AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO. UHM116800417
Page 1 of 55
AMENDMENT NO. 1
IFB NO. UHM116800417
TO THE PLANS AND SPECIFICATIONS FOR
SPALDING HALL
SECOND FLOOR RENOVATIONS
PROJECT NO. UHM 1168-004-17
UNIVERSITY OF HAWAI‘I AT MĀNOA HONOLULU, HAWAII
DECEMBER 28, 2018
This amendment modifies the original Solicitation Documents for the Project. The items listed within are hereby made a part of the contract for the above project and shall govern the work, taking precedence over previously issued plans and specifications governing the items mentioned. A. CHANGE TO DRAWINGS DISCIPLINE SHEET NUMBER DESCRIPTION None -- -- B. CHANGES TO TECHNICAL SPECIFICATIONS: The following pages of the
Solicitation Documents are revised: None
C. SUBSTITUTION OF MATERIALS AND EQUIPMENT SECTION / ITEMS
SPECIFIED BRAND
SUBSTITUTE BRAND
VARIANCE STATUS
FCU-1 through FCU-6
Carrier Daikin - Minor CFM variance. - Minor BTUH variance. - No valve package.
No exceptions taken, subject to notes on submittal.
2.02 – FAN COIL UNIT
Carrier Williams
- 6 row coils required to meet sensible capacities.
- Williams FCU is slight longer and slightly wider than Carrier FCU.
- Williams FCU height is slightly shorter than Carrier FCU.
Rejected, due to add’l rows of coil req’d as well as its larger dimensions.
AMENDMENT NO. 1 Project No.: UHM 1168-004-17 IFB NO. UHM116800417
Page 2 of 55
D. REQUEST FOR INFORMATION / CLARIFICATION
1. In regards to Section 11080 – Audio Video Systems, please confirm the following: a. Is there a one line drawing available for reference?
Response: The AV infrastructure shown is just “point to point”, so there isn’t a need for a one-line diagram. b. Will a full set of AV Drawings be made available for reference? In the
Drawing Set, drawings AV-3, AV-4 and AV-5 are missing.
Response: Drawings are not available.
2. Which doors require STC rating and what is the STC required? Response: The Control Room and Recording Rooms have STC 51 doors. The outer vestibule door only needs to be STC 30. See AC-1 Acoustical Details Layout for reference.
E. PRE-BID CONFERENCE AND JOB SITE WALK-THROUGH
1. Pre-bid conference and site walk through was held on December 19, 2018
at 9:00am at University of Hawaii, Manoa at Spalding Hall, Second Floor.
END OF AMENDMENT NO. 1
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation
1 of 37 www.DaikinApplied.com
SUBMITTAL DATA
for
Spalding Hall 2nd Floor Renovation
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation
2 of 37 www.DaikinApplied.com
Table of Contents
Drawings(1) for FCU-1 ................................................................................................................................................................ 3
Item Summary for FCU-1............................................................................................................................................................ 4
Technical Data Sheet for FCU-1 .................................................................................................................................................. 6
Drawings(1) for FCU-2 ................................................................................................................................................................ 8
Item Summary for FCU-2............................................................................................................................................................ 9
Technical Data Sheet for FCU-2 ................................................................................................................................................ 11
Drawings(1) for FCU-3 .............................................................................................................................................................. 13
Item Summary for FCU-3.......................................................................................................................................................... 14
Technical Data Sheet for FCU-3 ................................................................................................................................................ 16
Drawings(1) for FCU-4 .............................................................................................................................................................. 18
Item Summary for FCU-4.......................................................................................................................................................... 19
Technical Data Sheet for FCU-4 ................................................................................................................................................ 21
Drawings(1) for FCU-5 .............................................................................................................................................................. 23
Item Summary for FCU-5.......................................................................................................................................................... 24
Technical Data Sheet for FCU-5 ................................................................................................................................................ 26
Drawings(1) for FCU-6 .............................................................................................................................................................. 28
Item Summary for FCU-6.......................................................................................................................................................... 29
Technical Data Sheet for FCU-6 ................................................................................................................................................ 31
Specification for DST Vertical Fancoil ALL ................................................................................................................................ 33
Job
Nam
e:
Job
Nu
mb
er:
Draw
ings(1
) for FC
U-1
Spald
ing H
all 2n
d Flo
or
Ren
ovatio
n
E21
UYZ
3 o
f 37
Page
Pre
pare
d D
ate:
ww
w.D
aikinA
pp
lied.co
m
12
/21
/20
18
Drawings(1) for FCU-1
Product Drawing Unit Tag: FCU-1 Sales Office: Norman Wright Mech. Equip. Corp.
