Upload
trandan
View
215
Download
2
Embed Size (px)
Citation preview
Agenda and Objectives
Trane Engineers Newsletter Live Series
Dedicated Outdoor Air Equipment
Previous ENLs have discussed system design and control considerations for dedicated outdoor‐air systems.
This ENL will shift the discussion to the various types of equipment used for dedicated OA conditioning,
from packaged DX units to split DX systems to air handlers and water chillers.
By attending this ENL you will be able to:
1. Summarize the definition of a dedicated OA unit
2. Identify what leaving‐air dew point is required
3. Summarize what the difference between cold versus neutral‐temperature air
4. Identify ASHRAE Standard 90.1 requirements related to dedicated OA systems
5. Identify specific dedicated OA equipment configurations
Agenda
1) Opening (welcome, agenda, introductions)
2) Overview
a) What is a dedicated OA unit?
b) Review content from previous broadcasts
c) Review of ASHRAE 90.1 requirements relates to DOAS
3) Specific dedicated OA equipment configurations
a) Identify the goal(s)/purpose of the dedicated OA unit (
b) Goals = Dehumidify Ventilation Only + Meet ASHRAE 90.1
c) Goals = Dehumidify to Offset Space Latent Loads + Meet ASHRAE 90.1
d) Goals = Dehumidify Ventilation Only + Exceed 90.1 (Higher Efficiency)
e) Goals = Dehumidify to Offset Space Latent Loads + Exceed 90.1 (Higher Efficiency)
a) Cooling/heating sources (list advantages and drawbacks of each)
4) Summary
Agenda_APPCMC043.ai 1 6/12/2014 4:05:42 PM
Presenters
Trane Engineers Newsletter Live Series
Dedicated Outdoor Air Equipment (2011)
Ronnie Moffitt | applications engineer | TraneRonnie joined Trane in 1996 and currently is an airside applications engineer whose responsibility is to aid designengineers and Trane sales personnel in the proper design and application of HVAC systems. His primary focus hasbeen dehumidification and air‐to‐air energy recovery design. This includes the development, design and controloptimization of desiccants in commercial HVAC systems. He has several patents related to this subject and serveson related AHRI and ASHRAE engineering committees.Ronnie led the development of the Trane CDQ system, a winner of the R&D 100 Award for The MostTechnologically Significant New Products of 2005. He is a certified Energy Manager (CEM) by Association of EnergyEngineers and received his B.S. in Aerospace Engineering from Syracuse University.
John Murphy | applications engineer | TraneJohn has been with Trane since 1993. His primary responsibility as an applications engineer is to aid designengineers and Trane sales personnel in the proper design and application of HVAC systems. As a LEED AccreditedProfessional, he has helped our customers and local offices on a wide range of LEED projects. His main areas ofexpertise include energy efficiency, dehumidification, dedicated outdoor‐air systems, air‐to‐air energy recovery,psychrometry, and ventilation.
John is the author of numerous Trane application manuals and Engineers Newsletters, and is a frequent presenteron Trane’s Engineers Newsletter Live series of broadcasts. He also is a member of ASHRAE, has authored severalarticles for the ASHRAE Journal, and is a member of ASHRAE’s “Moisture Management in Buildings” and“Mechanical Dehumidifiers” technical committees. He was a contributing author of the Advanced Energy DesignGuide for K‐12 Schools and the Advanced Energy Design Guide for Small Hospitals and Health Care Facilities, andtechnical reviewer for The ASHRAE Guide for Buildings in Hot and Humid Climates.
Paul Solberg | applications engineer | TraneA mechanical engineer from the University of Wisconsin at Platteville, Paul is a 35‐year veteran of Trane. Hespecializes in compressor and refrigeration systems, and has authored numerous Trane publications on thesesubjects, including application manuals, engineering bulletins, and Engineers Newsletters. Paul served in thetechnical service and applications engineering areas at various manufacturing locations, where he developedparticular expertise supporting split systems, small packaged chillers, rooftop air conditioners, and other unitaryproducts.
Biographies_APPCMC043.ai 1 6/12/2014 4:06:26 PM
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 1
Dedicated Outdoor-Air Equipment
Ingersoll Rand
© 2011 Trane, a business of Ingersoll-Rand2
Dedicated Outdoor-Air Equipment
1.5
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 2
“Trane” is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members Certificates ofreported to CES Records for AIA members. Certificates of Completion for non-AIA members available on request.
This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product.Questions related to specific materials,
© 2011 Trane, a business of Ingersoll-Rand3
methods, and services will be addressedat the conclusion of this presentation.
Copyrighted Materials
This presentation is protected by U.S. and international i h l R d i di ib i di l d fcopyright laws. Reproduction, distribution, display, and use of
the presentation without written permission of Trane is prohibited.
© 2011 Trane, a business of Ingersoll-Rand. All rights reserved.
© 2011 Trane, a business of Ingersoll-Rand4
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 3
Learning Objectives
Summarize the definition of a dedicated OA unit
Identify what leaving-air dew point is required
Summarize what the difference between cold versus neutral-temperature air
Identify ASHRAE Standard 90.1 requirements related to dedicated OA systems
Identifyspecific dedicated OA equipment configurations
© 2011 Trane, a business of Ingersoll-Rand5
Identify specific dedicated OA equipment configurations
Dedicated Outdoor-Air Equipment
Today’s Topics
Definition of a dedicated OA unit• What leaving-air dew point is required?
• Cold versus neutral-temperature air?
ASHRAE 90.1 requirements related todedicated OA systems
Specific dedicated OA equipment configurations
© 2011 Trane, a business of Ingersoll-Rand6
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 4
Today’s Presenters
© 2011 Trane, a business of Ingersoll-Rand7
Ronnie Moffitt
ApplicationsEngineer
John Murphy
Applications Engineer
Paul Solberg
ApplicationsEngineer
Dedicated Outdoor-Air Equipment
Definition of a Dedicated OA Unit
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 5
What is a Dedicated OA Unit?
AHRI Standard 920 (currently in development)
A dedicated OA unit “operate[s] in combination with aA dedicated OA unit operate[s] in combination with a separate sensible cooling system to satisfy the entire building humidity load. The system is sized to maintain a prescribed ventilation rate under any load condition. The ventilation rate can be constant or varied based on the building operation or occupancy schedule or in response to the actual occupancy. It may pre-condition outdoor airby containing an enthalpy wheel, sensible wheel, desiccant wheel, plate heat exchanger, heat pipes or other heat or
© 2011 Trane, a business of Ingersoll-Rand9
, p g , p pmass transfer apparatus. It may reheat the ventilation air by containing a reheat refrigerant circuit, sensible wheel, heat pipe, or other heat or mass transfer apparatus.”
