Fire Alarm and Life Safety System Inspection Certificate For James Lick High School 57 North White Rd San Jose, CA 95127 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval. Inspection Date Jun 24, 2014 Building: James Lick High School Company: Intrepid Electronic Systems Contact: Anthony Revelo Contact: Michael Zinov Title: IT Title: Senior Technician

facilities.esuhsd.orgfacilities.esuhsd.org/wp-content/uploads/2016/01/02-Vol3-2014-0624...Fire Alarm and Life Safety System Inspection Certificate . For . James Lick High School 57

  • Upload
    votram

  • View
    216

  • Download
    0

Embed Size (px)

Citation preview

Fire Alarm and Life Safety System Inspection Certificate

For

James Lick High School 57 North White Rd San Jose, CA 95127

Tested to NFPA 72 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Inspection Date Jun 24, 2014

Building: James Lick High School Company: Intrepid Electronic Systems Contact: Anthony Revelo Contact: Michael Zinov

Title: IT Title: Senior Technician

Executive Summary Generated by: BuildingReports.com

Building Information Building: James Lick High School Contact: Anthony Revelo

Address: 57 North White Rd Phone: 408.347.5541

Address: Fax:

City/State/Zip: San Jose, CA 95127 Mobile:

Country: United States of America Email: [email protected]

Inspection Performed By Company: Intrepid Electronic Systems Inspector: Michael Zinov

Address: 6300 San Ignacio Avenue Phone: 510-597-9966

Address: Unit A Fax:

City/State/Zip: San Jose, CA 95119 Mobile: 510-774-0249

Country: United States of America Email: [email protected]

Monitoring Company: Phone: Account #:

Central Station Signal Verification Type: Digital Radio Mfg: AES Intellinet Model #: 7750-F-8

Test Time/Date: 5/1/14 8:21:30 PM Restore Time

Intrepid Electronic Systems 1 12/14/2014

Inspection Summary

Category Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Monitor 4 1.43% 4 100.00% 4 100.00% 0 0% Supervisory 1 0.36% 1 100.00% 1 100.00% 0 0% Auxiliary 17 6.09% 17 100.00% 15 88.24% 2 11.76% Indicating 9 3.23% 9 100.00% 9 100.00% 0 0% Initiating 199 71.33% 172 86.43% 169 98.26% 3 1.74% Control 49 17.56% 49 100.00% 49 100.00% 0 0%

Totals 279 100% 252 90.32% 247 98.02% 5 1.98%

Certification Company: Intrepid Electronic Systems Building: James Lick High School

Inspector: Michael Zinov Contact: Anthony Revelo

Signed: Signed:

Michael Zinov Certification Type Number

Intrepid Electronic Systems 2 12/14/2014

Discrepancy Report Generated by: BuildingReports.com

Building: James Lick High School Control Panel: 1

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is listed on the Consumer Product Safety Commission's website and is subject to a recall by the manufacturer is included. Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall by Manufacturer No recalled items found during this inspection.

ScanID Location Problem Address Reference

Auxiliary Elevator

18866671 North 1st Floor Elevator Machine Room Administration

Inaccessible 1-L1- D84 NFPA72 14.2.1.2.2

18866672 North 1st Floor Elevator Machine Room Administration

Inaccessible 1-L1- D85 NFPA72 14.2.1.2.2

Initiating Smoke Detector

18866668 1st Floor Administration Hall Elevator Lobby Inaccessible 1-L1- D39 NFPA72 17.4.5 18866675 2nd Floor Corridor Administration Building

Elevator Lobby Inaccessible 1-L1- D06 NFPA72 17.4.5

18866674 North 1st Floor Elevator Machine Room Administration

Inaccessible 1-L1- D07 NFPA72 17.4.5

Code References NFPA72 14.2.1.2.2 System defects and malfunctions shall be corrected. NFPA72 17.4.5 Initiating devices shall be installed in a manner that provides accessibility for periodic maintenance.

Intrepid Electronic Systems 3 12/14/2014

Proposed Solutions Report Generated by: BuildingReports.com

Building: James Lick High School Control Panel: 1

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

Auxiliary Elevator

18866671 North 1st Floor Elevator Machine Room Administration

RCE-95 T/M

18866672 North 1st Floor Elevator Machine Room Administration

RCE-95 T/M

Initiating Smoke Detector

18866668 1st Floor Administration Hall Elevator Lobby XP95-P T/M

18866675 2nd Floor Corridor Administration Building Elevator Lobby

XP95-P T/M

18866674 North 1st Floor Elevator Machine Room Administration

XP95-P T/M

Intrepid Electronic Systems 4 12/14/2014

Notes & Recommendations Generated by: BuildingReports.com

Building: James Lick High School Control Panel: 1

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

ScanID Note Device Type Location Comment

Auxiliary 18386345 1 Releasing Device ElectricalBuilding 200/300 Door Holders Passed

Second Floor Doors Don't Close Upon Alarm For Both Buildings. Doors need adjustment

Intrepid Electronic Systems 5 12/14/2014

Inspection & Testing Generated by: BuildingReports.com

Building: James Lick High School Control Panel: 1

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Passed Auxiliary

Damper Control Boys Locker Room Electrical Tested 4:44:24 PM 05/02/2014 Damper Control Northeast Classroom 1B Soffit

Fire Academy Tested 4:12:47 PM 05/01/2014

Fan Shutdown Boys Locker Room AHU Control Tested/Cleaned 4:08:27 PM 05/02/2014 Fan Shutdown Girls Locker Room AHU Control

Building Tested 3:00:49 PM 05/02/2014

Fan Shutdown HP-1 Shut Down Fire Academy

Tested 4:20:30 PM 05/01/2014

Fan Shutdown HP-2 Shut Down Fire Academy

Tested 4:19:13 PM 05/01/2014

Fan Shutdown Roof Administration Building A/C 1 SHUT DOWN

Tested 2:42:22 PM 05/05/2014

Fan Shutdown Roof Administration Building A/C 2 SHUT DOWN

Tested 2:41:49 PM 05/05/2014

Fan Shutdown Roof Administration Building A/C 3 SHUT DOWN

Tested 2:40:46 PM 05/05/2014

Fan Shutdown Roof Administration Building A/C 4 SHUT DOWN

Tested 2:40:11 PM 05/05/2014

Programmable Relay NORTH Bathroom Bld. Boys Tested 7:39:43 PM 05/02/2014 Programmable Relay NORTH Bathroom Bld. Boys Tested 4:43:57 PM 05/05/2014 Releasing Device ElectricalBuilding 200/300 Door Holders Tested 4:03:53 PM 05/19/2014 Releasing Device North 1st Floor Elevator Machine Room

Administration 1st Floor DH Tested/Cleaned 4:41:52 PM 05/05/2014

Releasing Device North 1st Floor Elevator Machine Room Administration 2nd Floor DH

Tested 4:41:46 PM 05/05/2014

Control Annunciator 1st Floor Administration Reception Tested 6:56:49 PM 05/02/2014 Annunciator 1st Floor Administration Reception Tested 6:56:53 PM 05/02/2014 Battery Boys Locker Room FACP Room Replaced 2:07:31 PM 05/06/2014 Battery Boys Locker Room FACP Room Replaced 2:08:30 PM 05/06/2014 Battery Boys Locker Room FACP Room Replaced 2:08:39 PM 05/06/2014 Battery Boys Locker Room FACP Room Replaced 2:08:46 PM 05/06/2014 Battery Boys Locker Room FACP Room Replaced 2:08:52 PM 05/06/2014 Battery Electrical

Building 600 Tested 7:52:08 PM 05/02/2014

Battery Electrical Building 600

Tested 7:52:11 PM 05/02/2014

Battery Fire academy FACP closet Replaced 2:09:26 PM 05/06/2014

Intrepid Electronic Systems 6 12/14/2014

Device Type Location Service Time Date

Passed Battery Fire academy FACP closet Replaced 2:09:47 PM 05/06/2014 Battery Multipurpose Building 900 Tested 8:20:28 PM 05/01/2014 Battery Multipurpose Building 900 Replaced 2:07:15 PM 05/06/2014 Battery Multipurpose Building 900 Replaced 2:07:24 PM 05/06/2014 Battery NORTH Bathroom Bld. Boys Tested 7:44:26 PM 05/02/2014 Battery NORTH Bathroom Bld. Boys Tested 7:44:30 PM 05/02/2014 Battery Press Box FCPS Tested 8:11:26 PM 05/02/2014 Battery Press Box FCPS Tested 8:11:29 PM 05/02/2014 Battery School Bank FCPS Room Tested 2:45:29 PM 05/02/2014 Battery School Bank FCPS Room Tested 2:45:39 PM 05/02/2014 Battery Second Floor FACP Student Services

MDF/SERVER Administration Building Tested 8:20:48 PM 05/02/2014

Battery Second Floor Student Services AES MDF/Server Administration Building

Tested 2:53:22 PM 05/01/2014

Battery Second Floor Student Services FACP Room Building Administration

Replaced 2:07:59 PM 05/06/2014

Battery Second Floor Student Services FACP Room Building Administration

Replaced 2:08:08 PM 05/06/2014

Battery Second Floor Student Services FACP Room Building Administration

Replaced 2:08:15 PM 05/06/2014

Battery Second Floor Student Services FCPS MDF/Server Administration Building

Tested 2:52:38 PM 05/01/2014

Battery Second Floor Student Services FCPS MDF/Server Administration Building

Tested 2:52:44 PM 05/01/2014

Battery Southeast First Floor Besides 304 Electrical Building 300

Tested 7:57:50 PM 05/02/2014

Battery Southeast First Floor Besides 304 Electrical Building 300

Tested 7:57:53 PM 05/02/2014

Battery Southwest Electrical Besides 706A Building 700 .

Tested 7:55:11 PM 05/02/2014

Battery Southwest Electrical Besides 706A Building 700 .

