, Basel, HongKong, 1993; ISBN: 0-8247-8767-6

    [3] Jonas Johansson, Master Thesis: FastEstimation of Symmetrical Components,Department of Industrial ElectricalEngineering and Automation, Lund

    University, Sweden 2002.

    [4] Z. Gaji, I. Brni, B. Hillstrm, I. Ivankovi"Sensitive Turn-to-Turn Fault protection forPower Transformers", CIGRE SC B5Colloquium, September 2005, Calgary-

    Canada

    [5] Z. Gaji, G.Z. Shen, J.M. Chen, Z.F. Xiang,"Verification of utility requirements onmodern numerical transformer protection bydynamic simulation" presented at the IEE

    Conference on Developments in PowerSystem Protection, Amsterdam, Netherlands,2001

    [6] F. Meki, Z. Gaji and S. Ganesan, "AdaptiveFeatures of Numerical Differential Relays,"presented at the 29th Annual Conference for

    Protective Relay Engineers, Spokane,Washington, USA, October 2002

    [7] ATP is the royalty-free version of theElectromagnetic Transients Program (EMTP).

    For more info please visit the following websites: http://www.eeug.de/ orhttp://www.ee.mtu.edu/atp/

    http://www.eeug.de/http://www.eeug.de/http://www.ee.mtu.edu/atp/http://www.ee.mtu.edu/atp/http://www.ee.mtu.edu/atp/http://www.eeug.de/