Upload
others
View
17
Download
0
Embed Size (px)
Citation preview
The
info
rmat
ion
prov
ided
in th
is d
ocum
enta
tion
cont
ains
gen
eral
des
crip
tions
and
/or t
echn
ical
cha
ract
eris
tics
of th
e pe
rform
ance
of t
he p
rodu
cts
cont
aine
d he
rein
.Th
is d
ocum
enta
tion
is n
ot in
tend
ed a
s a
subs
titut
e fo
r and
is n
ot to
be
used
for d
eter
min
ing
suita
bilit
y or
relia
bilit
y of
thes
e pr
oduc
ts fo
r spe
cific
use
r app
licat
ions
.It
is th
e du
ty o
f any
suc
h us
er o
r int
egra
tor t
o pe
rform
the
appr
opria
te a
nd c
ompl
ete
risk
anal
ysis
, eva
luat
ion
and
test
ing
of th
e pr
oduc
ts w
ith re
spec
t to
the
rele
vant
spe
cific
app
licat
ion
or u
se th
ereo
f.N
eith
er S
chne
ider
Ele
ctric
Indu
strie
s SA
S no
r any
of i
ts a
ffilia
tes
or s
ubsi
diar
ies
shal
l be
resp
onsi
ble
or li
able
for m
isus
e of
the
info
rmat
ion
cont
aine
d he
rein
.
Nov 22, 20211
Product data sheetCharacteristics
ATV630D30N4Variable speed drive, Altivar Process ATV600,ATV630, 30kW/40 hp, 380...480 V, IP21/ULtype 1
2
MainRange of product Altivar Process ATV600Product or componenttype
Variable speed drive
Product specificapplication
Process and utilities
Device short name ATV630Variant Standard versionProduct destination Asynchronous motors
Synchronous motorsEMC filter Integrated with 50 m conforming to EN/IEC 61800-3
category C2Integrated with 150 m conforming to EN/IEC 61800-3category C3
IP degree of protection IP21 conforming to IEC 61800-5-1IP21 conforming to IEC 60529
[Us] rated supplyvoltage
380...480 V
Degree of protection UL type 1 conforming to UL 508CType of cooling Forced convectionSupply frequency 50...60 Hz - 5...5 %[Us] rated supplyvoltage
380...480 V - 15...10 %
Motor power kW 30 KW (normal duty)22 kW (heavy duty)
Motor power hp 40 Hp normal duty30 hp heavy duty
Line current 53.3 A at 380 V (normal duty)45.9 A at 480 V (normal duty)40.5 A at 380 V (heavy duty)35.8 A at 480 V (heavy duty)
Prospective line Isc 50 kAApparent power 38.2 KVA at 480 V (normal duty)
29.8 kVA at 480 V (heavy duty)Continuous outputcurrent
61.5 A at 4 kHz for normal duty46.3 A at 4 kHz for heavy duty
Maximum transientcurrent
67.7 A during 60 s (normal duty)69.5 A during 60 s (heavy duty)
Asynchronous motorcontrol profile
Variable torque standardOptimized torque modeConstant torque standard
Synchronous motorcontrol profile
Permanent magnet motorSynchronous reluctance motor
Speed drive outputfrequency
0.1…500 Hz
Nominal switchingfrequency
4 kHz
Switching frequency 2...12 kHz adjustable4...12 kHz with derating factor
Safety function STO (safe torque off) SIL 3Discrete input logic 16 preset speeds
3
Communication portprotocol
EthernetModbus TCPModbus serial
Option card Slot A: communication module, Profibus DP V1Slot A: communication module, ProfinetSlot A: communication module, DeviceNetSlot A: communication module, Modbus TCP/EtherNet/IPSlot A: communication module, CANopen daisychain RJ45Slot A: communication module, CANopen SUB-D 9Slot A: communication module, CANopen screwterminalsSlot A/slot B: digital and analog I/O extensionmoduleSlot A/slot B: output relay extension moduleSlot A: communication module, Ethernet IP/ModbusTCP/MD-LinkCommunication module, BACnet MS/TPCommunication module, Ethernet Powerlink
ComplementaryMounting mode Wall mountNetwork number of phases 3 phasesDiscrete output number 0Discrete output type Relay outputs R1A, R1B, R1C 250 V AC 3000 mA
Relay outputs R1A, R1B, R1C 30 V DC 3000 mARelay outputs R2A, R2C 250 V AC 5000 mARelay outputs R2A, R2C 30 V DC 5000 mARelay outputs R3A, R3C 250 V AC 5000 mARelay outputs R3A, R3C 30 V DC 5000 mA
Output voltage <= power supply voltagePermissible temporary current boost 1.1 x In during 60 s (normal duty)
1.5 x In during 60 s (heavy duty)Motor slip compensation Adjustable
Automatic whatever the loadCan be suppressedNot available in permanent magnet motor law
Acceleration and deceleration ramps Linear adjustable separately from 0.01...9999 sPhysical interface Ethernet
2-wire RS 485Braking to standstill By DC injectionProtection type Thermal protection: motor
Safe torque off: motorMotor phase break: motorThermal protection: driveSafe torque off: driveOverheating: driveOvercurrent between output phases and earth: driveOverload of output voltage: driveShort-circuit protection: driveMotor phase break: driveOvervoltages on the DC bus: driveLine supply overvoltage: driveLine supply undervoltage: driveLine supply phase loss: driveOverspeed: driveBreak on the control circuit: drive