Tested 7:55:21 PM 05/02/2014

Battery Wrestling room Idf closet Tested 8:46:44 PM 05/01/2014 Battery Wrestling room Idf closet Tested 8:46:50 PM 05/01/2014 Communicator Boys Locker Room FACP Room Tested 8:37:08 PM 05/01/2014 Communicator FACP Room Building Administration Tested 2:53:26 PM 05/01/2014 Communicator Fire Academy FACP closet Tested 3:14:04 PM 05/01/2014 Communicator Multipurpose Building 900 Tested 8:21:30 PM 05/01/2014 Power Supply Boys Locker Room FACP Room Tested 8:34:48 PM 05/01/2014 Power Supply Electrical

Building 300 Conventional Heat Coverage Tested 7:57:58 PM 05/02/2014

Power Supply Electrical Building 600

Tested 7:51:47 PM 05/02/2014

Power Supply Electrical Building 700 Conventional Heat Coverage

Tested 7:55:27 PM 05/02/2014

Power Supply FACP Room Building Administration Tested 2:53:29 PM 05/01/2014 Power Supply NORTH Bathroom Bld. Boys Tested 7:39:38 PM 05/02/2014 Power Supply Pressbox Tested 8:11:33 PM 05/02/2014 Power Supply School Bank FCPS Room Tested 2:46:45 PM 05/02/2014 Power Supply Wrestling room IDF closet Tested 8:46:58 PM 05/01/2014

Intrepid Electronic Systems 7 12/14/2014

Device Type Location Service Time Date

Passed Indicating

Indicating Device Electrical Building 200 First Floor Smoke Detectors

Tested 3:13:06 PM 05/05/2014

Indicating Device Electrical Building 600 Conventional Heat Coverage

Tested 7:51:44 PM 05/02/2014

Indicating Device Electrical Building 700 Conventional Heat Coverage

Tested 7:55:31 PM 05/02/2014

Indicating Device FACP Room Building Administration Tested 2:53:36 PM 05/01/2014 Indicating Device FACP Room Building Administration Tested 2:53:40 PM 05/01/2014

Initiating Beam Detector Gymnasium Tested 3:23:29 PM 05/02/2014 Beam Detector Gymnasium Tested 3:23:30 PM 05/02/2014 Beam Detector Gymnasium Tested 3:23:33 PM 05/02/2014 Beam Detector Gymnasium Tested 3:23:37 PM 05/02/2014 Duct Detector Boys Locker Room Tested/Cleaned 8:40:51 PM 05/01/2014 Duct Detector Copy Room 126 Building Administration Tested/Cleaned 7:54:31 PM 05/01/2014 Duct Detector Corridor Girls Locker Room Tested/Cleaned 8:50:52 PM 05/01/2014 Duct Detector Multipurpose Building 900 Kitchen Above D22 Tested/Cleaned 8:00:20 PM 05/01/2014 Duct Detector Secretary 127 Building Administration Tested/Cleaned 7:46:08 PM 05/01/2014 Duct Detector Secretary 127 Building Administration Tested/Cleaned 7:46:41 PM 05/01/2014 Duct Detector Secretary 127 Building Administration Tested/Cleaned 7:50:23 PM 05/01/2014 Duct Detector West Cooridor Building Administration Tested/Cleaned 7:32:17 PM 05/01/2014 Duct Detector West Cooridor Building Administration Tested/Cleaned 7:37:36 PM 05/01/2014 Duct Detector West Cooridor Building Administration Tested/Cleaned 7:39:08 PM 05/01/2014 Initiating Device Electrical

Building 300 First Floor Smoke Detectors Tested 3:13:16 PM 05/05/2014

Initiating Device Fire academy FACP closet Tested 3:50:50 PM 05/01/2014 Pull Station 2nd MDF Admin Tested 6:42:10 PM 05/02/2014 Pull Station Gymnasium East Tested 3:19:50 PM 05/02/2014 Pull Station MDF Tested 6:40:43 PM 05/02/2014 Pull Station Multipurpose Building 900 Northeast Tested 5:20:39 PM 05/02/2014 Pull Station Multipurpose Building 900 Northwest Tested 5:21:18 PM 05/02/2014 Pull Station Multipurpose Building 900 Southeast Tested 5:19:26 PM 05/02/2014 Pull Station Multipurpose Building 900 Southwest Tested 5:16:53 PM 05/02/2014 Pull Station Northwest Gymnasium Southeast Tested 3:19:15 PM 05/02/2014 Pull Station South . Gym Vestibule Tested 4:38:28 PM 05/02/2014 Smoke Detector 1st Floor Administration Administrator APED Tested/Cleaned 7:13:44 PM 05/02/2014 Smoke Detector 1st Floor Administration Advisor Tested/Cleaned 7:22:43 PM 05/02/2014 Smoke Detector 1st Floor Administration Advisor Tested/Cleaned 7:27:07 PM 05/02/2014 Smoke Detector 1st Floor Administration APA Tested/Cleaned 7:21:05 PM 05/02/2014 Smoke Detector 1st Floor Administration Conference room Tested/Cleaned 7:30:11 PM 05/02/2014 Smoke Detector 1st Floor Administration Copy Room Tested/Cleaned 6:57:16 PM 05/02/2014 Smoke Detector 1st Floor Administration Counselor Tested/Cleaned 7:05:27 PM 05/02/2014 Smoke Detector 1st Floor Administration Counselor Tested/Cleaned 7:06:44 PM 05/02/2014 Smoke Detector 1st Floor Administration Counselor Tested/Cleaned 7:09:28 PM 05/02/2014 Smoke Detector 1st Floor Administration Counselor Tech Tested/Cleaned 7:08:03 PM 05/02/2014 Smoke Detector 1st Floor Administration English Office Tested/Cleaned 7:30:31 PM 05/02/2014 Smoke Detector 1st Floor Administration Hall Tested/Cleaned 6:44:35 PM 05/02/2014 Smoke Detector 1st Floor Administration Hall Tested/Cleaned 6:46:05 PM 05/02/2014

Intrepid Electronic Systems 8 12/14/2014

Device Type Location Service Time Date

Passed Smoke Detector 1st Floor Administration Hall Tested/Cleaned 6:47:06 PM 05/02/2014 Smoke Detector 1st Floor Administration Hall Tested/Cleaned 6:48:45 PM 05/02/2014 Smoke Detector 1st Floor Administration Hall Tested/Cleaned 7:30:23 PM 05/02/2014 Smoke Detector 1st Floor Administration Hallway Tested/Cleaned 6:50:05 PM 05/02/2014 Smoke Detector 1st Floor Administration Hallway Tested/Cleaned 7:02:40 PM 05/02/2014 Smoke Detector 1st Floor Administration Hallway Tested/Cleaned 7:12:10 PM 05/02/2014 Smoke Detector 1st Floor Administration Hallway Tested/Cleaned 7:18:36 PM 05/02/2014 Smoke Detector 1st Floor Administration Hallway Tested/Cleaned 7:24:26 PM 05/02/2014 Smoke Detector 1st Floor Administration Health Office Tested/Cleaned 7:19:38 PM 05/02/2014 Smoke Detector 1st Floor Administration IDF Tested/Cleaned 7:15:40 PM 05/02/2014 Smoke Detector 1st Floor Administration Liason Tested/Cleaned 7:28:08 PM 05/02/2014 Smoke Detector 1st Floor Administration Office Tested/Cleaned 6:52:39 PM 05/02/2014 Smoke Detector 1st Floor Administration Principal Tested/Cleaned 6:59:26 PM 05/02/2014 Smoke Detector 1st Floor Administration Principal Secretary's

Office Tested/Cleaned 7:00:54 PM 05/02/2014

Smoke Detector 1st Floor Administration Reception Tested/Cleaned 6:54:55 PM 05/02/2014 Smoke Detector 1st Floor Administration Registrar Tested/Cleaned 7:04:15 PM 05/02/2014 Smoke Detector 1st Floor Administration Security Tested/Cleaned 7:29:54 PM 05/02/2014 Smoke Detector 1st Floor Administration Workroom Tested/Cleaned 7:10:47 PM 05/02/2014 Smoke Detector 1st East Conference Administration Tested/Cleaned 6:58:52 PM 05/02/2014 Smoke Detector 2nd Corridor Administration Building Tested/Cleaned 6:34:21 PM 05/02/2014 Smoke Detector 2nd Corridor Administration Building Tested/Cleaned 6:35:04 PM 05/02/2014 Smoke Detector 2nd Corridor Administration Building Tested/Cleaned 6:35:33 PM 05/02/2014 Smoke Detector 2nd Corridor Building 200 Tested/Cleaned 3:36:55 PM 05/05/2014 Smoke Detector 2nd Corridor Building 200 Tested/Cleaned 3:42:43 PM 05/05/2014 Smoke Detector 2nd Corridor Building 200 Tested/Cleaned 3:42:47 PM 05/05/2014 Smoke Detector 2nd Corridor Building 200 Tested/Cleaned 3:43:01 PM 05/05/2014 Smoke Detector 2nd Corridor Building 200 Tested/Cleaned 3:43:16 PM 05/05/2014 Smoke Detector 2nd Corridor Building 200 Tested/Cleaned 3:43:45 PM 05/05/2014 Smoke Detector 2nd MDF Administration Tested/Cleaned 6:38:59 PM 05/02/2014 Smoke Detector 2nd MDF Administration Tested/Cleaned 6:39:42 PM 05/02/2014 Smoke Detector Boys Locker Room Tested/Cleaned 4:06:06 PM 05/02/2014 Smoke Detector Boys Locker Room Tested/Cleaned 4:07:14 PM 05/02/2014 Smoke Detector Boys Locker Room Tested/Cleaned 4:10:40 PM 05/02/2014 Smoke Detector Boys Locker Room Tested/Cleaned 4:13:00 PM 05/02/2014 Smoke Detector Boys Locker Room Corridor Tested/Cleaned 4:14:27 PM 05/02/2014 Smoke Detector Boys Locker Room Corridor Tested/Cleaned 4:18:31 PM 05/02/2014 Smoke Detector Boys Locker Room Corridor Tested/Cleaned 4:30:53 PM 05/02/2014 Smoke Detector Boys Locker Room Corridor Southern Entrance Tested/Cleaned 4:19:13 PM 05/02/2014 Smoke Detector Boys Locker Room Office Tested/Cleaned 4:15:30 PM 05/02/2014 Smoke Detector Boys Locker Room Office Restroom Tested/Cleaned 4:16:17 PM 05/02/2014 Smoke Detector Boys Locker Room Restroom Tested/Cleaned 4:23:48 PM 05/02/2014 Smoke Detector Boys Locker Room Staff R R Tested/Cleaned 4:28:45 PM 05/02/2014 Smoke Detector Boys Locker Room Staff Room Tested/Cleaned 4:26:09 PM 05/02/2014 Smoke Detector Boys Locker Room Staff Room Tested/Cleaned 4:27:11 PM 05/02/2014 Smoke Detector Boys Locker Room Storage Room Tested/Cleaned 4:25:11 PM 05/02/2014 Smoke Detector Boys Locker Room Team Room Tested/Cleaned 4:21:33 PM 05/02/2014 Smoke Detector Boys Locker Room Team Room Tested/Cleaned 4:33:24 PM 05/02/2014 Smoke Detector Boys Restroom Building 300 Tested/Cleaned 5:27:58 PM 05/02/2014 Smoke Detector Boys Restroom Building 300 Tested/Cleaned 5:28:42 PM 05/02/2014

