Altistart 22 soft start/soft stop unit
Reduce your operating costs
Simplify wiring
Protect your electrical installation Save space with a fully equipped product
Contents
Selection guide p. 6
Presentation p. 8
References p. 12Motor starters p. 16
Safe
InnovativeEconomical
8/10/2019 Alti Start 22
2/16
Reduce your costs with anintegrated bypass function*
* shuntage
Installation and operation couldnt be simpler
Save time on wiring (6 terminals instead of 12)
Optimise the size of your enclosures (Altistart 22 isvery compact)
Keep temperature rises to a minimum(low heat dissipation)
Reduce the number of components you need
to manage (multifunction product)3 controlled phases
50% reduction inwiring time
8/10/2019 Alti Start 22
3/16
Bypass the stresses and let yourapplications take the strain
Protect your installations By minimising jolts and shocks, Altistart 22 reduces
mechanical stresses on your machines and increasestheir service life.
Altistart 22 prevents installation failure by detecting andsignalling faults such as a blocked motor, underload orincorrect earthing of one of the 3 motor phases.
Cards are coated as standard to provide enhancedresistance to harsh environments.
Play it safe with a completeproduct Altistart 22, with its three controlled phases, incorporates
all the protection functions required to monitor the motor,the electrical installation and the starter itself.
Simplify setup and operation with: - 4 light emitting diodes (LEDs) - 4 navigation keys - 4-digit display - SoMove setup software (common to the
Altivar, Lexium and TeSys ranges)
8/10/2019 Alti Start 22
4/16
00
66
Applications Starting simple machines Controlled starting and deceleration ofsimple machines
Power range for 50...60 Hz (kW) line supply(connection to the motors power supply line)
0.37...11 0.75...15
Single-phase 110...230 V (kW) 0.37...2.2 Three-phase 200...240 V (kW) 0.75...7.5Three-phase 200...480 V (kW) 0.3711 Three-phase 208...600 V (kW) Three-phase 208...690 V (kW) Three-phase 230...415 V (kW) Three-phase 230...440 V (kW) Three-phase 380...415 V (kW) 1.515
Drive Number of controlled phases 1 2Type of control
Operating cycle
FunctionsBypass IntegratedNumberof I/O
Analogue inputs Logic inputs
Analogue outputs Logic outputs Relay outputs
Communication Integrated
Available as an option
Standards and certifcations IEC/EN 6 0947-4-2e , UL, CSA, C-Tick and CCC
References ATS 01N1 pppp ATS 01N2 pppp
Page Please refer to the Soft starters and variable speed drives catalogue.
Selection guide Soft startersfor asynchronous motors
More technical information on www.schneider-electric.com
8/10/2019 Alti Start 22
5/16
2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
77
Controlled starting and deceleration of simple and complex machines
4400 3900
4400
3900 3630 4355
3 3Con gurable voltage ramp TCS (Torque Control System)
Standard Standard and severe
Integrated Available as an option1 PTC probe 1 PTC probe3 4
1 22 ("N/C" / "N/O") 3
Modbus Modbus
Fipio, PROFIBUS DP, DeviceNet, Modbus TCP
IEC/EN 60947-4-2, EMC class Ae , UL, CSA, C-Tick, GOST, CCC
IEC/EN 60947-4-2, EMC classes A and Be , UL, CSA, DNV, C-Tick, GOST, CCC, NOM, SEPRO and TCF
ATS 22 pppp ATS 48 ppp Q ATS 48 ppp Y
12 Please refer to the Soft starters and variable speed drivescatalogue.
More technical information on www.schneider-electric.com
8/10/2019 Alti Start 22
6/16
0
88
Presentation Altistart 22soft start - soft stop units
PresentationThe Altistart 22 soft start - soft stop unit supports the controlled starting and
stopping, via voltage and torque, of three-phase squirrel cage asynchronous motorsfor power ratings between 4 and 400 kW.
It comes ready to use for standard applications with class 10 motor protection.
The Altistart 22 soft start - soft stop unit has been designed to satisfy theperformance requirements of applications where ruggedness, the safety ofpersonnel and equipment, and easy commissioning are at a premium.
The bypass function (based on a bypass contactor) has been made easier to use byintegrating it into the starter. This approach suits applications where it may benecessary to bypass the starter at the end of the starting process in order, forexample, to limit the starter's heat dissipation.
The Altistart 22 soft start - soft stop unit contains an integrated display terminalwhich allows the user to change both the programming and the adjustment ormonitoring parameters in order to adapt and customize the application in line wi thcustomer needs.
The unit also features thermal protection for motors as well as a monitoring facilityfor machines and, thanks to the SoMove setup software, enables the installation tobe commissioned immediately.
