Airflow Dampers En

  • Upload
    sudoku

  • View
    245

  • Download
    0

Embed Size (px)

Citation preview

  • 8/10/2019 Airflow Dampers En

    1/448

    Halton air flow damper range

    PRA PTS RMC UTK UTS UTT

    Nominal size 1001000 100...500 100400 100x100

    24002400

    100x100

    24002400

    100x100

    24002400

    Tightness in shut-off

    operation

    - PTS/A

    Class 4

    EN 1751

    Class1

    EN 1751

    Class 2

    EN 1751

    Class 4

    EN 1751

    Tightness of the

    casing

    Class C

    EN 1751

    Class C

    EN 1751

    Class B

    EN 1751

    Class B

    EN 1751

    Class B

    EN 1751

    Operation conditions ...100C,

    (UTK/H,J

    ...200C)

    -

    ...100C,

    (UTS/H,J

    ...200C)

    -

    ...100C,

    (UTT/H,J

    ...200C)

    -

    Adjustment X X X - X X

    Measurement X - - - - -

    Material options AISI 316 AISI 316 AISI 316

    Other Information RMC/I

    Casing

    insulation

    50 mm

    UTK/I

    Casing

    insulation

    20 mm

    UTS/I

    Casing

    insulation

    20 mm

    UTT/I

    Casing

    insulation

    20 mm

    Air flow dampers

  • 8/10/2019 Airflow Dampers En

    2/449

    PRA - Adjustment And Measurement Unit

    20/PRA/3500/0606/EN

    PRA

    Adjustment And Measurement Unit

    Airflow balancing, adjustment and measurement

    unit

    Manual adjustment, no tools required

    Accurate airflow measurement based on

    flow nozzle principle

    Minimised sound generation due to conical

    adjustment section

    Temperature operation range from -30 C to +70 C

    Self-locking adjustment mechanism, position can

    be ensured with locking screw

    Duct cleaning enabled through the unit up to

    size 315

    Adjustment position marker indicates

    proper position e.g. repositioning after cleaning

    Inlet and outlet spigots equipped with integral

    rubber gaskets

    Application option as supply air jet nozzle for air

    diffusion in large spaces

    Classification of casing leakage EN 1751 class C

    Product Models

    PRA -unit (PRA/R) integrated with cleaning access

    panel. RLA enables removal of the adjustment

    damper and access to ductwork for cleaning.

    MATERIAL

    PART MATERIAL NOTE

    Casing Galvanised steel

    Blades Galvanised steel

    Operating

    mechanism

    ABS and PBT plastic Sizes 100...315

    Operating

    mechanism Steel Sizes 350...1000

    Duct gaskets 1C-polyurethane

    hybrid

    Measurement taps Polyurethane (PU)

  • 8/10/2019 Airflow Dampers En

    3/4410

    D

    7036

    142

    57

    D

    39 114

    195

    H

    PRA 100...315

    NS D

    100 99

    125 124

    160 159

    200 199

    250 249

    315 314

    PRA 350...1000

    NS D H

    350 349 70

    400 399 70

    500 499 70

    630 629 70

    800 799 70

    1000 999 85

    20/PRA/3500/0606/EN

    PRA - Adjustment And Measurement Unit

    DIMENSIONS

    QUICK SELECTION

    D qmin qmax

    [mm] [l/s] [m3/h] [l/s ] [m3/h]

    100 8 28 47 170

    125 12 44 74 265

    160 20 72 121 434

    200 31 113 188 679

    250 49 177 295 1060

    315 78 281 468 1683

    350 96 346 577 2078

    400 126 452 754 2714

    500 196 707 1178 4241

    630 312 1122 1870 6733

    800 503 1810 3016 10857

    1000 785 2827 4712 16965

    qmin 1 m/s duct velocity

    qmax 6 m/s duct velocity - recommended maximum

    airflow for comfort applications

  • 8/10/2019 Airflow Dampers En

    4/4411

    PRA - Adjustment And Measurement Unit

    20/PRA/3500/0606/EN

    Function

    The airflow rate is adjusted by turning the adjustment

    knob in order to change the aperture size of the

    adjustment cone formed by iris blades. Once the

    opening area is reduced, the airflow rate decreases

    and the total pressure loss caused by the device

    increases.

    The airflow can be determined by measuring the

    differential pressure in the measurement taps.

    PRA 100315

    The operating mechanism is positioned partly outside

    the device and between the adjustment cone and

    casing. The unit can be cleaned with normal duct

    sweeping equipment when the device is fully opened.

    PRA 4001000The operating mechanism is located partly outside the

    device and inside the adjustment cone. The device can

    be cleaned with normal duct sweeping equipment,

    when the device is fully opened and the cleaning

    equipment is passed carefully through the operating

    mechanism.

    Supply air jet nozzle PRA/S

    The PRA-unit can also be used as a supply air nozzle

    in e.g. industrial spaces. Refer to the technical data for

    PRA/S -model presented in the technical performance

    chapter.

    Installation

    Sizes 100...315

    CODE DESCRIPTION

    1 Air flow direction indicator

    2 Adjustment knob

    3 Locking screw of adjustment Position

    4 Adjustment position indicator

    5 Adjustment position marker for Cleaning

    6 Adjustment scale

    7 Measurement taps

    Sizes 350...1000

    CODE DESCRIPTION

    1 Adjustment position indicator

    2 Adjustment knob

    3 Measurement taps

  • 8/10/2019 Airflow Dampers En

    5/4412

    1

    3

    5

    7

    8

    2

    4

    6

    8

    20/PRA/3500/0606/EN

    PRA - Adjustment And Measurement Unit

    Installation

    Fix the damper to the ductwork e.g. with rivets.

    Ensure that the rivet does not prevent the operation of

    the PRA. The position of the rivet must be at least 10

    mm from the duct end.

    The PRA iris damper shall be installed in the ductwork

    taking into account the safety distances outlined in

    the installation guidelines. Safety distances are not

    required next to duct transitions between only one

    nominal duct size.

    The orientation of the unit shall correspond to the

    airflow direction. The airflow direction is marked with

    an arrow indicator on the label on the casing. In order

    to get accurate measurement readings the orientation

    of the unit shall be selected so that the location of the

    measurement taps (below the knob) corresponds tothe installation guidelines.

    Safety distances

    Recommended safety distance in order to get

    accurate measurement readings are presented in the

    figure below.

    Direct duct with no flow disturbances

    - safety distance 4 D upflow of the PRA unit

    - safety distance 1 D downflow of the PRA unit

    In cases where recommended safety distances cannot

    be met, use the correction factors of the attached

    figures for determination of the airflow rate.

    Note the position of the measurement taps marked in

    the figures.

    F igure Insta llat ion case Duct velocity upflow of the pra unit K -factor

    1 Recommended safety distance 1

    2 T-branch, supply air 0.95 (1D) ...1.00 (4D)

    3 T-branch, exhaust air > 2 m/s 1 2 m/s 0.95 (1D) ...1.00 (4D) 0.90 (1D) ...1.00 (4D)

    4 90 bend 0.97 (0D) ...1.00 (4D)

    5 T-branch 1

    6 90 bend 1

    7 Upflow of a supply air device 1

    8 T-branch 1

  • 8/10/2019 Airflow Dampers En

    6/4413

    q = k pv m*

    PRA - Adjustment And Measurement Unit

    20/PRA/3500/0606/EN

    PRA 160, k-factor

    Opening a qv l/s qv m3/h qv cfm

    1 4,1 14,8 137,1

    1.5 4,7 16,9 157,2

    2 5,5 19,8 183,9

    2.5 6,4 23,0 214,0

    3 7,6 27,4 254,1

    3.5 9 32,4 300,9

    4 10,6 38,2 354,4

    4.5 12,6 45,4 421,3

    5 15 54,0 501,6

    5.5 18,2 65,5 608,6

    6 22,9 82,4 765,7

    Airflow (qv) diffrential pressure (Dpm) [Pa]

    PRA 100, k-factor

    Opening a qv l/s qv m3/h qv cfm

    1 1.8 6.5 60.2

    1.5 2.1 7.6 70.2

    2 2.4 8.6 80.3

    2.5 2.7 9.7 90.3

    3 3.1 11.2 103.7

    3.5 3.6 13.0 120.4

    4 4.1 14.8 137.1

    4.5 4.7 16.9 157.2

    5 5.5 19.8 183.9

    5.5 6.4 23.0 214.0

    6 7.8 28.1 260.8

    PRA 125, k-factor

    Opening a qv l/s qv m3/h qv cfm

    1 2,5 9,0 83.6

    1.5 2.9 10,4 97,0

    2 3,3 11,9 110,3

    2.5 3,8 13,7 127,1

    3 4,4 15,8 147,1

    3.5 5 18,0 167,2

    4 5,9 21,2 197,3

    4.5 6,8 24,5 227,4

    5 7,9 28,4 264,2

    5.5 9,5 34,2 317,7

    6 11,6 41,8 387,9

    PRA 200, k-factor

    Opening a qv l/s qv m3/h qv cfm

    1 7,1 25,6 237,4

    1.5 8 28,8 267,5

    2 8,8 31,7 294,3

    2.5 10 36,0 334,4

    3 11,4 41,0 381,2

    3.5 13,1 47,2 438,0

    4 15,1 54,4 504,9

    4.5 17,5 63,0 585,2

    5 20,5 73,8 685,5

    5.5 24,2 87,1 809,2

    6 29 104,4 969,7

    Adjustment

    Set the adjustment knob in the desired adjustment

    position (pre-set position if available).

