AirSwitch
8/12/2019 AirSwitch - Catalogue (en)_2005
2/32
8/12/2019 AirSwitch - Catalogue (en)_2005
3/32
8/12/2019 AirSwitch - Catalogue (en)_2005
4/32
2 ABB
8/12/2019 AirSwitch - Catalogue (en)_2005
5/32
3ABB
1
General 4
Operating mechanisms 4
Fuses 6
Fields of application 6
Compliance with Standards 6
Operating temperature 6
Main technical characteristics 6
Insulators 6
Insulating parts 7
Breaking principle 7
Degree of protection 7
Earthing 7
Quality Assurance System 8
Environmental Management System 8
Test laboratory 8
Electrical characteristics 8
DESCRIPTION
8/12/2019 AirSwitch - Catalogue (en)_2005
6/32
4 ABB
1
General
The AirSwitch series of switching and isolatingapparatus consists of medium voltage airinsulated isolators, suitable for use in metal-enclosed switchboards (rotary version) andfor wall-mounting (hinged version).
DESCRIPTION
They are used in secondary distribution substa-tions for supplying lines, power transformers andring networks.
The switchboard rotary isolators are available intwo versions: AM type switch-disconnectors AR and AS type rotary isolators.
The hinged wall-mounted switch-disconnectorsare the GS and IMC types for voltages up to 24 kV.
Operating mechanisms
One of the following operating mechanisms canbe used on the Airswitch isolators, according totheir foreseen use.
Operating mechanism with dependentoperation
This allows manual closing and opening with theoperator deciding the operating speed.
1) Operating mechanism onexceeding dead centre
2) Stored energy operatingmechanism for GS/IMCswitch-disconnector.
8/12/2019 AirSwitch - Catalogue (en)_2005
7/32
5ABB
1
2
Stored energy operating mechanism withindependent operation
This allows rapid manual closing with operationindependent of the operator, obtained by meansof a spring charged over the dead centre.
During the closing operation, a separate spring isautomatically charged which stores the energy foropening.
Isolator opening can be carried out by means of:
operating lever
knob
shunt opening release (applied on the operatingmechanism itself)
release system activated by the fuse striker(even in the case of a single blown fuse).
This type of operating mechanism is normally in-stalled in AM/Y, GS/Y and IMC/Y isolators.
Closing or opening is obtained by activating theoperating lever.Withdrawal of the lever from its coupling is onlypossible after completion of the closing or openingoperation.This type of operating mechanism is installed onAS-AR isolators and on AT earthing switches.
Operating mechanism with independentoperation on exceeding dead centre
This allows rapid manual closing and opening
with operation speed independent of the operator,obtained by means of a single spring. Closing oropening is carried out by charging this spring untilthe dead centre is exceeded.This type of operating mechanism is normallyinstalled in the AM/X, GS/X, and IMC/X isolators.On request, it is available in the version with motoroperator for AM and IMC isolators.
8/12/2019 AirSwitch - Catalogue (en)_2005
8/32
6 ABB
21
DESCRIPTION
Fuses
The isolators can be combined with fuse-holderframes suitable for mounting fuses according toDIN Standards which allow protection of powerand instrument transformers.
Fields of application
The rotary and hinged isolators are used insecondary distribution substations as feederswitching and/or isolating apparatus, fortransformer power supply (in combination
with protection fuses or circuit-breakers), etc.
Compliance with Standards
The Airswitch isolators comply with Italian CEI 17-9/1 (file 1672) Standards, International IEC 60265-1 and CENELEC HD 355.1 S2 Standards.The AM and GS switch-disconnectors are derivedfrom apparatus which has obtained Enel (ItalianElectricity Board) approval.
Operating temperature
The operating characteristics of the Airswitch iso-lators do not alter within a range of ambient tem-peratures from 5 C to + 40 C.
Main technical characteristics
Frame. Thisconsists of press-bent steel sections,welded, galvanised and shaped to make the struc-ture particularly sturdy.
Moving contacts. In the rotary type isolators,the rotating body consists of 3 copper bars,covered with insulating material with finned profile(to increase surface insulating distances).The isolator moving contacts are placed at theend of these bars.
