ChenHsong Multi-functional Computer1. Features:
This computer controller whose power supply ranges from AC110V to AC 280V,
50/60HZ, is developed by Japan and meets JIS acceptance standards, featuring color
LCD of 320×240,backlighting LED which is high in brightness and long in service
life, and the most advanced SMT technology adopted to electronic components and
production process to ensure stability and dependability. In addition, it is capable of
storing data for more than 5 years even the power is shut off to provide security and
reliability, offers Chinese and English languages options for free switch facilitating
study and operation, provides a smart detector for fault and instructions for auxiliary
operation, and fully support iChen wireless network system.
2. Basic functions:1. Store 150 sets of data on molding, e.g. time, time, times, pressure, speed, stroke,
measurement, mold thickness & name, selection condition, material temperature and so
on.
2. Prompts at large for online operation.
3. Classified lock for password for software data.
4. Prevention against and prompt for data input so the operator would not make
improper modification. Any modification can be saved via iChen System to the central
server for backup.
5. The most advanced SMT technology is adopted to assemble the electronic plate to
secure high dependability.
6. 32 CPU of high speed is used.
7. The value for mold clamping position is automatically set.
8.Injection nozzle proportion and temperature control (Standard), supporting additional
furnace mouth thermometer (optional).
℃9. 8 sets of PID temperature control allows regulation within 30 - ℃500 and
provides high precision.
10. Functions of protection against cold burden startup, automatic thermal insulation,
detection for nozzle clog and mold overflow.
11. High and low temperature setting and detection of broken down of temperature
sensing line in operation.
12. Injection 5 stage speeds, 5 stage pressures and 5 stage pressures maintaining
setting.
13. Plasticizing 3 stage speeds, 3 stage pressures and 3 stage backpressure setting.
14. Support 3 sets air blow and 3 sets of core-pulling.
15. All clamped mode, injection and ejector adopt high precision optics decoder
(standard) or electron ruler (optional).
16. Storage of alarm history which is convenient for process debugging and
maintenance.
17. Manufacturing numbers and setting in mass, setting automatic stop as per output,
and is capable of assisting iChen System production order arrangement system.
18. Automatic lubrication for module times setting of hinge, and warning of shortage of
fuel.
19. Display operation motion by graphs, which is very convenient for supervision over
the operation of injection molding machine.
20. Circulating monitoring of time over every motion, making it easy for regulation,
can shorten cycle.
1
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual21. Statistics of injection speed, pressure standard curve and present curve comparison
and ending position of injection.
22. Status of running program, all input points, timer and counter is under online
surveillance for convenience of debugging and maintenance.
23. Supports inspections into the conditions of 32 output points, 32 input points, 100
timers and 20 counters.
24. Offer free options for copying or clearing mold data, reservedly, use preset mold
data in the compute to save time.
25. Smart detection for fault and instructions for auxiliary operation.
26. Support as many as 40 sets of temperature control for hot runner.
27. Perfect support for iChen System of workshop network management
28. Perfect support for iChen Wireless network.
Ai-01 multi-functional computer is the enhanced version of CH3.8PC
computer with additional functions including 2 stage ejector, synchronous
core-pulling,synchronous plasticizing, 3 sets of air blow as compared as
flowing:
2
FUNCTION CH3.8PC CHAI-01
COMPARASON
Synchronous
core-pulling
No Yes Enhanced with synchronous core-
pulling
Synchronous
plasticizing
No Yes Enhanced with synchronous
plasticizing
Air blow 2 stage 3 stage Enhanced with one more set of air
blow control
Ejection One speed
and one
press
Two speeds
and two
pressures
Two levels of control on speed
and pressure of ejection
Function selection 18 stage 19 stage Enhanced with Synchronous
Motion, including synchronous
ejection, synchronous
plasticationand synchronous core
pulling.
Speed-up/down
setting
speed,
pressure
setting
Speed,
pressure,
backpressur
e and speed
2 setting
Enhanced with backpressure and
speed 2 setting
Speed and
pressure setting
19 stage 21 stage Enhanced with auxiliary oil pump
and backpressure ratio in the
action of opening and clamping
mold
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Contents3.1 Introduction to the Computer Panel
3.1.1 Computer panel ……… 6
3.1.2 Control keys for operation state ……… 7
3.1.3 Setting Keys for Forming Condition ……… 7
3.1.4 Keys and Cursor for numerical data on forming
conditions……… 8
3.1.5 Manual Operation Keys and Instructions thereof ……… 9
3.1.6 Power Switch ……… 9
3.2 Display Operation Instruction3.2.1 Compute Startup Screen (00-02) ……… 10
3.2.2 Normal Operation Setting Screen (03) ……… 12
3.2.3 Monitor over Cycle Screen (04) ……… 13
3.2.4 Setting for Mold opening Screen (05) ……… 14
3.2.5 Setting for Mold clamping Screen (06) ……… 16
3.2.6 Setting for Injection Pressure
of Mold clamping
Screen (07) ……… 18
3.2.7 Setting for Injection Screen (08) ……… 19
3.2.8 Setting for Pressure Holding Screen (09) ……… 21
3.2.9 Setting for
Plasticizing/Unscrewing
Screen (10) ……… 23
3.2.10 Setting for Automatic Purge Screen (11) ……… 25
3.2.11 Setting for Ejection Screen (12) ……… 26
3.2.12 Setting for Injection base Screen (13) ……… 28
3.2.13 Setting for Air blow Screen (14) ……… 29
3.2.14 Setting for Core Pulling a Screen (15) ……… 30
3.2.15 Setting for Core Pulling b Screen (16) ……… 32
3.2.16 Setting for Core Pulling c Screen (17) ……… 34
3.2.17 Setting for Time Screen (18) ……… 36
3.2.18 Setting 1 for Counter Screen (19) ……… 38
3.2.19 Setting for Alarm against
Temperature Deviation
Screen (20) ……… 39
3.2.20 Setting for Temperature Of
Hot Runner
Screen (21-22) ……… 41
3.2.21 Setting for Function Screen (23) ……… 43
3.2.22 Selection of Mold Number Screen (24-25) ……… 45
3.2.23 Statistics Screen (26) ……… 47
3
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual3.2.24 Monitor over Time Screen (27-31) ……… 49
3.2.25 Monitor over Counter Screen (32) ……… 52
3.2.26 Monitor over Input Screen (33-34) ……… 53
3.2.27 Monitor over Output Screen (35-37) ……… 55
3.2.28 Monitor over Relay Screen (38-42) ……… 57
3.2.29 Monitor over Procedure Screen (43) ……… 60
3.2.30 Ending position of Injection Screen (44) ……… 61
3.2.31Speed Curve of Injection
Screen (45) ……… 62
3.2.32Pressure Curve of Injection
Screen (46) ……… 63
3.2.33 Help Screen (47-51) ……… 64
3.2.34 Setting for Language Selection
and System Time
Screen (52) ……… 67
3.2.35 Selection of Number of Stage
of Motion Stroke
Screen (53) ……… 68
3.2.36Setting for Slope
Screen (54) ……… 69
3.2.37Setting for Speed l Output
Screen (55) ……… 70
3.2.38Pressure Output
Screen (56) ……… 71
3.2.39Setting for Backpressure
Screen (57) ……… 72
3.2.40 Setting for Speed 2 Output Screen (58) ……… 73
3.2.41 Setting for initialization
(Setting for decoder initial
position)
Screen (59) ……… 74
3.2.42 Setting for Reserved Speed &
Pressure
Screen (60-61) ……… 75
3.2.43 Setting for Timer Screen (62) ……… 77
3.2.44 Setting 2 for Counter Screen (63) ……… 79
3.2.45 Factory Setting Screen (64-65) ……… 81
3.2.46 Display of Alarm history Screen (66) ……… 83
3.2.47 Network Screen (67) ……… 84
3.2.48Modification of Password
Screen (68) ……… 86
3.2.49 Setting for Manual LubricationScreen (69) ……… 87
3.2.50 Setting for mold adjustment Screen (70) ……… 88
3.2.51 Mechanical Adjustment Screen (71) ……… 90
3.2.52 Maintenance ReminderScreen (72) ……… 91
3.2.53 Resetting Initial position ……… 93
3.2.54 Setting for Original Position of Decoder ……… 95
4
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.3Alarm and Response
3.3.1 Description of Alarm ……… 99
3.4 Instruction for forming operation3.4.1 Setting for Temperature Control ……… 103
3.4.2 Setting for Temperature Deviation
(Alarm)……… 104
3.4.3 Setting for The Function of
Temperature Holding……… 105
3.4.4 Fully Automatic, Semi-Automatic,
Manual Options……… 105
3.4.5 Setting for Data on Position, Speed
And Pressure……… 105
3.4.6 Setting for Numeral Data on
Forming Conditions……… 106
3.4.7 Adjustment of Proportional
Numerical Control……… 106
3.4.8 Instructions for The Internal
Counter of The Computer……… 108
3.4.9 Instructions for Internal Timer of
The Computer……… 109
3.4.10 Input Points and Descriptions
thereof……… 113
3.5 Ai-01 Operations on special screens ……… 117
3.6 Ai-01 Wiring diagram ……… 118
5
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.1 Introduction to the Compute Panel3.1.1 Compute Panel
7ABC DEF
8 9GHI
5MNO
2VWX
JKL
4 6PQR
STU
1 3YZ
0 CLEAR
OFF
+ON
.CONFRM
确认
清除
MAN SEMI AUTO
手动 半自动 全自动
OPENCLOSE
PUMP ON
马达启动 马达停止
PUMP OFF
输入
ENTER
电热开/关
HEAT
预热开/关
PREHEAT
开模 锁模
INJ
射胶
PLAST
熔胶
EJECT FWD
退针 顶针
EJECT BWD
NOZZ FWD
座进 座退
NOZZ BWD
MELT DEC
松退
HELP
帮助监视
MONITOR
SLOW
慢速调试
MOLD BWD
调模后退调模前进
MOLD FWD
自动清料
AUTO PURGE
MOV. AIR
工模吹气
母模吹气
FIX. AIR
LUB
CORE B IN CORE C IN
手动润滑
入芯B 入芯C
主页面
MENU
开锁模
OP/CL. INJECTION
射胶
EJE/CORE
顶针/抽芯 时间/计数
TIM/CNT TEMP.
电热
FUNC.
功能
MOLD/STAT
模号/品管
MOLD ADJ.
调模
CORE A IN
入芯A
出芯C
CORE C OUTCORE B OUT
出芯B
CORE A OUT
出芯A
GRAPH
射胶曲线
压力 锁模 顶针 射胶
6
Pressure Modelock thimble Injection
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.12 Control Keys for Operation State
MAN SEMI AUTO
手动 半自动 全自动
This keyboard is designed to switch among forming operation states.
3.1.3 Setting Keys for Forming Condition
主页面
MENU
开锁模
OP/CL. INJECTION
射胶
EJE/CORE
顶针/抽芯 时间/计数
TIM/CNT TEMP.
电热
FUNC.
功能
MOLD/STAT
模号/品管
This keyboard offers the following functions:
(1) To set the position, speed, press, time, timer, temperature and the like of the
forming condition.
(2) To edite mold number and rewrite its data.
(3) To select functions or motions required in the process of formation according to
the requirements of finished product and mold design.
(4) To move the cursor to the desired spot to edit data on any operation interface.
7
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.1.4 Functions of auxiliary operation and key and cursor for numeral data on
forming condition
7ABC DEF
8 9GHI
5MNO
2VWX
JKL
4 6PQR
STU
1 3YZ
0 CLEAR
OFF
+ON
.CONFRM
确认
清除 输入
ENTER HELP
帮助监视
MONITOR GRAPH
射胶曲线
This keyboard offers the following functions:
(1) Press CLEAR
清除
输入
ENTER CONFRM
确认
3 keys together then power the compute on to
initialize the data on mold and system setting, after a long beep signifying that
the initialization is over, release the keys to proceed.
(2)When manipulate the compute, press CLEAR
清除
and at the same time to
turn pages up, and press CLEAR
清除
and to turn pages down.
(3) Numerical data requisite for inputting forming condition:
Speed setting ranges from 00%~99%, in which 00% means zero speed.
Press setting ranges from 00%~99%, in which 00% means zero press.
Position setting ranges from 0000~999.9 mm.
Time setting ranges from 0~999.9 sec.
Counter setting ranges from 0~65535.
Mold thickness setting ranges from 0~999.9mm.
(4) To check if the function keyboard is all right. (5) To monitor the operation states of all outputs, inputs, timer and counter. (6) To display the injection curve. (7) To review help information.
8
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.1.5 Manual Operation Keys and Instructions thereof
MAN SEMI AUTO
手动 半自动 全自动
OPENCLOSE
PUMP ON
马达启动 马达停止
PUMP OFF
电热开/关
HEAT
预热开/关
PREHEAT
开模 锁模
INJ
射胶
PLAST
熔胶
EJECT FWD
退针 顶针
EJECT BWD
NOZZ FWD
座进 座退
NOZZ BWD
MELT DEC
松退
SLOW
慢速调试
MOLD BWD
调模后退调模前进
MOLD FWD
自动清料
AUTO PURGE
MOV. AIR
工模吹气
母模吹气
FIX. AIR
LUB
CORE B IN CORE C IN
手动润滑
入芯B 入芯C
MOLD ADJ.
调模
CORE A IN
入芯A
出芯C
CORE C OUTCORE B OUT
出芯B
CORE A OUT
出芯A
Manual operation is applicable to single motion of the whole circle.
3.1.6 Power Switch
(1) Emergency Stop
It's at the left lower corner of the controller panel, red . Press it to cut off
the power. To reboot the machine, turn the knob in the direction indicated by arrow to
release this stopper.
(3) StartupIt’s at the right lower corner of the controller panel, green. After the emergency
stop is released, press this key to power the machine on. This key is designed to
protect the controller system.
(3) Equipped with voltage stabilizer of high performance, this controller is enabled toapplicable to power input of AC90-AC265V, 50/60HZ with vast variation.
9
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2 Operation Illustration for Computer Screen3.2.1 Compute Startup
Compute Startup Screen (00)
Network 2006/07/20 16:20
user ID : AA Password BB **%**%***bar 59.5mm 6.1mm 11.6mm
Compute Startup Screen (01)
ChenHsong Group Tel. No.: 0755-84139999 Fax No.: 0755-84137878 Model : JM88C1 Number : 00123456
Date of
Production: 23-03-2006
Program
Name: 8A
10
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Compute Startup Screen (02)
Password: ****** Please enter 6-digit password (Operator, Administrator, Factory) (Press Key to skip)
(1) After the compute is powered on and when the system is performing automatic test,at which moment the startup screen (00) is displayed, just input the account no. and
password you will be authorized to log into the control system if the system is online,
then, press the CLEAR
清除
key and hold it, the compute shall pause at (02), this screen
indicates the model, machine no. and the running program, in the event the machine
wants maintaining or technical answer to the inquiry, please fill the customer service
of this factory with these data so as to enjoy expeditious service.