    The airflow rate is determined by measuring the

    differential pressure in measurement tabs using a

    manometer.

    The flow rate is calculated using the formula below.

    K-factor is retrieved in both the tables presented

    below and in installation guidelines. K-factor depends

    on the unit size and adjustment position (a).

    Note that when recommended safety distances are

    not met, the correction factors for the installation case

    shall be used.

  • 8/10/2019 Airflow Dampers En

    7/4414

    20/PRA/3500/0606/EN

    PRA - Adjustment And Measurement Unit

    PRA 250, k-factor

    Opening a qv l/s qv m3/h qv cfm

    1 10,5 37,8 351,1

    1.5 11,9 42,8 397,9

    2 13,8 49,7 461,4

    2.5 16,1 58,0 538,3

    3 18,9 68,0 632,0

    3.5 22 79,2 735,6

    4 25,6 92,2 856,0

    4.5 30,1 108,4 1006,5

    5 35,8 128,9 1197,1

    5.5 42,9 154,4 1434,5

    6 52,8 190,1 1765,5

    PRA 315, k-factor

    Opening a qv l/s qv m3/h qv cfm

    1 18,3 65,9 611,9

    1.5 21,8 78,5 728,9

    2 26 93,6 869,4

    2.5 30,7 110,5 1026,5

    3 36,5 131,4 1220,5

    3.5 43,3 155,9 1447,8

    4 51,3 184,7 1715,3

    4.5 61,5 221,4 2056,4

    5 74,3 267,5 2484,4

    5.5 92,6 333,4 3096,3

    6 120,2 306,0 4019,2

    PRA 350, k-factor

    Opening a qv l/s qv m3/h qv cfm

    1 17,6 63,4 588,5

    2 24,3 87,5 812,5

    3 35,2 126,7 1177,0

    4 50 80,0 1671,9

    5 71,6 257,8 2394,1

    6 99 356, 3310,3

    PRA 400, k-factor

    Opening a qv l/s qv m3/h qv cfm

    1 20,5 73,8 685,5

    2 26,5 95,4 886,1

    3 36,5 131,4 1220,5

    4 55 198,0 1839,1

    5 86 309,6 2875,6

    6 137 493,2 4581

    PRA 500, k-factor

    Opening a qv l/s qv m3/h qv cfm

    1 27,5 99,0 919,5

    2 39 140,4 1304,1

    3 59 212,4 1972,8

    4 86 309,6 2875,6

    5 123 442,8 4112,8

    6 175 630 5851,6

    PRA 630, k-factor

    Opening a qv l/s qv m3/h qv cfm

    1 65 234,0 2173,4

    2 90 324,0 3009,4

    3 115 414,0 3845,3

    4 154 554,4 5149,4

    5 202 727,2 6754,4

    6 295 954 8861

    PRA 1000, k-factor,

    Opening a qv l/s qv m3/h qv cfm

    1 144 518,4 4815,0

    2 220 792,0 7356,3

    3 310 116,0 10365,7

    4 440 1584,0 14712,5

    5 620 2232,0 20731,3

    6 890 3204,0 29759,5

    PRA 800, k-factor

    Opening a qv l/s qv m3/h qv cfm

    1 98 273,3 3276,9

    2 137 382,0 4581,0

    3 198 552,1 6620,6

    4 280 780,8 9362,5

    5 393 1095,9 13141,0

    6 570 1589,5 19059,4

    Airflow (qv) diffrential pressure (Dpm) [Pa]

  • 8/10/2019 Airflow Dampers En

    8/4415

    PRA-100 PRA-125

    PRA-160 PRA-200

    PRA - Adjustment And Measurement Unit

    20/PRA/3500/0606/EN

    Pressure drop and sound data

  • 8/10/2019 Airflow Dampers En

    9/4416

    PRA-250 PRA-315

    PRA-400 PRA-500

    20/PRA/3500/0606/EN

    PRA - Adjustment And Measurement Unit

    Pressure drop and sound data

  • 8/10/2019 Airflow Dampers En

    10/4417

    PRA-630 PRA-800

    PRA-1000

    PRA - Adjustment And Measurement Unit

    20/PRA/3500/0606/EN

    Pressure drop and sound data

  • 8/10/2019 Airflow Dampers En

    11/4418

    PRA/S-100 PRA/S-125

    PRA/S-160 PRA/S-200

    20/PRA/3500/0606/EN

    PRA - Adjustment And Measurement Unit

    Supply air jet nozzle; PRA/S

    Pressure drop, flow pattern and sound data

  • 8/10/2019 Airflow Dampers En

    12/4419

    PRA/S-250 PRA/S-315

    PRA - Adjustment And Measurement Unit

    20/PRA/3500/0606/EN

    Supply air jet nozzle; PRA/S

    Pressure drop, flow pattern and sound data

  • 8/10/2019 Airflow Dampers En

    13/4420

    100 Pa qv v F (Hz) LpA NR

    ( l/ s) (m3/h) m/ s 63 125 250 5 00 10 00 200 0 4 00 0 8 00 0 dB(A)

    100 20 72 2,5 36 37 36 37 38 38 34 27 38 37

    36 130 4,6 37 42 41 42 41 41 37 29 41 40

    50 180 6,4 38 45 45 45 45 45 42 35 45 44

    125 51 184 4,2 40 40 41 37 32 32 27 19 33 31

    72 259 5,9 40 42 43 41 37 38 34 25 39 38

    102 367 8,3 42 45 48 46 43 46 44 32 46 45160 45 162 2,2 41 38 34 31 28 28 25 13 29 27

    90 324 4,5 44 43 40 38 35 36 32 23 37 35

    133 479 6,6 45 45 44 42 41 43 37 29 43 42

    134 482 4,3 42 42 40 36 36 39 35 25 39 38

    188 677 6,0 44 44 42 39 40 43 39 30 43 42

    281 1012 8,9 47 49 48 46 50 51 49 37 52 50

    250 199 716 4,1 42 42 40 35 38 37 30 21 38 36

    292 1051 6,0 46 46 44 40 43 43 37 27 43 42

    475 1710 9,7 49 50 50 48 52 52 50 35 53 51

    315 259 932 3,3 45 40 36 31 31 28 23 13 31 27

    385 1386 4,9 46 44 40 37 38 34 28 19 37 34

    613 2207 7,9 47 49 46 44 47 45 40 27 47 44

    400 248 893 2,0 37 36 35 36 33 29 20 36 33

    466 1678 3,7 39 38 37 38 35 31 22 38 34

    1314 4730 10,5 52 51 50 51 48 44 35 51 47

    500 318 1145 1,6 40 39 41 40 36 29 17 39 36

    791 2848 4,0 44 43 45 44 40 33 21 44 403004 10814 15,3 65 64 66 65 61 54 42 65 61

    630 763 2747 2,4 44 41 41 39 37 31 21 40 36

    1562 5623 5,0 47 44 44 42 40 34 24 43 39

    4438 15977 14,2 64 61 61 59 57 51 41 60 56

    800 1195 4302 2,4 46 43 43 41 39 33 23 42 38

    2548 9173 5,1 49 46 46 44 42 36 26 45 41

    9493 34175 18,9 70 67 67 65 63 57 47 66 62

    1000 1739 6260 2,2 49 44 44 42 40 34 24 43 39

    4030 14508 5,1 52 47 47 45 43 37 27 46 42

    15000 54000 19,1 71 66 66 64 62 56 46 65 61

    250 Pa qv v F (Hz) LpA NR

    ( l/ s) (m3/h) m/s 63 125 2 50 50 0 100 0 200 0 4 000 800 0 d B(A)

