Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equipment Retrofit and Replacement

Embed Size (px)

Citation preview

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    1/82

    Alternativestohcfcs

    intherefrigerationandairconditioningsector

    Practical Guidelines and Case

    Studies or Equipment Retrotand Replacement

    Unite

    d

    nations

    environment

    Progr

    amme

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    2/822

    Copyright United Nations Environment Programme 2010

    This publication may be reproduced in whole or in part and in any orm or educational

    or non-proft purposes without special permission rom the copyright holder, provided

    acknowledgement o the source is made. UNEP would appreciate receiving a copy o

    any publication that uses this publication as a source.

    No use o this publication may be made or resale or or any other commercial prupose

    whatsoever without prior permission in writing rom the United Nations Environment

    Programme.

    Disclaimer

    The designations employed and the presentation o the material in this publication do

    not imply the epression o any opinion whatsoever on the part o the United Nations

    Environment Programme concerning the legal status o any country, territory, city or area

    or i its authorities, or concerning delimitation o its rontiers or boundaries. Moreover, the

    views epressed do not necessarily represent the decision or the stated policy o the

    United Nations Environment Programme, nor does citing o trade names or commercialprocesses constitute endorsement.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    3/82 3

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    4/824 UNITED NATIONS ENVIRONMENTAL PROGRAM

    Acknowledgements

    This pubication as poduced b the UNEP Diisiono Technoo, Indust and Economics (DTIE)OonAction Banch ith nancia suppot o the SedishEnionmenta Potection Aenc. It as poducedin the ameok o the HCFC Hep Desk poject toencouae deeopin counties to achiee compianceith thei HCFC phaseout obiations and adopt

    enionmenta iend atenaties to HCFCs.The poject as manaed b the ooin team in theOonAction Banch, UNEP DTIE, Fance:

    mr. Rajra shHead

    mr. Ja s. curInteim Netok and Poic Manae

    m. Barbara HubrPoamme Assistant

    mr. Rupr d JuPoamme Assistant

    m. muur kb UruDocumentation Assistant

    THIS PUBlICATION wAS wrITTEN By:

    mr. ka BrOne, Beo reieationTechnoo ltd, Seden

    THE rEvIEwErS:

    dr. Huau AhaaSenio AdiseSedish Enionmenta Potection Aenc

    dr. Jau kaAssociate Poesso, Head o Oone lae

    and Cimate Potection Unit, ICrI, Poand

    dr. era carPoamme Oce, OonAction Banch,UNEP DTIE, Fance

    DESIgN:

    A dAmstedam

    PHOTO CrEDITS:Photos used in ues Kas BeoPhoto o r22 cinde on pae 17 Enionmenta Inestiation Aenc

    JOB NUMBEr: DTI/1282/PA

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    5/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    5

    Practical Guidelines and Case StudiesFor Equipment Retrot and Replacement

    Atenaties to HCFCs

    in the Rerigeration andAir conditioning Sector

    United nAtions enviRonment PRogRAmme

    Division o Technology, Industry & Economics

    OzonAction Programme

    15, rue de Milan

    75441 Paris CEDEX 09

    France

    swedisH enviRonmentAl PRotection Agency

    106 48 Stockholm, Sweden

    Visiting address:

    Valhallavgen 195, Stockholm

    Telephone: +46-8-698 10 00.

    Fax: +46-8-20 29 25

    Internet: www.naturvardsverket.se

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    6/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    6

    Introduction

    Alternatives to HCFCs

    in the rerigerationand air conditioningsectorPraa gu a ca su reup cr, Rr a Rpa

    HydRocHloRoFlUoRocARBons (HcFcs) are ozone

    depleting substances (ODS) controlled by the Montreal

    Protocol on Substances that Deplete the Ozone Layer that

    are widely used in rerigeration and air conditioning, oam

    blowing and solvent applications.

    In September 2007, the Parties to the Protocol accelerated

    the phase-out schedule or these chemicals through

    Decision XIX/6. Developing countries operating under Article

    5 o the Protocol (Article 5 countries) now have to reeze by2013 their HCFC production and consumption to the average

    o their 2009-2010 levels, ollowed by a 10 percent reduction

    by 2015, by 35 percent by 2020, by 67.5 percent by 2025, and a

    100 percent phase-out by 2030 (with 2.5 percent allowed, i

    necessary, or servicing existing equipment until 2040). The

    same decision requires developed countries to accelerate

    their phase-out schedule by 10 years to completely eliminate

    HCFCs by 2020) with 0.5 percent allowed, i necessary, or

    servicing existing equipment until 2030).

    Action on HCFCs is important in that these chemicals have

    an impact on both ozone depletion and climate change. Interms o direct impact, the most commonly-used HCFCs

    have ozone depleting potentials (ODPs) ranging rom 0.02

    (HCFC-123) to 0.11 (HCFC-141b) and global warming potentials

    (GWPs) ranging rom 76 (HCFC-123) to 2270 (HCFC-142b).

    Equipment using HCFCs consumes energy, which

    contributes to indirect global warming impacts.

    The rerigeration and air conditioning (RAC) sector was the

    biggest consumer o CFCs and in preparation or the total

    CFC phase-out on January 1, 2010, it gradually shited to the

    alternative rerigerants, including HCFCs. Today the sector

    has become one o the primary consumers o HCFCs and will

    need appropriate assistance to enable it to comply with the

    accelerated phase out.

    UNEP DTIE in cooperation with the Swedish Environmental

    Protection Agency (SEPA) has produced this publication to

    provide decision makers in Article 5 countries, the end-users

    and the service technicians a comprehensive source o

    inormation on alternative technologies that can be adopted

    to phase out HCFCs in the RAC.

    The report contains a section on alternative technologies

    including technical aspects and inormation on current

    market situation in developed countries (Article 2

    countries) and Article 5 countries. Another section covers acollection o industry case studies that exemplies state-o-

    the-art solutions using dierent technologies or dierent

    market segments.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    7/82 7

    sUmmARy

    tecHnicAl inFoRmAtion

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    8/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    8

    Executive

    Summary

    tHe PHAse-oUt o chlorouorocarbons (CFCs), one o the

    most aggressive Ozone Depleting Substances (ODS), is now

    almost completed in accordance with the Montreal Protocol.

    The ocus is now gradually shiting towards the phase-out

    hydrochlorouorocarbons (HCFCs) whose phase-outschedule has been accelerated by the Parties to the Protocol

    in Spetember 2007 through Decision XIX/6. Developing

    countries operating under Article 5 o the Protocol (Article 5

    countries) now have to reeze by 2013 their HCFC production

    and consumption to the average o their 2009-2010 levels

    ollowed by a 10 percent reduction by 2015; 35 percent by

    2020; 67.5 percent by 2025 and a 100 percent phase-out by

    2030 (with 2.5 percent allowed, i necessary, or servicing

    existing equipment until 2040). The same decision requires

    developed countries to accelerate their phase-out schedule

    by 10 years to completely eliminate HCFCs by 2020) with

    0.5 percent allowed, i necessary, or servicing existingequipment until 2030).

    HCFCs are widely used as a rerigerant in rerigeration and air

    conditioning systems and equipment as well as a blowing

    agent in the exible and rigid oam sector.

    The rst target in the rerigeration and air conditioning

    sector should be to minimize the installation o new HCFC

    systems. Considering that the pre-charged air conditioning

    systems constitute the biggest sub-sector, minimising

    their production will create a specic challenge in non-

    producing Article 5 countries. th au HcFc

    a h h pr b

    u h aua h pr urHcFc up ba r h ar 20092010.

    Hr a h r , a r HcFc

    r h ra a, paruar

    ar h r 2013 a hruhu h phau

    pr. On the other hand, countries that export pre-

    charged systems will start with a high HCFC consumption

    baseline but they will be able to comply easily with the

    phase-out schedule by simply converting their production

    processes to use nonODS technologies.

    There are well established alternative substances to R-22

    applications in the rerigeration and air conditioning sector.The prominent group o alternative substances are HFCs

    which are synthetic rerigerants with similar characteristics

    to HCFCs but no ozone depleting potential (ODP).

    As HFCs have a high global warming potential (GWP)

    there is a strong interest to minimize the introduction

    and emissions o HFCs. Other alternatives with lower or

    near zero ODP are available but are all associated with

    challenges that have to be overcome in order or them

    to play a major role on the market. Alternatives with

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    9/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    9

    negligible or zero GWP are ammonia, carbon dioxide and

    hydrocarbons. These are oten called natural rerigerants.

    Only hydrocarbons have similar technical characteristics

    to HFCs that could allow them to be used without major

    technology changes. Hydrocarbons are ammable andsaety precautions need to be considered during design,

    manuacturing, installation, service and decommissioning.

    For larger systems ammonia is well established on many

    markets but several Article 5 countries lack qualied

    technicians. Most countries need to increase the ocus on

    training or all technologies and good practice to acilitate

    the use o the best alternatives or dierent applications.

    There is no one-size-ts-all solution.

    All the HCFC alternative technologies require Article 5

    countries to upgrade the capacity o the servicing sector.