(2) The system will switch to screen (02) 3 seconds later if the startup is not manuallyintervened, as this screen prompts: please input the 6-digit password, to skip please
press Menu Page key. If the corresponding password is input, then it will not
demanded again to input the password when you see this screen as the compute is
powered on but the system will directly enters into the page. This password is set by
the operator, administrator or the factory, 3 seconds later the system will
automatically run into the screen (03).
11
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.2 Normal Operation Setting
If the system is running normally, the screen(03) will be displayed asfollowing:
Normal Operation Screen (03)
2006-6-14 9:10
Injection
Nozzle
Temperature
1
Temperatur
e
2
Temperatur
e
3
Temperatur
e
4
Temperature
5
Temperature
6
Oil
Temperature
AA% BB CC DD EE FF GG HH
0 0 0 0
Quantity of Forming Mold IIt Filling time JJs
Cycle KKs Plasticizing time LLs
Cooling time MMs Injection end-point NNmm
**% **% ***bar 71.6mm 4.6mm 11.6mm
(1) After normal startup, the manual state is in default and the
screen (03) will be displayed. Give
主页面
MENUkey a press, and
screen (03) will also appear.
(2) To modify the set value, modify the stage desired in screen (03)
of normal operation, and press the key to select the
temperature value to set each stage.
(3) Input value, then press
输入
ENTER key, thus the setting is done.
In which:
“AA”: Setting for injection nozzle plus temperature proportion
“BB”: Setting for the temperature of the first stage
“CC”: Setting for the temperature of the second stage
“DD”: Setting for the temperature of the third stage
12
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“EE”: Setting for the temperature of the forth stage
“FF”: Setting for the temperature of the fifth stage (an optiondepending on the tonnage of the machine)
“GG”: Setting for the temperature of the sixth stage (an optiondepending on the tonnage of the machine)
“HH”: Setting for the oil temperature
“II”: Display the quantity of forming mold“JJ”: Display the filling time
“KK”: Display the cycle
“LL”: Display the plasticizing time
“MM”: Display the cooling time
“NN”: Display the injection end-point 3.2.3 Monitor over Cycle
Screen (04) of Monitor over Cycle
Monitor over cycle 2006/07/2016:20
Clamp
Mold Before
injection Injectio
n Pressure
Holding Delay
0.0 0.0 0.0 0.0 0.0
Recycle Cooling
Before
Unscrewi
ng 0.0 0.0 0.0
Ejecti
on Open
mold After
injection
After
unscrew
ing Plastic
izing 0.0 0.0 0.0 0.0 0.0 **% **% ***bar 59.5mm 6.1mm 11.6mm
Press
主页面
MENU
key twice then the screen (04) of monitor over cycle
will appear to display the motion cycle of the injection machine: clamp mold-
injector unit advance-injection-pressure maintenance-delay-ejection-recycle.
The corresponding value is the elapsed time of each step.
13
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.4 Setting for mold opening
Screen (05) of setting for mold opening
Setting for mold opening 2006-6-14 9:10 Speed Pressure Pressure
Fast mold opening AA% BB% CCP 2nd stage of mold opening DD% EE% FFmm 3rd stage of mold opening GG% HH% Iimm Fast mold opening JJ% KK% LLmm Slowed mold opening MM% NN% OOmm Reserved PPmm
Maximum stroke QQmm **% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press
开锁模
OP/CL.
key for once than the screen (05) of setting for
mold opening will appear.
(2) Press key to select parameters of mold opening.
Input value then press
输入
ENTER
to finish setting.
In which:
“AA”: Setting for speed of slow mold opening
“BB”: Setting for pressure of slow mold opening
“CC”: Setting for the end-point of mold opening
“DD”: Setting for speed of 2nd stage of mold opening
“EE”: Setting for pressure of 2nd stage of mold opening
“FF”: Setting for ending position of 2nd stage of mold opening
14
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“GG”: Setting for speed of 3rd stage of mold opening
“II”: Setting for ending position of 3rd stage of mold opening
“JJ”: Setting for speed of fast mold opening
“KK”: Setting for pressure of fast mold opening
“LL”: Setting for ending position of fast mold opening
“MM”: Setting for speed of slowed mold opening
“NN”: Setting for pressure of slowed mold opening
“OO”: Setting for ending position of slowed mold opening
“PP”: Setting for reserved of mold opening (Optional)
“QQ”: Display maximum stroke
←─── ←──── ←──── ←──── ←───
MM% NN% JJ% KK% GG% HH% DD% EE% AA% BB% Slowed mold Fast mold 3rd Stage of 2nd stage of slow mold
opening ↑ opening ↑ mold opening ↑ mold opening ↑ opening
OO mm LL mm II mm FF mm CC p
15
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.5 Setting for mold clamping
Screen (06) of setting for mold clamping
(1) Press
开锁模
OP/CL.
key twice then the screen (06) of setting for
mold clamping will appear.
(3) Press key to select parameters of mold clamping.
Input value then press
输入
ENTER key to finish.
In which
“AA”: Setting for speed of fast mold clamping
“BB”: Setting for pressure of fast mold clamping
“CC”: Setting for ending position of fast mold clamping
“DD”: Setting for speed of 2nd stage of mold clamping
“EE”: Setting for pressure of 2nd stage of mold clamping
“FF”: Setting for ending position of 2nd stage of mold clamping
16
Setting for mold clamping 2006-6-14 9:10 Time for mold clamping of low pressure 0.0s
Speed Pressure Position
Fast mold clamping AA% BB% CCmm 2nd stage of mold clamping DD% EE% FFmm 3rd stage of mold clamping GG% HH% IImm Mold clamping of low pressure JJ% KK% LLp Mold clamping of high pressure MM% NN% OOp
Reserved PPmm
Mold clamping force QQ ton **% **% ***bar 59.5mm 6.1mm 11.6mm
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“GG”: Setting for speed of 3rd stage of mold clamping
“HH”: Setting for pressure of 3rd stage of mold clamping.
“II”: Setting for ending position of 3rd stage of mold clamping
“JJ”: Setting for speed of mold clamping of low pressure
“KK”: Setting for pressure of mold clamping of low pressure
“LL”: Setting for ending position for mold clamping of lowpressure
“MM”: Setting for speed of mold clamping of high pressure
“NN”: Setting for pressure of mold clamping of high pressure
“OO”: Setting for ending position of mold clamping of high
pressure
“PP”: Setting for ending position of reserved of mold clamping
(Optional)
“QQ”: Display the tonnage of mold clamping force, this value is
automatically computed according to the FF p position.
←─── ←──── ←──── ←──── ←───
MM% NN% JJ% KK% GG% HH% DD% EE% AA% BB% Mold clamping Mold clamping 3rd stage 2nd stage Fast moldof high pressure↑of low pressure↑ mold clamping ↑ of mold clamping↑ clamping
OO p LL p II mm FF mm CC mm
17
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.6 Setting for injection pressure of mold clamping
Screen (07) of injection pressure of mold clamping
2006/07/20 16:20
Pressure of
mold clamping AA
Pressure of
injection BB **% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press
开锁模
OP/CL.
for 3 times or INJECTION
射胶
for 5 times and the
screen (07) of injection pressure of mold clamping will appear.
(3) Press key to select parameters of mold clamping.
Input value and press
输入
ENTER key to finish.
In which
“AA”: Maximum setting for pressure of mold clamping
“BB”: Maximum setting for injection pressure
18
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.7 Setting for injection
Screen (08) of setting for injection
Setting for injection 2006-6-14 9:10
Filling time AAs Injection ending
position BBmm
Injection time CCs
Speed Pressure Position
1st stage of injection DD
% EE% FFmm
2nd stage of injection GG
% HH% Iimm
3rd stage of injection JJ% KK% LLmm
4th stage of injection MM% NN% O
Omm
5th stage of injection PP% QQ% RRmm
**% **% ***bar 59.5mm 6.1mm 11.6m
m
(1) Press INJECTION
射胶
key for once and the screen (08) of setting for
injection of
(2) Press key to select parameters of injection.
Input value, then press
输入
ENTER
key to finish.
In which
“AA”: Display filling times at 1st-5th stages of injection.
“BB”: Display ending position of injection.
“CC”: Setting for injection time.
“DD”: Setting for speed of 1st stage of injection.
“EE”: Setting for pressure of 1st pressure of injection
19
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“FF”: Setting for ending position of 1st stage of injection
“GG”: Setting for speed of 2nd stage of injection
“HH”: Setting for pressure of 2nd stage of injection
“II”: Setting for ending position of 2nd stage of injection
“JJ”: Setting for speed of 3rd stage of injection
“KK”: Setting for pressure of 3rd stage of injection
“LL”: Setting for ending position of 3rd stage of injection
“MM”:Setting for speed of 4th stage of injection.
“NN”: Setting for pressure of 4th stage of injection
“OO”: Setting for ending position of 4th stage of injection
“PP”: Setting for speed of 5th stage of injection.
“QQ”: Setting for pressure of 5th stage of injection
“RR”: Setting for ending position of 5th stage of injection
←─────── Injection time TIM 0 ───────→
←──── ←───── ←───── ←───── ←──── PP% QQ% MM% NN% JJ% KK% GG% HH% DD% EE% 5th
stage of 4th stage of 3rd stage of 2nd stage of 1st stage of
injection injection injection injection injection Mold flash ↑ ↑ ↑ ↑
RR mm OO mm LL mm II mm FF mm
20
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.8 Setting for pressure holding
Screen (09) of setting for pressure holding Setting for pressure holding 2006-6-14 9:10
Filling time 0.00s Injection ending
position 0.0mm Injection time AAs Injection termination BBmm Speed Pressure Time
1st stage of
pressure holding CC% DD% EEs
2nd stage of pressure holding FF% GG% HHs
3rd stage of pressure holding II% JJ% KKs
4th stage of pressure holding LL% MM
% NN%
5th stage of
pressure holding OO
% PP% QQ%
**% **
% ***bar 59.5mm 6.1m
m 11.6m
m
(1) PressINJECTION
射胶
key twice and the screen of (09) of setting for
pressure holding will appear.
(2) Press key to select parameters.
Input value then press
输入
ENTER
to finish.
In which
“AA”: Setting for injection time ( to convert time into pressure
holding)
“BB”: Setting for ending position of injection
21
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“CC”: Setting for speed of 1st stage of pressure holding
“DD”: Setting for pressure of 1st stage of pressure holding
“EE”: Setting for time of 1st stage of pressure holding
“FF”: Setting for speed of 2nd stage of pressure holding
“GG”: Setting for pressure of 2nd stage of pressure holding
“HH”: Setting for time of 2nd stage of pressure holding
“II”: Setting for speed of 3rd stage of pressure holding
“JJ”: Setting for pressure of 3rd stage of pressure holding
“KK”: Setting for time of 3rd stage of pressure holding
“LL”: Setting for speed of 4th stage of pressure maintenance
“MM”: Setting for pressure of 4th stage of pressure holding
“NN”: Setting for time of 4th stage of pressure holding
“OO”: Setting for speed of 5th stage of pressure holding
“PP”: Setting for pressure of 5th stage of pressure holding
“QQ”: Setting for time of 5th stage of pressure holding
QQ Sec NN Sec KK Sec HH Sec EE Sec
←──── ←───── ←───── ←─────
←──── OO% PP% LL% MM% II% JJ% FF% GG% CC% DD%
5th stage of 4th stage of 3rd stage of 2nd stage of 1st stage of
pressure holding pressure holding pressure holding pressure holding pressure
holding
22
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.9 Setting for Plasticizing/Unscrewing
Screen (10) for setting of plasticizing/Unscrewing
Setting of Plasticizing/Unscrewing 2006-6-14 9:10
Plasticizing time AAs Injection ending position BBmm
Plasticizing delay CCs Alarm against low temperature DD
Speed Pressure Screw backpressure Position
1st stage of plasticizing EE% FF% GG% HHmm
2nd stage of plasticizing II% JJ% KK% LLmm
3rd stage of plasticizing MM
% NN% OO% PPmm
Unscrewing QQ% RR% SSmm
Maximum stroke T
Tmm
**% **% ***bar 59.5m
m 6.1mm 11.6m
m
(1) PressINJECTION
射胶
key for 3 times and the screen (10) of setting for
Plasticizing/Unscrewing.
(2) Press key to select parameter of plasticizing.
Input value and press
输入
ENTER
key to finish.
23
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
In which
AA: Display plasticizing time
BB: Display of injection ending position
CC: Setting for plasticizing delay
DD: Option for alarm against low temperature, press
+ON
OFF
to set (In the program, this function is disabled.)
“EE”: Setting for speed of 1st stage of plasticizing
“FF”: Setting for pressure of 1st stage of plasticizing
“GG”: Setting for screw backpressure of 1st stage of plasticizing
“HH”: Setting for ending position of 1st stage of plasticizing
“II”: Setting for speed of 2nd stage of plasticizing
“JJ”: Setting for pressure of 2nd stage of plasticizing
“KK”: Setting for screw backpressure of 2nd stage of plasticizing
“LL”: Setting for ending position of 2nd stage of plasticizing
“MM”: Setting for speed of 3rd stage of plasticizing
“NN”: Setting for pressure of 3rd stage of plasticizing
“OO”: Setting for screw backpressure of 3rd stage of plasticizing
“PP”: Setting for ending position of 3rd stage of plasticizing
“QQ”: Setting for speed of unscrewing
“RR”: Setting for pressure of unscrewing
“SS”: Setting for ending position of unscrewing
“TT”: Maximum stroke
←─── ←──── ←──── ←────
QQ% RR% MM% NN%OO% II% JJ% KK% EE% FF% GG%
↑ Unscrewing ↑3rd stage of plasticizing ↑2nd stage of plasticizing ↑1st stage of
plasticizing
SS mm PP mm LL mm HH mm
24
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.10 Setting for automatic purge
Screen (11) of automatic purge Setting for automatic purge 2006-6-14 9:10 Plastic Purge AAt Time Speed Pressure Screw backpressure Position
Plasticizin
g BB% CC% DD% EEs
Injection FF% GG% HHmm
Unscrewing II% JJ% KKmm
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press INJECTION
射胶
key for 4 times and the screen (11) of automatic
purge will appear.
(2) Press key to select parameters for automatic purge.
Input value and press
输入
ENTER
key to finish.
25
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
In which
“AA”: Setting for times of automatic purge.