ApplicationsThe integrated functions of the Altistart 22 soft start - soft stop unit are compatiblewith the more common types of application found in the construction, infrastructureor industrial sectors:
Centrifugal pumps, piston pumpsFansScrew compressors, etc.Material handling (conveyors, etc.)Specialist machines (agitators, mixers, centrifugal machines)
The Altistart 22 soft start - soft stop unit represents a truly cost-effective solution, as itsupports:
A reduction in installation costs by optimizing product sizes, integrating the bypassfunction and reducing wiring timeb A reduction in the stress associated with electrical distribution by reducing thecurrent peaks and line voltage drops caused by motors starting up
A reduction in running costs for machines by reducing mechanical stress
Controlling the three phases of the motor windings ensures that performanceremains satisfactory, whatever the situation (with or without a load, all voltage andpower ranges, etc.).
bbbb
b
b
b
Conformity to standardsType Performance
Conducted andradiated emissions
Conforming toIEC 60947-4-2
Class A
Vibration resistance Conforming toIEC 60068-2-6
1.5 mm from 2 to 13 Hz,1 gn from 13 to 200 Hz
Shock resistance Conforming toIEC 60068-2-27
15 gn for 11 ms
Maximum ambientpollution
Conforming toIEC 60664-1
Step 2
Relative humidity Conforming toIEC 60068-2-3
95% non-condensing, no dripping water
Degree of protection For ATS 22D17C11 IP 20(IP 00 if no connections)
For ATS 22C14C59 IP 00
The Altistart 22 soft start - soft stop unit conforms to the RoHS Directive.
References:page 12
Combinations:page 16
The Altistart 22 soft start - soft stop unit offer
8/10/2019 Alti Start 22
7/16
2
1
3
4
5
6
7
8
9
10
99
FunctionsThe main functions integrated in the drive are as follows:
Adjustment functions Adjustment of the Altistart 22 soft start - soft stop unit's current in line with the
motor's nominal currentLimiting currentSelection of the type of stop (freewheel or deceleration)
b
bb
Drive performance functionsManagement of the three supply phasesOption of connecting the starter in the motor delta connection in series with each
winding. This supports the use of a soft start - soft stop unit with a lower rating (onlyapplies to the ATS 22 ppp Q range)
Management of the ramp and torque supplied to the motor throughout theacceleration and deceleration period (signi cantly less jerk)
Variety of control pro les to suit different applications
Integrated and automated management of the bypass function at the end of thestarting process (based on a bypass contactor), whilst preserving electronicprotection features
bb
b
b
b
Protection functions for the motor and machineIntegration of con gurable motor thermal protectionThermal protection for the Altistart 22 soft start - soft stop unitIntegrated processing of the PTC thermal probe with electrical isolation (optimum
management of motor protection)Monitoring of the duration and number of starts (better installation safety)Management of stopping time before restart
Automatic restartProtection against underloads and overcurrents in transient or steady state
Automatic adjustment to the line frequencyDetection of phase sequence
Detection of phase lossDetection of imbalances between phases and of leakage currents (for the ATS 22 ppp S6 and S6U ranges)
bbb
bbbbbb
bb
Functions to ease integration into control systems3 programmable logic inputs2 programmable N/C / N/O relay outputsPluggable connectors for I/OSecond set of parameters for motor operationModbus serial link via RJ45 connector Display of soft start - soft stop unit and machine statesDisplay of I/O currents and statesError log, diagnostics for soft start - soft stop unitReturn to factory settings4 LEDs on the front face (Ready, Communication, Run and Trip)
bbbbbbbbbb
Presentation (continued) Altistart 22soft start - soft stop units
References:page 12
Combinations:page 16
8/10/2019 Alti Start 22
8/16
0
1010
The offer The Altistart 22 soft start - soft stop unit offer comprises 2 voltage ranges for motorpower ratings from 4 to 400 kW:b Three-phase power supply voltage from 230 V to 440 V, 50/60 Hz (ATS 22 ppp Q)b Three-phase power supply voltage from 208 V to 600 V, 50/60 Hz (ATS 22 ppp S6and ATS 22 ppp S6U)
Options
The Altistart 22 soft start - soft stop unit range also offers a number of options: A remote terminal unit can be installed on the front face of a oor-standing
enclosure with IP 54/NEMA 12 or IP 65 protection (depending on the model).It offers the same functions as an integrated display terminal.
Additional fans to support a greater number of startsSoMove lite setup softwareProtection shrouds for terminals to ensure compliance with IP 20 degree of
protection
b
bbb
Selection criteriaThe Altistart 22 soft start - soft stop unit has been designed for standard controlsystem applications.