13600 Industrial Park Blvd. Minneapolis, MN 55441
www.DaikinApplied.com Software Version: 06.70
Product: Project Name: Spalding Hall 2nd Floor Renovation
Sales Engineer:
Model: FCHH210 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
Item Summary for FCU-1
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 4 of 37 www.DaikinApplied.com
Item Summary for FCU-1
Job Information Item Summary
Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018
Model FCHH210 Software Version 06.70
Unit Tag FCU-1
Unit Options
Code Item
Code Value
Description
1 FC Unit Type; Fan Coil
2 HH Product Identifier; Horizontal Hideaway
3 2 Design Series; Design 2
4 10 Unit Size; 1000 CFM
5 A Voltage - Primary and Secondary; 115/60/1
6 A Coils - Fin Type; Aluminum
7 G Coils - Casing Material; Galvanized
8 M Coils - Air Vent; Manual
9 Y Coils - Coating; None
10 06 Coil Circuiting - Primary Coil; 6 Circuits
11 C Primary Coil Type; Chilled Water Only
12 4 Rows Primary Coil; 4-Row
13 12 Fins Per Inch - Primary Coil; 12 FPI
14 L Connection Location - Primary Coil; Left Hand
15 Y Piping Package - Primary Coil; None
16 S Connection Type - Primary Coil; Sweat
17 YY Preheat Coil Type; None
18 00 Fins Per Inch - Preheat Coil; None
19 Y Connection Location - Preheat Coil; None
20 Y Piping Package - Preheat Coil; None
21 Y Connection Type - Preheat Coil; None
22 YY Coil Circuiting - Secondary Coil; None
23 YY Reheat Coil Type; None
24 00 Fins Per Inch - Reheat Coil; None
25 Y Connection Location - Reheat Coil; None
26 Y Piping Package - Reheat Coil; None
27 Y Connection Type - Reheat Coil; None
28 Y Electric Heat Power Supply; None
29 000 Electric Heat Wattage; None
30 YY Future Use - Secondary Heating; None
31 S Drain Pan Material; Stainless Steel
32 VSP Blower Motor Type; Field Adjustable ECM
33 H Discharge Conditions; High Static
34 3 Motor Speed; 3 Speed
35 Q Motor Connections; Quick Connect
36 CC ECM Blower Motor Type; Constant CFM
37 YY Fresh Air Damper; None
38 YYY Cabinet Length; Standard Cabinet
39 D Unit Disconnect Switch; Disconnect Switch, Toggle
40 L Control Voltage; 24V control voltage
41 L Control Type; LV interface board, 3 sp switch
42 Y Network Communication Card; None
43 Y Changeover Type; None
44 Y Programmability; None
45 YY Setpoint Adjustment; None
Item Summary for FCU-1
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 5 of 37 www.DaikinApplied.com
Code Item
Code Value
Description
46 YBY Fan Speed Control; Off/Low/Med/High
47 Y Timed Override; None
48 YYYY Primary Coil Valve; None
49 YYYY Preheat Coil Valve; None
50 YYYY Reheat Coil Valve; None
51 Y Future Use - Controls; None
52 Y Low Temperature Protection; None
53 Y Condensate Overflow Protection; None
54 Y Discharge Air Thermistor; None
55 Y Smoke Input; None
56 Y Occ / Vacant Control Input; None
57 Y Filter Status; None
58 Y Fan Status; None
59 Y Entering Water Thermistor; None
60 Y Control Panel Revision; None
