Clean air solutions
Sean O’Reilly Global Director Life Science Segment
Air Filtration Standards & Sustainability
Clean air solutions Clean air solutions Clean air solutions Clean air solutions
• HVAC Filter Types • Filter Efficiency • Energy Consumption Examples-LCC • Terminal Housings & Hepa testing • Hepa repair • BIBO Housings • HVAC & Hepa Standards • CREO (Clean room design Software)
Clean air solutions Clean air solutions
Camfil Group
Clean air solutions Clean air solutions Clean air solutions Clean air solutions
Clean air solutions
Air Filtration Technologies…
Clean air solutions
6
© CA
MFIL
FARR
2013
-05-
04 Types of HEPA Filters...
Anodized Aluminum Frame
Galvaneal or Stainless Steel
Frame
Aluminum Separator
Gasket or Gel Seal
Polyurethane Sealant
Micro-fiberglass
HEPA media
Fiberglass or Thermoplastic Separator with
adhesive
Box-type HEPA Panel-type HEPA
Clean air solutions
7
© CA
MFIL
FAR
R 20
13-0
5-04
The energy cost of ventilation (simplified)
Air Handling Unit
Pre-filter Secondary-filter
Air intake
Inlet duct Distribution duct
Room distribution grille
Damper
Cooling coil Heating coil
FAN
MOTOR
Air supply
Molecular-filter
Noise attenuation
OUTSIDE INSIDE
Clean air solutions
LCC - the increased cost of energy
15
52
8
70
Filter Cost
Labor Cost
Disposal Cost
Cleaning Cost
Energy Cost
Typically 60-80% of the LCC of a filter is the energy consumption.
What if we gave you free filters in exchange for 50% of your Energy savings?
Clean air solutions
9
© CA
MFIL
FARR
2013
-05-
04 Field Efficiency; Real Life Testing...
• MERV 13, fine fiber media
• MERV 13, coarse fiber media
• MERV 11, fine fiber media
0
10
20
30
40
50
60
70
80
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000
Efficiency at 0.4 um (%)
Life Time (h)
Apples to Apples in efficiency when doing an LCC analysis
Clean air solutions
MERV 14/F8 Filter
Outside Air 1,500,000
Particles/ft3
Room Counts 420,000 Particles/ft3
Penetration
72% @ 0.3µm
72% @ 0.3µm
25% @ 0.3µm
Room Counts 1,125,000 Particles/ft3
Coarse Fiber Media (Same type media used at Wyeth,
prior to Camfil Farr)
Camfil Durafil Fine Fiber Media
How does efficiency work...
Clean air solutions
extraordinary Sales Tools
LCC & TCO Support Tools
Clean air solutions
LCC = Investment + PCenergy + PCmaint. + PCcleaning + PCdisposal
• Investment – capital cost of filters, frames, installation
• PCenergy – present total cost of power
• PCmaintenance – present total cost of maintenance including filter replacement, etc.
• PCcleaning – present cost of duct cleaning
• PCdisposal – present total cost for removal and disposal of the used filters
components of Life-Cycle Cost
Clean air solutions
• PCEnergy – the current cost of energy Energy (E) = [(Q * ΔP * T)/(ŋ * Co)] * Pc
Q – Air flow, m3/s (cfm) ΔP – Average filter pressure loss, Pa (inWG)
T – Operation time, hr
ŋ – Fan efficiency, % Co – Constant, 1000 in SI units, 8515 in IP units
Pc – Cost of Power, $/kWh
energy equation for life-cycle cost
Clean air solutions
Camfil Design vs. “Copy me” Design
Chandler or ‘V” type pleat will blind causing rapid increase in pressure drop.
Uniform radial style pleat loads evenly resulting, in lower
average pressure drop and long loading curve.
Clean air solutions
Clean air solutions
16
© CA
MFIL
FARR
2013
-05-
04
Clean air solutions
… and a Performance Comparison
17
© CA
MFIL
FARR
2013
-05-
04
• Easily compare stage by stage • Complete LCC cost graph • Includes all LCC reports and charts • Writes a conclusion and recommendation for
you • Includes the explanations needed most…
Clean air solutions
Camfield Mobile Lab
Clean air solutions
Clean air solutions
Clean air solutions
Background to cleanroom ventilation
Class 100 / ISO5 Class 10,000 / ISO7 & 100,000 / ISO8
Particles displaced
Particles diluted
Clean air solutions
Turbulent cleanroom ventilation – a component of contamination control
Clean air supply should dilute any residual particles shed from people and other emission sources and then be removed by the extract
system
Ventilation effectiveness defines how good the system is at diluting
contamination – and hence how much air is needed
(ac/hr)
Clean air solutions
Ventilation Effectiveness – key to successful contamination dilution Typical USA
Air can also bounce off the floor and
entrain contaminants
Clean air solutions
Ventilation Effectiveness – key to successful contamination dilution Typical EU/Asia
Cleaning could also be a concern
Clean air solutions
Clean air solutions Clean air solutions Clean air solutions Clean air solutions
Pharmaseal G Standard for Life Science applications.
