Upload
danielstanciuemail
View
15
Download
4
Embed Size (px)
DESCRIPTION
MV Insulators
Citation preview
POLYMER BUS-BAR SUPPORTS WITH FLEXIBLE AND RIGID FIXATIONOF ALUMINIUM TUBES AND WIRES
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BARAIZ-10-1L63-4 UHL1-AIZ-10-4L125-4 UHL1
CONDITIONAL DESIGNATION
63-125 - width of current-carrying mounting a bus- bar in mm
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-L...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
AIZ-10-L...-4 UHL1
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
1L,2L,3L - 1,2,3 - horizontal flat bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13 The outdoor application of bus- bar supports AIZ-10-L are used for fixing the flat rigid bus- bars in horizontal position at 10 (20) kV voltage open distribution devices of electric power stations and substations. Comply with GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-10-L are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
Building height H, mm
Weight, kgQuantity / width ofbus- bar mm
Picture
AIZ-10-1L63-4U HL1
AIZ-10-1L80-4U HL1
AIZ-10-1L100-4U HL1
AIZ-10-1L125-4U HL1
AIZ-10-2L63-4U HL1
AIZ-10-2L80-4U HL1
AIZ-10-2L100-4U HL1
AIZ-10-2L125-4U HL1
AIZ-10-3L63-4U HL1
AIZ-10-3L80-4U HL1
AIZ-10-3L100-4U HL1
AIZ-10-3L125-4U HL1
AIZ-10-4L63-4U HL1
AIZ-10-4L80-4U HL1
AIZ-10-4L100-4UHL1
AIZ-10-4L125-4UHL1
1/63
1/80
1/100
1/125
2/63
2/80
2/100
2/125
3/63
3/80
3/100
3/125
4/63
4/80
4/100
4/125
А
А
А
А
C
C
C
C
В
В
В
В
D
D
D
D
318
322
326
328
338
342
346
348
358
362
366
368
378
382
386
388
6,2
6,2
6,3
6,5
6,5
6,5
6,6
6,7
6,7
6,8
6,8
6,9
6,9
7,0
7,0
7,2
Rigid bus- barsupport type
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ10-L...-4 UHL1
H
Рic.В Рic.D
Рic.CРic.А
see table
H
HH
10
12
75
13
nominal voltage, kV10-
292AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBESAIZ-10-P100-4UHL- AIZ-10-P250-4 UHL
30
10
2
30
29
AIZ-10-P...-4 UHL1
31,5
1480
1
127х4 отв. 13
The outdoor application of bus- bar supports AIZ-10-P are used for fixing the box-shaped rigid bus- bars at 10(20) kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231, TS3414-005-59116459-06. The bus- bar supports AIZ-10-P are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.
Building height H, mm
Weight, kgWidth of box ofbus- bar mm
AIZ-10-P100-4 U HL1
AIZ-10-P125-4 U HL1
AIZ-10-P150-4 U HL1
AIZ-10-P175-4 U HL1
AIZ-10-P200-4 U HL1
AIZ-10-P225-4 U HL1
AIZ-10-P250-4 U HL1
100
125
150
175
200
225
250
412
437
462
487
512
537
562
10,60
10,70
10,80
10,95
11,10
11,30
11,50
Rigid bus- barsupport type
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-10-P...-4 UHL1
Ø13
4 hol. Ø159
Ø127
10
12
75
13
Н
CONDITIONAL DESIGNATION
100-250 - width of current-carrying mounting a bus- bar in mm
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-P...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
P - the box-shaped rigid bus- bars
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
127х4 hol. 13
nominal voltage, kV10-
293AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR
FOR THE 10KV CURRENT AIZ-10-1M63-4 UHL1-AIZ-10-3M125-4 UHL1 AIZ-10-М...-4 UHL1
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR AIZ-10-М...-4 UHL1
The outdoor application of bus- bar supports AIZ-10-M are used for fixing the flat rigid bus- bars in vertical position at 10 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-10-M are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
AIZ-10-1M63-4U HL1
AIZ-10-1M80-4U HL1
AIZ-10-1M100-4U HL1
AIZ-10-1M125-4U HL1
AIZ-10-2М63-4U HL1
AIZ-10-2М80-4U HL1
AIZ-10-2М100-4U HL1
AIZ-10-2М125-4U HL1
AIZ-10-3М63-4U HL1
AIZ-10-3М80-4U HL1
AIZ-10-3М100-4 UHL1
AIZ-10-3М125-4U HL1
1/63
1/80
1/100
1/125
2/63
2/80
2/100
2/125
3/63
3/80
3/100
3/125
A
A
A
A
C
C
C
C
В
В
В
В
362
380
400
425
362
380
400
425
362
380
400
425
5,90
5,96
6,09
6,15
5,92
5,98
6,11
6,17
5,94
6,00
6,13
6,19
Рic.C
H
Рic.А
А
Рic.В
Ø13
4 hol. Ø159
Ø127
CONDITIONAL DESIGNATION
69-125 - width of vertical bus-bar in mm.
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-М...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
1M,2M,3M - 1,2,3 - flat vertical bus-bars
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
see table
10
12
75
13
nominal voltage, kV10-
Building height H, mm
Weight, kgQuantity / width ofbus- bar mm
PictureRigid bus- barsupport type
294AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBESAIZ-10-Z-4UHL1 AIZ-10-Z...-4 UHL1
1
POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ-10-Z....-4 UHL1 The outdoor bus- bar supports AIZ-10-Z are used for aluminum tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-10-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request
Building height H, mm
Weight, kgDiameter
of rigid bus-bar tube, mm
Рic.№Diameter
D, мм
AIZ-10-Z30-4U HL1
AIZ-10-Z40-4U HL1
AIZ-10-Z50-4U HL1
AIZ-10-Z70-4U HL1
AIZ-10-Z80-4U HL1
AIZ-10-Z90-4U HL1
AIZ-10-Z100-4U HL1
AIZ-10-Z110-4U HL1
AIZ-10-Z120-4U HL1
AIZ-10-Z130-4U HL1
AIZ-10-Z140-4U HL1
AIZ-10-Z150-4U HL1
AIZ-10-Z170-4U HL1
AIZ-10-Z200-4U HL1
AIZ-10-Z250-4U HL1
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
30/25
40/35
50/45
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
30
40
50
70
80
90
100
110
120
130
140
150
170
200
250
359
359
360
370
378
382
394
400
402
415
420
430
450
470
495
12,8
12,9
13,2
13,5
14,7
15,0
15,2
13,5
14,0
18,0
18,0
19,1
20,2
24,3
30,2
Rigid bus- barsupport type
А
D
Рic.1 Рic.2
Ø13
4 hol. Ø159
Ø127
D
Н
А
CONDITIONAL DESIGNATION
Z -rigid connection of aluminium tubular bus-bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-Z...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
30-250- diameter of aluminium tubular bus-bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
295AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARSAIZ-10-SH50-4UHL- AIZ-10-SH250-4 UHL
AIZ-10-SH...-4 UHL1
The bus- bar supports of outdoor application AIZ-10-SH are used for hinged fastening of tubular rigid bus-bar at 10 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-10-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-10-SH50-4 1
AIZ-10-SH60-4 UHL1
AIZ-10-SH70-4 UHL1
AIZ-10-SH80-4 UHL1
AIZ-10-SH90-4 UHL1
AIZ-10-SH100-4 UHL1
AIZ-10-SH110-4 UHL1
AIZ-10-SH120-4 UHL1
AIZ-10-SH130-4 UHL1
AIZ-10-SH140-4 UHL1
AIZ-10-SH150-4 UHL1
AIZ-10-SH170-4 UHL1
AIZ-10-SH200-4 UHL1
AIZ-10-SH250-4 UHL1
UHL 50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
370
380
405
410
410
415
425
425
435
440
440
460
470
495
15,0
15,0
15,5
16,0
16,4
17,0
17,5
17,5
18,0
18,5
18,7
20,5
22,2
23,9
BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-10-SH...-4 UHL1
А Ø13
4 hol.
А
Ø159
Ø127
H
D
rotationangle
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-SH...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
SH - hinging of aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
Building height H, mm
Weight, kgDiameter
D, ммRigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
296AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTAN AIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
AIZ-10-D50-4U HL1
AIZ-10-D60-4 UHL1
AIZ-10-D70-4 UHL1
AIZ-10-D80-4 UHL1
AIZ-10-D90-4 UHL1
AIZ-10-D100-4 UHL1
AIZ-10-D110-4 UHL1
AIZ-10-D120-4 UHL1
AIZ-10-D130-4 UHL1
AIZ-10-D140-4 UHL1
AIZ-10-D150-4 UHL1
AIZ-10-D170-4 UHL1
AIZ-10-D200-4 UHL1
AIZ-10-D250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF RIGID BUS-BARSAIZ-10-D...-4 UHL1 AIZ-10-D...-4 UHL1
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-10-D...-4 UHL1
The outdoor bus- bar supports AIZ-10-D are used for flexible fitting of aluminium tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-10-D are included in the integrated rigid bus-bar project of substations.
370
380
405
410
410
415
425
425
435
440
440
460
470
495
15,0
15,0
15,5
16,0
16,4
17,0
17,5
17,5
18,0
18,5
18,7
20,5
22,2
23,9
А Ø13
4 hol.
А
Ø159
Ø127
H
D mdirection
ovement
Building height H, mm
Weight, kgDiameter
D, ммRigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-D...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
D-movable fastening of aluminium tubular bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10 -
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
297AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BARAIZ-10-К50-4 UHL1 - AIZ-10-К250-4 UHL1
29
AIZ-10-К...-4 UHL1
The outdoor bus- bar supports AIZ-10-K are used for end fixation of aluminium tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.
AIZ UHL
AIZ-10-К60-4U HL1
AIZ-10-К70-4U HL1
AIZ-10-К80-4U HL1
AIZ-10-К90-4U HL1
AIZ-10-К100-4U HL1
AIZ-10-К110-4U HL1
AIZ-10-К120-4U HL1
AIZ-10-К130-4U HL1
AIZ-10-К140-4U HL1
AIZ-10-К150-4U HL1
AIZ-10-К170-4U HL1
AIZ-10-К200-4U HL1
AIZ-10-К250-4U HL1
-10-К50-4 1 50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
335
338
365
370
370
385
385
390
400
410
440
460
490
495
12,0
12,0
12,1
12,2
12,4
12,7
14,5
14,8
14,9
15,0
15,3
15,5
15,7
15,9
BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ-10-К...-4 UHL1
АØ13
4 hol.А
Ø159
Ø127H
D
8AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-К...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
К - end fastening of aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
Building height H, mm
Weight, kgDiameter
D, ммRigid bus-barsupport type
Diameterof rigid bus-bar
tube, mm
AIZ I UHL
AIZ-10-I60-4U HL1
AIZ-10-I70-4U HL1
AIZ-10-I80-4U HL1
AIZ-10-I90-4U HL1
AIZ-10-I100-4U HL1
AIZ-10-I110-4U HL1
AIZ-10-I120-4U HL1
AIZ-10-I130-4U HL1
AIZ-10-I140-4U HL1
AIZ-10-I150-4U HL1
AIZ-10-I170-4U HL1
AIZ-10-I200-4U HL1
AIZ-10-I250-4U HL1
-10- 50-4 1 50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
18,0
18,0
18,5
19,0
19,4
20,0
20,5
20,5
21,0
21,5
21,7
23,5
25,2
26,9
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBEAIZ-10-I-4UHL1 AIZ-10-I...-4 UHL1 AIZ-10-I...-4 UHL1
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ-10-I...-4 UHL1
The outdoor bus- bar supports AIZ-10-I are used for flexible connection of aluminium tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
Ø13
4 hol.
А
Ø159
Ø127
А
H
SizeL, мм
360
360
400
400
420
420
450
460
460
460
480
500
520
520
370
380
405
410
410
415
425
425
435
440
440
460
470
495
movementdirection
Diameterof rigid bus-bar
tube, mm
Building height H, mm Weight, kg
DiameterD, мм
Rigid bus- barsupport type
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ -10-I...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
I -movable connection of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
299AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
movementdirection
BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBEAIZ-10-Е50-4 UHL1 - AIZ-10-Е250-4 UHL1
29
AIZ-10-Е...-4 UHL1
The outdoor bus- bar supports AIZ-10-E are used for double fixation of aluminium tube with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-E are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ UHL
AIZ-10-Е60-4U HL1
AIZ-10-Е70-4U HL1
AIZ-10-Е80-4U HL1
AIZ-10-Е90-4U HL1
AIZ-10-Е100-4U HL1
AIZ-10-Е110-4U HL1
AIZ-10-Е120-4U HL1
AIZ-10-Е130-4U HL1
AIZ-10-Е140-4U HL1
AIZ-10-Е150-4U HL1
AIZ-10-Е170-4U HL1
AIZ-10-Е200-4U HL1
AIZ-10-Е250-4U HL1
-10-Е50-4 1 50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
360
370
370
378
394
400
400
402
415
430
430
450
470
470
13,0
13,0
13,1
13,2
13,4
13,7
15,5
15,8
15,9
16,0
16,3
16,5
16,7
16,9
BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ-10-Е...-4 UHL1
А Ø13
4 hol.
А
Ø159
Ø127
H
D
10AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-Е...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
Е - double-grip of aluminum tube
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
Diameterof rigid bus-bar
tube, mm
Building height H, mm
Weight, kgDiameter
D, ммRigid bus- barsupport type
AIZ
AIZ-10-С60-4U HL1
AIZ-10-С70-4U HL1
AIZ-10-С80-4U HL1
AIZ-10-С90-4U HL1
AIZ-10-С100-4U HL1
AIZ-10-С110-4U HL1
AIZ-10-С120-4U HL1
AIZ-10-С130-4U HL1
AIZ-10-С140-4U HL1
AIZ-10-С150-4U HL1
AIZ-10-С170-4U HL1
AIZ-10-С200-4U HL1
AIZ-10-С250-4U HL1
-10-С50-4 UHL1 50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
620
630
655
660
660
665
675
685
685
690
690
710
740
780
30,5
31,6
32,0
33,0
34,2
35,0
35,5
47,0
40,0
41,0
42,0
45,0
111,0
119,0
BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBESAIZ-10-S...-4 UHL1 AIZ-10-S...-4 UHL1
BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ-10-S...-4 UHL1
The outdoor bus- bar supports AIZ-10-S are used for installation of two aluminium tubes with 10 kV voltage on opened distribution devices of electric power stations and substations.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-S are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Please indicate and fill data sheet if it is necessary to install tubes with different diameter.The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.