In the hinged isolators, the moving contacts areof the jointed type with double blades; the contactpressure is ensured by special springs and bythe self-tightening action of the moving contactpassed through by current.
Insulators
In the rotary type isolators the three upper insu-lators act as a support for the upper fixed contactsand allow direct fixing of the main busbars.The lower insulators act as a support for the lowerfixed contacts and allow direct connection of themedium voltage cables.
8/12/2019 AirSwitch - Catalogue (en)_2005
9/32
7ABB
1
3 4
The lower insulators of the AM switch-disconnec-tors also incorporate the pistons for the air blastand act as the support for the fixed arcing con-tacts.
In the hinged isolators, apart from being thesupport for the main fixed and arcing contacts,the blowing nozzles and the terminals, the threeupper insulators also incorporate the pistons forthe air blast. The lower insulators support theterminals of the main moving contacts.
Insulating parts
The insulators are made of self-extinguishingepoxy resin or polyester glass, and have a finnedprofile with extended exhaust lines to ensurewithstanding of surface discharges.
Breaking principle
In both the rotary and hinged switch-disconnec-tors, on opening there is compression of the airby means of the pistons contained in the insulatorcylinders. Thanks to the generation of a blast ofcompressed air which comes out through special
1) Insulator prepared for con-nection of the main busbars ofthe switchboard.
2) Detail of the lower insulatorwith piston and blast nozzleof the AM type switch-disconnector.
3) Upper insulator of the GS/IMCswitch-disconnector.
4) Arc extinguishing action by
means of air compression.
nozzles, the arc is cooled and deionised onseparation of the contacts. This means there is agradual increase in the arc resistance which de-termines extinction.The piston movement is synchronised with themovement of the main contacts of the isolator sothat the greatest flow of air is ensured at the mo-ment of contact separation and therefore arc ex-tinction is ensured.
Degree of protection
The frame of the AM and AR/AS rotary isolatorsis constructed so that, when inserted in a switch-board, metallic segregation between the busbarcompartment and the feeder-circuit-breakercompartment is always ensured, with degreeof protection IP20.
Earthing
Contact earthing is carried out by activatingthe earthing switch. Furthermore, in the rotary typeisolators, in the open position, the moving contactsare automatically earthed.
8/12/2019 AirSwitch - Catalogue (en)_2005
10/32
8 ABB
1DESCRIPTION
Quality Assurance System
Complies with ISO 9001 Standards, certified by an independent organisation.
Environmental Management System
Complies with ISO 14001 Standards, certified by an independent organisation.
Test laboratory
Complies with ISO 45001 Standards, accredited by an independent organisation.
Electrical characteristics
Apparatus AM AR/AS GSIMC
Rated voltage [kV] 24 24 24
Withstand voltage towards earth [kV] 50 50 50and between phases (50-60 Hz/1 min)
Withstand voltage between open [kV] 60 60 60contacts (50-60 Hz/1 min)
Impulse withstand voltage towards [kV] 125 125 125earth and between phases
Impulse withstand voltage [kV] 145 145 145between open contacts
Rated frequency [Hz] 50-60 50-60 50-60
Rated normal current [A] 400/630 400/630 400800/1250
Rated short-time withstand [kA] 12.5 12.5 12.5current (1 s) 16 16 16
20 25
Rated making capacity on [kA] 31.5 31.5
short-circuit 40 40Rated breaking capacity Isc
- Mainly active load service [A] 400/630 400
- No-load transformer service [A] 4 ... 16 10
- No-load feeder service [A] 25 16
- No-load cable service [A] 25 16
- Loop circuit service [A] 400/630 400
8/12/2019 AirSwitch - Catalogue (en)_2005
11/32
8/12/2019 AirSwitch - Catalogue (en)_2005
12/32
10 ABB
AMSWITCH-DISCONNECTORS
AM/XA: switch-disconnector with manual operat-ing mechanism on exceeding dead centre,upper earthing switch with operating mecha-nism with dependent operation, interlocked withthe line-side isolator. It is normally used toconstruct incoming units with cable entry frombelow (see fig. 3) (upside-down assembly).