In addition to the chosen application, the choice of starter will depend on thefollowing main criteria:
The power and nominal current on the motor rating plateThe load factor for the application
The starting capacity also needs to be considered when selecting an Altistart 22 softstart - soft stop unit:
bb
Starting capacity
The standard starting capacity for a class 10 motor is :3.5 In for 40 seconds from cold with S1 motor duty3.5 In for 20 seconds wi th S4 motor duty, based on a load factor of 95%
Note:S1 motor duty is based on a start followed by operation at constant load, making it possible toachieve thermal equilibrium.S4 motor duty is based on a cycle consisting of a start, operation at constant load and an idle
period.
bb
Number of starts per hour Assuming the starting capacity remains the same, the number of starts per hour canbe increased by adding a fan.The ATS 22D17QC17Q, ATS 22D17S6C17S6 and ATS 22D17S6UC17S6Usoft start - soft stop units can be tted with an additional fan. Page 15 has details ofthis option.
Possible number of starts per hour based on a capacity of 3.5 In for 20 seconds (S4motor duty) after adding a fan:
Soft start - soft stop units Number of starts per hour Without fan With additional fan
ATS 22D17 p D47 p 6 10
ATS 22D62 p D88 p 6 10
ATS 22C11 p C17 p 4 10
Note: The ATS 22C21QC59Q, ATS 22C21S6C59S6 and ATS 22C21S6UC59S6U soft start -soft stop units come with a fan as standard.The standard number of starts per hour for S4 motor duty is 4. Anything more would require thenext lowest rating.
Presentation (continued) Altistart 22soft start - soft stop units
References:page 12
Combinations:page 16
Commissioning the ATS 22 soft start - soft stop unit withSoMove lite setup software
8/10/2019 Alti Start 22
9/16
2
1
3
4
5
6
7
8
9
10
1111
Presentation (continued) Altistart 22soft start - soft stop units
Standard application areasExamples of functions performed by the Altistart 22 soft start - soft stop unit
depending on the application chosen Type of machine Functions performed by the Altistart 22
Centrifugal pump Controlled slowing-down and stopping (fewer hammer blows)Protection against underload orreversal of phase rotation direction
Piston pump Control of pump priming and the pump's direction of rotation
Fan Detection of overloads and underloads (motor/fan transmissionbroken)Braking torque on stopping
Turbine Thermal monitoring of motor via electrically isolated PTC probe
Refrigeration compressor Control of starting characteristics
Management of automatic restart
Screw compressor Protection against reversal of phase rotation directionContact for automatic emptying on stopping
Centrifugal compressor Protection against reversal of phase rotation directionContact for automatic emptying on stopping
Conveyor Monitoring of overloads for incident detection orunderloads for break detection
Conveyor belt Second set of motor parameters depending on the loadtransported
Lifting screw Monitoring of overloads for hard spot detection orunderloads for break detection
Agitator Displaying the current indicates the density of the material.
Mixer Displaying the current indicates the density of the material.Boost on start-up
Refner Torque control on starting and stopping
Dedicated applicationsThe ATS 22 soft start - soft stop unit can be used for applications outside thestandard characteristics, but this could involve derating to at least the next lowestlevel.Examples of applications outside the standard characteristics:
Greater number of startsMotor thermal protection higher than class 10Excess current required at time of startCertain ambient temperatures:
For ambient temperatures between +40C and +60C, derate the nominal current ofthe Altistart by 2.2% for each additional degree.
Certain altitudes:For altitudes between 1000 and 2000 metres, derate the nominal current of the
Altistart by 2% for each additional 100 metres.Etc.
