8
Advanced power quality analysis coupled with revenue accuracy in a web compatible meter PowerLogic ® ION7550/ION7650 series Energy and power meters Industry

Advanced power quality analysis coupled with revenue ... · > Trending and forecasting Forecast values, such as demand to better control demand charges and billing rates. View results

Embed Size (px)

Citation preview

Page 1: Advanced power quality analysis coupled with revenue ... · > Trending and forecasting Forecast values, such as demand to better control demand charges and billing rates. View results

Advanced power quality analysis coupled with revenue accuracy in a web compatible meter PowerLogic® ION7550/ION7650 seriesEnergy and power meters

Industry

Page 2: Advanced power quality analysis coupled with revenue ... · > Trending and forecasting Forecast values, such as demand to better control demand charges and billing rates. View results

PowerLogic ION7550/7650 series power and energy meters

Used at key distribution points and sensitive loads, the PowerLogic ION7550 and ION7650 series meters offer unmatched functionality, including advanced power quality analysis coupled with revenue accuracy, multiple communications options, web compatibility and control capabilities.

Integrate these meters with our PowerLogic ION Enterprise® software, or share operations data with existing SCADA systems, through multiple communication channels and protocols.

Typical applications

For infrastructure, industrials and buildings

•Energysavings> Measureefficiency,revealopportunitiesandverifysavings> Reducepeakdemandsurcharges> Reducepowerfactorpenalties> Strengthenratenegotiationwithenergysuppliers> Enableparticipationinloadcurtailmentprograms(e.g.,demandresponse)> Identifybillingdiscrepancies> Leverageexistinginfrastructurecapacityandavoidover-building> Supportproactivemaintenancetoprolongassetlife

•Energyavailabilityandreliability> Validatethatpowerqualitycomplieswiththeenergycontract> Verifythereliableoperationofequipment> Improveresponsetopowerquality-relatedproblems

For electric utilities

•Energyavailabilityandreliability> ImproveT&Dnetworkreliability> Enhancesubstationautomationtoreducefieldservicetime> Maximizetheuseofexistinginfrastructure

•Revenuemeteringandpowerquality> Installnewhigh-accuracymeteringatallinterchangepoints> Improveorverifymeteringaccuracyatexistinginterchangepoints> Verifycompliancewithnewpowerqualitystandards> Analyzeandisolatethesourceofpowerqualityproblems

2 • ION7550/7650 series power and energy meters

Page 3: Advanced power quality analysis coupled with revenue ... · > Trending and forecasting Forecast values, such as demand to better control demand charges and billing rates. View results

Features

> High visibility, multilingual, IEC/IEEE configureable displayLarge,backlitLCDpresentsmultiplesimultaneousreal-timeandtime-stampedhistoricalparameters,aswellasgraphicaltrendsandhistograms.

> High accuracy standardsMeetsstringentIECandANSImeasurementaccuracystandards,suchasIEC62053-22Class0.2S,ANSIC12.200.2Class10and20.

> Digital fault-recordingSimultaneouslycapturevoltageandcurrentchannelsforsub-cycledisturbancetransients,aswellasmulti-cyclesags/swellsandoutages:1024samples/cyclewaveformrecording,20/17μstransientcapture(50/60Hz).

> Power quality analysis and compliance monitoringAchoiceofTHDmetering,individualcurrentandvoltageharmonicsreadings,waveformcapture,EN50160andflicker(PowerLogicION7650only)powerqualitycomplianceevaluationandvoltageandcurrentdisturbance(sag/swell)detection.COMTRADEformatwaveformrecordsarenowavailableonlyformeterswiththeEthernetportoption.

> Complete communications:Ethernet (RJ 45 modular or SC fiber) – Serial (RS 485 and/or RS 232) – ModemGatewayfunctionalitysimplifiescommunicationsarchitectureandreducesleasedlineorconnectioncosts.Concurrent,independentportscommunicatewithprotocolssuchasION,DNP3.0,IEC61850,ModbusRTU,ModbusTCP,ModbusMaster.Ethernetportallowsthefollowingconcurrentconnections:24Modbus,8generic(ION/DNP/Modbus),4IEC61850dedicatedclient,1FTPand1SNMP.Dial-outcapabilitywhenmemoryisnearfull.DatapushcapabilitythroughSMTP(email).

