  • FORM 100.09-EG1 (100)

    27446A

    INDOOR CENTRAL STATION AIR HANDLING UNITS

    MA

    NU

    FAC

    TU

    RER

    CERT

    IFIEDTO ARI AS

    COM

    PLY

    ING

    WIT

    H

    ARI STANDARD43

    0

    CE

    NT

    RA

    LST

    ATION AIR-H

    AN

    DLIN

    G

    UNITS

    AIRPAKAIR HANDLING UNITS

    28669a

  • YORK INTERNATIONAL2

    TABLE OF CONTENTS

    GENERAL DESCRIPTION .............................................. 3Unit Description .......................................................... 3Quality ......................................................................... 3Flexibility ...................................................................... 3Serviceability ............................................................... 3Construction ............................................................... 3Unit Design Summary ................................................ 4Variable Air Volume Application .................................. 7Factory-Packaged Controls ........................................ 8Integrated Systems Network ...................................... 9Segment Availability .................................................... 10Nomenclature ............................................................. 11

    QUICK SELECTION TABLES .......................................... 12CDW Coils .................................................................. 12BDW Coils .................................................................. 12Forward Curved Fans ................................................. 13Dimensions and Weights .......................................... 14

    ENGINEERING DATA ....................................................... 16Forward Curved & Airfoil Fan and

    Motor Data...............................................................

    16Plenum Fan ................................................................ 17Variable Inlet Vanes Operating Torques (DWDI) ........ 18SWSI Plenum Fan Operating Torques ....................... 19Coil Data ..................................................................... 20Multi-Zone Coil Data ................................................... 21Flat Filter and Open Return Filter Segments ............. 22Angle, Filter/Mix. Box, Economizer Filter Segments ... 23Bag Filter and Rigid Filter Segments ......................... 24HEPA Filter Segments ................................................ 25Carbon Filter Segments ............................................. 26Damper Data .............................................................. 27

    Mixing Box/Filter Mixing Box Economizer ............... 27Internal Face & Bypass .......................................... 27External Face & Bypass ......................................... 28Face Damper Data ................................................ 28Damper Leakage Data .......................................... 29Blender Data .......................................................... 29

    Sound Attenuator ........................................................ 31Carbon Filter Design & Performance ......................... 32Electric Heater Design & Performance ...................... 33Min. Air Velocity for Open Coil-type Heaters ............... 33

    UNIT SELECTION ........................................................... 34Selecting an AirPak Unit ............................................. 34Reference Literature ................................................... 35Altitude/Temperature Conversion Factors ................. 35

    AIR PRESSURE DROP ................................................... 36Instructions ................................................................. 36Static Pressure Schematics ....................................... 36Turbofin CDW or CDX for Cooling & Dehumidifying .. 38Turbofin CDW for Heating & CDW or CDX for

    Sensible Cooling....................................................

    38Free-Flow BDW or BDX for Cooling & Dehumidifying 39Free-Flow BDW for Heating & BDW or BDX for

    Sensible Cooling....................................................

    39Air Blender .................................................................. 40Steam Distributing ...................................................... 40

    Electric Heater Air Pressure Drop .............................. 40Diffuser ....................................................................... 40Vertical Casing Pressure Loss .................................. 40Attenuator .................................................................... 40Filter ............................................................................ 40Carbon Filter Air Pressure Drop ................................. 41Mixing Box Damper/Filter Mixing Box/ Economizer And External Face and Bypass Damper ................ 41Internal Face and Bypass Damper Bypass ............ 42Internal Face and Bypass Damper Face ................ 43Face Damper Segment And External Face and Bypass Damper ............................................... 44Multi-Zone ................................................................... 45

    SEGMENT DIMENSIONS ................................................ 46FS Supply Fan Segment .......................................... 46FP Plenum Fan Segment ........................................ 48Coils (SC, MC, LC, XC, HC) ........................................ 50VC Vertical Coil Segment ........................................ 51IC Internal Face & Bypass Coil Segment ............... 52Filter Dimensions (OF, FF, AF, RF, BF, HF, CF) .......... 53FM Filter/ Mixing Box Segment ................................. 56MB Mixing Box Segment .......................................... 57FR Return Fan Segment ......................................... 58FE Exhaust Fan Segment ........................................ 60AB Air Blender Segment .......................................... 62EE Economizer Segment ........................................ 63EF Filter / Economizer .............................................. 64SA, MA, LA Access Segment ................................... 65IB Internal Face & Bypass Damper Segment ........ 66EB External Face & Bypass Segment ..................... 67FD Face Damper Segment ..................................... 68AT Sound Attenuator Segment ................................ 69DI Diffuser Segment ............................................... 70DP Discharge Plenum Segment ............................ 71VP Vertical Plenum .................................................. 72MZ Multi-Zone .......................................................... 73EH Electric Heat ....................................................... 74IO Inlet / Outlet .......................................................... 75

    PHYSICAL DATA .............................................................. 76AirPak Segment Overall Dimensions &

    Weight Calculations .............................................. 76AirPak Segment Weights ........................................... 77Coil Weights ............................................................... 78IC Coil Connection Locations .................................... 83Water Coil Connection Locations .............................. 84Steam Coil Connection Locations ............................. 86Water Coil Dimensions .............................................. 87Inlet Cone Dimensions .............................................. 88Unit & Coil Hand Selection ......................................... 89

    MISCELLANEOUS DATA ................................................. 90Power Wiring Options ................................................. 90Typical Electric Heater Wiring Diagram...................... 91

    GUIDE SPECIFICATIONS ................................................ 92Part 1 General .......................................................... 92Part 2 Products ........................................................ 93Part 3 Execution ....................................................... 98

    PAGE PAGE

  • YORK INTERNATIONAL 3

    FORM 100.09-EG1General Description

    UNIT DESCRIPTION

    The YORK AirPak introduces a new level of quality, flex-ibility, and serviceability to the HVAC industry.

    QUALITY

    AirPak units are available with single wall and/or doublewall panels. Panels are available with a variety of insula-tion. Double wall panels have a full 2 inches of insulationwith solid or perforated lining. The additional option of 4inch panels are available in discharge segments for acous-tical application. Insulation and liners can be mixed andmatched to meet a variety of applications.

    The AirPak coil drain pan is designed to meet the intentof Indoor Air Quality (IAQ) requirements. The pan is 4inches deep with a V-shaped design that reduces stand-ing condensate. The pan has a full 2 inches of insulationto give the pan the thermal protection it requires. IndoorAir Quality drain pans (optional) are sloped in all direc-tions with a single drain connection to minimize standingcondensate. Auxiliary drain pans are available in everysection. Intermediate drain pans are provided on all cool-ing coils that exceed 48 inches in finned height.

    FLEXIBILITY

    For maximum flexibility the AirPak is based on a seg-mented design concept. The unit construction is unit-ized, built as a single unit, for greater unit integrity. Theunit may be split per customer defined needs if required,to meet various shipping and job site requirements.

    The unitized construction means that each unit is builtas a unit, not as a assembly of segments. This addsintegrity to the unit and decreases the opportunity forunit air leakage by greatly reducing the number of sheetmetal joints.

    A complete line of Factory-Packaged Controls are avail-able with the YORK AirPak. Factory Packaged Controlsassures the customer of single source responsibility, lowerfirst cost and high quality. YORK International now fea-tures an RS-232 PROTOCOL that can communicate withany Building Automation System on the job site.

    SERVICEABILITY

    The AirPak features unparalleled accessibility. All AirPakpanels (single or double wall) are completely removableas a single piece assemble. This eliminates the timeconsuming practice of removing the interior and exteriorpanels as separate pieces.

    Access doors are available throughout the unit for ac-cess. The fan and filter segments come equipped withaccess doors as a standard feature.

    The YORK AirPak can also be offered with Quick-Con-nect Fasteners on the side access panels on most unitsizes. The unique YORK panel latching system allowspanels to be removed and replaced in a matter of sec-

    AIRPAK IAQ COIL DRAIN PAN REMOVABLE ACCESS PANELS

    00088VIP

    LD02600

  • YORK INTERNATIONAL4

    General Description

    CONSTRUCTION

    The YORK AirPak design and construction is unequaledin quality and serviceability. Its unique design gives thestrength and durability for industrial applications and thecomplete serviceability that can only be found in the YORKAirPak.

    AIRPAK (PANELS REMOVED)

    UNIT DESIGN SUMMARY

    Unitized Construction

    The design and application concept of the AirPak allowsthe designer the flexibility to arrange individual segmentsfor a variety of applications. Each unit is then engineeredand built as a single piece of equipment. This results insuperior integrity when compared to units utilizing mod-ules (sections) that are connected with sheet metalscrews to form a unit.

    Each individual unit is custom designed to minimize thenumber of panels in the unit. This decreases the opportu-nity for air leakage and assures better unit integrity.

    onds with a simple hand tool. The Quick Connect Fas-teners allow for easier and more complete unit access.The panels can also be removed in tight clearance areasthat do not permit normal door operation. This is an ex-clusive feature of the YORK AirPak.

    27509A

    LOW LEAKDAMPERS

    SPRING RETURNDAMPER ACTUATOR(OPTIONAL)

    4" DEEP"V" SHAPEDDRAIN PAN

    STRUCTURALBASE CHANNEL

    INTERNALSPRINGISOLATION

    CAST ALUMINUMCORNER CONNECTOR

    FILTER /MIXINGBOX

    HEATINGCOIL

    MEDIUMCOIL

    FANSEGMENT

  • YORK INTERNATIONAL 5

    FORM 100.09-EG1

    AIRPAK UNIT FRAME

    AIRPAK UNITIZED CONSTRUCTION

    Full Perimeter Base Rail Channel

    The AirPak is completely supported by a full-perimeterbase rail channel. The base rail is constructed of heavygage galvanized steel and has intermediate cross- mem-bers for unit support. The base rail gives support to theinternal components and protects the unit during ship-ment and installation. The base rail also provides addi-tional height for job site trapping of condensate drain pans.

    Unit Frame

    The rugged unit frame gives the unit industrial quality anddurability. The integral frame permits the unit panels tobe removed without affecting the integrity of the unit. Af-ter all of the panels have been removed, the frame re-mains to support the internal components.

    28669AR

    26744A

  • YORK INTERNATIONAL6

    General Description

    Cast Aluminum Corner Post

    The rugged cast aluminum corner posts add strength andrigidity to the unit. The beveled corner finish also symbol-izes the comprehensive engineering, style and quality ofthe YORK AirPak.

    Removable Panels

    All of the AirPak panels are completely removable with-out affecting the structural rigidity of the unit. As an op-tion, the panels can be provided with Quick-Connect Fas-teners on the side access panels for most unit sizes.The removable panels reduce the time required to serviceand clean components - which is an important part ofmaintaining good Indoor Environmental Quality.

    AIRPAK CORNER CONNECTOR

    Full Length and Height Raceway Channels

    The fully insulated, double-wall raceway channels tie theentire unit together by connecting the corner posts, unitframe and base rail. The raceway also creates the panelsealing.

    QUICK CONNECT FASTENER26833A, 26832A

    RACEWAY CHANNELS26753A

    28759A

    REMOVABLE ACCESS PANELS (CUTAWAY)

    Quick Connect Fastener

    The Quick-Connect Fastener is the key to the optionalpanel removal system. The latch is operable with a simplewrench. The motion of the latch is 180 degrees. The first90 degrees moves the lever arm to a sealing position onthe frame and the second 90 degrees pulls the latch snug,creating the panel seal.

    26757A

    RACEWAYCHANNELS

  • YORK INTERNATIONAL 7

    FORM 100.09-EG1

    VARIABLE AIR VOLUME APPLICATIONS

    Factory mounted variable frequency drives (YORK Air-Modulator) and variable inlet vanes are available with theYORK AirPak for Variable Air Volume Applications.

    YORK Air-Modulator (Variable Frequency Drive):

    The YORK Air-Modulator (variable frequency drive) offersthe most efficient means of fan control for variable airvolume systems. The Air-Modulator varies the speed ofthe fan to match the VAV load requirements.

    The Air-Modulator takes maximum advantage of the rela-tionship between fan speed and fan horsepower. Withthe Air-Modulator, any given reduction in fan speed re-sults in a cubic reduction in fan horsepower. For example,a 10% speed reduction results in a 27% fan horsepowerreduction!

    The Air-Modulator offers the following benefits over vari-able inlet vanes and discharge dampers: Extended Equipment Life - soft start of motor and fan. Quieter Fan Operation - fan operating at reduced speed

    and constant line of efficiency. Eliminates need for starter panels. Improved system control and response - DDC Controls

    with LED Digital Display. Available on all unit sizes as a factory mounted op-

    tion. Proven Reliability.

    YORK will balance the fan for the entire range of opera-tion (10 - 100% RPM) for added reliability. Actual fan turn-down will vary with fan type and selection.

    Variable Inlet Vanes

    Variable inlet vanes are another method of energy effi-cient fan control. While the fan runs at a constant speed,the inlet vanes modulate the air entering the fan. Thisproduces a reduced air volume which results in loweroperating horsepowers.

    Variable inlet vanes are available on all Airfoil fans, Ple-num fans and Forward Curved fans sizes 12 x 12 andlarger.

    The vanes are located within each inlet cone of Airfoilfans, Plenum fans, and adjacent to the inlet ring of For-ward Curved fans. The vanes consist of a series of radialdamper blades which operate in parallel and are con-trolled by a common control shaft which extends to theoutside of the fan. YORK AIR-MODULATOR WITH OPTIONS PANEL

    For additional information on the Air-Modulator, refer toForm 100.04-EG1.

    27447A

  • YORK INTERNATIONAL8

    General Description

    AIRPAK AIR HANDLING UNIT WITH FACTORY PACKAGEDCONTROLS (FPC) AND INTEGRATED SYSTEMS NETWORK (ISN) PANEL

    FACTORY-PACKAGED CONTROLSFactory EngineeredYORK Factory-Packaged Controls assures you of get-ting a complete factory-engineered system no surprises,no hassles, and no compromises. The control system isdesigned with each specific piece of equipment in mind.This assures you that the system will control, monitorand diagnose only those points that are necessary tomaintain optimum performance.

    Reduce CostsYORK Factory-Packaged Controls reduce costs by tak-ing the guesswork out of control installation. Each con-trol is mounted in the factory as the equipment is beingmanufactured. There are no worries over job site loca-tions or conditions. Factory labor means faster assem-bly and lower first cost.