Intrepid Electronic Systems 9 12/14/2014

Device Type Location Service Time Date

Passed Smoke Detector Boys Restroom Building 300 Tested/Cleaned 5:28:50 PM 05/02/2014 Smoke Detector Concession Mens Restroom Tested/Cleaned 3:54:01 PM 05/01/2014 Smoke Detector Concession Womens Restroom Tested/Cleaned 3:52:37 PM 05/01/2014 Smoke Detector Corridor Administration Building Tested/Cleaned 6:35:54 PM 05/02/2014 Smoke Detector Corridor Building 300 Tested/Cleaned 3:45:32 PM 05/05/2014 Smoke Detector Corridor Building 300 Tested/Cleaned 3:46:55 PM 05/05/2014 Smoke Detector Corridor Building 300 Tested/Cleaned 3:46:58 PM 05/05/2014 Smoke Detector Corridor Building 300 Tested/Cleaned 3:47:17 PM 05/05/2014 Smoke Detector Corridor Building 300 Tested/Cleaned 3:47:35 PM 05/05/2014 Smoke Detector Corridor Building 300 Tested/Cleaned 3:47:50 PM 05/05/2014 Smoke Detector Corridor Girls Locker Room Tested/Cleaned 2:55:46 PM 05/02/2014 Smoke Detector Corridor Girls Locker Room Tested/Cleaned 3:02:09 PM 05/02/2014 Smoke Detector Corridor Girls Locker Room Tested/Cleaned 3:50:43 PM 05/02/2014 Smoke Detector Electric Room Girls Locker Room Tested/Cleaned 2:59:40 PM 05/02/2014 Smoke Detector Fire Academy

Classroom 1A Tested/Cleaned 3:32:45 PM 05/01/2014

Smoke Detector Fire academy Break Room Tested/Cleaned 3:35:17 PM 05/01/2014 Smoke Detector Fire academy Classroom 1A FACP IDF Tested/Cleaned 3:45:49 PM 05/01/2014 Smoke Detector Fire academy Janitor Tested/Cleaned 4:03:40 PM 05/01/2014 Smoke Detector Fire academy Mens Restroom Tested/Cleaned 4:05:14 PM 05/01/2014 Smoke Detector Fire academy Office 1 Tested/Cleaned 3:58:18 PM 05/01/2014 Smoke Detector Fire academy Office 2 Tested/Cleaned 4:02:25 PM 05/01/2014 Smoke Detector Fire academy Womens Restroom Tested/Cleaned 4:06:49 PM 05/01/2014 Smoke Detector Girls Locker Room Tested/Cleaned 2:56:41 PM 05/02/2014 Smoke Detector Girls Locker Room Tested/Cleaned 3:00:43 PM 05/02/2014 Smoke Detector Girls Locker Room Team Room Tested/Cleaned 3:03:28 PM 05/02/2014 Smoke Detector Girls Locker Room Vestibule Tested/Cleaned 3:04:33 PM 05/02/2014 Smoke Detector Girls Locker Room Vestibule Tested/Cleaned 3:05:52 PM 05/02/2014 Smoke Detector Girls Restroom Building 200 Tested/Cleaned 5:26:41 PM 05/02/2014 Smoke Detector Girls Restroom Building 200 Tested/Cleaned 5:26:43 PM 05/02/2014 Smoke Detector Girls Restroom Building 200 Tested/Cleaned 5:26:46 PM 05/02/2014 Smoke Detector Gym Northwest Corridor Tested/Cleaned 3:12:56 PM 05/02/2014 Smoke Detector Gym Room Vestibule Tested/Cleaned 3:11:53 PM 05/02/2014 Smoke Detector Gymansium Mens Restroom Tested/Cleaned 3:31:07 PM 05/02/2014 Smoke Detector Gymansium Storage Tested/Cleaned 3:34:49 PM 05/02/2014 Smoke Detector Gymansium Team Room Tested/Cleaned 3:33:02 PM 05/02/2014 Smoke Detector Gymansium Womens restroom Tested/Cleaned 3:30:10 PM 05/02/2014 Smoke Detector Multipurpose Building 900 Boys restroom Tested/Cleaned 5:11:48 PM 05/02/2014 Smoke Detector Multipurpose Building 900 Boys restroom

vestibule Tested/Cleaned 5:11:07 PM 05/02/2014

Smoke Detector Multipurpose Building 900 East Entrance Tested/Cleaned 5:07:43 PM 05/02/2014 Smoke Detector Multipurpose Building 900 Girls Restroom Tested/Cleaned 5:14:31 PM 05/02/2014 Smoke Detector Multipurpose Building 900 Girls Restroom

Vestibule Tested/Cleaned 5:13:17 PM 05/02/2014

Smoke Detector Multipurpose Building 900 Kitchen Vending Area

Tested/Cleaned 5:01:34 PM 05/02/2014

Smoke Detector Multipurpose Building 900 Kitchen Vending Area

Tested/Cleaned 5:03:12 PM 05/02/2014

Smoke Detector Multipurpose Building 900 Kitchen/Locker Tested/Cleaned 4:59:38 PM 05/02/2014 Smoke Detector Multipurpose Building 900 Kitchen/Restroom Tested/Cleaned 4:58:39 PM 05/02/2014

Intrepid Electronic Systems 10 12/14/2014

Device Type Location Service Time Date

Passed Smoke Detector Multipurpose Building 900 Office Tested/Cleaned 5:04:40 PM 05/02/2014 Smoke Detector Pool Area Boys Restroom Tested/Cleaned 4:04:13 PM 05/02/2014 Smoke Detector Pool Area Room Storage Tested/Cleaned 4:11:44 PM 05/02/2014 Smoke Detector Restroom Building Mens Restroom Tested/Cleaned 4:54:19 PM 05/02/2014 Smoke Detector Restroom Building Womens Restroom Tested/Cleaned 4:52:34 PM 05/02/2014 Smoke Detector Restroom Girls Locker Room Tested/Cleaned 2:54:17 PM 05/02/2014 Smoke Detector Restroom Girls Locker Room Vestibule Tested/Cleaned 3:08:37 PM 05/02/2014 Smoke Detector Staff Restroom Girls Locker Room Tested/Cleaned 2:58:39 PM 05/02/2014 Smoke Detector Staff Room Girls Locker Room Tested/Cleaned 2:57:40 PM 05/02/2014 Smoke Detector Storage Girls Locker Room Vestibule Tested/Cleaned 3:10:09 PM 05/02/2014 Smoke Detector Storage Girls Locker Room Vestibule Tested/Cleaned 3:10:49 PM 05/02/2014 Smoke Detector Storage Room Girls Locker Room Vestibule Tested/Cleaned 3:06:34 PM 05/02/2014 Smoke Detector Storage Room Girls Locker Room Vestibule Tested/Cleaned 3:07:29 PM 05/02/2014 Smoke Detector Work Room Fire academy Tested/Cleaned 4:00:40 PM 05/01/2014 Smoke Detector Wrestling room Tested/Cleaned 3:44:49 PM 05/02/2014 Smoke Detector Wrestling room Tested/Cleaned 3:45:46 PM 05/02/2014 Smoke Detector Wrestling room Tested/Cleaned 3:46:34 PM 05/02/2014 Smoke Detector Wrestling room IDF closet Tested/Cleaned 3:41:58 PM 05/02/2014 Smoke Detector Wrestling room Vestibule Tested/Cleaned 3:40:33 PM 05/02/2014 Smoke Detector Classroom Fire Academy 1B Tested/Cleaned 3:43:26 PM 05/01/2014 Smoke Detector Electrical Boys Locker Tested/Cleaned 4:31:59 PM 05/02/2014 Smoke Detector Classroom Fire Academy 1A Tested/Cleaned 3:41:45 PM 05/01/2014 Smoke Detector Classroom Fire Academy 1B Tested/Cleaned 3:42:04 PM 05/01/2014 Smoke Detector Womens Restroom Pool Area Tested/Cleaned 3:56:33 PM 05/02/2014 Smoke Detector North Stairwell Building 200 Tested/Cleaned 4:00:08 PM 05/05/2014 Smoke Detector North Stairwell Building 300 Tested/Cleaned 3:56:11 PM 05/05/2014 Smoke Detector Northeast Gym Main entrance Tested/Cleaned 3:36:43 PM 05/02/2014 Smoke Detector Northeast Gym Main entrance Tested/Cleaned 3:38:12 PM 05/02/2014 Smoke Detector Northeast Classroom Storeroom Fire Academy

1B Tested/Cleaned 3:44:48 PM 05/01/2014

Smoke Detector Northwest Classroom Storeroom Fire academy 1A

Tested/Cleaned 3:39:06 PM 05/01/2014

Smoke Detector South Gym Vestibule Tested/Cleaned 4:34:31 PM 05/02/2014 Smoke Detector South Gym Vestibule Tested/Cleaned 4:35:36 PM 05/02/2014 Smoke Detector South Stairwell Building 200 Tested/Cleaned 3:57:10 PM 05/05/2014 Smoke Detector South Stairwell Building 300 Tested/Cleaned 3:51:35 PM 05/05/2014 Smoke Detector West Pool Area Ticket Booth Tested/Cleaned 4:02:14 PM 05/02/2014 Smoke Detector West Track And Field Concession Room Tested/Cleaned 4:11:04 PM 05/05/2014 Waterflow Switch Classroom Fire Academy 1A Above Ceiling Tested 3:13:45 PM 05/01/2014

Monitor Monitor Device Fire Academy 1A Above Ceiling Tested 3:49:01 PM 05/01/2014 Monitor Device NORTH Bathroom Bld. Boys Tested 4:42:36 PM 05/05/2014

Supervisory Tamper Switch West Fire academy 1A Above Ceiling Tested 3:13:41 PM 05/01/2014