    100 31 112 3,9 38 47 46 46 47 50 49 47 51 49

    43 155 5,5 39 48 48 49 50 50 51 48 52 51

    58 209 7,4 40 51 50 51 53 54 54 50 55 54

    125 42 151 3,4 43 47 48 45 41 40 40 37 43 41

    58 209 4,7 46 47 49 46 42 41 42 39 44 42

    113 407 9,2 45 52 53 52 50 53 53 49 54 54160 71 256 3,5 46 50 46 43 40 40 41 37 43 42

    97 349 4,8 47 50 47 44 42 42 46 41 46 46

    142 511 7,1 47 53 50 48 48 49 51 47 52 51

    117 421 3,7 50 51 50 46 44 45 45 43 47 46

    158 569 5,0 49 51 51 47 44 46 50 45 50 50

    212 763 6,8 50 53 53 49 46 49 52 48 52 53

    250 163 587 3,3 47 50 51 47 46 51 48 39 51 50

    223 803 4,5 49 52 51 48 46 48 46 41 49 47

    315 1134 6 ,4 52 54 52 49 49 51 47 44 52 50

    315 271 976 3,5 51 49 47 42 42 40 39 33 43 40

    410 1476 5,3 51 53 49 44 44 44 44 35 46 45

    609 2192 7,8 55 56 52 49 50 48 46 43 51 47

    400 392 1411 3,1 51 50 49 50 47 43 34 50 46

    737 2653 5,9 53 52 51 52 49 45 36 52 48

    2077 7477 16,5 66 65 64 65 62 58 49 64 61

    500 503 1811 2,6 53 52 54 53 49 42 30 53 49

    1250 4500 6,4 58 57 59 58 54 47 35 57 544750 17100 24,2 79 78 80 79 75 68 56 79 75

    630 1206 4342 3,9 57 54 54 52 50 44 34 53 49

    2469 8888 7,9 61 58 58 56 54 48 38 57 53

    7016 25258 22,5 78 75 75 73 71 65 55 74 70

    800 1890 6804 3,8 59 56 56 54 52 46 36 55 51

    4029 14504 8,0 63 60 60 58 56 50 40 59 55

    15010 54036 29,9 83 80 80 78 76 70 60 79 75

    1000 2750 9900 3,5 63 58 58 56 54 48 38 56 52

    6372 22939 8,1 66 61 61 59 57 51 41 60 56

    23717 85381 30,2 85 80 80 78 76 70 60 79 75

    500 Pa qv v F (Hz) LpA NR

    ( l/ s) (m3/h) m/s 63 125 2 50 5 00 10 00 200 0 4 00 0 8 00 0 dB(A)

    100 45 162 5,7 40 55 54 53 54 58 60 62 61 64

    61 220 7,8 41 55 55 56 58 59 62 64 63 6682 295 10,4 41 58 57 58 61 64 66 66 67 68

    125 60 216 4,9 48 55 58 55 52 50 51 51 54 53

    83 299 6,8 51 54 58 56 52 51 55 55 56 57

    115 414 9,4 50 56 60 58 55 58 57 54 59 57

    160 100 360 5,0 50 58 56 53 48 48 53 55 55 58

    137 493 6,8 51 59 56 53 52 51 59 60 59 62

    201 724 10,0 50 61 58 56 58 59 65 66 65 67

    166 598 5,3 56 60 59 55 53 54 57 60 59 62

    224 806 7,1 55 60 60 57 53 53 63 63 62 65

    300 1080 9,6 55 62 62 58 53 57 65 66 65 68

    250 230 828 4,7 52 59 61 57 54 62 63 57 63 63

    316 1138 6,4 55 61 61 58 53 58 60 59 61 61

    445 1602 9,1 59 63 62 59 57 62 60 61 63 63

    315 383 1379 4,9 56 58 56 51 51 48 50 50 53 52

    579 2084 7,4 56 62 58 54 54 56 60 52 60 60

    861 3100 11,1 61 65 60 58 59 58 60 61 62 63

    400 555 1998 4,4 61 60 59 60 57 53 44 60 56

    1042 3751 8,3 63 62 61 62 59 55 46 62 58

    2937 10573 23,4 76 75 74 75 72 68 59 75 71

    500 712 2563 3,6 63 62 64 63 59 52 40 63 59

    1768 6365 9,0 68 67 69 68 64 57 45 68 64

    6718 24185 34,2 90 89 91 90 86 79 67 90 86

    630 1705 6138 5,5 68 65 65 63 61 55 45 63 59

    3492 12571 11,2 72 69 69 67 65 59 49 67 63

    9923 35723 31,8 88 85 85 83 81 75 65 84 80

    800 2673 9623 5,3 70 67 67 65 63 57 47 66 62

    5698 20513 11,3 73 70 70 68 66 60 50 69 65

    21227 76417 42,3 93 90 90 88 86 80 70 89 85

    1000 3889 14000 5,0 73 68 68 66 64 58 48 67 63

    9012 32443 11,5 76 71 71 69 67 61 51 70 66

    33541 120748 42,7 95 90 90 88 86 70 70 89 85

    750 Pa qv v F (Hz) LpA NR

    ( l/ s) (m3/h) m/s 63 125 250 500 10 00 200 0 4 00 0 8 00 0 dB(A)

    100 55 198 7,0 41 60 59 57 58 64 66 71 68 72

    75 270 9,6 42 59 59 60 63 64 69 73 71 75100 360 12,7 42 62 61 62 66 69 74 76 75 77

    125 73 262,8 6,0 51 59 63 61 58 56 58 59 60 61

    101 363,6 8 ,2 54 59 63 61 58 57 62 65 64 67

    141 507,6 11,5 53 61 65 63 60 64 65 62 66 65

    160 122 439,2 6,1 52 64 62 59 54 54 60 66 63 68

    168 604,8 8 ,4 53 63 61 58 57 56 66 71 68 72

    247 889,2 12,3 51 66 63 61 64 65 73 76 74 78

    203 730,8 6 ,5 60 65 65 61 58 59 65 69 67 71

    274 986,4 8 ,7 59 64 66 63 57 57 71 73 71 74

    368 1324,8 11,7 58 67 68 64 57 61 72 77 74 78

    250 282 1015,2 5,7 55 64 66 62 59 68 72 67 71 72

    387 1393,2 7,9 5 9 66 67 64 57 64 69 69 69 71

    545 1962 11,1 64 69 68 65 62 68 67 72 71 73

    315 470 1692 6,0 59 63 62 56 56 53 57 60 60 62

    709 2552,4 9,1 59 67 63 60 60 63 69 62 68 69

    1054 3794,4 13,5 65 70 6 5 63 6 4 64 68 72 70 74

    400 679 2444,4 5,4 67 66 65 66 63 59 50 66 62

    12777 4597,2 10,2 69 68 67 68 65 61 52 68 64

    3598 12953 28,6 82 81 80 81 78 74 65 80 77

    500 871 3135,6 4,4 69 68 70 69 65 58 46 69 65

    2165 7794 11,0 74 73 75 74 70 63 51 74 70

    8227 29617 41,9 96 95 97 96 92 85 73 96 92

    630 2089 7520,4 6,7 74 71 71 69 67 61 51 69 65

    4277 15397 13,7 78 75 75 73 71 65 55 74 69

    12153 43751 39,0 94 91 91 89 87 81 71 90 86

    800 3273 11783 6,5 76 73 73 71 69 63 53 72 68

    6978 25121 13,9 79 76 76 74 72 66 56 75 71

    25997 93589 51,7 99 96 96 94 92 86 76 95 91

    1000 4763 17147 6,1 79 74 74 72 70 64 54 73 69

    11037 39733 14,1 83 78 78 76 74 68 58 76 72

    41079 147884 52,3 99 96 96 94 92 86 76 95 90

    20/PRA/3500/0606/EN

    PRA - Adjustment And Measurement Unit

    Supply air jet nozzle; PRA/S

    SOUND DATA

  • 8/10/2019 Airflow Dampers En

    14/4421

    PRA - Adjustment And Measurement Unit

    20/PRA/3500/0606/EN

    Servicing

    Before cleaning of the ductwork, check that the actual

    adjustment position is ticked with the adjustment

    position marker.