870
870
870
870
870
870
870
870
870
870
870
870
870
870
D
А
Ø134 hol.
АØ159
Ø127
H
L
Installation choices for bus- bar. The arrows indicate the axis of the aluminum tubes of rigid bus- bar.
Building height H, mm
Weight, kgDiameter
D, ммRigid bus- barsupport type
Diameter of rigid bus-bar
tube, mm
SizeL, мм
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ -10-C...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
S - for the installation of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
nominal voltage, kV10-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
2911AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
movementdirection
movementdirection
29
AIZ-10-GL...-4 UHL1
12
L HNumber
flexible wires bus- bar
Flat bus- barmm
AIZ-10-GL2/8-2/100-2 1
AIZ-10-GL2/12-3/125-2 UHL1
AIZ-10-GL2/12-4/125-2 UHL1
AIZ-10-GL2/16-3/125-2 UHL1
AIZ-10-GL2/16-4/125-2 UHL1
AIZ-10-GL2/20-3/125-2 UHL1
AIZ-10-GL2/20-4/125-2 UHL1
UHL 2+8
2+12
2+12
2+16
2+16
2+20
2+20
2bus- bar( 100*10)
3bus- bar(125*10)
4bus- bar(125*10)
3bus- bar(125*10)
4bus- bar(125*10)
3bus- bar(125*10)
4bus- bar(125*10)
400
470
470
590
590
590
590
360
400
400
400
400
400
400
The outdoor bus- bar supports AIZ-10-GL are used for transition from flexible to flat horizontal bus-bars with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-GL are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.
BUS-BAR SUPPORTS FOR TRANSITION FROM FLEXIBLE TO HORIZONTAL BUS-BAR AIZ-10-GL...-4 UHL1
Ø13
4 hol.
А
Ø159
Ø127
А
А
L
Н
Incorporated spacerAIZ-2, for wire maitainings
Hflat bus- bar
orizontal
Contact plate for transition
POLYMER BUS-BAR SUPPORTS INTENDED FOR TRANSITION FROM FLEXIBLE TO RIGID BUS-BARS AIZ-10-GL2/8-2/100-4 UHL1 - AIZ-10-GL2/24-4/125-4 UHL1
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Rigid bus- barsupport type
CONDITIONAL DESIGNATION
2/8-2/100 - modification of the cross section of bus- bar and wire
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ -10-GL...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
GL - go with a flexible busbar on flat bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
see table
10
12
75
13
nominal voltage, kV10-
Wires according GOST 839-80, type
Wires according TS16-505.397-72
Diameter of wires,
mmH max,
mmА, АKPАS,АSКS, АSКP, ASK
PM PА
Nominal cross-section, kv, mm2
AIZ-35-А1-4 UHL1 185; 240; 300185/24; 185/29;205/27; 240/32;
240/39- - 17,5 - 22,1 470
AIZ-35-А2-4 UHL1 350; 400
300/39; 300/48;330/30; 330/43;400/51; 400/64;450/56; 500/27
- - 24,0 - 29,4 473
AIZ-35-А3-4 UHL1550; 600; 650;
700; 750
500/26; 500/64;550/71; 600/72;650/79; 700/86
240,300
- 30,0 - 36,2 476
AIZ-35-А4-4 UHL1 - - - 500 45,0 482
450; 500
AIZ-35-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES
FIXATION AIZ-35-А...-4 UHL1
А -modification of bus bar support for one wire
35
40,540,5
4242
2020
1010
11
95
14
190190
AIZ-35-А...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-35-А...-4 UHL1
TECHNICAL CHARACTERISTICS
1,2,3,4 - modification according cross section and type of wire
31,5 31,5
1480 1480
1
127х4 hol. 13
Н
B
Ø159Ø159Ø13Ø13
Ø127Ø127
4 hol.4 hol.
BB
А
А
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR AIZ-35-A...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-07
CONDITIONAL DESIGNATION
AIZ- brand of polymeric bus- bar supports
nominal voltage, kV35-
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. The monolithic core of insulator of bus-bar support eliminates possibility of internal discharge and breakdown, unlike tubes filled with foam, as well as leakage of current in internal cavity and on the wall of tube as consequence of condensation in contrast to hollow tubes. Flanges of bus-bar supports are made from cast high-strength aluminium alloys. Absence of welds in flanges allows applying insulators in the conditions of low temperature in SiberiaThanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works.
Type of flexible bus-bar support
2913AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS-BAR FIXATION AIZ--35-B...-4 UHL1
CONDITIONAL DESIGNATION
35 - nominal voltage, kV
1,2,3,4 - modification according cross section and type of wire
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingUHL1 -
35
40,6
42
20
10
1
95
190
29
AIZ-brand of polymeric bus- bar supports
AIZ-35-B...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-35-B...-4 UHL1
TECHNICAL CHARACTERISTICS
B - modification of bus-bar support for two wires
127х4 hol. 13
31,5
1480
14
2
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. The monolithic core of insulator of bus-bar support eliminates possibility of internal discharge and breakdown, unlike tubes filled with foam, as well as leakage of current in internal cavity and on the wall of tube as consequence of condensation in contrast to hollow tubes. Flanges of bus-bar supports are made from cast high-strength aluminium alloys. Absence of welds in flanges allows applying insulators in the conditions of low temperature in Siberia.Advantages of bus-bar supports AIZ-35-B....UHL1Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury
AIZ-35-B1-4 UHL1 185; 240; 300185/24; 185/29;205/27; 240/32;
240/39- - 17,5 - 22,1 470
AIZ-35-B2-4 UHL1 350; 400
300/39; 300/48;330/30; 330/43;400/51; 400/64;450/56; 500/27
- - 24,0 - 29,4 473
AIZ-35-B3-4 UHL1550; 600; 650;
700; 750
500/26; 500/64;550/71; 600/72;650/79; 700/86
240,300
- 30,0 - 36,2 476
AIZ-35-B4-4 UHL1 - - - 500 45,0 485
450; 500
Н
B
60
Ø13
4 hol.
B
А
Ø159
Ø127
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR AIZ-35-B...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-05
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R АИЗ, Лыткарино
АИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
AIZ,RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Wires according GOST 839-80, type
Wires according TS16-505.397-72
Diameter of wires,
mm
H max,mm
А, АKPАS,АSКS, АSКP, ASK
PM PА
Nominal cross-section, kv, mm2
Type of flexible bus-bar support
according GOST 15150, IEC60721, IEC60068
AIZ-35-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBLE
14
2
AIZ-35-G1-4 UHL1 482 17,8
AIZ-35-G2-4 UHL1 502 18,0
500 65 45,0
500 120 45,0
Weight ,kg
Nominalcross-section
mm
Distance between
wires, L, mm,
AIZ-35-G3-4 UHL1 502 18,0 500 200 45,0
Pic.№
1
2
2
AIZ-35-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF FLEXIBLE BUS-BAR AIZ-35-G...-4 UHL1
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
35 - nominal voltage, kV35 - nominal voltage, kV
1,2 - bus-bar fitting modification1,2 - bus-bar fitting modification
4 - pollution level according GOST 9920, IEC60815, IEC606944 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 - UHL1 -
3535
40,540,5
4242
2020
1010
11
95
190190
2929
AIZ-brand of polymeric bus- bar supportsAIZ-brand of polymeric bus- bar supports
AIZ-35-G...-4 UHL1
TECHNICAL CHARACTERISTICTECHNICAL CHARACTERISTIC
G - modification for three hollow wiresG - modification for three hollow wires
31,5 31,5
1480
see table
3
Н
А
H
L LL L
Pic.2Pic.1
Ø13
4 hol.
А
Ø159
Ø127
127х4 hol. 13
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR AIZ-35-G...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-05
Type of flexible bus-bar support
Diameter of wires,
mm
H max,mm
Wires according TS16-505.397-72
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R АИЗ, Лыткарино
АИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
AIZ,RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. The monolithic core of insulator of bus-bar support eliminates possibility of internal discharge and breakdown, unlike tubes filled with foam, as well as leakage of current in internal cavity and on the wall of tube as consequence of condensation in contrast to hollow tubes. Flanges of bus-bar supports are made from cast high-strength aluminium alloys. Absence of welds in flanges allows applying insulators in the conditions of low temperature in Siberia.Advantages of bus-bar supports AIZ-35-G....UHL1Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury
POLYMER BUS-BAR SUPPORTS AIZ-35-G...-4 UHL1
15
AIZ-35-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ-35-V...-4 UHL1
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
35 - nominal voltage, kV35 - nominal voltage, kV
V- modification for two hollow wires V- modification for two hollow wires
4 - pollution level according GOST 9920, IEC60815, IEC606944 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 - UHL1 -
3535
40,540,5
4242
2020
1010
11
95 95
see tablesee table
190190
2929
AIZ-brand of polymeric bus- bar supportsAIZ-brand of polymeric bus- bar supports
AIZ-35-V...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-35-V...-4 UHL1
TECHNICAL CHARACTERISTICTECHNICAL CHARACTERISTIC
1,2 - bus-bar fitting modification1,2 - bus-bar fitting modification
31,5 31,5
1480 1480
22
Н
А
Pic.2
AIZ-35-V1-4 UHL1 482 17,8
AIZ-35-V2-4 UHL1 502 18,0
500 65 45,0
500 120 45,0
Ø13
4 hol.
А
Ø159
Ø127
AIZ-35-V3-4 UHL1 502 18,0 500 200 45,0
L L
Pic.1
1
2
2
127х4 hol. 13127х4 hol. 13
16
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-07
2
Weight ,kg
Nominalcross-section
mm
Distance between
wires, L, mm,
Pic.№Type of flexible bus-bar support
Diameter of wires,
mm
H max,mm
Wires according TS16-505.397-72
AIZ-35-V...-4 UHL1
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. The monolithic core of insulator of bus-bar support eliminates possibility of internal discharge and breakdown, unlike tubes filled with foam, as well as leakage of current in internal cavity and on the wall of tube as consequence of condensation in contrast to hollow tubes. Flanges of bus-bar supports are made from cast high-strength aluminium alloys. Absence of welds in flanges allows applying insulators in the conditions of low temperature in Siberia.Advantages of bus-bar supports AIZ-35-V....UHL1Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR FOR THE 35KV CURRENT AIZ-35-1М63-4 UHL1-AIZ-35-3М125-4UHL1 AIZ-35-М...-4 UHL1
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR AIZ-35-М...-4 UHL1
The outdoor application of bus- bar supports AIZ-35-M are used for fixing the flat rigid bus- bars in vertical position at 35 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-35-M are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
AIZ-35-1M63-4U HL1
AIZ-35-1M80-4 UHL1
AIZ-35-1M100-4 UHL1
AIZ-35-1M125-4 UHL1
AIZ-35-2М63-4 UHL1
AIZ-35-2М80-4 UHL1
AIZ-35-2М100-4 UHL1
AIZ-35-2М125-4 UHL1
AIZ-35-3М63-4 UHL1
AIZ-35-3М80-4 UHL1
AIZ-35-3М100-4 UHL1
AIZ-35-3М125-4 UHL1
1/63
1/80
1/100
1/125
2/63
2/80
2/100
2/125
3/63
3/80
3/100
3/125
A
A
A
A
C
C
C
C
В
В
В
В
482
500
520
545
482
500
520
545
482
500
520
545
7,90
7,96
8,09
8,15
7,92
7,98
8,11
8,17
7,94
8,00
8,13
8,19
Рic.C
H
Рic.А
Рic.В
Ø13
4 hol. Ø159
Ø127
CONDITIONAL DESIGNATION
69-125 - width of vertical bus-bar in mm
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
20
10
1
95
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-35-М...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
1M,2M,3M - 1,2,3 -flat vertical bus-bars
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
see table
35
40,5
190
42
nominal voltage, kV35-
Building height H, mm
Weight, kgQuantity / width ofbus- bar mm
PictureRigid bus- barsupport type
2917AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ-35-1L63-4 UHL1 - AIZ-35-4L125-4 UHL1
29
AIZ-35-L...-4 UHL1
The outdoor application of bus- bar supports AIZ-35-L are used for fixing the flat rigid bus- bars in horizontal position at 35 kV voltage open distribution devices of electric power stations and substations. Comply with GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-35-L are included in the integrated rigid bus- bar project of substations.Useful service life- 30 years.
AIZ L UHL
AIZ-35-1L80-4U HL1
AIZ-35-1L100-4U HL1
AIZ-35-1L125-4U HL1
AIZ-35-2L63-4U HL1
AIZ-35-2L80-4U HL1
AIZ-35-2L100-4U HL1
AIZ-35-2L125-4U HL1
AIZ-35-3L63-4U HL1
AIZ-35-3L80-4U HL1
AIZ-35-3L100-4U HL1
AIZ-35-3L125-4U HL1
AIZ-35-4L63-4U HL1
AIZ-35-4L80-4U HL1
AIZ-35-4L100-4 UHL1
AIZ-35-4L125-4 UHL1
-35-1 63-4 1 1/63
1/80
1/100
1/125
2/63
2/80
2/100
2/125
3/63
3/80
3/100
3/125
4/63
4/80
4/100
4/125
А
А
А
А
C
C
C
C
В
В
В
В
D
D
D
D
438
442
446
448
458
452
456
468
478
482
486
488
498
502
506
508
8,2
8,2
8,3
8,5
8,5
8,5
8,6
8,7
8,7
8,8
8,8
8,9
8,9
9,0
9,0
9,2
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ-35-L...-4 UHL1
H
Рic.В Рic.D
Рic.CРic.А
H
HH
18AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
63-125 - width of current-carrying mounting a bus- bar in mm
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
20
10
1
95
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-35-L...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
1L,2L,3L - 1,2,3 - flat horizontal bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
see table
35
40,5
190
42
nominal voltage, kV35-
Building height H, mm
Weight, kgQuantity / width of bus- bar mm
PictureRigid bus- barsupport type
Ø13
4 hol.
А
Ø159
Ø127
POLYMER BUS-BAR SUPPORTSS INTENDED FOR TRANSITION FROM FLEXIBLE TO FLAT HORIZOTAL BUS-BARS AIZ-35-GL2/8-2/100-4 UHL1 - AIZ-35-GL2/24-4/125-4 UHL1
AIZ-35-GL...-4 UHL1
А
А
L
Н
The outdoor bus- bar supports AIZ-35-GL are used for transition from flexible to flat horizontal bus-bars with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-35-GL are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.