Transmission rate 10, 100 Mbits4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Frequency resolution Display unit: 0.1 HzAnalog input: 0.012/50 Hz
Transmission frame RTUElectrical connection Control: removable screw terminals 0.5...1.5 mm²/AWG 20...AWG 16
Line side: screw terminal 25...50 mm²/AWG 4...AWG 1Motor: screw terminal 25...50 mm²/AWG 4...AWG 1
Connector type RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCPRJ45 (on the remote graphic terminal) for Modbus serial
Data format 8 bits, configurable odd, even or no parityType of polarization No impedance
4
Exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCPNumber of addresses 1…247 for Modbus serialMethod of access Slave Modbus TCPSupply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type:
overload and short-circuit protectionInternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %,<10 mA, protection type: overload and short-circuit protectionInternal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA,protection type: overload and short-circuit protection
Local signalling 3 LEDs for local diagnostic3 LEDs (dual colour) for embedded communication status4 LEDs (dual colour) for communication module status1 LED (red) for presence of voltage
Width 226 mmHeight 673 mmDepth 271 mmNet weight 28 kgAnalogue input number 3Analogue input type AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm,
resolution 12 bitsAI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm,resolution 12 bitsAI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12bits
Discrete input number 8Discrete input type DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)Input compatibility DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2
DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2
Discrete input logic Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1)Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
Analogue output number 2Analogue output type Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm,
resolution 10 bitsSoftware-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bitsSoftware-configurable current DQ-, DQ+: 30 V DCSoftware-configurable current DQ-, DQ+: 100 mA
Sampling duration 2 Ms +/- 0.5 ms (DI1...DI4) - discrete input5 Ms +/- 1 ms (DI5, DI6) - discrete input5 Ms +/- 0.1 ms (AI1, AI2, AI3) - analog input10 ms +/- 1 ms (AO1) - analog output
Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog inputAO1, AO2: +/- 0.2 % for analog output
Relay output number 3Relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles
Configurable relay logic R2: sequence relay NO electrical durability100000 cyclesConfigurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms)Minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DCMaximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC
Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DCRelay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at250 V ACRelay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at30 V DC
Isolation Between power and control terminalsMaximum output frequency 500 kHzMaximum input current 53.3 A
5
Variable speed drive application selection Building - HVAC Compressor centrifugalFood and beverage processing Other applicationMining mineral and metal FanMining mineral and metal PumpOil and gas FanWater and waste water Other applicationBuilding - HVAC Screw compressorFood and beverage processing PumpFood and beverage processing FanFood and beverage processing AtomizationOil and gas Electro submersible pump (ESP)Oil and gas Water injection pumpOil and gas Jet fuel pumpOil and gas Compressor for refineryWater and waste water Centrifuge pumpWater and waste water Positive displacement pumpWater and waste water Electro submersible pump (ESP)Water and waste water Screw pumpWater and waste water Lobe compressorWater and waste water Screw compressorWater and waste water Compressor centrifugalWater and waste water FanWater and waste water ConveyorWater and waste water Mixer
Motor power range AC-3 30…50 KW at 380…440 V 3 phases30…50 kW at 480…500 V 3 phases
Quantity per set 1Enclosure mounting Wall mounted
EnvironmentInsulation resistance > 1 MOhm 500 V DC for 1 minute to earthNoise level 63.5 dB conforming to 86/188/EECPower dissipation in W Natural convection: 93 W at 380 V, switching frequency 4 kHz