    In spite o the activities conducted during the phase outo CFCs, most o the Article 5 countries have a workorce

    that, to a large extent, still do not work according to

    internationally accepted good rerigeration and air

    conditioning paractises. The shortcomings in training,

    tools and enorcement o good practises cost industry

    and consumers large amounts o money in increased

    ailure rates and unnecessary high energy consumption.

    The strong ocus on initial cost oten results in poorly

    optimised systems and little interest to train sta.

    The industrialised countries have in most cases introduced

    certication schemes and restrictions on who can do certain

    activities related to ODS as well as HFCs. The alternatives all

    require special competencies to be used in an environmentally

    acceptable and sae way. A signicant upgrade o thecompetence level has taken place during the last 10 years in

    many non-Article 5 countries, where the use o virgin HCFCs

    have mostly been eliminated or totally phased out. Due

    to the challenges in upgrading the industry which mainly

    consists o small and medium enterprises (SMEs) most Article

    5 countries are only beginning this process. In order to phase

    out HCFCs and improve reliability as well as energy efciency,

    it is important or the industry to upgrade its competence in

    all alternative technologies as there is no single technology

    to date that can provide the ideal solution or all applications.

    To justiy investment in tools and training in alternative

    technologies, it is important to create an environmentwhere it is good business to do good practise. Providing clear

    regulatory rameworks and inormation to equipment owners

    is important to make necessary investments attractive or the

    industry. I purchasing environmentally hazardous rerigerants

    and working in the industry with little training and tools persist,

    the change will be very slow as there are many equipment

    owners with limited awareness and competence. Moreover,

    the high energy consumption and unnecessary short liespan

    o equipment are actors that are oten unknown to many.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    10/8210 UNITED NATIONS ENVIRONMENTAL PROGRAM

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    11/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    11

    ContentsIntroduction 6

    Guide to the Reader 7

    Executive summary 8

    Contents 11

    1 Alternatives to HCFCs in rerigeration and air conditioning 12

    1.1 Background 13

    1.2 HCFCs used in the rerigeration and air conditioning sector 15

    1.2.1 Air conditioning and industrial rerigeration traditional R-22 sub-sectors. 16

    1.2.2 Split and unitary air conditioning sector (including air-to-air heat pumps) 16

    1.2.3 VRV/VRF/multi-split systems (including heat pumps) 19

    1.2.4 Chillers in air conditioning and cooling applications (including heat pumps with indirect systems) 19

    1.2.5 HCFCs in commercial rerigeration 20

    1.2.6 Other HCFC-using sub-sectors in the RAC sector 20

    1.3 Energy efciency o air conditioning equipment 20

    1.4 Alternatives to HCFCs in air conditioning and rerigeration 21

    1.4.1 Ammonia 25

    1.4.2 Hydrocarbons 25

    1.4.3 Carbon dioxide (CO2) 27

    1.4.4 HFC alternatives used in new and retrotted systems with new oil 29

    1.4.5 HFC service blends used in existing systems 32

    1.5 Oils in rerigeration and air conditioning sytems 34

    1.6 Retrot procedures 36

    1.6.1 Documentation o status and perormance 38

    1.6.2 How to replace the oil? 39

    1.6.3 Retrot with the oil change method 41

    1.6.4 Retrot through ushing with the old rerigerant 411.6.5 Retrot through ushing with a solvent 41

    1.6.6 Number o oil changes required 43

    1.6.7 Methods o oil analysis and moisture content in oil 44

    1.6.8 Laboratory tests 44

    1.6.9 Reractometer test 44

    1.6.10 Test kit 44

    2 Case studies Alternative technologies in dierent applications 46

    2.1 The transition in the unitary and split air conditioning market 48

    2.1.1 Retrot o split air conditioning rom R-22 to R-407C with oil-change through ushing 48

    2.2 Chillers with HFCs 52

    2.2.1 Large low pressure chillers 52

    2.2.2 Medium-sized and small chillers 522.3 Fruit Storage with hydrocarbon chillers at Nickle arm in UK 53

    2.4 Cold store with low charge ammonia chiller 55

    2.5 Retrot o R-22 chiller to R-422D (oil change not required) 58

    2.5.1 Description o conversion procedures. 59

    2.6 Carbon dioxide heat pumps or domestic heating and tap water 60

    2.7 Carbon dioxide in supermarkets 62

    2.7.1 Evaluation o carbon dioxide supermarket in Sweden 63

    2.7.2 Evaluation o three carbon dioxide stores in Norway 66

    2.7.3 Market situation or CO2 as a rerigerant in supermarkets 67

    2.8 Retrot o R-22 supermarket in Romania to R-404A 67

    2.8.1 Results obtained or the rerigeration circuit operating at medium temperature 69

    2.8.2 Results obtained or the reezing circuit (LT) 71Appendix I - List o rerigerants 72

    Appendix II - Reerences 77

    Appendix II - Abbreviations and denitions 79

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    12/8212 UNITED NATIONS ENVIRONMENTAL PROGRAM

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    13/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    13

    UndeR tHe montReAl PRotocol on Substances

    that Deplete the Ozone Layer, developing countries (i.e.

    countries that operate under Article 5 o that agreement)

    have developed strategies and successully implemented

    measures which have phased out chlorouorocarbons

    (CFCs) - ODS with high ODP by 1 January 2010. In

    the coming years, the ocus will be to move away rom

    the HCFCs, substances with lower ODP values which

    have been used as transitional replacements while CFCs

    were being phased out. In Article 5 countries, HCFCs arescheduled to be completely phased out by 2030 (with a

    small servicing tail o only 2.5% allowed rom 2030-2040).

    This might seem to be a long time, but many countries are

    increasing their consumption o HCFCs rapidly and risk

    building an HCFC-based inrastructure that can be costly

    and complicated to convert to nonODS rerigerants

    in the uture. The reeze in 2013 (baseline is the average

    HCFC consumption between 2009 and 2010) will become

    a challenge i measures are not initiated immediately.

    It is important to ensure that all HCFC consumption

    (production and import - export) is correctly reported

    prior to baseline o 2009-2010 and reeze year o 2013,and that early actions are taken to reduce new HCFC

    consumption to a minimum.

    The rst priority should be to stop all new installations using

    HCFCs as soon as possible. There is a special challenge or

    countries importing HCFC-22 (R-22) equipment as they

    are shipped pre-charged with the rerigerant and does not

    count in the calculation o the countrys HCFC consumption

    baseline. As these equipment become old and servicing

    needs increase, only a limited quantity o HCFCs will be

    available on the market. Many Article 5 countries have

    no HCFC equipment production, but imports o R-22 air

    conditioning units are quickly increasing. Equipment thatuse alternative rerigerants are readily available or a slightly

    higher price, but it should also be kept in mind that R-22

    equipment on the market are o an older design, whereas

    newer models have been redesigned to meet much higher

    energy efciency standards. Thereore the installation o such

    equipment, while slightly higher in cost, will lead to additional

    energy savings in the long run. Many o the substances

    used to replace HCFCs have a signicant GWP which should

    be taken into account when alternative technologies are

    evaluated. The selection o alternative substances and

    technologies will signicantly aect the uture impact on

    the climate rom this sector. Both the direct impact rom thechosen substances and the energy consumed will depend on

    the technologies selected.

    1.1 Background

    01 Alternatives to

    HCFCs in rerigerationand air conditioning

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    14/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    14

    the installation o HCFCs has been in place since 2004 and a

    total ban on the use o virgin HCFCs began in 2010.

    The ollowing HCFCs are the most commonly used in the

    dierent sectors:

    HCFCs have traditionally been the global solution in sectors

    that are now rapidly growing in many developing countries,such as stationary air conditioning and large commercial

    and industrial rerigeration. In the later applications, HCFCs

    have been competing with ammonia, another well-proven

    mature technology. Other applications are new, since

    HCFC has been used as a replacement to acilitate the phase-

    out o CFC. Traditionally the retail ood sector mostly uses

    R-12 (CFC) and R-502 (containing CFC) but moved to R-22 as

    a transitional product beore non-ODS alternatives such as

    R-134a and R-404A/R-507 were accepted.

    HCFCs are used as a component in a large number o

    rerigerant blends, oten designed to match the behaviourand perormance o R-12 and R-502. These are oten called

    service or drop-in blends as they are intended to acilitate

    an easy replacement o CFCs in existing plants with minimal

    changes to the system.

