71
Agenda and Objectives Trane Engineers Newsletter Live Series Dedicated Outdoor Air Equipment Previous ENLs have discussed system design and control considerations for dedicated outdoorair systems. This ENL will shift the discussion to the various types of equipment used for dedicated OA conditioning, from packaged DX units to split DX systems to air handlers and water chillers. By attending this ENL you will be able to: 1. Summarize the definition of a dedicated OA unit 2. Identify what leavingair dew point is required 3. Summarize what the difference between cold versus neutraltemperature air 4. Identify ASHRAE Standard 90.1 requirements related to dedicated OA systems 5. Identify specific dedicated OA equipment configurations Agenda 1) Opening (welcome, agenda, introductions) 2) Overview a) What is a dedicated OA unit? b) Review content from previous broadcasts c) Review of ASHRAE 90.1 requirements relates to DOAS 3) Specific dedicated OA equipment configurations a) Identify the goal(s)/purpose of the dedicated OA unit ( b) Goals = Dehumidify Ventilation Only + Meet ASHRAE 90.1 c) Goals = Dehumidify to Offset Space Latent Loads + Meet ASHRAE 90.1 d) Goals = Dehumidify Ventilation Only + Exceed 90.1 (Higher Efficiency) e) Goals = Dehumidify to Offset Space Latent Loads + Exceed 90.1 (Higher Efficiency) a) Cooling/heating sources (list advantages and drawbacks of each) 4) Summary

Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

  • Upload
    trandan

  • View
    215

  • Download
    2

Embed Size (px)

Citation preview

Page 1: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Agenda and Objectives

Trane Engineers Newsletter Live Series

Dedicated Outdoor Air Equipment

Previous ENLs have discussed system design and control considerations for dedicated outdoor‐air systems.

This ENL will shift the discussion to the various types of equipment used for dedicated OA conditioning,

from packaged DX units to split DX systems to air handlers and water chillers.

By attending this ENL you will be able to:

1. Summarize the definition of a dedicated OA unit

2. Identify what leaving‐air dew point is required

3. Summarize what the difference between cold versus neutral‐temperature air

4. Identify ASHRAE Standard 90.1 requirements related to dedicated OA systems

5. Identify specific dedicated OA equipment configurations

Agenda

1) Opening (welcome, agenda, introductions)

2) Overview

a) What is a dedicated OA unit?

b) Review content from previous broadcasts

c) Review of ASHRAE 90.1 requirements relates to DOAS

3) Specific dedicated OA equipment configurations

a) Identify the goal(s)/purpose of the dedicated OA unit (

b) Goals = Dehumidify Ventilation Only + Meet ASHRAE 90.1

c) Goals = Dehumidify to Offset Space Latent Loads + Meet ASHRAE 90.1

d) Goals = Dehumidify Ventilation Only + Exceed 90.1 (Higher Efficiency)

e) Goals = Dehumidify to Offset Space Latent Loads + Exceed 90.1 (Higher Efficiency)

a) Cooling/heating sources (list advantages and drawbacks of each)

4) Summary

Agenda_APPCMC043.ai 1 6/12/2014 4:05:42 PM

Page 2: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Presenters

Trane Engineers Newsletter Live Series

Dedicated Outdoor Air Equipment (2011)

Ronnie Moffitt | applications engineer | TraneRonnie joined Trane in 1996 and currently is an airside applications engineer whose responsibility is to aid designengineers and Trane sales personnel in the proper design and application of HVAC systems. His primary focus hasbeen dehumidification and air‐to‐air energy recovery design. This includes the development, design and controloptimization of desiccants in commercial HVAC systems. He has several patents related to this subject and serveson related AHRI and ASHRAE engineering committees.Ronnie led the development of the Trane CDQ system, a winner of the R&D 100 Award for The MostTechnologically Significant New Products of 2005. He is a certified Energy Manager (CEM) by Association of EnergyEngineers and received his B.S. in Aerospace Engineering from Syracuse University.

John Murphy | applications engineer | TraneJohn has been with Trane since 1993. His primary responsibility as an applications engineer is to aid designengineers and Trane sales personnel in the proper design and application of HVAC systems. As a LEED AccreditedProfessional, he has helped our customers and local offices on a wide range of LEED projects. His main areas ofexpertise include energy efficiency, dehumidification, dedicated outdoor‐air systems, air‐to‐air energy recovery,psychrometry, and ventilation.

John is the author of numerous Trane application manuals and Engineers Newsletters, and is a frequent presenteron Trane’s Engineers Newsletter Live series of broadcasts. He also is a member of ASHRAE, has authored severalarticles for the ASHRAE Journal, and is a member of ASHRAE’s “Moisture Management in Buildings” and“Mechanical Dehumidifiers” technical committees. He was a contributing author of the Advanced Energy DesignGuide for K‐12 Schools and the Advanced Energy Design Guide for Small Hospitals and Health Care Facilities, andtechnical reviewer for The ASHRAE Guide for Buildings in Hot and Humid Climates.

Paul Solberg | applications engineer | TraneA mechanical engineer from the University of Wisconsin at Platteville, Paul is a 35‐year veteran of Trane. Hespecializes in compressor and refrigeration systems, and has authored numerous Trane publications on thesesubjects, including application manuals, engineering bulletins, and Engineers Newsletters. Paul served in thetechnical service and applications engineering areas at various manufacturing locations, where he developedparticular expertise supporting split systems, small packaged chillers, rooftop air conditioners, and other unitaryproducts.

Biographies_APPCMC043.ai 1 6/12/2014 4:06:26 PM

Page 3: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 1

Dedicated Outdoor-Air Equipment

Ingersoll Rand

© 2011 Trane, a business of Ingersoll-Rand2

Dedicated Outdoor-Air Equipment

1.5

Page 4: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 2

“Trane” is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to CES Records for AIA members Certificates ofreported to CES Records for AIA members. Certificates of Completion for non-AIA members available on request.

This program is registered with the AIA/CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product.Questions related to specific materials,

© 2011 Trane, a business of Ingersoll-Rand3

methods, and services will be addressedat the conclusion of this presentation.

Copyrighted Materials

This presentation is protected by U.S. and international i h l R d i di ib i di l d fcopyright laws. Reproduction, distribution, display, and use of

the presentation without written permission of Trane is prohibited.

© 2011 Trane, a business of Ingersoll-Rand. All rights reserved.

© 2011 Trane, a business of Ingersoll-Rand4

Page 5: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 3

Learning Objectives

Summarize the definition of a dedicated OA unit

Identify what leaving-air dew point is required

Summarize what the difference between cold versus neutral-temperature air

Identify ASHRAE Standard 90.1 requirements related to dedicated OA systems

Identifyspecific dedicated OA equipment configurations

© 2011 Trane, a business of Ingersoll-Rand5

Identify specific dedicated OA equipment configurations

Dedicated Outdoor-Air Equipment

Today’s Topics

Definition of a dedicated OA unit• What leaving-air dew point is required?

• Cold versus neutral-temperature air?

ASHRAE 90.1 requirements related todedicated OA systems

Specific dedicated OA equipment configurations

© 2011 Trane, a business of Ingersoll-Rand6

Page 6: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 4

Today’s Presenters

© 2011 Trane, a business of Ingersoll-Rand7

Ronnie Moffitt

ApplicationsEngineer

John Murphy

Applications Engineer

Paul Solberg

ApplicationsEngineer

Dedicated Outdoor-Air Equipment

Definition of a Dedicated OA Unit

Page 7: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 5

What is a Dedicated OA Unit?