Satisfies entire building humidity (latent) load
May reheat dehumidified ventilation air
May pre-condition outdoor air using
air-to-air energy recovery
dedicatedOA unit
CA
CA CA
EA
OA
Delivers prescribed (typically minimum)
ventilation rate
© 2011 Trane, a business of Ingersoll-Rand10
RA
Operates in combination with a separate sensible cooling/heating system
SA SA
RA
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 6
Dedicated OA Systems
What leaving-air dew point is required?• Cooled, but not dehumidified
• Cooled and dehumidified
© 2011 Trane, a business of Ingersoll-Rand11
180
16080
OA 95°F DB
example: kitchen
Cooled But Not Dehumidified
80
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry a
80
70
50
60
78°F WB
CA 70°F DB67°F DPT
CACA
80°F DB60% RH65°F DPT
50
55
60
65
70
75
80
dew
po
int tem
peratu
re, °F
OAOAOAOAspace
spacespacespacespace
© 2011 Trane, a business of Ingersoll-Rand12
40
20
air
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40
50
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 7
180
16080
OA
example: fan-coils, VAV, WSHPs, VRF
Cooled and Dehumidified
8095°F DB
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry a
80
70
50
60
CA 52°F DB52°F DPT
75°F DB60% RH61°F DPT
50
55
60
65
70
75
80
dew
po
int tem
peratu
re, °F
dry enough toremove spacelatent load
dry enough toremove spacelatent load
worst-caseupper limit
78°F WB
OAOAOAOAspace
spacespacespacespace
© 2011 Trane, a business of Ingersoll-Rand13
40
20
air
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30
CACA
30
40
50latent loadlatent load
What Leaving-AirDew Point is Required? “Dedicated Outdoor-Air Ventilation
Systems” Engineers Newsletter Livebroadcast APP CMC008 EN (2001)broadcast, APP-CMC008-EN (2001)
"Designing Dedicated Outdoor-Air Systems," Trane application guideSYS-APG001-EN (2003)
"Dedicated Ventilation Systems," Engineers Newsletter 30-3 (2001)
Morris, W. 2003. “The ABCs of DOAS: Dedicated Outdoor Air Systems.”
© 2011 Trane, a business of Ingersoll-Rand14
ASHRAE Journal (May)
Murphy, J. 2006. “Smart Dedicated Outdoor Air Systems.” ASHRAE Journal (July)
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 8
180
16080
OA
example: chilled beams, radiant cooling
Cooled and Over-Dehumidified
8095°F DB
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry a
80
70
50
60
CA 55°F DB45°F DPT
space 75°F DB50% RH55°F DPT
spacespacespacespace50
55
60
65
70
75
80
dew
po
int tem
peratu
re, °F
to preventcondensation
dry enough todry enough to
78°F WB
OAOAOAOA
© 2011 Trane, a business of Ingersoll-Rand15
40
20
air
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 CACA30
40
50y gremove spacelatent load
y gremove spacelatent load
Dedicated OA Systems
What leaving-air dew point is required?
Cold versus neutral-temperature air?
© 2011 Trane, a business of Ingersoll-Rand16
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 9
180
16080
OA 95°F DB78°F WB
CA 71°F DB52°F DPT
80
dedicated OA system(“neutral” air)
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry a
80
70
50
60
OAOAOAOA
(450 cfm)
RA 74°F DB50% RH55°F DPT
RARARARA50
55
60
65
70
75
80
dew
po
int tem
peratu
re, °F
SA 55°F DB(1380 cfm)
SASA
local unit:
local unit
© 2011 Trane, a business of Ingersoll-Rand17
40
20
air
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30
CACA
30
40
50local unit:1380 cfm2.4 tons
180
16080 80
dedicated OA system(“neutral” air)
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry a
80
70
50
60
CACA50
55
60
65
70
75
80
dew
po
int tem
peratu
re, °F
sensible cooling
deh
um
idificat
OAOAOAOA
spacespacespacespace
© 2011 Trane, a business of Ingersoll-Rand18
40
20
air
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40
50
wasted cooling energy
tion
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 10
180
16080
OA 95°F DB78°F WB
CA 52°F DB52°F DPT
80
dedicated OA system(“cold” air)
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry a
80
70
50
60
(450 cfm)
RA 74°F DB50% RH55°F DPT
RARARARA50
55
60
65
70
75
80
dew
po
int tem
peratu
re, °F
SA 55°F DB(930 cfm)
SASA local unit:
local unit
OAOAOAOA
© 2011 Trane, a business of Ingersoll-Rand19
40
20
air
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30
CACA
30
40
50SASA local unit:930 cfm1.6 tons
CA
930 cfm at 55°F
450 cfm at 52°F
cold-airsystem
SA
1380 cfmRA
CA
CA
1380 cfm at 55°F
450 cfm at 71°Fneutral-airsystem
© 2011 Trane, a business of Ingersoll-Rand20
1830 cfmRA
CA SA
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 11
Cold versus Neutral
Less overall cooling capacity• Sensible cooling provided by cold conditioned OA
reduces required cooling capacity of local HVAC units
• Cooling (dehumidification) capacity of the dedicated OA unit is the same in either case
Less overall cooling energy• Sensible cooling provided by cold conditioned OA
d li i d f l l HVAC it
© 2011 Trane, a business of Ingersoll-Rand21
reduces cooling required from local HVAC units
Cold versus Neutral
cold tospace
neutral tospace/unit
cold tolocal unit
dedicated OA unitcooling capacity, tons 3.4 3.4 3.4
reheat capacity, MBh 9.3 0 0
fan airflow, cfm 450 450 450
local HVAC unit
© 2011 Trane, a business of Ingersoll-Rand22
cooling capacity, tons 2.4 1.6 1.6
fan airflow, cfm 1380 930 1380
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 12
Cold versus Neutral
Less overall fan energy, if OA is delivered cold ( l) di tl t(or cool) directly to spaces
• Cold conditioned OA removes some of the space sensible cooling load, which reduces the airflow needed from local HVAC units
• Airflow delivered by the dedicated OA unit is the same in either case
© 2011 Trane, a business of Ingersoll-Rand23
Won’t Delivering OA Cold Overcool the Space?
Qs,space = 29,750 Btu/h (design load)s,space
Qs,ca = 1.085 450 cfm (74°F – 52°F)
= 10,740 Btu/h
Space sensible cooling loadt b < 36% f d i
© 2011 Trane, a business of Ingersoll-Rand24
must be < 36% of designbefore overcooling will occur!
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 13
When Should I Reheat Dehumidified OA?
Applications where space sensible cooling loads differ tl t i ti ( h t l d it i )greatly at any given time (e.g., hotels, dormitories)
To avoid overcooling at part-load conditions• Implement demand-controlled ventilation to reduce
outdoor airflow as population changes
• Activate heat in the local HVAC unit (few zones, WSHP)
• Reheat dehumidified air in dedicated OA unit
© 2011 Trane, a business of Ingersoll-Rand25
(consider using recovery energy)
Reheating Dehumidified OA
TT
BAS
dedicatedOA unit
CA
CA CA
EA
OATT
© 2011 Trane, a business of Ingersoll-Rand26
RA
SA SA
RA
local HVAC units
TT TT
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 14
When Should I Reheat Dehumidified OA?
Applications where space sensible cooling loads differ tl t i ti ( h t l d it i )greatly at any given time (e.g., hotels, dormitories)
To avoid overcooling at part-load conditions• Implement demand-controlled ventilation
• Activate heat in the local HVAC unit
• Reheat dehumidified air in dedicated OA unit
Applications requiring lower-than-normal dew points
© 2011 Trane, a business of Ingersoll-Rand27
pp q g p
To avoid condensation when conditioned OA is delivered to the ceiling plenum
Dedicated OA Systems
What leaving-air dew point is required?