61 Y Cabinet Style; None
62 18 Cabinet Gauge; 18 Gauge
63 Y Cabinet Coating Type; None
64 Y Cabinet Color; None
65 00 Cabinet Depth Extension; None
66 S Unit Lineup Position; Standalone
67 00 Left Hand End Pocket Extension; None
68 00 Right Hand End Pocket Extension; None
69 YYY Subbase; None
70 FD Discharge Air - Outlet; Front Discharge, Duct Collar
71 RD Return Air - Inlet; Rear Return Air, Duct Collar
72 1 Filter; 1" Throwaway MERV 4 Filter
73 YYY Special Options; None
74 F Cabinet/Plenum; 1/2 inch Fiberglass
75 A Agency Listing; ETL, CETL, ARI
76 S Packaging; Standard
77 L Extended Warranty; 1st Year Labor Allowance
78 C Shipping Options; Standard
Technical Data Sheet for FCU-1
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 6 of 37 www.DaikinApplied.com
Technical Data Sheet for FCU-1
Job Information Technical Data Sheet
Job Name Spalding Hall 2nd Floor Renovation
Date 12/21/2018
Submitted By Thomas Miske
Software Version 06.70
Unit Tag FCU-1
Unit Overview
Model Number Unit Size Voltage V/Hz/Phase
Air Flow CFM
External Static Pressure
inH₂O
Unit Configuration
FCHH210 10 115/60/1 509.0 0.20 Horizontal
Unit
Model Number: FCHH210 Type: Fan Coil
Orientation: Horizontal
Size: 10
Cabinet: Hideaway
Approval ETL, CETL, AHRI
Physical
Unit
Depth Width Height Shipping Weight
20.2 in 63.5 in 9.9 in 134 lb
Filters
Type (Quantity) Height x Width x Depth
1" Throwaway MERV 4 Filter (2) 9.38 in x 26.00 in x 1 in
Electrical
Unit
Voltage Fan Motor Amps Unit MCA Unit MROPD
115/60/1 V/Hz/Phase 8.5 A 10.6 A 15 A
Chilled Water Coil
Physical
Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity
12 4 6 3.1 ft² 162.1 ft/min
Performance
Capacity Air Temperature
Total Btu/hr
Sensible Btu/hr
Entering Leaving
Dry Bulb °F
Wet Bulb °F
Dry Bulb °F
Wet Bulb °F
22369 15175 80.0 67.0 52.7 52.5
Fluid
Temperature Type Flow rate gpm
Pressure Drop ft H₂O Entering
°F Leaving
°F
45.0 55.0 Water 4.5 3.65
Technical Data Sheet for FCU-1
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 7 of 37 www.DaikinApplied.com
Supply Fan
Fan
Fan Height Fan Width Quantity
8.00 in 6.00 in 4
Motor
Type Horsepower Quantity
Field Adjustable ECM (2) 1/4 hp 2
Sound
Casing Radiated Sound Power (db)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
56 56 58 57 53 46 47
Options
General
Cabinet Plenum Insulation: 1/2 inch Fiberglass
Cabinet Gauge: 18 Gauge
Return Air Plenum: Plenum
Return Air Location: Rear
Disconnect Switch: Disconnect Switch
Warranty
Warranty: Standard
AHRI Certification
All equipment is rated and certified in accordance with AHRI 440.
Notes
Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.
Job
Nam
e:
Job
Nu
mb
er:
Draw
ings(1
) for FC
U-2
Spald
ing H
all 2n
d Flo
or
Ren
ovatio
n
E21
UYZ
8 o
f 37
Page
Pre
pare
d D
ate:
ww
w.D
aikinA
pp
lied.co
m
12
/21
/20
18
Drawings(1) for FCU-2
Product Drawing Unit Tag: FCU-2 Sales Office: Norman Wright Mech. Equip. Corp.