L H
AIZ GL UHL
AIZ-35-GL2/12-3/125-2 U HL1
AIZ-35-GL2/12-4/125-2 U HL1
AIZ-35-GL2/16-3/125-2 U HL1
AIZ-35-GL2/16-4/125-2 U HL1
AIZ-35-GL2/20-3/125-2 U HL1
AIZ-35-GL2/20-4/125-2 U HL1
-35- 2/8-2/100-2 1 2+8
2+12
2+12
2+16
2+16
2+20
2+20
400
470
470
590
590
590
590
480
520
520
520
520
520
520
BUS-BAR SUPPORTS FOR TRANSITION FROM FLEXIBLE TO HORIZONTAL BUS-BAR AIZ-35-GL...-4 UHL1
CONDITIONAL DESIGNATION
2/8-2/100 - modification of the cross section of bus- bar and wire
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
20
10
1
95
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-35-GL...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
GL - go with a flexible busbar on flat bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
see table
nominal voltage, kV35 -
35
40,5
190
42
Horizontal flat bus- bar
Contact plate for transition
Incorporated spacerAIZ-2, for wiremaitaining
Numberflexible wires
bus- bar
Flat bus- barmm
Rigid bus- barsupport type
2bus- bar( 100*10)
3bus- bar(125*10)
4bus- bar(125*10)
3bus- bar(125*10)
4bus- bar(125*10)
3bus- bar(125*10)
4bus- bar(125*10)
2919AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-35-P100-4 UHL1 - AIZ-35-P250-4 UHL1
29
AIZ-35-P...-4 UHL1
The outdoor application of bus- bar supports AIZ-35-P are used for fixing the box-shaped rigid bus- bars at 35 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231, TS3414-005-59116459-06. The bus- bar supports AIZ-35-P are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.
AIZ-35-P100-4 1
AIZ-35-P125-4 UHL1
AIZ-35-P150-4 UHL1
AIZ-35-P175-4 UHL1
AIZ-35-P200-4 UHL1
AIZ-35-P225-4 UHL1
AIZ-35-P250-4 UHL1
UHL 100
125
150
175
200
225
250
532
557
582
607
632
657
682
12,60
12,70
12,80
12,95
13,10
13,30
13,50
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-35-P...-4 UHL1
20
Н
Ø13
4 hol.
А
Ø159
Ø127
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
100-250 - width of current-carrying mounting a bus- bar in mm
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-35-P...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
P - box shaped buses
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
127х4 hol. 13
nominal voltage, kV35-
20
10
1
90
31,5
1480
1
127х4 отв. 13
see table
127х4 hol. 13
35
40,5
190
42
Building height H, mm
Weight, kgWidth of box ofbus- bar mm
Rigid bus- barsupport type
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBESAIZ-35-Z...-4 UHL AIZ-35-Z...-4 UHL1
POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ-35-Z...-4 UHL1 The outdoor bus- bar supports AIZ-35-Z are used for aluminum tubular bus-bar support with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-35-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request
А
D
Рic.1 Рiс.2
Ø13
4 hol.
А
Ø159
Ø127
H
D
AIZ-35-Z30-4 1
AIZ-35-Z40-4 UHL1
AIZ-35-Z50-4 UHL1
AIZ-35-Z70-4 UHL1
AIZ-35-Z80-4 UHL1
AIZ-35-Z90-4 UHL1
AIZ-35-Z100-4 UHL1
AIZ-35-Z110-4 UHL1
AIZ-35-Z120-4 UHL1
AIZ-35-Z130-4 UHL1
AIZ-35-Z140-4 UHL1
AIZ-35-Z150-4 UHL1
AIZ-35-Z170-4 UHL1
AIZ-35-Z200-4 UHL1
AIZ-35-Z250-4 UHL1
UHL 2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
30/25
40/35
50/45
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
30
40
50
70
80
90
100
110
120
130
140
150
170
200
250
519
519
520
530
538
542
554
560
562
575
580
590
610
630
655
16,1
16,2
16,5
16,8
18,0
18,3
18,5
18,7
19,3
21,3
21,3
22,4
23,5
27,5
33,5
CONDITIONAL DESIGNATION
Ж -rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
30
10
2
30
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-10-Ж...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
30-250- rigid fastening of aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
10
12
75
13
10 - nominal voltage, kV10
CONDITIONAL DESIGNATION
Z -rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
20
10
1
95
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-35-Z...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
30-250- rigid fastening of aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
35
40,5
190
42
nominal voltage, kV35-
Building height H, mm
Weight, kgDiameter
of rigid bus-bar tube, mm
Рic.№Diameter
D, ммRigid bus- barsupport type
2921AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-35-SH50-4 UHL1 - AIZ-35-SH250-4 UHL1
29
AIZ-35-SH...-4 UHL1
The bus- bar supports of outdoor application AIZ-35-SH are used for hinged fastening of tubular rigid bus-bar at 35 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-35-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
А
Ø13
4 hol.
А
Ø159
Ø127H
D
AIZ-35- 50-4 1
AIZ-35-SH60-4 UHL1
AIZ-35-SH70-4 UHL1
AIZ-35-SH80-4 UHL1
AIZ-35-SH90-4 UHL1
AIZ-35-SH100-4 UHL1
AIZ-35-SH110-4 UHL1
AIZ-35-SH120-4 UHL1
AIZ-35-SH130-4 UHL1
AIZ-35-SH140-4 UHL1
AIZ-35-SH150-4 UHL1
AIZ-35-SH170-4 UHL1
AIZ-35-SH200-4 UHL1
AIZ-35-SH250-4 UHL1
SH UHL 50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
530
540
565
570
570
575
585
585
595
600
600
620
650
655
18,0
18,0
18,5
19,0
19,4
20,0
20,5
20,5
21,0
21,5
21,7
23,5
25,2
26,9
BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-35-SH...-4 UHL1
22AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
20
10
1
95
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-35-SH...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
SH - hinging of aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
35
40,5
190
42
nominal voltage, kV35-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
Building height H, mm
Weight, kgDiameter
D, ммRigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-35-D...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
D-movable fastening of aluminium tubular bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
nominal voltage, kV35-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
AIZ D UHL
AIZ-35-D60-4U HL1
AIZ-35-D70-4U HL1
AIZ-35-D80-4U HL1
AIZ-35-D90-4U HL1
AIZ-35-D100-4U HL1
AIZ-35-D110-4U HL1
AIZ-35-D120-4U HL1
AIZ-35-D130-4U HL1
AIZ-35-D140-4U HL1
AIZ-35-D150-4U HL1
AIZ-35-D170-4U HL1
AIZ-35-D200-4U HL1
AIZ-35-D250-4U HL1
-35- 50-4 1 50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
530
540
565
570
570
575
585
585
595
600
600
620
650
655
18,0
18,0
18,5
19,0
19,4
20,0
20,5
20,5
21,0
21,5
21,7
23,5
25,2
26,9
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF RIGID BUS-BARSAIZ-35-D...-4 UHL1
35
40,5
42
20
1
95
190
AIZ-35-D...-4 UHL1
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-35-D...-4 UHL1 The outdoor bus- bar supports AIZ-35-D are used for flexible fitting of aluminium tubular bus-bar support with 35 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-35-D are included in the integrated rigid bus-bar project of substations.
А
Ø13
4 hol.
А
Ø159
Ø127
H
D
10
Building height H, mm
Weight, kgDiameter
D, ммRigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
2923AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
10Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-35-К...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
К - end fastening of aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
nominal voltage, kV35-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ35-К50-4 UHL1 -AIZ35-К250-4 UHL1
35
40,5
42
20
1
95
190
29
AIZ-35-К...-4 UHL1
The outdoor bus- bar supports AIZ-35-K are used for end fixation of aluminium tubular bus-bar support with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-35-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.
AIZ-35-К50-4 UHL1
AIZ-35-К60-4 UHL1
AIZ-35-К70-4 UHL1
AIZ-35-К80-4 UHL1
AIZ-35-К90-4 UHL1
AIZ-35-К100-4 UHL1
AIZ-35-К110-4 UHL1
AIZ-35-К120-4 UHL1
AIZ-35-К130-4 UHL1
AIZ-35-К140-4 UHL1
AIZ-35-К150-4 UHL1
AIZ-35-К170-4 UHL1
AIZ-35-К200-4 UHL1
AIZ-35-К250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
495
498
525
530
530
545
545
550
560
570
600
620
650
655
15,0
15,0
15,1
15,2
15,4
15,7
17,5
17,8
17,9
18,0
18,3
18,5
18,7
18,9
BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ-35-К...-4 UHL1
А
Ø13
4 hol.
А
Ø159
Ø127H
24AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
10Minimum failing load atbending, kN
TYPE TESTS FOR AIZ- 35-I...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
I -movable connection of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
nominal voltage, kV35 -
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
AIZ-35-I50-4 UHL1
AIZ-35-I60-4 UHL1
AIZ-35-I70-4 UHL1
AIZ-35-I80-4 UHL1
AIZ-35-I90-4 UHL1
AIZ-35-I100-4 UHL1
AIZ-35-I110-4 UHL1
AIZ-35-I120-4 UHL1
AIZ-35-I130-4 UHL1
AIZ-35-I140-4 UHL1
AIZ-35-I150-4 UHL1
AIZ-35-I170-4 UHL1
AIZ-35-I200-4 UHL1
AIZ-35-I250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
530
540
565
570
570
575
585
585
595
600
600
620
650
655
18,0
18,0
18,5
19,0
19,4
20,0
20,5
20,5
21,0
21,5
21,7
23,5
25,2
26,9
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBE
AIZ35-I...-4 UHL1
35
40,5
42
20
1
95
190
AIZ-35-I...-4 UHL1
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ35-I...-4 UHL1 The outdoor bus- bar supports AIZ-35-I are used for flexible connection of aluminium tubular bus-bar support with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-35-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
А
Ø13
4 hol.
А
Ø159
Ø127
H
360
360
400
400
420
420
450
460
460
460
480
500
520
520
SizeL, мм
Diameterof rigid bus-bar
tube, mm
Building height H, mm Weight, kg
DiameterD, мм
Rigid bus- barsupport type
2925AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
10Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-35-Е...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
Е - double-grip of aluminum tube
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
nominal voltage, kV35-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBE AIZ-35-Е50-4 UHL1 -AIZ35-Е250-4 UHL1
35
40,5
42
20
1
95
190
AIZ-35-Е...-4 UHL1
The outdoor bus- bar supports AIZ-35-E are used for double fixation of aluminium tube with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-35-E are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-35-Е50-4 UHL1
AIZ-35-Е60-4 UHL1
AIZ-35-Е70-4 UHL1
AIZ-35-Е80-4 UHL1
AIZ-35-Е90-4 UHL1
AIZ-35-Е100-4 UHL1
AIZ-35-Е110-4 UHL1
AIZ-35-Е120-4 UHL1
AIZ-35-Е130-4 UHL1
AIZ-35-Е140-4 UHL1
AIZ-35-Е150-4 UHL1
AIZ-35-Е170-4 UHL1
AIZ-35-Е200-4 UHL1
AIZ-35-Е250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
520
530
530
538
554
560
560
562
575
590
590
610
630
630
16,0
16,0
16,1
16,2
16,4
16,7
18,5
18,8
18,9
19,0
19,3
19,5
19,7
19,9
BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ35-Е...-4 UHL1
Ø13
4 hol.
А
Ø159
Ø127
H
D
А
Diameterof rigid bus-bar
tube, mm
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus- barsupport type
2926AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
10Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-35-C...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
S - for the installation of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
31,5
1480
see table
127х4 hol. 13
1
nominal voltage, kV35 -
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
AIZ-35-С50-4 UHL1
AIZ-35-С60-4 UHL1
AIZ-35-С70-4 UHL1
AIZ-35-С80-4 UHL1
AIZ-35-С90-4 UHL1
AIZ-35-С100-4 UHL1
AIZ-35-С110-4 UHL1
AIZ-35-С120-4 UHL1
AIZ-35-С130-4 UHL1
AIZ-35-С140-4 UHL1
AIZ-35-С150-4 UHL1
AIZ-35-С170-4 UHL1
AIZ-35-С200-4 UHL1
AIZ-35-С250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
620
630
655
660
660
665
675
685
685
690
690
710
740
780
33,5
34,6
35,0
36,0
37,2
38,0
38,5
40,0
43,0
44,0
45,0
48,0
114,0
122,0
BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ35-S...-4 UHL1
1
95
AIZ-35-S...-4 UHL1
BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ35-S...-4 UHL1 The outdoor bus- bar supports AIZ-35-S are used for installation of two aluminium tubes with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-35-S are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Please indicate and fill data sheet if it is necessary to install tubes with different diameter. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.
870
870
870
870
870
870
870
870
870
870
870
870
870
870
D
А
Ø134 hol.
АØ159
Ø127
H
L
35
40,5
190
42
20
Diameterof rigid bus-bar
tube, mm
SizeL, мм
Building height H, mm
Weight, kgDiameter
D, ммRigid bus- barsupport type
Installation choices for bus- bar. The arrows indicate the axis of the aluminum tubes of rigid bus- bar.
2927AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
AIZ-110-А1-4 UHL1 185; 240; 300185/24; 185/29;205/27; 240/32;
240/39- - 17,5 - 22,1 1130
AIZ-110-А2-4 UHL1 350; 400
300/39; 300/48;330/30; 330/43;400/51; 400/64;450/56; 500/27
- - 24,0 - 29,4 1133
AIZ-110-А3-4 UHL1550; 600; 650;
700; 750
500/26; 500/64;550/71; 600/72;650/79; 700/86
240,300
- 30,0 - 36,2 1136
AIZ-110-А4-4 UHL1 - - - 500 45,0 1142
450; 500
CONDITIONAL DESIGNATION
110 - nominal voltage, kV
А -modification of bus bar support for one wire
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingUHL1 -
При удельной поверхностнойпроводимости слоя заGрязнения, мкСм
Минимальный разрушающий крутящиймомент, не менее, кНхм
Мининимальная разрушающая сила наизGиB, кН, не менее
29
AIZ-brand of polymeric bus- bar supports
AIZ-110-А...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-110-А...-4 UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury
TECHNICAL CHARACTERISTICS
1,2,3,4 - modification according cross section and type of wire
Ø220Ø18
Ø178
4 hol.
B
А
H
B
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-07
Wires according GOST 839-80, type
Wires according TS16-505.397-72
Diameter of wires,
mmH max,
mmА, АKPАS,АSКS, АSКP, ASK
PM PА
Nominal cross-section, kv, mm2
Type of flexible bus-bar support
AIZ-110-A...-4 UHL1
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
AIZ-110-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES
FIXATION AIZ-110-A...-4 UHL1
according GOST 15150, IEC60721, IEC60068
28
110
126
110
10
10
1
280
24
450
40
1480
1
178х4 hol. 18
H
HА
Ø18
4 hol.