“BB”: Setting for plasticizing speed
“CC”: Setting for plasticizing pressure
“DD”: Setting for screw backpressure of plasticizing
“EE”: Setting fro time of plasticizing motion
“FF”: Setting for speed of injection
“GG”: Setting for pressure of injection
“HH”: Setting for ending position of injection
“II”" Setting for speed of unscrewing
“JJ”: Setting for pressure of unscrewing
“KK”: Setting for ending position of unscrewing
3.2.11 Setting for ejection
Screen (12) of setting for ejection
Setting for ejection 2006-6-14 9:10
Times AAt Vibration BBt
Pause CCs Start DDmm
Mode EE
Speed Pressure Position
1st stage of ejection FF% GG% HHmm
2nd stage of ejection II% JJ% KKmm
1st stage of ejector retraction LL% MM% NNmm
2nd stage of ejector retraction OO% PP% QQmm
Maximum stroke RRmm
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) PressEJE/CORE
顶针/抽芯
key and the screen (12) of setting for ejection
will appear.
(2) Press key to select parameters of ejection .
26
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Input value and press
输入
ENTER
key to finish.
In which
“AA”: Setting for times of ejection.
“BB”: Setting for vibration times of ejector (in conjunction with
multi-ejection.)
“CC”: Display pause of ejection.
“DD”:Setting for the beginning point of mold opening for the
synchronous ejection in the process of mold opening
“ EE”: Ejection mode, press
+ON
OFF
to select
among the following 3
(i) No motion
(ii) Ejection pause
(iii) Multi-ejection
“FF”: Setting for speed of 1st ejector advance
“GG”: Setting for pressure of 1st ejector advance
“HH”: Setting for ending position of 1st ejector advance
“II”: Setting for speed of 2nd ejector advance
“JJ”: Setting for pressure of 2nd ejector advance
“KK”: Setting for ending position of 2nd ejector advance
“LL”: Setting for speed of 1st ejector retraction
“MM”: Setting for pressure of 1st ejector retraction
“NN”: Setting for switch point of decelerating motion of 1st
ejector retraction
“OO”: Setting for speed of 2nd ejector retraction
“PP”: Setting for pressure of 2nd ejector retraction
“QQ”: Setting for switch point of decelerating motion of 2nd
ejector retraction
“RR”: Setting for maximum stroke
Ejector advance
HHmm KKmm Ejection Termination1st stage 2nd stage
27
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
──────────→ ───────────→
FF% GG% II% JJ%
←── NN mm ──→ ←────────── ←──────────
OO% PP% LL% MM%
Retraction Termination
Ejector retraction
3.2.12 Setting for Injector unit
Screen (13) of setting for injector unit Setting for injector unit 2006-6-14 9:10 Speed Pressure Time
Fast injector unit AA% BB% CCs
Slow injector unit DD% EE%
Injector unit retraction FF% GG% HHs
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) PressEJE/CORE
顶针/抽芯
key twice and the screen (13) of setting for
injector unit will appear.
(3) Press key to select parameters of injector unit
28
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Input value and press
输入
ENTER
key to finish.
In which
“AA”: Setting for speed of fast advance of injector unit
“BB”: Setting for pressure of fast advance of injector unit
“CC”: Setting for time of stroke of fast advance of injector unit
“DD”: Setting for speed of slow advance of injector unit
“EE”: Setting for pressure of slow advance of injector unit
“FF”: Setting for speed of slow retraction of injector unit
“GG”: Setting for pressure of retraction of injector unit
“HH”: Setting for time of stroke of retraction of injector unit3.2.13 Setting for air blow
Screen (14) of setting for air blow
Setting for air blow 2006-6-14 9:10
Startup point of 1st air
blow AAmm
Motion of 1st air blow BBs
2nd air blow after mold opening CCs
Delay prior to 3rd air blow DDs
Motion of 3rd air blow EEs
**% **
% ***bar 59.5mm 6.1mm 11.6mm
(1) Press EJE/CORE
顶针/抽芯
for 3 times and the screen (14) of setting for
air blow will appear.
29
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(2) Press key to select parameter of air blow.
Input value and press
输入
ENTER
key to finish.
In which
1st air blow is startup in the process of mold opening.
2nd air blow is startup on the instant mold opening terminates.
3rd air blow is delayed startup after the mold opening terminates.
“AA”: The point of mold opening when 1st air blow starts up.
“BB”: Duration of 1st air blow
“CC”: Duration of 2nd air blow
“DD”: Delay prior to 3rd air blow
“EE”: Duration of 3rd air blow3.2.14 Setting for core pulling A
Screen (15) of setting for core pulling A
Setting for core-in A 2006-6-14 9:10
Core-in mode AAs
Core-out mode BBs
Core in/out recycle CC
Speed Pressure Time
Core in DD% EE% FFss
Core out GG% HH% IIss
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Pres EJE/CORE
顶针/抽芯
key for 4 times and the screen (15) of setting
for core pulling will appear.
(2) Press key to select parameters of core pulling.
30
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Input values, and press
输入
ENTER
key to finish.
In which
“AA”: Selections for core-in motion: press
+ON
and
OFF
keys to select from the following four modes:
(1) Before mold clamping (2) After mold clamping
(3) In the process of mold clamping (to set the point
of mold clamping to start up core-in motion)
(4) Not used
“BB” : Selections for core-out motion: press
+ON
and
OFF
keys to select from the following 4
(1) Before mold opening (2) After mold opening (3)In the process of mold opening (to set the point ofmold opening to start up core pulling)
(4) Not used
“ CC” : Setting for Core in/out recycle: press
+ON
and
OFF
keys to select from the following 2 modes:
(1) Time (2) Position switch
“DD”: Setting for speed of core-in motion
“EE”: Setting for pressure of core-in motion
“FF”: Setting for time of core-in motion
“GG”: Setting for speed of core-out motion
“HH”: Setting for pressure of core-out motion
“II”: Setting for time of core-out motion
31
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.15 Setting for Core Pulling B
Screen (16) of Core Pulling B
Setting for core-in 2006-6-14 9:10
Core-in mode AAs Core-out mode BBs Core in /out recycle CC
Speed Pressure Time
Core in DD% EE% FFss
Core out GG% HH% IIss
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press EJE/CORE
顶针/抽芯
key for 5 times and the screen (16) of setting
for core pulling B will appear.
(2) Press key to select parameters of core pulling.
32
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Input values and press
输入
ENTER
key to finish.
In which
“AA”: Selections for core-in motion: press
+ON
and
OFF
keys to select from the following four modes:
(1) Before mold clamping (2) After mold clamping(3) In the process of mold clamping (to set the point
of mold clamping to start up core-in motion)
(4) Not used
“BB” : Selections for core-out motion: press
+ON
and
OFF
keys to select from the following 4
(1) Before mold opening (2) After mold opening (3)In the process of mold opening (to set the point ofmold opening to start up core pulling)
(4) Not used
“ CC” : Setting for Core in/out recycle: press
+ON
and
OFF
keys to select from the following 2 modes:
(1) Time (2) Position switch
“DD”: Setting for speed of core-in motion
33
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“EE”: Setting for pressure of core-in motion
“FF”: Setting for time of core-in motion
“GG”: Setting for speed of core-out motion
“HH”: Setting for pressure of core-out motion
“II”: Setting for time of core-out motion
34
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.16 Setting for Core pulling CScreen (17) of Setting for Core pulling C
Setting for core-in C 2006-6-14 9:10
Core-in mode AAs Core-out mode BBs
Core in/out recycle CC
Speed Pressure Times Time
Core-in DD% EE% GG s
Core-out HH% II % KK s
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press EJE/CORE
顶针/抽芯
key for 6 times and the screen (17) of
setting for core pulling C will appear.
(2) Press key to select parameters of core pulling.
Input values and press
输入
ENTER
key to finish.
In which
“AA”: Selections for core-in motion: press
+ON
and
OFF
keys to select from the following four modes:
(1) Before mold clamping (2) After mold clamping
(3) In the process of mold clamping (to set the point
of mold clamping to start up core-in motion)
(4) Not used
35
FF t tF
JJ t
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“BB” : Selections for core-out motion: press
+ON
and
OFF
keys to select from the following 4
(1) Before mold opening (2) After mold opening (3)In the process of mold opening (to set the point ofmold opening to start up core pulling)
(4) Not used
“ CC”: Setting for Core in/out recycle: press
+ON
and
OFF
keys to select from the following 2 modes:
(1) Time (2) Position switch (3) Count
“DD”: Setting for speed of core-in motion
“EE”: Setting for pressure of core-in motion
“FF”: Setting for times of core-in motion
“GG”: Setting for time of core-in motion
“HH”: Setting for speed of core-out motion
“II”: Setting for pressure of core-out motion
“JJ”: Setting for times of core-out motion
“KK”: Setting for time of core-out motion
36
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.17 Setting for time
Screen (18) of Setting for time
2006/07/20 16:20Setting for timer 2006/07/20 16:20
Plasticizing delay AA Termination of advance of injector unitI I
Cooling time BB Injection delay J J
Recycle CC Ejector vibration K K
Unscrewing before plasticizing DD Reserved 42 L L
Cycle alarm EE Reserved 43 MM
Delay after termination of mold opening FF Reserved 44 N N
Monitor over mold clamping of lower pressGG Reserved 45 O O
Fast advance of injector unit HH Reserved 46 P P
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press
时间/计数
TIM/CNT
key for once and the screen (18) of setting for
time will appear.
(2) Press to select time options.
Input values and press
输入
ENTER
key to finish.
In which
“AA”: Setting for plasticizing delay
“BB”: Setting for cooling time
“CC”: Setting for recycle time
“DD”: Setting for time of prior-to-plastication unscrewing
“EE”: Setting for time of cycle alarm
“FF”: Setting for delay after termination of mold opening
“GG”: Setting for time of monitor over mold clamping of lowpress
37
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“HH”: Setting for time of fast advance of injector unit
“II”: Setting fort time of delay after termination of advance ofinjector unit
“JJ”: Setting for delay of injection
“KK”: Setting for time of core-out motion after vibration ofejector
“LL”: Delay of core-out motion of injector unit afterunscrewing
“MM”: Reserved
“NN”: Reserved
“OO”: Reserved
“PP”: Reserved
38
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.18 Setting 1 of Counter
Screen (19) of Setting for Counter
Setting for Counter 2006/07/20 16:20
Quantity of forming
mold AA Times of Core-in
motion C II
Quantity of defective
mold BB Times of Core
Pulling C JJ
Production time CC
Reserved 07 DD
Monitor over cycle EE
Clamping mold with mold
adjustment force FF
Pressing mold with mold
adjustment force GG
Reserved HH
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press
时间/计数
TIM/CNT
key for twice and the screen (19) of setting for
counter appear.
(2) Press key to select options of counter.
Input values and press
输入
ENTER key to finish.
Input
“AA”: Setting for quantity of forming mold
“BB”: Setting for alarm against an excess of defective products
“CC”: Setting for automatic production time
“DD”: Reserved
“EE”: Monitor over cycle
“FF”: Setting for clamping mold with mold adjusting force
39
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“GG”: Setting for pressing mold with mold adjusting force
“HH”: Reserved
“II”: Times of core-in motion C
“JJ”: Times of core pulling C
3.2.19 Setting for alarm against temperature deviation
Screen (20) of setting for alarm against temperature deviation
Temperature 2006/06/14 11:45
Injection Temperature 1 Temperature2 Temperature 3 Temperature 4 Temperature 5 Temperature 6 Oil Temperature
AA% BB CC DD EE 十
0 0 0 0
十 FF 十 GG 十 HH 十 II 十 JJ 十 KK 十 LL 十 MM
一 NN 一一一一 OO 一 PP 一 QQ 一 RR 一 SS 一 TT 一 UU
Temperature holding VV%
**% **% ***bar 71.6mm 4.6mm 11.6mm
(1) PressTEMP.
电热
key than the screen (20) of setting for alarm
against temperature deviation.
(2) Press key to select options of alarm against
temperature deviation for each stage . Input value and press
输入
ENTER key to
finish.
In which
“AA”: Setting for temperature of ejection nozzle
“BB”: Setting for temperature of 1st stage
“CC”: Setting for temperature of 2nd stage
40
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“DD”: Setting for temperature of 3rd stage
“EE”: Setting for temperature of 4th stage
“ FF”: Setting for alarm against higher temperature than that of
injection nozzle
“GG”: Setting for alarm against higher temperature than set value of
1st stage
“HH”: Setting for alarm against higher temperature than set value of
2nd stage
“II”: Setting for alarm against higher temperature than set value of
3rd stage
“JJ”: Setting for alarm against higher temperature than set value of
4th stage
“KK”: Setting for alarm against higher temperature than set value of
5th stage
“LL” Setting for alarm against higher temperature than set value of
6th stage
“MM”: Setting for alarm against lower oil temperature
“NN”: Setting for alarm against lower temperature than set value of
injection nozzle
“OO”: Setting for alarm against lower temperature than set value of
1st stage.
“PP”: Setting for alarm against lower temperature than set value of
2nd stage.
“QQ”: Setting for alarm against lower temperature than set value of
3rd stage.
“RR”: Setting for alarm against lower temperature than set value of
4th stage.
“SS”: Setting for alarm against lower temperature than set value of
5th stage.
“TT”: Setting for alarm against lower temperature than set value of
6th stage.
“UU”: Setting for alarm against lower temperature than set value of
oil
“VV”: Setting for time percentage of temperature holding
41
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.20 Setting for temperature of hot runner
Screen (21) of setting for temperature of hot runner
Temperature of hot runner 2006/07/20 16:20 T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 AA BB CC DD EE FF GG HH II JJ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ T11 T12 T13 T14 T15 T16 T17 T18 T19 T20 KK LL MM NN OO PP QQ RR SS TT _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Data Copy All UU **% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (22) of setting for temperature of hot runner
Temperature of hot runner 2006/07/20 16:20 T21 T22 T23 T24 T25 T26 T27 T28 T29 T30 AA BB CC DD EE FF GG HH II JJ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ T31 T32 T33 T34 T35 T36 T37 T38 T39 T40 KK LL MM NN OO PP QQ RR SS TT _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
42
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Data Copy All UU **% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press TEMP.
电热
key twice and the screen (21) of setting for
temperature of hot runner will appear.
Press TEMP.
电热
key for 3 times and the screen (22) of setting
for temperature of hot runner will appear.
(2) Press TEMP.
电热
key select options for alarm against
temperature deviation for each stage. Input value and press
TEMP.
电热
key to finish.