Cold versus neutral-temperature air?
How will conditioned OA be delivered to spaces?• Directly to each space
• To intake of each local unit
• To supply-side of each local unit
• To ceiling plenum, near each local unit
© 2011 Trane, a business of Ingersoll-Rand28
To ceiling plenum, near each local unit
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 15
Dedicated Outdoor-Air Equipment
ASHRAE 90.1-2010Requirements
ASHRAE 90.1 and Dedicated OA Systems
Minimum equipment efficiencies
Fan power limitation
Economizer
Exhaust-air energy recovery
Limitation on simultaneousheating and cooling
© 2011 Trane, a business of Ingersoll-Rand30
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 16
Section 6.4.1, mandatory requirements
Minimum Equipment Efficiencies
Currently there is no rating or certification standard f DX d di t d OA i t ASHRAE 90 1 dfor DX dedicated OA equipment, so ASHRAE 90.1 does not list a minimum efficiency requirement
AHRI Standard 920 isunder development
“6.4.1.3 Equipment Not Listed. Equipment not listed in the tables referenced in Sections 6.4.1.1 and 6.4.1.2 may be used.”
© 2011 Trane, a business of Ingersoll-Rand31
AHRI Standard 920 is under development
Section 6.5.3.1, prescriptive requirements
Fan Power Limitation
What is a “fan system”?
“fan system bhp: the sum of the fan brake horsepower (bhp) of all fans that are required to operate at fan system design conditions to supply air from the heating or cooling source to the conditioned space(s) and return it to the source or exhaust it to the outdoors” (Section 3.2)
© 2011 Trane, a business of Ingersoll-Rand32
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 17
example 6-DDD
User’s Manual for 90.1-2010
QUESTION: A wing of an elementary school building is served by eight WSHPs each equipped with a ¾-hp fan motor andserving aeight WSHPs, each equipped with a ¾ hp fan motor and serving a single classroom. Ventilation air is supplied directly to each classroom by a dedicated outdoor-air system. Each classroom requires 500 cfm of outdoor air, so the DOAS delivers the total of 4000 cfm of conditioned outdoor air using a 5-hp fan. Does this system need to comply with section 6.5.3.1?
ANSWER: Each WSHP is a separate fan system because each
© 2011 Trane, a business of Ingersoll-Rand33
ANSWER: Each WSHP is a separate fan system because each has a separate cooling and heating source. The power of the DOAS fan must be allocated to each heat pump on a cfm-weighted basis.
example 6-DDD
User’s Manual for 90.1-2010
© 2011 Trane, a business of Ingersoll-Rand34
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 18
Section 6.5.3.1, prescriptive requirements
Fan Power Limitation
Only applies to fan systems > 5 hp
Each fan system shall not exceed:• Option 1: fan system motor nameplate hp
• Option 2: fan system bhp
Exceptions:a. Health and safety (systems maintaining
space-to-space pressure differences)
© 2011 Trane, a business of Ingersoll-Rand35
p p p )
b. Individual exhaust fans ≤ 1 hp
Section 6.5.1, prescriptive requirements
Economizers
“6.5.1 Economizers. Each cooling system that has a fan shall include either an air or water economizer meeting
Most notable exceptions:a. Cooling capacity < 54,000 Btu/hr (4.5 tons)
b. Systems that use non-particulate air treatment
d. Systems with condenser heat recovery
shall include either an air or water economizer meeting the requirements of Sections 6.5.1.1 through 6.5.1.4.”
© 2011 Trane, a business of Ingersoll-Rand36
e. Residential with cooling capacity < 270,000 Btu/hr
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 19
If an Economizer is Required…
Oversize the dedicated OA system to “provide up to 100% f d i l i tit i f li ”100% of design supply air quantity air for cooling”
Include a second OA intake (path) for airside economizing
Waterside economizing• Fan-coils, radiant cooling
Comply using Energy Cost Budget (Section 10) method,
© 2011 Trane, a business of Ingersoll-Rand37
p y g gy g ( ) ,rather than prescriptive requirements
Section 6.5.6.1, prescriptive requirements
Exhaust-Air Energy Recovery
For dedicated (100%) OA systems, exhaust-air energy i i d ( ll ) t frecovery is required on more (smaller) systems for many
climate zones.
© 2011 Trane, a business of Ingersoll-Rand38
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 20
Section 6.5.6.1, prescriptive requirements
Exhaust-Air Energy Recovery
“…at least 50% energy recovery effectiveness. Fifty percent energy recovery effectiveness shall mean a
RARA75°F DB63°F WB
Be careful of this term!
Fifty percent energy recovery effectiveness shall mean a change in the enthalpy of the outdoor air supply equal to 50% of the difference between the outdoor air and return air enthalpies at design conditions.”
© 2011 Trane, a business of Ingersoll-Rand39
OAOA95°F DB78°F WB41.3 Btu/lb
28.5 Btu/lb
hleaving ≤ 34.9 Btu/lb
= (h1 – h2)ṁOA
ASHRAE Standard 84 and AHRI Standard 1060
Effectiveness
“total energy exchange rate”T = (h1 – h3)ṁmin
h3h4
ṁEA
“maximum energy exchange rate”
© 2011 Trane, a business of Ingersoll-Rand40
h1 h2
ṁOA
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 21
50% = (41.3 – h2)10,000 cfm
different definitions of effectiveness
Example of Unbalanced Airflows (ṁEA < ṁOA)
h2 = 36.2 Btu/lb50% (41.3 – 28.5)8,000 cfm
h4 h3 = 28.5 Btu/lb
8,000 cfm
h2 36.2 Btu/lb
Does not meet ASHRAE 90.1
© 2011 Trane, a business of Ingersoll-Rand41
10,000 cfm
h1 = 41.3 Btu/lb h2 ≤ 34.9 Btu/lb to meet ASHRAE 90.1
“As-Applied” vs. “Rated” Effectiveness
Be careful not to confuse “as-applied” effectiveness ( i d b ASHRAE 90 1) ith “ t d” ff ti(required by ASHRAE 90.1) with “rated” effectiveness per AHRI 1060
Strive for balanced airflows• Bring back as much exhaust air as possible
© 2011 Trane, a business of Ingersoll-Rand42
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 22
exhaust-air energy recovery
Using Restroom Exhaust
© 2011 Trane, a business of Ingersoll-Rand43
ASHRAE 62.1-2010
Recirculation of Restroom Exhaust
“5.16.3.2.5. Class 2 air [which includes restrooms] shall not be recirculated or transferred to Class 1 spaces
EAEAV4V4 V3V3
recirculated or transferred to Class 1 spaces.
Exception: When using an energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device is permitted. Recirculated Class 2 air shall not exceed 10% of the outdoor air intake flow.”
© 2011 Trane, a business of Ingersoll-Rand44
OAOA
EAEA
V1V1 V2V2
V3-to-2V3-to-2
EATR ≤ 10%
Exhaust Air Transfer Ratio is defined byASHRAE Standard 84 and certified byAHRI Standard 1060
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 23
Section 6.5.2, prescriptive requirements
Simultaneous Heating and Cooling
“6.5.2.3 Dehumidification. Where humidistatic controls are provided such controls shall prevent reheatingare provided, such controls shall prevent reheating, mixing of hot and cold airstreams, or other means of simultaneous heating and cooling of the same airstream.”