AM/YA: switch-disconnector with manual storedenergy operating mechanism, earthing switchupper with operating mechanism with depend-ent operation, interlocked with the line-side
isolator. It is normally used to construct incomingunits with cable entry from below (see fig. 3)(upside-down assembly).
AM/YFA: switch-disconnector with manual storedenergy operating mechanism, fuse-holder frameand release device for fuse intervention. Upperearthing switch with operating mechanism withdependent operation, interlocked with the line-side isolator. It is normally used to constructtransformer protection units with cable entryfrom below. It can be fitted with shunt openingrelease to carry out connection with the lowvoltage circuit (see fig. 4) (upside-down assem-bly).
AM/XMA: switch-disconnector with motor opera-tor, upper earthing switch with operating mecha-nism with dependent operation, interlocked withthe line-side isolator. It is normally used toconstruct units according to fig. 3.
AM/XMB: switch-disconnector with motor opera-tor, lower earthing switch with operating mecha-nism with dependent operation, interlocked withthe line-side isolator. It is normally used toconstruct units according to fig. 1.
AM type switch-disconnectorsaccording to CEI 17-9/1 andIEC 60265-1 Standards
AM/XB: switch-disconnector with manual operat-ing mechanism on exceeding dead centre,lower earthing switch with operating mechanismwith dependent operation, interlocked with theline-side isolator. It is normally used to constructincoming/outgoing units (see fig. 1). It is alsoavailable in the AM/XD version, with spacedlower earthing switch.
AM/YB: switch-disconnector with manual storedenergy operating mechanism, lower earthingswitch with operating mechanism with depend-ent operation, interlocked with the line-sideisolator. It is normally used to construct incom-ing/outgoing units (see fig. 1). It is also availablein the AM/YD version, with spaced lowerearthing switch.
AM/YFB: switch-disconnector with manual storedenergy operating mechanism, fuse-holder frameand release device for fuse intervention. Lowerearthing switch with operating mechanism with
dependent operation, interlocked with the line-side isolator. It is normally used to constructtransformer protection units and can be fittedwith a shunt opening release to carry outconnection with the low voltage circuit (see fig.2).
Description
The AM series of rotary isolators are available inseveral versions suitable for constructing differenttypes of units. The wide range has three types ofoperating mechanism (on exceeding dead centre,with stored energy, and with motor operator),earthing knives (lower and/or upper always inter-locked with the feeder), fuse-holder frame (suit-able for use with fuses according to DIN Stan-dards and fitted with automatic release device forfuse intervention), standard and upside-down ver-
sions.
8/12/2019 AirSwitch - Catalogue (en)_2005
13/32
8/12/2019 AirSwitch - Catalogue (en)_2005
14/32
12 ABB
AM
AMSWITCH-DISCONNECTORS
(1) Specify the power supplyvoltage 24, 48 V d.c., 110-220 V d.c. /a.c.