bbbb
b
b
References:page 12
Combinations:page 16
Example of pumping application usingthe Altistart 22 soft start - soft stop unit
8/10/2019 Alti Start 22
10/161212
References Altistart 22soft start - soft stop unitsThree-phase power supply voltage 230440 V
Presentation:page 8
Combinations:page 16
Connection to the motor's power supply lineMotor power given in kW in accordance with standard IEC/EN 60947-4-2. 220 V control power supply
Motor 230440 V - 50/60 Hz soft start - soft stop unitPower indicatedon rating plate
Nominalcurrent(In)(1)
Factorysetting forcurrent(IcL)(1) (2)
Dissipatedpower atnominalcurrent(4)
Dimensions(W x D x H)
Reference Weight
230 V
400 V
440 VkW kW kW A A W mm kg
4 7.5 7.5 14.8 17 39 130 x 169 x 265 ATS 22D17Q 7.0007.5 15 15 28.5 32 44 130 x 169 x 265 ATS 22D32Q 7.00011 22 22 42 47 48 130 x 169 x 265 ATS 22D47Q 7.00015 30 30 57 62 59 145 x 207 x 295 ATS 22D62Q 12.00018.5 37 37 69 75 63 145 x 207 x 295 ATS 22D75Q 12.00022 45 45 81 88 66 145 x 207 x 295 ATS 22D88Q 12.00030 55 55 100 110 73 150 x 229 x 356 ATS 22C11Q 18.000
37 75 75 131 140 82 150 x 229 x 356 ATS 22C14Q 18.00045 90 90 162 170 91 150 x 229 x 356 ATS 22C17Q 18.00055 110 110 195 210 117 206 x 299 x 425 ATS 22C21Q 33.00075 132 132 233 250 129 206 x 299 x 425 ATS 22C25Q 33.00090 160 160 285 320 150 206 x 299 x 425 ATS 22C32Q 33.000110 220 220 388 410 177 206 x 299 x 425 ATS 22C41Q 33.000132 250 250 437 480 218 304 x 340 x 455 ATS 22C48Q 50.000160 315 355 560 590 251 304 x 340 x 455 ATS 22C59Q 50.000
Connection to the motor's delta connectionMotor power given in kW in accordance with the standard IEC/EN 60947-4-2. 220 V control power supplyMotor 230440 V - 50/60 Hz soft start - soft stop unitPower indicated onrating plate
Nominalcurrent(In)
(1)
Factorysetting forcurrent
(IcL)(1) (3)
Dissipatedpower atnominal
current(4)
Dimensions(W x D x H)
Reference Weight
230 V
400 V
440 VkW kW kW A A W mm kg
5.5 11 15 25 17 39 130 x 169 x 265 ATS 22D17Q 7.00011 22 22 48 32 44 130 x 169 x 265 ATS 22D32Q 7.00018.5 45 45 70 47 48 130 x 169 x 265 ATS 22D47Q 7.00022 55 55 93 62 59 145 x 207 x 295 ATS 22D62Q 12.00030 55 75 112 75 63 145 x 207 x 295 ATS 22D75Q 12.00037 75 75 132 88 66 145 x 207 x 295 ATS 22D88Q 12.00045 90 90 165 110 73 150 x 229 x 356 ATS 22C11Q 18.00055 110 110 210 140 82 150 x 229 x 356 ATS 22C14Q 18.00075 132 132 255 170 91 150 x 229 x 356 ATS 22C17Q 18.00090 160 160 315 210 117 206 x 299 x 425 ATS 22C21Q 33.000110 220 220 375 250 129 206 x 299 x 425 ATS 22C25Q 33.000
132 250 250 480 320 150 206 x 299 x 425 ATS 22C32Q 33.000160 315 355 615 410 177 206 x 299 x 425 ATS 22C41Q 33.000220 355 400 720 480 218 304 x 340 x 455 ATS 22C48Q 50.000250 400 500 885 590 251 304 x 340 x 455 ATS 22C59Q 50.000
(1) In refers to the maximum continuous current for class 10. IcL refers to the starter rating.(2) The factory setting for the current equates to the nominal current of a standard 4-pole, 400 V, class 10 motor (standard
application). It should be adjusted in line with the current indicated on the motor rating plate.(3) The factory setting for the current should be adjusted in line with the current indicated on the motor rating plate.(4) Includes the power dissipated by the fan
ATS 22D17Q
ATS 22C11Q
ATS 22D62Q
8/10/2019 Alti Start 22
11/161313
References (continued) Altistart 22soft start - soft stop unitsThree-phase power supply voltage 208600 V
Connection to the motor's power supply lineMotor power given in kW in accordance with standard IEC/EN 60947-4-2. 220 V control power supply
Motor 230600 V - 50/60 Hz soft start - soft stop unitPowerindicated on rating plate
Nominalcurrent(In)(1)
Factorysetting forcurrent(IcL)(1) (2)
Dissipatedpower atnominalcurrent(3)
Dimensions(W x D x H)
Reference Weight
230 V
400 V