Exception A:“The system is capable of reducing supply air volume to 50% or less of the design airflow rate or the minimum outdoor air ventilation rate specified in ASHRAE Standard 62.1 …
© 2011 Trane, a business of Ingersoll-Rand45
See example 6-TT, User’s Manual for 90.1-2010
pwhichever is larger, before simultaneous heating and cooling takes place.”
Dedicated Outdoor-Air Equipment
Specific Dedicated OA Equipment Configurations
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 24
dedicated outdoor-air equipment
Which Configuration is Best?
1) Dehumidification Duty
2) Cooling Duty
3) Efficiency Target
4) Cooling Source
© 2011 Trane, a business of Ingersoll-Rand47
2) Cooling Duty 4) Cooling Source
What is the Dehumidification Duty?1
infiltration
people
permeanceventilation
space (indoor)
© 2011 Trane, a business of Ingersoll-Rand48
p ( )latent loads
typical latent loadsfor a school classroom
source: Humidity Control Design Guide, ASHRAE © 2001, p. 278
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 25
what is the dehumidification duty?
Dehumidify Ventilation Air Only
spacededicatedOA unit
CA
CA CA
EA
OAspacelatent loads
ventilationlatent load
• Dedicated OA unit removes latent load due to ventilation
• Space latent loads must be removed by local units (any space dehumidification is coincidental)
© 2011 Trane, a business of Ingersoll-Rand49
RA
SA SA
RA
localHVAC unit
dehumidification is coincidental)
180
160 h80
Dehumidify Ventilation Air Only
80
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
50
55
60
65
70
75
80
dew
po
int tem
peratu
re, °F
60% RH = 6060% RH = 60°°F DPTF DPT60% RH = 6060% RH = 60°°F DPTF DPT
50% RH = 5550% RH = 55°°F DPTF DPT50% RH = 5550% RH = 55°°F DPTF DPTDedicated OA unit delivers air
© 2011 Trane, a business of Ingersoll-Rand50
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
3030
40
50 F
at a dew point close to desired space condition (does not remove any space latent loads)
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 26
what is the dehumidification duty?
Dehumidify the Space (for Comfort)
spacededicatedOA unit
CA
CA CA
EA
OAspacelatent loads
ventilationlatent load
• Dedicated OA unit removes both ventilation and space latent loads (controls space humidity)
• Local HVAC units need only remove space sensible loads
© 2011 Trane, a business of Ingersoll-Rand51
RA
SA SA
RA
localHVAC unit
remove space sensible loads
dehumidify the space (for comfort)
What Leaving-Air Dew Point is Required?
55
Assumptions:• 200 Btu/h/person latent load• 75°Fspace temperature
eavi
ng
-air
dew
po
int,
°F
50
45
40
35
30
• 75 F space temperature
© 2011 Trane, a business of Ingersoll-Rand52
8 10 126 181614
outdoor airflow, cfm/person
le
25
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 27
dehumidify the space (for comfort)
What Leaving-Air Dew Point is Required?
55
Assumptions:• 200 Btu/h/person latent load• 75°Fspace temperature
eavi
ng
-air
dew
po
int,
°F
50
45
40
35
30
• 75 F space temperature
office
© 2011 Trane, a business of Ingersoll-Rand53
8 10 126 181614
outdoor airflow, cfm/person
le
25 lecturehall
K-12classroom
180
160 h80
Dehumidify to Space (for Comfort)
80
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
50
55
60
65
70
75
80
dew
po
int tem
peratu
re, °F
desired space conditiondesired space conditiondesired space conditiondesired space condition
Dedicated OA unit delivers air at a dew
© 2011 Trane, a business of Ingersoll-Rand54
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
3030
40
50 F
Dedicated OA unit delivers air at a dew point drier than desired space condition (removes all space latent loads)
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 28
what is the dehumidification duty?
Dehumidify the Space (for Condensation)
spacededicatedOA unit
CA
CA CA
EA
OAspacelatent loads
ventilationlatent load
radiantcooling
• Dedicated OA unit removes both ventilation and space latent loads (leaving-air DPT low enough to prevent condensation on local units)
• Local HVAC units only remove
© 2011 Trane, a business of Ingersoll-Rand55
gpanels • Local HVAC units only remove
space sensible loads
180
160 h80
Dehumidify the Space (for Condensation)
80
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
50
55
60
65
70
75
80
dew
po
int tem
peratu
re, °F
Dedicated OA unit delivers air at a dew point
desired space conditiondesired space conditiondesired space conditiondesired space condition
© 2011 Trane, a business of Ingersoll-Rand56
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
3030
40
50 F
Dedicated OA unit delivers air at a dew point low enough to prevent condensation on local cooling equipment
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 29
dedicated outdoor-air equipment
What is the Dehumidification Duty?1
1) Dehumidification Duty• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)
© 2011 Trane, a business of Ingersoll-Rand57
2 What is the Cooling Duty?
Neutral air• Remove the sensible ventilation load only
Cool air• Trim some of the space sensible cooling load
Cold air• Remove as much of the space sensible cooling
load as possible
© 2011 Trane, a business of Ingersoll-Rand58
p
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 30
what is the cooling duty?
Neutral AirdedicatedOA unit Dedicated OA unit delivers
air at dry bulb temperature
CA
CA CA
EA
OAair at dry-bulb temperature close to desired space condition
• Does not remove any space sensible loads
Space sensible loads must be removed by local cooling
© 2011 Trane, a business of Ingersoll-Rand59
localHVAC unit
RA
SA SA
RARA
SA SA
RA
y gequipment
what is the cooling duty?
Cold Air
Dedicated OA unit delivers air at dry bulb temperature
dedicatedOA unit
air at dry-bulb temperature cooler than the space
• Removes some of the space sensible loads
Remainder of space sensible loads removed by local cooling equipment
CA
CA CA
EA
OA
© 2011 Trane, a business of Ingersoll-Rand60
y g q p
RA
SA SA
RA
localHVAC unit
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 31
what is the cooling duty?
Cool AirdedicatedOA unit Dedicated OA unit delivers
air at dry bulb temperature
CA
SA SA
EA
OA
localHVAC unit
RA
CA CA
RA
air at dry-bulb temperature cooler than the space
• Air is reheated some before delivery
• Removes some of the space sensible loads
Remainder ofspacesensible
© 2011 Trane, a business of Ingersoll-Rand61
Remainder of space sensible loads removed by local cooling equipment
dedicated outdoor-air equipment
What is the Cooling Duty?2
1) Dehumidification Duty• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)
2) Cooling Duty• Neutral air
© 2011 Trane, a business of Ingersoll-Rand62
Neutral air• Cool air• Cold air
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 32
3 What is the Efficiency Target?
Code or ASHRAE 90.1 minimum• Meet the minimum requirements of the local energy
code or ASHRAE Standard 90.1
Higher level of efficiency• More efficient than the minimum requirements
© 2011 Trane, a business of Ingersoll-Rand63
What is the Cooling Source?