Apparatus identification
Switch-disconnectors according to CEI 17-9/1 and IEC 60265-1 Standards
AM/XB 24.04.12
AM/XB 24.04.16
AM/XB 24.06.16
AM/YB 24.04.12
AM/YB 24.04.16AM/YB 24.06.16
AM/YFB 24.04.12
AM/YFB 24.04.16
AM/YFB 24.06.16
AM/XD 24.04.12
AM/XD 24.04.16
AM/XD 24.06.16
AM/YD 24.04.12
AM/YD 24.04.16
AM/YD 24.06.16
AM/XA 24.04.12
AM/XA 24.04.16
AM/XA 24.06.16
AM/YA 24.04.12
AM/YA 24.04.16
AM/YA 24.06.16
AM/YFA 24.04.12
AM/YFA 24.04.16
AM/YFA 24.06.16
AM/XMB 24.04.12 (1)
AM/XMB 24.04.16 (1)
AM/XMB 24.06.16 (1)
AM/XMA 24.04.12 (1)
AM/XMA 24.04.16 (1)
AM/XMA 24.06.16 (1)
U [kV]
24
24
24
24
2424
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
In [A]
400
400
630
400
400630
400
400
630
400
400
630
400
400
630
400
400
630
400
400
630
400
400
630
400
400
630
400
400
630
Icw [kA]
12.5
16
16
12.5
1616
12.5
16
16
12.5
16
16
12.5
16
16
12.5
16
16
12.5
16
16
12.5
16
16
12.5
16
16
12.5
16
16
8/12/2019 AirSwitch - Catalogue (en)_2005
15/32
13ABB
2
AM
1
2 AM
1A 1B
XB
XA
YB
YA
YFB
YFA
XD
YD
Switch-disconnectors approved by Enel
Cubicle Switch-disconnectorStandardised Standardisedtable table U [kV] In [A] I cw [kA]
AM/XU 24.04.12 DY402 DY513 24 400 12.5
AM/XU 24.04.16 DY402 DY513 24 400 16
AM/XU-U 24.04.12 DY404 DY513 24 400 12.5
AM/XU-U 24.04.16 DY404 DY513 24 400 16
AM/XU-UA 24.04.12 DY408 DY513 24 400 12.5
AM/XU-UA 24.04.16 DY408 DY513 24 400 16
AM/XMU 24.04.12 DY406 DY513 24 400 12.5
AM/XMU 24.04.16 DY406 DY513 24 400 16
AM/XMU-T 24.04.12 C.TO 062 C.TO 062 24 400 12.5
AM/XMU-T 24.04.16 C.TO 062 C.TO 062 24 400 16
AM/YU 24.04.12 DY403 DY518 24 400 12.5
AM/YU 24.04.16 DY403 DY518 24 400 16
Key lock
This allows the line-side isolator and/or earthingswitch to be locked in the closed or open position.A maximum of two key locks for the line-side isola-tor and two key locks for the earthing switch oper-ating mechanism can be combined, or otherwise akey lock and an electromagnetic lock.Only one key lock can be combined with the motoroperator.
The possible selections are indicated below.2A One line-side isolator lock (key free in open
position) or earthing switch lock (key free inclosed position)
2B One line-side isolator lock (key free in closedposition) or earthing switch lock (key free inopen position)
2C Two locks (one in open, the other in closedposition)
2D Two line-side isolator locks (keys free in openposition) or earthing switch locks (keys free inclosed position)
2E Two line-side isolator locks (keys free inclosed position) or earthing switch locks(keys free in open position)
Accessories
Voltage signalling device
This device consists of voltage sensors (capacitordividers) and a set of three lamps.It allows the presence of voltage in a particularpoint of the medium voltage circuit to be signalled.Devices with fixed or withdrawable signalling boxand sets of three capacitive insulators - eitherloose or mounted on a metal crosspiece - areavailable.The following combinations are possible.1A Capacitive insulator crosspiece and fixed
signalling box (AM)1B Set of three capacitive insulators and fixedsignalling box (AM).
8/12/2019 AirSwitch - Catalogue (en)_2005
16/32
14 ABB
2
3
AM
3A 3B 3C
XB
XA
YB
YA
YFB
YFA
XD
YD
4
5
AMSWITCH-DISCONNECTORS
2F One electromagnetic lock and one line-sideisolator key lock (electromagnet de-energised,key free in open position) (1)
2G One electromagnetic lock and one earthingswitch key lock (electromagnet de-energised,key free in open position) (1)
2H One electromagnetic lock and one line-sideisolator key lock (electromagnet de-energised,key free in closed position) (1)
2I One electromagnetic lock and one earthingswitch key lock (electromagnet de-energised,key free in closed position) (1)
2L One line-side isolator lock (key free in openposition) for motor operator
2M One earthing switch lock (key free in openposition) for motor operator
2N One earthing switch lock (key free in closedposition) for motor operator.
Door lock
This is a mechanical device which does not allowthe compartment door to be opened with the earth-ing switch open.
The possible solutions are indicated below.
3A Door lock H=720 mm (panels H=1950 mm)
3B Door lock H=870 mm (panels H=2250 mm)
3C Upper door lock H=770 mm
3D Door lock (for Enel type I, TM, U and IE panels)
3E Door lock (for Enel type UA panels).