Device Type Location Service Time Date

Failed/Other

Intrepid Electronic Systems 11 12/14/2014

Device Type Location Service Time Date

Failed/Other Auxiliary

Elevator North 1st Floor Elevator Machine Room Administration

9:38:12 AM 06/24/2014

Elevator North 1st Floor Elevator Machine Room Administration

9:38:21 AM 06/24/2014

Initiating Smoke Detector 1st Floor Administration Hall Elevator Lobby 9:37:51 AM 06/24/2014 Smoke Detector 2nd Floor Corridor Administration Building

Elevator Lobby 9:38:55 AM 06/24/2014

Smoke Detector North 1st Floor Elevator Machine Room Administration

9:38:39 AM 06/24/2014

Device Type Location Service Time Date

Untested Initiating

Heat Detector Boys Locker Room Heat Detector Boys Locker Room Office Restroom Heat Detector Girls Locker Room Heat Detector Girls Locker Room Heat Detector Girls Locker Room Heat Detector Janitorial Girls Locker Room Vestibule Heat Detector Multipurpose 900 Above Ceiling Heat Heat Detector Press Box Heat Detector Press Box Heat Detector Ticket Booth Initiating Device Building 1300 Heats/Pulls Initiating Device Electrical

Building 1000 North Conventional Heat Coverage

Initiating Device Electrical Building 1000 North Conventional Heat Coverage

Initiating Device Electrical Building 1000 South Conventional Heat Coverage

Initiating Device Electrical Building 1000 South Conventional Heat Coverage

Initiating Device Electrical Building 300 Heat Coverage

Initiating Device Electrical Building 300 Heat Coverage

Initiating Device Electrical Building 300 Heat Coverage

Initiating Device Electrical Building 300 Heats/Pull Stations Coverage

Initiating Device Electrical

Intrepid Electronic Systems 12 12/14/2014

Device Type Location Service Time Date

Untested Building 600 Conventional Heat Coverage

Initiating Device Electrical Building 600 Conventional Heat Coverage

Initiating Device Electrical Building 700 Conventional Heat Coverage

Initiating Device Electrical Building 700 Conventional Heat Coverage

Initiating Device Electrical Building 700 Conventional Heat Coverage

Initiating Device Multipurpose Building 900 Heats/Pulls Initiating Device School Bank FCPS Room Initiating Device School Bank FCPS Room

Intrepid Electronic Systems 13 12/14/2014

Building: James Lick High School Control Panel: 2

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Device Type Location Service Time Date

Passed Indicating

Indicating Device Multipurpose Building 900 Tested 8:21:32 PM 05/01/2014

Intrepid Electronic Systems 14 12/14/2014

Building: James Lick High School Control Panel: 3

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Device Type Location Service Time Date

Passed Indicating

Indicating Device Boys Locker Room FACP Room Tested 8:34:38 PM 05/01/2014

Monitor Monitor Device Boys Locker Room FACP Room Tested 8:37:55 PM 05/01/2014

Intrepid Electronic Systems 15 12/14/2014

Building: James Lick High School Control Panel: 5

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Device Type Location Service Time Date

Passed Control

Battery Fire Academy FACP Closet Replaced 2:08:59 PM 05/06/2014

Indicating Indicating Device Fire Academy FACP Closet Tested 3:50:52 PM 05/01/2014

Intrepid Electronic Systems 16 12/14/2014

Building: James Lick High School Control Panel: 6

The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.

Device Type Location Service Time Date

Device Type Location Service Time Date

Passed Control

Battery 1st West Electrical Building 500 AES Tested 8:10:50 PM 05/01/2014 Communicator 1st West Electrical Building 500 AES Tested 8:11:57 PM 05/01/2014

Indicating Indicating Device 1st West Electrical Building 500 Tested 8:09:29 PM 05/01/2014

Monitor Monitor Device 1st West Electrical Building 500 AES Tested 8:13:32 PM 05/01/2014

Intrepid Electronic Systems 17 12/14/2014

Service Summary Generated by: BuildingReports.com

Building: James Lick High School

The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Failed/Other Elevator 2 Smoke Detector 3 Total 5

Passed Annunciator Tested 2 Battery Replaced 13 Battery Tested 20 Beam Detector Tested 4 Communicator Tested 5 Damper Control Tested 2 Duct Detector Tested/Cleaned 10 Fan Shutdown Tested 7 Fan Shutdown Tested/Cleaned 1 Indicating Device Tested 9 Initiating Device Tested 2 Monitor Device Tested 4 Power Supply Tested 9 Programmable Relay Tested 2 Pull Station Tested 9 Releasing Device Tested 2 Releasing Device Tested/Cleaned 1 Smoke Detector Tested/Cleaned 143 Tamper Switch Tested 1 Waterflow Switch Tested 1 Total 247

Untested Heat Detector 10 Initiating Device 17 Total 27

Intrepid Electronic Systems 18 12/14/2014

Auxiliary Functions Testing Generated by: BuildingReports.com

Building: James Lick High School Control Panel: 1

The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Damper Control

Boys Locker Room Electrical Passed 18863272

Northeast Classroom 1B Soffit Fire Academy

Passed 18863258

Fan Shutdown Supply Boys Locker Room AHU Control Passed 18863270

Supply Girls Locker Room AHU Control Building

Passed 18386355

Supply HP-1 Shut Down Fire Academy

Passed 18863259

Supply HP-2 Shut Down Fire Academy

Passed 18863261

Supply Roof Administration Building A/C 1 SHUT DOWN

Passed 18865494

Supply Roof Administration Building A/C 2 SHUT DOWN

Passed 18865495

Supply Roof Administration Building A/C 3 SHUT DOWN

Passed 18865496

Supply Roof Administration Building A/C 4 SHUT DOWN

Passed 18865497

Programmable Relay FCPS Trigger NORTH Bathroom Bld. Boys Passed 18862597

FCPS NAC Trip NORTH Bathroom Bld. Boys Passed 18862600

Releasing Device Door Holder ElectricalBuilding 200/300 Door Holders Passed 18386345

Door Holder North 1st Floor Elevator Machine Room Administration 1st Floor DH

Passed 18866673

Door Holder North 1st Floor Elevator Machine Room Administration 2nd Floor DH

Passed 18866679

Smoke Detector Door Release 2nd Corridor Building 200 Passed 18386533

Door Release 2nd Corridor Building 200 Passed 18386532

Door Release 2nd Corridor Building 200 Passed 18386531

Door Release 2nd Corridor Building 200 Passed 18386530

Door Release 2nd Corridor Building 200 Passed 18386513

Door Release 2nd Corridor Building 200 Passed 18386514

Door Release Corridor Building 300 Passed 18386525

Intrepid Electronic Systems 19 12/14/2014

Door Release Corridor Building 300 Passed 18386524

Door Release Corridor Building 300 Passed 18386523

Door Release Corridor Building 300 Passed 18386522

Door Release Corridor Building 300 Passed 18386521

Door Release Corridor Building 300 Passed 18386520

Door Release North Stairwell Building 200 Passed 18863280

Door Release North Stairwell Building 300 Passed 18863278

Door Release South Stairwell Building 200 Passed 18863279

Door Release South Stairwell Building 300 Passed 18863277

Failed/Other Elevator

Recall Alternate North 1st Floor Elevator Machine Room Administration

Inaccessible 18866671

Recall Primary North 1st Floor Elevator Machine Room Administration

Inaccessible 18866672

Smoke Detector Elevator Recall 1st Floor Administration Hall Elevator Lobby Inaccessible 18866668

Elevator Recall 2nd Floor Corridor Administration Building Elevator Lobby

Inaccessible 18866675

Elevator Recall North 1st Floor Elevator Machine Room Administration

Inaccessible 18866674

Intrepid Electronic Systems 20 12/14/2014

Sensitivity Testing Generated by: BuildingReports.com

Building: James Lick High School Control Panel: 1

The Sensitivity Testing section details the sensitivity test ranges and acceptable readings for each type of device. Items are grouped by Passed or Failed/Other. Normally, Devices that perform outside the acceptable range of sensitivity are listed in Failed/Other.

Location Address Model # Range Value ScanID

Passed Duct Detector

Boys Locker Room 1-L1- D72 XP95-P Normal 18386469 Copy Room 126 Building Administration 1-L1- D81 RW-AR-P Normal 18865510 Corridor Girls Locker Room 1-L1- D73 XP95-P Normal 18386388 Multipurpose Building 900 Kitchen Above D22 1-L1- D21 XP95-T Normal 18386425 Secretary 127 Building Administration 1-L1- D17 RW-AR-P Normal 18865514 Secretary 127 Building Administration 1-L1- D82 RW-AR-P Normal 18865511 Secretary 127 Building Administration 1-L1- D83 RW-AR-P Normal 18865513 West Cooridor Building Administration 1-L1- D28 RW-AR-P Normal 18865515 West Cooridor Building Administration 1-L1- D48 RW-AR-P Normal 18865509 West Cooridor Building Administration 1-L1- D35 RW-AR-P Normal 18865508

Smoke Detector 1st Floor Administration Administrator APED 1-L1- D24 XP95-P Normal 18386545 1st Floor Administration Advisor 1-L1- D33 XP95-P Normal 18386538 1st Floor Administration Advisor 1-L1- D45 XP95-P Normal 18386535 1st Floor Administration APA 1-L1- D32 XP95-P Normal 18386539 1st Floor Administration Conference room 1-L1- D16 XP95-P Normal 18866887 1st Floor Administration Copy Room 1-L1- D19 XP95-P Normal 18386552 1st Floor Administration Counselor 1-L1- D21 XP95-P Normal 18386548 1st Floor Administration Counselor 1-L1- D22 XP95-P Normal 18386547 1st Floor Administration Counselor 1-L1- D23 XP95-P Normal 18386546 1st Floor Administration Counselor Tech 1-L1- D26 XP95-P Normal 18386549 1st Floor Administration English Office 1-L1- D12 XP95-P Normal 18386558 1st Floor Administration Hall 1-L1- D36 XP95-P Normal 18386560 1st Floor Administration Hall 1-L1- D37 XP95-P Normal 18386561 1st Floor Administration Hall 1-L1- D38 XP95-P Normal 18386562 1st Floor Administration Hall 1-L1- D40 XP95-P Normal 18386563 1st Floor Administration Hall 1-L1- D10 XP95-P Normal 18386559 1st Floor Administration Hallway 1-L1- D41 XP95-P Normal 18866886 1st Floor Administration Hallway 1-L1- D27 XP95-P Normal 18386551 1st Floor Administration Hallway 1-L1- D31 XP95-P Normal 18386543 1st Floor Administration Hallway 1-L1- D34 XP95-P Normal 18386541 1st Floor Administration Hallway 1-L1- D47 XP95-P Normal 18386537 1st Floor Administration Health Office 1-L1- D42 XP95-P Normal 18386540 1st Floor Administration IDF 1-L1- D30 XP95-P Normal 18386542 1st Floor Administration Liason 1-L1- D44 XP95-P Normal 18386536 1st Floor Administration Office 1-L1- D88 XP95-P Normal 18386557 1st Floor Administration Principal 1-L1- D15 XP95-P Normal 18386555 1st Floor Administration Principal Secretary's Office 1-L1- D18 XP95-P Normal 18386554