13600 Industrial Park Blvd. Minneapolis, MN 55441
www.DaikinApplied.com Software Version: 06.70
Product: Project Name: Spalding Hall 2nd Floor Renovation
Sales Engineer:
Model: FCHH212 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
Item Summary for FCU-2
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 9 of 37 www.DaikinApplied.com
Item Summary for FCU-2
Job Information Item Summary
Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018
Model FCHH212 Software Version 06.70
Unit Tag FCU-2
Unit Options
Code Item
Code Value
Description
1 FC Unit Type; Fan Coil
2 HH Product Identifier; Horizontal Hideaway
3 2 Design Series; Design 2
4 12 Unit Size; 1200 CFM
5 A Voltage - Primary and Secondary; 115/60/1
6 A Coils - Fin Type; Aluminum
7 G Coils - Casing Material; Galvanized
8 M Coils - Air Vent; Manual
9 Y Coils - Coating; None
10 06 Coil Circuiting - Primary Coil; 6 Circuits
11 C Primary Coil Type; Chilled Water Only
12 4 Rows Primary Coil; 4-Row
13 12 Fins Per Inch - Primary Coil; 12 FPI
14 L Connection Location - Primary Coil; Left Hand
15 Y Piping Package - Primary Coil; None
16 S Connection Type - Primary Coil; Sweat
17 YY Preheat Coil Type; None
18 00 Fins Per Inch - Preheat Coil; None
19 Y Connection Location - Preheat Coil; None
20 Y Piping Package - Preheat Coil; None
21 Y Connection Type - Preheat Coil; None
22 YY Coil Circuiting - Secondary Coil; None
23 YY Reheat Coil Type; None
24 00 Fins Per Inch - Reheat Coil; None
25 Y Connection Location - Reheat Coil; None
26 Y Piping Package - Reheat Coil; None
27 Y Connection Type - Reheat Coil; None
28 Y Electric Heat Power Supply; None
29 000 Electric Heat Wattage; None
30 YY Future Use - Secondary Heating; None
31 S Drain Pan Material; Stainless Steel
32 VSP Blower Motor Type; Field Adjustable ECM
33 H Discharge Conditions; High Static
34 3 Motor Speed; 3 Speed
35 Q Motor Connections; Quick Connect
36 CC ECM Blower Motor Type; Constant CFM
37 YY Fresh Air Damper; None
38 YYY Cabinet Length; Standard Cabinet
39 D Unit Disconnect Switch; Disconnect Switch, Toggle
40 L Control Voltage; 24V control voltage
41 L Control Type; LV interface board, 3 sp switch
42 Y Network Communication Card; None
43 Y Changeover Type; None
44 Y Programmability; None
45 YY Setpoint Adjustment; None
Item Summary for FCU-2
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 10 of 37 www.DaikinApplied.com
Code Item
Code Value
Description
46 YBY Fan Speed Control; Off/Low/Med/High
47 Y Timed Override; None
48 YYYY Primary Coil Valve; None
49 YYYY Preheat Coil Valve; None
50 YYYY Reheat Coil Valve; None
51 Y Future Use - Controls; None
52 Y Low Temperature Protection; None
53 Y Condensate Overflow Protection; None
54 Y Discharge Air Thermistor; None
55 Y Smoke Input; None
56 Y Occ / Vacant Control Input; None
57 Y Filter Status; None
58 Y Fan Status; None
59 Y Entering Water Thermistor; None
60 Y Control Panel Revision; None
61 Y Cabinet Style; None
62 18 Cabinet Gauge; 18 Gauge
63 Y Cabinet Coating Type; None
64 Y Cabinet Color; None
65 00 Cabinet Depth Extension; None
66 S Unit Lineup Position; Standalone
67 00 Left Hand End Pocket Extension; None
68 00 Right Hand End Pocket Extension; None
69 YYY Subbase; None
70 FD Discharge Air - Outlet; Front Discharge, Duct Collar
71 RD Return Air - Inlet; Rear Return Air, Duct Collar
72 1 Filter; 1" Throwaway MERV 4 Filter
73 YYY Special Options; None
74 F Cabinet/Plenum; 1/2 inch Fiberglass
75 A Agency Listing; ETL, CETL, ARI
76 S Packaging; Standard
77 L Extended Warranty; 1st Year Labor Allowance
78 C Shipping Options; Standard
Technical Data Sheet for FCU-2
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 11 of 37 www.DaikinApplied.com
Technical Data Sheet for FCU-2
Job Information Technical Data Sheet
Job Name Spalding Hall 2nd Floor Renovation
Date 12/21/2018
Submitted By Thomas Miske
Software Version 06.70
Unit Tag FCU-2
Unit Overview
Model Number Unit Size Voltage V/Hz/Phase
Air Flow CFM
External Static Pressure
inH₂O
Unit Configuration
FCHH212 12 115/60/1 800.0 0.20 Horizontal
Unit
Model Number: FCHH212 Type: Fan Coil
Orientation: Horizontal
Size: 12
Cabinet: Hideaway
Approval ETL, CETL, AHRI
Physical
Unit
Depth Width Height Shipping Weight
20.2 in 72.5 in 9.9 in 155 lb
Filters
Type (Quantity) Height x Width x Depth
1" Throwaway MERV 4 Filter (2) 9.38 in x 31.50 in x 1 in
Electrical
Unit
Voltage Fan Motor Amps Unit MCA Unit MROPD
115/60/1 V/Hz/Phase 8.5 A 10.6 A 15 A
Chilled Water Coil
Physical
Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity
12 4 6 3.8 ft² 208.9 ft/min
Performance
Capacity Air Temperature
Total Btu/hr
Sensible Btu/hr
Entering Leaving
Dry Bulb °F
Wet Bulb °F
Dry Bulb °F
Wet Bulb °F
36121 23842 80.0 67.0 52.7 52.1
Fluid
Temperature Type Flow rate gpm
Pressure Drop ft H₂O Entering
°F Leaving
°F
45.0 55.0 Water 7.2 16.24
Technical Data Sheet for FCU-2
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 12 of 37 www.DaikinApplied.com
Supply Fan
Fan
Fan Height Fan Width Quantity
8.00 in 6.00 in 4
Motor
Type Horsepower Quantity
Field Adjustable ECM (2) 1/4 hp 2
Sound
Casing Radiated Sound Power (db)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
63 62 62 61 58 52 47
Options
General
Cabinet Plenum Insulation: 1/2 inch Fiberglass
Cabinet Gauge: 18 Gauge
Return Air Plenum: Plenum
Return Air Location: Rear
Disconnect Switch: Disconnect Switch
Warranty
Warranty: Standard
AHRI Certification
All equipment is rated and certified in accordance with AHRI 440.