(1) Specify the power supplyvoltage of the electromag-netic locks: 24, 48, 110, 220V d.c. /a.c.
Auxiliary contacts
These signal the state of the position of the isola-tor: open/closed.The possible solutions are indicated below.4A Auxiliary contacts for line-side isolator (3 clos-
ing + 3 opening)4B Auxiliary contacts for earthing switch (3 clos-
ing + 3 opening).
N.B.: in the AM/XMA types, the auxiliary contactsare always supplied, with a maximum number of
2 closing + 2 opening both for FEEDER and forEARTH.
Shunt opening release (1)
This is an electromechanical device which, follow-ing energisation of an electromagnet, activates therelease lever of the operating mechanism makingthe isolator open. This application is only compat-ible with stored energy operating mechanisms(AM/Y).Shunt opening release with auxiliary contacts ofthe line-side isolator (2 closing contacts + 3 open-ing contacts).
8/12/2019 AirSwitch - Catalogue (en)_2005
17/32
15ABB
3
Description 16
AS and AR rotary isolators 16
AT earthing switches 17
Apparatus identification 18
Accessories 20
AS, ARAND ATISOLATORS
8/12/2019 AirSwitch - Catalogue (en)_2005
18/32
16 ABB
GSSA0356a
GSSA0359a
GSSC0275a
Fig. 8Fig. 7 Fig. 9
Description
AS and AR rotary isolators
The AS and AR series of rotary isolators are avail-able in several versions suitable for constructingdifferent types of units.
The range foresees a manual operating mecha-nism with dependent operation, earthing knives(lower and/or upper always interlocked with thefeeder), fuse-holder frame (suitable for use withfuses according to DIN Standards).
The types available are:
AS/B: AS/B: line-side isolator and lower earthingswitch, interlocked, both with manual operatingmechanism with dependent operation. It isnormally used to construct incoming/outgoingunits (see fig. 7).
AS, ARAND ATISOLATORS
AS/FB: AS/FB: line-side isolator with fuse-holderframe, earthing switch on the load side of thefuse-holder frame, interlocked, both with manualoperating mechanism with dependent operation.It is normally used to construct measuring units(see fig. 8).
AR/D: line-side isolator and spaced earthingswitch lower, interlocked, both with manualoperating mechanism with dependent operation.It is normally used to construct incoming/outgoing units with fixed circuit-breaker (*)
(see fig. 9).It is also available in the AR/DC version to con-struct units with withdrawable circuit-breaker.
AS/D: line-side isolator and lower spacedearthing switch, interlocked, both with manualoperating mechanism with dependent operation.It is normally used to construct incoming/outgoing units.
(*) The use of HD4/R series cir-cuit-breakers, fixed versionwith right lateral operatingmechanism is recommended(see catalogue 649405). Con-nections to the switchboardmust be made by the Cus-
tomer.
8/12/2019 AirSwitch - Catalogue (en)_2005
19/32
17ABB
3
GSSC0337
a
GSSC0337b
Fig. 11Fig. 10
(*) The use of HD4/R series cir-cuit-breakers, fixed versionwith right lateral operatingmechanism is recommended(see catalogue 649405). Con-nections to the switchboardmust be made by the Cus-
tomer.
AS/D+CT kit: line-side isolator and lower spacedearthing switch, interlocked, both with manualoperating mechanism with dependent operation.It is normally used to construct incoming/outgoing units. This isolator is preset for connec-tion to the current transformers (2 CTs / 3 CTs).
ARS/B: this isolator can be used to constructcircuit-breaker units with double isolation(cables/busbars) and cable side isolator(fig. 10) (*).
ARS/BT: this isolator can be used to constructcircuit-breaker units with double isolation(cables/busbars), cable side isolator and currenttransformers (fig. 10) (*).
ARS: this isolator can be used to constructcircuit-breaker units with double isolation(cables/busbars) (fig. 10) (*).
AS/E: this isolator can be used to constructcircuit-breaker units with cable side isolator andbusbar side earthing switch (fig. 11) (*).
AT earthing switches
The AT type isolators are earthing switches with-
out making capacity.They are available in two versions: AT, for 700 mmwide units, and AT/R, for 550 mm wide units.