Intrepid Electronic Systems 21 12/14/2014

1st Floor Administration Reception 1-L1- D20 XP95-P Normal 18386553 1st Floor Administration Registrar 1-L1- D25 XP95-P Normal 18386550 1st Floor Administration Security 1-L1- D46 XP95-P Normal 18386534 1st Floor Administration Workroom 1-L1- D29 XP95-P Normal 18386544 1st East Conference Administration 1-L1- D14 XP95-P Normal 18386556 2nd Corridor Administration Building 1-L1- D04 XP95-P Normal 18386526 2nd Corridor Administration Building 1-L1- D05 XP95-P Normal 18386527 2nd Corridor Administration Building 1-L1- D08 XP95-P Normal 18386528 2nd Corridor Building 200 1-L1- D26 FSI-751 0.8 - 1.32 Normal 18386533 2nd Corridor Building 200 1-L1- D25 FSI-751 0.8 - 1.32 Normal 18386532 2nd Corridor Building 200 1-L1- D24 FSI-751 0.8 - 1.32 Normal 18386531 2nd Corridor Building 200 1-L1- D23 FSI-751 0.8 - 1.32 Normal 18386530 2nd Corridor Building 200 1-L1- D22 FSI-751 0.8 - 1.32 Normal 18386513 2nd Corridor Building 200 1-L1- D21 FSI-751 0.8 - 1.32 Normal 18386514 2nd MDF Administration 1-L1- D01 XP95-P Normal 18866907 2nd MDF Administration 1-L1- D02 XP95-P Normal 18863273 Boys Locker Room 1-L1- D84 XP95-P Normal 18386473 Boys Locker Room 1-L1- D14 XP95-P Normal 18386471 Boys Locker Room 1-L1- D75 XP95-P Normal 18386474 Boys Locker Room 1-L1- D15 XP95-P Normal 18386470 Boys Locker Room Corridor 1-L1- D20 XP95-P Normal 18386465 Boys Locker Room Corridor 1-L1- D19 XP95-P Normal 18386450 Boys Locker Room Corridor 1-L1- D18 XP95-P Normal 18386446 Boys Locker Room Corridor Southern Entrance 1-L1- D06 XP95-P Normal 18386451 Boys Locker Room Office 1-L1- D81 XP95-P Normal 18386466 Boys Locker Room Office Restroom 1-L1- D07 XP95-P Normal 18386467 Boys Locker Room Restroom 1-L1- D78 XP95-P Normal 18386449 Boys Locker Room Staff R R 1-L1- D02 XP95-P Normal 18386448 Boys Locker Room Staff Room 1-L1- D77 XP95-P Normal 18386447 Boys Locker Room Staff Room 1-L1- D76 XP95-P Normal 18386457 Boys Locker Room Storage Room 1-L1- D17 XP95-P Normal 18386476 Boys Locker Room Team Room 1-L1- D16 XP95-P Normal 18386475 Boys Locker Room Team Room 1-L1- D23 XP95-P Normal 18386455 Boys Restroom Building 300 1-L1- D89 XP95-P Normal 18386510 Boys Restroom Building 300 1-L1- D90 XP95-P Normal 18386511 Boys Restroom Building 300 1-L1- D91 XP95-P Normal 18386512 Concession Mens Restroom 1-L1- D24 XP95-P Normal 18866904 Concession Womens Restroom 1-L1- D25 XP95-P Normal 18866905 Corridor Administration Building 1-L1- D09 XP95-P Normal 18386529 Corridor Building 300 1-L1- D35 FSI-751 0.8 - 1.32 Normal 18386525 Corridor Building 300 1-L1- D40 FSI-751 0.8 - 1.32 Normal 18386524 Corridor Building 300 1-L1- D34 FSI-751 0.8 - 1.32 Normal 18386523 Corridor Building 300 1-L1- D33 FSI-751 0.8 - 1.32 Normal 18386522 Corridor Building 300 1-L1- D32 FSI-751 0.8 - 1.32 Normal 18386521 Corridor Building 300 1-L1- D31 FSI-751 0.8 - 1.32 Normal 18386520 Corridor Girls Locker Room 1-L1- D57 XP95-P Normal 18386349 Corridor Girls Locker Room 1-L1- D51 XP95-P Normal 18386378 Corridor Girls Locker Room 1-L1- D71 XP95-P Normal 18386348 Electric Room Girls Locker Room 1-L1- D50 XP95-P Normal 18385882 Fire Academy Classroom 1A

1-L1- D05 XP95-P Normal 18862611

Fire academy Break Room 1-L1- D08 XP95-P Normal 18866894 Fire academy Classroom 1A FACP IDF 1-L1- D27 XP95-P Normal 18866895 Fire academy Janitor 1-L1- D11 XP95-P Normal 18866891

Intrepid Electronic Systems 22 12/14/2014

Fire academy Mens Restroom 1-L1- D10 XP95-P Normal 18866890 Fire academy Office 1 1-L1- D14 XP95-P Normal 18866888 Fire academy Office 2 1-L1- D12 XP95-P Normal 18866889 Fire academy Womens Restroom 1-L1- D9 XP95-P Normal 18866892 Girls Locker Room 1-L1- D48 XP95-P Normal 18386353 Girls Locker Room 1-L1- D49 XP95-P Normal 18386354 Girls Locker Room Team Room 1-L1- D63 XP95-P Normal 18386357 Girls Locker Room Vestibule 1-L1- D118 XP95-P Normal 18386387 Girls Locker Room Vestibule 1-L1- D44 XP95-P Normal 18386386 Girls Restroom Building 200 1-L1- D92 XP95-P Normal 18386497 Girls Restroom Building 200 1-L1- D93 XP95-P Normal 18386498 Girls Restroom Building 200 1-L1- D94 XP95-P Normal 18386499 Gym Northwest Corridor 1-L1- D53 XP95-P Normal 18386389 Gym Room Vestibule 1-L1- D54 XP95-P Normal 18386379 Gymansium Mens Restroom 1-L1- D27 XP95-P Normal 18386502 Gymansium Storage 1-L1- D29 XP95-P Normal 18386500 Gymansium Team Room 1-L1- D28 XP95-P Normal 18386501 Gymansium Womens restroom 1-L1- D26 XP95-P Normal 18866912 Multipurpose Building 900 Boys restroom 1-L1- D37 XP95-P Normal 18386430 Multipurpose Building 900 Boys restroom vestibule 1-L1- D40 XP95-P Normal 18386429 Multipurpose Building 900 East Entrance 1-L1- D01 XP95-P Normal 18386437 Multipurpose Building 900 Girls Restroom 1-L1- D39 XP95-P Normal 18386432 Multipurpose Building 900 Girls Restroom Vestibule 1-L1- D38 XP95-P Normal 18386431 Multipurpose Building 900 Kitchen Vending Area 1-L1- D13 XP95-P Normal 18386427 Multipurpose Building 900 Kitchen Vending Area 1-L1- D18 XP95-P Normal 18386426 Multipurpose Building 900 Kitchen/Locker 1-L1- D16 XP95-P Normal 18386423 Multipurpose Building 900 Kitchen/Restroom 1-L1- D15 XP95-P Normal 18386422 Multipurpose Building 900 Office 1-L1- D19 XP95-P Normal 18386428 Pool Area Boys Restroom 1-L1- D74 XP95-P Normal 18386505 Pool Area Room Storage 1-L1- D21 XP95-P Normal 18386504 Restroom Building Mens Restroom 1-L1- D43 XP95-P Normal 18386442 Restroom Building Womens Restroom 1-L1- D44 XP95-P Normal 18386443 Restroom Girls Locker Room 1-L1- D47 XP95-P Normal 18386350 Restroom Girls Locker Room Vestibule 1-L1- D43 XP95-P Normal 18386382 Staff Restroom Girls Locker Room 1-L1- D58 XP95-P Normal 18386352 Staff Room Girls Locker Room 1-L1- D59 XP95-P Normal 18386351 Storage Girls Locker Room Vestibule 1-L1- D42 XP95-P Normal 18386381 Storage Girls Locker Room Vestibule 1-L1- D41 XP95-P Normal 18386380 Storage Room Girls Locker Room Vestibule 1-L1- D45 XP95-P Normal 18386384 Storage Room Girls Locker Room Vestibule 1-L1- D46 XP95-P Normal 18386383 Work Room Fire academy 1-L1- D13 XP95-P Normal 18866885 Wrestling room 1-L1- D35 XP95-P Normal 18862610 Wrestling room 1-L1- D37 XP95-P Normal 18866918 Wrestling room 1-L1- D38 XP95-P Normal 18866919 Wrestling room IDF closet 1-L1- D120 XP95-P Normal 18866916 Wrestling room Vestibule 1-L1- D33 XP95-P Normal 18866917 Classroom Fire Academy 1B 1-L1- D30 XP95-P Normal 18862612 Electrical Boys Locker 1-L1- D01 XP95-P Normal 18386456 Classroom Fire Academy 1A 1-L1- D06 XP95-P Normal 18863145 Classroom Fire Academy 1B 1-L1- D29 XP95-P Normal 18863143 Womens Restroom Pool Area 1-L1- D56 XP95-P Normal 18863269 North Stairwell Building 200 1-L1- D20 FSI-851 0.51 - 1.96 Normal 18863280 North Stairwell Building 300 1-L1- D30 FSI-851 0.51 - 1.96 Normal 18863278

Intrepid Electronic Systems 23 12/14/2014

Northeast Gym Main entrance 1-L1- D30 XP95-P Normal 18866911 Northeast Gym Main entrance 1-L1- D31 XP95-P Normal 18866910 Northeast Classroom Storeroom Fire Academy 1B 1-L1- D30 XP95-P Normal 18863256 Northwest Classroom Storeroom Fire academy 1A 1-L1- D07 XP95-P Normal 18863144 South Gym Vestibule 1-L1- D25 XP95-P Normal 18386453 South Gym Vestibule 1-L1- D24 XP95-P Normal 18386452 South Stairwell Building 200 1-L1- D27 FSI-851 0.51 - 1.96 Normal 18863279 South Stairwell Building 300 1-L1- D36 FSI-851 0.51 - 1.96 Normal 18863277 West Pool Area Ticket Booth 1-L1- D22 XP95-P Normal 18386503 West Track And Field Concession Room 1-L1- D23 XP95-P Normal 18866906

Intrepid Electronic Systems 24 12/14/2014

Smoke Management Testing Generated by: BuildingReports.com

Building: James Lick High School Control Panel: 1

The Smoke Management Testing section details the test and inspection of device items that are involved in controlling the spread of smoke in a building. Items are grouped by Passed or Failed/Other.