    AIRPAK MIXING BOX WITH DAMPER ACTUATOR

    27446A

    26750A

    Quality ControlYORK Factory-Packaged Controls assure you of gettinga higher quality control system, right from the factory.The control system is designed and mounted followingthe same stringent quality control standards by whichthe units are built.

    Single Source ResponsibilityWhen an air unit with field-applied controls develops aproblem, getting some answers and action can be diffi-cult. The controls supplier believes the equipment manu-facturer is responsible, and vice versa. With YORKFactory-Packaged Controls there is only one companyto call YORK.

    Full Service SupportBecause YORK Factory-Packaged Controls are an inte-gral part of the equipment, who better to troubleshootand service the system than a professional YORK Ser-vice technician. The YORK Service technician knows notonly the equipment and the controls hardware, but healso has a working knowledge of equipment applicationand operation. Every unit is backed by this kind of pro-fessional support.

    Stand-Alone Or Network ControlYORK Factory-Packaged Controls offer you the flexibil-ity of stand-alone or network control. Each unit has anintegral time clock and a full-featured array of optimiza-tion and diagnostic function. Included with the controls isthe capability to tie into a YORK Integrated SystemsNetwork (ISN). For further information see Form450.11-EG1.

  • YORK INTERNATIONAL 9

    FORM 100.09-EG1

    INTEGRATED SYSTEMS NETWORK (ISN)

    The YORK Integrated Systems Network (ISN) is thecomplete integration of airside, chiller, and building auto-mation controls. YORK Factory-Packaged Controlsmake it easy to upgrade from a group of air handlingunits operating individually to an ISN airside system, withall the units operating in concert. Thats because eachunit is able to share information with all the other units onthe network.

    Theres no need to duplicate or replace existing sensorsand actuators. Instead, a twisted pair of wires connects

    YORK INTEGRATED SYSTEMS NETWORK (ISN)INTEGRATED SYSTEMS NETWORK (ISN)CONTROL CENTER

    each unit control center with the central control center,which can coordinate the operation of the entire air han-dling system. Other YORK airside and waterside equip-ment can also be integrated into the system.

    No longer will HVAC equipment be responding as a col-lection of individual devices, but rather as a network theYORK Integrated Systems Network.

    26363ALD04321

  • YORK INTERNATIONAL10

    General Description

    SEGMENT AVAILABILITY

    LD04293

  • YORK INTERNATIONAL 11

    FORM 100.09-EG1

    SEGMENT IDENTIFICATION

    Unit Type: AP - AirPak Central Station

    Air Handling Unit

    Fan Segment:

    FS - Supply Fan FR - Return Fan FE - Exhaust Fan

    Fan Types: Forward Curved Fan

    Standard Class II

    Airfoil Standard Class II

    FP - SWSI Plenum FanFan Types: Airfoil

    Standard Class II

    Coils (Contd.)Access Segments: SA - Short Access (12") MA - Medium Access (18") LA - Long Access (24")Accessory Segments: AT - Attenuator (3', 5' & 7') Dl - Diffuser AB - Air Blender DP - Discharge Plenum FD - Face Damper IO - Inlet / Outlet VP - Vertical Plenum EH - Electric Heat (24" & 36")Bypass Segments: IB - Internal Face & Bypass EB - External Face & BypassCoil Segments: SC - Short Coil (10" Coil Space) MC - Medium Coil (20" Coil Space) MZ - Multi-Zone

    LC - Long Coil (28" Coil Space) XC - Extra-Long Coil (36" Coil Space) HC - Heating Coil (8" Coil Space) VC - Vertical Coil (20" Coil Space) IC - Integral Face & Bypass Coil

    Filter Segments: OF - Open Return Filter (2" & 4") FF - Flat Filter (2" & 4") AF - Angle Filter (2" & 4") BE - Bag Filter (21" & 32") w / 2" or 4" Pre-filters RF - Rigid Filter (12") w / 2" or 4" Pre-filters HF - HEPA Filter CF - Carbon Filter

    Mixing Box Segments: FM - Filter / Mixing Box MB - Mixing Box EE - Economizer EF - Filter / Economizer

    NOMENCLATUREAIR FLOW

    AP 120 FS 15 x 11 (AF) (MB)

    Fan Size

    AB - Air BlenderAF - Angle Filter (2" & 4")AT - Attenuator (3', 5', 7')BF - Bag Filter (21" & 32")CF - Carbon FilterDl - DiffuserDP - Discharge PlenumEB - External Face & BypassEE - EconomizerEF - Filter / EconomizerEH - Electric Heat (24" & 36")FD - Face DamperFF - Flat Filter (2" & 4")FM - Filter / Mixing Box (2" & 4")HC - Heating Coil (8")HF - HEPA Filter

    IB - Internal Face & BypassIC - Integral Face & BypassIO - Inlet / OutletLA - Long Access (24")LC - Long CoilMA - Medium Access (18")MB - Mixing BoxMC - Medium CoilMZ - Multi-ZoneOF - Open Return Filter (2" & 4")RF - Rigid Filter (12")SA - Short Access (12")SC - Short CoilVC - Vertical Coil (20")VP - Vertical PlenumXC - Extra-Long Coil (36")

    Accessories

    Unit Size35 30560 36080 400

    105 500120 580150 660170 800215 1000250

    Unit Type AP - AirPak

    FS - Supply Fan (Standard)FS II - Supply Fan (Class II)FE - Exhaust Fan (Standard)FE II - Exhaust Fan (Class II)FR - Return Fan (Standard)FR II - Return Fan (Class II)FP - Plenum Fan (Standard)FP II - Plenum Fan (Class II)

    Fan Segment

    SWSIFC Fans AF Fans Plenum Fans9x6 20x18 28x28 12 28 20 409x9 20x20 30x30 15 32 24 44

    10x10 22x20 32x32 18 36 27 4912x12 22x22 20 40 30 5415x11 25x22 22 44 33 6015x15 25x25 25 36 6618x18 27x25

  • YORK INTERNATIONAL12

    Quick Selection Tables

    CDW COILS (5/8" O.D.)

    UNIT FACE VELOCITY - FPM COIL COIL

    SIZE DIMENSIONS FACE

    AP 450 475 500 525 550 575 (INCHES) AREA

    CFM FH FL (SQ. FT.)35 1,527 1,612 1,697 1,782 1,867 1,952 21.25 23.00 3.460 2,470 2,607 2,744 2,881 3,018 3,156 27.25 29.00 5.580 3,406 3,595 3,785 3,974 4,163 4,352 27.25 40.00 7.6

    105 4,538 4,798 5,042 5,294 5,546 5,798 30.25 48.00 10.1120 5,388 5,688 5,987 6,286 6,586 6,885 30.25 57.00 12.0150 6,617 6,985 7,352 7,720 8,088 8,455 30.25 70.00 14.7170 7,585 8,007 8,428 8,849 9,271 9,692 33.25 73.00 16.9215 9,567 10,099 10,630 11,162 11,693 12,225 39.25 78.00 21.3250 11,030 11,642 12,255 12,868 13,481 14,093 45.25 78.00 24.5305 13,570 14,324 15,078 15,832 16,586 17,340 48.25 90.00 30.2360 16,172 17,070 17,969 18,867 19,766 20,664 57.50 90.00 35.9400 17,969 18,967 19,965 20,964 21,962 22,960 57.50 100.00 39.9500 22,225 23,460 24,694 25,929 27,164 28,399 63.50 112.00 49.4580 26,425 27,893 29,361 30,829 32,297 33,765 75.50 112.00 58.7660 29,728 31,380 33,031 34,683 36,334 37,986 75.50 126.00 66.1800 35,634 37,614 39,594 41,573 43,553 45,533 90.50 126.00 79.2

    1000 45,199 47,710 50,221 52,732 55,243 57,755 108.75 133.00 100.4

    BWD COILS (1/2" O.D.)

    UNIT FACE VELOCITY - FPM COIL COIL

    SIZE DIMENSIONS FACE

    AP 450 475 500 525 550 575 (INCHES) AREA

    CFM FH FL (SQ. FT.)35 1,438 1,517 1,597 1,677 1,757 1,837 20.00 23.00 3.260 2,492 2,631 2,769 2,908 3,046 3,184 27.50 29.00 5.580 3,438 3,628 3,819 4,010 4,201 4,392 27.50 40.00 7.6

    105 4,500 4,750 5,000 5,250 5,500 5,750 30.00 48.00 10.0120 5,344 5,641 5,938 6,234 6,531 6,828 30.00 57.00 11.9150 6,563 6,927 7,292 7,656 8,021 8,385 30.00 70.00 14.6170 7,414 7,826 8,238 8,650 9,062 9,474 32.50 73.00 16.5215 9,141 9,648 10,156 10,664 11,172 11,680 37.50 78.00 20.3250 10,969 11,578 12,188 12,797 13,406 14,016 45.00 78.00 24.4305 13,359 14,102 14,844 15,586 16,328 17,070 47.50 90.00 29.7360 16,172 17,070 17,969 18,867 19,766 20,664 57.50 90.00 35.9400 17,969 18,967 19,965 20,964 21,962 22,960 57.50 100.00 39.9500 22,750 24,014 25,278 26,542 27,806 29,069 65.00 112.00 50.6580 26,250 27,708 29,167 30,625 32,083 33,542 75.00 112.00 58.3660 29,531 31,172 32,813 34,453 36,094 37,734 75.00 126.00 65.6800 36,422 38,445 40,469 42,492 44,516 46,539 92.50 126.00 80.9

    1000 44,680 47,162 49,644 52,126 54,609 57,091 107.50 133.00 99.3

  • YORK INTERNATIONAL 13

    FORM 100.09-EG1

    NOTES: 1. All fan sizes specified in the quick selection chart above are based on the most efficient forward curved fan for the specifiedstatic pressure and CFM.

    FORWARD CURVED FANS

    CFMSTATIC PRESSURE UNIT

    2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 SIZE

    150020002500300035004000450050005500550060006500700075008000850090009500

    1000011000110001200013000140001500016000160001750019000190002050022000240002600028000280003000032000320003400036000

    AP35

    AP60

    AP80

    AP105

    AP120

    AP150

    AP170

    AP215

    AP250

    AP305

    AP360

    AP400

    AP500

    AP580

    AP660

    9 x 9

    10 x 10

    10 x 10 9 x 9

    15 x 15

    15 x 15

    18 x 18

    20 x 20

    20 x 20

    22 x 22

    25 x 25

    28 x 28

    28 x 28

    32 x 32

    32 x 32

    32 x 32

    12 x 12

    15 x 11

    15 x 15

    18 x 18

    18 x 18

    20 x 20

    22 x 22

    25 x 25

    25 x 25

    28 x 28

  • YORK INTERNATIONAL14

    Quick Selection Tables

    NOTES: 1. Add 6" in length (for the two end channels) to determine the overall unit length.2. The unit widths do not include coil connections.3. For coil segments, the dimensions in (") represents the coil space available.4. The unit height includes the base rail (5" for the AP-35 AP-500 and 8" for the AP-580 AP-1000.5. Fan weights includes the largest available motor.

    * = Same as FS.

    UNIT SIZE 35 60 80 105 120 150 170 215 250UNIT HEIGHT 37 43 43 46 46 46 52 55 61UNIT WIDTH 36 42 53 62 70 83 86 91 91

    SEGMENT L = LENGTH OF SEGMENT IN THE DIRECTION OF AIRFLOW (INCHES)FS FAN 1 L / lbs. 42 / 486 44 / 604 46 / 833 46 / 965 46 / 1065 48 / 1277 54 / 1729 54 / 1863 58 / 2040FR FAN 2 L / lbs. 40 / 479 44 / 669 44 / 742 46 / 936 46 / 1186 46 / 1252 48 / 1247 48 / 1604 54 / 1880FE FAN 3 L / lbs. N/A / N/A N/A / N/A N/A / N/A 46 / 1038 46 / 1180 46 / 1242 48 / 1418 54 / 1797 58 / 1993

    FAN 4 L / lbs. N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A 54 / 1847

    FPFAN 1 L / lbs. N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A 40 / 1141 44 / 1365 46 / 1534 50 / 1725FAN 2 L / lbs. N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A 46 / 1454 50 / 1744 52 / 1995

    SA SHORT ACCESS (12") L / lbs. 12 / 80 12 / 92 12 / 108 12 / 124 12 / 133 12 / 149 12 / 163 12 / 169 12 / 174MA MEDIUM ACCESS (18") L / lbs. 18 / 114 18 / 125 18 / 141 18 / 165 18 / 187 18 / 197 18 / 209 18 / 225 18 / 249LA LONG ACCESS (24") L / lbs. 24 / 144 24 / 158 24 / 177 24 / 207 24 / 222 24 / 245 24 / 260 24 / 280 24 / 317SC SHORT COIL (10') L / lbs. 16 / 227 18 / 301 18 / 345 18 / 423 18 / 480 18 / 547 18 / 608 20 / 679 20 / 743

    (using 6 Row / 8 FPI BDW coil)MC MEDIUM COIL (20") L / lbs. 26 / 311 28 / 493 28 / 459 28 / 539 28 / 601 28 / 692 28 / 779 30 / 864 30 / 987

    (using 8 Row / 8 FPI BDW coil)LC LONG COIL (28") L / lbs. 34 / 418 36 / 546 36 / 660 36 / 800 36 / 917 36 / 1051 36 / 1188 38 / 1308 38 / 1467

    (using (2) 8 Row/ 8 FPI BDW coil)XC EXTRA LONG COIL (36") (using (2) L / lbs. 42 / 492 44 / 650 44 / 773 44 / 915 44 / 1044 44 / 1189 44 / 1341 46 / 1487 46 / 1662

    8 Row/ 8 FPI & (1) 1 Row/ 8 FPI BDW coils)VC VERTICAL COIL (20") L / lbs. * / 400 * / 610 * / 610 * / 722 * / 806 * / 944 * / 1106 * / 1206 * / 1398HC HEATING COIL (10") L / lbs. 10 / 113 10 / 134 10 / 158 10 / 191 10 / 212 10 / 242 10 / 270 10 / 302 10 / 338

    (using 1 Row / 8 FPI SDC Coil)IC INTEGRAL FACE & BYPASS COIL L / lbs. N/A / N/A N/A / N/A N/A / N/A 24 / 601 24 / 682 24 / 789 24 / 899 24 / 931 24 / 1055OF OPEN RETURN FILTER (2") L / lbs. 0 / 11 0 / 14 0 / 17 0 / 28 0 / 31 0 / 36 0 / 46 0 / 47 0 / 53