> Patented ION technologyProvidesamodular,flexiblearchitecturethatoffersextensiveuserprogrammability.Uniquelyaddressescomplexmonitoringandcontrolapplications.Adaptstochangingneeds,avoidingobsolescence.

> Disturbance direction detectionDeterminethelocationofadisturbancemorequicklyandaccuratelybydeterminingthedirectionofthedisturbancerelativetothemeter.Analysisresultsarecapturedintheeventlog,alongwithatime-stampandconfidencelevelindicatinglevelofcertainty.

> Alarm setpoint learningHelpssimplifyalarmingconfigurationsbymonitoringnormaloperatingparametersand,overtime,learningwhatconstitutesasag,swell,transientorhighandlowsetpoint.LearningcanbeconfiguredineitherIONSetup™orPowerLogicIONEnterprisesoftware.

> Trending and forecastingForecastvalues,suchasdemandtobettercontroldemandchargesandbillingrates.Viewresultsviathemeter’swebpages.Analysetrendstosupportproactivemaintenanceschedules.

> Transformer/line loss compensationAutomaticallymeasure,compensateandcorrectfortransformerorlinelosseswhenmeterisphysicallyseparatedfromthepointofbillingorchangeofownership.

> Inputs and outputsDigitalandanaloginputsandoutputsforpulsecounting,demandmeteringforotherWAGESutilities,equipmentstatus/positionmonitoring,demandsynchronization,triggeringconditionalenergymetering,equipmentcontrolorinterfacing.

ION7550/7650 series power and energy meters • 3

Page 4: Advanced power quality analysis coupled with revenue ... · > Trending and forecasting Forecast values, such as demand to better control demand charges and billing rates. View results

Designed to fit DIN standard 192 cutout (186 mm by 186 mm). Circuit and control power connections include 4-Wire Wye, 3-Wire Wye, 3-Wire Delta, Direct Delta and single-phase systems. four voltage and five current inputs.

Installation Front panelUseforbothdisplayandconfigurationpurposes.ThelargebacklitLCDdisplayscreenandthenumerousselection,navigationandconfigurationsoftkeysallowquick,secureaccesstobasicmeterconfigurationscreens.Thefrontpanelalsoprovidesaccesstomanyothermeterfunctions,suchasmeterresetsandhasmultipleprogrammablescreensfornumericandtime-stampedvalues,frequencyspectrum(harmonics),trendlogsandnameplatedata.

Thelargedisplayautomaticallyscrollsthroughdisplaysscreensthatpresentat-a-glanceVolts,Amps,power,energyanddemandvalues.Screensareeasilycustomizedtosuituserrequirements.Setparametermeasurementsviafrontpaneltocomplywithregionalpreferences.ModbusMasterfeatureallowsdisplayofreal-timeparametersofanydownstreammodbusdevices.

Phasors display

Energy received/delivered display

Harmonic current display

Trend display

Input(s) Specifications

Voltage inputsNominalfullscale 347Vacdirectline-to-neutral,

600Vacdirectline-to-line,RMS

Overload 1500VacRMScontinuous

Inputimpedance 5MΩ/phase(phase-Vref)

Faultcapture 1200Vpeak

Current inputsNominalcurrent 5A,10Aand/or20A

(1A,2A,5Aoptionalcurrentrange)

Max.voltage 600VRMS(CATIIIIEC61010-1)

Withstand 2500Vac,60Hzfor1min

Load/burden 0.05VA/phase(at5Astandard)0.015VA/phase(at1Aoptional)

Impedance 0.002Ω/phase(phase-Vref)0.015Ω(optionalcurrentrange)

Control powerOperatingrange Standard:AC:85Vacto240Vac(±10%),

47Hzto63Hz;DC:110Vdcto300Vdc(±10%)Burden:Typical15VA,max.35VA

Optional:lowvoltageDCpowersupplyRatedinputs:DC:20Vdcto60Vdc(±10%)Burden:Typical12VA,max.18VA

Current probes with AC voltage outputRatedinputs 1VRMS

Overload 5.5V(CATIIEC61010-1)

Impedance 220kΩmax.