    Technologies to move away rom HCFCs are well-known

    and proven in the industrialised countries and many o the

    alternatives are already partly introduced in developing

    countries due to inuences rom neighbouring markets and

    international companies. The strongest incentive or the

    continuous growth o markets or HCFCs is the lower initial

    price o both the substance and the equipment intended oruse with HCFC (although this is oten only in a short time

    perspective as long-term energy and uture retrot cost

    will be high). R-22 is also a product that the entire industry is

    amiliar with. Alternatives with less environmental impact are

    oten associated with slightly higher initial cost and a need

    or technical know-how to be dispersed to a large number

    o technicians. This creates an uncertainty in the market

    that can be taken advantage o by competing companies

    by preserving old technologies at minimal cost. For some

    o the environmentally-preerred solutions, there are also

    saety barriers to be addressed to make these alternatives

    viable solutions. A more extensive list o alternatives toHCFCs are listed in Appendix I - List o rerigerants. In

    Article 2 (i.e. developed country) markets, the transition has

    been happening over the last 15 years, so the commercial

    alternatives are well-proven. For example, in Europe a ban on

    sectoR tyPe oF HcFc

    Rrra auaur a r

    Domestic eieation limited use o seice dopin bends (nee used in equipment poduction)

    (HCFC141b in appiance insuation oam)

    Commecia reieation HCFC bends in seice, (HCFC141b in oam)

    Industia eieation HCFC22, r502 (a bend o CFC/HCFC), HCFC bends, (HCFC141b in oam)

    Tanspot eieation HCFC22, r502, HCFC bends, (HCFC141b oam)

    saar Ar c

    residentia and commecia AC HCFC22

    Chies HCFC22, HCFC123

    mb ar None o minima (poo compatibiit ith hoses)

    Fa HCFC141b, HCFC142b, HCFC22

    ma Ar None

    nma Ar HCFC22, HCFC141b, HCFC142b

    Fr Pr HCFC123, HCFC124, HCFC22 (bends)

    s HCFC141b, HCFC225ca, HCFC225cb

    Dieent sectos hee HCFCs ae most common used.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    15/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    15

    1.2 HCFCs used in the rerigeration andair conditioning sector

    sUmmARy HcFc Use in tHe RAc sectoRHCFCs ae ide used oe the entie industia and commecia eieation secto incudin o ood pocessin,distibution, stoae and etai (shops and supemakets). In ai conditionin, HCFCs hae paed a dominant oe

    in unita, spit and chie tpe sstems o ai conditionin in piate homes, hotes, oce buidins, estauants

    and othe pubic buidins.

    r22 is b a the most commonused HCFC in this secto. Othe HCFCs such as r124 and r123 hae been used in

    smae quantities o specia appications. Sti othe HCFCs such as HCFC141b and HCFC142b hae been used as

    boin aents in eieation equipment insuation ate the phase out o CFCs, sometimes in mitues ith r22.

    reieation and ai conditionin equipment is oba one o the sectos ith the hihest eectica poe consumption.

    The apid oth in this secto in man counties i esut in a need to epand poe poduction and distibution sstems.

    The ene consumption o counties in this secto aso contibutes sinicant to oba amin. with the epectedequiements in the oba aeements on eduction o een house ases the emissions o eieants such as HCFCs and

    HFCs as e as ene consumption in this secto i pa a sinicant oe in hethe these aeements achiee its taets.

    Aside FRom Being one o the major ODS-consuming

    sectors the rerigeration and air conditioning sector (RAC)

    including heat pumps and dehumidiers, also uses 15% to

    20% (IIR, 2002) o global electrical energy. The economic

    growth in many Article 5 countries in hot climates results in

    a corresponding growth o the RAC sector. The applications

    where HCFCs are used are important to reduce the losses

    in the ood production and distribution chain. There arealso many applications that are essential or industrial

    production and human comort where HCFCs play an

    important role today. The growth will result in increasing

    energy consumption i measures to improve efciency

    including the introduction o more energy-efcient

    technologies - are not implemented eectively/appropriately.

    thr ar pr h aaab rpa

    HcFc h p uba a a

    pr r a rrra a ar

    appa.Alternatives such as HFCs can

    be used with minimal changes to the existing technology, but

    have a high GWP. Rerigerants with a low or zero GWP should

    be the preerred solution when they can be used in a saeand cost-eective manner without resulting in higher energy

    consumption. High GWP rerigerants should only be used when

    technical, economic or saety reasons require them, and in such

    cases they should be used in systems with minimized leakage

    and emissions during service and at the end o equipment lie.

    HCFC is also used as eedstock or the production o plastics

    and other chemicals.

    When replacing HCFCs it is important to evaluate the envi-

    ronmental impact o the alternatives since the most com-

    mon replacements are hydrouorocarbons (HFCs) which

    have a signicant Global Warming Potential. The impact

    o alternative rerigerants and the energy consumption o

    selected system solutions should also be evaluated

    to minimize their total impact on the environment.

    Adopting measures to reduce the rerigeration and

    air conditioning loads through good building design

    and processes are obviously the most efcient way

    o reducing the environmental impact o these

    technologies.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    16/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    16

    The emissions should be minimized through implementation

    o good servicing practices and eective re-use schemes.

    The main HCFC commonly used in air conditioning and

    rerigeration applications beore 1985 was R-22. The main

    sectors where R-22 was the preerred rerigerant were in the

    air conditioning and industrial systems sectors where it was

    also competing with ammonia. When CFCs were identied

    as powerul ODS and a global phase-out was agreed under

    the Montreal Protocol in 1987, HCFCs were identied as less

    harmul substances and introduced in several sub-sectors

    tHe PHysicAl PRoPeRties o R-22 result in good

    perormance in a wide range o applications but with a

    limiting actor caused by the high temperatures occurringduring compression. In rerigeration applications where the

    temperature dierence between the desired temperature

    and the surroundings is high, the risk o unacceptable

    conditions and ailures increases. In hot climates, the

    challenge in commercial rerigeration applications increases

    signicantly more than in air conditioning systems. In

    industrial applications R-22 was an alternative to ammonia

    where it provided better cooling capacities than R-12 andwas more readily available and cost less than R-502. In large

    installations the high temperatures could be handled with

    dierent technical solutions, but it was not as cost-eective

    in smaller commercial systems where R-12 and R-502 were

    more common.

    1.2.2 sPlit And UnitARy AiR conditioning sectoR (inclUding AiR-to-AiR HeAtPUmPs)

    that were not traditional HCFC applications. As a result,

    R-22 and HCFC-containing drop-in blends are now ound

    in commercial rerigeration and to some extent in transport

    rerigeration. The result is that replacement o HCFCs

    will have an impact on many sectors and to some extent

    the alternatives used will sometimes be the alternatives

    designed to replace CFCs rather than those designed or

    R-22 applications. The main ocus in this report will be on

    segments where R-22 has a signicant market share but in

    order to give a more complete update, other sectors will

    also be covered, although with less attention.

    1.2.1 AiR conditioning And indUstRiAl ReFRigeRAtion tRAditionAl R-22sUB-sectoRs.

    sUmmARysPlit And UnitARy systemsr22 is used main in spit and unita ai conditionin equipment (see Fiue 1.2). The quantit used in this

    appication is sometimes undeated because in the manuactuin/epotin count the initia chae is

    consideed consumption heeas it is not consideed as such in the impotin count hee the equipment i

    be instaed and seiced.

    In ne sstems atenaties ae eadi aaiabe. Most oten r22 is epaced ith r410A o r407C. lae oumes

    o r22 sstems ae sti bein instaed in some makets due to oe inestment outa and essinomed

    customes. As these units ae, the can be epected to pa a sinicant oe in the consumption o HCFCs, once the

    eee in HCFC consumption (this is usua equiaent to impots in most Atice 5 counties) in 2013 takes eect.

    One o the pioities shoud be to stop the intoduction o ne r22 equipment. The soone eisation to ban the

    impot, maketin and instaation o ne r22 sstems is estabished, the easie the tansition i be. The cost o

    tansition i be oe as the added initia cost is much oe than the cost to etot the sstem.

    F. 1.1 (opposite pae) HCFCsae used in a eieation and aiconditionin equipment that in tunis used eehee in societ.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    17/82 17

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    18/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    18

    tHis mARket is dominAted by large volume

    production, mostly rom Asia, but in some markets,

    small local manuacturers are also present (see 2.1 The

    transition in the unitary and split air conditioning market).

    The price competition is extremely tough and quality/

    perormance is not always a actor that the customer can

    evaluate. These systems are installed in ofces, hotels,

    restaurants, bars,shops and private homes. The numbers

    o suppliers/installers/service providers involved are high

    and the level o competency is oten low. Global players

    have local representation in many countries either through

    their own subsidiaries or through local distributors, but

    signicant volumes are traded by less skilled and specialised

    companies competing in segments with low pricing, which

    makes this sector challenging and diversied.

    A signicant part o the market will be ocused solely on low

    initial price at the expense o equipment efciency. As this

    market rapidly grows in many countries, so does the numbero units installed each year increase. Thereore this sector

    can play a signicant role as the limit on imports o HCFCs

    or servicing comes into eect. These units are supplied with

    a ull rerigerant charge and the HCFCs contained therein

    are not counted as part o the imported HCFC quantities,

    but their leakage rates can be expected to increase gradually

    through the year as the units grow old.

    The leakage rates are urther increased due to the oten low

    skills o the installers, particularly or split units, as they are

    installed on site with one component located outside and

    the other inside the building. For more than ten years, ODS-

    ree but high GWP HFC-based alternatives such as R-410A

    and R-407C have been available in this sector. However, due

    to the cost o retrot and relatively low value o old units,

    retrots to HFCs have not been the preerred solution on

    most markets since these systems will oten already be old

    beore the phase out o R-22 becomes urgent. On the other

    hand, in Article 5 countries, the price o labour is relatively

    low and retrots can be a more interesting option than

    replacements. This will be described urther in the sectionpresenting the case studies on retrot methods, options

    and available solutions or existing equipment.