Location Description Comment ScanID Simulated

Passed Fan Shutdown

Boys Locker Room AHU Control Supply Passed 18863270

Girls Locker Room AHU Control Building

Supply Passed 18386355

HP-1 Shut Down Fire Academy

Supply Passed 18863259

HP-2 Shut Down Fire Academy

Supply Passed 18863261

Roof Administration Building A/C 1 SHUT DOWN

Supply Passed 18865494

Roof Administration Building A/C 2 SHUT DOWN

Supply Passed 18865495

Roof Administration Building A/C 3 SHUT DOWN

Supply Passed 18865496

Roof Administration Building A/C 4 SHUT DOWN

Supply Passed 18865497

Releasing Device ElectricalBuilding 200/300 Door Holders Door Holder Passed 18386345

North 1st Floor Elevator Machine Room Administration 1st Floor DH

Door Holder Passed 18866673

North 1st Floor Elevator Machine Room Administration 2nd Floor DH

Door Holder Passed 18866679

Intrepid Electronic Systems 25 12/14/2014

Time, Temperature & Level Testing Generated by: BuildingReports.com

Building: James Lick High School Control Panel: 1

The Time, Temperature, & Level Testing section details the measurements taken from various devices that are designed to respond in a certain amount of time, respond at a certain temperature, or respond within the acceptable range of volume or level. Items are grouped by Passed or Failed/Other.

Type Location Comment Sec Deg Lvl ScanID

Passed Waterflow Switch

Classroom Fire Academy 1A Above Ceiling Passed 45 sec

n/a n/a 18866897

Intrepid Electronic Systems 26 12/14/2014

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: James Lick High School Control Panel: 1

The Control & Power Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Comment Amps Volts Pre Test

Post Test

Passed Battery

Lead Acid Boys Locker Room FACP Room Passed 18 Lead Acid Boys Locker Room FACP Room Passed 18 Lead Acid Boys Locker Room FACP Room Passed 7 Lead Acid Boys Locker Room FACP Room Passed 7 Lead Acid Boys Locker Room FACP Room Passed 7 Lead Acid Fire academy FACP closet Passed 18 Lead Acid Fire academy FACP closet Passed 18 Lead Acid Multipurpose Building 900 Passed 18 Lead Acid Multipurpose Building 900 Passed 18 Lead Acid Second Floor FACP Student Services

MDF/SERVER Administration Building Passed 18

Lead Acid Second Floor Student Services FACP Room Building Administration

Passed 18

Lead Acid Second Floor Student Services FACP Room Building Administration

Passed 18

Lead Acid Second Floor Student Services FACP Room Building Administration

Passed 18

Intrepid Electronic Systems 27 12/14/2014

Building: James Lick High School Control Panel: 5

The Control & Power Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Comment Amps Volts Pre Test

Post Test

Passed Battery

Fire Academy FACP Closet Passed 7 Ah

Intrepid Electronic Systems 28 12/14/2014

Inventory & Warranty Report Generated by: BuildingReports.com

Building: James Lick High School Control Panel: 1

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Item Category % of Inventory Quantity Heat Detector Initiating 3.58% 10

Initiating Device Initiating 6.81% 19 Battery Control 11.83% 33

Communicator Control 1.79% 5 Power Supply Control 3.23% 9

Indicating Device Indicating 3.23% 9 Tamper Switch Supervisory 0.36% 1

Waterflow Switch Initiating 0.36% 1 Smoke Detector Initiating 52.33% 146 Monitor Device Monitor 1.43% 4 Damper Control Auxiliary 0.72% 2 Fan Shutdown Auxiliary 2.87% 8 Duct Detector Initiating 3.58% 10

Pull Station Initiating 3.23% 9 Beam Detector Initiating 1.43% 4 Annunciator Control 0.72% 2

Programmable Relay Auxiliary 0.72% 2 Releasing Device Auxiliary 1.08% 3

Elevator Auxiliary 0.72% 2

Type Qty Model # Description Install Date

In Service - 90 Days - 1 Year .MK Battery 1 ES7-12 Lead Acid 05/06/2014

Genesis Battery 2 NP7-12 Lead Acid 05/06/2014

Power Patrol Battery 2 SLA1116 Lead Acid 05/06/2014

Ultra Tech Battery 7 UT 12180 Lead Acid 05/06/2014

In Service - 1 Year to 2 Years Gamewell Monitor Device 1 PID95 FCPS TRBL. 06/07/2013 Programmable Relay 1 RCE-95 FCPS NAC Trip 06/07/2013

Ultra Tech Battery 2 UT1270 Sealed Lead Acid 06/07/2013

Wheelock

Intrepid Electronic Systems 29 12/14/2014

Power Supply 1 PS-8 06/07/2013

Yuasa Battery 2 NP7-12 Sealed Lead Acid 06/07/2013

In Service - 2 Years to 3 Years Gamewell Elevator 1 RCE-95 Recall Alternate 10/18/2012 Elevator 1 RCE-95 Recall Primary 10/18/2012 Releasing Device 2 RCE-95 Door Holder 10/18/2012 Smoke Detector 6 XP95-P Photoelectric 10/18/2012

Ultra Tech Battery 2 UT 1270 Lead Acid 06/06/2012

AES Intellinet Communicator 1 7750-F-8 Digital Radio 06/05/2012

Gamewell Monitor Device 1 PID95-P PIV/Backflow Prev. 06/05/2012 Smoke Detector 11 XP95-P Photoelectric 06/05/2012

Ultra Tech Battery 4 UT 1270 Lead Acid 05/30/2012

Wheelock Power Supply 1 PS-24-8MC 05/30/2012

Ultra Tech Battery 1 UT 12180 Lead Acid 05/25/2012 Battery 4 UT 1270 Lead Acid 05/25/2012

Air Products Duct Detector 7 RW-AR-P Photoelectric 04/11/2012

AES Intellinet Communicator 1 7750-F-8 Digital Radio 02/08/2012

Gamewell Beam Detector 4 02/08/2012 Heat Detector 3 XP95-T Rate-of-Rise 02/08/2012 Indicating Device 1 IF-654 NAC CIRCUIT 02/08/2012 Smoke Detector 13 XP95-P Photoelectric 02/08/2012

Notifier Indicating Device 1 System 5000 NAC CIRCUIT 02/08/2012 Initiating Device 2 MMX-101 Monitor Module 02/08/2012 Power Supply 1 FCPS-24 02/08/2012 Smoke Detector 12 FSI-751 Ionization 02/08/2012 Smoke Detector 4 FSI-851 Ionization 02/08/2012

Wheelock Power Supply 1 PS-12/24-8MP 02/08/2012

AES Intellinet Communicator 2 7750-F-8 Digital Radio 02/07/2012

Gamewell

Intrepid Electronic Systems 30 12/14/2014

Annunciator 1 RAN-2 LCD Display 02/07/2012 Duct Detector 1 XP95-P Photoelectric 02/07/2012 Duct Detector 1 XP95-T Photoelectric 02/07/2012 Heat Detector 2 XP95-T Rate-of-Rise 02/07/2012 Initiating Device 1 PID-95P Monitor Module 02/07/2012 Pull Station 4 MS-95T Single Action 02/07/2012 Smoke Detector 65 XP95-P Photoelectric 02/07/2012

Honeywell Power Supply 1 FIREFORCE 8 02/07/2012

Notifier Annunciator 1 LCD-80 LCD Display 02/07/2012 Initiating Device 1 MMX-101 Monitor Module 02/07/2012 Pull Station 4 NBG-10 Dual Action 02/07/2012 Pull Station 1 NBG-10 Single Action 02/07/2012

Gamewell Damper Control 2 RCE-95 02/06/2012 Duct Detector 1 XP95-P Photoelectric 02/06/2012 Fan Shutdown 8 RCE-95 Supply 02/06/2012 Heat Detector 5 XP95-T Rate-of-Rise 02/06/2012 Programmable Relay 1 RCE-95 FCPS Trigger 02/06/2012 Smoke Detector 31 XP95-P Photoelectric 02/06/2012 Tamper Switch 1 PID-95P 02/06/2012 Waterflow Switch 1 PID-95P 02/06/2012

Honeywell Power Supply 1 Fireforce 8 02/06/2012

Notifier Indicating Device 1 CMX-2 Control Module Bld. 300 02/06/2012 Indicating Device 1 CMX-2 Control Module Bld. 600 02/06/2012 Indicating Device 1 CMX-2 Control Module Bld. 700 02/06/2012 Initiating Device 1 CMX-2 Monitor Module 02/06/2012 Initiating Device 14 MMX-101 Monitor Module 02/06/2012 Power Supply 3 FCPS-24 02/06/2012 Releasing Device 1 CMX-2 Door Holder 02/06/2012

Gamewell Smoke Detector 4 XP95-P Photoelectric 01/15/2012

In Service - 3 Years to 5 Years Genesis Battery 2 NP7-12 Lead Acid 06/07/2011

In Service - 5 Years to 10 Years Power Patrol Battery 2 SEC1075 Lead Acid 12/03/2009

Intrepid Electronic Systems 31 12/14/2014

Building: James Lick High School Control Panel: 2

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Type Qty Model # Description Install Date

In Service - 2 Years to 3 Years Gamewell Indicating Device 1 IF-632 NAC Circuit 02/07/2012