А
Ø220
Ø178
L L
CONDITIONAL DESIGNATION
110 - nominal voltage, kV
1,2,3,4 - modification according cross section and type of wire
4 - pollution level according GOST 9920, IEC60815, IEC60694
110
126
110
10
10
1
280
450
29
AIZ-brand of polymeric bus- bar supports
AIZ-110-B...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-110-B...-4 UHL1
TECHNICAL CHARACTERISTICS
B - modification of bus-bar support for two wires
178х4 hol. 18
40
1480
see table
2
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”.
Wires according GOST 839-80, type
А, АKP АS, АSКS,АSКP, АSК
Nominal cross-section, mm2
AIZ-110-B1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-110-B2-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-110-B3-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
Dis
tan
ce
bet
wee
n
wir
es,
L, m
m
AIZ-110-B5-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-110-B6-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-110-B7-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
AIZ-110-B8-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-110-B9-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-110-B10-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
AIZ-110-B11-4 UHL1 185; 240; 300185/24; 185/29; 205/27;
205/27; 240/39
AIZ-110-B12-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-110-B13-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
60
60
60
120
120
120
200
200
200
400
400
400
24,8
24,8
24,9
25,3
25,2
25,1
25,5
25,6
25,8
26,8
27,1
27,4
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
1130
1133
1136
1147
1150
1153
1147
1150
1153
1147
1150
1153
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR AIZ-110-B...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-05
Type of flexible bus-bar support
Weight ,kg
Diameter of wires,
mm
H max,mm
climate desing and category of spasingUHL1 - according GOST 15150, IEC60721, IEC60068
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R АИЗ, Лыткарино
АИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS-BAR FIXATION AIZ--110-B...-4 UHL1AIZ-110-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBLE
29
BUS-BAR FIXATION AIZ--110-V...-4 UHL1
CONDITIONAL DESIGNATION
110 - nominal voltage, kV
V- modification for two hollow wires
4 - pollution level according GOST 9920, IEC60815, IEC60694
UHL1 -
Минимальный разрушающий крутящиймомент, не менее, кНхм
110
126
110
10
10
1
280
see table
450
29
AIZ-brand of polymeric bus- bar supports
AIZ-110-V...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-110-V .....UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
TECHNICAL CHARACTERISTICS
1,2,3 - modification according cross section and type of wire
40
1480
2
AIZ-110-В1-4 UHL1 1142 27,8
AIZ-110-В2-4 UHL1 1162 28,0
500 65 45,0
500 120 45,0
AIZ-110-В3-4 UHL1 1162 28,0 500 200 45,0
L
Pic.1
1
2
2
178х4 hol. 18
Ø220Ø18
Ø178
4 hol.
H
Pic.2
Connection dimensions of bottom flange
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-07
2
Weight ,kg
Nominalcross-section
mm
Distance between
wires, L, mm,
Pic.№Type of flexible bus-bar support
Diameter of wires,
mm
H max,mm
Wires according TS16-505.397-72
AIZ-110-V...-4 UHL1
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ 30
AIZ-110-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
H
Ø18
4 hol. Ø220
Ø178
L LL L
AIZ-110-G1-4 UHL1 1142 27,8
AIZ-110-G2-4 UHL1 1162 28,0
500 65 45,0
500 120 45,0
AIZ-110-G3-4 UHL1 1162 28,0 500 200 45,0
1
2
2
OF FLEXIBLE BUS-BAR AIZ-110-G...-4 UHL1
CONDITIONAL DESIGNATION
110 - nominal voltage, kV
1,2,3 - bus-bar fitting modification
4 - pollution level according GOST 9920, IEC60815, IEC60694
110
126
110
10
10
1
280
450
29
AIZ-brand of polymeric bus- bar supports
AIZ-110-G...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-110-G...-4 UHL1
TECHNICAL CHARACTERISTICS
G - modification for three hollow wires
40
1480
see table
3
178х4 hol. 18
Connection dimensions of bottom flange
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR AIZ-110-G...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-05
2
Weight ,kg
Nominalcross-section
mm
Distance between
wires, L, mm,
Pic.№Type of flexible bus-bar support
Diameter of wires,
mm
H max,mm
Wires according TS16-505.397-72
climate desing and category of spasingUHL1 - according GOST 15150, IEC60721, IEC60068
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R АИЗ, Лыткарино
АИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
AIZ-110-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES
31
127х4 отв. 13
CONDITIONAL DESIGNATION
100-250 - width of current-carrying mounting a bus- bar in mm
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-110-Р...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
P - box shaped buses
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
nominal voltage, kV110 -
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBESAIZ-110-P100-4 UHL1 -AIZ110-P250-4 UHL1
10
10
1
280
AIZ-110-P...-4 UHL1
40
1480
1
178х4 hol. 18
The outdoor application of bus- bar supports AIZ-110-P are used for fixing the box-shaped rigid bus- bars at 110 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231, TS3414-005-59116459-06. The bus- bar supports AIZ-110-P are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.
AIZ-110-P100-4 UHL1
AIZ-110-P125-4 UHL1
AIZ-110-P150-4 UHL1
AIZ-110-P175-4 UHL1
AIZ-110-P200-4 UHL1
AIZ-110-P225-4 UHL1
AIZ-110-P250-4 UHL1
100
125
150
175
200
225
250
1232
1257
1282
1307
1332
1357
1382
22,60
22,70
22,80
22,95
23,10
23,30
23,50
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ110-P...-4 UHL1
110
126
450
110
Н
Ø18
4 hol.
А
Ø220
Ø178
Building height H, mm
Weight, kgWidth of box ofbus- bar mm
Rigid bus- barsupport type
2932AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
69-125 -width vertical of the bus- bar in mm
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-110-М...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
1M,2M,3M - 1,2,3 -flat vertical bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
see table
nominal voltage, kV110 -
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR FOR THE 110KV CURRENT AIZ110-1М63-4 UHL1-AIZ-110-3М125-4UHL1
110
126
450
110
10
10
1
28
AIZ-110-М...-4 UHL1
40
1480
178х4 hol. 18
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR AIZ110-М...-4 UHL1
The outdoor application of bus- bar supports AIZ-110-M are used for fixing the flat rigid bus- bars in vertical position at 110 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-110-M are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
AIZ-110-1M63-4 UHL1
AIZ-110-1M80-4 UHL1
AIZ-110-1M100-4 UHL1
AIZ-110-1M125-4 UHL1
AIZ-110-2М63-4 UHL1
AIZ-110-2М80-4 UHL1
AIZ-110-2М100-4 UHL1
AIZ-110-2М125-4 UHL1
AIZ-110-3М63-4 UHL1
AIZ-35-3М80-4 UHL1
AIZ-35-3М100-4 UHL1
AIZ-35-3М125-4 UHL1
1/63
1/80
1/100
1/125
2/63
2/80
2/100
2/125
3/63
3/80
3/100
3/125
A
A
A
A
C
C
C
C
В
В
В
В
1182
1200
1220
1245
1182
1200
1220
1245
1182
1200
1220
1245
17,90
17,96
18,09
18,15
17,92
17,98
18,11
18,17
17,94
18,00
18,13
18,19
Рiс.C
H
Рiс.А
Рiс.В
Ø18
4 hol. Ø220
Ø178
Building height H, mm
Weight, kgQuantity / width ofbus- bar mm
PictureRigid bus- barsupport type
2933AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
63-125 - width of current-carrying mounting a bus- bar in mm
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-110-L...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
1L,2L,3L - 1,2,3 -flat horizontal bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
see table
nominal voltage, kV110-
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ-110-1L63-4 UHL1 -AIZ-110-4L125-4 UHL1
10
10
1
280
AIZ-110-L...-4 UHL1
40
1480
178х4 hol. 18
The outdoor application of bus- bar supports AIZ-110-L are used for fixing the flat rigid bus- bars in horizontal position at 110 kV voltage open distribution devices of electric power stations and substations. Comply with GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-110-L are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
AIZ-110-1L63-4 UHL1
AIZ-110-1L80-4 UHL1
AIZ-110-1L100-4 UHL1
AIZ-110-1L125-4 UHL1
AIZ-110-2L63-4 UHL1
AIZ-110-2L80-4 UHL1
AIZ-110-2L100-4 UHL1
AIZ-110-2L125-4 UHL1
AIZ-110-3L63-4 UHL1
AIZ-110-3L80-4 UHL1
AIZ-110-3L100-4 UHL1
AIZ-110-3L125-4 UHL1
AIZ-110-4L63-4 UHL1
AIZ-110-4L80-4 UHL1
AIZ-110-4L100-4UHL1
AIZ-110-4L125-4UHL1
1/63
1/80
1/100
1/125
2/63
2/80
2/100
2/125
3/63
3/80
3/100
3/125
4/63
4/80
4/100
4/125
А
А
А
А
C
C
C
C
В
В
В
В
D
D
D
D
1138
1142
1146
1148
1158
1152
1156
1168
1178
1182
1186
1188
1198
1202
1206
1208
18,2
18,2
18,3
18,5
18,5
18,5
18,6
18,7
18,7
18,8
18,8
18,9
18,9
19,0
19,0
19,2
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ110-L...-4 UHL1
H
Рiс.В Рiс.D
Рiс.CРiс.А
H
HH
110
126
450
110
Building height H, mm
Weight, kgQuantity / width ofbus- bar mm
PictureRigid bus- barsupport type
2934AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
Z -rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-110-Z...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
30-250- rigid fastening of aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
nominal voltage, kV110 -
Ø18
4 hol. Ø220
Ø178
Connecting dimensionsof bottom flange
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ35-Z...-4 UHL1
110
126
110
10
10
1
280
450
AIZ-110-Z...-4 UHL1
40
1480
1
178х4 hol. 18
POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ110-Z...-4 UHL1 The outdoor bus- bar supports AIZ-110-Z are used for aluminum tubular bus-bar support with 110 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-110-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request
AIZ-110-Z30-4 UHL1
AIZ-110-Z40-4 UHL1
AIZ-110-Z50-4 UHL1
AIZ-110-Z70-4 UHL1
AIZ-110-Z80-4 UHL1
AIZ-110-Z90-4 UHL1
AIZ-110-Z100-4 UHL1
AIZ-110-Z110-4 UHL1
AIZ-110-Z120-4 UHL1
AIZ-110-Z130-4 UHL1
AIZ-110-Z140-4 UHL1
AIZ-110-Z150-4 UHL1
AIZ-110-Z170-4 UHL1
AIZ-110-Z200-4 UHL1
AIZ-110-Z250-4 UHL1
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
30/25
40/35
50/45
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
30
40
50
70
80
90
100
110
120
130
140
150
170
200
250
1179
1179
1180
1190
1198
1202
1214
1220
1222
1235
1240
1250
1270
1290
1315
26,1
26,2
26,5
26,8
28,0
28,3
28,5
28,7
29,3
31,3
31,3
32,4
33,5
37,5
43,5
DD
Pic.1
H
Рiс.2
Building height H, mm
Weight, kgDiameter
of rigid bus-bar tube, mm
Рic.№Diameter
D, ммRigid bus- barsupport type
2935AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
D
H
Ø18
4 hol. Ø220
Ø178
Connecting dimensionsof bottom flange
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARSAIZ-110-SH50-4 UHL1 -AIZ110-SH250-4 UHL1
110
126
110
10
10
1
280
450
AIZ-110-SH...-4 UHL1
40
1480
1
178х4 hol. 18
The bus- bar supports of outdoor application AIZ-110-SH are used for hinged fastening of tubular rigid bus-bar at 110 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-110-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-110-SH50-4 UHL1
AIZ-110-SH60-4 UHL1
AIZ-110-SH70-4 UHL1
AIZ-110-SH80-4 UHL1
AIZ-110-SH90-4 UHL1
AIZ-110-SH100-4 UHL1
AIZ-110-SH110-4 UHL1
AIZ-110-SH120-4 UHL1
AIZ-110-SH130-4 UHL1
AIZ-110-SH140-4 UHL1
AIZ-110-SH150-4 UHL1
AIZ-110-SH170-4 UHL1
AIZ-110-SH200-4 UHL1
AIZ-110-SH250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
1190
1200
1225
1230
1230
1235
1245
1245
1255
1260
1260
1280
1310
1315
28,0
28,0
28,5
29,0
29,4
30,0
30,5
30,5
31,0
31,5
31,7
33,5
35,2
36,9
BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BARAIZ110-SH...-4 UHL1
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-110-SH...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
SH - hinging of aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
nominal voltage, kV110-
CONDITIONAL DESIGNATION
see table
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
2936AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-110-D...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
1
nominal voltage, kV110-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
AIZ-110-D50-4 UHL1
AIZ-110-D60-4 UHL1
AIZ-110-D70-4 UHL1
AIZ-110-D80-4 UHL1
AIZ-110-D90-4 UHL1
AIZ-110-D100-4 UHL1
AIZ-110-D110-4 UHL1
AIZ-110-D120-4 UHL1
AIZ-110-D130-4 UHL1
AIZ-110-D140-4 UHL1
AIZ-110-D150-4 UHL1
AIZ-110-D170-4 UHL1
AIZ-110-D200-4 UHL1
AIZ-110-D250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF RIGID BUS-BARSAIZ110-D...-4 UHL1
110
126
110
10
10
1
280
450
AIZ-110-D...-4 UHL1
40
1480
178х4 hol. 18BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ110-D...-4 UHL1
The outdoor bus- bar supports AIZ-110-D are used for flexible fitting of aluminium tubular bus-bar support with 110 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-110-D are included in the integrated rigid bus-bar project of substations.
1190
1200
1225
1230
1230
1235
1245
1245
1255
1260
1260
1280
1310
1315
28,0
28,0
28,5
29,0
29,4
30,0
30,5
30,5
31,0
31,5
31,7
33,5
35,2
36,9
D
H
Ø18
4 hol. Ø220
Ø178
Connecting dimensionsof bottom flange
D-movable fastening of aluminium tubular bus- bar
50-250- rigid fastening of aluminum tube bus- bar
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
2937AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-110-К...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
К - end fastening of aluminum tube bus- bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
nominal voltage, kV110-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGIDBUS-BAR AIZ110-К...-4 UHL1
110
126
110
10
10
1
280
450
AIZ-110-К...-4 UHL1
40
1480
1
178х4 hol. 18
The outdoor bus- bar supports AIZ-110-K are used for end fixation of aluminium tubular bus-bar support with 110 kV voltage on opened distribution devices of electric power stations and substations.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-110-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.