    Fan

    Fan

    Air evaporator

    Air condenser

    Air condenser

    Air evaporator

    Connections to joinindoor and oudoor unit

    Fan

    Fan

    Outdoorun

    it

    Indoorunit

    F. 1.2 Unita sstems (et) ae mounted thouh the a ithout the need to connect the eieation sstem on site.Spit sstems (iht) ae assembed on site.

    sp fhar:

    UnitARy systemsp fhar:

    sPlit system

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    19/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    19

    cHilleRs ARe systems tHAt indiRectlycool a

    building or a process. Typically they are used in larger

    systems and the cooling distributed with water or amixture o water and anti-reeze when it is necessary to

    work at low temperatures. Chillers are mainly actory-built

    units that are intended to cool a liquid such as water or, i

    a lower temperature is desired, uids with lower reezing

    points. Chillers can be air-cooled, i.e. where the condenser

    is directly cooled by air, or water-cooled, where the

    condenser is cooled by circulating water (possibly with

    reeze depression i the climate is such that the water would

    risk reezing in the winter). Their main applications are

    or air conditioning in larger buildings, i.e. hotels, ofces,

    hospitals, military complexes, etc. or or process cooling in

    various industries. This solution is oten associated with ahigher investment cost than solutions with split systems or

    air conditioning or smaller units or each object in need o

    cooling in the industry. In many cases, small non-chiller RAC

    units can be installed gradually and oten by tenants, thus

    eliminating the need or the owner to invest and charge

    costs to the tenants. Central systems with chillers are oten

    preerred in larger systems where the possibilities o more

    stable operation by balancing cooling loads over time (as

    the loads are not occurring simultaneously over the whole

    building), reducing maintenance cost are preerred as it also

    avoids noise and/or esthetical drawbacks o having large

    numbers o split/unitary systems. This option is oten usedin larger buildings operated by owners with the capability

    to invest in more long term solutions. Chillers are globally

    used in central air conditioning systems where R-22 is one

    o the most commonly used rerigerants, apart rom CFCs

    1.2.4 cHilleRs in AiR conditioning And cooling APPlicAtions (inclUding HeAtPUmPs witH indiRect systems).

    1.2.3 vRv/vRF/mUlti-sPlit systems (inclUding HeAt PUmPs)

    which are still present in large quantities in the old chiller

    equipment in both developed and developing countries.

    Apart rom their use in the air conditioning sector, HCFCchillers using R-22 are also common in the ood processing

    industry as well as in other industries where processes need

    to be cooled. At one point a large chiller segment using R-11

    was to some extent converted to R-123 which is an HCFC,

    but has low ODP and low GWP. At the time this report was

    Pump

    secondary fluid i.e.

    water/glychol/brine/CO 2

    Refrigerant inside: NH3, HC or HFC

    Air or liquidcondenser

    F. 1.3 Chies use seconda fuid to indiect coo the oomo object.

    tHese ARe systems that have been developed rom the

    split systems (Daikin Industries developed and launched

    Variable Rerigerant Volume and protected the use o

    the acronym VRV so other manuacturers use VRF

    or Variable Rerigerant Flow). These system designs

    are characterised by one unit cooling (and sometimes

    heating) several rooms and adapting its capacity to

    the variations in the demand. These units have a lot

    in common with split systems, but are dependent on

    complex electronic controls and have an intricate design,

    which will make them more difcult to retrot. This is

    because oil transport and control behaviour could be

    aected and difcult to predict unless there is access to

    design ino and proper test acilities or support rom the

    manuacturer. For obvious reasons, the manuacturers are

    rarely interested in investing the resources required to

    extend the lie o existing equipment.

    sp fhar:

    cHilleR

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    20/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    20

    smAlleR volUmes o HCFCs are used in almost all other

    RAC sectors. Both R-22 and HCFC-containing service blendsare used to replace R-12 and R-502. In transport rerigeration

    some manuacturers have converted to R-22 while the

    majority went directly to R-134a and R-404A. In some niche

    markets such as the high temperature air conditioning in theindustry, there are applications where CFC rerigerant R-114

    was replaced with R-124, which is an HCFC.

    1.2.6 otHeR HcFc-Using sUB-sectoRs in tHe RAc sectoR

    1.2.5 HcFcs in commeRciAl ReFRigeRAtion

    in mAny ARticle 5 coUntRies, commercial rerigeration

    has traditionally been dominated by smaller plug-in systems

    and display cases cooled by individual condensing units. The

    introduction o larger central systems was limited to newerand larger supermarkets.

    These systems in stores and shops were oten cooled with

    R-12 and to some extent R-502 in the low temperature

    applications. With increasing pressure to phase out

    CFCs, transition to R-22 had occurred in many countries

    beore R-404A or R-507 were accepted as the rerigerants

    or this sector. In the process o phasing out R-22 rom

    commercial systems, R-404A and R-507 are being used

    as alternatives more requently than in air conditioning.The use o R-22 in commercial rerigeration is signicantly

    more challenging than the rerigerants it replaced and the

    non-ODS alternatives developed or this sector. This is due

    to the properties o R-22 which cause higher compressor

    temperatures requiring signicant changes to the systems

    design or quick xes such as installing water sprays or the

    condensers as shown in Fig. 1.4.

    F. 1.4 A commeciaeieation instaation usinr22 in a hot cimate. Thismode equies a ate spaon the condense to aoid hihpesssue and oeheatin othe compessos. Hoee thiscauses coosion and astesate that is oten in shot supp.In this case inceased eecticahaads ae obious and good

    Pactice has not been popeconsideed.

    written, there were no known alternatives to R-123 suitable

    or existing systems.

    R-245a is an HFC alternative that can be used in low pressure

    chiller applications but has a higher pressure making it

    unsuitable or most existing systems. With the current

    inormation it can be expected that in this sector existing

    systems using R-123 will be maintained with minimum leakages

    until the end o their lie. In most developing countries the

    introduction o R-123 has been limited although in some

    markets low pressure R-123 chillers could be a segment that

    will require special attention due to the challenges to replace

    it. As there are only a ew suppliers that produce R-123 chillers,

    six according to James M. Calm (James M. Calm, 2002), it

    would be possible to identiy exactly how many units o this

    system are in operation and where they were installed by

    contacting the manuacturers/importers.

    As the use o indirect systems make it possible to more

    reely locate rerigeration units with toxic or ammable

    rerigerant, chillers using ammonia and hydrocarbon

    rerigerants are becoming more common.

    the-art, non-ODS equipment then has to compete with the

    low cost R-22 equipment. The price dierence is not mainlydue to the change o rerigerant but rather to the larger heat

    exchangers and oten to design improvements that reduce

    energy consumption and noise to meet international market

    demands. A report o the International Energy Agency (IEA)

    one ReAson wHy R-22 still prevails in the new installa-

    tion market in many Article 5 countries is the lack o energyefciency requirements and the low awareness o customers

    about the cost o running the systems. In this situation, the

    equipment purchase price becomes the only criterion or

    equipment selection. The more energy efcient state-o-

    1.3 Energy efciency o air conditioningequipment

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    21/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    21

    [IEA, SATORU KOIZUMI, 2007] evaluated the impact on

    energy consumption o increased efciency requirements

    in Article 5 countries. The report gave the example o Ghana,

    an Article 5 country which imports its AC equipment and

    needs stronger national energy efciency requirements. It

    demonstrated why the efciency o installed equipment in

    the country is lower than that o the equipment available on

    the market.

    sUmmARyAlteRnAtives to HcFcThee is not and i most ike nee be one eieant that can be used to epace a HCFC appications, since

    the use is so idespead and the equiement o bette ene ecienc i esut in an inceased demand to

    adapt the technooies to the actua opeatin conditions.

    Each sstem, o at east each tpe o sstem, needs to be eauated om seea pespecties to nd

    the enionmenta and technica best option that can be used sae at an acceptabe inestmentand opeatin cost.

    when eauatin the impact o rAC equipment on the cimate, the diect gwP o the eieant used as e

    1.4 Alternatives to HCFCs in air conditioningand rerigeration

    F. 1.6 Deeopment o ene ecienc o AC equipment in Japan.

    6.0

    5.0

    4.0

    3.0

    2.0

    1.0

    0.0

    eeR

    1997 1998 1999 2000 2001 2002 2003 2004 2005

    F. 1.5 Deeopment o ene ecienc o AC equipment inghana. The count has no domestic equipment poduction.

    3.0

    2.5

    2.0

    1.5

    1.0

    0.5

    0.02000 2001 2003 2004 2005

    eeR

    In comparison, Japan, which has clear and strict energy

    efciency requirements, showed a rapid improvement o

    energy efciency despite the act that rom the beginning

    the country already had a signicantly better perormance

    rate than Ghana. The Japanese air conditioners used 50%

    less electricity than those installed in Ghana. The expected

    rapid increase in use o air conditioning systems in many

    Article 5 countries will result in drastically higher electricity

    consumption. The use o low efciency equipment will be

    costly in terms o energy consumption. Furthermore, the

    oten weak inrastructure used in producing and distributing

    electricity will be requently overloaded by excessive

    energy demands coming rom high air conditioning loads.An introduction o efciency requirements and labelling

    schemes to improve efciency is vital or Article 5 countries.