Intrepid Electronic Systems 32 12/14/2014

Building: James Lick High School Control Panel: 3

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Type Qty Model # Description Install Date

In Service - 2 Years to 3 Years Gamewell Indicating Device 1 IF-645 NAC CIRCUIT 02/07/2012 Monitor Device 1 PID-95 RF Trouble 02/07/2012

Intrepid Electronic Systems 33 12/14/2014

Building: James Lick High School Control Panel: 5

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Type Qty Model # Description Install Date

In Service - 90 Days - 1 Year Power Patrol Battery 1 05/06/2014

In Service - 2 Years to 3 Years Gamewell Indicating Device 1 IF-632 NAC Circuit 06/05/2012

Intrepid Electronic Systems 34 12/14/2014

Building: James Lick High School Control Panel: 6

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Type Qty Model # Description Install Date

In Service - 2 Years to 3 Years AES Intellinet Communicator 1 7750-F-8 Digital Radio 02/08/2012

Gamewell Indicating Device 1 IF-602 NAC CIRCUIT 02/08/2012 Monitor Device 1 PID-95 RF Trouble 02/08/2012

Power Sonic Battery 1 PS-1270 F1 Sealed Lead Acid 02/08/2012

Intrepid Electronic Systems 35 12/14/2014

Zone Address Report Generated by: BuildingReports.com

Building: James Lick High School Control Panel: 1

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Description ScanID

Zone/Circuit: CKT1- D100 Fan Shutdown Boys Locker Room AHU Control Supply 18863270 D102 Damper Control Boys Locker Room Electrical 18863272 D16 Tamper Switch West Fire academy 1A Above Ceiling 18866898 D17 Damper Control Northeast Classroom 1B Soffit

Fire Academy 18863258

D18 Fan Shutdown HP-1 Shut Down Fire Academy

Supply 18863259

D19 Fan Shutdown HP-2 Shut Down Fire Academy

Supply 18863261

D26 Monitor Device Fire Academy 1A Above Ceiling PIV/Backflow Prev. 18866899 D45 Programmable Relay NORTH Bathroom Bld. Boys FCPS Trigger 18862597

Zone/Circuit: CKT1-D47 Programmable Relay NORTH Bathroom Bld. Boys FCPS NAC Trip 18862600

Zone/Circuit: CKT1-D48 Monitor Device NORTH Bathroom Bld. Boys FCPS TRBL. 18862598

Zone/Circuit: L 1 M15 Pull Station Multipurpose Building 900 Northeast Dual Action 18386435 M15 Pull Station Multipurpose Building 900 Northwest Dual Action 18386436 M15 Pull Station Multipurpose Building 900 Southeast Dual Action 18386434 M15 Pull Station Multipurpose Building 900 Southwest Dual Action 18386433

Zone/Circuit: L1- D01 Smoke Detector 2nd MDF Administration Photoelectric 18866907 D01 Smoke Detector Multipurpose Building 900 East Entrance Photoelectric 18386437 D01 Smoke Detector Electrical Boys Locker Photoelectric 18386456 D02 Smoke Detector 2nd MDF Administration Photoelectric 18863273 D02 Smoke Detector Boys Locker Room Staff R R Photoelectric 18386448 D02 Heat Detector Press Box Rate-of-Rise 18386506 D03 Pull Station MDF Single Action 18866908 D03 Heat Detector Press Box Rate-of-Rise 18386507 D03 Pull Station South . Gym Vestibule Single Action 18386454 D04 Smoke Detector 2nd Corridor Administration Building Photoelectric 18386526 D05 Smoke Detector 2nd Corridor Administration Building Photoelectric 18386527 D05 Smoke Detector Fire Academy

Classroom 1A Photoelectric 18862611

D06 Smoke Detector 2nd Floor Corridor Administration Building Elevator Lobby

Photoelectric 18866675

D06 Smoke Detector Boys Locker Room Corridor Southern Entrance

Photoelectric 18386451

Intrepid Electronic Systems 36 12/14/2014

D06 Smoke Detector Classroom Fire Academy 1A Photoelectric 18863145 D07 Smoke Detector Boys Locker Room Office Restroom Photoelectric 18386467 D07 Smoke Detector North 1st Floor Elevator Machine Room

Administration Photoelectric 18866674

D07 Smoke Detector Northwest Classroom Storeroom Fire academy 1A

Photoelectric 18863144

D08 Smoke Detector 2nd Corridor Administration Building Photoelectric 18386528 D08 Smoke Detector Fire academy Break Room Photoelectric 18866894 D08 Pull Station Northwest Gymnasium Southeast Single Action 18386444 D09 Smoke Detector Corridor Administration Building Photoelectric 18386529 D09 Pull Station Gymnasium East Single Action 18866909 D10 Smoke Detector 1st Floor Administration Hall Photoelectric 18386559 D10 Smoke Detector Fire academy Mens Restroom Photoelectric 18866890 D10 Beam Detector Gymnasium 18386574 D10 Heat Detector Ticket Booth Rate-of-Rise 18386491

D101 Fan Shutdown Girls Locker Room AHU Control Building

Supply 18386355

D11 Smoke Detector Fire academy Janitor Photoelectric 18866891 D11 Beam Detector Gymnasium 18386573

D118 Smoke Detector Girls Locker Room Vestibule Photoelectric 18386387 D12 Smoke Detector 1st Floor Administration English Office Photoelectric 18386558 D12 Smoke Detector Fire academy Office 2 Photoelectric 18866889 D12 Beam Detector Gymnasium 18386572

D120 Smoke Detector Wrestling room IDF closet Photoelectric 18866916 D13 Beam Detector Gymnasium 18386571 D13 Smoke Detector Multipurpose Building 900 Kitchen

Vending Area Photoelectric 18386427

D13 Smoke Detector Work Room Fire academy Photoelectric 18866885 D14 Smoke Detector 1st East Conference Administration Photoelectric 18386556 D14 Smoke Detector Boys Locker Room Photoelectric 18386471 D14 Smoke Detector Fire academy Office 1 Photoelectric 18866888 D15 Smoke Detector 1st Floor Administration Principal Photoelectric 18386555 D15 Smoke Detector Boys Locker Room Photoelectric 18386470 D15 Smoke Detector Multipurpose Building 900

Kitchen/Restroom Photoelectric 18386422

D15 Waterflow Switch Classroom Fire Academy 1A Above Ceiling

18866897

D16 Smoke Detector 1st Floor Administration Conference room

Photoelectric 18866887

D16 Smoke Detector Boys Locker Room Team Room Photoelectric 18386475 D16 Smoke Detector Multipurpose Building 900

Kitchen/Locker Photoelectric 18386423

D17 Smoke Detector Boys Locker Room Storage Room Photoelectric 18386476 D17 Heat Detector Multipurpose 900 Above Ceiling Heat Rate-of-Rise 18386424 D17 Duct Detector Secretary 127 Building Administration Photoelectric 18865514 D18 Smoke Detector 1st Floor Administration Principal

Secretary's Office Photoelectric 18386554

D18 Smoke Detector Boys Locker Room Corridor Photoelectric 18386446 D18 Smoke Detector Multipurpose Building 900 Kitchen

Vending Area Photoelectric 18386426

D19 Smoke Detector 1st Floor Administration Copy Room Photoelectric 18386552 D19 Smoke Detector Boys Locker Room Corridor Photoelectric 18386450 D19 Smoke Detector Multipurpose Building 900 Office Photoelectric 18386428

Intrepid Electronic Systems 37 12/14/2014

D20 Smoke Detector 1st Floor Administration Reception Photoelectric 18386553 D20 Smoke Detector Boys Locker Room Corridor Photoelectric 18386465 D20 Smoke Detector North Stairwell Building 200 Ionization 18863280 D21 Smoke Detector 1st Floor Administration Counselor Photoelectric 18386548 D21 Smoke Detector 2nd Corridor Building 200 Ionization 18386514 D21 Duct Detector Multipurpose Building 900 Kitchen

Above D22 Photoelectric 18386425

D21 Smoke Detector Pool Area Room Storage Photoelectric 18386504 D22 Smoke Detector 1st Floor Administration Counselor Photoelectric 18386547 D22 Smoke Detector 2nd Corridor Building 200 Ionization 18386513 D22 Smoke Detector West Pool Area Ticket Booth Photoelectric 18386503 D23 Smoke Detector 1st Floor Administration Counselor Photoelectric 18386546 D23 Smoke Detector 2nd Corridor Building 200 Ionization 18386530 D23 Smoke Detector Boys Locker Room Team Room Photoelectric 18386455 D23 Smoke Detector West Track And Field Concession Room Photoelectric 18866906 D24 Smoke Detector 1st Floor Administration Administrator

APED Photoelectric 18386545

D24 Smoke Detector 2nd Corridor Building 200 Ionization 18386531 D24 Smoke Detector Concession Mens Restroom Photoelectric 18866904 D24 Smoke Detector South Gym Vestibule Photoelectric 18386452 D25 Smoke Detector 1st Floor Administration Registrar Photoelectric 18386550 D25 Smoke Detector 2nd Corridor Building 200 Ionization 18386532 D25 Smoke Detector Concession Womens Restroom Photoelectric 18866905 D25 Smoke Detector South Gym Vestibule Photoelectric 18386453 D26 Smoke Detector 1st Floor Administration Counselor Tech Photoelectric 18386549 D26 Smoke Detector 2nd Corridor Building 200 Ionization 18386533 D26 Smoke Detector Gymansium Womens restroom Photoelectric 18866912 D27 Smoke Detector 1st Floor Administration Hallway Photoelectric 18386551 D27 Smoke Detector Fire academy Classroom 1A FACP IDF Photoelectric 18866895 D27 Smoke Detector Gymansium Mens Restroom Photoelectric 18386502 D27 Smoke Detector South Stairwell Building 200 Ionization 18863279 D28 Smoke Detector Gymansium Team Room Photoelectric 18386501 D28 Duct Detector West Cooridor Building Administration Photoelectric 18865515 D29 Smoke Detector 1st Floor Administration Workroom Photoelectric 18386544 D29 Smoke Detector Gymansium Storage Photoelectric 18386500 D29 Smoke Detector Classroom Fire Academy 1B Photoelectric 18863143 D30 Smoke Detector 1st Floor Administration IDF Photoelectric 18386542 D30 Smoke Detector Classroom Fire Academy 1B Photoelectric 18862612 D30 Smoke Detector North Stairwell Building 300 Ionization 18863278 D30 Smoke Detector Northeast Gym Main entrance Photoelectric 18866911 D30 Smoke Detector Northeast Classroom Storeroom Fire