440 V
500 V
kW kW kW kW A A W mm kg4 7.5 7.5 9 14 17 39 130 x 169 x 265 ATS 22D17S6 7.0007.5 15 15 18.5 27 32 44 130 x 169 x 265 ATS 22D32S6 7.00011 22 22 30 40 47 48 130 x 169 x 265 ATS 22D47S6 7.00015 30 30 37 52 62 59 145 x 207 x 295 ATS 22D62S6 12.00018.5 37 37 45 65 75 63 145 x 207 x 295 ATS 22D75S6 12.00022 45 45 55 77 88 66 145 x 207 x 295 ATS 22D88S6 12.00030 55 55 75 96 110 73 150 x 229 x 356 ATS 22C11S6 18.000
37 75 75 90 124 140 82 150 x 229 x 356 ATS 22C14S6 18.00045 90 90 110 156 170 91 150 x 229 x 356 ATS 22C17S6 18.00055 110 110 132 180 210 117 206 x 299 x 425 ATS 22C21S6 33.00075 132 132 160 240 250 129 206 x 299 x 425 ATS 22C25S6 33.00090 160 160 220 302 320 150 206 x 299 x 425 ATS 22C32S6 33.000110 220 220 250 361 410 177 206 x 299 x 425 ATS 22C41S6 33.000132 250 250 315 414 480 218 304 x 340 x 455 ATS 22C48S6 50.000160 315 355 400 477 590 251 304 x 340 x 455 ATS 22C59S6 50.000
Motor power given in HP . 110 V control power supplyMotor 208600 V - 50/60 Hz soft start - soft stop unitPower indicated on rating plate
Nominalcurrent(In)(1)
Factorysetting forcurrent(IcL)
(1) (2)
Dissipatedpower atnominalcurrent
(3)
Dimensions(W x D x H)
Reference Weight
208 V
230 V
460 V
575 V
HP HP HP HP A A W mm kg3 5 10 15 14 17 39 130 x 169 x 265 ATS 22D17S6U 7.000
7.5 10 20 25 27 32 44 130 x 169 x 265 ATS 22D32S6U 7.000
15 30 40 40 47 48 130 x 169 x 265 ATS 22D47S6U 7.000
15 20 40 50 52 62 59 145 x 207 x 295 ATS 22D62S6U 12.000
20 25 50 60 65 75 63 145 x 207 x 295 ATS 22D75S6U 12.000
25 30 60 75 77 88 66 145 x 207 x 295 ATS 22D88S6U 12.000
30 40 75 100 96 110 73 150 x 229 x 356 ATS 22C11S6U 18.000
40 50 100 125 124 140 82 150 x 229 x 356 ATS 22C14S6U 18.000
50 60 125 150 156 170 91 150 x 229 x 356 ATS 22C17S6U 18.000
60 75 150 200 180 210 117 206 x 299 x 425 ATS 22C21S6U 33.000
75 100 200 250 240 250 129 206 x 299 x 425 ATS 22C25S6U 33.000
100 125 250 300 302 320 150 206 x 299 x 425 ATS 22C32S6U 33.000
125 150 300 350 361 410 177 206 x 299 x 425 ATS 22C41S6U 33.000
150 350 400 414 480 218 304 x 340 x 455 ATS 22C48S6U 50.000
200 400 500 477 590 251 304 x 340 x 455 ATS 22C59S6U 50.000
(1) In refers to the maximum continuous current for class 10. IcL refers to the starter rating.(2) The factory setting for the current should be adjusted in line with the current indicated on the motor rating plate.(3) Includes the power dissipated by the fan
Presentation:page 8
Combinations:page 16
ATS 22C48S6U
ATS 22C21S6
8/10/2019 Alti Start 22
12/161414
References (continued) Altistart 22soft start - soft stop unitsOption s: Dialogue and con guration tools,Modbus serial link
SoMove setup softwarePresentation
This software enables the user to con gure, set, debug and organize maintenance tasks for the Altistart 22 softstart - soft stop unit. It can also be used to customize the integrated display terminal menus.It can be downloaded from our website, www.schneider-electric.com.
ReferencesDescription For soft start -
soft stop unitsReference Weight
kg
SoMove lite setup software ATS 22
USB/RJ45 cordsetequipped with a USB connector andan RJ45 connector.For connecting a PC to the Altistart 22 soft start -soft stop unit.Length: 2.5 m
ATS 22 TCSM CNAM 3M002P 0.115
Remote display terminalPresentation
This terminal enables the human machine interface of the Altistart 22 soft start - soft stop unit to be positionedremotely on the door of a oor-standing enclosure. It has IP 54/NEMA12 or IP 65 degree of protection dependingon the model.It is used to:
Set and con gure the soft start - soft stop unit remotelyDisplay the status and faults of the soft start - soft stop unit remotely
Its maximum operating temperature is 50C. Please refer to our website at "www.schneider-electric.com" if thetemperature exceeds this.