    For Ghana, an enorcement o minimum energy standards in

    installed air conditioning units was estimated to reduce the

    countrys total need or generated electrical power by 8%.

    The report contains an evaluation o barriers and possible

    counter-measures to introduce higher efciency equipment.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    22/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    22

    dUe to tHe HUge nUmBeR o applications or

    rerigeration and air conditioning systems with dierent

    operating conditions and requirements, it is practically

    impossible to nd a single ideal rerigerant. The ideal

    rerigerant would need to have the ollowing properties and

    characteristics, among others:

    Zero Ozone Depleting Potential (ODP)

    Energy efcient = have high Coefcient o Perormance

    (COP), i.e. low indirect Global Warming Impact

    Zero or low Global Warming Potential (GWP), i.e. low Direct

    Global Warming Impact

    Chemically stable at all temperatures and environments

    including contaminated systems

    Compatible with all materials

    metals

    elastomers (plastic/rubber materials)

    oil, including suitable miscibility/solubility with oil

    Non-toxic

    Non-ammable

    Low cost

    Commercially available

    The above list does not reect an order o priority as this

    cannot be dened on a general level. Obviously, rerigerants

    with high ammability and toxicity can be easily handled in

    some applications and may be more or less impossible to

    be applied in others, at least without a signicant increase

    in energy consumption and/or cost. Zero ODP is a legal

    requirement in many countries already. The total warming

    impact o a rerigeration air conditioning system will consist

    o a direct eect rom released rerigerants and an indirect

    eect rom carbon dioxide emissions during the production

    o energy used to operate the system. The combined eect

    o Direct and Indirect warming eect is oten calculated

    as the ta eua war ipa r tewi (see

    Abbreviations and denitions)

    TEWI takes into consideration leakage rates, emissions

    rom the site where systems are scrapped and energy

    consumption. As these actors are dierent or each system

    and difcult to estimate, TEWI is oten calculated based on

    statistical values and experience. The result will be aected by

    how the dierent actors are estimated. Factors like leakage

    and recovery rate are dependent on the quality o installation

    and service. This will change over time as service is improved

    through training in combination with regulations that require

    end-users and contractors to keep records, discourage

    emissions and enorcement actions. To assume leakage

    rates o 30% common on many markets or 5% achieved inothers will drastically change the balance between direct

    emissions rom leakage and indirect emissions rom energy

    consumption. Few Article 5 countries have so ar been

    successul in implementing unctional rerigerant re-use

    as the sstems tota ene ecienc shoud be measued. A sstem usin a eieant ith a hihe gwP can

    be moe ene ecient and hae a oe tota impact on the cimate.

    U a r gwP rrra a a a r a a a apab a prrab u

    u hh gwP ara uh a HFc. HFc u b a hu b u

    h u a a hr a r a rr h ar pa. HFc ar a

    h r uba ur h k Pr a a b p b har h ra

    ruar r h uur.

    Thee is aas a numbe o atenatie technooies that can be used. The easiest oute oud seem to be

    to choose the atenaties that equie no o minima sstem chanes but it is impotant to eaise that ne

    technooies ae continua bein intoduced and that the indust i eentua hae to keep its knoede

    abeast ith these ne technooies. An eauation o enionmenta impact incudin ene ecienc, cost,

    technica as e as saet isks is equied. The outcome i be dieent o dieent opeatin conditions and

    i depend on hee the equipment is instaed and ho it is used. geneaisations oten esut in poo decisions

    and that is h it is impotant to estabish indust standads to hae acceptabe seice aaiabiit and to make

    the equied tainin o the seice secto manaeabe.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    23/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    23

    schemes that reprocess signicant volumes. As the average

    recovery rate in Article 5 countries is currently low the relative

    impact o direct emissions is high. With a strong ocus on

    the introduction o good practice, the relative impact o

    GWP is expected to decrease although energy consumption

    also decreases with improved service practice. I a low-GWP

    rerigerant can be used saely at the same or lower energy

    consumption level with an acceptable investment, this will

    obviously be the solution with the lowest TEWI.

    Energy efciency is becoming more and more the ocus

    when selecting rerigerants but it is important to realise that

    efciency is only, to a small part, a result o the rerigerant

    selection. Typically the dierent rerigerants theoretical

    impact on the total perormance varies within a ew

    percent, whereas the dierence between various technical

    solutions o equipment design with a given rerigerant can

    be 20-30% or more. The solution that is 20% better in one

    application can also be signicantly worse at other operatingconditions. Simplied generalisations o perormance that is

    not specically reerring to a specic application should be

    viewed with scepticism. i u b ru,

    prbab .

    In the technical sections and case studies below, a number

    o technical and commercial aspects to be considered will

    be covered. In many countries there is a need to establish or

    increase local capacity to evaluate the suitability o dierent

    alternatives and to implement them in dierent systems.

    It is important to evaluate not only the lowest investment

    options but also the energy efciency and cost eectivenesso the dierent options.

    Thereore, it is easy to conclude that the ideal one-size-

    ts-all rerigerant does not exist and that some rerigerants

    will be more suitable in some applications than others. All

    rerigerants have their advocates on the market and there

    are interest groups promoting the dierent technologies.

    It is important that the rerigeration and air conditioning

    sector and equipment owners do a proper evaluation

    o the total environmental impact o using dierent

    alternatives. Any attempt to come up with one solution or

    all applications will with almost certainly not be the mostenvironmental nor the most cost-eective option.

    The opportunity to make improvements to the system in

    terms o efciency when they are replaced or retrotted

    tHeRe ARe FoUR mAin RoUtes to RePlAcing HcFcs in tHe RAc sectoR

    1 Ammonia NH3 (r717)

    2 Hdocabons Isobutane (r600a), popane (r290), popene (r1270),

    bends, etc.

    3 Cabon dioide CO2 (r744)

    4 Hdofuoocabons HFCs (i.e. r134a and bends such as r407C, r410A)

    should not be neglected. The pay o time or such

    improvements is oten short when done in connection with

    other work on the plant. Ensuring a proper commissioning

    and adjustment o controls can oten in itsel save a

    signicant amount o energy.

    Due to the phase-out o R-134a in the automotive air

    conditioning sector, a new low-GWP HFC alternative

    named HFO-1234y has been developed by DuPont and

    Honeywell. At this stage it is not clear i the automotiveindustry will go this way or move to CO2. As o March 2010

    several HFO (hydrouoroolene) components are also

    being considered/studied or RAC applications. There

    is no sufcient inormation available to date whether

    HFO1234y, by itsel or in mixtures with other rerigerants, is

    a good solution or the RAC sector or i and when it will be

    commercially available. I the automotive industry takes this

    route it will require large amount and production capacity:

    It will take time to establish this to satisy MAC demand

    increasing rom 2011 as the quantities required in this

    sector are signicant. Introducing additional products in

    the stationary sector will not be the highest priority in thatscenario. It can be expected that the development work in

    the RAC sector, i it takes place, will require several years o

    additional research and development. The interest on the

    market will be dependent on how cost eectively these

    substances are in design o highly efcient equipment.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    24/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    24

    ANy ATTEMPT TOCOME UP wITH ONESOlUTION FOr AllAPPlICATIONS wIll

    AlMOST CErTAINlyNOT BE THE MOSTENvIrONMENTAlly-FrIENDly NOrTHE MOST

    COST-EFFECTIvEOPTION

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    25/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    25

    AmmoniA is A well-PRoven rerigerant in largercommercial and industrial applications. Ammonia has

    technical properties that make it considered incompatible

    with copper which is a preerred material or tubing and

    motor winding or mass produced hermetic systems.

    The toxicity and risk to human saety i released, limit the

    applications where ammonia can be used saely and at an

    acceptable cost. The extremely strong and irritating odour

    emitted by ammonia when released may incite people

    to panic as they try to evacuate the area. On the positive

    side however, this odour also acts as a useul early warning

    signal in case o system leakage. The use o ammonia in its

    traditional sectors has increased on many markets due tothe desire to avoid the use o high GWP rerigerants such

    as HFCs. Ammonia is still used mainly in the traditional

    application o larger industrial rerigeration systems althoughit has also been introduced in certain new segments

    such as large central air conditioning systems and smaller

    commercial systems on some markets. One way o reducing

    the risk when using ammonia is to minimize the charge by

    building compact chillers that can be placed in machine

    rooms specially designed or the purpose o eliminating the

    risks. There are also systems designed to absorb any releases

    o ammonia in water sprays beore it can reach the area with

    public access.

    The introduction o soluble oils or ammonia resulted in the

    development o dry expansion systems with lower chargeand simplied oil return versus ooded systems with non-

    miscible oil.

    1.4.1 AmmoniA

    1.4.2 HydRocARBons

    sUmmARy AmmoniAAmmonia is a eestabished eieant equiin specia pesonne competencies and sstem desin. Thee ae

    a numbe o epeienced companies and technicians ith these competencies. An inceased use o ammonia i

    depend on moe technicians and eninees eceiin tainin in this secto.

    Thee ae enionmenta benets om the use o ammonia because it has eo ODP and neiibe gwP.