8/12/2019 AirSwitch - Catalogue (en)_2005
20/32
18 ABB
AS-AR
AS, ARAND ATISOLATORS
Apparatus identification
AS/B 24.04.12
AS/B 24.04.16
AS/B 24.06.16
AS/B 24.08.20
AS/B 24.12.20
AS/B 24.12.25
AS/D 24.04.12
AS/D 24.04.16
AS/D 24.06.16
AS/D 24.08.20
AS/D 24.12.20
AS/D 24.12.25
AS/D 24.04.12 + kit 2TA
AS/D 24.04.16 + kit 2TA
AS/D 24.06.16 + kit 2TA
AS/D 24.08.20 + kit 2TA
AS/D 24.12.20 + kit 2TA
AS/D 24.12.25 + kit 2TA
AS/D 24.04.12 + kit 3TA
AS/D 24.04.16 + kit 3TA
AS/D 24.06.16 + kit 3TA
AS/D 24.08.20 + kit 3TA
AS/D 24.12.20 + kit 3TA
AS/D 24.12.25 + kit 3TA
AS/FB 24.04.12
AS/FB 24.04.16
AS/FB 24.06.16
AS/FB 24.08.20
AS/FB 24.12.20
AS/FB 24.12.20
AR/D 24.04.12
AR/D 24.04.16
AR/D 24.06.16
AR/DC 24.04.12
AR/DC 24.04.16
AR/DC 24.06.16
AR/DC 24.08.20
AR/DC 24.12.20
AR/DC 24.12.25
U [kV]
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
In [A]
400
400
630
800
1250
1250
400
400
630
800
1250
1250
400
400
630
800
1250
1250
400
400
630
800
1250
1250
400
400
630
800
1250
1250
400
400
630
400
400
630
800
1250
1250
Icw [kA]
12.5
16
16
20
20
25
12.5
16
16
20
20
25
12.5
16
16
20
20
25
12.5
16
16
20
20
25
12.5
16
16
20
20
25
12.5
16
16
12.5
16
16
20
20
25
8/12/2019 AirSwitch - Catalogue (en)_2005
21/32
8/12/2019 AirSwitch - Catalogue (en)_2005
22/32
20 ABB
3
1
3
4
2
1A 1B
XS/B
AT
AS/FB
AR/D
AS/D
AS/D + kit TA
AS/E
AS, ARAND ATISOLATORS
(1) Specify the power supplyvoltage of the electromag-netic locks: 24, 48, 110, 220
V d.c. /a.c.
2C Two locks (one in open, the other in closedposition)
2D Two line-side isolator locks (keys free in openposition) or earthing switch locks (keys free inclosed position)
2E Two line-side isolator locks (keys free inclosed position) or earthing switch locks (keysfree in open position)
2F One electromagnetic lock and one line-sideisolator key lock (electromagnet de-energised,key free in open position) (1)
2G One electromagnetic lock and one earthingswitch key lock (electromagnet de-energised,key free in open position) (1)
2H One electromagnetic lock and one line-sideisolator key lock (electromagnet de-energised,key free in closed position) (1)
2I One electromagnetic lock and one earthingswitch key lock (electromagnet de-energised,key free in closed position) (1).
Door lock
This is a mechanical device which does not allowthe compartment door to be opened with theearthing switch open.
The possible solutions are indicated below.
3A Door lock H=720 mm (panels H=1950 mm)
3B Door lock H=870 mm (panels H=2250 mm).
Auxiliary contacts
These signal the state of the position of the isola-tor: open/closed.
The possible solutions are indicated below.
4A Auxiliary contacts for line-side isolator (3 clos-ing + 3 opening)
4B Auxiliary contacts for earthing switch (3 clos-ing + 3 opening).
Key lock
This allows the line-side isolator and/or the earth-ing switch to be locked in the closed or open posi-tion.A maximum of two key locks can be combined forthe operating mechanism of the line-side isolatorand two key locks for the operating mechanism of
the earthing switch, or otherwise one key lock andone electromagnetic lock.
The possible selections are indicated below.