Typical Model - 80% of Install Base
Clean air solutions
Fully Equipped for GMP In situ Controls Integrated Aerosol Dispersion Ring
Immediate access from room-side
100% Sampling Port Aerosol Injection Port
Hinged Grille Quick closing with
¼ Turn Fasteners
PAO Test Pressure Drop Airflow Velocity
Clean air solutions
Pharmaseal: Long Term Security
Airtight by Design Fully continuous welded. Airtight continuity with clean room ceiling with permanent
trim standard design. “Universal Knife Edge” Housing
Silicon gel (recommended). Immediate seal without mechanical strength. Gel belongs to filter.
Expanded PU Gasket possible.
No Risks for Leaks During Life Cycle
Cleanroom False Ceiling
Gel Expanded PU
Clean air solutions
1. aerosol particle size – different aerosols – different generation techniques
2. aerosol concentration – different generation techniques – generator input conditions – volume flow rate through filter
3. filtering velocity – system conditions
factors influencing filter penetration
LEAKS
Clean air solutions 31 © CAMFIL FARR 2013-05-04
99.988
99.990
99.992
99.994
99.996
99.998
100.000
0.01 0.1 1
Effic
iency
%
Particle Size (µm)
Example performance of a HEPA Filter
Viruses Bacteria Droplet Nuclei
HEPA filters should be tested at the Most Penetrating Particle Size (MPPS)
MPPS (0.16-0.2 micron)
0.3 micron
0.12 micron
Clean air solutions
Room-Side Certification
Aerosol Dispersion Ring:
PAO test performed in compliance with ISO-IEST standards.
NO PAO IN HVAC DUCTING for fire safety & increased filter life.
Control Panel - Centralized & Ergonomic: Injection + control from room-side
requiring only 1 person to test filter.
Quick plus airtight connection using the quick disconnect ports.
Clean air solutions
How & where to use aerosol injection is often overlooked during the design process…
1 2
3
4
Why is Room-Side Certification Important?
What location should aerosol be introduced? What type of terminal housing should an owner
or engineer select & why?
AHU Injection? 1 Ductwork Injection? 2 Hood Injection? 3
4 RA Injection?
Clean air solutions
How to Test a WM Pharmaseal ?
Clean air solutions
Price
Customer Value BSL 1
BSL/Pharma BSL/Pharma/Nuclear G
BSL/Pharma/Nuclear
No test
NI EFF/ NI Manual Scan
CamBox
CamSafe
CamContain CS NI Auto Scanning
NI Auto Scanning CamContain C CamContain CL
NI EFF /NI Maual Scan
Products for Bio Safety / Life Science:
BSL 2 BSL 2+3 BSL 3 BSL 3+4
Pharmatain
Camtain BIBO DC
Clean air solutions
36
© CA
MFIL
FARR
2013
-05-
04
Clean air solutions
Current Standards-IEST (Cont.);
Type E-AG1 Type K-Recommended for 0.01% leak test with thermal PAO
Clean air solutions
Current Standards – EN1822 (Cont);
Clean air solutions
New Standard 2012; ISO -29463 parts 1 thru 5
Clean air solutions
40
© CA
MFIL
FARR
2013
-05-
04
Updated Cleanroom Filter Standards:
Clean air solutions
41
© CA
MFIL
FARR
2013
-05-
04
Updated Cleanroom Standards:
• Simplify the classification process and if possible remove the need to evaluate the 95% UCL for 2-9 sample locations
• Review the classification procedure and make it more applicable to rooms in operation. The contamination isn’t expected to be evenly distributed an assumption the current statistical approach makes.
• Avoid any radical changes to the principals of the current ISO cleanliness classes 1-9
Clean air solutions
42
© CA
MFIL
FARR
2013
-05-
04
HVAC Global Air Filter Standards
Clean air solutions
CREO a new CleanRoom design & Energy Optimization software.
Clean air solutions
Clean air solutions
45
© CA
MFIL
FARR
04/05
/201