Options Currentprobeinputsforusewith0Vacto1Vaccurrentprobes.Probessoldseparately.Accuracydependsonprobespecs.

CurrentprobeinputswiththreecalibratedUniversalTechnic10Aclamp-onCTs,meetingIEC61036accuracy.

4 • ION7550/7650 series power and energy meters

Page 5: Advanced power quality analysis coupled with revenue ... · > Trending and forecasting Forecast values, such as demand to better control demand charges and billing rates. View results

Power and energy measurements

High-accuracyfour-quadrantenergymeteringinaccordancewithIEC62053-22Class0,2Sforboth3-and2-elementsystems.Real,bidirectional,reactiveandapparentvalues.Fullyprogrammableintegratingperiod(1,5,10,15,30,60minorother).

Supportsblock,rollingblockandpredicteddemandcalculationssuchas:kW,kVArandkVAdemand,min./max.;VoltsandAmpsdemand,min./max.;cumulativedemand;demandonanyinstantaneousmeasurement.

Power quality

Powerqualitycompliancemonitoringforinternationalquality-of-supplystandardsplusspecificdataforlocalizedandcustomcomplianceagreementsandnetworkconnectionrequirements.

•Harmonics (all models):individualharmonicsuptothe63rd,Kfactorandtotalharmonicsdistortion(THD).

•Sag/swell (all models):voltagewaveformsforsagsandswells(i.e.ITI(CBEMA))Type2andType3disturbances);reportoneachdisturbance’smagnitudeandduration.Detectsub-disturbancesduringasag/swellevent.

•Disturbance direction detection (all models):analyzedisturbanceinformationtodeterminethedirectionofthedisturbancerelativetothemeter.Resultsareprovidedintheeventlog,alongwithtime-stampandthelevelofcertaintyofdisturbancedirection.

•EN50160 (ION7650 with EN50160 ordering option only):monitorcompliancewithEN50160parameters.

•IEC 61000-4-30 (ION7650 only):monitorcomplianceofrelevant4-30parameterssuchaspowerfrequency,magnitudeofsupplyvoltage,flicker,supplyvoltagesags/swells,transientsandvoltageinterruptions.

•Transient (ION7650 only):voltagewaveformsoftransientactivity(i.e.,ITICBEMAType1disturbances).

•COMTRADE waveform format:recordsareavailabledirectlyfromthemeterviatheFTPserver(meterswithEthernetportoptiononly)

Example screen from PowerLogic ION Enterprise software showing continuous, wide-area monitoring, data capture and reporting for power quality and reliability conditions.

Measurement specifications[1]

Parameter Accuracy ± (% reading)

Voltage(line-line,line-neutral):perphase,min./max.,unbalance

0.1%

Frequency:present,min./max.

±0.005Hz

Current(I1,I2,I3) 0.1%

Current(I4,I5) 0.4%

Power:real(kW),reactive(kVAr),apparent(kVA),per-phase,total

IEC62053-22Class0,2S[2]

Energy:real(kWh),reactive(kVArh),apparent(kVAh),in/out

IEC62053-22Class0,2S[2]

kWA,kVAdemandcalculations

IEC62053-22Class0,2S[2]

Powerfactor(atUnityPF) 0.2%

[1]Refertouser’smanualforvalidmeasurementranges[2]Refertocompliancesection.NotapplicableforNICTmeters,contactfactoryformeasurementspecifications

ION7550/7650 series power and energy meters • 5

Page 6: Advanced power quality analysis coupled with revenue ... · > Trending and forecasting Forecast values, such as demand to better control demand charges and billing rates. View results

Data and event logging

Shipswithacomprehensivedata-loggingconfiguration.Dataisprioritizedandstoredon-boardinnonvolatilememorytoeliminatedatagapsintheeventofoutagesorserverdowntime.RetrieveddataisstoredinanODBC-compliantdatabasewhenusingIONEnterprise.Trendingandforecastingcapabilitiestrackspecifiedquantitiesovertimeandforecastthevalueoffuturequantities.Viewtrendingandforecastingdatathroughthemeter’swebpages.Loggingcapacityisavailablein5MBor10MBconfigurations.Defaultdepthandintervalofloggingissetatthefactory,anddependsuponon-boardmemorysize.