2A One line-side isolator lock (key free in openposition) or earthing switch lock (key free inclosed position)
2B One line-side isolator lock (key free in closedposition) or earthing switch lock (key free inopen position)
Accessories
Voltage signalling device
This device consists of voltage sensors (capacitordividers) and a set of three lamps.It allows the presence of voltage in a particularpoint of the medium voltage circuit to be signalled.Devices with fixed or withdrawable signallingbox and sets of three capacitive insulators - eitherloose or mounted on a metal crosspiece - areavailable.
The following combinations are possible:
1A Capacitive insulator crosspiece and fixedsignalling box.
1B Set of three capacitive insulators and fixedsignalling box
8/12/2019 AirSwitch - Catalogue (en)_2005
23/32
21ABB
4
Description 22
Apparatus identification 22
Accessories 23
Overall dimensions 26
GSAND IMCSWITCH-DISCONNECTORS
8/12/2019 AirSwitch - Catalogue (en)_2005
24/32
8/12/2019 AirSwitch - Catalogue (en)_2005
25/32
23ABB
4
4
6
23
5
5
7
8
1 Crosspiece withcapacitive insulators
This device consists of ametal crosspiece onwhich three voltage sen-sors (capacitor dividers)are installed preset forconnection in a suitabledetection circuit.
The possible combina-tions are indicated below.
1A Crosspiece with capacitive insulators (insula-tors H = 260 mm) (GS)
1B Crosspiece with capacitive insulators (insula-tors H = 215 mm) (GS)
1C Crosspiece with capacitive insulators (insula-tors H = 170 mm) (GS).
Isolator operation
The hinged isolators are mainly used in open sub-stations and are normally placed at a height of 2-4metres.To be able to operate these isolators, it is neces-sary to use a transmission operating mechanismand/or an insulated rod operating mechanism.To be able to construct a transmission operatingmechanism (earth and/or feeder), the followingcomponents are required (see figure on the fol-lowing page).
Back of switchboard or wall operatingplate (2).The wall operating plate is fixed onto the samewall as the isolator at a height easily accessibleto the operator.The switchboard operating plate is fixed to a
wall of the switchboard and allows transmissionof the operation as far as the isolator.
Key lock for operating plate (3).This is a mechanical device which allows theoperating plate to be locked in the open orclosed position.
Operating levers (4) for transmission orinsulated rod operating mechanism.The GS/IMC series of isolators are always pre-set to take both types of operating mechanism.Selection of the type of operating mechanismconsequently implies the type of lever which the
isolator must be fitted with.
Transmission rod (5).This is normally supplied with a diameter of 3/4and a length of three metres. It is used to makethe mechanical connection between the operat-ing plate and the lever for the isolator operatingmechanism. The final length must be set up bythe customer.
Intermediate supports (6).There are two types of intermediate supports,one with a simple lever and one with a 90lever.The intermediate support with simple lever al-
lows the bending moments of the transmissionrod to be discharged, permitting particularly longtransmissions.The 90 intermediate support allows operationof an isolator lying on a surface parallel to theoperating plate.
Feeder shaft support (7).This is used to guide the movement of the shaftextension (8).
Shaft extension with sleeve (8).This allows extended operating mechanismshafts to be made.
Example of transmission operating mechanism
with intermediate support, for wall-mounted iso-
lator with feeder shaft extension.
Accessories
8/12/2019 AirSwitch - Catalogue (en)_2005
26/32
24 ABB
2
3
A - B
C - D
4
A - B
C - D
5
6
7
8
9
GSAND IMCSWITCH-DISCONNECTORS
Operating lever
4A Operating lever with insulated
rod operating mechanism forline-side isolator (GS)
4B Operating lever with insulatedrod operating mechanism forearthing switch (GS)
4C Operating lever with transmis-sion operating mechanism forLINE-SIDE isolator (GS) (1)
4D Operating lever with transmis-sion operating mechanism forEARTHING SWITCH (GS) (1).