AHRI Standard 920 (currently in development)

A dedicated OA unit “operate[s] in combination with aA dedicated OA unit operate[s] in combination with a separate sensible cooling system to satisfy the entire building humidity load. The system is sized to maintain a prescribed ventilation rate under any load condition. The ventilation rate can be constant or varied based on the building operation or occupancy schedule or in response to the actual occupancy. It may pre-condition outdoor airby containing an enthalpy wheel, sensible wheel, desiccant wheel, plate heat exchanger, heat pipes or other heat or

© 2011 Trane, a business of Ingersoll-Rand9

, p g , p pmass transfer apparatus. It may reheat the ventilation air by containing a reheat refrigerant circuit, sensible wheel, heat pipe, or other heat or mass transfer apparatus.”

Satisfies entire building humidity (latent) load

May reheat dehumidified ventilation air

May pre-condition outdoor air using

air-to-air energy recovery

dedicatedOA unit

CA

CA CA

EA

OA

Delivers prescribed (typically minimum)

ventilation rate

© 2011 Trane, a business of Ingersoll-Rand10

RA

Operates in combination with a separate sensible cooling/heating system

SA SA

RA

Page 8: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 6

Dedicated OA Systems

What leaving-air dew point is required?• Cooled, but not dehumidified

• Cooled and dehumidified

© 2011 Trane, a business of Ingersoll-Rand11

180

16080

OA 95°F DB

example: kitchen

Cooled But Not Dehumidified

80

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry a

80

70

50

60

78°F WB

CA 70°F DB67°F DPT

CACA

80°F DB60% RH65°F DPT

50

55

60

65

70

75

80

dew

po

int tem

peratu

re, °F

OAOAOAOAspace

spacespacespacespace

© 2011 Trane, a business of Ingersoll-Rand12

40

20

air

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40

50

Page 9: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 7

180

16080

OA

example: fan-coils, VAV, WSHPs, VRF

Cooled and Dehumidified

8095°F DB

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry a

80

70

50

60

CA 52°F DB52°F DPT

75°F DB60% RH61°F DPT

50

55

60

65

70

75

80

dew

po

int tem

peratu

re, °F

dry enough toremove spacelatent load

dry enough toremove spacelatent load

worst-caseupper limit

78°F WB

OAOAOAOAspace

spacespacespacespace

© 2011 Trane, a business of Ingersoll-Rand13

40

20

air

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30

CACA

30

40

50latent loadlatent load

What Leaving-AirDew Point is Required? “Dedicated Outdoor-Air Ventilation

Systems” Engineers Newsletter Livebroadcast APP CMC008 EN (2001)broadcast, APP-CMC008-EN (2001)

"Designing Dedicated Outdoor-Air Systems," Trane application guideSYS-APG001-EN (2003)

"Dedicated Ventilation Systems," Engineers Newsletter 30-3 (2001)

Morris, W. 2003. “The ABCs of DOAS: Dedicated Outdoor Air Systems.”

© 2011 Trane, a business of Ingersoll-Rand14

ASHRAE Journal (May)

Murphy, J. 2006. “Smart Dedicated Outdoor Air Systems.” ASHRAE Journal (July)

Page 10: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 8

180

16080

OA

example: chilled beams, radiant cooling

Cooled and Over-Dehumidified

8095°F DB

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry a

80

70

50

60

CA 55°F DB45°F DPT

space 75°F DB50% RH55°F DPT

spacespacespacespace50

55

60

65

70

75

80

dew

po

int tem

peratu

re, °F

to preventcondensation

dry enough todry enough to

78°F WB

OAOAOAOA

© 2011 Trane, a business of Ingersoll-Rand15

40

20

air

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 CACA30

40

50y gremove spacelatent load

y gremove spacelatent load

Dedicated OA Systems

What leaving-air dew point is required?

Cold versus neutral-temperature air?

© 2011 Trane, a business of Ingersoll-Rand16

Page 11: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 9

180

16080

OA 95°F DB78°F WB

CA 71°F DB52°F DPT

80

dedicated OA system(“neutral” air)

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry a

80

70

50

60

OAOAOAOA

(450 cfm)

RA 74°F DB50% RH55°F DPT

RARARARA50

55

60

65

70

75

80

dew

po

int tem

peratu

re, °F

SA 55°F DB(1380 cfm)

SASA

local unit:

local unit

© 2011 Trane, a business of Ingersoll-Rand17

40

20

air

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30

CACA

30

40

50local unit:1380 cfm2.4 tons

180

16080 80

dedicated OA system(“neutral” air)

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry a

80

70

50

60

CACA50

55

60

65

70

75

80

dew

po

int tem

peratu

re, °F

sensible cooling

deh

um

idificat

OAOAOAOA

spacespacespacespace

© 2011 Trane, a business of Ingersoll-Rand18

40

20

air

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40

50

wasted cooling energy

tion

Page 12: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 10

180

16080

OA 95°F DB78°F WB

CA 52°F DB52°F DPT

80

dedicated OA system(“cold” air)

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry a

80

70

50

60

(450 cfm)

RA 74°F DB50% RH55°F DPT

RARARARA50

55

60

65

70

75

80

dew

po

int tem

peratu

re, °F

SA 55°F DB(930 cfm)

SASA local unit:

local unit

OAOAOAOA

© 2011 Trane, a business of Ingersoll-Rand19

40

20

air

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30

CACA

30

40

50SASA local unit:930 cfm1.6 tons

CA

930 cfm at 55°F

450 cfm at 52°F

cold-airsystem

SA

1380 cfmRA

CA

CA

1380 cfm at 55°F

450 cfm at 71°Fneutral-airsystem

© 2011 Trane, a business of Ingersoll-Rand20

1830 cfmRA

CA SA

Page 13: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 11

Cold versus Neutral

Less overall cooling capacity• Sensible cooling provided by cold conditioned OA

reduces required cooling capacity of local HVAC units

• Cooling (dehumidification) capacity of the dedicated OA unit is the same in either case

Less overall cooling energy• Sensible cooling provided by cold conditioned OA

d li i d f l l HVAC it

© 2011 Trane, a business of Ingersoll-Rand21

reduces cooling required from local HVAC units

Cold versus Neutral

cold tospace

neutral tospace/unit

cold tolocal unit

dedicated OA unitcooling capacity, tons 3.4 3.4 3.4

reheat capacity, MBh 9.3 0 0

fan airflow, cfm 450 450 450

local HVAC unit

© 2011 Trane, a business of Ingersoll-Rand22

cooling capacity, tons 2.4 1.6 1.6

fan airflow, cfm 1380 930 1380

Page 14: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 12

Cold versus Neutral

Less overall fan energy, if OA is delivered cold ( l) di tl t(or cool) directly to spaces

• Cold conditioned OA removes some of the space sensible cooling load, which reduces the airflow needed from local HVAC units

• Airflow delivered by the dedicated OA unit is the same in either case

© 2011 Trane, a business of Ingersoll-Rand23

Won’t Delivering OA Cold Overcool the Space?

Qs,space = 29,750 Btu/h (design load)s,space

Qs,ca = 1.085 450 cfm (74°F – 52°F)

= 10,740 Btu/h

Space sensible cooling loadt b < 36% f d i

© 2011 Trane, a business of Ingersoll-Rand24

must be < 36% of designbefore overcooling will occur!

Page 15: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 13

When Should I Reheat Dehumidified OA?