    Open the damper by turning the adjustment knobcounter-clockwise.

    Clean the ductwork.

    Reset the damper position to the marked adjustment

    position.

    Suggested specifications

    The adjustment damper shall comprise an adjustable

    cone and airflow measurement taps for differential

    pressure measurement.

    The casing and adjustment cone vanes shall be made

    of galvanised steel.

    The airflow determination shall be based on the

    differential pressure measurement caused by airflow

    over the damper cone.

    The adjustment damper shall have an adjustment

    position indicator and adjustment position marker to

    be used during cleaning.

    Product code

    PRA/S-D

    S = Model

    N Standard R With RLA cleaning

    access panel

    D = Diameter of duct connection

    100, 125, 160, 200, 250, 315, 350,

    400, 500, 630, 800, 1000

    Code example

    PRA/N-100

  • 8/10/2019 Airflow Dampers En

    15/4422

    20/PTS/3500/0606/EN

    PTS - Single-Blade Damper

    PTS

    Single-Blade Damper

    Shut-off, adjustment, balancing or control damper

    Casing leakage classification: EN 1751, Class C

    Casing and damper blade made of galvanised steel

    Tightness classification of shut-off damper: EN 1751,

    Class 4

    Product models and Accessories

    Shut-off, adjustment, balancing or control damper

    Adjustment, balancing or control damper

    Adjustment, balancing or control damper with

    perforated blade

    Several actuator options

    MATERIAL

    PART MATERIAL NOTE

    Casing Galvanised steel

    Blade and shaft Galvanised steel

    Operating

    mechanism Stainless steel

    Blade gasket EPDM rubber Used only in

    PTS/A model

    Duct gaskets 1C-polyurethane

    hybrid

    Actuator platform Galvanised steel

    QUICK SELECTION

    D qmin qmax

    [mm] [l/s] [m3/h] [l/s ] [m3/h]

    100 8 28 47 170

    125 12 44 74 265

    160 20 72 121 434

    200 31 113 188 679

    250 49 177 295 1060

    315 78 281 468 1683

    400 126 452 754 2714

    500 196 707 1178 4241

    qmin 1 m/s duct velocity

    qmax 6 m/s duct velocity - recommended maximum airflow for

    comfort applications

  • 8/10/2019 Airflow Dampers En

    16/4423

    65

    D

    L

    L1L2

    25

    160

    45.2

    70

    24.5

    45.

    2

    4.7160

    45.2

    70

    57.5

    45.2

    4.7

    25

    NS L L1 L2 D

    100 145 70 36 99

    125 145 70 36 124

    160 145 70 36 159

    200 145 70 36 199

    250 145 70 36 249

    315 145 70 36 314

    400 245 175 35 399500 245 175 35 499

    PTS - Single-Blade Damper

    20/PTS/3500/0606/ENDIMENSIONS

    Product models and Accessories

    There are three different product models, for different

    purposes:

    Shut-off, adjustment, balancing or control damper,

    PTS/A

    Tightness classification: EN 1751, Class 4

    Adjustment, balancing or control damper, PTS/B

    Adjustment, balancing or control damper with

    perforated blade, PTS/C

    Actuator platform, low (ML) Actuator platform, high (MH)

    Actuator options

    Standard actuators

    Belimo LM24A / LM230A / LM24A-SR (5 Nm), NM24A

    / NM230A / NM24A-SR (10 Nm) and LF24 / LF230

    (4 Nm)

    For technical data for available actuators, consult the

    list below.

    After sales installation of the actuator

    Actuator installation on the site is possible with the

    help of an actuator bed and extension shaft. This

    enables installation of a universal actuator type. The

    actuator bed selected can be of standard type when

    the ductwork is not insulated or of high type if the

    ductwork is insulated.

    Minimum torque 4 Nm 10 Nm

    PTS/A 10 0...250 x

    PTS/A 315...500 x

    PTS/B 10 0...500 x

    PTS/C 10 0...500 x

    Manual operation

    Handle for manual operation with blade position

    locking.

  • 8/10/2019 Airflow Dampers En

    17/4424

    20/PTS/3500/0606/EN

    PTS - Single-Blade Damper

    Electrical actuator: specific data

    If other actuator types are required, consult Halton in

    order to specify the type and manufacturer.

    CODE NAME MANUFACTURER TORQUE Nm POWER SUPPLY CONTROL TYPE POWER

    CONSUMPTION

    B1 LM24A-F Belimo 5 24 VAC/VDC On-off, 2-wire 3 VA / 2 W

    B2 LM230A-F Belimo 5 230 VAC On-off, 2-wire 12 VA / 1 W

    B3 LM24A-SR-F Belimo 5 24 VAC/VDC Modulating

    010 VDC

    4 VA / 2 W

    B4 NM24A Belimo 10 24 VAC/VDC On-off, 2-wire 3.5 VA / 2 W

    B5 NM230A Belimo 10 24 VAC/VDC On-off, 2-wire 18 VA / 2 W

    B6 NM24A-SR Belimo 10 24 VAC Modulating

    010 VDC

    3 VA / 1.5 W

    B7 LF24 Belimo 4 24 VAC On-off, spring

    return

    7 VA / 5 W

    B8 LF230 Belimo 4 230 VAC On-off, spring

    return

    8 VA / 5 W

    PTS/A with actuator (B4) Actuator IL / IH PTS

  • 8/10/2019 Airflow Dampers En

    18/4425

    PTS/C

    PTS/BPTS/A

    PTS - Single-Blade Damper

    20/PTS/3500/0606/EN

    Function

    The PTS unit can operate as a shut-off, control or

    adjustment damper depending on the product model.

    This damper is available for circular standard duct

    sizes 100 mm to 500 mm. Damper position is visuallyindicated below the operating mechanism.

    The PTS/A is a shut-off damper of leakage class

    4 according to the EN 1751 standard. It includes

    rubber gaskets to ensure low leakage flow when the

    damper is in closed position. The PTS/A is available

    with a handle for manual operation or with an electric

    actuator for on-off control or for modulating control

    using a 0...10 VDC control signal.

    The PTS/B can be used for airflow control or

    adjustment of airflow rates in the ductwork. It includes

    a steel blade without gasket. The PTS/B is available

    with a handle for manual operation or with an electric

    actuator for on-off control or for modulating control

    using a 010 VDC control signal.

    The PTS/C is an airflow adjustment damper. The

    damper blade is a perforated blade that is acoustically

    and operationally designed for balancing of airflow

    rates.

    The electric actuator is normally installed in the factory

    on the actuator platform with screws. On-site actuator

    installation is possible with the help of an actuator

    installation kit. The actuator installation kit, available

    as an accessory, includes an actuator platform and

    extension shaft for universal actuator fixing. The

    actuator platform and actuator can be installed easily

    using standard hand tools.

  • 8/10/2019 Airflow Dampers En

    19/4426

    LM...A

    NM...A

    24 VAC, 24 VDC

    230 VAC

    1 2 3 5

    ~

    ~LM24A-SR

    NM24A-SRLF24-SR

    SM24A-SR

    24 VAC, 24 VDC

    1 2 3 5

    ~

    ~

    0-10 VDC

    2-10 VDC

    AF2 4- SR

    24 VAC, 24 VDC~

    ~

    0-10 VDC

    2-10 VDC

    Y1

    1 2 3 5

    S1

    LF

    AF

    S2 S 3

    MU

    Y1 UY1 UY1

    20/PTS/3500/0606/EN

    PTS - Single-Blade Damper

    Installation

    Fasten the damper to the ductwork with, e.g., rivets.

    Ensure that the rivets do not prevent the operation of

    the damper. The position of each rivet must be at least

    10 mm from the duct end.External duct gaskets ensure an airtight joint when the

    damper has been mechanically fastened to the duct

    with rivets or screws.

    The electric actuator (where applicable) is to be

    connected to the power supply and control signal

    wires according to the wiring diagram. Examples of

    connections for the standard actuators are shown in a

    separate diagram.

    The electric actuator can also be installed, when

    necessary, in an on-site procedure with the help of an

    actuator platform and universal shaft fitting, available

    as an accessory:

    Remove the operating mechanism (1) by opening the

    locking screw.

    Assemble the actuator platform in the location of

    the operation mechanism (2) and ensure its stability

    mechanically by bending the legs of the actuator

    platform with a hand tool.

    The universal actuator fitting enables connection of

    most actuator types to the shaft (3) (4).

    Wire connections are to be performed according to

    the instruction for the actuator installed.