•Revenuelog:configuredforusewithUTSMV-90billingsoftware.LogskWhdel.int.,kWhrec.int.,kVARhdel.int.,kVARhrec.int.values.

•Historiclogs:recordstandardpowersystemquantities,suchasphasecurrent,phasevoltageandpowerfactor.

•Reportgeneratorlog:configuredtoprovidepowersystemdataforIONEnterprisesoftware.

•Eventlog•Trenddisplaylogs

> Multiple tariffs and time-of-use (TOU) calculations20-yearcalendarwithautomaticleap-yearandseasonaltimeadjustmentsandclocksynchronizationovercommunicationschannelorGPS.TOUisconfiguredfourseasons,fivedailyprofilesperseason,fourtariffperiodsperdailyprofile.Automaticmid-seasonratechange.Active,reactiveandapparentenergyanddemand;automaticrecordingofmax.(peak)demandduringeachtariffperiod.

> Example logging configurations:

Inputs and outputs

AllmodelsprovidedigitalinputsaswellasFormC(mechanicalrelays)andFormA(solidstaterelays)digitaloutputs.OptionaldigitalandanalogI/Oisalsoavailable.

Digitaloutputrelaysrespondtointernalalarms,externaldigitalinputstatuschangesorcommandsovercommunications.Usedigitalinputstotriggeralarmsorlogging,synchronizetoademandpulseorcontrolconditionalenergyaccumulation.

PowerLogic ION7650 I/O card

Trending and forecasting, as viewed from PowerLogic ION7650 web page

ION7550 ION7650Event 500events 500events 500events 500events

Data[1] 1.5yrs 3.1yrs 1.3yrs 2.9yrs

Waveforms 180[2] 180[2] 360[3] 360[3]

Type Input/output

Specifications

Electro-mechanical relays

3FormCrelays:R1-R3

FormCcontacts:NO,K,NC

250Vac/30Vdc,max.voltage:380Vac/125Vdc.Turn-ontime:15msmax.;Turn-offtime:5msmax.Updaterate:½-cycleor1sec

Solid state relays

4FormAdigitaloutputs:D1-D41

Max.voltage:30Vdc;max.current:80mA;isolation:optical;updaterate:½-cycleor1sec

Analog (op-tion)

4inputs:AI1toAI4

Signaltype:DCcurrent;range:0to20mA(scalable4to20),or0to1mA;accuracy:±0.3%offullscale;updaterate:1sec

4outputs:AO1toAO4

Signaltype:DCcurrent;range:0-20mA(scalable4-20)or-1mAto1mA(scalable0-1);updaterate:½-cycleor1sec

Digital 8inputs:S1-S8

SCOMself-excited,drycontactsensing,noexternalvoltagerequired.Min.pulsewidth:1ms;max.pulserate:20pulses/sec.Timingresolution:1ms;updaterate:½-cycle(aftertimingresolution);isolation:300Vpeak;max.ratedvoltage120Vdc(externalexcitation)

8inputs(option):DI1-DI8

Self-excited(internal30Vdcsupply);drycontactsensing,orwithexternalexcitation1.3mm2to0.1mm2(16AWGto28AWG);min.pulsewidth:20ms;max.pulserate:25pulses/sec;updated½-cycle(aftertimingresolution)

[1] 16parametersrecordedevery15min[2] 30waveformson6channelsatthemax.samplingrate[3] 30waveformson12channelswithanyselectableformat(forexample,6channelsare

512samples/cyclefor4cyclesand6channelsare32samples/cyclefor54cycles)

6 • ION7550/7650 series power and energy meters

Page 7: Advanced power quality analysis coupled with revenue ... · > Trending and forecasting Forecast values, such as demand to better control demand charges and billing rates. View results

Multiplecommunicationportsthatoperatesimultaneouslyallowthemeterstobeusedaspartofapowerandenergymanagementsystemandtointerfacewithotherautomationsystems.Uploadwaveforms,alarms,billingdataandmoretosoftwareforviewingandanalysis.