Applications where space sensible cooling loads differ tl t i ti ( h t l d it i )greatly at any given time (e.g., hotels, dormitories)

To avoid overcooling at part-load conditions• Implement demand-controlled ventilation to reduce

outdoor airflow as population changes

• Activate heat in the local HVAC unit (few zones, WSHP)

• Reheat dehumidified air in dedicated OA unit

© 2011 Trane, a business of Ingersoll-Rand25

(consider using recovery energy)

Reheating Dehumidified OA

TT

BAS

dedicatedOA unit

CA

CA CA

EA

OATT

© 2011 Trane, a business of Ingersoll-Rand26

RA

SA SA

RA

local HVAC units

TT TT

Page 16: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 14

When Should I Reheat Dehumidified OA?

Applications where space sensible cooling loads differ tl t i ti ( h t l d it i )greatly at any given time (e.g., hotels, dormitories)

To avoid overcooling at part-load conditions• Implement demand-controlled ventilation

• Activate heat in the local HVAC unit

• Reheat dehumidified air in dedicated OA unit

Applications requiring lower-than-normal dew points

© 2011 Trane, a business of Ingersoll-Rand27

pp q g p

To avoid condensation when conditioned OA is delivered to the ceiling plenum

Dedicated OA Systems

What leaving-air dew point is required?

Cold versus neutral-temperature air?

How will conditioned OA be delivered to spaces?• Directly to each space

• To intake of each local unit

• To supply-side of each local unit

• To ceiling plenum, near each local unit

© 2011 Trane, a business of Ingersoll-Rand28

To ceiling plenum, near each local unit

Page 17: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 15

Dedicated Outdoor-Air Equipment

ASHRAE 90.1-2010Requirements

ASHRAE 90.1 and Dedicated OA Systems

Minimum equipment efficiencies

Fan power limitation

Economizer

Exhaust-air energy recovery

Limitation on simultaneousheating and cooling

© 2011 Trane, a business of Ingersoll-Rand30

Page 18: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 16

Section 6.4.1, mandatory requirements

Minimum Equipment Efficiencies

Currently there is no rating or certification standard f DX d di t d OA i t ASHRAE 90 1 dfor DX dedicated OA equipment, so ASHRAE 90.1 does not list a minimum efficiency requirement

AHRI Standard 920 isunder development

“6.4.1.3 Equipment Not Listed. Equipment not listed in the tables referenced in Sections 6.4.1.1 and 6.4.1.2 may be used.”

© 2011 Trane, a business of Ingersoll-Rand31

AHRI Standard 920 is under development

Section 6.5.3.1, prescriptive requirements

Fan Power Limitation

What is a “fan system”?

“fan system bhp: the sum of the fan brake horsepower (bhp) of all fans that are required to operate at fan system design conditions to supply air from the heating or cooling source to the conditioned space(s) and return it to the source or exhaust it to the outdoors” (Section 3.2)

© 2011 Trane, a business of Ingersoll-Rand32

Page 19: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 17

example 6-DDD

User’s Manual for 90.1-2010

QUESTION: A wing of an elementary school building is served by eight WSHPs each equipped with a ¾-hp fan motor andserving aeight WSHPs, each equipped with a ¾ hp fan motor and serving a single classroom. Ventilation air is supplied directly to each classroom by a dedicated outdoor-air system. Each classroom requires 500 cfm of outdoor air, so the DOAS delivers the total of 4000 cfm of conditioned outdoor air using a 5-hp fan. Does this system need to comply with section 6.5.3.1?

ANSWER: Each WSHP is a separate fan system because each

© 2011 Trane, a business of Ingersoll-Rand33

ANSWER: Each WSHP is a separate fan system because each has a separate cooling and heating source. The power of the DOAS fan must be allocated to each heat pump on a cfm-weighted basis.

example 6-DDD

User’s Manual for 90.1-2010

© 2011 Trane, a business of Ingersoll-Rand34

Page 20: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 18

Section 6.5.3.1, prescriptive requirements

Fan Power Limitation

Only applies to fan systems > 5 hp

Each fan system shall not exceed:• Option 1: fan system motor nameplate hp

• Option 2: fan system bhp

Exceptions:a. Health and safety (systems maintaining

space-to-space pressure differences)

© 2011 Trane, a business of Ingersoll-Rand35

p p p )

b. Individual exhaust fans ≤ 1 hp

Section 6.5.1, prescriptive requirements

Economizers

“6.5.1 Economizers. Each cooling system that has a fan shall include either an air or water economizer meeting

Most notable exceptions:a. Cooling capacity < 54,000 Btu/hr (4.5 tons)

b. Systems that use non-particulate air treatment

d. Systems with condenser heat recovery

shall include either an air or water economizer meeting the requirements of Sections 6.5.1.1 through 6.5.1.4.”

© 2011 Trane, a business of Ingersoll-Rand36

e. Residential with cooling capacity < 270,000 Btu/hr

Page 21: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 19

If an Economizer is Required…

Oversize the dedicated OA system to “provide up to 100% f d i l i tit i f li ”100% of design supply air quantity air for cooling”

Include a second OA intake (path) for airside economizing

Waterside economizing• Fan-coils, radiant cooling

Comply using Energy Cost Budget (Section 10) method,

© 2011 Trane, a business of Ingersoll-Rand37

p y g gy g ( ) ,rather than prescriptive requirements

Section 6.5.6.1, prescriptive requirements

Exhaust-Air Energy Recovery

For dedicated (100%) OA systems, exhaust-air energy i i d ( ll ) t frecovery is required on more (smaller) systems for many

climate zones.

© 2011 Trane, a business of Ingersoll-Rand38

Page 22: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 20

Section 6.5.6.1, prescriptive requirements

Exhaust-Air Energy Recovery

“…at least 50% energy recovery effectiveness. Fifty percent energy recovery effectiveness shall mean a

RARA75°F DB63°F WB

Be careful of this term!

Fifty percent energy recovery effectiveness shall mean a change in the enthalpy of the outdoor air supply equal to 50% of the difference between the outdoor air and return air enthalpies at design conditions.”

© 2011 Trane, a business of Ingersoll-Rand39

OAOA95°F DB78°F WB41.3 Btu/lb

28.5 Btu/lb

hleaving ≤ 34.9 Btu/lb

= (h1 – h2)ṁOA

ASHRAE Standard 84 and AHRI Standard 1060

Effectiveness

“total energy exchange rate”T = (h1 – h3)ṁmin

h3h4

ṁEA

“maximum energy exchange rate”

© 2011 Trane, a business of Ingersoll-Rand40

h1 h2

ṁOA

Page 23: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 21

50% = (41.3 – h2)10,000 cfm

different definitions of effectiveness

Example of Unbalanced Airflows (ṁEA < ṁOA)

h2 = 36.2 Btu/lb50% (41.3 – 28.5)8,000 cfm

h4 h3 = 28.5 Btu/lb

8,000 cfm

h2 36.2 Btu/lb

Does not meet ASHRAE 90.1

© 2011 Trane, a business of Ingersoll-Rand41

10,000 cfm

h1 = 41.3 Btu/lb h2 ≤ 34.9 Btu/lb to meet ASHRAE 90.1

“As-Applied” vs. “Rated” Effectiveness

Be careful not to confuse “as-applied” effectiveness ( i d b ASHRAE 90 1) ith “ t d” ff ti(required by ASHRAE 90.1) with “rated” effectiveness per AHRI 1060

Strive for balanced airflows• Bring back as much exhaust air as possible

© 2011 Trane, a business of Ingersoll-Rand42

Page 24: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 22

exhaust-air energy recovery

Using Restroom Exhaust

© 2011 Trane, a business of Ingersoll-Rand43

ASHRAE 62.1-2010

Recirculation of Restroom Exhaust

“5.16.3.2.5. Class 2 air [which includes restrooms] shall not be recirculated or transferred to Class 1 spaces

EAEAV4V4 V3V3

recirculated or transferred to Class 1 spaces.