In which
“AA”: Setting for T1 temperature
“BB”: Setting for T2 temperature
“CC”: Setting for T3 temperature
“DD”: Setting for T4 temperature
“EE”: Setting for T5 temperature
“FF”: Setting for T6 temperature
“GG”: Setting for T7 temperature
“HH”: Setting for T8 temperature
“II”: Setting for T9 temperature
“JJ”: Setting for T10 temperature
“KK”: Setting for T11 temperature
“LL”: Setting for T12 temperature
“MM”: Setting for T13 temperature
“NN”: Setting for T14 temperature
“OO”: Setting for T15 temperature
“PP”: Setting for T16 temperature
“QQ”: Setting for T17 temperature
“RR”: Setting for T18 temperature
43
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“SS”: Setting for T19 temperature
“TT”: Setting for T20 temperature
3.2.21 Setting for function
Screen (23) for setting of function selection
Function setting 2006/07/20 16:20
Express mold clamping OFF Manipulator OFF
Air blow OFF Alarm of nozzle clog OFF
Nitrogen injection OFF Alarm of plastic leakage OFF
Unscrewing before plasticizing OFF Alarm of shortage OFF
Fast injection OFF Auto color
changing OFF
Express plasticizing OFF Core pulling in
order OFF
Reserved 06 OFF Special ejection OFF
Injection nozzle of oil pressure OFF Special core pulling OFF
Electronic eye OFF Reserved OFF
Auto stop Not
used
Synchronization Not
used
Switch of pressure holding Position
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press FUNC.
功能
key and the screen (23) of function selection will appear.
(2) Press key and move to the option of function selection,
press
+ON
key to select ON, press
OFF
key to select
OFF, then finish setting.
(3) Auto stop Option: Press
+ON
and
OFF
key to select
the following mode, this function is to be used in
44
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
conjunction with the setting of quantity of
forming mold and production batch and
malfunction stop.
(i) Not used
(ii) Oil bump
(iii) Electric heat
(iv) Oil bump and electric heat
(4) Switch option of pressure holding : Switch between filling and
pressure holding:
(i)Time: With this option, as the timer TIM014 runs out, the
pressure holding is switched over.
(ii)Position: With this option, the pressure holding is set at the
position of 5th stage
(iii)Press: Pressure sensor should be used in conjunction with this
option, as the injection pressure reaches the preset value, the
pressure holding will be switched over.
(5) Nitrogen injection: As this option is set on, the Nitrogen injectiondevice is available(this device is to be specially ordered by the
user).
(6) Alarm against leakage: As this option is set on, when there is
plastic leakage at the nozzle, the alarm will sound. (Additional
device)
(7) Alarm against shortage: As this option is set on, the alarm will go
off as the bucket is short of material; as this option is set off, even if the
cooling time is over but the plasticizing is not finished, yet the alarm
will not go off.
(8) Synchronous motion
(i) Ejection: As this option is set on, it is possible toopen mold while ejection is being carried out. This
position where the mold starts opening when the ejection
starts.
(ii) Plasticizing: With this option on, it is possible to
open mold and carry out ejection while plasticizing.
(iii) Core pulling: With this option on, it’s possible to
carry out core-in/out motion while opening and clamping
mold.
(iv) Not used
(9) For the meanings of other functions, they are self-evident by the
terms and this manual shall refrain from elaborating.
45
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.22 Selection of mold number
Screen (24) of selection of mold number
Selection of mold number 2006/07/20 16:20 001 002 003 004 005 006 007 008 009 010 011 012 013 014 015 016 017 018
Mold
number AA BB
Copy mold
number CC —> DD
Select mold
number EE **% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (25) of selection of mold number
Selection of mold number 2006/07/20 16:20
Mold number
transmission FF
46
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Mold number reception GG **% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press
MOLD/STAT
模号/品管
key once and the screen (24) of selection of mold
number will appear.
Press key twice and the screen (25) of selection of mold number
will appear.
In which
“AA”: means the number of the mold parameter desired
“BB”: Means basic remarks on the mold number
“CC”: Means the mold number to be copied
“DD”: Means the mold number saved after being copied.
“ EE”: Means the code of mold number currently in use. To
change the code, it can only be done in the manual state.
“ FF”: Means the mold number to be transmitted to other
machine.
“GG”: Means the mold number received from other machine.(2) How to input the name of mold number
Move the cursor to AA of mold number and input number, then
press
输入
ENTERkey to finish mold number setting. Press
key to move the cursor to BB, input code in English or
digit from left to right, and press key to input the next
digit, then press
输入
ENTER
key to finish setting for remarking on
mold number.
(3) To change the mold number 01 to 02, follow the operationprocedure:
47
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(i) Move the cursor to EE of mold number selection, input 02 and
press
输入
ENTERkey, to confirm, press
CONFRM
确认
key, if not, press
CLEAR
清除
key.
(ii) There are 1-150 sets of memory available for the mold number,
in which 1 to 99 of compute mold number are standard data
module, and 101-150 are easy operation module (some data of
the easy operation module is not editable, in this case, use
mold number 100 to edit data). Uneditable data could not be
copied, so please think twice before using mold number 100,
some data in this module shall available for uneditable data in
mold number from 101 to 150.
3.2.23 Statistics
Screen (26) of quality statistics
Statistics 2006-6-14 9:10
Target Deviation Present Previous
Times of recycle AA BB
Time of recycle CC DD
Time of injection EE FF
Time of plasticizing GG HH
Injection termination II JJ
Plasticizing termination KK LL
Quality CLEAR SEND No No
Production time MM
Production times NN Reject OO 0%
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press
MOLD/STAT
模号/品管
key for 3 times and the screen (26) of statistics on
quality.
48
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(2) Press key to selection option. Input value and press
输入
ENTERkey to finish.
In which
“AA”: Present production times
“BB”: Previous production times
“CC”: Target value of recycle time
“DD”: Deviation from recycle time
“EE”: Target value of injection time
“FF”: Deviation from injection time
“GG”: Target value of plasticizing time
“HH”: Deviation from plasticizing time
“II”: Target value of injection termination time
“JJ”: Deviation from injection termination time
“KK”: Target value of plasticizing termination time
“LL”: Deviation from plasticizing termination time
“MM”: Production time. Press input key when the cursor is
moved here, a ? will appear next to the cursor, then
press Enter to clear the datum.
“NN”: Production times. Press input key when the cursor is
moved here and a ? will appear next to the cursor, then
press Enter to clear the NN and OO.
“OO”: Quantity of rejectCLEAR: Clear the statistics. Press Enter when the cursor is
moved here and a ? will appear next to the cursor,
then press Enter to clear the data in this page.
49
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.24 Monitor over time
Screen (27) of monitor over time
Monitor over time 2006/07/20 16:20 Set. Act. Set. Act. TM00 999.9 0.0 TM10 999.9 0.0 TM01 999.9 0.0 TM11 999.9 0.0 TM02 999.9 0.0 TM12 999.9 0.0 TM03 99.99 0.00 TM13 0.2 0.0 TM04 999.9 0.0 TM14 1.0 0.0 TM05 0.1 0.0 TM15 0.3 0.0 TM06 3.0 0.0 TM16 0.3 0.0 TM07 999.9 0.0 TM17 0.3 0.0 TM08 99.99 0.00 TM18 0.1 0.0 TM09 999.9 0.0 TM19 0.1 0.0 **% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (28) of monitor over time
Monitor over time 2006/07/20 16:20
50
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Set. Act. Set. Act. TM20 999.9 0.0 TM30 999.9 0.0 TM21 999.9 0.0 TM31 999.9 0.0 TM22 999.9 0.0 TM32 999.9 0.0 TM23 99.99 0.00 TM33 0.2 0.0 TM24 999.9 0.0 TM34 1.0 0.0 TM25 0.1 0.0 TM35 0.3 0.0 TM26 3.0 0.0 TM36 0.3 0.0 TM27 999.9 0.0 TM37 0.3 0.0 TM28 99.99 0.00 TM38 0.1 0.0 TM29 999.9 0.0 TM39 0.1 0.0 **% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (29) of monitor over time
Monitor over time 2006/07/20 16:20 Set. Act. Set. Act. TM40 999.9 0.0 TM50 999.9 0.0 TM41 999.9 0.0 TM51 999.9 0.0 TM42 999.9 0.0 TM52 999.9 0.0 TM43 99.99 0.00 TM53 0.2 0.0 TM44 999.9 0.0 TM54 1.0 0.0 TM45 0.1 0.0 TM55 0.3 0.0 TM46 3.0 0.0 TM56 0.3 0.0 TM47 999.9 0.0 TM57 0.3 0.0 TM48 99.99 0.00 TM58 0.1 0.0 TM49 999.9 0.0 TM59 0.1 0.0 **% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (30) of monitor over time
Monitor over time 2006/07/20 16:20
51
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Set. Act. Set. Act. TM60 999.9 0.0 TM70 999.9 0.0 TM61 999.9 0.0 TM71 999.9 0.0 TM62 999.9 0.0 TM72 999.9 0.0 TM63 99.99 0.00 TM73 0.2 0.0 TM64 999.9 0.0 TM74 1.0 0.0 TM65 0.1 0.0 TM75 0.3 0.0 TM66 3.0 0.0 TM76 0.3 0.0 TM67 999.9 0.0 TM77 0.3 0.0 TM68 99.99 0.00 TM78 0.1 0.0 TM69 999.9 0.0 TM79 0.1 0.0 **% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (31) of monitor over time
Monitor over Time 2006/07/20 16:20 Set. Act. Set. Act. TM80 999.9 0.0 TM90 999.9 0.0 TM81 999.9 0.0 TM91 999.9 0.0 TM82 999.9 0.0 TM92 999.9 0.0 TM83 99.99 0.00 TM93 0.2 0.0 TM84 999.9 0.0 TM94 1.0 0.0 TM85 0.1 0.0 TM95 0.3 0.0 TM86 3.0 0.0 TM96 0.3 0.0 TM87 999.9 0.0 TM97 0.3 0.0 TM88 99.99 0.00 TM98 0.1 0.0 TM89 999.9 0.0 TM99 0.1 0.0 **% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press
监视
MONITOR, the screen (27) of monitor over time will appear.
52
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(2) The setting and operation of all timers can be monitored in this screen. If
other timers need monitoring, press and CLEAR
清除
, switch
between any two screens from (27) to (31).
3.2.25Monitor over counter
Screen (32) of monitor over counter
Monitor over counter 2006/07/20 16:20
Set. Act. Set. Act. CT000 65535 5159 CT10 0 0 CT001 1234 1234 CT11 0 0 CT002 0 143 CT12 0 0 CT003 0 0 CT13 0 0 CT004 1 1 CT14 0 0 CT005 0 0 CT15 0 0 CT006 35 0 CT16 0 0 CT007 0 0 CT17 0 0 CT008 0 0 CT18 0 0 CT009 0 0 CT19 0 0 **% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press
监视
MONITOR twice, the screen (32) of monitor over time will appear.
(2)The setting and operation of all counters can be monitored in this screen.
53
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.26Monitor over input
Screen (33) of monitor over input
Monitor over input 2006/07/20 16:20
EI00:
Front Safety
Door ○ EI10:
Electronic Eye
Confirmation ○
EI01:
Back Safety
Door ○ EI11:
Storage
Termination ○
EI02: Safety Door ○ EI12:
Mechanical and
manual clamping ○
EI03:
Nozzle Front
Side ○ EI13: Injecting Allowed ○
EI04: Core-in B End ○ EI14:
Take-out
completed ○
EI05:
Core-out B
End ○ EI15:
Confirmation of
Injecting Plate ○
EI06: Reserved ○ EI16:
Adjustment Mold
Overloading ○
EI07: Nozzle Cover ○ EI17:
Oil Pump
Overloading ○
EI08: Core-in A End ○ EI18:
Adjustment Mold
Front Side ○
EI09:
Core-out A
End ○ EI19:
Adjustment Mold
Back Side ○
**% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (34) of monitor over inputMonitor over input 2006/07/20 16:20
54
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
EI20:
Adjustment
Mold
Displacement ○ EI30:
Resetting of
Injection ○
EI21:
Level of
Lubricant ○ EI31:
Resetting of
Injection ○
EI22:
Lubricating
Press ○
EI23: Core-in C End ○
EI24: Core-out C End ○
EI25:
Oil Filtering
Machine ○
EI26: Reserved ○
EI27:
Termination of
Door Opening ○
EI28:
Termination of
Door Closing ○
EI29:
Resetting of
Clamping Mold ○
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press
监视
MONITOR three times. The screen (33) of monitor over input will
appear.
(2)All kinds of input can be monitored in this screen. If any other input needs
monitoring, press and CLEAR
清除
at the same time and switch
between screen (33) and (34).
55
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.27 Monitor over output
Screen (35) of monitor over outputMonitor over output 2006/07/20 16:20
EO00:
Adjustable mold
advance ○ E010: Ejector retraction ○
E001:
Adjustable Mold
retraction ○ E011: Express ○
E002:
Clamping mold
advance ○ E012: Core-in A ○
E003: Nozzle advance ○ E013: Core-out A ○
E004: Injection ○ E014: Core-in B ○
E005:
Plasticizin
g ○ E015: Core-out B ○
E006:
Unscrewi
ng ○ E016: Filling Press ○
E007: Nozzle retraction ○ E017:
Releasing
Press ○
E008:
Mold
opening ○ E018: Air blow 2 ○
E009: Ejector advance ○ E019: Air blow 1 ○
**% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (36) of monitor over output Monitor over output 2006/07/20 16:20
56
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
E020:
Backpress of Mold
opening ○ E030: Core-in C ○
E021:
High Speed/Low
Press ○ E031: Core-out C ○
E022:
Low Pressure of
mold clamping ○
E023: Reserved ○
E024:
Automatic
Opening of
Door ○
E025:
Automatic
Closing of Door
○
E026:
Fast Mold
opening ○
E027: Fully Automatic ○
E028:
Termination of
Mold opening ○
E029:
Safety Closing of
Door ○
**% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (37) of monitor over output Monitor over time 2006/07/20 16:20
ER00:
Function of
Oil Pump ○
ER01:
Startup of
Oil Pump ○
ER02:
Lubricant
Pump ○
ER03: Alarm ○
ER04: 4NO ○
**
%
**
% ***bar 59.5m
m 6.1mm 11.6mm
57
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(1)Press
监视
MONITOR for four times. The screen (35) of monitor over output
will appear.
(2)All output can be monitored in this screen. If other output need monitoring,
press and CLEAR
清除
, and switch between any two screens
from screen (35) to (37).