Shared chiller plant
4
• Chiller plant that serves both thededicated outdoor-air equipmentand the local cooling equipment
Dedicated chiller• Chiller that serves only the
dedicated outdoor-air equipment
Di t i (DX) it
air-cooledchiller
© 2011 Trane, a business of Ingersoll-Rand64
Direct expansion (DX) unit• Packaged or split
• Air-cooled or water-cooled packaged DXdedicated OA unit
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 33
many combinations … no silver bullet!
Financial Constraints?
1) Dehumidification Duty• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)
2) Cooling Duty• Neutral air
3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency
4) Cooling Source• Shared chiller plant
$
© 2011 Trane, a business of Ingersoll-Rand65
Neutral air• Cool air• Cold air
p• Dedicated chiller• Direct expansion (DX)
1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)
2) Cooling Duty• Neutral air• Cool air• Cold air
3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency
4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)
© 2011 Trane, a business of Ingersoll-Rand66
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 34
energy wheel + cooling coil
Dehumidify Ventilation Only (Cold Air)
EA'
total-energycooling
OA'CC57 F
© 2011 Trane, a business of Ingersoll-Rand67
75 F DB55% RH
EA OACA
total energywheel
coolingcoil
95 F DB78 F WB
72 F DPT
59 F DB57 F DPT
180
160 h80
OA 95°F DB72°F DPT
CC 57°F DB
energy wheel + cooling coilDehumidify Ventilation Only (Cold Air)
80
OA' 81°F DB63°F DPT
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
OAOAOAOA
CC 57 F DB57°F DPT
75°F DB55% RH57°F DPT
50
55
60
65
70
75
dew
po
int tem
peratu
re, °F
EA
OA'OA'OA'OA'
CACA EAEAnot dry enoughto remove spacel t t l d
not dry enoughto remove spacel t t l d
CA 59°F DB57°F DPT
CCCC
© 2011 Trane, a business of Ingersoll-Rand68
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40latent loadlatent load
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 35
180
160 h80
OA 95°F DB72°F DPT
energy wheel + cooling coilDehumidify Ventilation Only (Cold Air)
80
OA' 81°F DB67°F DPT
CC 57°F DB140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
OAOAOAOA
50
55
60
65
70
75
dew
po
int tem
peratu
re, °F
space latent loadspace latent load
OA'OA'OA'OA'
EAEA
CC 57 F DB57°F DPT
75°F DB71% RH65°F DPT
EA
CA 59°F DB57°F DPT
CACACCCC
© 2011 Trane, a business of Ingersoll-Rand69
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40
1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)
2) Cooling Duty• Neutral air• Cool air• Cold air
3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency
4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)
© 2011 Trane, a business of Ingersoll-Rand70
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 36
energy wheel + cooling coil
Dehumidify Space (Cold Air)
EA'
total-energycooling
OA'CC46 F
© 2011 Trane, a business of Ingersoll-Rand71
75 F DB55% RH
EA OA
total energywheel
coolingcoil
95 F DB78 F WB
72 F DPT
CA48 F DB46 F DPT
180
160 h80
OA 95°F DB72°F DPT
energy wheel + cooling coilDehumidify Space (Cold Air)
80
OA' 81°F DB63°F DPT
CC 46°F DB140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
OAOAOAOA
50
55
60
65
70
75
dew
po
int tem
peratu
re, °F
OA'OA'OA'OA'
EAEA space latent loadspace latent load
CC 46 F DB46°F DPT
75°F DB55% RH57°F DPT
EA
CA 48°F DB46°F DPT
CCCC
© 2011 Trane, a business of Ingersoll-Rand72
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACA
CCCC
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 37
energy wheel + cooling coil
Dehumidify Space (Cool Air)
EA'
total-energycooling
OA'
heating
CC46 F
© 2011 Trane, a business of Ingersoll-Rand73
75 F DB55% RH
EA
95 F DB78 F WB
72 F DPT
OA58 F DB46 F DPT
CA
total energywheel
coolingcoil
heatingcoil
180
160 h80
OA 95°F DB72°F DPT
energy wheel + cooling coilDehumidify Space (Cool Air)
80
OA' 81°F DB63°F DPT
CC 46°F DB140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
OAOAOAOA
50
55
60
65
70
75
dew
po
int tem
peratu
re, °F
OA'OA'OA'OA'
EAEA space latent loadspace latent load
CC 46 F DB46°F DPT
75°F DB55% RH57°F DPT
EA
CA 58°F DB46°F DPT
CCCC
© 2011 Trane, a business of Ingersoll-Rand74
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACA
CCCC
reheatreheat
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 38
“In humid climates,seriously consider providing
Consider Unoccupied Humidity Control
In humid climates, seriously consider providing dehumidification during the summer, even if schoolis unoccupied, to prevent mold and mildew.”
Chapter 7 (p. 7.3), 2011 ASHRAE Handbook—HVAC Applications
© 2011 Trane, a business of Ingersoll-Rand75
energy wheel + cooling coil
Dehumidify Space (Unoccupied Mode)
total-energycoolingreheat OA dampers
CC
© 2011 Trane, a business of Ingersoll-Rand76
RACA
total energywheel
coolingcoil
reheatcoil
OA dampersclosed
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 39
180
160 h80
OA 95°F DB72°F DPT
energy wheel + cooling coilDehumidify Space (Cool Air)
80
OA' 81°F DB63°F DPT
CC 46°F DB140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
OAOAOAOA
50
55
60
65
70
75
dew
po
int tem
peratu
re, °F
OA'OA'OA'OA'
EAEA space latent loadspace latent load
CC 46 F DB46°F DPT
75°F DB55% RH57°F DPT
EA
CA 58°F DB46°F DPT
CCCC
© 2011 Trane, a business of Ingersoll-Rand77
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACA
CCCC
reheat = cooling energy wastedreheat = cooling energy wasted
series air-to-air HX (with bypass) + cooling coil
Dehumidify Space (Cool Air)
95 F DB78 F WB
72 F DPT
OA
CA
coolingil
OA'
heatingil
CC
air-to-airHX
46 F
© 2011 Trane, a business of Ingersoll-Rand78
CAcoilcoil
58 F DB46 F DPT
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 40
180
160 h80
OA 95°F DB72°F DPT
series air-to-air HX + cooling coilDehumidify Space (Cool Air)
80
OA' 88°F DB70°F DPT
CC 46°F DB 75% b passes75% b passes140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
50
55
60
65
dew
po
int tem
peratu
re, °F
OA'OA'OA'OA'
CACA
CC 46 F DB46°F DPT
CA 58°F DB46°F DPT
CCCC
25% passesthrough HX25% passesthrough HX
75% bypassesaround HX
75% bypassesaround HX
pre-cooling
OAOAOAOA
70
75
© 2011 Trane, a business of Ingersoll-Rand79
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACACCCC
recovered reheat energy
Series Air-to-Air Devices (Cool Air)
sensible pressure drop OA temp below whicheffectiveness (per pass) reheat is required*