bb
Description4-digit displaySelection/validation key ENT : opens a menu or validates the value chosenNavigation keys ,Selection key ESC : used to exit a menu
1234
ReferencesDescription Degree of
protectionLength Dimensions
W x D x HReference Weight
m mm kgRemote display terminals
A remote-mounting cordsetis also required -VW3 A1 104 R pp
IP 54/NEMA 12 50 x 15 x 70 VW3 G22 101 0.250IP 65 66 x 19 x 106 VW3 G22 102 0.275
Remote-mounting cordsetsequipped with 2 RJ45connectors
1 VW3 A1 104 R10 0.050 3 VW3 A1 104 R30 0.150
Modbus serial linkConnection via splitter box and RJ45 connectorsDescription Number Length
mUnitreference
Weightkg
Modbus splitter box with 10 RJ45 connectors
1 LU9 GC3 0.500
Cordsets for Modbus serial linkwith 2 RJ45 connectors
2 0.3 VW3 A8 306 R03 0.0251 VW3 A8 306 R10 0.0603 VW3 A8 306 R30 0.130
Modbus T-junction boxes (with integrated cable)
3 0.3 VW3 A8 306 TF03 0.1901 VW3 A8 306 TF10 0.210
Line terminators(2) (3)
R = 120 WC = 1 nf
4 VW3 A8 306 RC 0.010
R = 120 W 4 VW3 A8 306 R 0.010
(1) Cable depends on the type of controller or PLC (2) Sold in lots of 2 (3) Depends on the bus architecture
SoMove setup software
Presentation:page 8
Combinations:page 16
VW3 G22 101
4
1
2
3
4 2
2
21 3
ATS 22
4
Programmablecontroller
M o
d b u s s e r i a
l l i n k ( 1 )
Example of a connectionusing a Modbus serial link via
a splitter box with RJ45connectors
8/10/2019 Alti Start 22
13/161515
References (continued) Altistart 22soft start - soft stop unitsOptions: Fans, accessories and documentation
FansPresentation
The ATS 22C21QC59Q, ATS 22C21S6C59S6 and ATS 22C21S6UC59S6U soft start - soft stop unitscome with an integrated fan.The ATS 22D17QC17Q, ATS 22D17S6C17QS6 and ATS 22D17S6UC17S6U soft start - soft stop unitsare ventilated by means of natural convection.For more demanding applications, such as those with a greater number of starts, the Altistart 22 range offers fansas an option. These are driven by the soft start - soft stop unit and attached to the back of the device.The fan's noise level is less than 60 dBA.
ReferencesDescription Power supply
voltage forcontrol
For soft start -soft stop units
DimensionsW x D x H
Reference Weight
V mm kgFans 220 ATS 22D17QD47Q,
ATS 22D17S6D47S6130 x 40 x 265 VW3 G22 400 1.200
ATS 22D62QD88Q, ATS 22D62S6D88S6
145 x 40 x 295 VW3 G22 401 1.400
ATS 22C11QC17Q, ATS 22C11S6C17S6
150 x 40 x 350 VW3 G22 402 1.600
110 ATS 22D17S6UD47S6U 130 x 40 x 265 VW3 G22 U400 1.200
ATS 22D62S6UD88S6U 145 x 40 x 295 VW3 G22 U401 1.400
ATS 22C11S6UC17S6U 150 x 40 x 350 VW3 G22 U402 1.600
Protection shrouds for power terminals (to be used with eyelet connections)The ATS 22C11QC59Q, ATS 22C11S6C59S6 and ATS 22C11S6UC59S6U soft start - soft stop units have6 unprotected power terminals. These terminals can be tted with protection shrouds.
Description For soft start -soft stop units
Reference Weightkg
Set of 6 power terminal protectionshrouds
ATS 22C11QC17Q, ATS 22C11S6C17S6, ATS 22C11S6UC17S6U
LA9 F702 0.250
ATS 22C21QC59Q, ATS 22C21S6C59S6, ATS 22C21S6UC59S6U
LA9 F703 0.250
DocumentationDescription Reference Weight
kgDescription of the Motion & Drives Offer DVD ROM (1)It consists of:
Technical documentation (programming manuals,installation manuals, quick reference guides)
SoMove lite setup softwareBrochures, catalogues.
The documentation relating to the ATS 22 offer is also available onour website, www.schneider-electric.com.
b
bb
VW3 A8 200 0.100
(1) Updated version including the Altistart 22 range available 1st
quarter 2010.
Presentation:page 8
Combinations:page 16
VW3 G22 40 p
LA9 F70 p
8/10/2019 Alti Start 22
14/16
0
1616
Compatible components in accordance with standard IEC/EN 60947-4-2Use the contactor and starter with either a circuit breaker or a fuse switch disconnector.