    Electric wire connections

    Belimo

  • 8/10/2019 Airflow Dampers En

    20/4427

    PTS/A-100 PTS/A-125

    PTS/A-160 PTS/A-200

    PTS - Single-Blade Damper

    20/PTS/3500/0606/EN

    Pressure drop and sound data

  • 8/10/2019 Airflow Dampers En

    21/4428

    PTS/A-250 PTS/A-315

    PTS/A-400 PTS/A-500

    20/PTS/3500/0606/EN

    PTS - Single-Blade Damper

    Pressure drop and sound data

  • 8/10/2019 Airflow Dampers En

    22/4429

    PTS/B-100 PTS/B-125

    PTS/B-160 PTS/B-200

    PTS - Single-Blade Damper

    20/PTS/3500/0606/EN

    Pressure drop and sound data

  • 8/10/2019 Airflow Dampers En

    23/4430

    PTS/B-250 PTS/B-315

    PTS/B-400 PTS/B-500

    20/PTS/3500/0606/EN

    PTS - Single-Blade Damper

    Pressure drop and sound data

  • 8/10/2019 Airflow Dampers En

    24/4431

    PTS/C-100 PTS/C-125

    PTS/C-160 PTS/C-200

    PTS - Single-Blade Damper

    20/PTS/3500/0606/EN

    Pressure drop and sound data

  • 8/10/2019 Airflow Dampers En

    25/4432

    PTS/C-250 PTS/C-315

    PTS/C-400 PTS/C-500

    20/PTS/3500/0606/EN

    PTS - Single-Blade Damper

    Pressure drop and sound data

  • 8/10/2019 Airflow Dampers En

    26/4433

    PTS - Single-Blade Damper

    20/PTS/3500/0606/EN

    Suggested specifications

    The casing and circular (perforated) blade of the shut-

    off / adjustment / control damper shall be made of

    galvanised steel.

    The shut-off damper shall meet EN 1751, Class 4

    tightness requirements.

    External rubber gaskets on the spigot shall provide an

    airtight connection to circular ductwork.

    Product code

    PTS/S-D

    S = Version

    A Damper with blade gasket

    B Damper without blade gasket

    C Damper with perforated blade

    D = Diameter of duct connection

    100, 125, 160, 200, 250, 315, 400, 500

    Specifics and accessories

    MA = Material

    CS Steel

    MO = Actuator type

    NA Manual=default

    B1 LM24A-F, 5 Nm, 24 VAC/VDC, on-off

    B2 LM230A-F, 5 Nm, 230 VAC, on-off

    B3 LM24A-SR-F, 5 Nm, 24 VAC/VDC,

    modulating

    B4 NM24A, 10 Nm, 24 VAC/VDC, on-off

    B5 NM230A, 10 Nm, 230 VAC, on-off

    B6 NM24A-SR, 10 Nm, 24 VAC/VDC,

    modulating

    B7 LF24, 4 Nm, 24 VAC/VDC, on-off,

    spring return

    B8 LF230, 4 Nm, 230 VAC, on-off, spring

    return

    AC = Accessories

    BA Handle for manual operation

    ML Actuator platform, low

    MH Actuator platform, high

    IL Installation kit for actuator, low

    IH Installation kit for actuator, high

    IJ Actuator platform; low for LF actuator

    Code example

    PTS/A-100, MA=CS,MO=NA

  • 8/10/2019 Airflow Dampers En

    27/4434

    20/RMC/3500/0606/EN

    RMC - Constant Airflow Damper

    RMC

    Constant Airflow Damper

    Constant airflow damper without external power

    supply, self-balancing operation

    Effective commissioning

    Large operation area, pressure range of 50...600 Pa

    and optionally up to 1000 Pa

    Galvanised steel design

    Product models

    Models with and without insulated casing

    MATERIAL

    PART MATERIAL

    Housing Galvanised steel

    Damper blade Aluminium

    Damper blade

    bearings PTFE

    Tube for the

    adjustment Plastic

    Ring seals Rubber

    QUICK SELECTION

    D qmin qmin(recommend) qmax

    [mm] [l/s] [m3/h] [l/s] [m3/h] [l/s] [m3/h]

    100 19 70 31 113 61 220

    125 28 100 49 177 78 280

    160 50 180 80 290 139 500

    200 69 250 126 452 250 900

    250 139 500 196 707 417 1500

    315 222 800 312 1122 611 2200

    350 278 1000 503 1810 1056 3800

    qmin Minimum airflow

    qmin(recommend) Recommmende minimum airflow at 50Pa

    minimum unit pressure loss

    qmax Maximum airflow

  • 8/10/2019 Airflow Dampers En

    28/4435

    D

    70

    L1 L L1

    NS L L1 D

    100 170 40 99

    125 170 40 124

    160 240 40 159

    200 240 40 199

    250 240 40 249315 220 60 314

    400 295 60 399

    D

    70

    LL1 L1

    50

    RMC - Constant Airflow Damper

    20/RMC/3500/0606/EN

    DIMENSIONS

    RMC/A

    RMC/AI

    PRODUCT MODELS

    PRODUCT MODEL CODE DESCRIPTION

    External insulation I Mineral wool, thickness 50 mm, for sound insulation and reduction of

    heat transfer

    Standard N No insulation

  • 8/10/2019 Airflow Dampers En

    29/4436

    P1

    P1 qV1

    V1

    P2 = P1 + (P2 - P1)

    P2 qv2 = qV1

    V2

    250

    200

    150

    Pa

    100

    50

    2 3 4 5 6 7 8 9 10 11

    v=m s

    100

    100 200 300

    125

    100 200 300 400

    160

    200 400 600 800

    200

    400 600 800 1000 1200

    250

    500 1000 1500 2000

    315

    600 1000 1500 2000 2500 3000

    400

    1000 2000 3000 4000 5000

    m3/h

    20/RMC/3500/0606/EN

    RMC - Constant Airflow Damper

    Function

    Constant airflow damper RMC is an independent

    control element operating without an external power

    supply, maintaining the required airflow rate regardless

    of upstream pressure changes. Consequently, system

    balancing is not needed.

    As the dynamic pressure in the duct branch increases,

    the damper turns, thus increasing the pressure loss

    and preventing an excessive increase in the airflow

    rate. Similarly, as the dynamic pressure increases, the

    spring returns the blade to the open position, reducing

    the pressure loss and thus maintaining a constant

    airflow rate.

    The constant airflow damper includes a damper

    blade, supported by bearings and connected to

    an adjustment spring. As a result of the balance

    between aerodynamic forces and the spring effect,

    the necessary throttling effect is achieved and the set

    airflow rate is achieved.

    Operation range

    The constant airflow damper operates from a

    minimum pressure difference over the unit, which

    depends on the air velocity (see diagram below) to a

    maximum pressure difference of 1000 Pa.

    For example, if air velocity in duct is 7 m/s, the unit

    pressure loss is approximately 100 Pa or above.

  • 8/10/2019 Airflow Dampers En

    30/4437

    RMC/N-100 RMC/N-125

    RMC/N-160 RMC/N-200

    RMC - Constant Airflow Damper

    20/RMC/3500/0606/EN

    Pressure drop and sound data

  • 8/10/2019 Airflow Dampers En

    31/4438

    RMC/N-250 RMC/N-315

    RMC/N-400

    20/RMC/3500/0606/EN

    RMC - Constant Airflow Damper

    Pressure drop and sound data

  • 8/10/2019 Airflow Dampers En

    32/4439

    D V (m/s)qv qv 65 Pa 100 Pa 250 Pa 500 Pa

    mm m3/h l/s 63 125 250 500 1k 2k 4k 8k Lp(A ) 63 125 250 500 1k 2k 4k 8k Lp(A ) 63 125 250 500 1k 2k 4k 8k Lp(A ) 63 125 250 500 1k 2k 4k 8k Lp(A )

    100 2 ,4 68 19 39 3 7 35 3 2 30 3 1 25 2 4 31 40 3 9 38 3 6 35 3 6 30 2 9 36 43 45 4 6 46 4 7 49 4 4 43 4 9 49 5 2 52 5 3 54 5 5 50 5 0 55

    3,6 101 28 43 4 1 39 3 6 34 3 4 28 2 7 34 46 4 4 42 3 9 38 3 8 32 3 1 38 52 5 2 50 4 9 49 4 9 43 4 2 49 55 5 6 55 5 5 56 5 7 52 5 1 57