    OPEN RETURN FILTER (4") L / lbs. 2 / 13 2 / 18 2 / 22 2 / 38 2 / 42 2 / 49 2 / 61 2 / 63 2 / 69FF FLAT FILTER (2" or 4") L / lbs. 10 / 111 10 / 128 10 / 146 10 / 181 10 / 202 10 / 228 10 / 239 10 / 253 10 / 267AF ANGLE FILTER (2") L / lbs. 18 / 170 20 / 190 20 / 219 20 / 253 20 / 283 20 / 314 16 / 357 22 / 387 18 / 416

    ANGLE FILTER (4") L / lbs. 20 / 181 22 / 215 22 / 249 22 / 281 22 / 318 22 / 340 18 / 398 24 / 437 20 / 503BF

    BAG FILTER (21" w/ 2" or 4" Pre-filter) L / lbs. 26 / 199 26 / 224 26 / 255 26 / 308 26 / 351 26 / 390 26 / 425 26 / 451 26 / 480BAG FILTER (32" w/ 2" or 4" Pre-filter) L / lbs. 36 / 300 36 / 327 36 / 365 36 / 430 36 / 465 36 / 525 36 / 549 36 / 615 36 / 656

    RF RIGID FILTER (12" w/ 2" Pre-filter) L / lbs. 18 / 164 18 / 192 18 / 220 18 / 277 18 / 318 18 / 353 18 / 378 18 / 418 18 / 435RIGID FILTER (12" w/ 4" Pre-filter) L / lbs. 20 / 178 20 / 211 20 / 238 20 / 301 20 / 345 20 / 387 20 / 413 20 / 466 20 / 483

    HF HEPA FILTER L / lbs. 18 / 186 18 / 223 18 / 273 18 / 326 18 / 413 18 / 430 18 / 520 18 / 594 18 / 617EF FILTER / ECONOMIZER (2") L / lbs. 42 / 36 46 / 42 46 / 53 46 / 62 46 / 70 46 / 83 44 / 66 56 / 91 56 / 91

    FILTER / ECONOMIZER (4") L / lbs. 44 / 36 48 / 42 48 / 53 40 / 62 48 / 70 48 / 83 46 / 66 58 / 91 58 / 91FM

    FILTER / MIXING BOX (2") L / lbs. 22 / 258 26 / 318 26 / 379 26 / 448 26 / 503 26 / 571 24 / 628 30 / 739 30 / 846FILTER / MIXING BOX (4") L / lbs. 24 / 292 28 / 343 28 / 407 28 / 477 28 / 536 28 / 609 26 / 663 32 / 789 32 / 928

    MB MIXING BOX L / lbs. 20 / 222 20 / 263 20 / 296 20 / 365 20 / 402 20 / 455 22 / 506 26 / 596 26 / 651AB AIR BLENDER L / lbs. 22 / 173 28 / 235 34 / 289 36 / 362 28 / 330 30 / 380 34 / 450 36 / 497 34 / 504

    ATTENUATOR (3') L / lbs. 38 / 242 38 / 294 38 / 336 38 / 385 38 / 441 38 / 485 38 / 526 38 / 560 38 / 610AT ATTENUATOR (5') L / lbs. 62 / 403 62 / 490 62 / 559 62 / 642 62 / 736 62 / 809 62 / 877 62 / 933 62 / 1017

    ATTENUATOR (7') L / lbs. 86 / 564 86 / 686 86 / 783 86 / 898 86 / 1030 86 / 1133 86 / 1228 86 / 1307 86 / 1423DI DIFFUSER L / lbs. 18 / 141 18 / 166 22 / 223 22 / 261 22 / 284 22 / 302 26 / 357 26 / 419 30 / 478DP DISCHARGE PLENUM L / lbs. 20 / 185 20 / 206 20 / 228 20 / 276 20 / 310 20 / 335 22 / 395 26 / 452 26 / 474EB EXTERNAL FACE & BYPASS L / lbs. 26 / 209 26 / 255 26 / 302 26 / 378 26 / 403 26 / 458 26 / 512 32 / 608 32 / 674EE ECONOMIZER L / lbs. 40 / 374 40 / 431 40 / 481 40 / 546 40 / 624 40 / 691 42 / 777 52 / 916 52 / 1074FD FACE DAMPER L / lbs. 12 / 128 12 / 161 12 / 193 12 / 240 12 / 268 12 / 305 12 / 348 12 / 395 12 / 424IB INTERNAL FACE & BYPASS L / lbs. 12 / 111 12 / 145 12 / 168 12 / 195 12 / 215 12 / 236 12 / 271 12 / 293 12 / 325VP VERTICAL PLENUM L / lbs. N/A / N/A N/A / N/A N/A / N/A N/A / N/A N/A / N/A * / 580 * / 688 * / 778 * / 860EH

    ELECTRIC HEATER (EH-2) L / lbs. 24 / 391 24 / 460 24 / 523 24 / 615 24 / 658 24 / 746 24 / 837 24 / 917 24 / 969ELECTRIC HEATER (EH-3) L / lbs. 36 / 482 36 / 567 36 / 644 36 / 754 36 / 807 36 / 914 36 / 1020 36 / 1114 36 / 1176

    CF CARBON FILTER (CF-1) (Rechargeable) L / lbs. 32 / 480 32 / 569 32 / 667 32 / 832 32 / 942 32 / 1068 32 / 1219 32 / 1311 32/ 1488CARBON FILTER (CF-2) (Rechargeable) L / lbs. 38 / 546 38 / 648 38 / 756 38 / 942 38 / 1066 38 / 1207 38 / 1370 38 / 1474 38 / 1607

    MZ MULTI-ZONE (Includes Hot Deck L / lbs. N/A / N/A 46 / 1202 50 /1348 50 / 1558 50 / 1726 50 / 1964 54 / 2195 56 / 2472 60 / 2756and Cold Deck with coils & Diffuser)

    IO SEGMENT L / lbs. 20 / 192 20 / 220 20 / 242 20 / 297 20 / 325 20 / 365 22 / 398 26 / 478 26 / 517End Channels - 5" Base Weight (lbs.) 74 81 88 100 106 116 121 126 128End Channels - 8" Base Weight (lbs.) 85 92 101 114 121 133 138 143 146

    DIMENSIONS & WEIGHTS

  • YORK INTERNATIONAL 15

    FORM 100.09-EG1

    6. See VC segment dimensions on page 51 for specific segment height.7. MZ, VC and VP segments are taller than the nominal unit height.8. Certain items (i.e. coil connections, door handles, mounting feet, etc.) may extend beyond the cabinet

    dimensions.9. Weights are shipping weights not operating weights.

    * = Same as FS.

    UNIT SIZE 305 360 400 500 580 660 800 1000UNIT HEIGHT 64 73 73 81 95 95 113 131UNIT WIDTH 103 103 113 125 125 139 139 146

    SEGMENT L = LENGTH OF SEGMENT IN THE DIRECTION OF AIRFLOW (INCHES)FS FAN 1 L / lbs 62 / 2497 68 / 2834 68 / 3071 76 / 3958 76 / 4276 76 / 5205 82 / 6131 82 / 6419FR FAN 2 L / lbs. 58 / 2738 62 / 2808 62 / 3068 68 / 3874 72 / 4264 76 / 4694 88 / 5971 88 / 7057FE FAN 3 L / lbs. 62 / 2679 62 / 2751 68 / 3112 76 / 4080 76 / 4392 82 / 5181 94 / 7028 94 / 8502

    FAN 4 L / lbs. 58 / 2625 58 / 2670 62 / 2925 68 / 3704 N/A / N/A N/A / N/A N/A / N/A N/A / N/AFP

    FAN 1 L / lbs. 52 / 2292 52 / 2462 56 / 2819 60 / 3617 66 / 4376 70 / 5255 74 / 5823 80 / 6945FAN 2 L / lbs. 56 / 2403 56 / 2557 60 / 3212 66 / 3966 70 / 4704 74 / 5709 80 / 6405 84 / 7867

    SA SHORT ACCESS (12") L / lbs. 12 / 219 12 / 243 12 / 275 12 / 302 12 / 328 12 / 353 12 / 374 12 / 399MA MEDIUM ACCESS (18") L / lbs. 18 / 289 18 / 310 18 / 330 18 / 384 18 / 429 18 / 461 18 / 489 18 / 523LA LONG ACCESS (24") L / lbs. 24 / 359 24 / 375 24 / 396 24 / 477 24 / 530 24 / 586 24 / 605 24 / 647SC SHORT COIL (10') L / lbs. 22 / 933 24 / 1044 24 / 1137 26 / 1404 26 / 1603 28 / 1826 32 / 2109 36 / 2555

    (using 6 Row / 8 FPI BDW coil)MC MEDIUM COIL (20") L / lbs. 32 / 1197 34 / 1364 34 / 1467 36 / 1740 36 / 2003 38 / 2224 42 / 2621 46 / 3153

    (using 8 Row / 8 FPI BDW coil)LC LONG COIL (28") L / lbs. 40 / 1788 42 / 2061 42 / 2257 44 / 2714 44 / 3119 46 / 3462 50 / 4049 54 / 4993

    (using (2) 8 Row/ 8 FPI BDW coil)XC EXTRA LONG COIL (36") (using (2) L / lbs. 48 / 2042 50 / 2326 50 / 2510 52 / 3129 52 / 3458 54 / 3819 N/A / N/A N/A / N/A

    8 Row /8 FPI & (1) 1 Row/8 FPI BDW coils)VC VERTICAL COIL (20") L / lbs. * / 1691 * / 1954 * / 2105 * / 2554 N/A / N/A N/A / N/A N/A / N/A N/A / N/AHC HEATING COIL (10") L / lbs. 10 / 399 10 / 435 10 / 474 10 / 545 10 / 657 10 / 705 10 / 835 10 / 969

    (using 1 Row / 8 FPI SDC Coil)IC INTEGRAL FACE & BYPASS COIL L / lbs. 24 / 1117 24 / 1355 23 / 1437 34 / 1843 34 / 2028 34 / 2387 34 / 2615 34 / 2950OF OPEN RETURN FILTER (2") L / lbs. 0 / 52 0 / 61 0 / 76 0 / 91 0 / 95 0 / 111 0 / 138 0 / 167

    OPEN RETURN FILTER (4") L / lbs. 2 / 72 2 / 87 2 / 105 2 / 126 2 / 131 2 / 139 2 / 190 2 / 234FF FLAT FILTER (2" or 4") L / lbs. 10 / 333 10 / 360 10 / 400 10 / 478 10 / 554 10 / 611 10 / 683 10 / 764AF ANGLE FILTER (2") L / lbs. 18 / 539 20 / 588 20 / 627 20 / 738 22 / 785 22 / 904 22 / 1092 22 / 1187

    ANGLE FILTER (4") L / lbs. 20 / 618 22 / 680 22 / 726 22 / 836 26 / 934 26 / 1054 24 / 1323 26 / 1497BF BAG FILTER (21" w/ 2" or 4" Pre-filter) L / lbs. 26 / 597 26 / 648 26 / 697 26 / 838 26 / 967 26 / 1065 26 / 1206 26 / 1632

    BAG FILTER (32" w/ 2" or 4" Pre-filter) L / lbs. 36 / 768 36 / 831 36 / 895 36 / 1085 36 / 1238 36 / 1303 36 / 1473 36 / 2002RF

    RIGID FILTER (12" w/ 2" Pre-filter) L / lbs. 18 / 517 18 / 611 18 / 661 18 / 772 18 / 856 18 / 953 18 / 1100 18 / 1292RIGID FILTER (12" w/ 4" Pre-filter) L / lbs. 20 / 563 20 / 654 20 / 718 20 / 841 20 / 931 20 / 1035 20 / 1194 20 / 1407

    HF HEPA FILTER L / lbs. 18 / 737 18 / 799 18 / 893 18 / 1121 18 / 1267 18 / 1420 18 / 1660 18 / 1942EF

    FILTER / ECONOMIZER (2") L / lbs. 58 / 103 68 / 103 68 / 113 72 / 125 82 / 125 82 / 139 92 / 139 96 / 146FILTER / ECONOMIZER (4") L / lbs. 60 / 103 70 / 103 70 / 113 72 / 125 84 / 125 84 / 139 94 / 139 98/ 146

    FMFILTER / MIXING BOX (2") L / lbs. 32 / 1102 36 / 1265 36 / 1363 40 / 1740 44 / 2028 44 / 2286 52 / 2846 52 / 3246FILTER / MIXING BOX (4") L / lbs. 34 / 1179 38 / 1354 38 / 1462 40 / 1827 48 / 2104 48 / 2447 54 / 3077 54 / 3513

    MB MIXING BOX L / lbs. 28 / 822 32 / 946 32 / 1050 40 / 1408 44 / 1703 44 / 1703 50 / 1900 50 / 2709AB AIR BLENDER L / lbs. 36 / 648 40 / 739 42 / 801 42 / 1006 48 / 1169 50 / 1250 48 / 1305 54 / 1587

    ATTENUATOR (3') L / lbs. 38 / 775 38 / 932 38 / 999 38 / 1125 38 / 1279 38 / 1373 38 / 1541 38 / 1642AT ATTENUATOR (5') L / lbs. 62 / 1291 62 / 1554 62 / 1666 62 / 1875 62 / 2131 62 / 2288 62 / 2568 62 / 2737

    ATTENUATOR (7') L / lbs. 86 / 1808 86 / 2175 86 / 2332 86 / 2624 86 / 2984 86 / 3203 86 / 3595 86 / 3832DI DIFFUSER L / lbs. 30 / 595 34 / 680 34 / 724 34 / 864 36 / 1065 36 / 1150 36 / 1245 36 / 1366DP DISCHARGE PLENUM L / lbs. 28 / 615 32 / 720 32 / 774 40 / 1096 44 / 1343 44 / 1496 50 / 1769 50 / 2032EB EXTERNAL FACE & BYPASS L / lbs. 32 / 825 38 / 981 38 / 1057 38 / 1298 44 / 1567 44 / 1701 44 / 1938 50 / 2121EE ECONOMIZER L / lbs. 54 / 1208 64 / 1532 64 / 1675 72 / 2123 82 / 2620 82 / 2674 90 / 3123 94 / 3602FD FACE DAMPER L / lbs. 12 / 531 12 / 590 12 / 639 12 / 785 12 / 910 12 / 1022 12 / 1155 12 / 1361IB INTERNAL FACE & BYPASS L / lbs. 12 / 418 12 / 463 12 / 501 12 / 607 12 / 695 12 / 765 12 / 875 12 / 1023VP VERTICAL PLENUM L / lbs. * / 1000 * / 1039 * / 1159 * / 1412 N/A / N/A N/A / N/A N/A / N/A N/A / N/AEH ELECTRIC HEATER (EH-2) L / lbs. 24 / 1080 24 / 1197 24 / 1326 24 / 1477 24 / 1605 24 / 1795 24 / 1980 24 / 2384