Exception: When using an energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device is permitted. Recirculated Class 2 air shall not exceed 10% of the outdoor air intake flow.”

© 2011 Trane, a business of Ingersoll-Rand44

OAOA

EAEA

V1V1 V2V2

V3-to-2V3-to-2

EATR ≤ 10%

Exhaust Air Transfer Ratio is defined byASHRAE Standard 84 and certified byAHRI Standard 1060

Page 25: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 23

Section 6.5.2, prescriptive requirements

Simultaneous Heating and Cooling

“6.5.2.3 Dehumidification. Where humidistatic controls are provided such controls shall prevent reheatingare provided, such controls shall prevent reheating, mixing of hot and cold airstreams, or other means of simultaneous heating and cooling of the same airstream.”

Exception A:“The system is capable of reducing supply air volume to 50% or less of the design airflow rate or the minimum outdoor air ventilation rate specified in ASHRAE Standard 62.1 …

© 2011 Trane, a business of Ingersoll-Rand45

See example 6-TT, User’s Manual for 90.1-2010

pwhichever is larger, before simultaneous heating and cooling takes place.”

Dedicated Outdoor-Air Equipment

Specific Dedicated OA Equipment Configurations

Page 26: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 24

dedicated outdoor-air equipment

Which Configuration is Best?

1) Dehumidification Duty

2) Cooling Duty

3) Efficiency Target

4) Cooling Source

© 2011 Trane, a business of Ingersoll-Rand47

2) Cooling Duty 4) Cooling Source

What is the Dehumidification Duty?1

infiltration

people

permeanceventilation

space (indoor)

© 2011 Trane, a business of Ingersoll-Rand48

p ( )latent loads

typical latent loadsfor a school classroom

source: Humidity Control Design Guide, ASHRAE © 2001, p. 278

Page 27: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 25

what is the dehumidification duty?

Dehumidify Ventilation Air Only

spacededicatedOA unit

CA

CA CA

EA

OAspacelatent loads

ventilationlatent load

• Dedicated OA unit removes latent load due to ventilation

• Space latent loads must be removed by local units (any space dehumidification is coincidental)

© 2011 Trane, a business of Ingersoll-Rand49

RA

SA SA

RA

localHVAC unit

dehumidification is coincidental)

180

160 h80

Dehumidify Ventilation Air Only

80

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

50

55

60

65

70

75

80

dew

po

int tem

peratu

re, °F

60% RH = 6060% RH = 60°°F DPTF DPT60% RH = 6060% RH = 60°°F DPTF DPT

50% RH = 5550% RH = 55°°F DPTF DPT50% RH = 5550% RH = 55°°F DPTF DPTDedicated OA unit delivers air

© 2011 Trane, a business of Ingersoll-Rand50

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

3030

40

50 F

at a dew point close to desired space condition (does not remove any space latent loads)

Page 28: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 26

what is the dehumidification duty?

Dehumidify the Space (for Comfort)

spacededicatedOA unit

CA

CA CA

EA

OAspacelatent loads

ventilationlatent load

• Dedicated OA unit removes both ventilation and space latent loads (controls space humidity)

• Local HVAC units need only remove space sensible loads

© 2011 Trane, a business of Ingersoll-Rand51

RA

SA SA

RA

localHVAC unit

remove space sensible loads

dehumidify the space (for comfort)

What Leaving-Air Dew Point is Required?

55

Assumptions:• 200 Btu/h/person latent load• 75°Fspace temperature

eavi

ng

-air

dew

po

int,

°F

50

45

40

35

30

• 75 F space temperature

© 2011 Trane, a business of Ingersoll-Rand52

8 10 126 181614

outdoor airflow, cfm/person

le

25

Page 29: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 27

dehumidify the space (for comfort)

What Leaving-Air Dew Point is Required?

55

Assumptions:• 200 Btu/h/person latent load• 75°Fspace temperature

eavi

ng

-air

dew

po

int,

°F

50

45

40

35

30

• 75 F space temperature

office

© 2011 Trane, a business of Ingersoll-Rand53

8 10 126 181614

outdoor airflow, cfm/person

le

25 lecturehall

K-12classroom

180

160 h80

Dehumidify to Space (for Comfort)

80

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

50

55

60

65

70

75

80

dew

po

int tem

peratu

re, °F

desired space conditiondesired space conditiondesired space conditiondesired space condition

Dedicated OA unit delivers air at a dew

© 2011 Trane, a business of Ingersoll-Rand54

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

3030

40

50 F

Dedicated OA unit delivers air at a dew point drier than desired space condition (removes all space latent loads)

Page 30: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 28

what is the dehumidification duty?

Dehumidify the Space (for Condensation)

spacededicatedOA unit

CA

CA CA

EA

OAspacelatent loads

ventilationlatent load

radiantcooling

• Dedicated OA unit removes both ventilation and space latent loads (leaving-air DPT low enough to prevent condensation on local units)

• Local HVAC units only remove

© 2011 Trane, a business of Ingersoll-Rand55

gpanels • Local HVAC units only remove

space sensible loads

180

160 h80

Dehumidify the Space (for Condensation)

80

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

50

55

60

65

70

75

80

dew

po

int tem

peratu

re, °F

Dedicated OA unit delivers air at a dew point

desired space conditiondesired space conditiondesired space conditiondesired space condition

© 2011 Trane, a business of Ingersoll-Rand56

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

3030

40

50 F

Dedicated OA unit delivers air at a dew point low enough to prevent condensation on local cooling equipment

Page 31: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 29

dedicated outdoor-air equipment

What is the Dehumidification Duty?1

1) Dehumidification Duty• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)

© 2011 Trane, a business of Ingersoll-Rand57

2 What is the Cooling Duty?

Neutral air• Remove the sensible ventilation load only

Cool air• Trim some of the space sensible cooling load

Cold air• Remove as much of the space sensible cooling

load as possible

© 2011 Trane, a business of Ingersoll-Rand58

p

Page 32: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 30

what is the cooling duty?

Neutral AirdedicatedOA unit Dedicated OA unit delivers

air at dry bulb temperature

CA

CA CA

EA

OAair at dry-bulb temperature close to desired space condition

• Does not remove any space sensible loads

Space sensible loads must be removed by local cooling

© 2011 Trane, a business of Ingersoll-Rand59

localHVAC unit

RA

SA SA

RARA

SA SA

RA

y gequipment

what is the cooling duty?

Cold Air

Dedicated OA unit delivers air at dry bulb temperature

dedicatedOA unit

air at dry-bulb temperature cooler than the space

• Removes some of the space sensible loads

Remainder of space sensible loads removed by local cooling equipment

CA

CA CA

EA

OA

© 2011 Trane, a business of Ingersoll-Rand60

y g q p

RA

SA SA

RA

localHVAC unit

Page 33: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 31

what is the cooling duty?

Cool AirdedicatedOA unit Dedicated OA unit delivers

air at dry bulb temperature

CA

SA SA

EA

OA

localHVAC unit

RA

CA CA

RA

air at dry-bulb temperature cooler than the space

• Air is reheated some before delivery

• Removes some of the space sensible loads

Remainder ofspacesensible

© 2011 Trane, a business of Ingersoll-Rand61

Remainder of space sensible loads removed by local cooling equipment

dedicated outdoor-air equipment

What is the Cooling Duty?2

1) Dehumidification Duty• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)

2) Cooling Duty• Neutral air

© 2011 Trane, a business of Ingersoll-Rand62

Neutral air• Cool air• Cold air

Page 34: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 32

3 What is the Efficiency Target?

Code or ASHRAE 90.1 minimum• Meet the minimum requirements of the local energy

code or ASHRAE Standard 90.1

Higher level of efficiency• More efficient than the minimum requirements

© 2011 Trane, a business of Ingersoll-Rand63

What is the Cooling Source?