3.2.28 Monitor over relay
Screen (38)of monitor over relay Monitor over relay 2006/07/20 16:20 01234 56789 01234 56789
EI000 …… …… …… ……
EI020 …… …… …… ……
EI040 …… …… **% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (39) of monitor over relay Monitor over relay 2006/07/20 16:20 01234 56789 01234 56789
E0000 …… …… …… ……
E0020 …… …… …… ……
58
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
E0040 …… … **% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (40) of monitor over relay
Monitor over relay 2006/07/20 16:20 01234 56789 01234 56789
ER000 …@… … **% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (41) of monitor over relay
Monitor over relay 2006/07/20 16:20 01234 56789 01234 56789
KY000 …@… …@… …… ……
59
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
KY020 …… …… ……
**% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (42)of monitor over relay
Monitor over relay 2006/07/20 16:20 01234 56789 01234 56789
LS000 …… …… …… ……
LS020 …… …… …@… ……
LS040 …… …… … **% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press
监视
MONITOR five times. The screen (38) of monitor over
relay will appear.
60
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(2)The state of all internal relays can be monitored in this screen.
If the state of other relays need monitoring, press
and CLEAR
清除
,and switch between any two screens among all of
relay monitoring.
3.2.29 Monitor over procedure
Screen (43) of monitor over procedure Monitor over procedure 2006/07/20 16:20 AA BB Search 00000 LDI EI000 . 00001 AND EI002 . 00002 OUT WK020 . 00003 ANI EI001 . 00004 OUT WK068 . 00005 LDI KY005 . 00006 ANI EI001 . 00007 OR ER001 . 00008 ANI LS040 . 00009 ANI KY006 @ **% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press
监视
MONITOR six times. The screen (34) of monitor over
procedure will appear.
(2)AA:Find the output location of internal relays. Press
+ON
and
OFF
, and switch different types of
61
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
internal relays. Then press them to confirm.
BB:Find the output location of internal number. Input the
number which have been found and then press
输入
ENTER
to
confirm.
“Search”: When the cursor is here, press
输入
ENTER
and you
can find one such relay which is searched and
needs to be used by the program. Press it again
and you can find the second relay needed by the
program. The same applies to the following.
3.2.30 Ending position of injection
Screen (44) of ending position of injection Ending position of injection 2006/07/20 16:20 0.0mm 1-10 11-20 21-30 31-40 41-50 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm 0.0mm **% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press GRAPH
射胶曲线
, the screen (44) of ending position will appear.
This screen can display the ending position and its average
value of the fifty produced injection.
62
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.31 Speed Curve of Injection
Screen (45) of Speed Curve of InjectionSpeed of Injection 2006/07/20 16:20 100.0mm/s Std. Disp AA 0.9s 4.9mm 11.6mm BB **% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press GRAPH
射胶曲线
twice. The speed curve screen (45) will
63
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
appear.
(2)Press it again and switch the input.
(3)Press
+ON
and
OFF
, and choose ON or OFF.
Press
输入
ENTER
, and the setting can be finished.
3.2.32 Pressure Curve of Injection
Screen (46) of Pressure Curve of Injection Pressure of Injection 2006/07/20 16:20 145bar Std. Disp OFF 0.9s 4.9mm 11.6mm Std. Save **% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press GRAPH
射胶曲线
three times. The screen (46) of injection
64
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
pressure will appear.
(2)Press
输入
ENTER
and computers will work with the machine to
automatically adjust the pressure linearization. Besides, the value
of linearization will be automatically displayed on screen.
3.2.33 Help
Screen (47)of Help
Help 2006/07/20 16:20 AA BB CC
**%**%***bar 59.5mm 6.1mm 11.6mm
Screen (48) of Help
65
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual Help 2006/07/20 16:20 Introduction Option of automatic stop
Selects among four modes
in accordance with the number of forming mold To be selected for produces in batches and breakdown. **%**%***bar 59.5mm 6.1mm 11.6mm
Screen (49) of Help Help 2006/07/20 16:20 Maintenance Cycle Content Daily checking Function of emergency stop knob Check if the emergency stop knob can cut the motor of oil pump off **%**%***bar 59.5mm 6.1mm 11.6mm
Screen (50) of Help
Help 2006/07/20 16:20
Troubleshooting No. Content
AL03: The temperature of the pipe does not reach preset value.
The actual temperature is lower than preset value.
66
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual Narrow the temperature deviation
**% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (51) of Help Help 2006/07/20 16:20 Introduction Filling time Time display in the first to the fourth injection stage **%**%***bar 59.5mm 6.1mm 11.6mm
(1)Press HELP
帮助
, and the Screen (47) of Help will appear.
(2)Press
+ON
and
OFF
and you can choose different
types of help functions.
67
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Functions of Help, maintenance and problem resolution and
parameters are introduced from help screen (48) to (51).
(3)Press , and the main menu AA is switched into
Submenu BB. Press
+ON
and
OFF
to see the
detailed content CC of Help menu.
In which
“AA”: This is the help type. Use
+ON
and
OFF
to
switch help types.
“BB”: This is a submenu of Help.
“CC”: Specific content of Help.
3.2.34Setting for Language Selection and System Time
Screen (52) of Setting for Language Selection and System Time
Help 2006/07/20 16:20 Language Chinese Date AA / BB / CC Time DD : EE Setting **% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press CLEAR
清除
and
主页面
MENU then enter screen (52) of
language selection.
68
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(2)Press
+ON
and
OFF
and switch between
English and Chinese.
(3)Press to set the present date and time. Input
corresponding date and time. Press
输入
ENTER
to finish.
In which
“AA”: This is the setting of year.
“BB”: This is the setting of month.
“CC”: This is the setting of Date.
“DD”: This is the setting of hour.
“EE”: This is the setting of minute.
3.2.35 Selection of Number of Stage of Motion Stroke
Screen (53) of Stage Number Selection 2006/07/20 08:40 Stage Number of mold opening AA Stage Number of mold clamping BB Stage Number of injection CC Stage Number of pressure holding DD Stage Number of plasticizing EE **% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press CLEAR
清除
and
主页面
MENUto enter screen (53) of stage
number selection .
69
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(2)Press and you can choose those needs to be changed.
Input
输入
ENTER
and finish setting.
In which
“AA”: This is the stage number of mold opening.
“BB”: This is the stage number of mold clamping.
“CC”: This is the stage number of injection.
“DD”: This is the stage number of pressure holding.
“DD”: This is the stage number of plasticizing.
3.2.36 Setting for Slope
Screen (54) of Setting for Slope Setting for slope 2006/07/20 16:20 S11 AA PR1 BB BP1 0.10 S21 0.10 S12 0.10 PR2 0.10 BP2 0.10 S22 0.10 S13 0.10 PR3 0.10 BP3 0.10 S23 0.10 S14 0.10 PR4 0.10 BP4 0.10 S24 0.10 S15 0.10 PR5 0.10 BP5 0.10 S25 0.10 **% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press CLEAR
清除
andMOLD/STAT
模号/品管
to enter screen (54) of setting for
slope.
70
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(2)Press and enter the slope. Press
输入
ENTER
to finish
setting.
In which
“S”: The abbreviation for Speed.
“PR”: The abbreviation for Press
“BP”: The abbreviation for Backpress.S11: The speed and slope of mold clamping and low pressure
opening.
S12: The speed and slope of mold opening.
S13: The speed and slope of injection and plasticizing.
S14: The speed and slope of unscrewing.
S15: The speed and slope of the mold clamping force when
adjusted.
PR1: The pressure slope of fast mold clamping.
PR2: The pressure slope of mold opening.
PR3: The pressure slope of injection and plasticizing.
PR4: The pressure slope of loosening and backward motion.
PR5: The pressure slope of mold clamping when the mold
clamping force is adjusted.
3.2.37 Setting for Speed l Output
Screen (55) of Setting for Speed l Output Screen (55) of Setting for Speed l Output 2006/07/20 16:20 0rpm ***bar 0Volt 0 AA% BB 30% 300 60% 600 90% 900 5% 50 35% 350 65% 650 95% 950 10% 100 40% 400 70% 700 99% 1000 15% 150 45% 450 75% 750 0% 0 20% 200 50% 500 80% 800 0% 0 25% 250 55% 550 85% 850 0% 0 **% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press CLEAR
清除
and MOLD/STAT
模号/品管
twice at the same time. The screen (55) of
setting for speed l output will appear.
71
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(2)Press , select speed and enter it. Then press
输入
ENTER
to finish
setting.
In which
“AA”: Speed percentage
“BB”: Analog value of speed output
Note: When the speed percentage becomes higher, the corresponding
analog value of speed output should become larger accordingly. By no
means should the speed become lower. Otherwise, the output speed signal
will be in disorder and the machine will become unstable in consequence.
3.2.38 Pressure Output
Screen (56) of Setting for Pressure Output Setting for Pressure Output 2006/07/20 16:20 0rpm ***bar 0Volt 0 AA% BB 30% 300 60% 600 90% 900 5% 50 35% 350 65% 650 95% 950 10% 100 40% 400 70% 700 99% 1000 15% 150 45% 450 75% 750 0% 0 20% 200 50% 500 80% 800 0% 0 25% 250 55% 550 85% 850 0% 0 **% **% ***bar 59.5mm 6.1mm 11.6mm
72
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(1)Press CLEAR
清除
and MOLD/STAT
模号/品管
three times at the same time. The mage (56)
of setting for press output will appear.
(2)Press , select press and enter corresponding value. Then press
输入
ENTER
to finish setting.
In which
“AA”: Pressure percentage
“BB”: Analog value of t pressure output
Note: When the pressure percentage becomes higher, the corresponding
analog value of pressure output should become higher accordingly. By no
means should the pressure become lower. Otherwise, the output pressure
signal will be in disorder and the machine will become unstable in
consequence.
3.2.39 Setting for Backpressure
Screen (57) of Setting for Backpress Setting for Backpressure Output 2006/07/20 16:20 0rpm ***bar 0Volt 0 AA% BB 30% 300 60% 600 90% 900 5% 50 35% 350 65% 650 95% 950 10% 100 40% 400 70% 700 99% 1000 15% 150 45% 450 75% 750 0% 0 20% 200 50% 500 80% 800 0% 0 25% 250 55% 550 85% 850 0% 0 **% **% ***bar 59.5mm 6.1mm 11.6mm
73
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(1)Press CLEAR
清除
and MOLD/STAT
模号/品管
four times at the same time. The screen
(57) of setting for pressure output will appear.
(2) Press , select press and enter corresponding value.
Then press
输入
ENTER
to finish setting.
In which
“AA”: Backpressure percentage
“BB”: Analog value of output backpress.
Note: When the backpressure percentage becomes higher, the
corresponding analog value of backpressure output should become higher
accordingly. By no means should the backpressure become lower.
Otherwise, the output press signal will be in disorder and the machine will
become unstable in consequence.
3.2.40 Setting for Speed 2 Output
Screen (58) of Setting for Speed 2 Output Setting for Speed 2 Output 2006/07/20 16:20 0rpm ***bar 0Volt 0 AA% BB 0% 0 0% 0 0% 0 99% 1023 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 0% 0 **% **% ***bar 59.5mm 6.1mm 11.6mm
74
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(1)Press CLEAR
清除
and MOLD/STAT
模号/品管
five times at the same time. The
screen (58) of setting for speed 2 output will appear.
(2)Press , select speed and enter corresponding value.
Then press
输入
ENTER
to finish setting.
In which
“AA”: speed percentage
“BB”: Analog value of output speed.
Note: When speed percentage becomes higher, the corresponding analog
value of output speed should become higher accordingly. By no means
should the speed become lower. Otherwise, the output speed signal will be
in disorder and the machine will become unstable in consequence.
3.2.41 Setting for initialization (Setting for decoder initial position)
Screen (59) of Setting for Initialization Setting for initialization 2006/07/20 16:20 Mold thickness AA Mold clamping Force 84ton BBp 168ton CCp 2763p 122p 929p Preset DDp EEmm FF mm Initial position GGp HHmm IImm **% **% ***bar 59.5mm 6.1mm 11.6mm
75
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(1) Press CLEAR
清除
and MOLD/STAT
模号/品管
six times at the same time. The screen
(59) of setting for initialization will appear.
(2)Press , select input and enter corresponding value. Then
press
输入
ENTER
to finish setting.
In which
“AA”: Setting for mold thickness
“BB”: The minimum number of mold clamping position.
“CC”: The maximum number of mold clamping position.
“DD”: The preset number of mold clamping position.
“EE”: The preset number of ejection position.
“FF”: The preset number of injection position.
“GG”: The starting number of mold clamping.
“HH”: The starting number of ejection.
“II”: The starting number of injection.
3.2.42 Setting for Reserved Speed & Pressure
Screen (60) of Setting for Reserved Speed & Press
2006/07/20 16:20 Speed Press OTO12 AA% BB% OTO13 0% 30% OTO14 0% 30% OTO15 0% 30% OTO16 30% 30% OTO17 0% 30% OTO18 0% 30% OTO19 0% 30%
76
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual **%**%***bar 59.5mm 6.1mm 11.6mm
Screen (61) Setting for Speed & Press
2006/07/20 16:20 Speed Press OTO20 0% 30% OTO21 0% 30% OTO22 0% 30% OTO23 0% 30% OTO24 0% 30%
Mold clamping
Force CC% DD% Reserved Mold opening 2 EEp **% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press CLEAR
清除
and MOLD/STAT
模号/品管
seven times at the same time. The
screen (60) of setting for reserved speed & pressure will appear.
Turn to next page and the screen (61) of setting for reserved speed
& pressure will appear.
(2)Press , select output and enter corresponding number.
Then press
输入
ENTER
to finish setting.
In which
“AA”: This is the reserved speed.
“BB”: This is the reserved press.
“CC”: This is the setting for speed of mold clamping force when
77
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
the mold is adjusted automatically.
“DD”: This is the setting for pressure of mold clamping forcewhen the mold is adjusted automatically..
“EE”: This is reserved position setting of mold opening.
OTO12: These are the setting of reset mold clamping, injection,
starting speed of ejectordecoder and press.
OTO16: These are the speed and pressure set of the mold clamping
of special low press.
Others are not utilized.
3.2.43 Setting for Timer
Screen (62) of Setting for Timer
Setting for timer 2006/07/20 16:20
Motor Startup AA Closing ofNozzle KK
Resetting of
Initial position BB Delay of Nitrogen LL
Monitor over
Mold adjustment CC Delay of Low Press MM
Alarm duration DD Delay of motion NN
Alarm Pause EE Monitor over
Safety Door OO
Monitor over
motion FF Special Low Press PP
Reserved GG Backpressure of
Mold opening QQ
Reserved HH Opening of Nozzle RR
Interval of ejection II Buffering of Injection SS
Anti-cold startup JJ Buffering of Plasticizing TT
78
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press CLEAR
清除
and MOLD/STAT
模号/品管
eight times at the same time. The
mage (62) of setting for timer will appear.
(2)Press , select output and enter corresponding number.
Then press
输入
ENTER
to finish setting.
In which
“AA”: Motor Y – startup time
“BB”: Reset time of decoder initial position.