Three-phase,4-pole motor50/60 Hz
Class 10starter (1) Circuit breaker Contactor (3) Fuse switchdisconnector(for front andside control)
aM fuse
Reference
Rating
Unitreference(4)
Size
Rating400 V 440 V
kW kW A A mm AM1 M1 A1 Q1 KM1 F17.5 7.5 14.8 ATS 22D17 p GV3 L20 LC1 D18 pp GS1 DD3 DF2 CA16 10 x 38 16
NS80H6-MA 2515 15 28.5 ATS 22D32 p GV3 L32 LC1 D32 pp GS1 DD3 DF2 CA32 10 x 38 32
NS80H6-MA 5022 22 42 ATS 22D47 p GV3 L50 LC1 D50A pp GS2 F3 DF2 EA50 14 x 51 50
NS80H6-MA 5030 30 57 ATS 22D62 p GV3 L65 LC1 D65A pp GS2 J3 DF2 FA63 22 x 58 63
NS80H6-MA 8037 37 69 ATS 22D75 p NS80H6-MA 80 LC1 D80 pp GS2 J3 DF2 FA80 22 x 58 80
45 45 81 ATS 22D88 p NSX100 p MA(2)
100 LC1 D115 pp GS2 J3 DF2 FA100 22 x 58 100
55 55 100 ATS 22C11 p NSX160 p MA(2)
150 LC1 D115 pp GS2 K3 DF2 FA125 22 x 58 125
75 75 131 ATS 22C14 p NSX160 p MA(2)
150 LC1 D150 pp GS2 L3 DF2 GA1161 0 160
90 90 162 ATS 22C17 p NSX250 p MA(2)
220 LC1 F185 pp GS2 N3 DF2 HA1201 1 200
110 110 195 ATS 22C21 p NSX250 p MA(2)
220 LC1 F225 pp GS2 N3 DF2 HA1251 1 250
132 132 233 ATS 22C25 p NSX400 pMicrologic1.3-M (2)
320 LC1 F265 pp GS2 N3 DF2 HA1251 1 250
160 160 285 ATS 22C32p
NSX400 p
Micrologic1.3-M (2)
320 LC1 F330pp
GS2 QQ3 DF2 JA1311 2 315
220 220 388 ATS 22C41 p NSX630 pMicrologic1.3-M (2)
500 LC1 F400 pp GS2 S3 DF2 KA1401 3 400
250 250 437 ATS 22C48 p NSX630 pMicrologic1.3-M (2)
500 LC1 F500 pp GS2 S3 DF2 KA1501 3 500
315 355 560 ATS 22C59 p NS630b p Micrologic5.0 (2)
500 LC1 F630 pp GS2 S3 DF2 KA1631 3 630
(1) Replace p with Q or S6 depending on the starter's voltage range.To nd more information on combinations for motor power supply voltages of 230 V (ATS 22 ppp Q starters) or 500 V(ATS 22 ppp S6 starters), please visit our website at www.schneider-electric.com.(2) Replace p with F, N, H, S or L depending on the breaking capacity; see table below.(3) Replace pp with the control circuit voltage reference: please consult our Motor starter solutions. Control and protectioncomponents catalogue.(4) DF2 CA, EA, FA: sold in lots of 10.DF2 GA, HA, JA, KA: sold in lots of 3.
Combinations Altistart 22soft start - soft stop unitsMotor starters:400440 V three-phase power supply voltageType 1 coordination
Presentation:page 8
References:page 12
Motor starter with protectionby circuit breaker or switchdisconnector
M1: three-phaseasynchronousmotor
KM1:TeSys LC1 p
A1: ATS 22 p
Q1: GV p /NS ppp
Q1: GS2 ppp
2 4
1
6
5 3
W / T 3
U / T 1
V / T 2
R / L 1
S / L 2
T / L 3
W 1
V 1
3
U 1
M1
2 4
1 3
6
5 1 3 5
2 4 6
F1 :DF2 p A
Maximum prospective short-circuit current of the starter according to standard IEC/EN 60947-4-2
Starter Iq (kA) in 500 V
ATS 22D17 p ATS 22D75 p 25
ATS 22D88 p ATS 22C59 p 50
Breaking capacity of circuit-breakers according to standard IEC/EN 60947-4-2
Circuit-breaker Icu (kA)in 400 V
Icu (kA)in 440 V
GV3 L 50 50
NS80H6-MA 70 65
Circuit-breaker Icu (kA)in 400 V Icu (kA)in 440 V
F N H S L F N H S L
NSX100NSX630 36 50 70 100 150 35 50 65 90 130
NS630b 50 70 150 50 65 130
8/10/2019 Alti Start 22
15/16
2
1
3
4
5
6
7
8
9
10
1717
Compatible components in accordance with standard UL 508Product without enclosure
Three-phase,4-pole motor 50/60 Hz Class 10 starter Maximumshort-circuitcurrent (SCC)at 600 V
Contactor (1) Time delay fuse(sold by Ferraz)
208 VHP
230 VHP
460 VHP
575 VHP
A
kA
Class J
M1 M1 M1 M1 A1 KM1 F13 5 10 15 14 ATS 22D17S6U 5 LC1 D18 pp AJT 40