Shared chiller plant

4

• Chiller plant that serves both thededicated outdoor-air equipmentand the local cooling equipment

Dedicated chiller• Chiller that serves only the

dedicated outdoor-air equipment

Di t i (DX) it

air-cooledchiller

© 2011 Trane, a business of Ingersoll-Rand64

Direct expansion (DX) unit• Packaged or split

• Air-cooled or water-cooled packaged DXdedicated OA unit

Page 35: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 33

many combinations … no silver bullet!

Financial Constraints?

1) Dehumidification Duty• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)

2) Cooling Duty• Neutral air

3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency

4) Cooling Source• Shared chiller plant

$

© 2011 Trane, a business of Ingersoll-Rand65

Neutral air• Cool air• Cold air

p• Dedicated chiller• Direct expansion (DX)

1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)

2) Cooling Duty• Neutral air• Cool air• Cold air

3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency

4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)

© 2011 Trane, a business of Ingersoll-Rand66

Page 36: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 34

energy wheel + cooling coil

Dehumidify Ventilation Only (Cold Air)

EA'

total-energycooling

OA'CC57 F

© 2011 Trane, a business of Ingersoll-Rand67

75 F DB55% RH

EA OACA

total energywheel

coolingcoil

95 F DB78 F WB

72 F DPT

59 F DB57 F DPT

180

160 h80

OA 95°F DB72°F DPT

CC 57°F DB

energy wheel + cooling coilDehumidify Ventilation Only (Cold Air)

80

OA' 81°F DB63°F DPT

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

OAOAOAOA

CC 57 F DB57°F DPT

75°F DB55% RH57°F DPT

50

55

60

65

70

75

dew

po

int tem

peratu

re, °F

EA

OA'OA'OA'OA'

CACA EAEAnot dry enoughto remove spacel t t l d

not dry enoughto remove spacel t t l d

CA 59°F DB57°F DPT

CCCC

© 2011 Trane, a business of Ingersoll-Rand68

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40latent loadlatent load

Page 37: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 35

180

160 h80

OA 95°F DB72°F DPT

energy wheel + cooling coilDehumidify Ventilation Only (Cold Air)

80

OA' 81°F DB67°F DPT

CC 57°F DB140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

OAOAOAOA

50

55

60

65

70

75

dew

po

int tem

peratu

re, °F

space latent loadspace latent load

OA'OA'OA'OA'

EAEA

CC 57 F DB57°F DPT

75°F DB71% RH65°F DPT

EA

CA 59°F DB57°F DPT

CACACCCC

© 2011 Trane, a business of Ingersoll-Rand69

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40

1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)

2) Cooling Duty• Neutral air• Cool air• Cold air

3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency

4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)

© 2011 Trane, a business of Ingersoll-Rand70

Page 38: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 36

energy wheel + cooling coil

Dehumidify Space (Cold Air)

EA'

total-energycooling

OA'CC46 F

© 2011 Trane, a business of Ingersoll-Rand71

75 F DB55% RH

EA OA

total energywheel

coolingcoil

95 F DB78 F WB

72 F DPT

CA48 F DB46 F DPT

180

160 h80

OA 95°F DB72°F DPT

energy wheel + cooling coilDehumidify Space (Cold Air)

80

OA' 81°F DB63°F DPT

CC 46°F DB140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

OAOAOAOA

50

55

60

65

70

75

dew

po

int tem

peratu

re, °F

OA'OA'OA'OA'

EAEA space latent loadspace latent load

CC 46 F DB46°F DPT

75°F DB55% RH57°F DPT

EA

CA 48°F DB46°F DPT

CCCC

© 2011 Trane, a business of Ingersoll-Rand72

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACA

CCCC

Page 39: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 37

energy wheel + cooling coil

Dehumidify Space (Cool Air)

EA'

total-energycooling

OA'

heating

CC46 F

© 2011 Trane, a business of Ingersoll-Rand73

75 F DB55% RH

EA

95 F DB78 F WB

72 F DPT

OA58 F DB46 F DPT

CA

total energywheel

coolingcoil

heatingcoil

180

160 h80

OA 95°F DB72°F DPT

energy wheel + cooling coilDehumidify Space (Cool Air)

80

OA' 81°F DB63°F DPT

CC 46°F DB140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

OAOAOAOA

50

55

60

65

70

75

dew

po

int tem

peratu

re, °F

OA'OA'OA'OA'

EAEA space latent loadspace latent load

CC 46 F DB46°F DPT

75°F DB55% RH57°F DPT

EA

CA 58°F DB46°F DPT

CCCC

© 2011 Trane, a business of Ingersoll-Rand74

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACA

CCCC

reheatreheat

Page 40: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 38

“In humid climates,seriously consider providing

Consider Unoccupied Humidity Control

In humid climates, seriously consider providing dehumidification during the summer, even if schoolis unoccupied, to prevent mold and mildew.”

Chapter 7 (p. 7.3), 2011 ASHRAE Handbook—HVAC Applications

© 2011 Trane, a business of Ingersoll-Rand75

energy wheel + cooling coil

Dehumidify Space (Unoccupied Mode)

total-energycoolingreheat OA dampers

CC

© 2011 Trane, a business of Ingersoll-Rand76

RACA

total energywheel

coolingcoil

reheatcoil

OA dampersclosed

Page 41: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 39

180

160 h80

OA 95°F DB72°F DPT

energy wheel + cooling coilDehumidify Space (Cool Air)

80

OA' 81°F DB63°F DPT

CC 46°F DB140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

OAOAOAOA

50

55

60

65

70

75

dew

po

int tem

peratu

re, °F

OA'OA'OA'OA'

EAEA space latent loadspace latent load

CC 46 F DB46°F DPT

75°F DB55% RH57°F DPT

EA

CA 58°F DB46°F DPT

CCCC

© 2011 Trane, a business of Ingersoll-Rand77

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACA

CCCC

reheat = cooling energy wastedreheat = cooling energy wasted

series air-to-air HX (with bypass) + cooling coil

Dehumidify Space (Cool Air)

95 F DB78 F WB

72 F DPT

OA

CA

coolingil

OA'

heatingil

CC

air-to-airHX

46 F

© 2011 Trane, a business of Ingersoll-Rand78

CAcoilcoil

58 F DB46 F DPT

Page 42: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 40

180

160 h80

OA 95°F DB72°F DPT

series air-to-air HX + cooling coilDehumidify Space (Cool Air)

80

OA' 88°F DB70°F DPT

CC 46°F DB 75% b passes75% b passes140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

50

55

60

65

dew

po

int tem

peratu

re, °F

OA'OA'OA'OA'