AIZ-110-К50-4U HL1
AIZ-110-К60-4U HL1
AIZ-110-К70-4U HL1
AIZ-110-К80-4U HL1
AIZ-110-К90-4U HL1
AIZ-110-К100-4U HL1
AIZ-110-К110-4U HL1
AIZ-110-К120-4U HL1
AIZ-110-К130-4 UHL1
AIZ-110-К140-4 UHL1
AIZ-110-К150-4 UHL1
AIZ-110-К170-4 UHL1
AIZ-110-К200-4 UHL1
AIZ-110-К250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
1155
1158
1185
1190
1190
1205
1205
1210
1220
1230
1260
1280
1310
1315
25,0
25,0
25,1
25,2
25,4
25,7
27,5
27,8
27,9
28,0
28,3
28,5
28,7
28,9
BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ110-К...-4 UHL1
H
Ø18
4 hol. Ø220
Ø178
Connecting dimensionsof bottom flange
D
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
2938AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ- 110-I...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
I -movable connection of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
nominal voltage, kV110 -
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
H Ø18
4 hol. Ø220
Ø178
Connecting dimensionsof bottom flange
AIZ-110-I50-4U HL1
AIZ-110-I60-4U HL1
AIZ-110-I70-4U HL1
AIZ-110-I80-4U HL1
AIZ-110-I90-4U HL1
AIZ-110-I100-4U HL1
AIZ-110-I110-4U HL1
AIZ-110-I120-4U HL1
AIZ-110-I130-4U HL1
AIZ-110-I140-4U HL1
AIZ-110-I150-4U HL1
AIZ-110-I170-4U HL1
AIZ-110-I200-4U HL1
AIZ-110-I250-4U HL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
28,0
28,0
28,5
29,0
29,4
30,0
30,5
30,5
31,0
31,5
31,7
33,5
35,2
36,9
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBEAIZ110-I...-4 UHL1
110
126
110
10
10
1
280
450
AIZ-110-I...-4 UHL1
40
1480
1
178х4 отв. 18BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ110-I...-4 UHL1
The outdoor bus- bar supports AIZ-110-I are used for flexible connection of aluminium tubular bus-bar support with 110 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-110-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
360
360
400
400
420
420
450
460
460
460
480
500
520
520
1190
1200
1225
1230
1230
1235
1245
1245
1255
1260
1260
1280
1310
1315
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
SizeL, мм
2939AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-110-Е...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
Е - double-grip of aluminum tube
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
nominal voltage, kV110-
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBEAIZ110-Е...-4 UHL1
CONDITIONAL DESIGNATION
110
126
110
10
10
1
280
450
AIZ-110-Е...-4 UHL1
40
1480
1
178х4 отв. 18
The outdoor bus- bar supports AIZ-110-E are used for double fixation of aluminium tube with 110 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-110-E are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-110-Е50-4U HL1
AIZ-110-Е60-4U HL1
AIZ-110-Е70-4U HL1
AIZ-110-Е80-4U HL1
AIZ-110-Е90-4U HL1
AIZ-110-Е100-4U HL1
AIZ-110-Е110-4U HL1
AIZ-110-Е120-4U HL1
AIZ-110-Е130-4U HL1
AIZ-110-Е140-4U HL1
AIZ-110-Е150-4U HL1
AIZ-110-Е170-4U HL1
AIZ-110-Е200-4U HL1
AIZ-110-Е250-4U HL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
1180
1190
1190
1198
1214
1220
1220
1222
1235
1250
1250
1270
1290
1290
26,0
26,0
26,1
26,2
26,4
26,7
28,5
28,8
28,9
29,0
29,3
29,5
29,7
29,9
BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ110-Е...-4 UHL1
D
H
Ø18
4 hol. Ø220
Ø178
Connecting dimensionsof bottom flange
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus- barsupport type
Diameterof rigid bus-bar
tube, mm
2940AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
50-250- rigid fastening of aluminum tube bus- bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-110-C...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
S - for the installation of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
nominal voltage, kV110 -
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
AIZ-110-С50-4 UHL1
AIZ-110-С60-4 UHL1
AIZ-110-С70-4 UHL1
AIZ-110-С80-4 UHL1
AIZ-110-С90-4 UHL1
AIZ-110-С100-4 UHL1
AIZ-110-С110-4 UHL1
AIZ-110-С120-4 UHL1
AIZ-110-С130-4 UHL1
AIZ-110-С140-4 UHL1
AIZ-110-С150-4 UHL1
AIZ-110-С170-4 UHL1
AIZ-110-С200-4 UHL1
AIZ-110-С250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
43,5
44,6
45,0
46,0
47,2
48,0
48,5
50,0
53,0
54,0
55,0
58,0
124,0
132,0
BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ110-S...-4 UHL1
CONDITIONAL DESIGNATION
110
126
110
10
10
1
280
450
AIZ-110-S...-4 UHL1
40
1480
1
178х4 отв. 18BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ110-S...-4 UHL1
The outdoor bus- bar supports AIZ-110-S are used for installation of two aluminium tubes with 110 kV voltage on opened distribution devices of electric power stations and substations.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-110-S are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years.Please indicate and fill data sheet if it is necessary to install tubes with different diameter. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.
870
870
870
870
870
870
870
870
870
870
870
870
870
870
1280
1290
1315
1320
1320
1325
1325
1335
1345
1350
1350
1370
1400
1440
D
HL
Installation choices for bus- bar.The arrows indicate the axis
of aluminum tuberigid bus-bar.
Ø184 hol. Ø220
Ø178
Connecting dimensionsof bottom flange
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus- barsupport type
Diameter of rigid bus-bar
tube, mm
SizeL, мм
2941AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
CONDITIONAL DESIGNATION
2/8-2/100 - modification of the cross section of bus- bar and wire
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-110-GL...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus- bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TS3494-005-59116459-05
GL- transition fromr
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
see table
see table
nominal voltage, kV110 -
110
126
110
10
10
1
280
450
AIZ-110-GL...-4 UHL1
40
1480
178х4 hol. 18
Ø18
4 hol.
The of bottom flange
Ø220
Ø178
А
А
L
Н
Incorporated spacerAIZ-2, for wiremaitaining
Horizontal flat bus- bar
Contact plate for transition
L H
AIZ-110-GL2/8-2/100-2 UHL1
AIZ-110-GL2/12-3/125-2 U HL1
AIZ-110-GL2/12-4/125-2 U HL1
AIZ-110-GL2/16-3/125-2 U HL1
AIZ-110-GL2/16-4/125-2 U HL1
AIZ-110-GL2/20-3/125-2 U HL1
AIZ-110-GL2/20-4/125-2 U HL1
2+8
2+12
2+12
2+16
2+16
2+20
2+20
400
470
470
590
590
590
590
1180
1220
1220
1220
1220
1220
1220
The outdoor bus- bar supports AIZ-110-GL are used for transition from flexible to flat horizontal bus-bars with 110 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-110-GL are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.
BUS-BAR SUPPORTS FOR TRANSITION FROM FLEXIBLE TO HORIZONTAL BUS-BAR AIZ110-GL...-4 UHL1
POLYMER BUS-BAR SUPPORTS INTENDED FOR TRANSITION FROM FLEXIBLE TO FLAT HORIZOTAL BUS-BARS AIZ110-GL2/8-2/100-4 UHL1 - AIZ35-GL2/24-4/125-4 UHL1
Rigid bus- barsupport type
Numberflexible wires
bus- bar
Flat bus- barmm
2bus- bar( 100*10)
3bus- bar(125*10)
4bus- bar(125*10)
3bus- bar(125*10)
4bus- bar(125*10)
3bus- bar(125*10)
4bus- bar(125*10)
2942AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
AIZ-150-А1-4 UHL1 185; 240; 300185/24; 185/29;205/27; 240/32;
240/39- - 17,5 - 22,1 1630
AIZ-150-А2-4 UHL1 350; 400
300/39; 300/48;330/30; 330/43;400/51; 400/64;450/56; 500/27
- - 24,0 - 29,4 1633
AIZ-150-А3-4 UHL1550; 600; 650;
700; 750
500/26; 500/64;550/71; 600/72;650/79; 700/86
240,300
- 30,0 - 36,2 1636
AIZ-150-А4-4 UHL1 - - - 500 45,0 1642
450; 500
AND WIRES FIXATION AIZ-150-А...-4 UHL1
AIZ-150-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
150 - nominal voltage, kV150 - nominal voltage, kV
А -modification of bus bar support for one wireА -modification of bus bar support for one wire
4 - pollution level according GOST 9920, IEC60815, IEC606944 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 - UHL1 -
Минимальный разрушающий крутящийМинимальный разрушающий крутящий
150150
172172
150150
1010
1010
11
390 390
2828
650650
2929
AIZ-brand of polymeric bus- bar supportsAIZ-brand of polymeric bus- bar supports
AIZ-150-А...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-150-А...-4 UHL1
TECHNICAL CHARACTERISTICSTECHNICAL CHARACTERISTICS
1,2,3,4 - modification according cross section and type of wire1,2,3,4 - modification according cross section and type of wire
40 40
1480 1480
11
178х4 hol. 18178х4 hol. 18
Ø220Ø18
Ø178
4 hol.
B
АH
B
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-07
Wires according GOST 839-80, type
Wires according TS16-505.397-72
Diameter of wires,
mmH max,
mmА, АKPАS,АSКS, АSКP, ASK
PM PА
Nominal cross-section, kv, mm2
Type of flexible bus-bar support
AIZ-150-A...-4 UHL1
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
43
H
H
А
Ø18
4 hol.
А
Ø220
Ø178
L L
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
150 - nominal voltage, kV150 - nominal voltage, kV
1,2,3,4 - modification according cross section and type of wire
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 - UHL1 -
150150
172172
150
10
10
11
390
650650
2929
AIZ-brand of polymeric bus- bar supportsAIZ-brand of polymeric bus- bar supports
AIZ-150-B...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-150-B...-4 UHL1
TECHNICAL CHARACTERISTICS
B - modification of bus-bar support for two wiresB - modification of bus-bar support for two wires
178х4 hol. 18178х4 hol. 18
40
1480 1480
see tablesee table
22
AIZ-150-B1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-150-B2-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-150-B3-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
AIZ-150-B5-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-150-B6-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-150-B7-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
AIZ-150-B8-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-150-B9-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-150-B10-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
AIZ-150-B11-4 UHL1 185; 240; 300185/24; 185/29; 205/27;
205/27; 240/39
AIZ-150-B12-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-150-B13-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
60
60
60
120
120
120
200
200
200
400
400
400
28,8
28,8
28,9
29,3
29,2
29,1
29,5
29,6
29,8
30,8
31,1
31,4
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
1630
1633
1636
1647
1650
1653
1647
1650
1653
1647
1650
1653
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR AIZ-150-B...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-05
Wires according GOST 839-80, type
А, АKP АS, АSКS,АSКP, АSК
Nominal cross-section, mm2 D
ista
nce
b
etw
een
w
ires
, L
, mmType of flexible
bus-bar supportWeight ,
kgDiameter
of wires,mm
H max,mm
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R АИЗ, Лыткарино
АИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
BUS-BAR FIXATION AIZ--150-B...-4 UHL1AIZ-150-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBLE
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”.
44
BUS-BAR FIXATION AIZ-150-V...-4 UHL1
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
150 - nominal voltage, kV150 - nominal voltage, kV
V- modification for two hollow wires V- modification for two hollow wires
4 - pollution level according GOST 9920, IEC60815, IEC606944 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 - UHL1 -
Минимальный разрушающий крутящийМинимальный разрушающий крутящий
150150
172172
150150
1010
1010
11
390 390
see tablesee table
650650
2929
AIZ-brand of polymeric bus- bar supportsAIZ-brand of polymeric bus- bar supports
AIZ-150-V...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-150-V...-4 UHL1
TECHNICAL CHARACTERISTICSTECHNICAL CHARACTERISTICS
1,2,3 - modification according cross section and type of wire1,2,3 - modification according cross section and type of wire
40 40
1480 1480
22
AIZ-150-В1-4 UHL1 1642 31,8
AIZ-150-В2-4 UHL1 1662 32,0
500 65 45,0
500 120 45,0
AIZ-150-В3-4 UHL1 1662 32,0 500 200 45,0
L
Pic.1
1
2
2
178х4 hol. 18178х4 hol. 18
Ø220Ø18
Ø178
4 hol.