    Technica it is a ood eieant, but it has some saet dabacks and technica chaenes associated ith

    mateia compatibiit and hih tempeatues occuin duin compession.

    The inestment cost is tpica hihe than o conentiona sstems, at east in oe capacities. we desined

    sstems can hae e ood ene ecienc and ne desins ae etendin the appication ane ith oe

    chae and ne ois suitabe o nonfooded eapoatos. The fooded sstems tpica equie pocedues o oi

    etun and ae tpica used in ocations hee thee ae quaied pesonne on site.

    sUmmARy HydRocARBonsHdocabons ae ood eieants ith eo ODP and neiibe gwP. Thei fammabiit equies specic

    competencies in desin, manuactuin and seice. To ensue sae use, thee ae estictions on hee and ho

    the can be appied. Hdocabons as eieants ae adua bein coeed in Intenationa Standads detaiin

    the necessa equiements o sae use (i.e. in EN 378 and ISO5149).

    Isobutane (r600a) has become the standad eieant in ne domestic appiances in man makets. The sma

    amounts used in a domestic appiance ae not consideed to be a sinicant isk ate edesin o the eieatos

    F. 1.7 Ammonia instaationtpica o industia appications.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    26/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    26

    hee a sitches (e.. themostats and amp sitches) hae been emoed om the eieated compatment.

    A eak into the oom hee the unit is paced i dispese and not esut in daneous concentation.

    Popane (r290) and Popene (r1270) hae moe appopiate popeties to epace r22. Seea hdocabon

    mitues ee aso intoduced as epacements o CFCs and HCFCs. On seea makets hdocabons hae been

    used in smae commecia eieation equipment and aicooed chies.

    Sae use o hdocabons equies tainin o those inoed in the desin, instaation and seicin the equipment.

    Standads and euations adapted o use in rAC sstems ae impotant so as to aoid the eposue o technicians

    and uses to dane due to iesponsibe pactice.

    Toda thee ae intenationa poduct standads that coe sma hemetic sstems (hain a chae o

    appoimate ess than 150 ams) that ao them to be instaed in most paces poided that pope desin

    pecautions hae been taken. Fo ae sstems the poduct standads ee to eeant nationa and intenationa

    standads i.e. EN378 and ISO 5149 (gTzPokima, 2008).

    I the chae o hdocabons can be kept o esus the ai oume in the oom (tpica 8 ams/m3) the isk o

    ceatin fammabe mitues is eiminated.

    The compatibiit o ois in connection ith hdocabons is sometimes an undeestimated question since hih

    ees o miscibiit hae caused man sstem aiues hen hdocabons hae been intoduced ithout pope

    edesin.

    This epot i not discuss the etot o eistin HCFC sstems to hdocabons as the eauation o an od unit

    desined and ocated ithout consideation to the eieant fammabiit is in most cases compe and i need

    to be done in accodance ith intenationa as e as nationa eisation. It can be said that thee is obious much

    ess isk inoed in sstems ith a chae beo that hich can ceate an eposie enionment in the oom o i

    the hoe eieation sstem is paced outside i.e. ai cooed chies. The inomation on desin o hdocabon

    sstems pesented hee i be eeant in considein hen hdocabons ae used, but additiona equiements

    i oten app. Saet eated to opeation as e as seice must aas be caeu eauated beoe a fammabeeieant is appied. Thee ae seea makets hee etots ae caied out and the inomation is oten aaiabe

    on the intenet. See .Hdocabons21.com.

    inteRnAtionAl stAndARds have to some extent

    been adapted to accommodate saety requirements

    or hydrocarbons but uncertainty on regulations still

    remain in some applications. There is a signicant interest

    in hydrocarbons on the market since they are good

    rerigerants, and as a result the number o components

    and systems is gradually increasing. However due to saety

    considerations and the small market outside domesticappliances, many components are not approved by the

    manuacturers. There are concerns over liability and unclear

    regulations even i the components unction. Due to the

    potential damage a ailure can cause the requirements

    are higher, in many cases, or components or ammable

    rerigerants than or those that are non ammable. I there is

    a lack o approvals the challenges or the technicians involved

    increase as they cannot ully rely on manuacturers validation

    which species that the particular component ulls all

    relevant pressure and saety standards. For most applications

    the relevant components are available rom some source, but

    they can be more difcult to nd and the cost is sometimeshigher. For systems with rerigerant charges above 150 grams

    and/or a charge over approximately 8 grams/m3 air in the

    room (charge limitations can vary depending on country and

    application) the saety requirements increase and it oten

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    27/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    27

    becomes necessary to make a risk assessment to ensure

    that risks are acceptable. On most markets hydrocarbons

    are rarely introduced in existing equipment as electrical

    systems and controls are oten not suitable and need to be

    redesigned. There are systems that ater careul evaluation

    can be modied to be sae but the challenges are much

    bigger than in new systems designed or a ammable

    rerigerant. Extensive presentation o hydrocarbons as an

    option in RAC systems can be ound in (GTZ-Proklima, 2008).

    The hydrocarbons most commonly used in traditional HCFC

    applications are:

    Propane (R-290) having characteristics similar to those o

    R-22 has been introduced in a wide range o commercial

    and air conditioning applications. The cooling capacity is

    typically signicantly lower than R-22 and perormance

    (COP) in the range o -2 to +6% relative to R-22 [Bitzer,

    2008]. Propane has been introduced in a wide range

    o applications and when proper consideration o high

    solubility in oils has been taken good operating experiences

    are reported.

    Propylene (R-1270) has higher cooling capacity and lower

    boiling temperature than propane and is the preerred

    option by some manuacturers. The higher pressures

    and discharge temperatures need to be taken into

    consideration especially or use in hot climates.

    Hydrocarbons are oten claimed to be compatible with all

    commonly used oil (mineral, alkyl benzene and ester oils).

    This statement is very questionable as not all oils will give a

    reliable unction with hydrocarbons. Use o hydrocarbons

    with traditional oils without changing oil viscosity and/

    or making system design modications has in many

    cases resulted in high ailure rates caused by the extreme

    miscibility between oils and hydrocarbons resulting

    in increased wear in compressor. Besides redesign or

    relocation o electrical systems and controls, it is oten

    advisable to also increase the viscosity o the oil and

    ensure sufcient superheat through a suction gas heatexchanger [Bitzer, 2008].

    tecHnicAl inFoRmAtionFr a ua ara h a rrra

    har ra a faab :

    mma= 0.25 lFl A 2.2 [T. JABBOUr, D. ClODIC]

    whee lFl is the loe Fammabiit limit in k/m3

    and A is oom aea in m2

    .

    Fo popane (r290) lFl = 0.038 k/m3

    Fo Isobutane (r600a) lFl = 0.043 k/m3

    The saet imit o 0.25 is used to compensate o

    the dieences in densit esutin in an inceased

    concentation nea the foo.

    Fo eampe, in a oom that is 34 metes the

    maimum aoed chae o r290 is 250.8 ams, not

    takin into account the inceased saet measues

    accodin to standad IEC 60335240 [IEC, 2005].

    1.4.3 cARBon dioxide (co2)

    sUmmARy cARBon dioxideCabon dioide technoo is cuent the most innoatie aea in eieation. CO 2 is not a ne technoo, but

    it has been ide used in the rAC secto o a on time because thee hae been easie and oe cost competin

    technooies. Hoee, ith an inceased moement to educe the use o HFCs and the seach o nonfammabe,

    nontoic eieants, CO2 has become an inteestin atenatie ith eo ODP and insinicant gwP. The to

    main chaenes inoed ae the hih sstem pessue at noma opeatin tempeatues and the o eneecienc (COP) o a standad eieation cce.

    It is possibe to desin ne equipment to make it suitabe o hihe pessues and moe and moe manuactues

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    28/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    28

    ae oein components and sstems o CO2 makin it possibe to desin a ide ane o appications.

    CO2 is intoduced in dieent appications both as sine stae supecitica eieant, pat o a cascade ith a

    second eieant and as seconda fuid in indiect sstems ith a dieent eieant in the compession cce.

    The chaene and hat is oin to dene the utue maket shae o CO2 is deteminin at hat cost it i be

    possibe to achiee competitie ene ecienc in ed conditions.

    The specia chaacteistics o CO2 and the need to desin the sstems ith consideation to the oca conditions

    to achiee competitie COP i (een moe than o conentiona technooies) make it necessa to eauate

    soutions appication b appication. Discussion is onoin i supecitica CO2 sstem i be ene ecient in

    am cimates.

    Specia tainin is equied to desin, buid and seice sstems o CO 2 and hih pessues. This incudes not on

    deain ith the hih pessues but aso the technica kno ho to make the sstem ene ecient.

    cARBon dioxide has a negligible GWP but will operate

    under signicant higher pressure than the traditionalrerigerants and cannot be used in existing equipment. As

    CO2 has a low critical point the behaviour will be dierent

    to traditional rerigeration systems. Above 31C the system

    will work in supercritical (sometimes called trans-critical)

    conditions, i.e. traditional condensing will not take place.

    There are several applications where CO2 can be consideredas a commercially-available alternative although the price

    level is oten higher than that o conventional technologies.