    5,2 148 4 1 47 4 5 42 3 9 38 3 8 31 3 1 38 51 4 9 46 4 3 42 4 1 35 3 4 41 60 5 9 55 5 3 51 5 0 45 4 3 51 62 6 2 60 5 9 58 5 8 54 5 2 59

    7,8 220 6 1 51 4 8 45 4 3 41 4 3 36 3 6 42 55 5 3 50 4 8 46 4 6 40 3 9 46 65 6 6 61 6 1 57 5 5 52 4 8 57 74 72 6 9 67 6 4 60 5 8 54 6 3

    125 2 ,3 101 28 39 3 6 34 3 0 29 3 0 24 2 3 30 41 4 0 38 3 6 35 3 6 30 2 9 36 45 4 7 47 4 8 48 4 9 44 4 3 49 52 5 4 54 5 4 55 5 6 50 4 9 56

    3,2 140 3 9 44 4 1 38 3 4 33 3 2 26 2 4 33 46 4 5 42 3 9 38 3 8 32 3 1 38 50 5 1 50 5 0 50 5 0 45 4 4 50 57 5 8 57 5 6 56 5 7 51 5 1 57

    4,5 198 5 5 49 4 6 43 3 8 37 3 5 29 2 7 36 51 4 9 46 4 3 41 4 1 35 3 3 41 56 5 5 54 5 1 51 5 1 46 4 5 52 61 6 1 59 5 8 57 5 8 53 5 2 59

    6,4 281 7 8 49 4 9 46 4 3 40 4 1 35 3 2 41 54 5 3 50 4 7 45 4 5 39 3 7 45 63 6 1 58 5 5 54 5 3 47 4 6 54 64 6 4 62 6 1 61 6 2 57 5 6 62

    160 2 ,5 180 5 0 41 3 9 36 3 4 32 3 2 26 2 5 33 44 4 3 41 3 9 38 3 8 32 3 1 39 48 5 0 50 5 0 50 5 1 46 4 5 51 55 5 7 57 5 7 57 5 8 53 5 1 58

    3,5 252 7 0 45 4 3 40 3 7 36 3 5 29 2 7 36 49 4 7 45 4 2 41 4 0 34 3 3 41 55 5 5 53 5 2 51 5 1 45 4 4 51 60 6 1 60 5 9 59 5 9 54 5 3 60

    4,9 353 9 8 49 4 7 44 4 0 39 3 8 32 3 0 39 53 5 1 48 4 4 43 4 2 36 3 4 44 62 6 0 56 5 3 51 5 1 44 4 3 52 65 6 5 62 6 0 60 6 0 55 5 4 61

    6,9 500 139 5 2 50 4 7 44 4 2 43 3 5 34 4 3 57 5 5 52 4 9 47 4 7 40 3 9 48 66 6 4 61 5 8 56 5 5 49 4 8 56 72 7 0 67 6 4 62 6 2 56 5 4 63

    200 2,2 248 6 9 42 3 8 36 3 3 32 3 1 25 2 4 32 45 4 3 41 3 9 38 3 7 31 3 0 38 51 5 2 52 5 1 51 5 1 45 4 4 52 57 5 9 58 5 8 57 5 8 52 5 0 58

    3,4 382 106 4 6 44 4 1 37 3 6 35 2 9 28 3 6 50 4 8 46 4 3 41 4 1 34 3 3 42 58 5 7 55 5 3 52 5 2 46 4 5 53 62 6 3 61 6 0 60 6 0 54 5 3 61

    5,2 583 1 62 5 0 48 4 6 42 4 0 40 3 3 32 4 1 55 5 3 50 4 6 44 4 4 37 3 6 45 64 6 2 58 5 5 53 5 3 46 4 5 54 66 6 6 64 6 2 62 6 2 56 5 6 63

    8,0 900 250 5 4 52 4 8 45 4 4 44 4 0 36 4 5 59 5 7 54 5 1 49 4 9 44 4 1 50 68 6 6 63 6 0 58 5 8 52 5 0 59 75 7 3 70 6 7 65 6 5 58 5 7 66

    250 2 ,8 500 139 4 6 43 4 0 37 3 5 35 2 9 28 3 6 48 4 7 45 4 3 41 4 1 35 3 4 42 54 5 6 55 5 5 54 5 5 49 4 8 56 61 6 2 62 6 1 61 6 2 56 5 4 63

    4,1 720 2 00 48 4 7 44 4 1 39 3 8 32 3 1 40 53 5 1 49 4 6 44 4 4 37 3 6 45 60 6 0 58 5 6 55 5 5 48 4 7 56 65 6 5 65 6 3 63 6 3 58 5 6 645,8 1033 287 5 2 50 4 7 44 4 2 41 3 4 33 4 3 57 5 5 52 5 0 47 4 7 40 3 9 48 66 6 4 61 5 8 56 5 6 49 4 8 57 70 6 9 68 6 5 64 6 4 59 5 8 66

    8,5 1501 417 5 6 55 5 2 51 4 7 49 4 0 41 4 9 61 5 9 56 5 4 51 5 2 44 4 4 53 70 6 8 65 6 2 60 6 0 53 5 2 61 77 7 5 72 6 8 67 6 6 60 5 8 68

    315 2 ,8 799 2 22 4 6 44 4 1 38 4 0 37 2 9 27 3 9 50 4 9 46 4 4 43 4 3 36 3 4 44 57 5 8 57 5 6 50 5 6 50 4 8 56 63 6 5 64 6 3 63 6 3 57 5 5 64

    4,3 1210 336 5 2 50 4 7 43 4 2 40 3 4 32 4 2 55 5 4 51 4 7 45 4 5 38 3 6 46 64 6 3 59 5 7 54 5 4 48 4 6 56 68 6 8 66 6 5 64 6 4 58 5 7 65

    6,5 1829 508 5 6 54 4 9 46 4 4 43 3 7 35 4 5 61 5 9 54 5 1 49 4 8 42 4 0 50 69 6 7 63 6 0 58 5 7 51 4 9 59 74 73 7 0 67 6 6 65 5 9 58 6 7

    10,0 2801 778 5 9 58 56 54 5 0 4 9 43 4 4 5 1 64 62 60 57 54 5 3 4 7 47 5 5 73 7 1 6 8 65 63 62 5 6 5 5 64 80 7 8 74 71 70 69 63 6 1 7 1

    400 2 ,2 1001 278 4 7 43 39 35 3 4 3 3 26 2 4 3 5 50 48 45 42 41 4 0 3 3 31 4 2 58 5 9 5 7 56 55 54 4 7 4 5 56 65 6 5 6 4 62 61 61 54 5 1 6 2

    3,6 1642 456 5 1 49 4 5 42 4 0 39 3 2 30 4 1 55 5 3 49 4 6 45 4 4 37 3 5 46 64 6 3 60 5 7 55 5 4 48 4 6 56 69 6 9 67 6 5 64 6 4 57 5 5 65

    6,0 2700 750 6 1 59 5 5 53 5 1 50 4 3 41 5 2 64 6 2 58 5 5 53 5 2 45 4 3 54 69 6 7 63 6 0 58 5 7 51 4 9 59 76 74 71 6 9 67 6 6 61 5 8 69

    9,9 4500 1250 79 78 74 71 6 9 6 8 62 6 0 7 0 78 76 72 69 67 6 6 6 0 58 6 8 75 7 3 6 9 66 64 63 5 7 5 5 65 85 8 1 8 0 76 73 70 67 6 2 74

    D V (m/s)qv qv 65 Pa 100 Pa 250 Pa 500 Pa

    mm m3/h l/s 63 125 250 500 1k 2k 4k 8k Lp(A ) 63 125 250 500 1k 2k 4k 8k Lp(A ) 63 125 250 500 1k 2k 4k 8k Lp(A ) 63 125 250 500 1k 2k 4k 8k Lp(A )

    100 2,4 68 19 5 5 5 10 14 19 14 14 17 6 7 8 14 19 24 19 19 23 9 13 16 24 31 37 33 33 37 15 20 22 31 38 43 39 40 43

    3,6 101 2 8 9 9 9 14 18 2 2 17 17 2 1 12 12 12 17 22 26 21 21 26 18 20 20 27 33 37 32 32 37 21 24 25 33 40 45 41 41 45

    5,2 148 4 1 13 1 3 12 1 7 22 2 6 20 2 1 25 17 1 7 16 2 1 26 2 9 24 2 4 29 26 2 7 25 3 1 35 3 8 34 3 3 38 28 3 0 30 3 7 42 4 6 43 4 2 47