Key lock for operating plate
3A Key lock, with different keys, forswitchboard operating plateCQR (GS)
3B Key lock, with same keys, for
switchboard operating plateCQR (GS)
3C Key lock, with different keys, forwall operating plate CPR (GS)
3D Key lock, with same keys, forwall operating plate CPR (GS).
Operating plate
2A CQR switchboard operatingplate for line-side isolator (GS)
2B CQR switchboard operatingplate for earthing switch (GS)
2C CPR wall operating plate forline-side isolator (GS)
2D CPR wall operating plate forearthing switch (GS).
Auxiliary contacts
These signal the state of the positionof the isolator: open/closed (can beconverted from opening contact toclosing contact and vice versa).The possible solutions are indicatedbelow.9A Set of 5 auxiliary contacts for
line-side isolator (GS/IMC)9B Set of 10 auxiliary contacts for
line-side isolator (GS/IMC)9C Set of 5 auxiliary contacts for
earthing switch (GS/IMC)9D Set of 10 auxiliary contacts for
earthing switch (GS/IMC).
Shaft support
This is the operating shaft support ofthe line-side isolator (GS).
Extension for operating shaft
8A Extension with sleeve foroperating shaft of the line-sideisolator (L = 1 m) (GS)
8B Extension with sleeve for operat-ing shaft of the earthing switch (L= 1 m) (GS).
Transmission rod
3/4 transmission rod (L = 3 m) (GS).
Intermediate supports
6A Intermediate support with simple
lever (GS)6B Intermediate support with 90le-
ver (GS).
(1) Automatically supplied if the lever for insulatedrod operating mechanism is not provided.
8/12/2019 AirSwitch - Catalogue (en)_2005
27/32
25ABB
4
10 11
U [V] GS/XB GS/YB GS/YFB IMC/XAU IMC/XBU IMC/YFBU
24 V -
48 V -
110 V -
220 V -
110 V ~
220 V ~
380 V ~
24 V -
48 V -
110 V -
220 V -
110 V ~
220 V ~
380 V ~
Shunt opening release
This is an electromechanical devicewhich, following energisation of anelectromagnet, activates the operat-ing mechanism release lever makingthe isolator open. This application isonly compatible with stored energyoperating mechanisms (GS/IMC ... /Y).N.B. The shunt opening release must al-ways be combined with a set of 5 or 10auxiliary contacts of the line-side isolator(see kit No. 9).
Fuse intervention signalling
This device allows signalling or oneor more fuses and consequent open-ing of the isolator.The possible solutions are indicatedbelow.11A Set of No. 1 microcontact
signalling fuse intervention11B Set of No. 2 microcontacts sig-
nalling fuse intervention.
8/12/2019 AirSwitch - Catalogue (en)_2005
28/32
26 ABB
GS/XB GS/YB IMC/XB IMC/YB
GS/YF... IMC/YF...
[mm] A B C D E F
GS/XB IMC/XB 300 800 1240 65 260 60
GS/YB IMC/YB 300 800 1240 133 265 100
GSAND IMCSWITCH-DISCONNECTORS
Overall dimensions
Note: by moving the pliersappropriately, it is possible tomount fuses with a length =
292 or 367 mm.
8/12/2019 AirSwitch - Catalogue (en)_2005
29/32
27ABB
4
GS/XAU IMC/XAU
GS/XBU IMC/XBU
8/12/2019 AirSwitch - Catalogue (en)_2005
30/32
28 ABB
4
GS/YFBU IMC/YFBU
Note: by moving the pliers appropri-ately, it is possible to mount fuseswith a length = 292 or 367 mm.
GSAND IMCSWITCH-DISCONNECTORS
8/12/2019 AirSwitch - Catalogue (en)_2005
31/32
8/12/2019 AirSwitch - Catalogue (en)_2005
32/32
The data and illustrations are not binding. We reserve the right to make changes in the course of technical development of the product.1YMR601001-en
Publication09.2005
ABB Sp. z o.o.Power Technologies Divisionul. Leszno 5906-300 Przasnysz, PolandPhone: (+48 22) 51 52 838, 51 52 831
(+48 29) 75 33 233, 75 33 240Fax: +48 22 51 52 659, +48 29 75 33 327e-mail: [email protected]
www.abb.com