HH
Pic.2
Connection dimensions
of bottom flange
45
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-07
2
Weight ,kg
Nominalcross-section
mm
Distance between
wires, L, mm,
Pic.№Type of flexible bus-bar support
Diameter of wires,
mm
H max,mm
Wires according TS16-505.397-72
AIZ-150-V...-4 UHL1
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
AIZ-150-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
HH
Ø18
4 hol. Ø220
Ø178
L LL L
AIZ-150-G1-4 UHL1 1642 31,8
AIZ-150-G2-4 UHL1 1662 32,0
500 65 45,0
500 120 45,0
AIZ-150-G3-4 UHL1 1662 32,0 500 200 45,0
1
2
2
OF BUS-BAR FIXATION AIZ-150-G...-4 UHL1
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
150 - nominal voltage, kV150 - nominal voltage, kV
1,2,3 - bus-bar fitting modification1,2,3 - bus-bar fitting modification
4 - pollution level according GOST 9920, IEC60815, IEC606944 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 - UHL1 -
150150
172172
150150
1010
1010
11
390
650650
2929
AIZ-brand of polymeric bus- bar supportsAIZ-brand of polymeric bus- bar supports
AIZ-150-G...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-150-G...-4 UHL1
TECHNICAL CHARACTERISTICSTECHNICAL CHARACTERISTICS
G - modification for three hollow wiresG - modification for three hollow wires
40
1480
see tablesee table
3
178х4 hol. 18178х4 hol. 18
Connection dimensions of bottom flange
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR AIZ-150-G...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-05
2
Weight ,kg
Nominalcross-section
mm
Distance between
wires, L, mm,
Pic.№Type of flexible bus-bar support
Diameter of wires,
mm
H max,mm
Wires according TS16-505.397-72
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R АИЗ, Лыткарино
АИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
AIZ-35-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES
46
CONVENTIONAL MARKING
Z -rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-150-Z...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
30-250- rigid fastening of aluminum tube bus bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV150 -
Ø18
4 hol. Ø220
Ø178
Connecting dimensions of bottom flange
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBESSAIZ-150-Z...-4 UHL1 AIZ -150-Z...-4 UHL1
POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ-150-Z...-4 UHL1 The outdoor bus- bar supports AIZ-150-Z are used for aluminum tubular bus-bar support with 150 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-150-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request
AIZ-150-Z30-4 UHL1
AIZ-150-Z40-4 UHL1
AIZ-150-Z50-4 UHL1
AIZ-150-Z70-4 UHL1
AIZ-150-Z80-4 UHL1
AIZ-150-Z90-4 UHL1
AIZ-150-Z100-4 UHL1
AIZ-150-Z110-4 UHL1
AIZ-150-Z120-4 UHL1
AIZ-150-Z130-4 UHL1
AIZ-150-Z140-4 UHL1
AIZ-150-Z150-4 UHL1
AIZ-150-Z170-4 UHL1
AIZ-150-Z200-4 UHL1
AIZ-150-Z250-4 UHL1
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
30/25
40/35
50/45
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
30
40
50
70
80
90
100
110
120
130
140
150
170
200
250
1679
1679
1680
1690
1698
1702
1714
1720
1722
1735
1740
1750
1770
1790
1815
30,1
30,2
30,5
30,8
32,0
32,3
32,5
32,7
33,3
35,3
35,3
36,4
37,5
41,5
47,5
DD
Pic.1
H
Pic.2
Building height H, mm
Weight, kgDiameter
of rigid bus-bar tube, mm
Рic.№Diameter
D, ммRigid bus barsupport type
2947AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
150
172
150
10
10
1
390
650
40
1480
1
178х4 hol. 18
40
1480
1
178х4 hol. 18
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-150-SH...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
SH - hinging of aluminum tube bus-bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
nominal voltage, kV150-
CONVENTIONAL MARKING
see table
D
H
Ø18
4 hol. Ø220
Ø178
Connecting dimensions of bottom flange
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-150-SH50-4 UHL1 - AIZ-150-SH250-4 UHL1
29
AIZ -150-SH...-4 UHL1
The bus- bar supports of outdoor application AIZ-150-SH are used for hinged fastening of tubular rigid bus-bar at 150 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-150-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-150-SH50-4 UHL1
AIZ-150-SH60-4 UHL1
AIZ-150-SH70-4 UHL1
AIZ-150-SH80-4 UHL1
AIZ-150-SH90-4 UHL1
AIZ-150-SH100-4 UHL1
AIZ-150-SH110-4 UHL1
AIZ-150-SH120-4 UHL1
AIZ-150-SH130-4 UHL1
AIZ-150-SH140-4 UHL1
AIZ-150-SH150-4 UHL1
AIZ-150-SH170-4 UHL1
AIZ-150-SH200-4 UHL1
AIZ-150-SH250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
1690
1700
1725
1730
1730
1735
1745
1745
1755
1760
1760
1780
1810
1815
32,0
32,0
32,5
33,0
33,4
34,0
34,5
34,5
35,0
35,5
35,7
37,5
39,2
40,9
BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-150-SH...
48AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
Assemblage
150150
172172
150150
1010
1010
11
390 390
650650
40
CONVENTIONAL MARKING
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-150-D...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV150-
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
D-movable fastening of aluminum tube bus-bar
50-250- rigid fastening of aluminum tube bus bar
AIZ-150-D50-4 UHL1
AIZ-150-D60-4 UHL1
AIZ-150-D70-4 UHL1
AIZ-150-D80-4 UHL1
AIZ-150-D90-4 UHL1
AIZ-150-D100-4 UHL1
AIZ-150-D110-4 UHL1
AIZ-150-D120-4 UHL1
AIZ-150-D130-4 UHL1
AIZ-150-D140-4 UHL1
AIZ-150-D150-4 UHL1
AIZ-150-D170-4 UHL1
AIZ-150-D200-4 UHL1
AIZ-150-D250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF RIGID BUS-BARSAIZ-150-D...-4 UHL1
29
AIZ -150-D...-4 UHL1
178х4 hol. 18
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF RIGID BUS-BARS AIZ-150-D...-4 UHL1
The outdoor bus- bar supports AIZ-150-D are used for flexible fitting of aluminium tubular bus-bar support with 150 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-150-D are included in the integrated rigid bus-bar project of substations
1690
1700
1725
1730
1730
1735
1745
1745
1755
1760
1760
1780
1810
1815
32,0
32,0
32,5
33,0
33,4
34,0
34,5
34,5
35,0
35,5
35,7
37,5
39,2
46,9
D
H
Ø18
4 hol. Ø220
Ø178
Connecting dimensions of bottom flange
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
AIZ- registrated trade mark of the group of companies AIZR
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
2949AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
150
172
150
10
10
1
390
650
40
1480
1
CONVENTIONAL MARKING
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-150-К...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
К - end fastening of aluminum tube bus bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV150-
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ-150-К...-4 UHL1
29
AIZ -150-К...-4 UHL1
The outdoor bus- bar supports AIZ-150-K are used for end fixation of aluminium tubular bus-bar support with 150 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-150-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.
AIZ-150-К50-4 UHL1
AIZ-150-К60-4 UHL1
AIZ-150-К70-4 UHL1
AIZ-150-К80-4 UHL1
AIZ-150-К90-4 UHL1
AIZ-150-К100-4 UHL1
AIZ-150-К110-4 UHL1
AIZ-150-К120-4 UHL1
AIZ-150-К130-4 UHL1
AIZ-150-К140-4 UHL1
AIZ-150-К150-4 UHL1
AIZ-150-К170-4 UHL1
AIZ-150-К200-4 UHL1
AIZ-150-К250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
1655
1658
1685
1690
1690
1705
1705
1710
1720
1730
1760
1780
1810
1815
29,0
29,0
29,1
29,2
29,4
29,7
29,5
31,8
31,9
32,0
32,3
32,5
32,7
32,9
BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ-150-К...-4 UHL1
H
Ø18
4 hol. Ø220
Ø178
Connecting dimensions of bottom flange
D
50AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
150150
172172
150150
1010
1010
11
390 390
650650
40
1480 1480
1
178х4 hol. 18
CONVENTIONAL MARKING
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ- 150-I...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
I -movable connection of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV150 -
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
H Ø18
4 hol. Ø220
Ø178
Connecting dimensions of bottom flange
AIZ-150-I50-4 UHL1
AIZ-150-I60-4 UHL1
AIZ-150-I70-4 UHL1
AIZ-150-I80-4 UHL1
AIZ-150-I90-4 UHL1
AIZ-150-I100-4 UHL1
AIZ-150-I110-4 UHL1
AIZ-150-I120-4 UHL1
AIZ-150-I130-4 UHL1
AIZ-150-I140-4 UHL1
AIZ-150-I150-4 UHL1
AIZ-150-I170-4 UHL1
AIZ-150-I200-4 UHL1
AIZ-150-I250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
32,0
32,0
32,5
33,0
33,4
34,0
34,5
34,5
35,0
35,5
35,7
37,5
39,2
40,9
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBE AIZ-150-I...-4 UHL1
150
172
150
10
10
1
390
650
29
AIZ -150-I...-4 UHL1
40
1480
1
178х4 hol. 18
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ-150-I...-4 UHL1 The outdoor bus- bar supports AIZ-150-I are used for flexible connection of aluminium tubular bus-bar support with 150 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-150-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years.The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
360
360
400
400
420
420
450
460
460
460
480
500
520
520
1690
1700
1725
1730
1730
1735
1745
1745
1755
1760
1760
1780
1810
1815
51AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
SizeL, мм
CONVENTIONAL MARKING
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-150-Е...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
Е - double-grip of aluminum tube
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV150-
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBE AIZ-150-Е...-4 UHL1
29
AIZ -150-Е...-4 UHL1
The outdoor bus- bar supports AIZ-150-E are used for double fixation of aluminium tube with 150 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-150-E are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-150-Е50-4 UHL1
AIZ-150-Е60-4 UHL1
AIZ-150-Е70-4 UHL1
AIZ-150-Е80-4 UHL1
AIZ-150-Е90-4 UHL1
AIZ-150-Е100-4 UHL1
AIZ-150-Е110-4 UHL1
AIZ-150-Е120-4 UHL1
AIZ-150-Е130-4 UHL1
AIZ-150-Е140-4 UHL1
AIZ-150-Е150-4 UHL1
AIZ-150-Е170-4 UHL1
AIZ-150-Е200-4 UHL1
AIZ-150-Е250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
1680
1690
1690
1698
1714
1720
1720
1722
1735
1750
1750
1770
1790
1790
30,0
30,0
30,1
30,2
30,4
30,7
32,5
32,8
32,9
33,0
33,3
33,5
33,7
33,9
BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ-150-Е...-4 UHL1
LD
H
Ø18
4 hol. Ø220
Ø178
Connecting dimensions of bottom flange
52AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
GOST R 52082-03, TU3494-005-59116459-05
150150
172172
150150
1010
1010
11
390 390
650650
40
1480 1480
1
178х4 hol. 18
AIZ-220-А1-4 UHL1 185; 240; 300185/24; 185/29;205/27; 240/32;
240/39- - 17,5 - 22,1 2130
AIZ-220-А2-4 UHL1 350; 400
300/39; 300/48;330/30; 330/43;400/51; 400/64;450/56; 500/27
- - 24,0 - 29,4 2133
AIZ-220-А3-4 UHL1550; 600; 650;
700; 750
500/26; 500/64;550/71; 600/72;650/79; 700/86
240,300
- 30,0 - 36,2 2136
AIZ-220-А4-4 UHL1 - - - 500 45,0 2142
450; 500
AND WIRES FIXATION AIZ--220-А...-4 UHL1
CONDITIONAL DESIGNATION
220 - nominal voltage, kV
А -modification of bus bar support for one wire
4 - pollution level according GOST 9920, IEC60815, IEC60694
UHL1 -
220
252
220
10
8
2
570
75
950
29
AIZ-brand of polymeric bus- bar supports
AIZ-220-А...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-220-А...-4 UHL1
TECHNICAL CHARACTERISTICS
1,2,3,4 - modification according cross section and type of wire
100
1480
1
225х4 hol. 18
Ø265Ø18
Ø225
4 hol.
B
А
B
H
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-07
Wires according GOST 839-80, type
Wires according TS16-505.397-72
Diameter of wires,
mmH max,
mmА, АKPАS,АSКS, АSКP, ASK
PM PА
Nominal cross-section, kv, mm2
Type of flexible bus-bar support
AIZ-220-A...-4 UHL1
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ 53
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
AIZ-220-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS
CONDITIONAL DESIGNATION
220 - nominal voltage, kV
1,2,3,4 - modification according cross section and type of wire
4 - pollution level according GOST 9920, IEC60815, IEC60694
220
252
220
10
8
1
570
950
29
AIZ-brand of polymeric bus- bar supports
AIZ-220-B...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-220-B...-4 UHL1
TECHNICAL CHARACTERISTICS
B - modification of bus-bar support for two wires
225х4 hol. 18
100
1480
see table
2
AIZ-220-B1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-220-B2-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-220-B3-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
AIZ-220-B5-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-220-B6-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-220-B7-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
AIZ-220-B8-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-220-B9-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-220-B10-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
AIZ-220-B11-4 UHL1 185; 240; 300185/24; 185/29; 205/27;
205/27; 240/39
AIZ-220-B12-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-220-B13-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
60
60
60
120
120
120
200
200
200
400
400
400
74,8
74,8
74,9
75,3
75,2
75,1
75,5
75,6
75,8
76,8
77,1
77,4
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
2130
2133
2136
2147
2150
2153
2147
2150
2153
2147
2150
2153
H
А
Ø18
4 hol.
А
Ø265
Ø225
L L
H
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR AIZ-220-B...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-05
Wires according GOST 839-80, type
А, АKP АS, АSКS,АSКP, АSК
Nominal cross-section, mm2 D
ista
nce
b
etw
een
w
ires
, L
, mmType of flexible
bus-bar supportWeight ,
kgDiameter
of wires,mm
H max,mm
climate desing and category of spasingUHL1 - according GOST 15150, IEC60721, IEC60068
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R АИЗ, Лыткарино
АИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
FLEXIBILE BUS-BAR FIXATION AIZ--220-B...-4 UHL1AIZ-220-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”.
54
BUS-BAR FIXATION AIZ--220-V...-4 UHL1
CONDITIONAL DESIGNATION
220 - nominal voltage, kV
V- modification for two hollow wires
4 - pollution level according GOST 9920, IEC60815, IEC60694
UHL1 -
220
252
220
10
8
2
570
see table
950
29
AIZ-brand of polymeric bus- bar supports
AIZ-220-V...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-220-V...-4 UHL1
TECHNICAL CHARACTERISTICS
1,2,3 - modification according cross section and type of wire
100
1480
2
AIZ-220-В1-4 UHL1 2142 77,8
AIZ-220-В2-4 UHL1 2162 78,0
500 65 45,0
500 120 45,0
AIZ-220-В3-4 UHL1 2162 78,0 500 200 45,0
1
2
2
225х4 hol. 18
L
Pic.1
Ø265Ø18
Ø225
4 hol.