Communications

EtherGate

Ethernet Serial

Telephone line Serial

ModemGate

EtherGate and ModemGate The meters can provide gateway functionality depending on communication options.

EtherGate: provides access via Modbus TCP through the meter’s Ethernet port to devices communicating via Modbus connected to the meter’s serial ports.

ModemGate: provides access from the telephone network to devices connected to the meter’s serial ports.

Internet connectivity Exchange information using XML to integrate with custom reporting, spreadsheet, database, and other applications.

WebMeter®: an on-board web server, provides access to real-time values and PQ data through any web-enabled device and even supports basic meter configuration tasks.

MeterM@il®: automatically emails user-configured, high-priority alarm notifications or scheduled system-status update messages to anyone, anywhere within the facility or around the world.

General specifications

Port SpecificationsSerial RS-232/ RS-485 port (COM 1)

ProtocolsincludeION,ModbusRTU,ModbusMaster,DNP3.0,GPS,EtherGate,ModemGate.Datarates:300bpsto115,200bps(RS-485limitedto57,600bps).Connectors:maleDB9(RS-232DTE)orcapturedwire(RS-485).Duplex:Full(RS-232),Half(RS-485)

Serial RS-485 port (COM 2) ProtocolsincludeION,ModbusRTU,ModbusMaster,DNP3.0,GPS,EtherGate,ModemGate.Datarates:300bpsto57,600bps2400to38400.Duplex:Half

Internal modem (COM 3) Datarates:300bpsto33.6kbps(V.3.4,V.32bis,V.32,V.22bis,V.22A/B,V.23,V.21,Bell212A,Bell103).Supportsautomaticdataratedetection.RJ11interface.Approvals:FCCP68(USA),IndustryCanadaCS-03.Alsoapprovedforusein:Austria,Belgium,Denmark,Finland,France,Germany,Greece,Iceland,Ireland,Italy,Luxembourg,Netherlands,Norway,Portugal,Spain,Sweden,Switzerland,UnitedKingdom

ANSI Type 2 optical port (COM 4)

ProtocolsincludeION,DNP3.0,ModbusRTUDatarates:1200bpsto19,200bps.Halfduplex

Ethernet port Protocols:TCP/IP,Telnet,ION,ModbusTCP,SNMPInterface:IEEE802.3-1993,ISO/IEC8802-31993,IEC61850(Ethernet).Datarates:10Mbps,Halfduplex

10BASE-T,100BASE-TX:Connectors:RJ45,cabling:unshieldedtwisted-paircable,0.5mm(24AWG),max.length100m(109yds).Isolation:Transformerisolatedto1500VRMS

100BASE-FX(fibre)connectors:ST;Cabling:Fibreopticcable,62.5/125μmnominal,wavelength820nm,max.length2000m

Description SpecificationsAccuracy IEC62053-220,2S,1Aand5AtestedbyKEMA;ComplieswithANSIC12.20,Class10andClass20

Safety/construction IEC1010-1(EN61010-1);CSAC22.2No1010-1;UL61010B-1ElectromagneticImmunity;IEEEC.37-90.1-1989;EN50082-2

Electromagnetic compatibility

IEC61000-4-2(EN61000-4-2/IEC8012);IEC61000-4-3(EN61000-4-3/IEC801-3)RadiatedEMFieldImmunity

IEC61000-4-4(EN61000-4-4/IEC801-4)ElectricFastTransient;IEC61000-4-5(EN61000-4-5/IEC801-5)SurgeImmunity

IEC61000-4-6(EN61000-4-6/IEC801-6)ConductedImmunity;IEC61000-3-2(EN61000-3-2);IEC61000-3-3(EN61000-3-3)

FCCPart15SubpartB,ClassADigitalDevice;EN55011(CISPR11);EN55022(CISPR22);EN61000-6-4(EN50081-2)

Environmental conditions Operatingtemperature:-20°Cto+70°C(noformationofice)(-4°Fto158°F)

LowVoltageDCPowerSupply:-20°Cto50°C(-4°Fto122°F)

Storage:-40°Cto+85°C(-40°Fto185°F)

Humidity:5%to95%non-condensing

ION7550/7650 series power and energy meters • 7

Page 8: Advanced power quality analysis coupled with revenue ... · > Trending and forecasting Forecast values, such as demand to better control demand charges and billing rates. View results

Schneider Electric USA, Inc.