    7,8 220 6 1 17 1 6 15 2 1 25 3 1 25 2 6 29 21 2 1 20 2 6 30 3 4 29 2 9 34 31 3 4 31 3 9 41 4 3 41 3 8 44 40 4 0 39 4 5 48 4 8 47 4 4 50

    125 2,3 101 28 10 7 3 6 8 11 9 12 13 12 11 7 12 14 17 15 18 19 16 18 16 24 27 30 29 32 32 23 25 23 30 34 37 35 38 39

    3,2 140 3 9 15 1 2 7 10 1 2 13 11 13 1 5 17 1 6 11 15 1 7 19 1 7 20 2 1 21 22 19 26 2 9 31 3 0 33 3 3 28 2 9 26 3 2 35 3 8 36 4 0 40

    4,5 198 5 5 20 1 7 12 1 4 16 1 6 14 16 1 8 22 2 0 15 19 20 2 2 20 2 2 24 27 2 6 23 2 7 30 3 2 31 3 4 35 32 3 2 28 3 4 36 3 9 38 4 1 41

    6,4 281 7 8 20 2 0 15 19 19 22 2 0 21 2 4 25 2 4 19 23 2 4 26 2 4 26 2 8 34 3 2 27 3 1 33 3 4 32 3 5 36 35 3 5 31 3 7 40 4 3 42 4 5 45

    160 2 ,5 180 5 0 18 1 6 16 1 6 21 2 2 17 1 7 23 21 2 0 21 2 1 27 2 8 23 2 3 29 25 2 7 30 3 2 39 4 1 37 3 7 42 32 3 4 37 3 9 46 4 8 44 4 3 48

    3,5 252 7 0 22 2 0 20 19 25 2 5 20 19 26 26 2 4 25 2 4 30 3 0 25 2 5 31 32 3 2 33 3 4 40 4 1 36 3 6 41 37 3 8 40 4 1 48 4 9 45 4 5 50

    4,9 353 9 8 26 2 4 24 2 2 28 2 8 23 2 2 29 30 2 8 28 2 6 32 3 2 27 2 6 33 39 3 7 36 3 5 40 4 1 35 3 5 42 42 4 2 42 4 2 49 5 0 46 4 6 51

    6,9 500 139 2 9 2 7 27 26 3 1 3 3 26 2 6 3 3 34 32 32 31 36 3 7 3 1 31 3 7 43 4 1 4 1 40 45 45 4 0 4 0 46 49 4 7 4 7 46 51 52 47 4 6 5 3

    200 2,2 248 6 9 20 19 20 1 7 17 2 0 16 1 6 20 23 2 4 25 2 3 23 2 6 22 2 2 27 29 3 3 36 3 5 36 4 0 36 3 6 40 35 4 0 42 4 2 42 4 7 43 4 2 47

    3,4 382 106 2 4 25 2 5 21 2 1 24 2 0 20 2 5 28 2 9 30 2 7 26 3 0 25 2 5 30 36 3 8 39 3 7 37 4 1 37 3 7 41 40 4 4 45 4 4 45 4 9 45 4 5 495,2 583 1 62 2 8 29 3 0 26 2 5 29 2 4 24 2 9 33 3 4 34 3 0 29 3 3 28 2 8 34 42 4 3 42 3 9 38 4 2 37 3 7 43 44 4 7 48 4 6 47 5 1 47 4 8 52

    8,0 900 250 3 2 33 3 2 29 2 9 33 3 1 28 3 4 37 3 8 38 3 5 34 3 8 35 3 3 39 46 4 7 47 4 4 43 4 7 43 4 2 48 53 5 4 54 5 1 50 5 4 49 4 9 54

    250 2 ,8 500 139 2 7 27 2 7 25 2 3 25 2 0 20 2 6 29 3 1 32 3 1 29 3 1 26 2 6 32 35 4 0 42 4 3 42 4 5 40 4 0 46 42 4 6 49 4 9 49 5 2 47 4 6 52

    4,1 720 2 00 29 3 1 31 2 9 27 2 8 23 2 3 30 34 3 5 36 3 4 32 3 4 28 2 8 35 41 4 4 45 4 4 43 4 5 39 3 9 46 46 4 9 52 5 1 51 5 3 49 4 8 54

    5,8 1033 287 3 3 34 34 32 3 0 3 1 25 2 5 3 4 38 39 39 38 35 3 7 3 1 31 3 8 47 4 8 4 8 46 44 46 4 0 4 0 47 51 5 3 5 5 53 52 54 50 5 0 5 5

    8,5 1501 417 3 7 39 3 9 39 3 5 39 3 1 33 3 9 42 4 3 43 4 2 39 4 2 35 3 6 43 51 5 2 52 5 0 48 5 0 44 4 4 51 58 5 9 59 5 6 55 5 6 51 5 0 57

    315 2 ,8 799 2 22 2 8 30 2 9 25 2 9 26 2 1 19 29 32 3 5 34 3 1 32 3 2 28 2 6 34 39 4 4 45 4 3 39 4 5 42 4 0 46 45 5 1 52 5 0 52 5 2 49 4 7 54

    4,3 1210 336 3 4 36 3 5 30 3 1 29 2 6 24 3 2 37 4 0 39 3 4 34 3 4 30 2 8 36 46 4 9 47 4 4 43 4 3 40 3 8 45 50 5 4 54 5 2 53 5 3 50 4 9 55

    6,5 1829 508 3 8 40 3 7 33 3 3 32 2 9 27 3 5 43 4 5 42 3 8 38 3 7 34 3 2 40 51 5 3 51 4 7 47 4 6 43 4 1 49 56 5 9 58 5 4 55 5 4 51 5 0 56

    10,0 2801 778 4 1 44 44 41 3 9 3 8 35 3 6 4 1 46 48 48 44 43 4 2 3 9 39 4 5 55 5 7 5 6 52 52 51 4 8 4 7 54 62 6 4 6 2 58 59 58 55 5 3 6 0

    400 2 ,2 1001 278 3 0 32 29 25 2 4 2 4 19 18 27 33 37 35 32 31 3 1 2 6 25 3 3 41 4 8 4 7 46 45 45 4 0 3 9 47 48 5 4 5 4 52 51 52 47 4 5 5 3

    3,6 1642 456 3 4 38 3 5 32 3 0 30 2 5 24 3 2 38 4 2 39 3 6 35 3 5 30 2 9 37 47 5 2 50 4 7 45 4 5 41 4 0 47 52 5 8 57 5 5 54 5 5 50 4 9 56

    6,0 2700 750 4 4 48 4 5 43 4 1 41 3 6 35 4 3 47 5 1 48 4 5 43 4 3 38 3 7 45 52 5 6 53 5 0 48 4 8 44 4 3 50 59 6 3 61 5 9 57 5 7 54 5 2 60

    9 ,9 4 50 0 1 25 0 6 2 6 7 6 4 6 1 59 5 9 55 5 4 60 61 65 62 59 57 5 7 53 5 2 59 58 6 2 59 56 54 54 5 0 49 5 7 68 7 0 70 6 6 63 61 60 5 6 66

    RMC - Constant Airflow Damper

    20/RMC/3500/0606/EN

    SOUND LEVEL DATA

    RMC/N AIRBORNE SOUND

    RMC/N RADIATED SOUND

  • 8/10/2019 Airflow Dampers En

    33/44

  • 8/10/2019 Airflow Dampers En

    34/4441

    RMC

    RMC

    >3xD

    RMC - Constant Airflow Damper

    20/RMC/3500/0606/EN

    Installation

    Safety distances for the damper

    The airflow control damper should be installed in

    undisturbed airflow. The airflow velocity profile in the

    duct should be sufficiently even, without disturbances

    caused by bends, T-branches etc.

    The necessary safety distance after a bend or a T-

    branch is 3 x the duct diameter.

    The airflow control damper should be installed so that

    the arrow on the damper corresponds to the direction

    of the airflow. See the installation examples.

    Suggested specifications

    The constant airflow damper shall operate without an

    electric or pneumatic external power supply.

    The damper casing shall be made of galvanised steel

    and the blade of aluminium.

    The damper shall operate with an adjustable spring.

    Dampers shall be factory-set to the required airflow

    rate.

    The damper with a manual adjustment device shall be

    able to be easily set or reset on the work site, during

    commissioning.

    The damper casing shall be insulated with mineral

    wool as sound and heat insulation material (optional).