Notes
Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.
Job
Nam
e:
Job
Nu
mb
er:
Draw
ings(1
) for FC
U-3
Spald
ing H
all 2n
d Flo
or
Ren
ovatio
n
E21
UYZ
13
of 3
7
Page
Pre
pare
d D
ate:
ww
w.D
aikinA
pp
lied.co
m
12
/21
/20
18
Drawings(1) for FCU-3
Product Drawing Unit Tag: FCU-3 Sales Office: Norman Wright Mech. Equip. Corp.
13600 Industrial Park Blvd. Minneapolis, MN 55441
www.DaikinApplied.com Software Version: 06.70
Product: Project Name: Spalding Hall 2nd Floor Renovation
Sales Engineer:
Model: FCHH206 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
Item Summary for FCU-3
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 14 of 37 www.DaikinApplied.com
Item Summary for FCU-3
Job Information Item Summary
Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018
Model FCHH206 Software Version 06.70
Unit Tag FCU-3
Unit Options
Code Item
Code Value
Description
1 FC Unit Type; Fan Coil
2 HH Product Identifier; Horizontal Hideaway
3 2 Design Series; Design 2
4 06 Unit Size; 600 CFM
5 A Voltage - Primary and Secondary; 115/60/1
6 A Coils - Fin Type; Aluminum
7 G Coils - Casing Material; Galvanized
8 M Coils - Air Vent; Manual
9 Y Coils - Coating; None
10 04 Coil Circuiting - Primary Coil; 4 Circuits
11 C Primary Coil Type; Chilled Water Only
12 4 Rows Primary Coil; 4-Row
13 12 Fins Per Inch - Primary Coil; 12 FPI
14 L Connection Location - Primary Coil; Left Hand
15 Y Piping Package - Primary Coil; None
16 S Connection Type - Primary Coil; Sweat
17 YY Preheat Coil Type; None
18 00 Fins Per Inch - Preheat Coil; None
19 Y Connection Location - Preheat Coil; None
20 Y Piping Package - Preheat Coil; None
21 Y Connection Type - Preheat Coil; None
22 YY Coil Circuiting - Secondary Coil; None
23 YY Reheat Coil Type; None
24 00 Fins Per Inch - Reheat Coil; None
25 Y Connection Location - Reheat Coil; None
26 Y Piping Package - Reheat Coil; None
27 Y Connection Type - Reheat Coil; None
28 Y Electric Heat Power Supply; None
29 000 Electric Heat Wattage; None
30 YY Future Use - Secondary Heating; None
31 S Drain Pan Material; Stainless Steel
32 VSP Blower Motor Type; Field Adjustable ECM
33 H Discharge Conditions; High Static
34 3 Motor Speed; 3 Speed
35 Q Motor Connections; Quick Connect
36 CC ECM Blower Motor Type; Constant CFM
37 YY Fresh Air Damper; None
38 YYY Cabinet Length; Standard Cabinet
39 D Unit Disconnect Switch; Disconnect Switch, Toggle
40 L Control Voltage; 24V control voltage
41 L Control Type; LV interface board, 3 sp switch
42 Y Network Communication Card; None
43 Y Changeover Type; None
44 Y Programmability; None
45 YY Setpoint Adjustment; None
Item Summary for FCU-3
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 15 of 37 www.DaikinApplied.com
Code Item
Code Value
Description
46 YBY Fan Speed Control; Off/Low/Med/High
47 Y Timed Override; None
48 YYYY Primary Coil Valve; None
49 YYYY Preheat Coil Valve; None
50 YYYY Reheat Coil Valve; None
51 Y Future Use - Controls; None
52 Y Low Temperature Protection; None
53 Y Condensate Overflow Protection; None