    ELECTRIC HEATER (EH-3) L / lbs. 36 / 1309 36 / 1445 36 / 1594 36 / 1775 36 / 1927 36 / 2147 36 / 2364 36 / 2829CF

    CARBON FILTER (CF-1) (Rechargeable) L / lbs. 32 / 1755 32 / 1919 32 / 2127 32 / 2491 34 / 2991 34 / 3256 34 / 3856 34 / 4662CARBON FILTER (CF-2) (Rechargeable) L / lbs. 38 / 1953 38 / 2139 38 / 2378 38 / 2777 40 / 3309 40 / 3611 40 / 4267 40 / 5131

    MZ MULTI-ZONE (Includes Hot Deck L / lbs. 62 / 3277 68 / 3686 68 / 3971 70 / 4671 N/A / N/A N/A / N/A N/A / N/A N/A / N/Aand Cold Deck with coils & Diffuser)

    IO SEGMENT L / lbs 28 / 662 32 / 755 32 / 840 40 / 1123 44 / 1367 44 / 1528 50 / 1811 50 / 2107End Channels - 5" Base Weight (lbs.) 146 150 158 171 N/A N/A N/A N/AEnd Channels - 8" Base Weight (lbs.) 168 171 181 196 200 213 220 237

    DIMENSIONS & WEIGHTS

  • YORK INTERNATIONAL16

    Engineering Data Fans

    1. Fan Segment Numbers (1), (2) and (3) refer to segment lengths which vary in size FC = Forward Curved Fandepending on the fan selected within a given AP unit size. AF = Airfoil Fan

    FORWARD CURVED & AIRFOIL FAN AND MOTOR DATA

    UNITFAN MAX. MAX. FAN OUTLET

    SIZE SEGMENT MOTOR MOTOR AREANUMBER1 TYPE SIZE HP FRAME (sq. ft.)35 1 FC 9-9 3 182T 0.84

    2 FC 9-6 3 182T 0.5960 1 FC 10-10 5 184T 1.03

    2 FC 9-9 7.5 213T 0.8480 1 FC 12-12 7.5 213T 1.45

    2 FC 10-10 7.5 213T 1.03105 1 FC 15-15 7.5 213T 2.04

    2 FC 12-12 10 215T 1.453 AF 12 15 254T 1.45

    120 1 FC 15-15 7.5 213T 2.042 FC 15-11 10 215T 1.623 AF 15 20 256T 2.04

    150 1 FC 18-18 15 254T 2.862 FC 15-15 10 215T 2.043 AF 15 20 256T 2.04

    170 1 FC 20-20 20 256T 4.382 FC 18-18 15 254T 2.863 AF 18 25 284T 2.86

    215 1 FC 20-20 25 284T 4.382 FC 18-18 15 254T 2.863 AF 20 30 286T 4.38

    250 1 FC 22-22 20 256T 5.502 FC 20-20 25 284T 4.383 AF 22 30 286T 5.504 FC 20-18 25 284T 3.91

    305 1 FC 25-25 20 256T 6.912 FC 22-22 40 324T 5.503 AF 25 40 324T 6.914 FC 22-20 40 324T 4.78

    360 1 FC * 28-28 30 286T 8.682 FC 25-25 40 324T 6.913 AF 25 40 324T 6.914 FC 22-20 40 324T 4.78

    400 1 FC * 28-28 25 284T 8.682 FC 25-25 40 324T 6.913 AF 28 50 326T 8.684 FC 25-22 40 324T 6.13

    500 1 FC * 32-32 40 324T 10.922 FC * 28-28 50 326T 8.683 AF 32 60 364T 10.923 FC 27-25 50 326T 7.55

    580 1 FC * 32-32 50 326T 10.922 FC 30-30 50 326T 9.383 AF 32 75 365T 10.92

    660 1 FC 32-32 60 364T 10.922 AF 32 75 365T 10.923 AF 36 75 365T 13.75

    800 1 AF 36 100 404T 13.752 AF 40 75 365T 17.283 AF 44 60 364T 20.49

    1000 1 AF 36 100 404T 13.752 AF 40 100 404T 17.283 AF 44 100 404T 20.49

  • YORK INTERNATIONAL 17

    FORM 100.09-EG1

    PLENUM FAN AND MOTOR DATA

    PLENUM FAN

    UNITFAN MAX. MAX. FAN INLET

    SIZE SEGMENT MOTOR MOTOR AREANUMBER1 TYPE SIZE HP FRAME (sq. ft.)150 1 SWSI 20 15 215T 2.16

    170 1 SWSI 24 15 254T 3.212 SWSI 27 15 254T 3.60

    215 1 SWSI 27 20 256T 3.602 SWSI 30 20 256T 4.72

    250 1 SWSI 30 20 256T 4.722 SWSI 33 20 256T 5.82

    305 1 SWSI 33 25 256T 5.822 SWSI 36 25 256T 7.05

    360 1 SWSI 33 30 286T 5.822 SWSI 36 30 286T 7.05

    400 1 SWSI 36 40 324T 7.052 SWSI 40 40 324T 8.62

    500 1 SWSI 40 40 324T 8.622 SWSI 44 40 324T 10.47

    580 1 SWSI 44 50 326T 10.472 SWSI 49 50 326T 12.80

    660 1 SWSI 49 60 364T 12.802 SWSI 54 60 364T 15.54

    800 1 SWSI 54 75 365T 15.542 SWSI 60 75 365T 19.02

    1000 1 SWSI 60 75 365T 19.022 SWSI 66 75 365T 22.87

    1. Fan Segment Numbers (1) and (2) refer to segment lengths which vary in size depending on the fanselected within a given AP unit size.

    2. Plenum fan performance is not within the scope of ARI Certification.

  • YORK INTERNATIONAL18

    Engineering Data FansVARIABLE INLET VANES OPERATING TORQUES (in. lbs.)

    FORWARD CURVED

    Shaded area indicatesan area where the RPMis below minimum orexceed the Class II lim-its.

    FAN SIZES (IN.)RPM 12 x 12 15 x 15 18 x 18 22 x 22 25 x 25 27 x 27 30 x 30

    15 x 1120 x 20

    300 37 48400 35 40 45 73500 35 35 40 48 71 100600 35 35 44 48 61 88 133700 35 38 53 60 75 110 165800 35 35 43 64 72 90 135 200900 35 35 49 75 83 108 160 225

    1000 35 42 55 85 95 125 1891100 35 45 63 95 108 1371200 35 50 70 108 1201300 38 55 78 1201400 43 61 85 1331500 45 68 901600 50 731700 52 781800 58 831900 602000 652100 69

    RPM FAN SIZES (IN.)12 15 18 20 22 25 28 32 36 40 44

    400 20 20 20 20 20 20 20 26 39 57 86500 20 20 20 20 20 20 20 41 61 89 134600 20 20 20 20 20 20 26 58 87 129 193700 20 20 20 20 20 24 36 79 119 175 263800 20 20 20 20 21 32 47 104 155 229 343900 20 20 20 20 27 40 59 131 197 289 435

    1000 20 20 20 22 33 49 73 162 243 357 5361100 20 20 20 26 40 60 88 196 294 432 6491200 20 20 22 32 48 71 105 234 350 514 7721300 20 20 25 37 56 83 123 274 410 9071400 20 20 29 43 65 97 142 318 476 10511500 20 20 34 49 75 111 164 365 5461600 20 20 38 56 85 126 186 4151700 20 20 43 63 96 142 210 4691800 20 22 49 71 108 160 2361900 20 25 54 79 120 1782000 20 28 60 88 133 1972100 20 31 66 97 1472200 22 34 73 106 1612300 24 37 79 116 1762400 26 40 86 126 1912500 28 43 94 1372600 31 47 101 1482700 33 50 1092800 36 54 1182900 38 58 1263000 41 623100 44 673200 47 713300 49 753400 533500 563600 593700 623800 663900 694000 734100 764200 8843004400450046004700

    AIRFOIL FAN (DWDI)

  • YORK INTERNATIONAL 19

    FORM 100.09-EG1

    VARIABLE INLET VANES OPERATING TORQUES (in. lbs.)

    Shaded area indicates an area where the fanexceeds the Class II limits.

    RPMFAN SIZE (in.)

    20 22 24 27 30 33 36 40 44 49 54 60 66400 20 20 20 20 20 20 20 26 39 57 84 128 188500 20 20 20 20 20 20 27 40 61 89 132 201 294600 20 20 20 20 20 26 40 58 87 129 190 289 423700 20 20 20 20 25 36 54 79 119 175 258 393 576800 20 20 20 21 32 47 70 103 155 228 337 514 752900 20 20 20 27 41 59 89 131 197 289 426 650 952

    1000 20 20 22 33 50 73 110 162 243 357 527 8021100 20 20 27 40 61 89 133 196 294 432 6371200 20 22 32 47 72 106 158 233 350 5141300 20 25 38 56 85 124 186 273 4101400 20 29 44 64 98 144 215 317 4761500 22 34 50 74 113 165 247 3641600 25 39 57 84 128 188 2811700 29 43 64 95 145 212 3181800 32 49 72 107 163 2381900 36 54 81 119 181 2652000 40 60 89 132 2012100 44 66 98 145 2212200 48 73 108 159 2432300 52 80 118 1742400 57 87 129 1902500 62 94 1392600 67 102 1512700 72 1102800 78 1182900 83 1263000 89 1353100 953200 1013300340035003600370038003900400041004200

    SWSI PLENUM FAN

  • YORK INTERNATIONAL20

    Engineering Data Coils

    NOTE: 1. (Quantity) = Connections per Unit (1) = 1 set of connections (1 supply, 1 return) (2) = 2 set of connections (2 supply, 2 return) (3) = 3 set of connections (3 supply, 3 return)

    FH x FL = Finned Height (Inches) x Finned Length (Inches)

    COIL DATA

    FREE FLOW COILS TURBOFIN COILS NON-FREEZE COILSUNIT 1/2" DIA. TUBES 5/8" DIA. TUBES 1" DIA. TUBES (SDC TYPES)SIZE Full Face Reduced Face Full Face Reduced Face Full Face Reduced Face

    1(Quantity) Area 1(Quantity) Area 1(Quantity) Area 1(Quantity) Area 1(Quantity) Area1 (Quantity) AreaFH x FL (sq.ft.) FH x FL (sq.ft.) FH x FL (sq.ft.) FH x FL (sq.ft.) FH x FL (sq.ft.) FH x FL (sq.ft.)

    35(1)

    3.2(1)

    2.4(1)

    3.4(1)

    2.4(1)

    3.4(1)

    2.420.0 x 23.0 15.0 x 23.0 21.25 x 23.0 15.25 x 23.0 21.0 x 23.0 15.0 x 23.0

    60(1)

    5.5(1)

    4.0(1)

    5.5(1)

    4.3(1)

    5.4(1)

    4.227.5 x 29.0 20.0 x 29.0 27.25 x 29.0 21.25 x 29.0 27.0 x 29.0 21.0 x 29.0

    80(1)

    7.6(1)

    5.6(1)

    7.6(1)

    5.9(1)

    7.5(1)

    5.827.5 x 40.0 20.0 x 40.0 21.25 x 40.0 21.25 x 40.0 27.0 x 40.0 21.0 x 40.0

    105(1)

    10.0(1)

    7.5(1)

    10.1(1)

    7.1(1)

    10.0(1)

    7.030.0 x 48.0 22.5 x 48.0 30.25 x 48.0 21.25 x 48.0 30.0 x 48.0 21.0 x 48.0

    120(1)

    11.9(1)

    8.9(1)

    12.0(1)

    8.4(1)

    11.9(1)

    8.330.0 x 57.0 22.5 x 57.0 30.25 x 57.0 21.25 x 57.0 30.0 x 57.0 21.0 x 57.0

    150(1)

    14.6(1)

    10.9(1)

    14.7(1)

    10.3(1)

    14.6(1)

    10.230.0 x 70.0 22.5 x 70.0 30.25 x 70.0 21.25 x 70.0 30.0 x 70.0 21.0 x 70.0

    170(1)

    16.5(1)

    12.7(1)

    16.9(1)

    12.3(1)

    16.7(1)

    12.232.5 x 73.0 25.0 x 73.0 33.25 x 73.0 24.25 x 73.0 33.0 x 73.0 24.0 x 73.0

    215(1)

    20.3(1)

    14.9(1)

    21.3(1)

    14.8(1)

    21.1(1)

    14.637.5 x 78.0 27.5 x 78.0 39.25 x 78.0 27.25 x 78.0 39.0 x 78.0 27.0 x 78.0

    250(1)

    24.4(1)

    17.6(1)

    24.5(1)

    18.0(1)

    24.4(1)

    17.845.0 x 78.0 32.5 x 78.0 45.25 x 78.0 33.25 x 78.0 45.0 x 78.0 33.0 x 78.0

    305(1)

    29.7(1)

    21.9(1)

    30.2(1)

    22.7(1)

    30.0(1)

    22.547.5 x 90.0 35.0 x 90.0 48.25 x 90.0 36.25 x 90.0 48.0 x 90.0 36.0 x 90.0

    360(2)

    35.9(1)

    26.6(2)

    35.9(1)

    26.4(2)

    35.6(1)

    26.357.5 x 90.0 42.5 x 90.0 57.5 x 90.0 42.25 x 90.0 57.0 x 90.0 42.0 x 90.0

    400(2)

    39.9(1)

    29.5(2)

    39.9(1)

    29.3(2)

    39.6(1)

    29.257.5 x 100.0 42.5 x 100.0 57.5 x 100.0 42.25 x 100.0 57.0 x 100.0 42.0 x 100.0

    500(2)

