Air Handling Unit 350 P
Typebetegnelse:E = elvarmefladeW = vandvarmeflade
Dimensioner
Type AccessoriesUNI PROTPC
1141RC02-F2
KFF-4
SP TJK10KC04C***
SSBHeating
SSBCooling
RMG80/600C
RMG80/400C
VVP/VXP80/600C
VVP/VXP80/600C
350PE + + * - - - - - - -
350PW + + ** + 61 81 3-0,63-4 3-0,63-4 45.10-0,63 45.10-0,63
* - LM230A-TP for the fresh air dampers** - NF230A*** - anti-frost thermostat
Type Dimensions [mm]W W1 W2 H H1 H2 H3 E L S øD
350PE 398 196 550 610 160 160 83 764 961 652 200 350PW 398 196 550 610 160 160 83 764 961 652 200
Accessories
SSB p. 194
Thermic watervalve actuator Mixing point
2 and 3 way valves
RMG VVP/VXP p. 195 p. 196
Duct sensor
TJK 10K p. 198
Extract air = 20°C/60% RH - � utdoor air = -20°C/90% RHBalance between supply air/extract air = 1.0
RIRS 350PE EKOAir intake side (L- left)
View from inspection side
350PE Heater -phase/voltage [50Hz/VAC] ~1, 230
-power consumption [kW] 0,6EC Fans -phase/voltage [50Hz/VAC] ~1, 230
exhaust -power/current [kW/A] 0,130/1,9-fan speed [min-1] 3490
supply -power/current [kW/A] 0,130/1,22-fan speed [min-1] 3490
Motor protection class IP-4480%
Max power consumption [kW/A] 0,88/5,3Automatic control integratedFilter class -exhaust F5
-supply F7Thermal insulation [mm] 30Weight [kg] 54,0Comply with ERP 2013 +
Extract airExhaust air Fresh air Supply air
350PE Performance
Power consumption
η [%
]
3/h]
Sta
tic p
ress
ure
[Pa]
3/h]
Pow
er [W
]Exhaust air
3/h]
Sta
tic p
ress
ure
[Pa]
Pow
er [W
]
Supply air
Sta
tic p
ress
ure
[Pa]
3/h]total power for supply & exhaust fans kW3/h
x 3600SFP=
AIR
HA
ND
LIN
G U
NIT
S
350PE Lwa total, dB(A)
LWA, dB(A)125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Supply 69 54 53 66 64 60 58 55Extract 64 52 54 59 58 57 54 49Surrounding 54 40 39 48 41 47 44 46Measured at 356 m3/h, 120 Pa
Designed for operation indoors only
Extract air = 20°C/60% RH - � utdoor air = -20°C/90% RHBalance between supply air/extract air = 1.0
View from inspection side
Extract airExhaust air Fresh air Supply air
350PW Performance
Power consumption
η [%
]
3/h]
Sta
tic p
ress
ure
[Pa]
3/h]
Pow
er [W
]
Exhaust air3/h]
Sta
tic p
ress
ure
[Pa]
Pow
er [W
]
Supply air
Sta
tic p
ress
ure
[Pa]
3/h]total power for supply & exhaust fans kW3/h
x 3600SFP=
350PW Water heater -power [kW]
AVS 200-water . Tin/Tout
[oC][l/s]
-water pressure drop [kPa]
EC Fans -phase/voltage [50Hz/VAC] ~1, 230exhaust -power/current [kW/A] 0,130/1,19
-fan speed [min-1] 3490supply -power/current [kW/A] 0,130/1,22
-fan speed [min-1] 3490Motor protection class IP-44
80%Max power consumption [kW/A] 0,27/2,5Automatic control integratedFilter class -exhaust F5
supply F7Thermal insulation [mm] 30Weight [kg] 54,0Comply with ERP 2013 +
350PW Lwa total, dB(A)
LWA, dB(A)125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
Supply 69 54 53 66 64 60 58 55Extract 64 52 54 59 58 57 54 49Surrounding 54 40 39 48 41 47 44 46Measured at 356 m3/h, 120 Pa
Designed for operation indoors only
350PW Air intake side (L- left)
350PE (ceiling mounted) versions with electrical heater
350PW (ceiling mounted) versions with water heater
Fresh air
Fresh air
Supply air
Supply air
Exhaust air
Exhaust air
Extract air
Extract air
IV - exhaust air fanPV - supply air fanRR - rotary heat exchangerR - rotor motorKE - electrical heaterPF IF
IV - exhaust air fanPV - supply air fanRR - rotary heat exchangerR - rotor motorPF IF
TL - temperature sensor for fresh air TA - temperature sensor for extract airPS1 - extract air differential pressure switchPS2 - fresh air differential pressure switch
TL - temperature sensor for fresh air TA - temperature sensor for extract airPS1 - extract air differential pressure switchPS2 - fresh air differential pressure switchAVS - optionally supplied water heater