CACA

CC 46 F DB46°F DPT

CA 58°F DB46°F DPT

CCCC

25% passesthrough HX25% passesthrough HX

75% bypassesaround HX

75% bypassesaround HX

pre-cooling

OAOAOAOA

70

75

© 2011 Trane, a business of Ingersoll-Rand79

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACACCCC

recovered reheat energy

Series Air-to-Air Devices (Cool Air)

sensible pressure drop OA temp below whicheffectiveness (per pass) reheat is required*

heat pipe 40% 0.5 in. H2O 76°F

coil loop 50% 0.5 in. H2O 70°F

fixed-plate HX 65% 0.5 in. H2O 64°F

* to achieve 58°F leaving dry-bulb temperature with 46°F dew point

© 2011 Trane, a business of Ingersoll-Rand80

Page 43: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 41

OA

OA46 F 46 F58 F 58 F

series HX + cooling coil• 13% less cooling capacity• 12 F less reheat

cooling coil + reheat (cool air)• Delivering conditioned OA at

same dew point and dry bulb

CA58 F DB46 F DPT

CA58 F DB46 F DPT

© 2011 Trane, a business of Ingersoll-Rand81

58 F DB46 F DPT

48 F DB46 F DPT

series HX + cooling coil• Dedicated OA unit

• 13% lesscooling capacity

cooling coil + reheat (cold air)• Dedicated OA unit

• 13% more cooling capacity

© 2011 Trane, a business of Ingersoll-Rand82

13% less cooling capacity• 12°F less reheat

• Local HVAC equipment• 13% more cooling capacity• 13% more airflow

13% more cooling capacity

• Local HVAC equipment• 13% less cooling capacity• 13% less airflow

Page 44: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 42

1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)

2) Cooling Duty• Neutral air• Cool air• Cold air

3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency

4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)

© 2011 Trane, a business of Ingersoll-Rand83

series air-to-air HX (without bypass) + cooling coil

Dehumidify Space (Neutral Air)

95 F DB78 F WB

72 F DPT

OA

CA

coolingil

OA'

heatingil

CC

air-to-airHX

80 F

46 F

© 2011 Trane, a business of Ingersoll-Rand84

CAcoilcoil

80 F DB46 F DPT

Page 45: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 43

180

160 h80

OA 95°F DB72°F DPT

series air-to-air HX + cooling coilDehumidify Space (Neutral Air)

80

OA' 71°F DB69°F DPT

CC 46°F DB140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

50

55

60

65

dew

po

int tem

peratu

re, °F

OA'OA'OA'OA'

CACA

CC 46 F DB46°F DPT

CA 80°F DB46°F DPT

CCCC

pre-cooling

OAOAOAOA

70

75

© 2011 Trane, a business of Ingersoll-Rand85

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACACCCC

recovered reheat energy

Series Air-to-Air Devices (Neutral Air)

sensible pressure drop OA temp below whicheffectiveness (per pass) reheat is required*

heat pipe 40% 0.5 in. H2O 118°F

coil loop 50% 0.5 in. H2O 100°F

fixed-plate HX 65% 0.5 in. H2O 90°F

* to achieve 75°F leaving dry-bulb temperature with 46°F dew point

© 2011 Trane, a business of Ingersoll-Rand86

Page 46: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 44

Parallel or Series?

energy wheel + cooling coil(parallel)• Exhaust air is available

for recovery• Deliver air at a cool (or cold)

series HX + cooling coil (series)• Exhaust air NOT available

for recovery• Deliver air at a neutral

© 2011 Trane, a business of Ingersoll-Rand87

Deliver air at a cool (or cold) temperature

• Recoverable reheat (if needed) energy is available

temperature• Recoverable reheat

energy is NOT available

1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)

2) Cooling Duty• Neutral air• Cool air• Cold air

3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency

4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)

© 2011 Trane, a business of Ingersoll-Rand88

Page 47: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 45

series desiccant wheel + cooling coil

Dehumidify Space (Cool Air)heatingcoil

95 F DB78 F WB

72 F DPT

OA CC

coolingil

OA'

seriesd i t

52 F

© 2011 Trane, a business of Ingersoll-Rand89

coildesiccantwheel

CA58 F DB46 F DPT

180

160 h80

OA 95°F DB72°F DPT

series desiccant wheel + cooling coilDehumidify Space (Cool Air)

80

OA' 89°F DB75°F DPT

CC 52°F DB140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

50

55

60

65

dew

po

int tem

peratu

re, °F

OA'OA'OA'OA'

CACA

CC 52 F DB52°F DPT

CA 58°F DB46°F DPT

CCCC

OAOAOAOA

70

75

© 2011 Trane, a business of Ingersoll-Rand90

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACA

cooling energy saved

reheat energy saved

Page 48: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 46

1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)

2) Cooling Duty• Neutral air• Cool air• Cold air

3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency

4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)

© 2011 Trane, a business of Ingersoll-Rand91

series desiccant wheel + cooling coil

Dehumidify Space (Neutral Air)heatingcoil

95 F DB78 F WB

72 F DPT

OA CC

coolingil

OA'

reheatil

seriesd i t

© 2011 Trane, a business of Ingersoll-Rand92

CA

coil

75 F DB46 F DPT

coil desiccantwheel

Page 49: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 47

Parallel or Series?

energy wheel + cooling coil(parallel)• Exhaust air is available

for recovery• Deliver air at a cool (or cold)

series desiccant + cooling coil (series)• Required leaving-air

DPT < CHW temp + 5 F• Deliver air at a cool

© 2011 Trane, a business of Ingersoll-Rand93

temperature• Recoverable reheat (if needed)

energy is available

temperature• Recoverable reheat

energy is NOT available

1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)

2) Cooling Duty• Neutral air• Cool air• Cold air

3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency

4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)

© 2011 Trane, a business of Ingersoll-Rand94

Page 50: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 48

total-energy wheel + cooling coil + coil loop

Dehumidify Space (Cool Air)

CC

cooling

OA'

coil total-energy

EA''

46 F

EA'

© 2011 Trane, a business of Ingersoll-Rand95

95 F DB78 F WB

72 F DPT

OAg

coilloopgy

wheelCA58 F DB46 F DPT

75 F DB55% RH

EA

180

160 h80

OA 95°F DB72°F DPT

energy wheel + cooling coil + coil loopDehumidify Space (Cool Air)

80

OA' 75°F DB62°F DPT

CC 46°F DB46°F DPT

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

OAOAOAOA

50

55

60

65

70

75

dew

po

int tem

peratu

re, °F

OA'OA'OA'OA'

EAEA

75°F DB55% RH57°F DPT

EA

CA 58°F DB46°F DPT

CCCCEA'EA'

EA' 63°F DB57°F DPT

© 2011 Trane, a business of Ingersoll-Rand96

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACA

CCCC

Page 51: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 49

total-energy wheel + cooling coil + fixed-plate HX

Dehumidify Space (Cool Air)

CC

cooling

OA'

fixed-plateHX

total-energy

EA''

EA'68 F

© 2011 Trane, a business of Ingersoll-Rand97

95 F DB78 F WB

72 F DPT

OAg

coilgy

wheel

EA75 F DB55% RH

70 F DB46 F DPT

CA

total-energy wheel + cooling coil + parallel desiccant wheel

Dehumidify Space (Cool Air)95 F DB78 F WB72 F DPT

coolingcoil

reheatcoil

OACC

OA'

total-energywheel

55 F DB46 F DPT

CA

EA''

EA'

desiccantwheel EA

70 F DB72% RH

51 F

© 2011 Trane, a business of Ingersoll-Rand98

75 F DB55% RH

EA

Page 52: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 50

180

160 h80

OA 95°F DB72°F DPT

energy wheel + cooling coil + parallel desiccant wheelDehumidify Space (Cool Air)

80

OA' 78°F DB65°F DPT

CC 51°F DB51°F DPT

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

OAOAOAOA

50

55

60

65

70

75

dew

po

int tem

peratu

re, °F

OA'OA'OA'OA'

EAEA

75°F DB55% RH57°F DPT

EA

CA 55°F DB46°F DPT

EA'EA'