“CC”: Checking time of mold adjustment sensor
“DD”: Alarm duration
“EE”: Alarm pause
“FF”: Time of monitor over motion
“GG”: Reserved
“HH”: Reserved
“II”: Interval between ejection and retraction.
“JJ”: Time of prevention against cold startup.
“KK”: Closing time of nozzle (use for oil pressure nozzle)
“LL”: Delay of nitrogen injection
“MM”: Delay of mold clamping of low pressure .
“NN”: Buffering delay of all motions
“OO”: Time of monitor over the motion of safety door
“PP”: Time of special low pressure of mold clamping.
“QQ”: Backpressure duration of mold opening
“RR”: Opening time of injection nozzle (for oil pressure nozzle)
“SS”: Buffering time of injection
“TT”: Buffering time of plasticizing.
79
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.44 Setting 2 for Counter
Screen (63) of Setting for Counter
Setting for Counter 2006/07/20 16:20
Quantity of
forming mold AA Pressing mold with
mold adjustment force KK
Quantity of
reject BB Reserved 11 LL
Time of reject CC Times of core-in C MM
Purge DD Times of core clamped out C NN
Amount of ejector EE Reserved 14 OO
Vibration of ejector FF Reserved 15 OO
Period of lubrication GG Reserved 16 OO
Reserved 07 HH Reserved 17 OO
Monitor over cycle II Reserved 18 OO Clamping mold with JJ Reserved 14 OO
80
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual mold adjustment force
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press CLEAR
清除
and MOLD/STAT
模号/品管
nine times at the same time. The
screen (63) of setting for counter will appear.
(2)Press , select output and enter corresponding number.
Then press
输入
ENTER
to finish setting.
In which
“AA”: This is the quantity of the forming mold.
“BB”: This is the quantity of the reject.
“CC”: This is the secondary product time.
“DD”: This is the time of purge.
“EE”: This is the amount of ejection.
“FF”: This is the times of vibration of ejector.
“GG”: This is the lubrication period.
“HH”: This is the reserved 07.
“II”: This is the monitor over cycle.
“JJ”: This is the times of clamping mold with mold adjustmentforce.
“KK”: This is the times of pressing mold with mold adjustmentforce.
“LL”: This is the reserved ll.
“MM”: This is the times of core-in C .
“NN”: This is the times of core-out C .
“OO”: Reserved.
81
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.45 Factory Setting
Screen (64) of Factory Setting Factory Setting 2006/07/20 16:20 Machine model : AA Machine number : BB Ex-factory date : CC
82
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual **% **% ***bar 59.5mm 6.1mm 11.6mm
Screen (65) of Factory Setting Factory Setting 2006/07/20 16:20 Maximum injecting speed DD Startup delay EE Adjustment delay for dead loop in each stage FF Time period of adjustment of dead loop GG **% **% ***bar 59.5mm 6.1mm 11.6mm
(1)Press CLEAR
清除
and MOLD/STAT
模号/品管
ten times at the same time. The screen
(63) of factory setting will appear. Turn to next page and the screen
(65) will appear.
(2)Press , select output and enter corresponding number.
Then press
输入
ENTER
to finish setting.
In which
“AA”: This is the setting for machine model .
83
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“BB”: This is the setting for machine number .
“CC”: This is the setting for ex-factory date .
“DD”: This is the maximum injecting speed.
“EE”: This is the setting for startup delay .
“FF”: This is the setting for adjustment delay for dead loop ineach stage.
“GG”: This is the setting for time period of adjustment of deadloop.
3.2.46 Display of alarm history
Screen (66) of Display of Alarm History Alarm 2006/07/20 16:20 AA BB CC DD 2006/06/14 10:02 AL45: Malfunction of threshold switch 2006/06/14 10:12 AL06: Overloading of oil pump 2006/06/14 10:12 AL45: Malfunction of threshold switch 2006/06/14 10:27 AL06: Overloading of oil pump 2006/06/14 10:27 AL45: Malfunction of threshold switch 2006/06/14 14:47 AL06: Overloading of oil pump 2006/06/14 14:47 AL45: Malfunction of threshold switch 2006/06/14 14:52 AL06: Overloading of oil pump
84
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual 2006/06/14 14:52 AL45: Malfunction of threshold switch **% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press CLEAR
清除
and
监视
MONITOR once. The screen (66) of alarm
history alarming will appear.
(2)Press again to switch the displayed content.
In which
“AA”: Date.
“BB”: Time.
“CC”: Alarm number.
“DD”: Alarm content.
3.2.47 Network
Screen (67) of Network
Network 2006/07/20 16:20 ******** 0 AA Employee name Mold number transmitted BB Mold number searched CC Job Card
85
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual Mold number received **% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press CLEAR
清除
and GRAPH
射胶曲线
once. The screen (67) of network will
appear. (The network function is only available for those who purchased
iCHEN network system produced by this company.
(2) Press to switch to option need setting.
(3) Input value and press
输入
ENTER
to finish setting,
in which
In which
“AA”: press
+ON
and
OFF
the select the following
modes.
(1)Adjustment
(2)Halt
(3) Cycle
(4) Waiting for mold
(5)Waiting for plastic
(6)Plastic Changing
(7)Mold Changing
(8)Mold Trial
(9)Mold Repair
(10)Coloring
(11)Production
(12)No single
(13)Other 3.
“BB”: Mold number transmission
“CC”: Mold number search
86
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.2.48 Modification of Password
Screen (68) of Modification of Password 2006/07/20 16:20
Old Password ******
New Password ******
Confirm ****** Setting
87
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual **% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press CLEAR
清除
and HELP
帮助
keys together and hold them for more than
5 seconds and the screen (68) of modification of password will
appear(This password is for the authorized access to the network
system).
(2) Then press key to move to the option desired.
(3) Input value and press key to confirm and finish.
In which
“AA”: Old password
“BB”: New password
“CC”: Confirm new password
“DD”: Confirm modification
3.2.49 Setting for manual lubrication
Screen (69) of Setting for Lubrication Setting for Lubrication 2006/07/20 16:20
Lubrication
period AAt BBt
Lubrication
time CCs Lubrication DDs
88
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manualalarm
**% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press LUB
手动润滑
key and the screen (69) of setting for lubrication
will appear.
(2) Press key to selection options for lubrication
parameters. Input value and press key to
输入
ENTER
finish.
In which
“AA”: Setting for lubrication period
“BB”: Display of lubrication period
“CC”: Setting for lubrication time
“DD”: Setting for time of lubrication alarm
3.2.49 Setting for mold adjustment
Screen (70) of Setting for Mold adjustment Mold thickness & Mold clamping force 2006/07/20 16:20
Automatic adjustment of
Mold clamping force AA BB Actual thickness of mold CC mm Mold thickness DD mm
89
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual Mold clamping force EE ton FF p **% **% ***bar 59.5mm 6.1mm 11.6mm
(1) Press MOLD ADJ.
调模
key and the screen (70) of mold thickness and
mold clamping force will appear.
(2) Press key to switch to the item needing modifying,
press numerical keys and then press
输入
ENTER
key to finish.
(3) Manual adjustment of mold thickness:
Press
调模前进
MOLD FWD key, then the mold will move forward and the mold
thickness will be reduced, press MOLD BWD
调模后退
key , then the mold will
move backward and the mold thickness will increase, to stop, just
press the MOLD ADJ.
调模
key again.
In which
“ AA”: Option of automatic adjustment of mold clamping
force, press
+ON
and
OFF
keys to set
this function on or off.
90
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
“ BB”: Switch between automatic and manual mold
adjustment, press
+ON
and
OFF
keys to
select.
“CC”: Display of actual mold thickness
“DD”: Display of present mold thickness
“EE”: Setting for tonnage of mold clamping force
3.2.50 Mechanical Adjustment
Screen (71) of Mechanical Adjustment
Mechanical adjustment 2006/07/20 16:20
91
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Deceleration AA% **%**%***bar 59.5mm 6.1mm 11.6mm
(1) Press SLOW
慢速调试
key and the screen (70) of mechanical adjustment
will appear.
(2) Press key to switch to AA, input value and press
输入
ENTER
key again to confirm and finish.
In which
“AA”: Setting for deceleration percentage for all the motions
3.2.52 Maintenance Reminder
Screen (72) of Setting for Maintenance Reminder Maintenance Reminder
2006/08/20 17:21
Maintenance Content
Date
1 Set cooling water running and check for
Lubrication. AA BB
2 Make sure the safety door is closed and
Limit switch is applied 2006/08/21 0
3 Lubricant shortage in the tank 2006/08/22 0
4 Lubricant leakage 2006/08/23 0
92
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
5 Check oil pressure and temperature 2006/08/24 0
6 Lubricate all moving part needing
lubricating 2006/08/25 0
7 Check oilway of the machine for leakage 2006/08/26 0
8 Check each switches and connects 2006/08/27 0
9 Clean the cooling machine 2006/08/28 0
**% **% ***bar 0.1mm 3.0mm 3.1mm
Screen (73) of Setting for Maintenance Reminder
Maintenance Reminder 2006/08/20 17:21
Maintenance content
Date
10 Check oil quality AA BB
11 Grease bush 2006/08/21 0
12 Change hydraulic oil regularly 2006/08/22 0
13
Check wires for hardening and aging 2006/08/23 0
14
Check for alignment of nozzle center
with top plate center 2006/08/24 0
15
Check secondary mold clamping
plate
and bottom plate 2006/08/25 0
16 2006/08/26 0
17 2006/08/27 0
18 2006/08/28 0
**% **% ***bar 0.1mm 3.0mm 3.1mm
(1) Press CLEAR
清除
and MOLD/STAT
模号/品管
keys for 14 times and the page (72) of
maintenance reminder will appear, press CLEAR
清除
and MOLD/STAT
模号/品管
keys
for 15 times, page (72) of maintenance reminder will appear, or, press
93
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
CLEAR
清除
and keys together to switch between page (72)
and (72)
(3) Press key to move the cursor to the Date, and press
输入
ENTER
key, then a ? will appear next to the Date, then press
CONFRM
确认
key to initialize the Date as current system date to set the
latter as the start of maintenance reminding.
3.2.53 Retting Initial position
After reboot of the computer as a result of computer powerfailure when
the machine is in operation, there will be alarm displayed on the screen
to remind the operator to reset the initial position.
Before resetting staring point, please check the following set value:
(i)Setting for speed and pressure of the initial positionSpeed=50% Press=99%
(ii) Reset timer at initial position: TIM20= 4 seconds
(iii) In screen (61) of setting for initialization
Preset mold clamping Position DD=1P
94
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Preset ejection Position EE=0.5 mm
Preset injection Position=0.5 mm
(1) For mold clamping If the computer power is cut off when opening or clamping mold, then
the alarm of “Reset Staring Point Please Press Mold clamping Key
Until the Alarm Disappears” will be displayed on the screen after
reboot, following is the method to reset the initial position:
Press CLOSE
锁模
key, after 4 seconds runs out as how the timer TIM 20 is
set, the actual position where the hinge is straightened to clamp mold
will change into 1p, the value DD preset as mold clamping position, by
which time the alarm will go off, denote the resetting is done.
In case there is product in the mold, do eject the product out first,
following is the operation:
(i) Open mold until the mold clamping plate stops moving, in theoption of mold clamping presetting in the screen (61) of setting for
initialization, set 9999P as DD , this value must be larger than the preset
value in the option of decelerating mold opening (termination). Then
move the cursor back to the option of mold clamping presetting and press
输入
ENTERkey, a ? will appear on the screen, then press
CONFRM
确认
key, the
actual position of mold clamping will automatically change into 9999p
preset as mold clamping. Thus the alarm will vanish.
(i) Press OPEN
开模
key until the signal of Termination of Mold opening
is displayed on the screen.
(ii) Press EJECT FWD
顶针
key to eject product out.
(iii) Move the cursor back to the DD option of mold clamping and
change 9999P to 1p.
(2) For ejectionIf the computer power is cut off before and after the ejection, after
the reboot, appear on the screen will be the alarm of “Reset Initial
position Please Press Ejection Key Until the Alarm Disappears”
Resetting initial position of ejection:
95
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Press
退针
EJECT BWD
key, after 4 seconds runs out as how the timer TIM
20 is set, the ejector will retract to full extent, then the alarm will
vanish, mean while, the actual ejection position will automatically
change into 0.5mm, the preset position of ejection, thus the
resetting is done.
In the event the ejector does not retract to full extent, repeat the
above procedures until it’s correctly done.
(3) For InjectionIf the computer power is cut off in the process of injection and
plasticizing, after the reboot, appear on the screen will be the alarm
of Reset Initial position Please Press Injection Key Until the Alarm
Disappears.
Resetting initial position of injection
Press INJ
射胶
key, after 4 seconds runs out as how the timer TIM
20 is set, the ejector will move to full extent, then the alarm will
vanish, mean while, the actual injection position will automatically
change into 0.5mm, the preset position of ejection, thus the
resetting is done.
In the event the ejection does not move to full extent after the
TIM20 runs out, repeat the above procedures until it’s correctly
done.
3.2.54 Setting for Original Position of Decoder
(1) In the screen (61) of setting for initialization, there offers the options for
mold clamping presetting and initial position, injection presetting and
initial position, and ejection presetting and initial position.
(i) By presetting, the present value of the position of the decoder could bemodified and the position of initial position could be manually adjusted.
(ii) By setting start point, the position of the decoder could be reset.
(2) Presetting (modify the actual position of the decoder)(mold clamping)
Move the cursor to DD option of the mold clamping presetting, input the
96
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
desired position value, press Enter, then move the cursor back to the mold
clamping presetting, press Enter again, then the ? will appear on the screen,
press Enter yet again to finish. Now the present position of mold clamping
is the preset one(this presetting procedure is applicable both to injection
and ejection.)
Presetting- Manual adjustment of the position of initial position
In the event that the initial position changes when then machine
is in operation, it's feasible to relocate the initial position by
manual adjustment.
(3) Manual adjustment of the position of initial position of mold clamping
Before adjusting, please check the following set value:
(i) Set values of speed and pressure of initial position (in screen (61) ofinitialization), Speed=50%, Press=99%
(ii) Resetting time of initial position, TIM20=4 sec (iii) Check the preset position DD=1P Notice: (i) Make sure there is not product in the mold, if there is, take
the product out.
(ii) The mold is equipped with core-pulling and -rotary devices.
So please check the position stroke to make sure that the
mentioned devices are mounted in the safe and correct
position so as to avoid any damage.
Method: Press key and the hinge will move, after the preset 4 seconds runs
out as how the TIM20 is set, the hinge will fully straighten, then the
actual position of mold clamping will automatically change to the
1p, the preset position of mold clamping, thus the manual setting of
initial position of mold clamping is done.
If the hinge does not fully straighten after the TIM20 runs out, please
repeat the above procedures.