Academy 1B Photoelectric 18863256

D31 Smoke Detector 1st Floor Administration Hallway Photoelectric 18386543 D31 Smoke Detector Corridor Building 300 Ionization 18386520 D31 Smoke Detector Northeast Gym Main entrance Photoelectric 18866910 D32 Smoke Detector 1st Floor Administration APA Photoelectric 18386539 D32 Smoke Detector Corridor Building 300 Ionization 18386521 D33 Smoke Detector 1st Floor Administration Advisor Photoelectric 18386538 D33 Smoke Detector Corridor Building 300 Ionization 18386522 D33 Smoke Detector Wrestling room Vestibule Photoelectric 18866917 D34 Smoke Detector 1st Floor Administration Hallway Photoelectric 18386541 D34 Smoke Detector Corridor Building 300 Ionization 18386523 D35 Smoke Detector Corridor Building 300 Ionization 18386525

Intrepid Electronic Systems 38 12/14/2014

D35 Duct Detector West Cooridor Building Administration Photoelectric 18865508 D35 Smoke Detector Wrestling room Photoelectric 18862610 D36 Smoke Detector 1st Floor Administration Hall Photoelectric 18386560 D36 Smoke Detector South Stairwell Building 300 Ionization 18863277 D37 Smoke Detector 1st Floor Administration Hall Photoelectric 18386561 D37 Smoke Detector Multipurpose Building 900 Boys

restroom Photoelectric 18386430

D37 Smoke Detector Wrestling room Photoelectric 18866918 D38 Smoke Detector 1st Floor Administration Hall Photoelectric 18386562 D38 Smoke Detector Multipurpose Building 900 Girls

Restroom Vestibule Photoelectric 18386431

D38 Smoke Detector Wrestling room Photoelectric 18866919 D39 Smoke Detector 1st Floor Administration Hall Elevator

Lobby Photoelectric 18866668

D39 Smoke Detector Multipurpose Building 900 Girls Restroom

Photoelectric 18386432

D40 Smoke Detector 1st Floor Administration Hall Photoelectric 18386563 D40 Smoke Detector Corridor Building 300 Ionization 18386524 D40 Smoke Detector Multipurpose Building 900 Boys

restroom vestibule Photoelectric 18386429

D41 Smoke Detector 1st Floor Administration Hallway Photoelectric 18866886 D41 Smoke Detector Storage Girls Locker Room Vestibule Photoelectric 18386380 D42 Smoke Detector 1st Floor Administration Health Office Photoelectric 18386540 D42 Smoke Detector Storage Girls Locker Room Vestibule Photoelectric 18386381 D43 Smoke Detector Restroom Building Mens Restroom Photoelectric 18386442 D43 Smoke Detector Restroom Girls Locker Room Vestibule Photoelectric 18386382 D44 Smoke Detector 1st Floor Administration Liason Photoelectric 18386536 D44 Smoke Detector Girls Locker Room Vestibule Photoelectric 18386386 D44 Smoke Detector Restroom Building Womens Restroom Photoelectric 18386443 D45 Smoke Detector 1st Floor Administration Advisor Photoelectric 18386535 D45 Smoke Detector Storage Room Girls Locker Room

Vestibule Photoelectric 18386384

D46 Smoke Detector 1st Floor Administration Security Photoelectric 18386534 D46 Smoke Detector Storage Room Girls Locker Room

Vestibule Photoelectric 18386383

D47 Smoke Detector 1st Floor Administration Hallway Photoelectric 18386537 D47 Smoke Detector Restroom Girls Locker Room Photoelectric 18386350 D48 Smoke Detector Girls Locker Room Photoelectric 18386353 D48 Duct Detector West Cooridor Building Administration Photoelectric 18865509 D49 Smoke Detector Girls Locker Room Photoelectric 18386354 D50 Smoke Detector Electric Room Girls Locker Room Photoelectric 18385882 D51 Smoke Detector Corridor Girls Locker Room Photoelectric 18386378 D53 Smoke Detector Gym Northwest Corridor Photoelectric 18386389 D54 Smoke Detector Gym Room Vestibule Photoelectric 18386379 D55 Heat Detector Janitorial Girls Locker Room Vestibule Rate-of-Rise 18386385 D56 Smoke Detector Womens Restroom Pool Area Photoelectric 18863269 D57 Smoke Detector Corridor Girls Locker Room Photoelectric 18386349 D58 Smoke Detector Staff Restroom Girls Locker Room Photoelectric 18386352 D59 Smoke Detector Staff Room Girls Locker Room Photoelectric 18386351 D60 Heat Detector Girls Locker Room Rate-of-Rise 18385883 D61 Heat Detector Girls Locker Room Rate-of-Rise 18385889 D62 Heat Detector Girls Locker Room Rate-of-Rise 18386356 D63 Smoke Detector Girls Locker Room Team Room Photoelectric 18386357

Intrepid Electronic Systems 39 12/14/2014

D71 Smoke Detector Corridor Girls Locker Room Photoelectric 18386348 D72 Duct Detector Boys Locker Room Photoelectric 18386469 D73 Duct Detector Corridor Girls Locker Room Photoelectric 18386388 D74 Smoke Detector Pool Area Boys Restroom Photoelectric 18386505 D75 Smoke Detector Boys Locker Room Photoelectric 18386474 D76 Smoke Detector Boys Locker Room Staff Room Photoelectric 18386457 D77 Smoke Detector Boys Locker Room Staff Room Photoelectric 18386447 D77 Fan Shutdown Roof Administration

Building A/C 4 SHUT DOWN Supply 18865497

D78 Smoke Detector Boys Locker Room Restroom Photoelectric 18386449 D78 Fan Shutdown Roof Administration

Building A/C 3 SHUT DOWN Supply 18865496

D79 Fan Shutdown Roof Administration Building A/C 2 SHUT DOWN

Supply 18865495

D80 Fan Shutdown Roof Administration Building A/C 1 SHUT DOWN

Supply 18865494

D81 Smoke Detector Boys Locker Room Office Photoelectric 18386466 D81 Duct Detector Copy Room 126 Building

Administration Photoelectric 18865510

D82 Heat Detector Boys Locker Room Office Restroom Rate-of-Rise 18386468 D82 Duct Detector Secretary 127 Building Administration Photoelectric 18865511 D83 Heat Detector Boys Locker Room Rate-of-Rise 18386472 D83 Duct Detector Secretary 127 Building Administration Photoelectric 18865513 D84 Smoke Detector Boys Locker Room Photoelectric 18386473 D84 Elevator North 1st Floor Elevator Machine Room

Administration Recall Alternate 18866671

D85 Elevator North 1st Floor Elevator Machine Room Administration

Recall Primary 18866672

D86 Releasing Device North 1st Floor Elevator Machine Room Administration 1st Floor DH

Door Holder 18866673

D87 Releasing Device North 1st Floor Elevator Machine Room Administration 2nd Floor DH

Door Holder 18866679

D88 Smoke Detector 1st Floor Administration Office Photoelectric 18386557 D89 Smoke Detector Boys Restroom Building 300 Photoelectric 18386510 D9 Smoke Detector Fire academy Womens Restroom Photoelectric 18866892 D90 Smoke Detector Boys Restroom Building 300 Photoelectric 18386511 D91 Smoke Detector Boys Restroom Building 300 Photoelectric 18386512 D92 Smoke Detector Girls Restroom Building 200 Photoelectric 18386497 D93 Smoke Detector Girls Restroom Building 200 Photoelectric 18386498 D94 Smoke Detector Girls Restroom Building 200 Photoelectric 18386499 D99 Initiating Device Fire academy FACP closet Monitor Module 18866901 M01 Initiating Device Electrical

Building 300 Heats/Pull Stations Coverage

Monitor Module 18386371

M03 Initiating Device Electrical Building 300 First Floor Smoke Detectors

Monitor Module 18386344

M04 Initiating Device Electrical Building 300 Heat Coverage

Monitor Module 18386370

M05 Initiating Device Electrical Building 300 Heat Coverage

Monitor Module 18386369

M06 Indicating Device Electrical Building 200 First Floor Smoke

Control Module Bld. 300

18386347

Intrepid Electronic Systems 40 12/14/2014

Detectors M07 Initiating Device Electrical

Building 300 Heat Coverage Monitor Module 18386368

M08 Initiating Device Electrical Building 700 Conventional Heat Coverage

Monitor Module 18386183

M085 Initiating Device Electrical Building 1000 South Conventional Heat Coverage

Monitor Module 18385884

M086 Initiating Device Electrical Building 1000 North Conventional Heat Coverage

Monitor Module 18385885

M087 Initiating Device Electrical Building 1000 North Conventional Heat Coverage

Monitor Module 18385887

M088 Initiating Device Electrical Building 1000 South Conventional Heat Coverage

Monitor Module 18385888

M09 Initiating Device Electrical Building 600 Conventional Heat Coverage

Monitor Module 18386358

M12 Initiating Device Electrical Building 700 Conventional Heat Coverage

Monitor Module 18386182

M14 Initiating Device School Bank FCPS Room Monitor Module 18386494 M15 Initiating Device Multipurpose Building 900 Heats/Pulls Monitor Module 18386416 M19 Initiating Device School Bank FCPS Room Monitor Module 18386493 M20 Initiating Device Building 1300 Heats/Pulls Monitor Module 18386390 M23 Initiating Device Electrical

Building 600 Conventional Heat Coverage

Monitor Module 18386359

M24 Indicating Device Electrical Building 600 Conventional Heat Coverage

Control Module Bld. 600

18386360

M25 Pull Station 2nd MDF Admin Single Action 18863274 M40 Releasing Device ElectricalBuilding 200/300 Door

Holders Door Holder 18386345

M74 Indicating Device Electrical Building 700 Conventional Heat Coverage

Control Module Bld. 700

18386180

M75 Initiating Device Electrical Building 700 Conventional Heat Coverage

Monitor Module 18386181

Intrepid Electronic Systems 41 12/14/2014

Building: James Lick High School Control Panel: 3

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Description ScanID

Zone/Circuit: CKT1- D126 Monitor Device Boys Locker Room FACP Room RF Trouble 18863268

Intrepid Electronic Systems 42 12/14/2014