EA' 70°F DB61°F DPT

CACA

© 2011 Trane, a business of Ingersoll-Rand99

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACACCCC

180

160 h80

OA 72°F DB68°F DPT

energy wheel + cooling coil + parallel desiccant wheelDehumidify Space (Cool Air)

80

OA' 71°F DB62°F DPT

CC 51°F DB51°F DPT

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

OAOAOAOA

50

55

60

65

70

75

dew

po

int tem

peratu

re, °F

CACAEAEA

75°F DB55% RH57°F DPT

EA

CA 55°F DB46°F DPT

EA'EA'

EA' 70°F DB61°F DPT

cooling energy savedOA'OA'OA'OA'

© 2011 Trane, a business of Ingersoll-Rand100

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACACCCC

cooling energy saved

reheat energy saved

Page 53: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 51

total-energy wheel + cooling coil + parallel desiccant wheel

Dehumidify Space (Cool Air)95 F DB78 F WB72 F DPT

coolingcoil

reheatcoil

OACC

OA'

total-energywheel

55 F DB46 F DPT

CA

EA''

EA'

desiccantwheel( ll l)

EA

70 F DB72% RH

51 F

© 2011 Trane, a business of Ingersoll-Rand101

75 F DB55% RH

(parallel)EA

total-energy wheel + cooling coil + series desiccant wheel

Dehumidify Space (Cool Air)95 F DB78 F WB72 F DPT

desiccant( )72 F DPT

OA

CC

coolingcoil

OA'

total-energywheel CAEA'

OA''

wheel (series)

EAreheat

coil

© 2011 Trane, a business of Ingersoll-Rand102

75 F DB55% RH

57 F DB46 F DPT

Page 54: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 52

180

160 h80

OA 95°F DB72°F DPT

energy wheel + cooling coil + series desiccant wheelDehumidify Space (Cool Air)

80

OA' 81°F DB63°F DPT

OA'' 77°F DB67°F DPT

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

OAOAOAOA

50

55

60

65

70

75

dew

po

int tem

peratu

re, °F

OA'OA'OA'OA'

EAEA

CC 52°F DB52°F DPT

75°F DB55% RH57°F DPT

EA

CA 57°F DB46°F DPT OA''OA''

CACACCCC

© 2011 Trane, a business of Ingersoll-Rand103

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACACCCC

180

160 h80

OA 72°F DB68°F DPT

energy wheel + cooling coil + series desiccant wheelDehumidify Space (Cool Air)

80

OA' 74°F DB62°F DPT

OA'' 70°F DB64°F DPT

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

50

55

60

65

70

75

dew

po

int tem

peratu

re, °F

OA'OA'OA'OA'

EAEA

CC 51°F DB51°F DPT

75°F DB55% RH57°F DPT

EA

CA 55°F DB46°F DPT

OA''OA''

CACA

OAOAOAOAcooling energy saved

© 2011 Trane, a business of Ingersoll-Rand104

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACACCCC

cooling energy saved

reheat energy saved

Page 55: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 53

180

160 h80 80

energy wheel + cooling coil + downstream desiccant wheel

Parallel vs. Series

80

140

120

100

80

60

hu

mid

ity ratio, g

rains/lb

of d

ry ai

70

50

60

OAOAOAOA

50

55

60

65

70

75

dew

po

int tem

peratu

re, °F

OA'OA'OA'OA'

OAOAOAOA

OA'OA'OA'OA'

OA''OA''seriesparallel

© 2011 Trane, a business of Ingersoll-Rand105

40

20

ir

11030 40 50 60 70 80 10090

dry-bulb temperature, °F

40

30 30

40CACA

CCCC

30

energy wheel + cooling coil + downstream desiccant wheel

Parallel vs. Series

cooling leaving-aircoil load conditions

52 tons 55°F DB46°F DPT

41 t 55°F DB

outdoor airconditions

95°F DB48% RH

72°F DB

cooling leaving-aircoil load conditions

49 tons 57°F DB46°F DPT

41 t 55°F DB

parallel series

© 2011 Trane, a business of Ingersoll-Rand106

41 tons 55°F DB46°F DPT

23 tons 55°F DB46°F DPT

72°F DB88% RH

60°F DB95% RH

41 tons 55°F DB46°F DPT

32 tons 55°F DB46°F DPT

Page 56: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 54

energy wheel + cooling coil + downstream desiccant wheel

Parallel vs. Series

desiccant wheel in parallel• Better on mild, humid days• Horizontal duct connections

desiccant wheel in series• Better on hot and warm days• Ratio of EA/OA flows < 0.9• High external static pressures

© 2011 Trane, a business of Ingersoll-Rand107

1) Dehumidification Duty 3) Efficiency Target• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)

2) Cooling Duty• Neutral air• Cool air• Cold air

3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency

4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)

© 2011 Trane, a business of Ingersoll-Rand108

Page 57: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 55

Dedicated OA Cooling Sources

35°F 40°F 45°F 50°F 60°F

Dew Point of Conditioned Outdoor Air (CA)

55°F35 F 40 F 45 F 50 F 60 F55 F

60% space RH

50% space RH

Dew point required

packaged DX

split DX system

Dew point capability

© 2011 Trane, a business of Ingersoll-Rand109

chiller + AHU

split DX system

specialty dehumidifier

considerations for

Packaged DX Dedicated OA Equipment

Air-cooled or water-cooled condensing

Required leaving-air dew point• Reheat only as much as necessary

• Cool or cold air reduces capacity of local equipment

© 2011 Trane, a business of Ingersoll-Rand110

packaged DXdedicated OA unit

Page 58: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 56

Packaged vs. Split DX

Pre engineered Local design to the

Packaged DX Unit Split DX System

Pre-engineered

Laboratory tested

Smaller footprint

Integral reheat andhot gas bypass

Local design to the specific application

Potentially long line lengths (and more refrigerant)

Difficult reheat design

Indoor or outdoor location

© 2011 Trane, a business of Ingersoll-Rand111

HGBP line length

Oil management

DX Compressor Unloading

Single, on/off compressor

Single, unloading compressor (including pulsed)

Single, variable-speed compressor

Manifolded, on/off compressors

Manifolded compressors, one unloading

Manifolded compressors, one variable speed

© 2011 Trane, a business of Ingersoll-Rand112

Page 59: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 57

ASHRAE Standard 90.1-2010

Hot Gas Bypass

“6.5.9 Hot Gas Bypass Limitation. Cooling systems shall not use hot gas bypass or other evaporatorshall not use hot gas bypass or other evaporator pressure control systems unless the system is designed with multiple steps of unloading or continuous capacity modulation. The capacity of the hot gas bypass shall be limited as indicated in Table 6.5.9.”