    50.6(1)

    36.9(2)

    49.4(1)

    37.5(2)

    49.0(1)

    37.365.0 x 112.0 47.5 x 112.0 63.5 x 112.0 48.25 x 112.0 63.0 x 112.0 48.0 x 112.0

    580(2)

    58.3(2)

    44.7(2)

    58.7(2)

    44.7(2)

    58.3(2)

    44.375.0 x 112.0 57.5 x 112.0 75.5 x 112.0 57.5 x 112.0 75.0 x 112.0 57.0 x 112.0

    660(2)

    65.6(2)

    50.3(2)

    66.1(2)

    50.3(2)

    65.6(2)

    49.975.0 x 126.0 57.5 x 126.0 75.5 x 126.0 57.5 x 126.0 75.0 x 126.0 57.0 x 126.0

    800(2)

    80.9(2)

    59.1(2)

    79.2(2)

    58.2(2)

    78.8(2)

    57.892.5 x 126.0 67.5 x 126.0 90.5 x 126.0 66.5 x 126.0 90.0 x 126.0 66.0 x 126.0

    1000(3)

    99.3(2)

    73.9(3)

    100.4(2)

    75.3(3)

    99.8(2)

    74.8107.5 x 133.0 80.0 x 133.0 108.75 x 133.0 81.5 x 133.0 108.0 x 133.0 81.0 x 133.0

    BDW CDW SDC

  • YORK INTERNATIONAL 21

    FORM 100.09-EG1

    NOTES: 1. All coils have one set of connections (1 supply, 1 return).2. FH x FL = Finned Height (inches) x Finned Length (inches)

    MULTI-ZONE HOT DECK COIL DATA

    BDW CDWFREE FLOW COILS TURBOFIN COILS NON-FREEZE COILSUNIT 1/2" DIA. TUBES 5/8" DIA. TUBES 1" DIA. TUBESSIZE Quantity Area Quantity Area Quantity Area

    FH x FL (sq. ft.) FH x FL (sq. ft.) FH x FL (sq. ft.)60 12.5 x 29 2.5 12.25 x 29 2.5 12 x 29 2.4

    80 12.5 x 40 3.5 12.25 x 40 3.4 12 x 40 3.3

    105 15 x 48 5.0 15.25 x 48 5.1 15 x 48 5.0

    120 15 x 57 5.9 15.25 x 57 6.0 15 x 57 5.9

    150 15 x 70 7.3 15.25 x 70 7.4 15 x 70 7.3

    170 15 x 73 7.6 15.25 x 73 7.7 15 x 73 7.6

    215 17.5 x 78 9.5 18.25 x 78 9.9 18 x 78 9.8

    250 20 x 78 10.8 21.25 x 78 11.5 21 x 78 11.8

    305 22.5 x 90 14.1 21.25 x 90 13.6 21 x 90 13.1

    360 27.5 x 90 17.2 27.25 x 90 17.0 27 x 90 16.9

    400 27.5 x 100 19.1 27.25 x 100 18.9 27 x 100 18.8

    500 27.5 X 112 21.4 27.25 X 112 21.2 27 X 112 21.0

    SDC

    INTEGRAL FACE & BYPASS COILSINTEGRAL FACE & BYPASS COILS

    UNITMAXIMUM OUTLET L.J. WINGSIZE CFM AREA MODEL

    35 N/A N/A N/A60 N/A N/A N/A80 N/A N/A N/A

    105 5,632 7.04 IFB - B - 36

    120 6,176 7.72 IFB - B - 42

    150 9,264 11.58 IFB - B - 60

    170 12,384 15.48 IFB - C - 60215 12,384 15.48 IFB - C - 60250 15,392 19.24 IFB - D - 60

    305 15,392 19.24 IFB - D - 60

    360 21,600 27.00 IFB - F - 60

    400 21,600 27.00 IFB - F - 60

    500 28,980 32.20 VIFB - VC - 9580 36,180 40.20 VIFB - VD - 9

    660 44,190 49.10 VIFB - VD - 11

    800 57,420 63.80 VIFB - VE - 11

    1000 70,830 78.70 VIFB - VF - 11

    NOTES: 1. All coil information used with permission of the L.J. Wing Company.2. IFB coils are available in 2 or 4 row. VIFB coils are available in 1 and 2 rows.3. All IFB coils have side connections.4. All VIFB coils have center connections.

  • YORK INTERNATIONAL22

    Engineering Data FiltersFLAT FILTER (FF) AND OPEN RETURN FILTER (OF) SEGMENTS 2" or 4"

    LD04351

    FILTER SIZES AND QUANTITIES PER UNIT SIZEUNIT SIZE

    35 60 80 105 120 150 170 215 250 305 360 400 500 580 660 800 1000Area (sq. ft.) 4.0 6.0 8.0 11.1 13.3 16.7 17.8 22.2 24.0 32.0 40.0 41.7 50.0 60.0 66.0 82.7 108.8

    12" x 24" 1 3 316" x 20" 6 8

    Filter 16" x 25" 4 6Size 20" x 20" 8 15 14

    24" x 20" 12 15 5 2124" x 24" 1 1 2 6 8 15 15 15

    NOTES: 1. See the filter configurations below for specific filter arrangements.2. Flat filters are side-loaded.3. Open return filters are front-loaded.

  • YORK INTERNATIONAL 23

    FORM 100.09-EG1

    ANGLE FILTER (AF), FILTER/MIXING BOX (FM) SEGMENTS, ECONOMIZER/FILTER SEGMENT (EF), 2" or 4"

    UNIT SIZE35 60 80 105 120 150 170 215 250 305 360 400 500 580 660 800 1000

    Area (sq. ft.) 4.4 8.9 11.1 15.6 16.7 21.1 22.2 29.2 35.6 42.2 50.0 55.6 66.7 80.0 88.0 133.3 140.012" x 24" 416" x 20" 2 4 2 2 16 4

    Filter 16" x 25" 8 12

    Size 20" x 20" 4 4 6 6 8 8 24 4820" x 24" 4220" x 25" 2 8 1624" x 24" 20 20

    NOTES: 1. See the filter configurations below for specific filter arrangements.2. Angle and filter / mixing box filters are side-loading.

    LD04352

    FILTER SIZES AND QUANTITIES PER UNIT SIZE

  • YORK INTERNATIONAL24

    Engineering Data FiltersBAG FILTER (BF) AND RIGID FILTER (RF) (WITH 2" or 4" PREFILTERS) SEGMENTS

    LD04353

    FILTER SIZES AND QUANTITIES PER UNIT SIZEUNIT SIZE

    35 60 80 105 120 150 170 215 250 305 360 400 500 580 660 800 1000Area (sq. ft.) 4.0 6.0 8.0 12.0 12.3 16.0 17.1 22.2 24.0 32.0 40.0 41.7 50.0 60.0 66.0 82.7 108.8

    12" x 24" 1 2 2 3 3 3 3Filter 20" x 20" 3 4 8 15 14Size 24" x 20" 2 3 12 15 5 21

    24" x 24" 1 1 2 6 8 15 15 15

    NOTES: 1. Filter sizes are dimensioned width by height (W x H). Example: Filter size 12 x 24 = 12" wide by 24" high filter.2. See the filter configurations below for specific filter arrangements.3. Bag, rigid & pre-filter filters are all side-loading.

  • YORK INTERNATIONAL 25

    FORM 100.09-EG1

    HEPA FILTER (HF) SEGMENTSFILTER SIZES AND QUANTITIES PER UNIT SIZE

    NOTES: 1. See the filter configurations below for specific filter arrangements.2. HEPA filters are front-loading.3. All gasketing is located on the HEPA Media. The filter holding frames are

    not gasketed.4. 500 fpm is the maximum face velocity.

    LD04353

    UNIT SIZE35 60 80 105 120 150 170 215 250 305 360 400 500 580 660 800 1000

    Area (sq. ft.) 4.0 6.2 7.5 10.0 12.5 15.0 18.0 21.1 26.0 30.0 37.5 40.0 49.8 61.7 68.2 81.3 98.9 Max CFM 2,000 3,125 3,750 5,000 6,250 7,500 9,000 10,563 13,000 15,000 18,750 20,000 24,938 30,875 34,125 40,888 49,500

    24" x 24" 1 3 2 4 2 2 8 8 1224" x 12"12" x 24" 3 315" x 24" 2 1 4

    Filter 15" x 30" 1 3 1

    Size 24" x 30" 1 2 6 6 6 2 2 812" x 30" 230" x 24" 1 2 3 8 1 4 430" x 30" 1 2 6 3 1 130" x 12" 1

  • YORK INTERNATIONAL26

    Engineering Data FiltersCARBON FILTER (CF) SEGMENTS CF1 or CF2FILTER SIZES AND QUANTITIES PER UNIT SIZE

    LD02513

    UNIT SIZE35 60 80 105 120 150 170 215 250 305 360 400 500 580 660 800 1000

    AREA (sq.ft.) 16 24 32 40 50 60 72 84 98 128 144 162 200 240 264 330 43224" x 24" 4 4 8 10 10 15 18 18 21 32 36 36 50 60 60 75 10824" x 12" 4 5 6 7 9 12 15

    NOTES: 1. See the filter configurations below for specific filter arrangements.2. Carbon filters are side loading.

  • YORK INTERNATIONAL 27

    FORM 100.09-EG1Engineering Data DampersDAMPERSMIXING BOX (MB) / FILTER MIXING BOX (FM) ECONOMIZER (EE),ECONOMIZER / FILTER (EF), DAMPER DATA OA/RA/EA

    NOTES: 1. Damper openings are 1/8" larger than the actual damper body.2. Combination torque is for the combination of two dampers.

    TORQUE: 1. Torque required to achieve maximum leakage performance.2. Torques are based on 1 inch wg pressure differential.3. Damper performance is based on AMCA 500 test setup 5.4/5.5.4. Maximum damper face velocity is 2000 FPM.

    UNIT DAMPER ACTUAL DIMENSIONS* INDIVIDUAL COMBINATION MINIMUM

    SIZE WIDTH HEIGHT AREADAMPERS DAMPERS # OF ACTUATORS

    TORQUE (in.lbs.) TORQUE (in. lbs.) REQUIRED35 15.00 14.75 1.54 20 28 160 22.00 14.75 2.25 20 30 180 30.00 14.75 3.07 20 31 1

    105 39.00 14.75 3.99 20 34 1120 46.00 14.75 4.71 20 35 1150 56.00 14.75 5.74 20 37 2170 64.00 14.75 6.56 20 40 2215 55.00 20.75 7.93 24 43 2250 63.00 20.75 9.08 27 49 2305 78.00 20.75 11.24 34 65 2360 70.00 26.75 13.00 39 70 2400 78.00 26.75 14.49 43 78 2500 98.00 26.75 18.20 55 98 3580 92.00 32.75 20.92 63 112 3660 103.00 32.75 23.43 76 126 3800 125.00 32.75 28.43 85 153 3

    1000 131.00 38.75 35.25 105 190 3

    NOTES: 1. Damper openings are 1/8" larger than the actual damper body.2. The torque data is for the combined face & bypass damper assembly.3. The face damper is opposed blade, the bypass damper is parallel blade.

    TORQUE: 1. Torque required to achieve maximum leakage performance.2. Torques are based on 1 inch wg pressure differential.3. Damper performance is based on AMCA 500 test setup 5.4/5.5.4. Maximum damper face velocity is 2000 FPM.

    INTERNAL FACE & BYPASS (IB) DAMPER DATAUNIT FACE DAMPER BYPASS DAMPER FACE & BYPASS MINIMUM

    SIZE WIDTH HEIGHT AREA WIDTH HEIGHT AREADAMPERS TORQUE # OF ACTUATORS

    (in.lbs.) REQUIRED35 28.00 15.00 2.92 28.00 9.00 1.75 20 160 34.00 21.00 4.96 34.00 9.00 2.13 20 180 45.00 21.00 6.56 45.00 9.00 2.81 23 1

    105 54.00 23.88 8.95 54.00 9.12 3.42 31 2120 62.00 23.88 10.28 62.00 9.12 3.93 36 2150 75.00 23.88 12.44 75.00 9.12 4.75 43 2170 78.00 26.29 14.24 78.00 12.71 6.88 51 2215 83.00 27.00 15.56 83.00 15.00 8.65 57 2250 83.00 33.00 19.02 83.00 15.00 8.65 67 2305 95.00 37.88 24.99 95.00 13.12 8.66 85 2360 95.00 44.75 29.52 95.00 15.25 10.06 101 2400 105.00 44.75 32.63 105.00 15.25 11.12 111 3500 117.00 49.38 40.12 117.00 18.62 15.13 138 3580 117.29 57.04 46.46 117.29 21.00 17.10 160 3660 131.29 57.04 52.01 131.29 21.00 19.15 179 3800 131.29 69.29 63.17 131.29 26.75 24.39 218 4

    1000 138.29 81.75 78.51 138.29 32.29 31.01 272 4

  • YORK INTERNATIONAL28

    Engineering Data DampersDAMPER DATA

    EXTERNAL FACE & BYPASS (EB) DAMPER DATA

    TORQUE: 1. Torque required to achieve optimum leakage performance.2. Torques are based on 1 inch wg pressure differential.3. Damper performance is based on AMCA 500 test setup 5.4/5.5.4. Maximum damper face velocity is 2000 FPM.

    TORQUE: 1. Torque required to achieve optimum leakage performance.2. Torques are based on 1 inch wg pressure differential.3. Damper performance is based on AMCA 500 test setup 5.4/5.5.4. Maximum damper face velocity is 2000 FPM.