heat pipe 40% 0.5 in. H2O 76°F
coil loop 50% 0.5 in. H2O 70°F
fixed-plate HX 65% 0.5 in. H2O 64°F
* to achieve 58°F leaving dry-bulb temperature with 46°F dew point
© 2011 Trane, a business of Ingersoll-Rand80
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 41
OA
OA46 F 46 F58 F 58 F
series HX + cooling coil• 13% less cooling capacity• 12 F less reheat
cooling coil + reheat (cool air)• Delivering conditioned OA at
same dew point and dry bulb
CA58 F DB46 F DPT
CA58 F DB46 F DPT
© 2011 Trane, a business of Ingersoll-Rand81
58 F DB46 F DPT
48 F DB46 F DPT
series HX + cooling coil• Dedicated OA unit
• 13% lesscooling capacity
cooling coil + reheat (cold air)• Dedicated OA unit
• 13% more cooling capacity
© 2011 Trane, a business of Ingersoll-Rand82
13% less cooling capacity• 12°F less reheat
• Local HVAC equipment• 13% more cooling capacity• 13% more airflow
13% more cooling capacity
• Local HVAC equipment• 13% less cooling capacity• 13% less airflow
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 42
1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)
2) Cooling Duty• Neutral air• Cool air• Cold air
3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency
4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)
© 2011 Trane, a business of Ingersoll-Rand83
series air-to-air HX (without bypass) + cooling coil
Dehumidify Space (Neutral Air)
95 F DB78 F WB
72 F DPT
OA
CA
coolingil
OA'
heatingil
CC
air-to-airHX
80 F
46 F
© 2011 Trane, a business of Ingersoll-Rand84
CAcoilcoil
80 F DB46 F DPT
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 43
180
160 h80
OA 95°F DB72°F DPT
series air-to-air HX + cooling coilDehumidify Space (Neutral Air)
80
OA' 71°F DB69°F DPT
CC 46°F DB140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
50
55
60
65
dew
po
int tem
peratu
re, °F
OA'OA'OA'OA'
CACA
CC 46 F DB46°F DPT
CA 80°F DB46°F DPT
CCCC
pre-cooling
OAOAOAOA
70
75
© 2011 Trane, a business of Ingersoll-Rand85
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACACCCC
recovered reheat energy
Series Air-to-Air Devices (Neutral Air)
sensible pressure drop OA temp below whicheffectiveness (per pass) reheat is required*
heat pipe 40% 0.5 in. H2O 118°F
coil loop 50% 0.5 in. H2O 100°F
fixed-plate HX 65% 0.5 in. H2O 90°F
* to achieve 75°F leaving dry-bulb temperature with 46°F dew point
© 2011 Trane, a business of Ingersoll-Rand86
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 44
Parallel or Series?
energy wheel + cooling coil(parallel)• Exhaust air is available
for recovery• Deliver air at a cool (or cold)
series HX + cooling coil (series)• Exhaust air NOT available
for recovery• Deliver air at a neutral
© 2011 Trane, a business of Ingersoll-Rand87
Deliver air at a cool (or cold) temperature
• Recoverable reheat (if needed) energy is available
temperature• Recoverable reheat
energy is NOT available
1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)
2) Cooling Duty• Neutral air• Cool air• Cold air
3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency
4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)
© 2011 Trane, a business of Ingersoll-Rand88
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 45
series desiccant wheel + cooling coil
Dehumidify Space (Cool Air)heatingcoil
95 F DB78 F WB
72 F DPT
OA CC
coolingil
OA'
seriesd i t
52 F
© 2011 Trane, a business of Ingersoll-Rand89
coildesiccantwheel
CA58 F DB46 F DPT
180
160 h80
OA 95°F DB72°F DPT
series desiccant wheel + cooling coilDehumidify Space (Cool Air)
80
OA' 89°F DB75°F DPT
CC 52°F DB140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
50
55
60
65
dew
po
int tem
peratu
re, °F
OA'OA'OA'OA'
CACA
CC 52 F DB52°F DPT
CA 58°F DB46°F DPT
CCCC
OAOAOAOA
70
75
© 2011 Trane, a business of Ingersoll-Rand90
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACA
cooling energy saved
reheat energy saved
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 46
1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)
2) Cooling Duty• Neutral air• Cool air• Cold air
3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency
4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)
© 2011 Trane, a business of Ingersoll-Rand91
series desiccant wheel + cooling coil
Dehumidify Space (Neutral Air)heatingcoil
95 F DB78 F WB
72 F DPT
OA CC
coolingil
OA'
reheatil
seriesd i t
© 2011 Trane, a business of Ingersoll-Rand92
CA
coil
75 F DB46 F DPT
coil desiccantwheel
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 47
Parallel or Series?
energy wheel + cooling coil(parallel)• Exhaust air is available
for recovery• Deliver air at a cool (or cold)
series desiccant + cooling coil (series)• Required leaving-air
DPT < CHW temp + 5 F• Deliver air at a cool
© 2011 Trane, a business of Ingersoll-Rand93
temperature• Recoverable reheat (if needed)
energy is available
temperature• Recoverable reheat
energy is NOT available
1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)
2) Cooling Duty• Neutral air• Cool air• Cold air
3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency
4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)
© 2011 Trane, a business of Ingersoll-Rand94
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 48
total-energy wheel + cooling coil + coil loop
Dehumidify Space (Cool Air)
CC
cooling
OA'
coil total-energy
EA''
46 F
EA'
© 2011 Trane, a business of Ingersoll-Rand95
95 F DB78 F WB
72 F DPT
OAg
coilloopgy
wheelCA58 F DB46 F DPT
75 F DB55% RH
EA
180
160 h80
OA 95°F DB72°F DPT
energy wheel + cooling coil + coil loopDehumidify Space (Cool Air)
80
OA' 75°F DB62°F DPT
CC 46°F DB46°F DPT
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
OAOAOAOA
50
55
60
65
70
75
dew
po
int tem
peratu
re, °F
OA'OA'OA'OA'
EAEA
75°F DB55% RH57°F DPT
EA
CA 58°F DB46°F DPT
CCCCEA'EA'
EA' 63°F DB57°F DPT
© 2011 Trane, a business of Ingersoll-Rand96
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACA
CCCC
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 49
total-energy wheel + cooling coil + fixed-plate HX
Dehumidify Space (Cool Air)
CC
cooling
OA'
fixed-plateHX
total-energy
EA''
EA'68 F
© 2011 Trane, a business of Ingersoll-Rand97
95 F DB78 F WB
72 F DPT
OAg
coilgy
wheel
EA75 F DB55% RH
70 F DB46 F DPT
CA
total-energy wheel + cooling coil + parallel desiccant wheel
Dehumidify Space (Cool Air)95 F DB78 F WB72 F DPT
coolingcoil
reheatcoil