Forced convection: 640 W at 380 V, switching frequency 4 kHzVolume of cooling air 240 m3/hOperating position Vertical +/- 10 degreeMaximum THDI <48 % from 80...100 % of load conforming to IEC 61000-3-12Electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conformingto IEC 61000-4-3Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-41.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Pollution degree 2 conforming to EN/IEC 61800-5-1Vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6Shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27Relative humidity 5…95 % without condensation conforming to IEC 60068-2-3Ambient air temperature for operation -15…50 °C (without derating)
50…60 °C (with derating factor)Ambient air temperature for storage -40…70 °COperating altitude <= 1000 m without derating
1000...4800 m with current derating 1 % per 100 mStandards UL 508C
EN/IEC 61800-3Environment 1 category C2 EN/IEC 61800-3Environment 2 category C3 EN/IEC 61800-3EN/IEC 61800-5-1IEC 61000-3-12IEC 60721-3IEC 61508IEC 13849-1
Product certifications TÜVATEX INERISULCSAATEX zone 2/22DNV-GL
Marking CE
6
Standards UL 508CEN/IEC 61800-3EN/IEC 61800-3 environment 1 category C2EN/IEC 61800-3 environment 2 category C3EN/IEC 61800-5-1IEC 61000-3-12IEC 60721-3IEC 61508IEC 13849-1
Overvoltage category IIIRegulation loop Adjustable PID regulatorNoise level 63.5 dBPollution degree 2
Packing UnitsUnit Type of Package 1 PCENumber of Units in Package 1 1Package 1 Weight 37.6 kgPackage 1 Height 55.5 cmPackage 1 width 33 cmPackage 1 Length 84 cmUnit Type of Package 2 PALNumber of Units in Package 2 1Package 2 Weight 40 kgPackage 2 Height 52 cmPackage 2 width 35 cmPackage 2 Length 81 cm
Offer SustainabilitySustainable offer status Green Premium productREACh Regulation REACh DeclarationEU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS
DeclarationMercury free YesRoHS exemption information YesChina RoHS Regulation China RoHS DeclarationEnvironmental Disclosure Product Environmental ProfileCircularity Profile End Of Life InformationWEEE The product must be disposed on European Union markets following specific
waste collection and never end up in rubbish binsCalifornia proposition 65 WARNING: This product can expose you to chemicals including: Lead and
lead compounds, which is known to the State of California to cause cancerand birth defects or other reproductive harm. For more information go towww.P65Warnings.ca.gov
Upgradeability Upgraded Components Available
7
Product data sheetDimensions Drawings
ATV630D30N4
Dimensions
Drives with IP21 Top CoverFront, Left and Rear Views
Drives Without IP21 Top CoverLeft and Rear Views
8
Product data sheetMounting and Clearance
ATV630D30N4
Clearances
X1 X2 X3
≥ 100 mm (3.94 in.) ≥ 100 mm (3.94 in.) ≥ 10 mm (0.39 in.)
Mounting Types
Mounting Type A: Individual IP21
a ≥ = 110 mm (4.33 in.)
9
Mounting Type B: Side by Side IP20 (Possible, 2 Drives Only)
Mounting Type C: Individual IP20
a ≥ = 110 mm (4.33 in.)
10
Product data sheetConnections and Schema
ATV630D30N4
Three-Phase Power Supply with Upstream Breaking via Line Contactor
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordancewith standard IEC/EN 60204-1
(1) Line choke if used(2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected.A1 : DriveKM1 : Line ContactorQ2, Q3 : Circuit breakersS1, S2 : PushbuttonsT1 : Transformer for control part
Three-Phase Power Supply with Downstream Breaking via Contactor
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordancewith standard IEC/EN 60204-1
(1) Line choke if used(2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected.A1 : DriveKM1 : Contactor
11
Control Block Wiring Diagram
(1) Safe Torque Off(2) Analog Output(3) Digital Input(4) Reference potentiometer(5) Analog InputR1A, R1B, R1C : Fault relayR2A, R2C : Sequence relayR3A, R3C : Sequence relay
Sensor ConnectionIt is possible to connect either 1 or 3 sensors on terminals AI2 or AI3.
Sink / Source Switch Configuration
The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.● Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.● Set the switch to Ext if using PLC outputs with NPN transistors.
Switch Set to SRC (Source) Position Using the Output Power Supply for the Digital Inputs
12
Switch Set to SRC (Source) Position and Use of an External Power Supply for the DIs
Switch Set to SK (Sink) Position Using the Output Power Supply for the Digital Inputs
Switch Set to EXT Position Using an External Power Supply for the DIs
13
Product data sheetPerformance Curves
ATV630D30N4
Derating Curves
40 °C (104 °F) - Mounting type A, B and C 50 °C (122 °F) - Mounting type A, B and C 60 °C (140 °F) - Mounting type B and C
In : Nominal Drive CurrentSF : Switching Frequency