    FACE DAMPER BYPASS DAMPER FACE & MINIMUMUNIT BYPASS # OFSIZE

    WIDTH HEIGHT AREA TORQUE WIDTH HEIGHT AREA TORQUE DAMPERS ACTUATORSTORQUE REQUIRED35 28.0 24.0 4.67 20 15.0 14.8 1.54 20 28 160 34.0 24.0 5.67 21 22.0 14.8 2.25 20 30 180 45.0 30.0 9.38 28 30.0 14.8 3.07 20 35 1

    105 54.0 33.0 12.38 37 39.0 14.8 3.99 20 42 2120 62.0 33.0 14.21 43 46.0 14.8 4.71 20 48 2150 75.0 33.0 17.19 52 56.0 14.8 5.74 20 58 2170 78.0 39.0 21.13 63 64.0 14.8 6.56 20 73 2215 83.0 42.0 24.21 73 55.0 20.8 7.93 24 83 2250 83.0 48.0 27.67 83 63.0 20.8 9.08 27 94 2305 95.0 51.0 33.65 102 78.0 20.8 11.24 34 115 3360 95.0 60.0 39.58 118 70.0 26.8 13.00 39 134 3400 105.0 60.0 43.75 131 78.0 26.8 14.49 43 147 3500 117.0 68.0 55.25 165 98.0 26.8 18.20 55 187 4580 117.0 78.0 63.38 190 92.0 32.8 20.92 63 215 4660 131.0 78.0 70.96 213 103.0 32.8 23.43 76 241 5800 131.0 96.0 87.33 263 125.0 32.8 28.43 85 296 5

    1000 138.0 114.0 109.25 327 131.0 38.8 35.25 105 396 5

    FACE (FD) DAMPER DATA

    UNIT FACE DAMPER MINIMUM

    SIZE WIDTH HEIGHT AREA# OF ACTUATORS

    TORQUE REQUIRED35 28.0 24.0 4.67 20 160 34.0 24.0 5.67 21 180 45.0 30.0 9.38 28 1

    105 54.0 33.0 12.38 37 2120 62.0 33.0 14.21 43 2150 75.0 33.0 17.19 52 2170 78.0 39.0 21.13 63 2215 83.0 42.0 24.21 73 2250 83.0 48.0 27.67 83 2305 95.0 51.0 33.65 102 3360 95.0 60.0 39.58 118 3400 105.0 60.0 43.75 131 3500 117.0 68.0 55.25 165 4580 117.0 78.0 63.38 190 4660 131.0 78.0 70.96 213 5800 131.0 96.0 87.33 263 5

    1000 138.0 114.0 109.25 327 5

  • YORK INTERNATIONAL 29

    FORM 100.09-EG1

    DAMPER DATA

    DAMPER LEAKAGE DATA

    UNITLOW LEAK ULTRA LOW LEAK

    SIZE LEAKAGE (cfm. / sq. ft.)@ 1" WG @ 4" WG @ 1" WG @ 4" WG

    35 7.2 14.5 3.7 8.060 7.2 14.5 3.7 8.080 7.2 14.5 3.7 8.0

    105 7.2 14.5 3.7 8.0120 7.2 14.5 3.7 8.0150 7.2 14.5 3.7 8.0170 7.2 14.5 3.7 8.0215 7.2 14.5 3.7 8.0250 7.2 14.5 3.7 8.0305 7.2 14.5 3.7 8.0360 7.2 14.5 3.7 8.0400 7.2 14.5 3.7 8.0500 7.2 14.5 3.7 8.0580 7.2 14.5 3.7 8.0660 7.2 14.5 3.7 8.0800 7.2 14.5 3.7 8.0

    1000 7.2 14.5 3.7 8.0NOTE: Damper performance is based on AMCA 500 test setup 5.4/5.5.

    BLENDER DATA

    VENDOR TOTAL BLENDERUNIT SIZE MODEL* QUANTITY AREA(sq. ft.)

    35 H - 16 1 1.4560 H - 20 1 2.2880 H - 24 1 3.29

    105 H - 26 1 3.85120 H - 20 2 4.56150 H - 22 2 5.52170 H - 24 2 6.58215 H - 26 2 7.72250 H - 24 3 9.87305 H - 26 3 11.58360 H - 28 3 13.44400 H - 30 3 15.42500 H - 34 3 19.80580 H - 36 3 20.20660 H - 38 3 24.75800 H - 42 3 30.24

    1000 H - 44 3 33.18

    *Model numbers are used with the permission of Blender Products Inc.*Air Blender is a registered trademark of Blender Products Inc.

  • YORK INTERNATIONAL30

    Engineering Data Dampers

    DAMPER DATA

    MULTI-ZONE (MZ)

    UNIT QUANTITY TOTAL DAMPER ACTUAL DIMENSIONS COMBINATIONSIZE OF ZONES WIDTH HEIGHT AREA DAMPER TORQUE (in.lbs)

    60 5 35.5 9.0 2.2 12080 7 46.5 9.0 2.9 168

    105 8 55.5 9.0 3.5 192120 10 63.5 9.0 4.0 240150 12 76.5 9.0 4.8 288170 12 79.5 9.0 5.0 288215 13 84.5 11.0 6.5 312250 13 84.5 12.0 7.0 312305 15 96.5 12.0 8.0 360360 15 96.5 15.0 10.1 360400 17 106.5 15.0 11.1 408500 19 118.5 16.0 13.2 456

    NOTES: 1. Torque required to achieve maximum leakage performance.2. Torques are based on 1 inch wg pressure differential.3. Damper performance is based on AMCA 500 test setup 5.4/5.5.4. See page 73 for actual damper locations.5. Maximum damper face velocity is 2000 FPM.

  • YORK INTERNATIONAL 31

    FORM 100.09-EG1

    SOUND ATTENUATOR

    LD02500

    UNIT SIZE35 60 80 105 120 150 170 215 250 305 360 400 500 580 660 800 1000

    Area (sq. ft.) 4.0 4.0 5.0 7.5 7.5 10.0 12.0 15.0 15.0 21.0 24.0 24.0 30.0 35.0 40.0 48.0 63.0

    ATTENUATOR AREAS

    ATTENUATOR ATTENUATOR FACE FLOW DYNAMIC INSERTION LOSS (dB)LENGTH TYPE VEL. (FPM) 1 2 3 4 5 6 7 83 STANDARD 1000 FORWARD 7 12 16 28 35 35 28 17

    1000 REVERSE 7 13 17 30 36 33 26 13

    5 STANDARD 1000 FORWARD 8 18 24 40 45 46 41 261000 REVERSE 11 21 25 43 47 44 39 22

    7 STANDARD 1000 FORWARD 10 20 35 45 50 48 45 341000 REVERSE 12 23 37 46 51 48 44 30

    3 LOW 1000 FORWARD 10 13 23 27 26 22 17 14FREQUENCY 1000 REVERSE 9 14 24 27 25 19 16 14

    5 LOW 1000 FORWARD 13 19 31 36 39 27 22 16FREQUENCY 1000 REVERSE 16 21 35 41 41 28 21 15

    7 LOW 1000 FORWARD 13 24 40 48 49 37 29 19FREQUENCY 1000 REVERSE 16 26 44 49 50 35 25 17

    3 HOSPITAL / 1000 FORWARD 7 9 14 19 22 28 30 13CLEAN ROOM 1000 REVERSE 7 11 17 22 25 30 30 13

    5 HOSPITAL / 1000 FORWARD 9 13 19 26 35 44 35 15CLEAN ROOM 1000 REVERSE 10 15 22 30 40 46 35 16

    7 HOSPITAL / 1000 FORWARD 12 14 23 36 50 51 38 17CLEAN ROOM 1000 REVERSE 15 18 27 40 50 51 38 17

    DYNAMIC INSERTION LOSS RATING

    ATTENUATOR FACE FLOW DYNAMIC INSERTION LOSS (dB)TYPE VEL. (FPM) 1 2 3 4 5 6 7 8

    STANDARD 1000 FORWARD 55 49 49 47 46 49 42 321000 REVERSE 54 51 50 51 54 56 52 40

    LOW 1000 FORWARD 46 42 45 43 45 49 44 37FREQUENCY 1000 REVERSE 45 42 45 43 45 49 44 37HOSPITAL / 1000 FORWARD 55 49 49 47 46 49 42 32

    CLEAN ROOM 1000 REVERSE 54 51 50 51 54 56 52 40

    SELF-NOISE POWER LEVELS

  • YORK INTERNATIONAL32

    Engineering Data

    NOTES:

    1. Standard media will be 60% CTC Virgin activated carbon.2. Standard media will absorb VOC (organic solvents and hydrocarbons), ozone, chlorine, ambient levels of sulfur

    dioxide, and nitrogen dioxide.3. Carbon panels filled with IVP (Improved Vapor Phase) are available as a SQ.4. Carbon Media Volume (Cu.Ft.) is based on nominal carbon panel dimensions.5. Carbon Weight is the nominal weight of the carbon in the tray.6. Filter weight is the weight of the filter tray with carbon.7. Ozone and VOC (Toluene) Efficiency is based on single pass and not indicative of total removal during recirculation.8. The efficiency is based on design media velocities listed in above table. While higher velocities reduce the efficiency

    and service life, lower than design velocities will increase the efficiency.9. The average VOC efficiency is the time-averaged (arithmetic) efficiency based on 50% saturation service life.10. Ozone efficiency is constant with service time.11. All performance data listed above is based upon 500 FPM design face velocity across the coil.12. The design is based on a minimum residence time of 0.08 seconds with a resulting contact efficiency of 99.6%13. Contact efficiency is the percent of total contaminant molecules which have come in contact with the media.14. Removal efficiency is that fraction of the contaminant molecules which, once in contact with the media, are removed

    by either physical or chemical means.

    UNIT CARBON CARBON OZONE VOC (TOLUENE)SIZE WEIGHT MEDIA EFFICIENCY EFFICIENCY %(Lbs) (ft3) % INITIAL AVERAGE

    35 48 2.67 80 71 5060 72 4.00 80 71 5080 96 5.33 80 71 50

    105 120 6.67 80 71 50120 150 8.33 80 71 50150 180 10.00 80 71 50170 216 12.00 80 71 50215 252 14.00 80 71 50250 294 16.33 80 71 50305 384 21.33 80 71 50360 432 24.00 80 71 50400 486 27.00 80 71 50500 600 33.33 80 71 50580 720 40.00 80 71 50660 792 44.00 80 71 50800 990 55.00 80 71 50

    1000 1296 72.00 80 71 50

    CARBON FILTER SEGMENT DESIGN & PERFORMANCE DATA

  • YORK INTERNATIONAL 33

    FORM 100.09-EG1

    ELECTRIC HEATER DESIGN & PERFORMANCE DATA (OPEN COIL TYPE ELEMENTS)

    MINIMUM AIR VELOCITY FOR OPEN COIL TYPE HEATERS

    LD02453

    28 KW/FT2 MAXIMUM

    NOTES:

    1. The maximum kW ratings are at design CFM conditionsonly and applications at lower than design CFM willresult in lower ratings.

    2. The minimum velocity for each heater of a certain kWis to be calculated from the minimum velocity vs. kW/sq.ft curves.

    3. Delta T = kW x 3160 CFM

    AirPak HEATER OPEN MAXSIZE AREA KW

    35 2.2 4660 3.3 7880 4.6 106

    105 5.7 149120 6.7 180150 8.3 219170 9.5 252215 12.1 315250 14.0 361305 17.9 435360 22.8 485400 25.4 538500 32.7 673580 40.3 742660 45.4 831800 59.3 957

    1000 77.4 1160

  • YORK INTERNATIONAL34

    Unit SelectionSELECTING AN AIRPAK AIR HANDLING UNIT

    AirPak air handlers permit selection of components tomeet individual job requirements. The wide selection ofbasic sections, optional components, coils, and acces-sories, enables the design engineer to obtain optimumperformance and temperature control.

    Selection of the optimum system for each individual ap-plication requires only the following simple steps:Step 1 - Determination of Total Air Supply Quantity.Step 2 - Selection of Basic Unit Size and Arrangement.Step 3 - Selection of Cooling and/or Heating Coils.Step 4 - Selection of Accessories (filters, mixing boxes,

    dampers, etc.).Step 5 - Selection of Fan, Motor and Drive.

    STEP 1TOTAL AIR SUPPLY QUANTITY

    The total air supply quantity will be determined by thelargest of:a. Ventilation, make-up or pressurization requirementb. Cooling load (most frequent for air conditioning)c. Heating load (for heating only)d. Contaminant or odor removal

    Ventilation requirements may be dictated by the localcode or ordinance, or established through the use of rec-ommendations in the ASHRAE Guide. Make-up air shouldat least equal total exhaust from the space, plus allow-ance for pressurization to minimize infiltration.

    For comfort air conditioning, the total air supply quantitywill usually be determined by the simultaneous peak cool-ing load - calculated by established methods publishedin the ASHRAE Guide. The required air supply may bedetermined by the formula:

    CFM = Sensible Space Cooling (or Heating) Load (BTU/HR)

    1.08 x (Entering dry Bulb F Leaving dry Bulb F)

    Depending on available cooling medium, air distributionconsiderations, and humidity control requirements, theCooling Temperature Differential is usually in the 15F to25F range.

    Since Heating Temperature Differentials are frequentlymuch higher, the air quantity required for heating is usu-ally less than for cooling. For projects requiring heatingonly, the heating load may be the controlling factor. Heatlosses in long duct runs must be considered.

    Humidity control, contaminant removal, or odor controlwill occasionally effect total air quantity.

    STEP 2BASIC UNIT SIZE AND ARRANGEMENT

    With a selection of five different fans for most units, thebasic unit size may be selected on the basis of coil facearea.

    AirPak units for cooling and dehumidification service musthold the coil face velocity below the point of moisturecarry-over. The usual limit is 600 FPM. For lower life cyclecosts, 350-400 FPM velocity is recommended. For a VAVsystem at minimum part load conditions, it is recom-mended that coil face velocity not be allowed to fall below200 FPM for a water coil and 400 FPM for a refrigerantcoil. Use the next larger unit size if the approximate facearea falls between that of two units.

    Refer to the Table on page 20 (Coil Data) for actual faceareas.

    Approximate Total CFM Face Area = Desired Face Velocity

    For heating and ventilation service, or for units involvingonly sensible cooling, face velocity is limited only by thehigh internal air pressure drop and resultant higher soundlevel of higher air flows. Selections are typically made inthe 800 to 1000 FPM face velocity range. The followingformula may be used:

    Unit arrangement will be determined by system require-ments and space considerations.

    STEP 3COOLING AND HEATING COILS

    Approximate Total CFM Face Area = Desired Face Velocity

    Cooling and Heating loads may be determined by estab-lished methods as published in the ASHRAE Guide. Avail-able media will determine whether coils will be selectedfor hot water, chilled water, steam, refrigerant or glycol.

    With loads determined and the medium selected, thecoil rows, fins, and circuiting can be selected from theappropriate Engineering Guides on YORK TURBOFIN andFREEFLOW coils or by a YORK Sales Engineer withYorkWorks. Coil sizes and face areas for each unit sizeare shown in the Engineering Data Section.