    Product code

    RMC/S-D

    S = Model

    N Standard, without insulation

    I Casing with 50 mm insulation

    D = Diameter of duct connection

    100, 125, 160, 200, 250, 315, 400

    Code example

    RMC/A-100

  • 8/10/2019 Airflow Dampers En

    35/44

  • 8/10/2019 Airflow Dampers En

    36/4443

    UTK/UTS/UTT - Multi-blade Damper

    20/UTK,U

    TS,U

    TT/3500/0606/EN

    MATERIAL UTK

    PART MATERIAL NOTE

    Casing Galvanised steel Stainless steel AISI 316 also available

    Blades (envelope design) Galvanised steel Stainless steel AISI 316 also available

    Damper blade gaskets Silicon Heat-proof model: EPDM rubber

    Duct gasket Rubber compound Circular connections

    Slide bearings Alloy of polyamide and molybdenum

    sulphide

    Self-lubricated Heat-proof model stainless steel AISI 316

    Drive shaft Galvanised steel Rectangular (15x15 mm) bar

    MATERIAL UTS

    PART MATERIAL NOTE

    Casing Galvanised steel Stainless steel AISI 316 also available

    Blades (envelope design) Galvanised steel Stainless steel AISI 316 also available

    Damper blade gaskets Silicon Heat-proof model: EPDM rubber

    Gasket ins ide the casing Si li conDuct gasket Rubber compound Circular connections

    Slide bearings Alloy of polyamide and molybdenum

    sulphide

    Self-lubricated Heat-proof model stainless steel AISI 316

    Drive shaft Galvanised steel Rectangular (15x15 mm) bar

    MATERIAL UTT

    PART MATERIAL NOTE

    Casing Galvanised steel Stainless steel AISI 316 also available

    Blades (sandwich design) Galvanised steel Stainless steel AISI 316 also available

    Damper blade insulation Polyurethane CFC free

    Damper blade gaskets Silicon Heat-proof model: EPDM rubber

    Gasket inside the casing Silicon Fixed in an aluminium profile

    Duct gasket Rubber compound Circular connections

    Slide bearings Alloy of polyamide and molybdenum

    sulphide

    Self-lubricated Heat-proof model stainless steel AISI 316

    Drive shaft Galvanised steel Rectangular (15x15 mm) bar

    QUICK SELECTION

    HxW qmin qmax

    [mm] [l/s] [m3/h] [l/s ] [m3/h]

    200x400 160 576 480 1728

    400x400 320 1152 960 3456

    400x800 640 2304 1920 6912

    800x800 1280 4608 3840 13824

    1000x1000 2000 7200 6000 21600

    1000x2000 4000 14400 12000 43200

    qmin 1 m/s duct velocity

    qmax 6 m/s duct velocity - recommended maximum airflow for

    comfort applications

  • 8/10/2019 Airflow Dampers En

    37/4444

    H+44

    W+44

    W+4

    H+4

    210

    15x15

    90

    W H

    100,200,...,240 0 10 0,20 0,...,240 0

    H+44

    W+44

    W+4

    H+4

    210

    D

    15x15

    90

    67

    CT=D1; CT=D2

    D WxH

    100 150x150

    125 150x150160 200x200

    200 200x200

    250 250x250

    315 300x300

    400 400x400

    500 500x500

    630 600x600

    800 800x800

    1000 1000x1000

    1250 1250X1250

    20/UTK,U

    TS,U

    TT/3500/0606/EN

    UTK/UTS/UTT - Multi-blade Damper

    DIMENSIONS

    Models with circular connections

    Product models and Accessories

    The product models MD=I and MD=J have a double

    sheet casing with mineral wool insulation. The

    insulation thickness is 20 mm.

    The damper is available equipped with either manual

    adjustment or actuator operation.

    The adjustment and control arrangement options are:

    ADJUSTMENT & CONTROL OPTIONS CODE NOTE

    Manual handle adjustment MO = MA

    Manual ex tension bar adjus tment AC = BA Handle extens ion arrangement

    Flexible coupling bar AC = FS For remote actuator coupling

    Actuator operation MO= See Actuator options

    The damper actuator is selected from the list

    below according to the operating voltage, control

    arrangement and the required torque of the damper.

    The torque of the selected actuator can be higher than

    the required torque of the damper.

  • 8/10/2019 Airflow Dampers En

    38/44

  • 8/10/2019 Airflow Dampers En

    39/4446

    400

    600

    800

    1000

    1200

    1400

    1800

    2000

    2200

    2400

    H ( mm)

    1600

    2400

    2200

    2000

    1800

    1600

    1400

    1200

    1000

    800

    600

    400

    B ( mm)

    2 3 5 10 20 30 50

    0 Pa

    500 Pa

    1000 Pa

    Mv -max =50 NmMv(Nm)

    Pst(Pa)

    250 Pa

    20/UTK,U

    TS,U

    TT/3500/0606/EN

    UTK/UTS/UTT - Multi-blade Damper

    AF-MODELS

    Torque, damper size ... 15 Nm A

  • 8/10/2019 Airflow Dampers En

    40/4447

    2000

    1000

    500

    200

    100

    50

    1 3 10 30 100 300 500 1000 2000

    4 3 2 1

    DIN 1946/4

    UTT

    UTS

    UTK

    CLASS

    UTK/UTS/UTT - Multi-blade Damper

    20/UTK,U

    TS,U

    TT/3500/0606/EN

    Function

    UTK

    The UTK dampers are used to shut off, adjust or

    control airflow in ductwork in applications where

    damper leakage does not have significant importance.

    In the closed position the UTK damper leakage class is

    1 in accordance with the EN1751 standard.

    UTS

    The UTS dampers are used to shut off or control

    airflow in ductwork.

    In the closed position the UTS damper leakage class is

    2 in accordance with the EN1751 standard.

    UTT

    The UTT dampers are used to shut off or control

    airflow in ductwork where tightness, thermal

    insulation and reliability are important.

    In the closed position the UTT damper leakage class is

    4 in accordance with the EN1751 standard.

    In the open position the blades are turned in the

    direction of flow and do not cause significant pressure

    losses.

    Damper sizes conform with the international standards

    EN 1505, EN1506 and ISO 1707 for rectangular and

    circular ducts.The maximum operation temperature of a standard

    damper is +100C (for optional models +200C).

    Heat transmission of the damper is 6 W/(m2K).

  • 8/10/2019 Airflow Dampers En

    41/44

  • 8/10/2019 Airflow Dampers En

    42/4449

    A[m2] 0,10 0,12 0,25 0,30 0,40 0,50 0,60 1,0 1,6 2,0

    KA /dB -10 -9 -6 -5 -4 -3 -2 0 +2 -3

    f/[Hz] 63 125 250 500 1000 2000 4000 8000

    kok 11 11 9 7 5 3 -4 -10

    l/dB +/-6 +/-6 +/-5 +/-4 +/-3 +/-3 +/-3 +/-3

    UTK/UTS/UTT - Multi-blade Damper

    20/UTK,U

    TS,U

    TT/3500/0606/EN

    Pressure drop and sound data

    Sound power level Lw [dB]

    UTK, UTS, UTT

    Suggested specifications

    The casing and blades shall be made from galvanised

    steel (or stainless steel AISI 316).

    The blade gaskets shall be of silicon (or EPDM-

    rubber).

    The drive shaft socket shall be of galvanised steel with

    self-lubricating slide bearings.

    The bearing shall be made from an alloy of polyamide

    and molybdenum sulphide (or stainless steel AISI 316

    or stainless steel AISI 304 or bronze).

    The damper shall be installed into rectangular

    ductwork in compliance with EN 1751, or in circular

    ducts D=100 ... 1250 mm in accordance with EN 1751.

    UTK: The damper shall meet the tightness

    requirements of EN 1751 class 1.

    UTS: The damper shall meet the tightness

    requirements of EN 1751 class 2.

    UTT: The damper shall meet the tightness

    requirements of EN 1751 class 4.

    The casing of the damper shall meet the tightness

    requirements of EN 1751 class B.

    The damper shall be suitable for either manual

    adjustment or actuator operation.

    The sound power level LWin each octave band iscomputed by adding the corresponding correction

    factor Kokto the sound pressure level in the

    selection chart according to the following equation.

    LW= LPA+ Kok+ KA

    The correction factor Kokis the average of the

    operating area.

  • 8/10/2019 Airflow Dampers En

    43/44

  • 8/10/2019 Airflow Dampers En

    44/44