H
Pic.2
Connection dimensions of bottom flange
L
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-07
2
Weight ,kg
Nominalcross-section
mm
Distance between
wires, L, mm,
Pic.№Type of flexible bus-bar support
Diameter of wires,
mm
H max,mm
Wires according TS16-505.397-72
AIZ-220-V...-4 UHL1
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ 55
AIZ-220-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068according GOST 15150, IEC60721, IEC60068
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
AIZ-220-G1-4 UHL1 2142 77,8
AIZ-220-G2-4 UHL1 2162 78,0
500 65 45,0
500 120 45,0
AIZ-220-G3-4 UHL1 2162 78,0 500 200 45,0
1
2
2
BUS-BAR AIZ--220-G1-4 UHL1, AIZ-220-G2-4 UHL1, AIZ-220-G3-4 UHL1
CONDITIONAL DESIGNATION
220 - nominal voltage, kV
1,2,3 - bus-bar fitting modification
4 - pollution level according GOST 9920, IEC60815, IEC60694
220
252
220
10
8
2
570
950
29
AIZ-brand of polymeric bus- bar supports
AIZ-220-G...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-220-G...-4 UHL1
TECHNICAL CHARACTERISTICS
G - modification for three hollow wires
100
1480
see table
3
225х4 hol. 18
H
Ø184 hol. Ø265
Ø225
L LL
Connection dimensions of bottom flange
L
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR AIZ-220-G...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-05
2
Weight ,kg
Nominalcross-section
mm
Distance between
wires, L, mm,
Pic.№Type of flexible bus-bar support
Diameter of wires,
mm
H max,mm
Wires according TS16-505.397-72
climate desing and category of spasingUHL1 - according GOST 15150, IEC60721, IEC60068
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R АИЗ, Лыткарино
АИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works.The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
AIZ-220-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF FLEXIBLE
56
CONVENTIONAL MARKING
Z -rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ (ШОП)-10-Z...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
30-250- rigid fastening of aluminum tube bus bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV10-
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBESAIZ-220-Z...-4 UHL1
29
AIZ -220-Z...-4 UHL1
POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ-220-Z...-4 UHL1 The outdoor bus- bar supports AIZ-220-Z are used for aluminum tubular bus-bar support with 220 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-220-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request
AIZ-220-Z30-4 UHL1
AIZ-220-Z40-4 UHL1
AIZ-220-Z50-4 UHL1
AIZ-220-Z70-4 UHL1
AIZ-220-Z80-4 UHL1
AIZ-220-Z90-4 UHL1
AIZ-220-Z100-4 UHL1
AIZ-220-Z110-4 UHL1
AIZ-220-Z120-4 UHL1
AIZ-220-Z130-4 UHL1
AIZ-220-Z140-4 UHL1
AIZ-220-Z150-4 UHL1
AIZ-220-Z170-4 UHL1
AIZ-220-Z200-4 UHL1
AIZ-220-Z250-4 UHL1
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
30/25
40/35
50/45
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
30
40
50
70
80
90
100
110
120
130
140
150
170
200
250
2179
2179
2180
2190
2198
2202
2214
2220
2222
2235
2240
2250
2270
2290
2315
76,1
76,2
76,5
76,8
78,0
78,3
78,5
78,7
79,3
81,3
81,3
82,4
83,5
87,5
83,5
Ø184 hol. Ø265
Ø225
Connecting dimensions of bottom flange
DD
Pic.1
H
Pic.2
57AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
Рic.№
CONVENTIONAL MARKING
AIZ - brand of polymeric bus bar supports
Z -rigid fastening of aluminum tube bus bar
nominal voltage, kV10-
220
252
220
10
8
2
570
950
100
1480
1
225х4 hol. 18
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-220-SH...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
SH - hinging of aluminum tube bus-bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV220-
CONVENTIONAL MARKINGCONVENTIONAL MARKING
D
Ø18
4 hol. Ø220
Ø178
Connecting dimensions of bottom flange
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-220-SH50-4 UHL1 - AIZ-220-SH250-4 UHL1
29
AIZ -220-SH...-4 UHL1
The bus- bar supports of outdoor application AIZ-220-SH are used for hinged fastening of tubular rigid bus-bar at 220 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-220-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-220-SH50-4 UHL1
AIZ-220-SH60-4 UHL1
AIZ-220-SH70-4 UHL1
AIZ-220-SH80-4 UHL1
AIZ-220-SH90-4 UHL1
AIZ-220-SH100-4 UHL1
AIZ-220-SH110-4 UHL1
AIZ-220-SH120-4 UHL1
AIZ-220-SH130-4 UHL1
AIZ-220-SH140-4 UHL1
AIZ-220-SH150-4 UHL1
AIZ-220-SH170-4 UHL1
AIZ-220-SH200-4 UHL1
AIZ-220-SH250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
2190
2200
2225
2230
2230
2235
2245
2245
2255
2260
2260
2280
2310
2315
78,0
78,0
78,5
79,0
79,4
80,0
80,5
80,5
81,0
81,5
81,7
83,5
85,2
86,9
BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-220-SH..
H
58AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
220
252
220
10
8
2
570
950
100
1480
1
178х4 hol. 18
CONVENTIONAL MARKING
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-220-D...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV220-
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
D-movable fastening of aluminum tube bus-bar
50-250- rigid fastening of aluminum tube bus bar
D
Ø18
4 hol. Ø220
Ø178
Connecting dimensions of bottom flange
H
AIZ-220-D50-4 UHL1
AIZ-220-D60-4 UHL1
AIZ-220-D70-4 UHL1
AIZ-220-D80-4 UHL1
AIZ-220-D90-4 UHL1
AIZ-220-D100-4 UHL1
AIZ-220-D110-4 UHL1
AIZ-220-D120-4 UHL1
AIZ-220-D130-4 UHL1
AIZ-220-D140-4 UHL1
AIZ-220-D150-4 UHL1
AIZ-220-D170-4 UHL1
AIZ-220-D200-4 UHL1
AIZ-220-D250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BARAIZ-220-D...-4 UHL1
220
252
220
10
8
2
570
950
29
AIZ -220-D...-4 UHL1
100
1480
1
178х4 hol. 18
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-220-D...-4 UHL1 The outdoor bus- bar supports AIZ-220-D are used for flexible fitting of aluminium tubular bus-bar support with 220 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-220-D are included in the integrated rigid bus-bar project of substations.
2190
2200
2225
2230
2230
2235
2245
2245
2255
2260
2260
2280
2310
2315
78,0
78,0
78,5
79,0
79,4
80,0
80,5
80,5
81,0
81,5
81,7
83,5
85,2
86,9
59AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
CONVENTIONAL MARKING
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-220-К...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
К - end fastening of aluminum tube bus bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV220-
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ-220-К...-4 UHL1
29
AIZ -220-К...-4 UHL1
The outdoor bus- bar supports AIZ-220-K are used for end fixation of aluminium tubular bus-bar support with 220 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-220-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.
AIZ-220-К50-4 UHL1
AIZ-220-К60-4 UHL1
AIZ-220-К70-4 UHL1
AIZ-220-К80-4 UHL1
AIZ-220-К90-4 UHL1
AIZ-220-К100-4 UHL1
AIZ-220-К110-4 UHL1
AIZ-220-К120-4 UHL1
AIZ-220-К130-4 UHL1
AIZ-220-К140-4 UHL1
AIZ-220-К150-4 UHL1
AIZ-220-К170-4 UHL1
AIZ-220-К200-4 UHL1
AIZ-220-К250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
2155
2158
2185
2190
2190
2205
2205
2210
2220
2230
2260
2280
2310
2315
75,0
75,0
75,1
75,2
75,4
75,7
75,5
77,8
77,9
78,0
78,3
78,5
78,7
78,9
BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ-220-К...-4 UHL1
Ø18
4 hol. Ø220
Ø178
Connecting dimensions of bottom flange
D
H
60AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
220
252
220
10
8
2
570
950
100
1480
1
178х4 hol. 18
CONVENTIONAL MARKING
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ- 220-I...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
I -movable connection of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV220 -
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
H Ø18
4 hol. Ø220
Ø178
Connecting dimensions of bottom flange
AIZ-220-I50-4 UHL1
AIZ-220-I60-4 UHL1
AIZ-220-I70-4 UHL1
AIZ-220-I80-4 UHL1
AIZ-220-I90-4 UHL1
AIZ-220-I100-4 UHL1
AIZ-220-I110-4 UHL1
AIZ-220-I120-4 UHL1
AIZ-220-I130-4 UHL1
AIZ-220-I140-4 UHL1
AIZ-220-I150-4 UHL1
AIZ-220-I170-4 UHL1
AIZ-220-I200-4 UHL1
AIZ-220-I250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
78,0
78,0
78,5
79,0
79,4
80,0
80,5
80,5
81,0
81,5
81,7
83,5
85,2
86,9
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBEAIZ-220-I...-4 UHL1
220
252
220
10
8
2
570
950
29
AIZ -220-I...-4 UHL1
100
1480
1
178х4 hol. 18
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ-220-I...-4 UHL1 The outdoor bus- bar supports AIZ-220-I are used for flexible connection of aluminium tubular bus-bar support with 220 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06.The bus-bar supports AIZ-220-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
360
360
400
400
420
420
450
460
460
460
480
500
520
520
2190
2200
2225
2230
2230
2235
2245
2245
2255
2260
2260
2280
2210
2215
61AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
SizeL, мм
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-220-Е...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
Е - double-grip of aluminum tube
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV220-
BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBE AIZ-220-Е...-4 UHL1
29
AIZ -220-Е...-4 UHL1
The outdoor bus- bar supports AIZ-220-E are used for double fixation of aluminium tube with 220 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-220-E are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-220-Е50-4 UHL1
AIZ-220-Е60-4 UHL1
AIZ-220-Е70-4 UHL1
AIZ-220-Е80-4 UHL1
AIZ-220-Е90-4 UHL1
AIZ-220-Е100-4 UHL1
AIZ-220-Е110-4 UHL1
AIZ-220-Е120-4 UHL1
AIZ-220-Е130-4 UHL1
AIZ-220-Е140-4 UHL1
AIZ-220-Е150-4 UHL1
AIZ-220-Е170-4 UHL1
AIZ-220-Е200-4 UHL1
AIZ-220-Е250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
2180
2190
2190
2198
2214
2220
2220
2222
2235
2250
2250
2270
2290
2290
76,0
76,0
76,1
76,2
76,4
76,7
78,5
78,8
78,9
79,0
79,3
79,5
79,7
79,9
BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ-220-Е...-4 UHL1
LD
Ø18
4 hol. Ø220
Ø178
Connecting dimensions of bottom flange
H
62AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
220
252
220
10
8
2
570
950
100
1480
1
178х4 hol. 18
CONVENTIONAL MARKING
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-220-S...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
S - for the installation of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV220 -
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
AIZ-220-С50-4 UHL1
AIZ-220-С60-4 UHL1
AIZ-220-С70-4 UHL1
AIZ-220-С80-4 UHL1
AIZ-220-С90-4 UHL1
AIZ-220-С100-4 UHL1
AIZ-220-С110-4 UHL1
AIZ-220-С120-4 UHL1
AIZ-220-С130-4 UHL1
AIZ-220-С140-4 UHL1
AIZ-220-С150-4 UHL1
AIZ-220-С170-4 UHL1
AIZ-220-С200-4 UHL1
AIZ-220-С250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
93,5
94,6
95,0
96,0
97,2
98,0
98,5
100,0
103,0
104,0
105,0
108,0
174,0
182,0
BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBESAIZ-220-S...-4 UHL1
220
252
220
10
8
2
570
950
29
AIZ -220-S...-4 UHL1
100
1480
1
178х4 hol. 18
BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ-220-S...-4 UHL1
The outdoor bus- bar supports AIZ-220-S are used for installation of two aluminium tubes with 220 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-220-S are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years.Please indicate and fill data sheet if it is necessary to install tubes with different diameter. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.
870
870
870
870
870
870
870
870
870
870
870
870
870
870
2190
2200
2225
2230
2230
2235
2245
2245
2255
2260
2260
2280
2310
2315
D
H
L
Installation choices for bus bar.The arrows indicate the axis
aluminum tuberigid busbar
Ø184 hol. Ø220
Ø178
Connecting dimensions of bottom flange
63AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
SizeL, мм
AIZ-330-А1-4 UHL1 185; 240; 300185/24; 185/29;205/27; 240/32;
240/39- - 17,5 - 22,1 2972
AIZ-330-А2-4 UHL1 350; 400
300/39; 300/48;330/30; 330/43;400/51; 400/64;450/56; 500/27
- - 24,0 - 29,4 2975
AIZ-330-А3-4 UHL1550; 600; 650;
700; 750
500/26; 500/64;550/71; 600/72;650/79; 700/86
240,300
- 30,0 - 36,2 2978
AIZ-330-А4-4 UHL1 - - - 500 45,0 2984
450; 500
AND WIRES FIXATION AIZ-330-А...-4 UHL1
CONDITIONAL DESIGNATIONCONDITIONAL DESIGNATION
330 - nominal voltage, kV330 - nominal voltage, kV
А -modification of bus bar support for one wireА -modification of bus bar support for one wire
4 - pollution level according GOST 9920, IEC60815, IEC606944 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068according GOST 15150, IEC60721, IEC60068
UHL1 - UHL1 -
330330
363363
315315
3030
88
950950
920 920
150150
11751175
2929
AIZ-brand of polymeric bus- bar supportsAIZ-brand of polymeric bus- bar supports
AIZ-330-А...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-330-А...-4 UHL1
TECHNICAL CHARACTERISTICTECHNICAL CHARACTERISTIC
1,2,3,4 - modification according cross section and type of wire1,2,3,4 - modification according cross section and type of wire
160 160
1480 1480
11
300х8 hol. 18300х8 hol. 18
Ø340
Ø18
Ø300
8 hol.
B
H
B
64
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-07
Wires according GOST 839-80, type
Wires according TS16-505.397-72
Diameter of wires,
mmH max,
mmА, АKPАS,АSКS, АSКP, ASK
PM PА
Nominal cross-section, kv, mm2
Type of flexible bus-bar support
AIZ-330-A...-4 UHL1
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works.The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
AIZ-330-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS
CONDITIONAL DESIGNATION
330 - nominal voltage, kV
1,2,3,4 - bus-bar fitting modification
4 - pollution level according GOST 9920, IEC60815, IEC60694
330
363
315
30
8
950
920
1175
29
AIZ-brand of polymeric bus- bar supports
AIZ-330-B...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-330-B...-4 UHL1
TECHNICAL CHARACTERISTICS
B - modification of bus-bar support for two wires
300х8 hol. 18
160
1480
see table
2
AIZ-330-B1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-330-B2-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-330-B3-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
AIZ-330-B5-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-330-B6-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-330-B7-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
AIZ-330-B8-4 UHL1 185; 240; 300 185/24; 185/29; 205/27;205/27; 240/39
AIZ-330-B9-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-330-B10-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
AIZ-330-B11-4 UHL1 185; 240; 300185/24; 185/29; 205/27;
205/27; 240/39
AIZ-330-B12-4 UHL1350; 400 300/39; 300/48;330/30; 330/43
400/51; 400/64; 450/56; 500/27
AIZ-330-B13-4 UHL1550; 600; 650;
700; 750500/26; 500/64;550/71; 600/72650/79; 700/86; ПМ240;ПМ300
450; 500
60
60
60
120
120
120
200
200
200
400
400
400
154,8
154,8
154,9
155,3
155,2
155,1
155,5
155,6
155,8
156,8
157,1
157,4
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
17,5-22,1
24,0-29,4
30,0-36,2
2972
2975
2978
2989
2992
2995
2989
2992
2995
2989
2992
2995
А
H
LL
Ø340
Ø18
Ø300
8 hol.
B
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR AIZ-330-B...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-05
Wires according GOST 839-80, type
А, АKP АS, АSКS,АSКP, АSК
Nominal cross-section, mm2 D
ista
nce
b
etw
een
w
ires
, L
, mmType of flexible
bus-bar supportWeight ,
kgDiameter
of wires,mm
H max,mm
climate desing and category of spasingUHL1 - according GOST 15150, IEC60721, IEC60068
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R АИЗ, Лыткарино
АИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
FLEXIBILE BUS-BAR FIXATION AIZ--330-B...-4 UHL1AIZ-330-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”.