7.5 10 20 25 27 ATS 22D32S6U 5 LC1 D32 pp AJT 70
15 30 40 40 ATS 22D47S6U 5 LC1 D50A pp AJT 100
15 20 40 50 52 ATS 22D62S6U 10 LC1 D65A pp AJT 125
20 25 50 60 65 ATS 22D75S6U 10 LC1 D80A pp AJT 175
25 30 60 75 77 ATS 22D88S6U 10 LC1 D115 pp AJT 200
30 40 75 100 96 ATS 22C11S6U 10 LC1 D115 pp AJT 250
40 50 100 125 124 ATS 22C14S6U 10 LC1 D150 pp AJT 300
50 60 125 150 156 ATS 22C17S6U 10 LC1 F185 pp AJT 40060 75 150 200 180 ATS 22C21S6U 18 LC1 F225 pp AJT 500
75 100 200 250 240 ATS 22C25S6U 18 LC1 F265 pp AJT 600
100 125 250 300 302 ATS 22C32S6U 18 LC1 F330 pp 2 x AJT 350
125 150 300 350 361 ATS 22C41S6U 18 LC1 F400 pp 2 x AJT 400
150 350 400 414 ATS 22C48S6U 18 LC1 F500 pp 2 x AJT 500
200 400 500 477 ATS 22C59S6U 30 LC1 F630 pp 2 x AJT 600
Enclosed productThree-phase,4-pole motor 50/60 Hz
Class 10starter
Maximumshort-circuitcurrent (SCC)at 600 V
Minimumwall-mountedenclosurevolume
Contactor (1) Time delay fuse
kA
cm 3
inch 3
Class JA
Class LA
208 VHP
230 VHP
460 VHP
575 VHP
A
M1 M1 M1 M1 A1 KM1 F1
3 5 10 15 14 ATS 22D17S6U 100 40 2406 LC1 D18 pp 30
7.5 10 20 25 27 ATS 22D32S6U 100 40 2406 LC1 D32 pp 60
15 30 40 40 ATS 22D47S6U 100 40 2406 LC1 D50A pp 90
15 20 40 50 52 ATS 22D62S6U 100 52 3149 LC1 D65A pp 110
20 25 50 60 65 ATS 22D75S6U 100 52 3149 LC1 D80A pp 150
25 30 60 75 77 ATS 22D88S6U 100 52 3149 LC1 D115 pp 175
30 40 75 100 96 ATS 22C11S6U 100 125 7630 LC1 D115 pp 200
40 50 100 125 124 ATS 22C14S6U 100 125 7630 LC1 F150 pp 250
50 60 125 150 156 ATS 22C17S6U 100 125 7630 LC1 F185 pp 300
60 75 150 200 180 ATS 22C21S6U 100 130 7892 LC1 F225 pp 400
75 100 200 250 240 ATS 22C25S6U 100 130 7892 LC1 F265 pp 450
100 125 250 300 302 ATS 22C32S6U 100 130 7892 LC1 F330 pp 600
125 150 300 350 361 ATS 22C41S6U 100 130 7892 LC1 F400 pp 600 150 350 400 414 ATS 22C48S6U 100 195 11,869 LC1 F500 pp 800
200 400 500 477 ATS 22C59S6U 100 195 11,869 LC1 F630 pp 800
(1) Replace pp with the control circuit reference: please consult our Motor starter solutions. Control and protection componentscatalogue.
Combinations (continued) Altistart 22soft start - soft stop unitsMotor starters:208575 V three-phase power supply voltage
Presentation:page 8
References:page 12
Motor starter with protectionby fuse
M1: three-phaseasynchronousmotor
2 4
1
6
5 3
W / T 3
U / T 1
V / T 2
R / L 1
S / L 2
T / L 3
W 1
V 1
3
U 1
M1
1 3
2 6 4
5
A1 : ATS 22 p
KM1 :TeSys LC1 p
F1 : AJT ppp
8/10/2019 Alti Start 22
16/16
D I A 2 E D 2 0 9 0 8 0 4 E N
The information provided in this documentation contains general descriptions and/or technicalcharacteristics of the performance of the products contained herein. This documentation is notintended as a substitute for and is not to be used for determining suitability or reliability of theseproducts for speci c user applications. It is the duty of any such user or integrator to perform theappropriate and complete risk analysis, evaluation and testing of the products with respect to therelevant speci c application or use thereof. Neither Schneider Electr ic nor any of its af liates or
subsidiaries shall be responsible or liable for misuse of the information contained herein.
Design: Schneider ElectricPhotos: Schneider ElectricPrinted by:
Head Of ce35, rue Joseph Monier F-92500 Rueil-MalmaisonFrance
Schneider Electric Industr ies SAS www.schneider-electric.com