OACC
OA'
total-energywheel
55 F DB46 F DPT
CA
EA''
EA'
desiccantwheel EA
70 F DB72% RH
51 F
© 2011 Trane, a business of Ingersoll-Rand98
75 F DB55% RH
EA
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 50
180
160 h80
OA 95°F DB72°F DPT
energy wheel + cooling coil + parallel desiccant wheelDehumidify Space (Cool Air)
80
OA' 78°F DB65°F DPT
CC 51°F DB51°F DPT
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
OAOAOAOA
50
55
60
65
70
75
dew
po
int tem
peratu
re, °F
OA'OA'OA'OA'
EAEA
75°F DB55% RH57°F DPT
EA
CA 55°F DB46°F DPT
EA'EA'
EA' 70°F DB61°F DPT
CACA
© 2011 Trane, a business of Ingersoll-Rand99
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACACCCC
180
160 h80
OA 72°F DB68°F DPT
energy wheel + cooling coil + parallel desiccant wheelDehumidify Space (Cool Air)
80
OA' 71°F DB62°F DPT
CC 51°F DB51°F DPT
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
OAOAOAOA
50
55
60
65
70
75
dew
po
int tem
peratu
re, °F
CACAEAEA
75°F DB55% RH57°F DPT
EA
CA 55°F DB46°F DPT
EA'EA'
EA' 70°F DB61°F DPT
cooling energy savedOA'OA'OA'OA'
© 2011 Trane, a business of Ingersoll-Rand100
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACACCCC
cooling energy saved
reheat energy saved
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 51
total-energy wheel + cooling coil + parallel desiccant wheel
Dehumidify Space (Cool Air)95 F DB78 F WB72 F DPT
coolingcoil
reheatcoil
OACC
OA'
total-energywheel
55 F DB46 F DPT
CA
EA''
EA'
desiccantwheel( ll l)
EA
70 F DB72% RH
51 F
© 2011 Trane, a business of Ingersoll-Rand101
75 F DB55% RH
(parallel)EA
total-energy wheel + cooling coil + series desiccant wheel
Dehumidify Space (Cool Air)95 F DB78 F WB72 F DPT
desiccant( )72 F DPT
OA
CC
coolingcoil
OA'
total-energywheel CAEA'
OA''
wheel (series)
EAreheat
coil
© 2011 Trane, a business of Ingersoll-Rand102
75 F DB55% RH
57 F DB46 F DPT
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 52
180
160 h80
OA 95°F DB72°F DPT
energy wheel + cooling coil + series desiccant wheelDehumidify Space (Cool Air)
80
OA' 81°F DB63°F DPT
OA'' 77°F DB67°F DPT
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
OAOAOAOA
50
55
60
65
70
75
dew
po
int tem
peratu
re, °F
OA'OA'OA'OA'
EAEA
CC 52°F DB52°F DPT
75°F DB55% RH57°F DPT
EA
CA 57°F DB46°F DPT OA''OA''
CACACCCC
© 2011 Trane, a business of Ingersoll-Rand103
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACACCCC
180
160 h80
OA 72°F DB68°F DPT
energy wheel + cooling coil + series desiccant wheelDehumidify Space (Cool Air)
80
OA' 74°F DB62°F DPT
OA'' 70°F DB64°F DPT
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
50
55
60
65
70
75
dew
po
int tem
peratu
re, °F
OA'OA'OA'OA'
EAEA
CC 51°F DB51°F DPT
75°F DB55% RH57°F DPT
EA
CA 55°F DB46°F DPT
OA''OA''
CACA
OAOAOAOAcooling energy saved
© 2011 Trane, a business of Ingersoll-Rand104
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACACCCC
cooling energy saved
reheat energy saved
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 53
180
160 h80 80
energy wheel + cooling coil + downstream desiccant wheel
Parallel vs. Series
80
140
120
100
80
60
hu
mid
ity ratio, g
rains/lb
of d
ry ai
70
50
60
OAOAOAOA
50
55
60
65
70
75
dew
po
int tem
peratu
re, °F
OA'OA'OA'OA'
OAOAOAOA
OA'OA'OA'OA'
OA''OA''seriesparallel
© 2011 Trane, a business of Ingersoll-Rand105
40
20
ir
11030 40 50 60 70 80 10090
dry-bulb temperature, °F
40
30 30
40CACA
CCCC
30
energy wheel + cooling coil + downstream desiccant wheel
Parallel vs. Series
cooling leaving-aircoil load conditions
52 tons 55°F DB46°F DPT
41 t 55°F DB
outdoor airconditions
95°F DB48% RH
72°F DB
cooling leaving-aircoil load conditions
49 tons 57°F DB46°F DPT
41 t 55°F DB
parallel series
© 2011 Trane, a business of Ingersoll-Rand106
41 tons 55°F DB46°F DPT
23 tons 55°F DB46°F DPT
72°F DB88% RH
60°F DB95% RH
41 tons 55°F DB46°F DPT
32 tons 55°F DB46°F DPT
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 54
energy wheel + cooling coil + downstream desiccant wheel
Parallel vs. Series
desiccant wheel in parallel• Better on mild, humid days• Horizontal duct connections
desiccant wheel in series• Better on hot and warm days• Ratio of EA/OA flows < 0.9• High external static pressures
© 2011 Trane, a business of Ingersoll-Rand107
1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)
2) Cooling Duty• Neutral air• Cool air• Cold air
3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency
4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)
© 2011 Trane, a business of Ingersoll-Rand108
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 55
Dedicated OA Cooling Sources
35°F 40°F 45°F 50°F 60°F
Dew Point of Conditioned Outdoor Air (CA)
55°F35 F 40 F 45 F 50 F 60 F55 F
60% space RH
50% space RH
Dew point required
packaged DX
split DX system
Dew point capability
© 2011 Trane, a business of Ingersoll-Rand109
chiller + AHU
split DX system
specialty dehumidifier
considerations for
Packaged DX Dedicated OA Equipment
Air-cooled or water-cooled condensing
Required leaving-air dew point• Reheat only as much as necessary
• Cool or cold air reduces capacity of local equipment
© 2011 Trane, a business of Ingersoll-Rand110
packaged DXdedicated OA unit
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 56
Packaged vs. Split DX
Pre engineered Local design to the
Packaged DX Unit Split DX System
Pre-engineered
Laboratory tested
Smaller footprint
Integral reheat andhot gas bypass
Local design to the specific application
Potentially long line lengths (and more refrigerant)
Difficult reheat design
Indoor or outdoor location
© 2011 Trane, a business of Ingersoll-Rand111
HGBP line length
Oil management
DX Compressor Unloading
Single, on/off compressor
Single, unloading compressor (including pulsed)
Single, variable-speed compressor
Manifolded, on/off compressors
Manifolded compressors, one unloading
Manifolded compressors, one variable speed
© 2011 Trane, a business of Ingersoll-Rand112
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 57
ASHRAE Standard 90.1-2010
Hot Gas Bypass
“6.5.9 Hot Gas Bypass Limitation. Cooling systems shall not use hot gas bypass or other evaporatorshall not use hot gas bypass or other evaporator pressure control systems unless the system is designed with multiple steps of unloading or continuous capacity modulation. The capacity of the hot gas bypass shall be limited as indicated in Table 6.5.9.”