(4) Manual adjustment of the position of initial position of injection
Notice:Make sure the temperature of plasticizing barrel does reach the set
value.
Preset position of injection GG=0.5mm
Press INJ
射胶
key, the injection will be carried out to full extent, then the
actual position of injection will automatically change to 0.5mm, the preset
position, thus the manual adjustment of initial position of injection is done.
(5) Manual adjustment of the position of initial position of ejectionNotice: Make sure the mold reaches the ending position while being clamped.
97
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
Preset FF of ejection=0.55mm, and press
退针
EJECT BWD
key to retract the ejector to
full extent, then the actual position of ejection will automatically change to
0.1mm, the preset position. By setting the initial position, the position of the
decoder is automatically reset. Please be noted that the position of initial
position refers where the sensor is reset to as benchmark to reset the initial
position.
(6) Setting the position of initial position of mold clampingThe position of initial position of mold clamping refers where resetting
sensor is reset to. In the process of mold opening, when the resetting sensor
is triggered, the position of start point of mold clamping is automatically
reset.
(i) By adjusting the thickness of mold, the molds respectively on the
primary plate and secondary plate will not conflict after the hinge
fully straightens. If there is no mold on the plate, skip this procedure.
(ii) In the screen (61) of setting for initialization, input a large
value(i.e.2000p) in the HHP, the position of initial position of mold
clamping.
(iii)Change the value into 0p in the option of the position of high-pressure mold clamping in the screen (06) of mold clamping.
(iv) In manual state, clamp and open mold for 3 times. When clamping it,
make sure the hinge fully straightens, and when opening it, make sure
the resetting sensor is triggered.
(v) After clamping mold for 3 times and when the hinge fully straightens,
record the actual position of mold clamping (i.e. 1250p)
(vi) New position of initial position of mold clamping(where the resetting
sensor is triggered) HH=2000p-1250p=750p
(vii)Input new value 750p in the GG option.
(viii)Again, open and clamp mold for 3 times, if every time the actualending position of mold clamping is a one-digit number, then the
setting is done, otherwise repeat the procedure (v)-(viii).
(ix) Input 100p in the option of position of high-pressure mold clamping in
the screen (06) of mold clamping.
(7)Setting the position of initial position of injectionThe position of initial position of injection refers to where the resetting
sensor of injection is. In the process of plasticizing, when the resetting
sensor is triggered, the starting port of injection position will be
automatically reset.
Notice: Make sure the temperature of the plasticizing barrel does reach the
set value.
98
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(i)In the screen (61) of setting for initialization, input a large value (i.e.100mm) in the IIp, position of initial position of injection. Make sure
this value is smaller than that of the plasticizing position.
(ii)In manual state, conduct injection and plasticization for 3 times. Everytime after injection, make sure not to conduct plasticization until full
stroke. When plasticizing, the resetting sensor will be triggered.
(iii) After 3 times of injection and the injection stroke is carried out to fullextent, record the actual position of injection.
(iv) The new position of initial position of inject (where the resettingsensor is triggered) II=100mm-68mm=32mm.
(v) Input new value 32mm into the II option of the position of initialposition of injection.
(vi) Again conduct injection and plasticization for 3 times, if the positionwhere the actual stroke of inject is less than 0.5mm every time, then
the setting is done, otherwise repeat the above procedures (iii)-(vi).
(8) Setting the position of initial position of ejection
The position of initial position of ejection refers where the resetting sensor
of ejection is. After ejection, the resetting sensor is triggered to reset the
initial position.
Notice: Make sure the position of mold opening does reach the ending
position.
(i)In the screen (61) of setting for original position, input a large value(i.e. 15mm) in the IIp option of the position of initial position of
ejection.
(ii)In manual state, move ejector back and forth for 3 times respectively,
make sure that the ejector retracts to full extent and the resetting sensor
of ejection is triggered.
(iii)After 3 times of moving back and forth and retraction terminates,record the actual position(i.e. 8.5mm) of the ejector.
(iv)The new position of initial position of ejection (where the resettingsensor is triggered )II=15mm-8.5mm=6.5mm.
(iv)Input new value 6.5mm in the II option of the position of initialposition of injection.
(vii) Again move the ejector back and forth for about 3 times, if each time
the position where the retraction stroke terminates is less than 1mm,
then the setting is done, otherwise, repeat the above procedures (iii)-
(vi).
Notice: The values in this screen is based on test.
99
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.3 Alarm and Response
3.3.1 Description of AlarmNo. Subtitle Description
AL000 Alarm 1 Not used
AL001 Alarm Not used
AL002 The temperature of
material pipe is lower than
the set value
The actual temperature of material pipe is lower
than its set value plus low temperature deviation
AL003 Lubricant shortage Oil level of lubricant tank is too low
AL004 Drainage valve of
lubricator clogs
Not used
100
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manualAL005 Leakage or shortage of
lubricant
Lubricant pipe leaks or lubricating pressure falls short
AL006 Motor of oil bump
overloads
Check the overload relay of the motor of oil pump
AL007 Motor of mold adjustment
overloads
Check the overload relay of the motor of mold
adjustment
AL008 Rear safety door is left
open
Close the rear safety door and check its limit switch.
AL009 Front safety door is left
open
Close the front safety door and check its limit
switch
AL010 Mold adjustment is
beyond the minimum.
The mold thickness is beyond the minimum or
check the limit switch of front adjustment limit
AL011 Mold adjustment is
beyond the maximum.
The mold thickness is beyond the maximum or
check the limit switch of front adjustment limit.
AL019 Please check the limit of
nozzle advance
The front limit switch of nozzle is not triggered
during the automatic operation.
AL020 The nozzle protective
cover is left open
The nozzle protective cover is not closed in the
process of injection.
AL021 Injection nozzle is clogged The injection stroke is not carried out to full extent
of 2nd stage of injection or the nozzle is clogged or
when the nozzle alarm is in operation. Check the
setting of injection position or the injection nozzle.
AL022 Plastic shortage or mold
flash
The injection stroke was carried out beyond the
mold flash position when the plastic leakage is in
operation. Adjust the position of mold flash or of
plasticizing termination.
AL023 Material shortage or clog
of the bucket
The plasticizing motion takes longer time than the
set cooling value when the machine is in automatic
operation. Check the bucket against clog or if the
set value of plasticizing is too long
No. Subtitle Description
AL024 Quantity of forming mold has
reached the set value
In the manual state, the quantity of forming mold has reached the
set value of the preset production.
AL025 Long cycle The production cycle is longer than the alarm cycle. Check if the
set value of alarm cycle is too short.
AL026 Please clean the foreign
substances out of the mold
There are foreign substances in the mold or the high-pressure
position and low-pressure time are incorrectly set. Check the
mold or the their set values.
AL027 Please check if the manipulator is
taking out the right article
The manipulator fails to take out the product.
101
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
AL028 Abnormal signal
of confirmation of product
The enabled electronic eye does detect any product
AL029 Sensor piece of electronic eyes is
blocked
When the electronic eye is in operation, its eye is block but the
injection terminates please clean the finished products or foreign
substances off the plate.
AL030 Temperature of cycle oil is too low The actual temperature of hydraulic oil is lower than the set
value(-low temperature deviation)
AL031 Temperature of cycle oil is too
high
The actual temperature of hydraulic oil is higher than the set
value(+high temperature deviation)
AL032 Please check the limit switch of
core pulling
The motion of core pulling takes longer time than the set value
of limit alarm when the machine is in automatic operation.
Check the stroke of core pulling or the time of limit alarm
AL033 Please check the limit switch of
ejection
The motion of ejection takes longer time than the set value of
limit alarm when the machine is in automatic operation. Check
the stroke of ejection or the time of limit alarm.
AL034 Manipulator is out of order The manipulator does not move to full extent when clamping or
opening mold. Please check the manipulator
AL035 Abnormal pressure filling of the
accumulator
Pressure accumulation takes longer time than that of the cooling
time when the nitrogen injection function is used. Please check
the switch of accumulation pressure.
AL036 The switch of counter of mold
adjustment is out of order
The sensor of mold adjustment detects malfunction when the
mold is being adjusted. Please check the sensor of mold
adjustment.
AL037 Low pressure for the manipulator Not used
AL039 Check the switch of thread counter The threading motion takes longer time than the alarm time set
for it, please check the thread limit switch or the thread counter.
AL040 Reserved Not used
AL041 Automatically adjusting mold
clamping force
This subtitle is displayed when the mold clamping force is being
automatically adjusted.
AL042 Automatic adjustment of mold
clamping force is done
This subtitle is displayed when the automatic adjustment of mold
clamping force is done.
No. Subtitle Description
AL043 The actual temperature of the
material pipe is too highThe actual temperature of the material pipe is higher than the set
value (+high temperature deviation)
AL045 Limit of safety door is out of order The limit of safety does not give off signal in the set time
AL046 Failure of termination of mold
opening
The mold opening takes longer time than the set value when the
machine is in automatic operation
AL048 Oil filter screen clogs The filter screen clogs when the high pressure oil filter is in use.
AL049 Alarm 3 Alarm
AL050 The motor of oil pump is not
actuated.
Not used
AL051 Mold adjusting time is too long Not used
AL052 Lubricating This subtitle is displayed when the lubricant is being output.
102
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
AL053 Cut the power off and restart the machine Not used
AL055 Automatically changing mold Not used
AL056 A half-nut is out of position Not used
AL057 Please check the limit switch of the
rotational dist
Not used
AL058 Abnormal pressure release of mold
clamping
Not used
AL059 Stroke of large oil tank is out of
scope
Not used
AL060 Mold clamping force is under
stress
Not used
AL061 Shortage of hydraulic oil Not used
AL062 Check mold clamping gear for
abnormality
Not used
AL063 Check the mold mounting position Not used
AL064 Check the hydraulic mold
clamping for abnormality
Not used
AL065 Check the mold closing force for
abnormality
Not used
AL066 The actual temperature of the
material pipe is too high
Not used
AL067 The function of mold adjustment is
being actuated
Not used
AL068 Reserved Not used
AL069 Reserved Not used
AL070 Reserved Not used
AL071 Reserved Not used
AL072 Reserved Not used
AL073 Reserved Not used
AL074 Reserved Not used
AL075 Reserved Not used
No. Subtitle Description
AL076 Reserved Not used
AL077 Reserved Not used
AL078 Reserved Not used
AL079 Reserved Not used
AL080 Reserved Not used
AL081 Reserved Not used
AL082 Reserved Not used
AL083 Reserved Not used
103
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
AL086 The ejector plate does not
retract
When the mold is being clamping, no signal of
retraction f ejector plate is detected
MG01 The stroke of mold
clamping has terminated
This subtitle is displayed as the motion of mold
clamping is finished when the machine is in manual
operation
MG02 The stroke of mold
opening has terminated
This subtitle is displayed as the motion of mold
opening is finished when the machine is in manual
operation
MG03 The stroke of mold
opening has terminated
This subtitle is displayed as the stroke of mold
opening terminates when the mold is being
manually adjusted or the ejection is being carried
out.
MG04 The stroke of ejection has
terminated
This subtitle is displayed as the ejection is finished
when the machine is in manual operation
MG05
The stroke of retraction of
ejector has terminated
This subtitle is displayed as the retraction of ejector
is finished when the machine is in manual operation
MG06 The stroke of plasticizing
has terminated
This subtitle is displayed as the motion of
plasticizing is finished when the machine is in
manual operation
MG07 The stroke of unscrewing
has terminated
This subtitle is displayed as the unscrewing is
finished when the machine is in manual operation
MG11 The material pipe is being
preheated
Function of temperature holding for the material
pipe is being enabled
MG12 Plasticizing in delay After the injection termination, the plasticizing
would not start until the delay is over
104
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.4 Instruction for forming operation3.4.1 Setting for temperature control
When the machine is powered on and the temperature is displayed, refer
to the screen of (03)
◢The sign of on appearing on the screen mean that the electrothermal
laminates are being heated and the indicator of temperature control key
will light up.
(1)Setting for temperatures of each stage
For the setting for temperature of 1st stage, press
主页面
MENUkey, and the
reverse cursor will appear on the temperature setting option T1 on the
screen, then input the desired number, proceed to press
输入
ENTERkey
to enter the value into the computer. By now the cursor will jump the
set value of the next stage, to stop setting temperature, press any other
functional key to clear the cursor.
For the setting for temperature of 2nd stage, all the procedures are
identical to those of the 1st stage with the exception of
pressing key.
For the setting for temperature of 3rd stage, all the procedures are
identical to those of the 1st stage with the exception of
pressing key.
For the setting for temperature of 4th stage, all the procedures are
identical to those of the 1st stage with the exception of
pressing key.
For the setting for temperature of 5th stage, all the procedures are
identical to those of the 1st stage with the exception of
pressing key.
105
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
For the setting for temperature of 6th stage, all the procedures are
identical to those of the 1st stage with the exception of
pressing key.
For the temperature setting for stage 5th and 6th, it’s only
conditionally available, depending on the model of the machine or
the request from the customers. If the machine is equipped with the
oil temperature controller, the standard set value to control the oil
℃ ℃temperature is usually 35 -40 , when TC7 is output, it’s by means
of a relay to directly control the switch of spill-way gate to make the
oil temperature acceptable. Normally the set value of positive
deviation from high temperature of 6th ℃ stage is 15 while that of the
℃negative deviation from the lower one is 30 , namely, if the set
℃ ℃value of standard oil temperature is 35 , the tolerance is from 5 -
℃50 , out of which range the alarm will go off.
(2) Setting for temperature holding stage of the injection nozzle The temperature holding stage, whose set value ranges from
00%~99%, controls constant temperature according to the injection
nozzle of the material pipe. If 99% is set, it offers all-time heating
of 10~30 sec to set internal constant temperature. Take 20 sec for
instance, it means the constant temperature control period is based
on the cycle of 20 seconds.
i.e.: 60% is set for the temperature holding stage for the nozzle
while 20 seconds for the time of constant temperature.
Namely 20x605=12 sec The electrothermal heating of the
temperature holding stage of the injection nozzle is on
20-12=8 The electrothermal heating is off
(3) Set the value as 0 to give up the temperature control over a stage.
3.4.2 Setting for temperature deviation (alarm)
There are set values for higher and lower temperature for the deviation
alarm, please refer to the screen (20) for details. If the set value of
deviation is exceed, the alarm of The Temperature Is Too High/Low will
appear on the screen
℃Set value of deviation of higher temperature ranges from +20 ~℃+90
℃Set value of deviation of lower temperature ranges from -20 ~ ℃-90
106
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.4.2 Setting for the function of temperature holding
Please refer to screen (20) for the setting for the function of temperature
holding
Temperature holding by definition is to hold the temperatures of each
stage at the set percentage.