    The ongoing discussion is in which applications the energy

    efciency will be comparable with the one achieved in other

    alternative technologies. In the commercial rerigeration

    sector, much o the development is ocused on this

    rerigerant due to the negligible direct GWP. The applications

    with the longest experience are where CO2 is used as

    secondary uid in indirect systems and at low temperature

    industrial/commercial rerigeration in cascade system with

    ammonia (or HFC) in the high stage. A signicant number

    o supercritical CO2 systems have been installed and severalreports on the coefcient o perormance (COP) o these

    systems have been published. The statements on efciency

    vary depending on the source, and urther development

    and more documentation rom commercial installations is

    needed beore actual COP, cost and reliability in dierent

    systems and conditions are established. It should be noted

    that the relative energy efciency versus other technologies

    will depend on the climate where the system operates

    (warm climate will have a more negative eect on COP in

    supercritical CO2 than in conventional HFC systems).

    In Japan, CO2 heat pumps with supercritical operationor domestic hot water have ound a large market (their

    development and introduction have been promoted

    with the help o subsidies rom government and utility

    companies). This technology has also been introduced in

    Refrigerant inside: CO2

    Gas condenser

    F. 1.8 Supecitica CO2 sstem ith as cooe opeatin atpessues 2 to 3 times that o conentiona sstems.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    29/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    29

    rerigerant charges and leak risk signicantly and is preerred

    in several applications on some markets. Indirect systems

    also give more exibility in the selection o rerigerants as

    the risks and costs o using ammable (HCs) and toxic (NH3)

    rerigerants decrease.

    CO2

    is also a leading candidate as an alternative to R-134a in

    automotive air conditioning as the latter will be phased out in

    new car models in the EU rom 2011.

    Europe where these heat pumps are used or combined hot

    water and space heating.

    CO2 is also used as a secondary uid in low temperature

    applications as it can reduce the energy consumptions or

    pumps and tube dimensions in indirect cooling systems.

    The use o indirect systems is increasing as it reduces the

    Sub critical CO2

    Refrigerant inside: NH3

    or HFC

    Air or liquidcondenser

    CO2

    Pump

    Standard chiller

    Refrigerant inside: NH3

    or HFC

    Air or liquidcondenser

    F. 1.9 CO2 in subcitica opeation in cascade ithhdocabon, ammonia, o HFC eieant.

    F. 1.10 CO2 as seconda fuid in an indiect sstem.

    1.4.4 HFc AlteRnAtives Used in new And RetRoFitted systems witH new oil

    sUmmARyHFcHFCs ae b a the most common epacement o HCFCs in ne equipment and a ide ane o such equipment

    has been aaiabe on the maket o the past 15 eas.

    The eatie hih gwP o HFCs hae inceased the pessue on ndin atenaties ith oe impact on cimate and

    the deeopment eots hae inceased as cimate chane has become the numbe one enionmenta chaene.

    The auments used in aou o HFCs ae that the can be used sae and cost eectie in a appications hee

    CFCs and HCFCs hae been used ith minima technica chanes. As the ocus on cimate chane inceased, this

    aso esuted in an inceased ocus on ene ecienc. In man appications the ene ecienc o todas HFCs

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    30/8230 UNITED NATIONS ENVIRONMENTAL PROGRAM

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    31/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    31

    tHe only mARket segments where ODS have been

    replaced widely by non-HFC alternatives are domestic

    appliances and some plug-in display cases that have

    changed rom R-12 to isobutane (R-600a). In markets whereammability and toxicity have been considered difcult

    and/or costly to handle saely the transition has been to

    HFCs. As new technologies are developed and mature and

    more technicians receive training and become amiliar with

    non-HFC alternatives, these not-in-kind alternatives can be

    expected to increase their market share. As the HFCs are not

    compatible with traditional rerigeration oils the introduction

    o HFC normally requires a change to ester-oils (e.g. PAG-oils

    are used with R-134a in the automotive sector). There is a

    special range o HFC rerigerants called drop-in or service-

    blends that are tailored to allow the use o HFCs with

    traditional mineral oils by adding a component to address oiltransport characteristics (see service blends below).

    In most R-22 applications the two dominating HFC

    alternatives or new installations are R-407C and R-410A.

    The ormer is closest to R-22 in terms o capacity and

    pressure. Provided the change to an ester oil has been made,

    R-407C gives a similar capacity and perormance as R-22 but

    presents a special characteristic. As it is a zeotropic blend i.e. it has a gliding temperature during condensation and

    evaporation (glide) - it is less suitable or some applications.

    R-410A was introduced later and it requires redesign to

    handle the higher pressure but has an advantage o higher

    capacity and insignicant glide. R-407C has lost a signicant

    part o its initial markets to R-410A, but is still the preerred

    solution in several segments such as small- and medium-

    sized chillers and water/brine heat-pumps. R-410A, on the

    other hand, has taken most o the market in smaller air

    conditioning systems o unitary and split type.

    In commercial applications that traditionally used R-12 andR-502, R-22 is normally replaced by R-404A/R-507.

    In some traditional R-22 segments such as larger chillers

    R-134a has taken a signicant market share.

    sstems is much hihe than that o the HCFCs sstems the ae epacin. In man sectos thee ae equiements

    on minimum eciencies epessed as Seasona Ene Eciencies, o eampe. In some makets, the oenment

    oes ta eemptions o subsidies to hih ene ecienc soutions.

    In most appications the ene consumption i be the majo contibuto to oba amin om a rAC sstem.

    TEwI (see Abbeiations and denitions) as e as the lie Cce Anasis (lCA) o cost and enionmenta impact ae

    impotant actos to conside hen compain dieent atenaties.

    The most common HFC atenaties in ne appications and etots ith chane o oi to a poo este oi ae:

    Spit and unita ai conditionin units r407C and r410A

    Heat pumps r134a, r407C and r410A

    Dispa cases and sma sstems r134a and r404A/r507

    Chies, ai conditionin r134a, r407C and r410A

    Chies, commecia r134a and r404A/r507

    Centa sstem commecia r404A/r507

    Industia r404A and r507

    Out o the HFC eieants isted aboe on r410A equies components desined o sinicant hihe pessue.

    Seice bends intended o use in eistin sstems ae isted in the net section.

    th ru pra a ua ru h a ah a a

    hh r .

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    32/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    32

    tHe FiRst so cAlled R-22 drop-in alternatives or serviceblends was the R-417A, but lately R-422A, R-422D, R-424A,

    R-427A, R-428A and R-434A have been launched to oer

    alternatives tailored to general or specic R-22 applications.

    Almost all service blends (except R-427A) have a similar

    sUmmARy HFc seRvice BlendsSeice bends ae deeoped to oe a dopin technoo that oes cost as compaed to chanin the oi,

    hich is equied, hen adoptin the same HFC atenaties used in ne sstems.

    retot is the tem oten used to descibe the pocedue in hich the eieant and the oi ae chaned (and, i nec

    essa, cetain pats o the equipment ae aso epaced). In this epot,etot ees on to this pocedue and not to

    the one usin seice bends. Most seice bends ae popieta poducts maketed as a ocost, eastouse soution,

    so sometimes the technicians usin them do not hae a u undestandin o thei chaacteistics and imitations.

    To oecome the need to chane to este ois hen ODS ae epaced b HFCs, a numbe o seice bends hae been

    deeoped to epace the HCFCs. One component (oten a hdocabon), hich chanes the chaacteistics o the oi

    eieant mitue in the sstem, is added. These atenaties ae sod ith the adantae that the oe a cost eectie

    option to epacin ODS. A chane in eieant i esut in a chane in the chaacteistics o the oi hich aect oi

    tanspot and ubicit. It is ecommended that beoe an decision to intoduce a seice bend is taken, an eauation be

    conducted to detemine hethe the sstem i be sinicant aected b the chane in oi tanspot and ubication.

    The st citeia hen eauatin options o epacin HCFCs is to dene the status o the eistin sstem. Aas

    check that the eistin sstem is in sucient ood shape to justi the equied inestment.

    Inestment, een i imited, in equipment that is about to ai is a aste o mone. The ene ecienc and histoica

    eakae ates ae impotant actos to conside beoe an decisions ae made. I the equipments condition is such

    that epacement ith a seice bend is deemed the best option, additiona measues to be taken in connection ith

    the chane shoud aso be eauated in ode to minimie eaks and etend the equipments ie time.

    The seice aaiabiit duin the emainin ie time o the equipment shoud be ensued to aoid that a utue

    ack o aaiabiit oces additiona inestments. The numbe o bends oeed on the maket makes the stoae o

    seice quantities a chaene o the seice poides uness some standadisation occus in the maket.