© 2011 Trane, a business of Ingersoll-Rand113
hot gas reheat
Refrigerant Heat Recovery
Prudent to use recovered heat for reheat
Deliver conditioned outdoor cold, if possible
For a split DX system:• Design reheat coil for little reheat
• Actively control head pressure
• Pay particular attention to oil management
© 2011 Trane, a business of Ingersoll-Rand114
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 58
Split DX System Selection
18
Assumptions:• 200 Btu/h/person latent load• 75°Fspace temperature
16
14
12
10
8
• 75 F space temperature
© 2011 Trane, a business of Ingersoll-Rand115
35 40 45
saturated suction temperature, °F
6
50
Chilled-Water DOAS
Standalone or shared chiller
Air-cooled or water-cooled
Indoor or outdoor equipment
© 2011 Trane, a business of Ingersoll-Rand116
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 59
Benefits of Chilled-Water DOAS Can achieve lower dew points
Wider operating envelope
Especially when using variable airflow• Especially when using variable airflow
• DX equipment often requires hot gas bypass (energy waste)
Greater flexibility and efficiency
• Fans, air cleaning, energy recovery, desiccant wheel, airflow measurement, ice storage, potential to eliminate HGBP
© 2011 Trane, a business of Ingersoll-Rand117
Certified performance
• AHRI, UL, ETL
• No AHRI certification for DX dedicated OA units (EER’s typically not published)
Reduced refrigerant charge
OA
air-handling unit
CA
oo
p r
etu
rn
Vreheat
t t t
up
ply
© 2011 Trane, a business of Ingersoll-Rand118
Pload
lo
Psource load-sideheat exchanger
source-sideheat exchanger
water-to-waterheat pump
loo
p s
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 60
OA
air-handling unit
CAu
pp
ly
oo
p r
etu
rn
i l d
© 2011 Trane, a business of Ingersoll-Rand119
loo
p slo
Psource evaporator
air-cooledchiller
© 2011 Trane, a business of Ingersoll-Rand120
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 61
Dedicated Outdoor-Air Equipment
Summary
dedicated outdoor-air equipment
Which Configuration is Best?
1) D h idifi ti D t1) Dehumidification Duty• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)
2) Cooling Duty• Neutral air• Cool air• Cold air
3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency
4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)
© 2011 Trane, a business of Ingersoll-Rand122
Cold air Direct expansion (DX)
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 62
dedicated outdoor-air equipment
Which Configuration is Best?
1 2 3 4+ + + = no silver bullet!
packaged DXdedicated OA unit
indoor
© 2011 Trane, a business of Ingersoll-Rand123
air-handling unit
outdoorair-handling unit
references for this broadcast
Where to Learn More
© 2011 Trane, a business of Ingersoll-Rand124
www.trane.com/EN
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 63
LEED Continuing Education Courseson-demand, no charge, 1.5 CE credits
ASHRAE Standards 62.1 and 90.1 d VAV S tand VAV Systems
ASHRAE standard 62.1: Ventilation Rate Procedure
ASHRAE 90.1-2010
Energy Saving Strategies for Rooftop VAV Systems
Air-Handing Systems, Energy and IAQ
Central Geothermal System Design and Control
© 2011 Trane, a business of Ingersoll-Rand125
Central Geothermal System Design and Control
Ice Storage Design and Control
www.trane.com/ContinuingEducation
watch past broadcasts
ENL Archives
Insightful topics on HVAC system design:• Chilled-water plants• Air distribution• Refrigerant-to-air systems• Control strategies• Industry standards and LEED• Energy and the environment• Acoustics• Ventilation• Dehumidification
© 2011 Trane, a business of Ingersoll-Rand126
www.trane.com/ENL
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 64
2012 ENL Programs
MarchHi h P f G B ildi Th I t fHigh Performance Green Buildings: The Impact of ASHRAE Standard 189.1-2011
JuneHeat Pump Systems
OctoberAir-to-Air Energy Recovery
© 2011 Trane, a business of Ingersoll-Rand127
Dedicated Outdoor-Air Equipment
Supplemental Slides
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 65
Dedicated OA System Configurations
Conditioned OA delivered…
1. Directly to each zone
2. To intake of each local unit
3. To supply-side of each local unit
4. To ceiling plenum, near each local unit
© 2011 Trane, a business of Ingersoll-Rand129
conditioned OA delivered
Directly to Each Zone
dedicatedOA
dedicatedOA unit
CACA CACA
CACA
• fan-coil• WSHP
© 2011 Trane, a business of Ingersoll-Rand130
RA
SA
RA
SA
WSHP• PTAC• passive chilled beams• radiant cooling panels
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 66
conditioned OA delivered
Directly to Each Zone
Advantages
Easier to ensure required outdoor airflow reaches each
Drawbacks
Requires installation of additional ductwork and
zone (separate diffusers)
Opportunity to cycle off local fan because OA is not distributed through it
Allows dedicated OA system to operate during unoccupied periods without needing to
separate diffusers
May require multiple diffusers to ensure that outdoor air is adequately dispersed throughout the zone
© 2011 Trane, a business of Ingersoll-Rand131
operate local fans
Opportunity to downsize local equipment (if OA delivered cold)
conditioned OA delivered
To Intake of Local HVAC Equipment
dedicateddedicatedOA unitOA
SASA SASARARA RARA
CACA
• fan-coil• WSHP• small RTU• VRF
© 2011 Trane, a business of Ingersoll-Rand132
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 67
conditioned OA delivered
To Intake of Local HVAC Equipment
Advantages
Helps ensure required OA reaches each zone (ducted
Drawbacks
Measurement and balancing is more difficult than if OA (
directly to each unit)
Avoids cost and space to install additional ductwork and separate diffusers
Easier to ensure that OA is adequately dispersed throughout zone because it is
delivered directly to zone
Typically requires field-fabricated plenum to connect OA duct to mix with RA
Local fan must operate continuously to provide OA during scheduled occupancy
© 2011 Trane, a business of Ingersoll-Rand133
distributed by local fan Local fan must operate if dedicated OA system operates during unoccupied period
conditioned OA delivered
To Supply-Side of Local HVAC Equipment
dedicateddedicatedOA unitOA
SASA SASARARA RARA
CACACACA
• fan-coil• WSHP• small RTU
© 2011 Trane, a business of Ingersoll-Rand134
direct tospaces
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 68
conditioned OA delivered
To Supply-Side of Local HVAC Equipment
Advantages
Helps ensure required OA reaches each zone (ducted
Drawbacks
Measurement and balancing is more difficult than if OA (
directly to each unit)
Avoids cost and space to install additional ductwork and separate diffusers
Easier to ensure that OA is adequately dispersed throughout zone because it is
delivered directly to zone
Local fan typically must operate continuously to provide OA during scheduled occupancy (unless pressure-independent VAV terminal)
© 2011 Trane, a business of Ingersoll-Rand135
distributed by local fan
Opportunity to downsize local equipment (if OA delivered cold)
conditioned OA delivered
To Plenum, Near Local HVAC Equipment
dedicateddedicatedOA unitOA
SASA SASARARA RARA
CACA
• fan-coil• WSHP• VRF
© 2011 Trane, a business of Ingersoll-Rand136
Engineers Newsletter Live
Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 69
conditioned OA delivered
To Plenum, Near Local HVAC Equipment
Advantages
Avoids cost and space to install additional ductwork and
Drawbacks
More difficult to ensure required OA reaches each zone (not
separate diffusers(
ducted directly)• Refer to Figure 5-E and 5-F of
ASHRAE 62.1-2010 User’s Manual
Local fan must operate continuously to provide OA during scheduled occupancy
Conditioned OA not able to be d li d t ld t t
© 2011 Trane, a business of Ingersoll-Rand137
delivered at a cold temperature due to concerns over condensation