℃i.e.: The set percentage is 20% while the set temperature is 250 ,
℃ ℃then, 250 x (100% - 20%) = 200
℃Now when the set temperature drops down to 200 , the temperature will
be held under control.
3.4.4 Fully automatic, semi-automatic, manual options
(1) Press MAN
手动
key for manual operation. The compute is powered
on and automatically enters into manual state, saving the effort to press
this key. Press this key to return to manual state or reset screen after some
other operations.
(2) Press SEMI
半自动
key for semi-automatic operation. At this moment,
confirm the next cycle by every time the front safety door closes. Please
be noted that when the rear safety opens, the power of oil pump will be
automatically cut off.
(3) Press key for fully automatic operation. The operator may preset
options and then confirm the next cycle by recycle time, electronic eye
induction or manipulator return.
* Only one state can be selected by any of these three keys, formingcondition must have been set as well as each motion within the cycle, do
not select before the selection. If a LED on any of these three keys are
blinking, signifying the data of the computer is clamped and could not be
modified. For employment of data clamping, please turn to the appointed
person responsible for data modification.
3.4.5 Setting for data on position, speed and pressure
(1) Press screen control key to select the key of desired motion. Whenpressing the key of desired motion, there appear on the screen will be
the desired screen for setting for modification.
107
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
(2) For setting for data on position there are two methods: opticaldecoder parameter (p) and stroke set value (mm). the compute will, if
the later is employed, automatically convert it into the value of the
optical parameter.
(3) When the screen of the desired motion is held stay on the screen butthe operator intends no further modification or setting, press, press
any one of the MAN
手动
or SEMI
半自动
or AUTO
全自动
keys, the screen will
return to the screen of normal operation. In the SEMI-AUTOMATIC
and FULLY-AUTOMATIC states, the screen will automatically turn
to the screen of normal operation if no key is pressed within 30
seconds.
3.4.6 Setting for numeral data on forming conditions
When setting forming conditions, it’s required to input data on times ofposition stroke of the optical decoder, speed, pressure, timer, counter and
etc. For number input, press cursor key to move to the desired position to
input data. For incorrect input, there appear on the screen will be a alarm
and a prompt for data range, to make next modification, please press
CLEAR
清除
key.
3.4.7 Adjustment of proportional numerical control
The advanced proportional adjustment approach is employed to
control the pressure and speed of the mechanical motion, the percentage
system greatly facilitates the recording and future readjustment.
The computer outputs corresponding current according todifferent motion to control the proportional pressure valve and flow valve
in the oil way so as to numerically control the speed and control.
If the pressure is within the range from 20Kg/cm2 to 145-
175Kg/cm2, , then the range of set value for the working current
corresponding to the proportional pressure value is from 200mA to
800mA
The range of set value for the working current of the proportional
flow valve (speed valve ) is from 200mA to 680mA.
(1) Dead loop controlTo employ the program of dead loop control, it's required to mount
sensor to pick up system pressure and proximity switch to detect
rotate speed of screw. In this mode, the computer will automatically
make adjustment and record linearization parameter.
108
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
For details, please make linearization adjustment to the speed and
pressure according to the screens (45) and (46), only after which
procedure will the computer proceeds to next step.
(2) Open loop control
Normally the computer in under the open loop control, in this case,
the proportional numerical control could be adjusted manually
only.
For details, please make linearization adjustment to the pressureand speed according to the screens of (45) and (46) . On the I/O
electronic plate of the computer, the adjustable PRG is to adjust the
maximum output 99% of the pressure, while the PR0F zero output 0%,
by analogy, the SPIG maximum output 99% of the speed while the
SPI0G zero output 0%.
109
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.4.8 Instructions for the internal counter of the computer
No. Function Description
CT000 Counter cycle Setting for quantity of forming
mould
CT001 Quantity of reject
mould
Setting for quantity of reject
mold
CT002 Counter of production
time
Total time required by
production, with 0.1 hr as a unit
CT003 Reserved
CT004 Times of vibration of
ejector
Times of vibration of ejection
pin, setting for the times of
vibration after ejection
CT005 Times of ejection Setting for times of ejection
CT006 Mold number of
lubricant output
Setting for mold number interval
between automatic lubrication
CT007 Reserved
CT008 Reserved
CT009 Counter of retraction
of mold
For the purpose of the function of
automatic adjustment of mold
clamping force
CT010 Counter of advance
of mold
For the purpose of the function of
automatic adjustment of mold
clamping force
CT011 Reserved
CT012 Reserved
CT013 Reserved
CT014 Reserved
CT015 Reserved
3.4.9 Instructions for internal timer of the computer
110
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manualNo. Function Description
TM000 Reserved for system Display of cycle time
TM001 Reserved for system Display of time of mold clamping
TM002 Reserved for system Display of time of advance of injector unit
TM003 Reserved for system Display of filling time
TM004 Reserved for system Display of time of pressure holding
TM005 Plasticizing delay after
injection termination
Plasticizing delay after injection termination in
the semi/fully automatic operation state
TM006 Cooling time A period between injection termination and
mold opening in the automatic state
TM007 Reserved for system Display of unscrewing before plasticizing
TM008 Reserved for system Display of plasticizing time
TM009 Reserved for system Display of unscrewing after plasticizing
TM010 Reserved for system Display of time of retraction of injector unit
TM011 Reserved for system Display of time of mold opening
TM012 Reserved for system Display of time of ejection
TM013 Interim cycle time A interval between the ejection completion and
mold clamping of the next cycle in the fully
automatic state.
TM014 Injection time Total time of injection, exclusive of that of
pressure holding
TM015 Time for pressure holding
of 1st stage
Time of motion of pressure holding for
injection of 1st stage
TM016 Time for pressure holding
of 2nd stage
Time of motion of pressure holding for
injection of 2nd stage
TM017 Time for pressure holding
of 3rd stage
Time of motion of pressure holding for
injection of 3rd stage
TM018 Time for pressure holding
of 4th stage
Time of motion of pressure holding for
injection of 4th stage
TM019 Time for pressure holding
of 5th stage
Time of motion of pressure holding for
injection of 5th stage
TM020 Time of purge and
plasticizing
Setting for plasticizing under the condition of
automatic purge
TM021
Ejection pause
A pause preceded by automatic ejection but
prior to retraction of ejector
TM022
Time of core-in A
Time of core-in A
TM023 Time of core pulling A Time of core pulling A
TM024 Time of core-in B Time of core-in
TM025 Time of core pulling Time of core pulling
TM026 Time of core-in C Time of core-in C
TM027 Time of core pulling C Time of core pulling C
TM028 Time of core-in D Reserved
No. Function Description
TM029 Time of core pulling D Reserved
111
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manualTM030 Time of lubrication Time of lubrication output, recommended to be
over 10 seconds
TM031 Time of lubrication alarm Reserved
TM032 Fast advance of injector
unit
Duration of fast advance of injector unit
TM033 Time of retraction of
injector unit
Time of retraction of injector unit in the
semi/fully automatic operation, if not retraction
is needed, just set this time as 0
TM034 Reserved Reserved
TM035 Time of monitor over
cycle
Allowable maximum cycle, beyond which the
alarm will go off
TM036 Delay of termination of
mold opening
An interval between the termination of mold
opening and next motion
TM037 Time of monitor over
low-pressure mold
clamping
Maximum allowable interval between the
position of low pressure and that of high one of
mold clamping
TM038 Reserved Reserved
TM039 Reserved Reserved
TM040
Injection delay
An interval between termination of mold
clamping and next motion
TM041 Time of vibration of
ejector
Control the retraction position in the vibration
of ejector
TM042 Delay of retraction of
injector unit
A delay after unscrewing but before retraction
of injector unit
TM043 Reserved Reserved
TM044 Reserved Reserved
TM045 Reserved Reserved
TM046 Reserved Reserved
TM047 Mold adjustment buffer A buffering period between mold forward
adjustment and backward one (recommend to be
over 0.3 sec)
TM048 Buffer of mold opening
and clamping
A buffering period between mold opening and
clamping (recommended to be over 0.1 sec)
TM049 Reserved Reserved
TM050 Duration of air blow 1 Duration of air blow 1
TM051 Duration of air blow 2 Duration of air blow 2
TM052 Delay of air blow 3 Delay of air blow 3
TM053 Duration of air blow 3 Duration of air blow 3
TM054 Time 1 of automatic mold
adjustment and press
Time 1 of automatic mold adjustment and press
(recommended to be over 2 sec)
TM055 Time 2 of automatic mold
adjustment and press
Time 2 of automatic mold adjustment and press
(recommended to be over 0.3 sec)
No. Function Description
TM056 Reserved Reserved
TM057 Reserved Reserved
TM058 Reserved Reserved
TM059 Reserved Reserved
112
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manualTM060 Motor startup △Motor startup Y→ time
TM061 Resetting initial position
Resetting time for initial position of decoder
(recommended to be over 3~5)
TM062 Monitor over mold
adjustment
Time of monitor over sensor of mold
adjustment, beyond which range the alarm will
go off
TM063 Alarm duration Duration (recommended to be over 10 sec ) of
alarm (buzzer and alarm light)
TM064 Alarm pause Duration (recommended to be over 10 sec ) of
alarm (buzzer and alarm light)
TM065 Monitor over motion Monitor over motions of mold opening,
clamping, ejection, retraction of ejector, core
out/in, slow injector unit, injection, beyond
whose time the alarm will go off (recommended
to be over 5 sec)
TM066 Reserved Reserved
TM067 Reserved Reserved
TM068 Interval between ejection A buffering period between ejector advance and
retraction (recommended to be over 0.1 sec)
TM069 Anti-cold startup Start timing after motor startup, no injection,
plasticizing, unscrewing will be carried out
unless the time runs out and the temperature of
the material pipe reaches the set value
TM070 Nozzle close Time for nozzle close (for the purpose of nozzle
close of oil pressure)
TM071 Nitrogen delay Put Nitrogen release off after injection when the
function of injection of Nitrogen accumulation
is working
TM072 Delay of low pressure Put lift of auxiliary oil valve off when the
function of mold clamping of low pressure(low
pressure/express value or backpressure valve)
TM073 Delay of motion A buffering period between each successive
motion (mold opening and clamping, retraction
of ejector, core out/in, injection, recommended
to be over 0.1 sec)
TM074 Monitor over safety door Allowable maximum time for safety door
motion, beyond which range the alarm will go
off
No. Function Description
TM075 Special low pressure Duration of special low pressure at the
beginning of mold clamping
TM076 Backpressure & mold
opening
Duration mold opening synchronous with
backpress
113
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manualTM077 Open the injection nozzle Time took by the motion of opening the
injection nozzle (for the purpose of nozzle close
of oil pressure)
TM078 Injection buffer A buffering period for injection
TM079 Plasticizing buffer A buffering period for plasticizing
TM080~~
TM099
Reserved Reserved
3.4.10 Input points and descriptions thereof
No. Function Description
114
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
I00 Input point Front safety door
I01 Input Point Rear safety door
I02 Input Point Safety door limit
I03 Input Point Front limit injection nozzle
I04 Input Point B limit of core in
I05 Input Point B limit of core pulling
I06 Input Point Reserved
I07 Input Point Protecting mask of injection nozzle
I08 Input Point A limit of core in
I09 Input Point Core pulling A limit
I10 Input Point Electronic eye confirmation
I11 Input Point Reserved energy termination
I12 Input Point Mechanical and manual clamping
I13 Input Point Ejection available
I14 Input Point Mold emptied
I15 Input Point Confirmation of ejection plate
I16 Input Point Mold adjustment overload
I17 Input Point Oil pump overload
I18 Input Point Front limit of mold adjustment
I19 Input Point Rear limit of mold adjustment
I20 Input Point Count of mold adjustment
I21 Input Point Oil level of lubrication
I22 Input Point Lubrication pressure
I23 Input Point C limit of core in
I24 Input Point C limit of core pulling
I25 Input Point Oil cleaner
I26 Input Point Reserved
I27 Input Point Door-open termination
No. Function Description
I28 Input Point Door-closing termination
I29 Input Point Mold clamping reset
115
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
I30 Input Point Ejection reset
I31 Input Point Injection reset
116
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
117
No. Functions Description
O00 t Point Mold adjustment advance
O01 Output Point Mold adjustment retreat
O02 Output Point Mold clamping advance
O03 Output Point Injector unit advance
O04 Output Point Injection
O05 Output Point Plasticizing
O06 Output Point Unscrewing
O07 Output Point Injector unit retreat
O08 Output Point Mold opening
O09 Output Point Ejection advance
O10 Output Point Ejection retreat
O11 Output Point Express mold clamping
O12 Output Point A Core in A
O13 Output Point Core out A
O14 Output Point Core in B
O15 Output Point Core out B
O16 Output Point Nitrogen pressure increasing
O17 Output Point Nitrogen pressure release
O18 Output Point Air blow II
O19 Output Point Air blow I
O20 Output Point Mold opening backpress
O21 Output Point Express/low pressure
O22 Point Low pressure molding clamping
O23 Point Air blow3/Reserved
O24 Point Auto door open
O25 Point Auto door closed
O26 Point Rapid mold opening
No. Functions Description
O27 Output Point Full automation
O28 Output Point Mold opening termination
O29 Output Point Safety door closed
O30 Output Point Core in C
O31 Output Point Core out C
Ai-01 operation manualAi-01 operation manualAi-01 operation manualAi-01 operation manual
3.5 Ai-01 Operations on special screens
1 Automatic purge setting (10) Four presses on injection key
2 Injector unit setting (12) Two presses on ejection /core pulling key
3 Temperature alarm (19) One press on electrothermal key
4 Hot-runner temperature setting
(20-21) Two presses on electrothermal key
5 Function setting One press on functional key
6 Mold choices copying (23) One press on mold no./attribute control
7
Quality statistics (25)
Three presses on mold no./attribute
control
8 Monitor over time (26-30) One press on monitoring key
9 Monitor over counter (31) Two presses on monitoring key
10 Monitor over input (32-33) Three presses on monitoring key
11 Monitor over output (34-36) Four presses on monitoring key
12 Monitor over relay (37-41) Five presses on monitoring key
13 Program monitoring (42) Six presses on monitoring key
14 Injection velocity adjustment
(44)
Two presses on injection curve key
15 Injection pressure adjustment
(45)
Three presses on injection curve key
16 Language selection(51-52) Press “Clear” key + “Main menu” key
17
Stage selection (53)
Two presses on “Clearance” + “Main
menu”
18 Factory setting (65-66) Ten presses on “Clearance”+ “Mold No./
Attribute control”
19
Network (68)
One press on “Clearance” + “Injection
curve”
20
Grease setting (69)
One press on manual greasing key
21 Mechanical adjustment (71) One press on slow debugging key