    Internal face and bypass coil selection may be deter-mined using reduced face coils.

  • YORK INTERNATIONAL 35

    FORM 100.09-EG1

    REFERENCE LITERATURE

    FAN PERFORMANCE ............................................................................................................ FORM 100.09-EG1.1

    COOLING AND HEATING COILS DRAINABLE WATER (DW) AND DIRECT EXPANSION (DX) 5/8" O.D. TUBES ................... FORM 105.17-EG1DRAINABLE WATER (DW) DIRECT EXPANSION (DX) 1/2" O.D. TUBES ........................... FORM 105.18-EG1NON-FREEZE STEAM COILS (SDC) 1" O.D. TUBES......................................................... FORM 105.26-EG2FACTORY-PACKAGED CONTROLS................................................................................... FORM 450.11-EG1AIR-MODULATOR ............................................................................................................... FORM 100.40-EG1

    STEP 4ACCESSORIES

    A wide range of accessories are available to tailor theYORK AirPak to specific system requirements. Includedin the Accessories are: face and bypass dampers, mix-ing dampers, flat or angle filters, rigid or bag filters, airblenders, economizers, diffusers, discharges, accesssegments, etc.

    STEP 5FANS, MOTORS AND DRIVES

    Total air system resistance must be determined for fanselection. Internal air flow resistance of the unit acces-sories can be determined from Tables on pages 38-45.Add the external system resistance (ref. ASHRAE Guide)

    to the internal resistance to obtain total static pressurefor fan selection.

    The nominal ranges of Total Static Pressure (TSP) for theavailable fan types are: up to 6" for FC, 9" for AF and upto 6.25" for SWSI fans. Casing limitations are 6" w.g.

    Fan RPM and BHP is determined from fan performancecurves and tables using unit size, fan type, CFM andTSP. Correct fan RPM and BHP, if necessary, for air tem-perature and altitude, using factors given on page 35.Fan tables and curves do not include drive losses.

    Refer to Form 100.09-EG1.1 (Forward Curved and AirfoilFan Curves and Tables) for individual AirPak units.

    ALTITUDE / TEMPERATURE CONVERSION FACTORS

    AIR ALTITUDE (FEET)TEMP F 0 1000 2000 3000 4000 5000 6000 7000 8000

    -20 1.20 1.16 1.12 1.08 1.04 1.00 .97 .93 .890 1.15 1.10 1.06 1.02 .99 .95 .92 .88 .8520 1.11 1.06 1.02 .98 .95 .92 .88 .85 .8240 1.06 1.02 .98 .94 .91 .88 .84 .81 .7860 1.02 .98 .94 .91 .88 .85 .81 .79 .7670 1.00 .96 .93 .89 .86 .83 .80 .77 .7480 .98 .94 .91 .88 .84 .81 .78 .72 .72100 .94 .91 .88 .84 .81 .78 .75 .70 .70120 .92 .88 .85 .81 .78 .76 .72 .68 .67140 .89 .85 .82 .79 .76 .73 .70 .68 .65160 .85 .82 .79 .76 .74 .70 .68 .65 .63200 .80 .77 .75 .72 .69 .67 .64 .62 .60250 .75 .72 .69 .67 .65 .62 .60 .58 .56

  • YORK INTERNATIONAL36

    Air Pressure Drop

    The air pressure drop Tables on pages 38-45 are to beused to determine the unit internal resistance. The inter-nal resistance, along with the supply duct pressure drops,return duct pressure drops and external static pressuresshould be used to select supply, return and/or exhaust

    INSTRUCTIONS FOR USING AIR PRESSURE DROP TABLES

    fans from the fan performance curves and tables, Form100.09-EG1.1 and 100.09-EG1.2. The Engineering Datatables, (pages 16-33) provide the necessary data (faceareas) to develop the face velocity required to use theappropriate air pressure drop tables.

    STATIC PRESSURE SCHEMATICS

    LD00011(09)

    LD00012(09)

    Supply Air Fan Total Static Pressure (TSP)External Static Pressure (ESP - given) ________________Final Filters (BF, RF, HF) ________________Prefilters (BF, RF) ________________Diffuser (DI) ________________Reheat Coil (HC, MC, LC, XC) ________________Cooling Coil (SC, MC, LC, XC) ________________Preheat Coil (HC, MC, LC, XC, IC) ________________Face & Bypass (IB, EB) ________________High Efficiency Filters (BF, RF) ________________Prefilters (OF, FF, AF, FM) ________________Blender (AB) ________________Outside Air Damper (FM, MB, EE) ________________ Supply Air Fan (TSP) ________________

    Return Air Fan Total Static Pressure (TSP):External Static Pressure (RETURN ESP - given) ________________Exhaust Air Damper (EE) ________________

    Return Air Fan (TSP) ________________

    ECONOMIZER WITH RETURN AIR FAN

    Supply Fan Total Static Pressure (TSP)External Static Pressure (ESP - given) ________________Final Filters (BF, RF, HF) ________________Prefilters (BF, RF) ________________Diffuser (DI) ________________Reheat Coil (HC, MC, LC, XC) ________________Cooling Coil (SC, MC, LC, XC) ________________Preheat Coil (HC, MC, LC, XC, IC) ________________Face & Bypass (IB, EB) ________________High Efficiency Filters (BF, RF) ________________Prefilters (OF, FF, AF, FM) ________________Blender (AB) ________________Outside Air Damper (FM, MB, EE) ________________ Supply Fan (TSP) ________________

    Exhaust Fan Total Static Pressure (TSP):External Static Pressure (RETURN ESP - given) ________________Exhaust Air Damper (EE) ________________

    Exhaust Fan (TSP) ________________

    ECONOMIZER WITH EXHAUST AIR FAN

  • YORK INTERNATIONAL 37

    FORM 100.09-EG1

    STATIC PRESSURE SCHEMATICS (Contd.)

    LD00013(09)

    LD00014(09)

    Supply Fan Total Static Pressure (TSP)External Static Pressure (ESP - given) ________________Final Filters (BF, RF, HF) ________________Prefilters (BF, RF) ________________Diffuser (DI) ________________Reheat Coil (HC, MC, LC, XC) ________________Cooling Coil (SC, MC, LC, XC) ________________Preheat Coil (HC, MC, LC, XC, IC) ________________Face & Bypass (IB, EB) ________________High Efficiency Filters (BF, RF) ________________Prefilters (OF, FF, AF, FM) ________________Blender (AB) ________________Outside Air (OA) ________________ Supply Fan (TSP) ________________

    EE - ECONOMIZER WITHOUT RETURN AIR FAN

    EE - ECONOMIZER WITH HORIZONTAL SWSI RETURN AIR FAN

    Supply Fan Total Static Pressure (TSP)External Static Pressure (ESP - given) ________________High Efficiency Filters (BF, RF, HF) ________________Prefilters (OF, FF, AF, FM) ________________Reheat Coil (HC, MC, LC, XC) ________________Cooling Coil (SC, MC, LC, XC) ________________Preheat Coil (HC, MC, LC, XC, IC) ________________High Efficiency Filters (BF, RF) ________________Prefilters (OF, FF, AF, FM) ________________Blender (AB) ________________Return Air (Damper) (RA) ________________Other Components ________________

    Supply Fan (TSP) ________________

    Return Fan Total Static Pressure (TSP):External Static Pressure - Return Air ________________Exhaust Air Damper ________________

    Return Fan (TSP) ________________

  • YORK INTERNATIONAL38

    Air Pressure Drop CoilsTURBOFIN CDW OR CDX FOR COOLING AND DEHUMIDIFYING (5/8") APD (in. wg.)WET COIL For Standard Air

    TURBOFIN CDW FOR HEATING & CDW OR CDX FOR SENSIBLE COOLING (5/8") APD (in. wg.)DRY COIL For Standard Air

    * Beyond scope of ARI Certification for cooling applications.

    ROWS FIN NO. AIR VELOCITY (FPM)400 425 450 475 500 525 5508 0.35 0.38 0.42 0.42 0.48 0.52 0.56

    410 0.40 0.44 0.48 0.52 0.56 0.60 0.6412 0.45 0.50 0.55 0.59 0.64 0.70 0.7514 0.50 0.56 0.62 0.66 0.72 0.80 0.868 0.44 0.48 0.62 0.56 0.61 0.65 0.69

    510 0.50 0.55 0.60 0.65 0.70 0.75 0.8112 0.57 0.62 0.68 0.74 0.80 0.87 0.9414 0.64 0.69 0.76 0.83 0.90 0.99 1.078 0.53 0.58 0.63 0.68 0.73 0.78 0.83

    6 10 0.60 0.66 0.72 0.78 0.84 0.90 0.9712 0.68 0.75 0.82 0.89 0.97 1.04 1.1214 0.76 0.84 0.92 1.00 1.10 1.18 1.278 0.70 0.77 0.83 0.90 0.97 1.04 1.11

    8 10 0.80 0.88 0.95 1.03 1.12 1.20 1.2912 0.91 1.00 1.09 1.19 1.29 1.39 1.5014 1.02 1.12 1.23 1.35 1.46 1.58 1.718 0.87 0.95 1.04 1.12 1.20 1.29 1.38

    10 10 0.99 1.09 1.18 1.28 1.39 1.49 1.6012 1.12 1.24 1.35 1.47 1.60 1.72 1.8614 1.25 1.39 1.52 1.66 1.81 1.95 2.128 1.05 1.14 1.24 1.34 1.44 1.55 1.65

    12 10 1.19 1.30 1.42 1.54 1.66 1.79 1.9212 1.35 1.48 1.62 1.77 1.91 2.07 2.2314 1.51 1.66 1.82 2.00 2.16 2.35 2.54

    ROWS FIN NO. AIR VELOCITY (FPM)400 450 500 550 600 700 800 900* 1000*

    8 0.07 0.09 0.10 0.12 0.14 0.19 0.23 0.29 0.34

    110 0.08 0.10 0.12 0.14 0.16 0.21 0.26 0.32 0.3812 0.09 0.11 0.13 0.15 0.18 0.23 0.29 0.35 0.4214 0.10 0.12 0.14 0.17 0.20 0.25 0.32 0.38 0.468 0.14 0.17 0.21 0.25 0.28 0.37 0.47 0.57 0.68

    2 10 0.16 0.20 0.23 0.27 0.32 0.41 0.52 0.63 0.7612 0.18 0.22 0.26 0.31 0.36 0.46 0.58 0.70 0.8414 0.24 0.29 0.35 0.40 0.51 0.64 0.77 0.928 0.21 0.26 0.31 0.37 0.43 0.56 0.70 0.86 1.03

    3 10 0.24 0.29 0.35 0.41 0.48 0.62 0.78 0.95 1.1312 0.27 0.33 0.39 0.46 0.53 0.69 0.86 1.05 1.2514 0.30 0.37 0.43 0.51 0.58 0.76 0.94 1.15 1.378 0.28 0.35 0.42 0.49 0.57 0.74 0.93 1.14 1.37

    410 0.32 0.39 0.47 0.55 0.64 0.83 1.04 1.26 1.5112 0.36 0.44 0.52 0.61 0.71 0.92 1.15 1.40 1.6714 0.40 0.49 0.57 0.67 0.78 1.10 1.26 1.54 1.838 0.35 0.43 0.52 0.61 0.71 0.93

    5 10 0.40 0.49 0.58 0.69 0.80 1.03 12 0.45 0.55 0.66 0.77 0.89 1.15 14 0.50 0.61 0.76 0.85 0.98 1.27 8 0.43 0.52 0.62 0.73 0.85 1.11

    6 10 0.48 0.59 0.70 0.82 0.95 1.24 12 0.54 0.66 0.79 0.92 1.07 1.38 14 0.60 0.73 0.88 1.02 1.19 1.52 8 0.57 0.69 0.83 0.98 1.14 1.48

    8 10 0.64 0.78 0.93 1.10 1.27 1.65 12 0.72 0.88 1.05 1.23 1.42 1.84 14 0.80 0.98 1.17 1.36 1.52 2.30 8 0.71 0.87 1.04 1.22 1.42 1.85

    10 10 0.80 0.98 1.17 1.37 1.59 2.06 12 0.90 1.10 1.31 1.54 1.78 2.30 14 1.00 1.22 1.45 1.71 1.97 8 0.85 1.04 1.25 1.47 1.70 2.22

    1210 0.96 1.17 1.40 1.64 1.91 2.48 12 1.08 1.32 1.57 1.84 2.13 2.76 14 1.20 1.47 1.71 2.04 2.35

  • YORK INTERNATIONAL 39

    FORM 100.09-EG1

    FREE-FLOW BDW OR BDX FOR COOLING AND DEHUMIDIFYING (1/2") APD (IN. WG.)WET COIL For Standard Air

    FREE-FLOW BDW FOR HEATING & BDW OR BDX FOR SENSIBLE COOLING (1/2") APD (IN. WG.)WET COIL For Standard Air

    * Beyond scope of ARI Certification for cooling applications.