© 2011 Trane, a business of Ingersoll-Rand113

hot gas reheat

Refrigerant Heat Recovery

Prudent to use recovered heat for reheat

Deliver conditioned outdoor cold, if possible

For a split DX system:• Design reheat coil for little reheat

• Actively control head pressure

• Pay particular attention to oil management

© 2011 Trane, a business of Ingersoll-Rand114

Page 60: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 58

Split DX System Selection

18

Assumptions:• 200 Btu/h/person latent load• 75°Fspace temperature

16

14

12

10

8

• 75 F space temperature

© 2011 Trane, a business of Ingersoll-Rand115

35 40 45

saturated suction temperature, °F

6

50

Chilled-Water DOAS

Standalone or shared chiller

Air-cooled or water-cooled

Indoor or outdoor equipment

© 2011 Trane, a business of Ingersoll-Rand116

Page 61: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 59

Benefits of Chilled-Water DOAS Can achieve lower dew points

Wider operating envelope

Especially when using variable airflow• Especially when using variable airflow

• DX equipment often requires hot gas bypass (energy waste)

Greater flexibility and efficiency

• Fans, air cleaning, energy recovery, desiccant wheel, airflow measurement, ice storage, potential to eliminate HGBP

© 2011 Trane, a business of Ingersoll-Rand117

Certified performance

• AHRI, UL, ETL

• No AHRI certification for DX dedicated OA units (EER’s typically not published)

Reduced refrigerant charge

OA

air-handling unit

CA

oo

p r

etu

rn

Vreheat

t t t

up

ply

© 2011 Trane, a business of Ingersoll-Rand118

Pload

lo

Psource load-sideheat exchanger

source-sideheat exchanger

water-to-waterheat pump

loo

p s

Page 62: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 60

OA

air-handling unit

CAu

pp

ly

oo

p r

etu

rn

i l d

© 2011 Trane, a business of Ingersoll-Rand119

loo

p slo

Psource evaporator

air-cooledchiller

© 2011 Trane, a business of Ingersoll-Rand120

Page 63: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 61

Dedicated Outdoor-Air Equipment

Summary

dedicated outdoor-air equipment

Which Configuration is Best?

1) D h idifi ti D t1) Dehumidification Duty• Dehumidify ventilation only• Dehumidify space (comfort)• Dehumidify space (condensation)

2) Cooling Duty• Neutral air• Cool air• Cold air

3) Efficiency Target• Code / ASHRAE 90.1 minimum• Higher efficiency

4) Cooling Source• Shared chiller plant• Dedicated chiller• Direct expansion (DX)

© 2011 Trane, a business of Ingersoll-Rand122

Cold air Direct expansion (DX)

Page 64: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 62

dedicated outdoor-air equipment

Which Configuration is Best?

1 2 3 4+ + + = no silver bullet!

packaged DXdedicated OA unit

indoor

© 2011 Trane, a business of Ingersoll-Rand123

air-handling unit

outdoorair-handling unit

references for this broadcast

Where to Learn More

© 2011 Trane, a business of Ingersoll-Rand124

www.trane.com/EN

Page 65: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 63

LEED Continuing Education Courseson-demand, no charge, 1.5 CE credits

ASHRAE Standards 62.1 and 90.1 d VAV S tand VAV Systems

ASHRAE standard 62.1: Ventilation Rate Procedure

ASHRAE 90.1-2010

Energy Saving Strategies for Rooftop VAV Systems

Air-Handing Systems, Energy and IAQ

Central Geothermal System Design and Control

© 2011 Trane, a business of Ingersoll-Rand125

Central Geothermal System Design and Control

Ice Storage Design and Control

www.trane.com/ContinuingEducation

watch past broadcasts

ENL Archives

Insightful topics on HVAC system design:• Chilled-water plants• Air distribution• Refrigerant-to-air systems• Control strategies• Industry standards and LEED• Energy and the environment• Acoustics• Ventilation• Dehumidification

© 2011 Trane, a business of Ingersoll-Rand126

www.trane.com/ENL

Page 66: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 64

2012 ENL Programs

MarchHi h P f G B ildi Th I t fHigh Performance Green Buildings: The Impact of ASHRAE Standard 189.1-2011

JuneHeat Pump Systems

OctoberAir-to-Air Energy Recovery

© 2011 Trane, a business of Ingersoll-Rand127

Dedicated Outdoor-Air Equipment

Supplemental Slides

Page 67: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 65

Dedicated OA System Configurations

Conditioned OA delivered…

1. Directly to each zone

2. To intake of each local unit

3. To supply-side of each local unit

4. To ceiling plenum, near each local unit

© 2011 Trane, a business of Ingersoll-Rand129

conditioned OA delivered

Directly to Each Zone

dedicatedOA

dedicatedOA unit

CACA CACA

CACA

• fan-coil• WSHP

© 2011 Trane, a business of Ingersoll-Rand130

RA

SA

RA

SA

WSHP• PTAC• passive chilled beams• radiant cooling panels

Page 68: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 66

conditioned OA delivered

Directly to Each Zone

Advantages

Easier to ensure required outdoor airflow reaches each

Drawbacks

Requires installation of additional ductwork and

zone (separate diffusers)

Opportunity to cycle off local fan because OA is not distributed through it

Allows dedicated OA system to operate during unoccupied periods without needing to

separate diffusers

May require multiple diffusers to ensure that outdoor air is adequately dispersed throughout the zone

© 2011 Trane, a business of Ingersoll-Rand131

operate local fans

Opportunity to downsize local equipment (if OA delivered cold)

conditioned OA delivered

To Intake of Local HVAC Equipment

dedicateddedicatedOA unitOA

SASA SASARARA RARA

CACA

• fan-coil• WSHP• small RTU• VRF

© 2011 Trane, a business of Ingersoll-Rand132

Page 69: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 67

conditioned OA delivered

To Intake of Local HVAC Equipment

Advantages

Helps ensure required OA reaches each zone (ducted

Drawbacks

Measurement and balancing is more difficult than if OA (

directly to each unit)

Avoids cost and space to install additional ductwork and separate diffusers

Easier to ensure that OA is adequately dispersed throughout zone because it is

delivered directly to zone

Typically requires field-fabricated plenum to connect OA duct to mix with RA

Local fan must operate continuously to provide OA during scheduled occupancy

© 2011 Trane, a business of Ingersoll-Rand133

distributed by local fan Local fan must operate if dedicated OA system operates during unoccupied period

conditioned OA delivered

To Supply-Side of Local HVAC Equipment

dedicateddedicatedOA unitOA

SASA SASARARA RARA

CACACACA

• fan-coil• WSHP• small RTU

© 2011 Trane, a business of Ingersoll-Rand134

direct tospaces

Page 70: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 68

conditioned OA delivered

To Supply-Side of Local HVAC Equipment

Advantages

Helps ensure required OA reaches each zone (ducted

Drawbacks

Measurement and balancing is more difficult than if OA (

directly to each unit)

Avoids cost and space to install additional ductwork and separate diffusers

Easier to ensure that OA is adequately dispersed throughout zone because it is

delivered directly to zone

Local fan typically must operate continuously to provide OA during scheduled occupancy (unless pressure-independent VAV terminal)

© 2011 Trane, a business of Ingersoll-Rand135

distributed by local fan

Opportunity to downsize local equipment (if OA delivered cold)

conditioned OA delivered

To Plenum, Near Local HVAC Equipment

dedicateddedicatedOA unitOA

SASA SASARARA RARA

CACA

• fan-coil• WSHP• VRF

© 2011 Trane, a business of Ingersoll-Rand136

Page 71: Agenda and Objectives - Trane · PDF file · 2018-03-03been dehumidification and air‐to‐air energy recovery design. ... at the conclusion of this presentation. ... by containing

Engineers Newsletter Live

Dedicated Outdoor-Air Equipment© 2011 Trane, a business of Ingersoll-Rand 69

conditioned OA delivered

To Plenum, Near Local HVAC Equipment

Advantages

Avoids cost and space to install additional ductwork and

Drawbacks

More difficult to ensure required OA reaches each zone (not

separate diffusers(

ducted directly)• Refer to Figure 5-E and 5-F of

ASHRAE 62.1-2010 User’s Manual

Local fan must operate continuously to provide OA during scheduled occupancy

Conditioned OA not able to be d li d t ld t t

© 2011 Trane, a business of Ingersoll-Rand137

delivered at a cold temperature due to concerns over condensation