65
FLEXIBILE BUS-BAR FIXATION AIZ--330-V...-4 UHL1
CONDITIONAL DESIGNATION
330 - nominal voltage, kV
V- modification for two hollow wires
4 - pollution level according GOST 9920, IEC60815, IEC60694
UHL1 -
330
363
315
30
8
950
920
see table
1175
29
AIZ-brand of polymeric bus- bar supports
AIZ-330-V...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-330-V...-4 UHL1
TECHNICAL CHARACTERISTICS
1,2,3 - modification according cross section and type of wire
160
1480
2
AIZ-330-В1-4 UHL1 2142 157,8
AIZ-330-В2-4 UHL1 2162 158,0
500 65 45,0
500 120 45,0
AIZ-330-В3-4 UHL1 2162 158,0 500 200 45,0
1
2
2
300х8 hol. 18
H
Pic.2
L
Pic.1
L
Ø340Ø18
Ø300
8 hol.
B
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-07
2
Weight ,kg
Nominalcross-section
mm
Distance between
wires, L, mm,
Pic.№Type of flexible bus-bar support
Diameter of wires,
mm
H max,mm
Wires according TS16-505.397-72
AIZ-330-V...-4 UHL1
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ 66
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
AIZ-330-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works.The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
AIZ-330-G1-4 UHL1 3014 157,8
AIZ-330-G2-4 UHL1 3034 158,0
500 65 45,0
500 120 45,0
AIZ-330-G3-4 UHL1 3034 158,0 500 200 45,0
1
2
2
FLEXIBILE BUS-BAR AIZ--330-G...-4 UHL1
CONDITIONAL DESIGNATION
330 - nominal voltage, kV
1,2,3 - bus-bar fitting modification
4 - pollution level according GOST 9920, IEC60815, IEC60694
330
363
315
30
8
950
920
1175
29
AIZ-brand of polymeric bus- bar supports
AIZ-330-G...-4 UHL1
POLYMER BUS-BAR SUPPORTS AIZ-330-G...-4 UHL1
TECHNICAL CHARACTERISTICS
G - modification for three hollow wires
160
1480
see table
3
300х8 hol. 18
L LL
Connection dimensions of bottom flange
L
H Ø340
Ø18
Ø300
8 hol.
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
Minimum creepage distance, cm
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted
TYPE TESTS FOR AIZ-330-G...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to coloring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
GOST R 52082-03, TS3494-005-59116459-05
2
Weight ,kg
Nominalcross-section
mm
Distance between
wires, L, mm,
Pic.№Type of flexible bus-bar support
Diameter of wires,
mm
H max,mm
Wires according TS16-505.397-72
climate desing and category of spasingUHL1 - according GOST 15150, IEC60721, IEC60068
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R
АИЗ, ЛыткариноАИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
АИЗ - зареGистрированный товарный знак GрUппы предприятий “АрматUрно-изоляторный завод”R АИЗ, Лыткарино
АИЗ, ТUлаАИЗ, БеларUSьАИЗ, КазахстанАИЗ, Литва
www.insulators.ruw w w . t a i z . r uw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ t a i z . r um a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+7-4872-316844+375-222455264+7725-2-561716+370-62749925
AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage”. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works.The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
AIZ-330-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF
67
CONVENTIONAL MARKING
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-330-Е...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
Е - double-grip of aluminum tube
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV330-
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBEAIZ-330-Е...-4 UHL1
29
AIZ -330-Е...-4 UHL1
The outdoor bus- bar supports AIZ-330-E are used for double fixation of aluminium tube with 330 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-330-E are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-330-Е50-4 UHL1
AIZ-330-Е60-4 UHL1
AIZ-330-Е70-4 UHL1
AIZ-330-Е80-4 UHL1
AIZ-330-Е90-4 UHL1
AIZ-330-Е100-4 UHL1
AIZ-330-Е110-4 UHL1
AIZ-330-Е120-4 UHL1
AIZ-330-Е130-4 UHL1
AIZ-330-Е140-4 UHL1
AIZ-330-Е150-4 UHL1
AIZ-330-Е170-4 UHL1
AIZ-330-Е200-4 UHL1
AIZ-330-Е250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
3052
3062
3062
3070
3086
3092
3092
3094
3107
3122
3122
3142
3162
3162
158,0
158,0
158,1
158,2
158,4
158,7
160,5
160,8
160,9
161,0
161,3
161,5
161,7
161,9
BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ-330-Е...-4 UHL1
L
Connecting dimensions of bottom flange
Ø340
Ø18
Ø300
8 hol.
H
D
68AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
330
363
315
30
8
950
920
1175
160
1480
1
300х8 hol. 18
CONVENTIONAL MARKING
Z -rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-330-Z...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
30-250- rigid fastening of aluminum tube bus bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV330 -
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBESAIZ-330-Z...-4 UHL1
330
363
315
30
8
950
920
1175
29
AIZ -330-Z...-4 UHL1
160
1480
1
300х8 hol. 18
The outdoor bus- bar supports AIZ-330-Z are used for aluminum tubular bus-bar support with 330 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-330-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request
AIZ-330-Z30-4 UHL1
AIZ-330-Z40-4 UHL1
AIZ-330-Z50-4 UHL1
AIZ-330-Z70-4 UHL1
AIZ-330-Z80-4 UHL1
AIZ-330-Z90-4 UHL1
AIZ-330-Z100-4 UHL1
AIZ-330-Z110-4 UHL1
AIZ-330-Z120-4 UHL1
AIZ-330-Z130-4 UHL1
AIZ-330-Z140-4 UHL1
AIZ-330-Z150-4 UHL1
AIZ-330-Z170-4 UHL1
AIZ-330-Z200-4 UHL1
AIZ-330-Z250-4 UHL1
2
2
2
2
2
2
2
1
1
1
1
1
1
1
1
30/25
40/35
50/45
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
30
40
50
70
80
90
100
110
120
130
140
150
170
200
250
3051
3051
3052
3062
3070
3074
3086
3092
3094
3107
3112
3122
3142
3162
3187
156,1
156,2
156,5
156,8
158,0
158,3
158,5
158,7
159,3
161,3
161,3
162,4
163,5
167,5
163,5
DD
Pic.1 Pic.2
H
Ø340
Ø18
Ø300
8 hol.
69AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Рic.№Diameter
of rigid bus-bar tube, mm
POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ-330-Z
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-330-SH...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
SH - hinging of aluminum tube bus-bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
nominal voltage, kV330-
CONVENTIONAL MARKING
see table
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-330-SH50-4 UHL1 - AIZ-330-SH250-4 UHL1
29
AIZ -330-SH...-4 UHL1
The bus- bar supports of outdoor application AIZ-330-SH are used for hinged fastening of tubular rigid bus-bar at 330 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-330-SH are included in the integrated rigid bus- bar project of substations.Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
AIZ-330-SH50-4 UHL1
AIZ-330-SH60-4 UHL1
AIZ-330-SH70-4 UHL1
AIZ-330-SH80-4 UHL1
AIZ-330-SH90-4 UHL1
AIZ-330-SH100-4 UHL1
AIZ-330-SH110-4 UHL1
AIZ-330-SH120-4 UHL1
AIZ-330-SH130-4 UHL1
AIZ-330-SH140-4 UHL1
AIZ-330-SH150-4 UHL1
AIZ-330-SH170-4 UHL1
AIZ-330-SH200-4 UHL1
AIZ-330-SH250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-330-SH
Connecting dimensions of bottom flange
Ø340
Ø18
Ø300
8 hol.
H
D
3062
3072
3097
3102
3102
3107
3117
3117
3127
3132
3132
3152
3182
3187
160,0
160,0
160,5
161,0
161,4
162,0
162,5
162,5
163,0
163,5
163,7
165,5
167,2
168,9
70AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
330
363
315
30
8
950
920
1175
160
1480
1
300х8 hol. 18
CONVENTIONAL MARKING
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-330-D...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV330-
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
D-movable fastening of aluminum tube bus-bar
50-250- rigid fastening of aluminum tube bus bar
Connecting dimensions of bottom flange
Ø340
Ø18
Ø300
8 hol.
HD
AIZ-330-D50-4 UHL1
AIZ-330-D60-4 UHL1
AIZ-330-D70-4 UHL1
AIZ-330-D80-4 UHL1
AIZ-330-D90-4 UHL1
AIZ-330-D100-4 UHL1
AIZ-330-D110-4 UHL1
AIZ-330-D120-4 UHL1
AIZ-330-D130-4 UHL1
AIZ-330-D140-4 UHL1
AIZ-330-D150-4 UHL1
AIZ-330-D170-4 UHL1
AIZ-330-D200-4 UHL1
AIZ-330-D250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-330-D...-4 UHL1
330
363
315
30
8
950
920
1175
29
AIZ -330-D...-4 UHL1
160
1480
1
BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-330-D...-4 UHL1 The outdoor bus- bar supports AIZ-330-D are used for flexible fitting of aluminium tubular bus-bar support with 330 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-330-D are included in the integrated rigid bus-bar project of substations.
3062
3072
3097
3102
3102
3107
3117
3117
3127
3132
3132
3152
3182
3187
160,0
160,0
160,5
161,0
161,4
162,0
162,5
162,5
163,0
163,5
163,7
165,5
167,2
168,9
300х8 hol. 18
71AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
CONVENTIONAL MARKING
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ-330-К...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ - brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
К - end fastening of aluminum tube bus bar
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV330-
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ-330-К...-4 UHL1
29
AIZ -330-К...-4 UHL1
The outdoor bus- bar supports AIZ-330-K are used for end fixation of aluminium tubular bus-bar support with 330 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06.The bus-bar supports AIZ-330-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.
AIZ-330-К50-4 UHL1
AIZ-330-К60-4 UHL1
AIZ-330-К70-4 UHL1
AIZ-330-К80-4 UHL1
AIZ-330-К90-4 UHL1
AIZ-330-К100-4 UHL1
AIZ-330-К110-4 UHL1
AIZ-330-К120-4 UHL1
AIZ-330-К130-4 UHL1
AIZ-330-К140-4 UHL1
AIZ-330-К150-4 UHL1
AIZ-330-К170-4 UHL1
AIZ-330-К200-4 UHL1
AIZ-330-К250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
3027
3030
3057
3062
3062
3077
3077
3082
3092
3102
3132
3152
3182
3187
157,0
157,0
157,1
157,2
157,4
157,7
157,5
159,8
159,9
160,0
160,3
160,5
160,7
160,9
BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ-330-К...-4 UHL1
D
Connecting dimensions of bottom flange
Ø340
Ø18
Ø300
8 hol.
H
72AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
330
363
315
30
8
950
920
1175
160
1480
1
300х8 hol. 18
CONVENTIONAL MARKING
50-250- rigid fastening of aluminum tube bus bar
4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasingaccording GOST 15150, IEC60721, IEC60068
UHL1 -
Nominal voltage, kV
Highest working voltage, kV
Minimum lightning impulse withstandvoltage, kV
50%- discharge voltage ofindustrial frequency atpolluted and humid conditions, kV
For specified surface conductivityof polluted layer, mkCm
Minimum failing torsionmoment, kNxm
Minimum failing load atbending, kN
TYPE TESTS FOR AIZ- 330-I...-4 UHL1
Assemblage
External inspection ( outer view and marking )
Weight, length of insulating part,fitting dimensions, armature spacingcorrespondence
Quality and thickness of armature’santicorrosional coating
Alternating short term test voltagein dry condition
Evaluation of partial discharge level
Hydrophobic resistance to water
Hydrophobic resistance to colouring liquid
Adhesion of coating layer to insulating body
Failing load at bending (torsion )
Minimum creepage distance, cm
Testing load at bending ( torsion ) 1 min. withstand.Deviation angle control at bending ( torsion ) andabsence of plastic deformation at bending ( torsion )
AIZ- brand of polymeric bus bar supports
TECHNICAL CHARACTERISTICS
GOST R 52082-03, TU3494-005-59116459-05
I -movable connection of two aluminum tubes
Weight, not more than, kg
Bottom flange fitting dimensions, mm
The highest peak of the nominalshort-term withstandcurrent (current of the electrodynamicstability), kA
Permissible tension of wires inhorizontal plane of bus bar supports for connecting of wires, N
Number of bus bar mounted
see table
nominal voltage, kV330 -
CONVENTIONAL MARKINGCONVENTIONAL MARKINGCONVENTIONAL MARKING
H
AIZ-330-I50-4 UHL1
AIZ-330-I60-4 UHL1
AIZ-330-I70-4 UHL1
AIZ-330-I80-4 UHL1
AIZ-330-I90-4 UHL1
AIZ-330-I100-4 UHL1
AIZ-330-I110-4 UHL1
AIZ-330-I120-4 UHL1
AIZ-330-I130-4 UHL1
AIZ-330-I140-4 UHL1
AIZ-330-I150-4 UHL1
AIZ-330-I170-4 UHL1
AIZ-330-I200-4 UHL1
AIZ-330-I250-4 UHL1
50/45
60/54
70/64
80/72
90/80
100/90
110/100
120/110
130/116
140/120
150/136
170/156
200/180
250/230
50
60
70
80
90
100
110
120
130
140
150
170
200
250
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBE AIZ-330-I...-4 UHL1
330
363
315
30
8
950
920
1175
29
AIZ -330-I...-4 UHL1
160
1480
1
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ-330-I...-4 UHL1
The outdoor bus- bar supports AIZ-330-I are used for flexible connection of aluminium tubular bus-bar support with 330 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-330-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request
360
360
400
400
420
420
450
460
460
460
480
500
520
520
300х8 hol. 18
3062
3072
3097
3102
3102
3107
3117
3117
3127
3132
3132
3152
3182
3187
160,0
160,0
160,5
161,0
161,4
162,0
162,5
162,5
163,0
163,5
163,7
165,5
167,2
168,9
Connecting dimensions of bottom flange
Ø340
Ø18
Ø300
8 hol.
73AIZ, RUSSIAAIZ, BELARUSAIZ, KAZAKHSTANAIZ, LITHUANIA
www.bus-bar.ruw w w . a i z . b yw w w . a i z . k zwww.bus-bar.eu
[email protected] a i l @ a i z . b ym a i l @ a i z . k [email protected]
+7-495-7412286+375-222455264+7-717-296-5353+370-62749925
AIZ- registrated trade mark of the group of companies AIZ
Building height H, mm
Weight, kgDiameterD, мм
Rigid bus barsupport type
Diameterof rigid bus-bar
tube, mm
SizeL, мм