    Rows Fin No. AIR VELOCITY (in. wg.)300 325 350 375 400 425 450 475 500 525 550

    8 0.06 0.08 0.09 0.10 0.10 0.12 0.13 0.14 0.15 0.16 0.18

    2 10 0.08 0.09 0.10 0.12 0.13 0.14 0.15 0.17 0.18 0.20 0.2112 0.10 0.11 0.12 0.14 0.16 0.17 0.18 0.20 0.21 0.23 0.2514 0.12 0.13 0.14 0.16 0.18 0.19 0.20 0.22 0.23 0.25 0.278 0.10 0.11 0.13 0.14 0.16 0.18 0.19 0.21 0.23 0.25 0.26

    3 10 0.12 0.14 0.16 0.18 0.19 0.21 0.23 0.25 0.27 0.29 0.3212 0.15 0.17 0.19 0.21 0.23 0.25 0.27 0.30 0.32 0.35 0.3714 0.18 0.20 0.22 0.24 0.26 0.29 0.30 0.35 0.37 0.40 0.428 0.13 0.15 0.17 0.19 0.21 0.23 0.26 0.28 0.30 0.33 0.35

    4 10 0.17 0.19 0.21 0.23 0.26 0.28 0.31 0.34 0.36 0.39 0.4212 0.20 0.22 0.25 0.28 0.31 0.34 0.37 0.40 0.43 0.46 0.4914 0.23 0.25 0.29 0.33 0.36 0.40 0.43 0.46 0.49 0.51 0.568 0.17 0.19 0.21 0.24 0.27 0.29 0.32 0.35 0.38 0.41 0.44

    5 10 0.21 0.23 0.26 0.29 0.32 0.35 0.39 0.42 0.45 0.49 0.5312 0.25 0.28 0.31 0.35 0.38 0.42 0.46 0.50 0.54 0.58 0.6214 0.29 0.33 0.36 0.42 0.44 0.49 0.53 0.58 0.63 0.67 0.718 0.20 0.23 0.26 0.29 0.32 0.35 0.38 0.42 0.45 0.49 0.53

    6 10 0.25 0.28 0.31 0.35 0.39 0.42 0.46 0.50 0.55 0.59 0.6312 0.30 0.34 0.38 0.42 0.46 0.50 0.55 0.60 0.64 0.69 0.7414 0.35 0.40 0.45 0.49 0.53 0.58 0.64 0.70 0.73 0.79 0.858 0.27 0.31 0.34 0.38 0.42 0.47 0.51 0.56 0.61 0.65 0.71

    8 10 0.33 0.37 0.42 0.47 0.52 0.57 0.62 0.67 0.73 0.78 0.8412 0.40 0.45 0.50 0.56 0.61 0.67 0.73 0.79 0.86 0.92 0.9914 0.47 0.53 0.58 0.65 0.70 0.77 0.84 0.91 0.99 1.06 1.148 0.34 0.39 0.42 0.47 0.52 0.58 0.65 0.72 0.79 0.88 0.93

    10 10 0.43 0.47 0.54 0.61 0.68 0.75 0.83 0.90 0.97 1.05 1.1212 0.51 0.56 0.62 0.70 0.78 0.86 0.94 1.03 1.11 1.20 1.2914 0.59 0.65 0.70 0.79 0.88 0.97 1.05 1.16 1.25 1.35 1.468 0.42 0.48 0.54 0.60 0.66 0.73 0.81 0.89 0.99 1.10 1.20

    12 10 0.52 0.60 0.68 0.78 0.88 0.98 1.08 1.13 1.28 1.38 1.4812 0.63 0.73 0.83 0.93 1.03 1.13 1.23 1.34 1.46 1.58 1.7014 0.74 0.86 0.98 1.08 1.18 1.28 1.38 1.55 1.64 1.78 1.92

    Rows Fin No. AIR VELOCITY (in. wg.)400 450 500 550 600 650 700 800 900* 1000*

    8 0.04 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.14 0.17

    1 10 0.04 0.05 0.06 0.07 0.08 0.09 0.11 0.13 0.16 0.2012 0.05 0.06 0.07 0.08 0.10 0.11 0.12 0.15 0.19 0.2214 0.06 0.06 0.08 0.09 0.12 0.13 0.14 0.17 0.21 0.248 0.07 0.09 0.10 0.12 0.14 0.16 0.18 0.23 0.28 0.33

    2 10 0.08 0.10 0.12 0.14 0.17 0.19 0.21 0.27 0.33 0.3912 0.10 0.12 0.14 0.16 0.19 0.22 0.25 0.31 0.38 0.4514 0.12 0.14 0.16 0.18 0.21 0.25 0.29 0.35 0.43 0.518 0.11 0.13 0.16 0.18 0.21 0.24 0.27 0.34 0.42 0.50

    3 10 0.13 0.15 0.18 0.21 0.25 0.28 0.32 0.40 0.49 0.5912 0.14 0.18 0.21 0.25 0.29 0.33 0.37 0.46 0.56 0.6714 0.16 0.21 0.24 0.29 0.33 0.38 0.42 0.52 0.63 0.758 0.14 0.17 0.21 0.24 0.28 0.32 0.37 0.46 0.56 0.67

    4 10 0.17 0.20 0.24 0.29 0.33 0.38 0.43 0.54 0.65 0.7812 0.19 0.23 0.28 0.33 0.38 0.43 0.49 0.62 0.75 0.9014 0.21 0.26 0.32 0.37 0.43 0.48 0.55 0.70 0.85 1.028 0.18 0.22 0.26 0.30 0.35 0.40 0.46

    5 10 0.21 0.25 0.30 0.36 0.41 0.47 0.54 12 0.24 0.29 0.35 0.41 0.48 0.54 0.62 14 0.27 0.33 0.40 0.46 0.55 0.61 0.70 8 0.21 0.26 0.31 0.36 0.42 0.48 0.55

    6 10 0.25 0.31 0.36 0.43 0.50 0.57 0.60 12 0.29 0.35 0.42 0.49 0.57 0.65 0.74 14 0.33 0.39 0.48 0.55 0.64 0.73 0.88 8 0.28 0.35 0.41 0.49 0.56 0.64 0.73

    8 10 0.33 0.41 0.49 0.57 0.66 0.76 0.86 12 0.38 0.47 0.56 0.66 0.76 0.87 0.98 14 0.43 0.53 0.63 0.75 0.86 0.98 1.10 8 0.37 0.44 0.50 0.58 0.65 0.73 0.82

    10 10 0.43 0.51 0.59 0.67 0.76 0.86 0.96 12 0.49 0.58 0.67 0.76 0.87 0.98 1.09 14 0.55 0.65 0.75 0.85 0.98 1.10 1.22 8 0.48 0.55 0.61 0.69 0.76 0.84 0.93

    12 10 0.55 0.63 0.71 0.79 0.88 0.98 1.08 12 0.62 0.71 0.80 0.89 1.00 1.11 1.22 14 0.69 0.79 0.89 0.99 1.12 1.24 1.36

  • YORK INTERNATIONAL40

    Air Pressure DropAIR BLENDER APD (IN. WG.)

    BLENDER FACE VELOCITY 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000PRESSURE DROP .07 .08 .10 .12 .14 .16 .18 .20 .23 .26 .29

    NOTE: Variable air volume locations with blender velocities below 1000 FPM should be reviewed to ensure proper blender performance.

    STEAM DISTRIBUTING (SDC) APD (IN. WG.)COIL ROW FIN AIR VELOCITY (FPM)

    DEPTH SERIES 200 300 400 500 600 700 800 900 1000 1100 12006 .02 .04 .07 .10 .14 .18 .22 .28 .34 .40 .468 .03 .05 .09 .13 .17 .22 .28 .34 .41 .48 .55

    SDC 1 10 .03 .06 .10 .15 .21 .27 .33 .40 .48 .56 .6611 .03 .07 .11 .16 .22 .29 .36 .44 .52 .61 .7012 .04 .07 .12 .18 .24 .31 .38 .47 .56 .65 .7513 .04 .08 .13 .19 .25 .33 .41 .50 .59 .70 .8114 .04 .08 .14 .20 .27 .35 .44 .53 .63 .74 .86

    Ratings for more than one row deep are obtained with multiple sections of one-row coils. All unit coils are rated and certified In accordance with ARIStandard 410.

    ELECTRIC HEATER AIR PRESSURE DROP (IN. WG.)Air Velocity (FPM) 400 450 500 550 600 650 700 750 800APD 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10

    DIFFUSER APD (IN. WG.)FAN OUTLET VELOCITY

    1600 1800 2000 2200 2400 2600 2800 3000DIFFUSER (DIF) 0.09 0.11 0.14 0.17 0.20 0.24 0.27 0.32

    VERTICAL CASING PRESSURE LOSS APD (IN. WG.)COIL FACE VELOCITY

    350 400 450 500 550 600CASING LOSS 0.14 0.18 0.23 0.29 .0.36 0.41

    ATTENUATOR APD (IN. WG.)MODEL FACE VELOCITY

    300 400 500 600 700 800 900 10003' Standard 0.03 0.06 0.09 0.13 0.18 0.23 0.30 0.375' Standard 0.04 0.07 0.11 0.15 0.20 0.26 0.33 0.407' Standard 0.04 0.07 0.11 0.16 0.22 0.28 0.35 0.433' Hospital 0.03 0.06 0.09 0.13 0.18 0.23 0.30 0.375' Hospital 0.04 0.07 0.11 0.15 0.20 0.26 0.33 0.407' Hospital 0.04 0.07 0.11 0.16 0.22 0.28 0.35 0.433' Low Frequency 0.05 0.09 0.14 0.21 0.28 0.37 0.46 0.575' Low Frequency 0.05 0.10 0.16 0.23 0.31 0.41 0.51 0.637' Low Frequency 0.06 0.08 0.14 0.22 0.32 0.43 0.53 0.63

    FILTER APD (IN. WG.)TYPE FILTER MEDIA FILTER VELOCITY (FPM)200 250 300 350 400 450 500 550 6252" - Throwaway 0.08 0.10 0.12 0.14 0.18 0.21 0.25 0.30 0.372" - Pleated 0.08 0.10 0.12 0.15 0.20 0.24 0.27 0.32 0.382" - Cleanable 0.02 0.03 0.04 0.05 0.07 0.09 0.10 0.11 0.134" - Pleated 0.06 0.08 0.10 0.13 0.16 0.19 0.22 0.28 0.33

    12" - 65% Rigid 0.15 0.17 0.20 0.23 0.28 0.31 0.39 0.44 0.5412" - 85% Rigid 0.17 0.21 0.26 0.30 0.37 0.45 0.53 0.63 0.7712" - 95% Rigid 0.20 0.24 0.29 0.33 0.41 0.50 0.58 0.67 0.8121" - 65% Efficient Bag 0.07 0.09 0.11 0.13 0.16 0.19 0.22 NR NR21" - 85% Efficient Bag 0.14 0.18 0.22 0.26 0.30 0.35 0.39 NR NR21" - 95% Efficient Bag 0.19 0.23 0.27 0.31 0.36 0.42 0.48 NR NR30" - 65% Efficient Bag 0.08 0.11 0.13 0.15 0.19 0.23 0.27 0.32 0.3730" - 85% Efficient Bag 0.09 0.12 0.15 0.19 0.23 0.27 0.32 0.38 0.4530" - 95% Efficient Bag 0.15 0.21 0.27 0.33 0.39 0.45 0.51 0.59 0.68HEPA XT - 99.97% Efficient 0.44 0.60 0.76 0.92 1.08 1.24 1.40 NR NR

    NOTE: 1. Filter pressure drop is through clean filters.

  • YORK INTERNATIONAL 41

    FORM 100.09-EG1

    MIXING BOX DAMPER (MB) / FILTER MIXING BOX (FM) / ECONOMIZER (EE) / ECONOMIZERFILTER (EF) AND EXTERNAL FACE AND BYPASS DAMPER (EB) (BYPASS DAMPER)

    CARBON FILTER AIR PRESSURE DROP (IN W.G.)CARBON MEDIA VELOCITY

    Air Velocity (FPM) 63 75 88 100 113 125 138 150APD 0.19 0.26 0.34 0.41 0.48 0.55 0.63 0.71

    NOTES: 1. Damper performance is based on AMCA 500 test setup 5.4/5.5.2. Based on 100% open dampers.

    UNIT DAMPER DAMPER VELOCITY (FPM)SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 160035 1.54 0.04 0.06 0.08 0.10 0.12 0.15 0.18 0.22 0.25 0.28 0.32 0.3960 2.25 0.04 0.06 0.07 0.09 0.11 0.14 0.17 0.20 0.22 0.25 0.29 0.3280 3.07 0.04 0.05 0.07 0.08 0.10 0.12 0.15 0.18 0.20 0.23 0.27 0.30

    105 3.99 0.03 0.05 0.06 0.08 0.10 0.12 0.14 0.16 0.18 0.22 0.25 0.27120 4.71 0.03 0.04 0.05 0.07 0.09 0.11 0.13 0.16 0.18 0.21 0.23 0.26150 5.74 0.03 0.04 0.05 0.07 0.09 0.10 0.12 0.15 0.17 0.20 0.22 0.25170 6.56 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.21 0.24215 7.93 0.02 0.04 0.05 0.06 0.07 0.09 0.11 0.13 0.15 0.17 0.20 0.22250 9.08 0.02 0.03 0.04 0.06 0.07 0.09 0.10 0.12 0.14 0.16 0.17 0.19305 11.24 0.02 0.03 0.04 0.05 0.06 0.08 0.09 0.11 0.13 0.14 0.16 0.18360 13.00 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.11 0.13 0.14 0.15 0.17400 14.49 0.02 0.02 0.03 0.04 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.16500 18.20 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.09 0.10 0.12 0.13 0.14580 21.92 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.10 0.11 0.12 0.13660 23.43 0.01 0.02 0.03 0.03 0.04 0.05 0.06 0.08 0.09 0.10 0.11 0.12800 28.43 0.01 0.02 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10 0.11

    1000 35.25 0.01 0.02 0.02 0.03 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.10

    ULTRA LOW LEAK APD (IN. WG.)

    UNIT DAMPER DAMPER VELOCITY (FPM)SIZE AREA 500 600 700 800 900 1000 1100 1200 1300 1400 1500 160035 1.54 0.06 0.09 0.12 0.15 0.18 0.23 0.29 0.33 0.38 0.43 0.48 0.5660 2.25 0.06 0.09 0.10 0.14 0.17 0.21 0.26 0.30 0.33 0.38 0.44 0.4880 3.07 0.06 0.08 0.10 0.12 0.15 0.18 0.23 0.27 0.30 0.36 0.44 0.46105 3.99 0.05 0.08 0.09 0.12 0.15 0.18 0.21 0.24 0.29 0.33 0.38 0.41120 4.71 0.05 0.06 0.08 0.10 0.14 0.17 0.19 0.24 0.27 0.32 0.35 0.39150 5.74 0.05 0.06 0.08 0.10 0.14 0.15 0.18 0.23 0.26 0.30 0.33 0.38170 6.56 0.05 0.06 0.08 0.10 0.12 0.15 0.18 0.21 0.24 0.29 0.32 0.36215 7.93 0.03 0.06 0.06 0.09 0.10 0.14 0.17 0.19 0.23 0.26 0.30 0.33250 9.08 0.03 0.05 0.06 0.09 0.10 0.14 0.15 0.18 0.21 0.23 0.26 0.29305 11.24 0.03 0.05 0.06 0.08 0.09 0.12 0.14 0.17 0.19 0.21 0.24 0.27360 13.00 0.03 0.05 0.05 0.08 0.09 0.11 0.14 0.17 0.19 0.21 0.23 0.26400 14.49 0.03 0.03 0.05 0.06 0.08 0.11 0.12 0.15 0.18 0.19 0.21 0.24500 18.20