    Beo ae the most common consideed seice bends o epacin r22.

    r417A r22 repacements taetin sma diect epansion sstems

    r422A r502 and o tempeatue r22 epacement

    r422D r22 repacements in o eampe chie appications

    r424A r22 repacements taetin sma diect epansion sstems

    r427A r22 repacements

    r428A r502 and o tempeatue r22 epacement

    r434A r22 repacements in o eampe chie appications

    r438A r22 repacement taetin a ide ane o opeatin conditions

    1.4.5 HFc seRvice Blends Used in existing systems

    approach in composition where one or two componentsare added (oten hydrocarbon). This part o the blend

    composition is extremely soluble in the oil which results

    in the viscosity o the oil not increasing when the HCFC is

    replaced with a non-soluble HFC. This strategy has proved

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    33/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    33

    problems that should be avoided. Several actors should

    be taken into account when evaluating the service blend

    option and when deciding to what extent case studies can be

    considered relevant or the applications under consideration.

    tecHnicAl inFoRmAtionFar r b apa, coP a har praur h r b ar:

    The component (oten a hdocabon) absobed b the oi does not make the oi miscibe ith the eieant, but it adjusts

    the iscosit to be moe simia to the od oi/eieant mitue o hich the compesso as desined and to impoe oi

    tanspot, paticua in the eapoato and suction ine hee a thicke oi inceases the isk o poo oi etun. Since in

    most cases the component intoduced to decease the ois iscosit is a fammabe substance, thee ae imits on ho much

    o this component can be added beoe thee is a isk o eposion, especia i eakae outside the equipment occus.

    At the same time the atio beteen oi and eieant i aect ho diuted the oi is, e.. i the oi chae is eatie

    sma as compaed to the eieant chae, the oieieant mitue i hae oe iscosit than i the oi content

    is sinicant hihe eatie to the eieant chae.

    The oi that is cicuated noma has a oe densit than the eieant and i thee ae stabe iquid ees, e.. in the

    eceie, tube o she condense, the oi i tend to foat on top o the eieant iquid and can accumuate to an

    etent hee the compesso i eentua ai.

    In compe eieation sstems thee ae cases that hae been epoted hee the oi accumuated in the

    eapoato and suction ines.

    In sstems ith tubes ith ifes/ooes to enae tube suace and impoe heat tanse, thee hae been epots

    hee heat tanse as dastica aected due to bockin o the ooes ith oi.

    Theeoe, the caims that seice bends ae eas to use and do not equie the same caeu eauation as a etot to

    standad HFC eieants can oten be questioned.

    Some o the dieences in ecommendations beteen suppies o dieent seice bends can pobab be moe

    eated to poicies and isk assessment athe than technica dieences beteen the atenaties.

    Some compesso and/o eieant manuactues ecommend that akbenene ois be used ith HFC seice

    bends and/o that a pat o the od oi is epaced ith este ois. The impotance o cean and d sstems and the

    isks associated ith conetin od sstems o oten questionabe condition shoud not be undeestimated. The

    consequence o these aspects is not that seice bends cannot be used; athe thei suitabiit shoud be eauated

    esus the sstem in question to aoid isk o aiues. The eauation o the dieent commeciaaaiabe options

    is dicut to do as objectie inomation is ackin. A suppies o seice bends ae ocusin on success stoies and

    thee is a tendenc to t to minimie an concens.

    In opeations on mitues o od and ne ois, thee is the isk o a chemica beak don o the oi caused b

    contaminants in the od oi. Thee is aso a isk that ne oi i dissoe and tanspot deposits to the compesso.

    Suction tes duin the chane oe pocedue can be used to educe this pobem.

    to be unctional in many systems, but there also have been

    reports o problems in some applications. There is limited

    unbiased inormation readily available and it is obvious that

    success stories are more widespread than those describing

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    34/82

    section01 Ara HcFc in the reieation and Ai Conditionin Secto

    34

    wHen evAlUAting AlteRnAtive rerigerants or

    dierent applications, careul consideration should be

    paid to the oil properties and how they are aected by

    the dierent rerigerants. How a rerigerant behaves in a

    system is signicantly easier to predict than how the mixture

    o oil and rerigerant will behave. It is easy to dene the

    properties o a rerigerant or pure oil at dierent pressures

    and temperatures. It much more complex to predict and test

    lubrication properties in the compressor and oil transport

    in the system ater the rerigerant and oil has mixed. The

    selection o oil must take into account all aspects to ensure

    long term reliability o the system. Many systems have ailed

    because end users have not considered the interaction

    between the oil and the rerigerant.

    1.5 Oils in rerigeration and air conditioningsystems

    sUmmARy oils in RAc systemswith a e eceptions, rAC sstems contain an oi to sea and ubicate the compesso. A sma amount o oi i

    aas eae the compesso and i be tanspoted aound the sstem (een ith oi sepaatos, a sma amount i

    cicuate in the sstem).

    In most sstems, oi etun equies that the oi is miscibe ith the eieant. The miscibiit aso deceases the

    neatie impact o oi in the heat echanes.

    The ois used ith CFCs and HCFCs ae not miscibe ith HFCs, hich makes an oi chane equied to achiee the

    same chaacteistics.

    The Minea oi (MO), akbenene (AB) and sometimes Poaaoens (PAO) ois used ith CFC o HCFC

    eieants ae most common epaced ith Pooeste (POE) ois hen HFCs ae used. Aso Poakene cos

    (PAg) ois and Poinethes (PvE) ae used o HFCs. PAg is the oi used in automotie ai conditionin.

    Seice o dopin bends ae desined to achiee a behaiou simia to that o HFC/MO o HCFC/MO to aoid

    the cost o chanin the oi to a miscibe oi. It shoud be noted that thee i be sinicant dieences that i aect

    some sstems consideab.

    th r HFc ar hrp a rur ra a prpr ha a ra aur ra.

    lae cans o oi that cannot be emptied at one instaation shoud not be used uness oi is moed to a pessue

    esse, i.e. a to pot eieant cinde hee it can be kept unde oepessue ith nitoen.

  • 8/2/2019 Alternatives to HFCs in the Refrigeration and Air Conditioning Sector: Practical Guidelines and Case Studies for Equi

    35/82

    section01Ara HcFc in the reieation and Ai Conditionin Secto

    35

    tHe need to ensure lubrication and oil transport

    creates a challenge in RAC systems as the lubricating

    properties will vary greatly, depending on operating

    conditions. It is thereore not uncommon that compressor

    manuacturers will recommend dierent oils or dierent

    applications. Neglecting the importance o oil properties

    has resulted in a large number o ailures in systems that

    use alternatives to R-22 including HFCs, service blends and

    hydrocarbons. There have been serial problems in new HFCand new hydrocarbon systems, as well as in connection

    with dierent service blends. The oil behaviour in the

    rerigeration systems is oten signicantly more complex

    and challenging than the rerigerants behaviour.

    When a system is modied, it is important to consider how

    this will impact lubrication and oil transport. When there is

    inormation rom the compressor and/or oil manuacturer,

    this should be taken into account. System manuacturers

    should be consulted i they are aware o any problems with

    their particular system although some do not consider it

    to be in their own interest to extend the lie o old (oten

    inefcient) equipment or to assume responsibility or advice

    that will involve some risk o problems.

    Ester oils and HFCs act as a solvent in the system and

    there is a risk that debris and contaminants that have

    accumulated in the system over time are dissolved

    tecHnicAl inFoRmAtions prpr ar b:

    lubra prpr ae impotant to ceate a eiabe sstem ith a on ie. The ubication is ston aected

    b the eieant in the sstem hen thee is a miscibe oieieant mitue. The miscibiit is impotant due to

    the equiement to hae acceptabe oi tanspot thouhout the sstem. The amount o the eieant dissoed

    in the oi is aected b pessue and tempeatue, hich means that the ubication aies ith the opeatin

    conditions. Sometimes compesso manuactues equie dieent oi based on the opeatin conditions. The

    miscibiit o the eieant in oi is an impotant acto to poide the iht ubication popeties hen the

    eieant is dissoed in the oi at a pessues and tempeatues that can occu in the compessos opeatin

    eneope. Aso, the CFC o HCFC eieant b itse aects the ubication popeties as the choine om the CFC

    o HCFC acts as an antiea additie.

    cha ab in the sstem in the pesence o eieant and a mateias that coud be used oe the hoe

    opeatin eneope. This must aso take into account the pesence o moistue and contaminants that can occu

    in a eieation/ai conditionin sstem. This is a ke concen as contaminants dastica decease stabiit. Poo

    pactices appied duin manuactuin, instaation and seicin esuts in a deceased ie epectanc o the

    sstem. Uness pactices ae impoed, the phase out o ODS i esut in an inceased aiue ate as the ne ois

    ae moe sensitie to poo handin. On the othe hand, ith the intoduction o ood seicin pactices, the ie

    o rAC sstems can oten be man times hat as epected ith CFC o HCFCs and od seicin methods. mb o rapr. As thee i aas be a sma amount o oi that eaes the compesso ith the

    compessed eieant it is essentia to ensue that it comes back. I the oi is not tanspoted aound the sstem, the

    compesso i eentua un out o oi and ai. Oi in the heat echanes i aso hae a neatie impact on the

    heat tanse and decease the ene ecienc. Noma the oi tanspot pobem i be citica at o eapoation

    tempeatues and o capacit and coud occu ate a on time hen the sstem opeates unde specic conditions.

    ear pab ith ois is an impotant issue, in paticua in od sstems hee Oins and othe seas

    can be aected b a chane o oi. Thee ae some common used mateias ike viton (a tade name o specia

    fuoopome oeed b DuPont) that ae not ecommended toethe ith POE and PAg ois. I these ois ae

    i