295TechParkDriveLaVergne,TN37086Tel:615-287-3500www.PowerLogic.com

DocumentNumber3000BR0604R10/10

©201

0Sch

neiderElectric

.AllRightsRes

erve

d.

October2010tk

This document has been printed on recycled paper

PowerLogicION7550/7650 seriesfeatures and options

Asstandards,specificationsanddesignsdevelopfromtime,alwaysaskforconfirmationoftheinformationgiveninthispublication.SquareD,PowerLogic,ION,IONEnterprise,MeterM@il,webmeterandModbusareeithertrademarksorregisteredtrademarksofSchneiderElectricoritsaffiliates.Othermarksusedhereinmaybethepropertyoftheirrespectiveowners.

Software integrationIntegratewithinPowerLogicfacility-levelorenterprise-widepowerandenergymanagementsystems.Real-timedataanddatalogsstoredon-boardcanbeautomaticallyretrievedonascheduledbasisforanalysisatthesystemlevel.CompatiblewithPowerLogicIONEnterpriseandPowerLogicIONSetup.Modbuscompatibilityandregister-basedloggeddatasupportsintegrationanddataaccessbybuildingautomation,SCADAandotherthird-partysystems.

•PowerLogicIONEnterprisesoftware

•IONSetupsoftware

•ModbusMaster

•Internetconnectivity

•XMLcompatibility

Special features – flash-based firmwareFlash-basedfirmwareallowsupgradesviacommunicationswithoutremovingthemeterfromthesite.Simplydownloadthelatestfirmwarefromwww.powerlogic.com.Realtimedata,datalogsandwaveformsstoredonboard.

Safety & Security. Reliability & Productivity. Aesthetics & Comfort. Efficiency & Sustainability.WhateveryourneedSchneiderElectrichasthesolution.TofindgenuineSchneiderElectricandSquareDBrandproducts,gotowww.squared.comtofindyournearestauthorizeddistributororcall1-888-SquareD.

Features and options ION7550 ION7650

MeteringPower,energyanddemand n n

Power qualitySag/swell,harmonicsmonitoring n n

Harmonics:individual,even,odd,upto 63th 63th

Harmonics:magnitude,phaseandinter-harmonics — 50th

Symmetricalcomponents:zero,positive,negative n n

RecordingcompliantwithIEC61000-4-30classAed.2 — n

IEC61000-4-15flicker — n

EN50160compliancechecking — n

Transientdetection,microseconds(20μsfor50Hz,17μsfor60Hz)

— 20/17

Samplingrate,max.samples/cycle 256 1024

Disturbancedirectiondetection n n

Logging and recordingMemorystandard/optional 5MB/10MB 5MB/10MB

Min./max.,historical,waveformlogging n n

Time-stampresolutioninseconds 0.001 0.001

Historicaltrendinformationviafrontpaneldisplay n n

GPStimesynchronization n n

Communications and I/OIEC61850 n n

RS-232/485;RS-485;Ethernet;optical n n

Internalmodem 1 1

3-portDNP3.0viaserial,modem,Ethernet,I/Rports n n

ModbusRTUslave/master;ModbusTCP n n

EtherGate,ModemGate,MeterM@il,WebMeter n n

Analoginputs/outputs(optional) 4/4 4/4

Digitalstatusinputs/outputs 16/4 16/4

Relayoutputs(standard) 3 3

Setpoints, alarming and controlSetpoints,number/min.responsetime 65/½-cyc 65/½-cyc

Math,logic,trig,log,linearizationformulas n n

Call-outonsingleandmulti-conditionalarms n n

Alarmsetpointlearning n nFile#002188