54 Y Discharge Air Thermistor; None
55 Y Smoke Input; None
56 Y Occ / Vacant Control Input; None
57 Y Filter Status; None
58 Y Fan Status; None
59 Y Entering Water Thermistor; None
60 Y Control Panel Revision; None
61 Y Cabinet Style; None
62 18 Cabinet Gauge; 18 Gauge
63 Y Cabinet Coating Type; None
64 Y Cabinet Color; None
65 00 Cabinet Depth Extension; None
66 S Unit Lineup Position; Standalone
67 00 Left Hand End Pocket Extension; None
68 00 Right Hand End Pocket Extension; None
69 YYY Subbase; None
70 FD Discharge Air - Outlet; Front Discharge, Duct Collar
71 RD Return Air - Inlet; Rear Return Air, Duct Collar
72 1 Filter; 1" Throwaway MERV 4 Filter
73 YYY Special Options; None
74 F Cabinet/Plenum; 1/2 inch Fiberglass
75 A Agency Listing; ETL, CETL, ARI
76 S Packaging; Standard
77 L Extended Warranty; 1st Year Labor Allowance
78 C Shipping Options; Standard
Technical Data Sheet for FCU-3
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 16 of 37 www.DaikinApplied.com
Technical Data Sheet for FCU-3
Job Information Technical Data Sheet
Job Name Spalding Hall 2nd Floor Renovation
Date 12/21/2018
Submitted By Thomas Miske
Software Version 06.70
Unit Tag FCU-3
Unit Overview
Model Number Unit Size Voltage V/Hz/Phase
Air Flow CFM
External Static Pressure
inH₂O
Unit Configuration
FCHH206 06 115/60/1 308.0 0.20 Horizontal
Unit
Model Number: FCHH206 Type: Fan Coil
Orientation: Horizontal
Size: 06
Cabinet: Hideaway
Approval ETL, CETL, AHRI
Physical
Unit
Depth Width Height Shipping Weight
20.2 in 47.0 in 9.9 in 94 lb
Filters
Type (Quantity) Height x Width x Depth
1" Throwaway MERV 4 Filter (1) 9.38 in x 35.75 in x 1 in
Electrical
Unit
Voltage Fan Motor Amps Unit MCA Unit MROPD
115/60/1 V/Hz/Phase 4.2 A 5.3 A 15 A
Chilled Water Coil
Physical
Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity
12 4 4 2.1 ft² 146.0 ft/min
Performance
Capacity Air Temperature
Total Btu/hr
Sensible Btu/hr
Entering Leaving
Dry Bulb °F
Wet Bulb °F
Dry Bulb °F
Wet Bulb °F
13103 9003 80.0 67.0 53.3 53.1
Fluid
Temperature Type Flow rate gpm
Pressure Drop ft H₂O Entering
°F Leaving
°F
45.0 55.0 Water 2.6 3.63
Technical Data Sheet for FCU-3
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 17 of 37 www.DaikinApplied.com
Supply Fan
Fan
Fan Height Fan Width Quantity
8.00 in 6.00 in 2
Motor
Type Horsepower Quantity
Field Adjustable ECM 1/4 hp 1
Sound
Casing Radiated Sound Power (db)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
54 56 57 56 52 45 39
Options
General
Cabinet Plenum Insulation: 1/2 inch Fiberglass
Cabinet Gauge: 18 Gauge
Return Air Plenum: Plenum
Return Air Location: Rear
Disconnect Switch: Disconnect Switch
Warranty
Warranty: Standard
AHRI Certification
All equipment is rated and certified in accordance with AHRI 440.
Notes
Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.
Job
Nam
e:
Job
Nu
mb
er:
Draw
ings(1
) for FC
U-4
Spald
ing H
all 2n
d Flo
or
Ren
ovatio
n
E21
UYZ
18
of 3
7
Page
Pre
pare
d D
ate:
ww
w.D
aikinA
pp
lied.co
m
12
/21
/20
18
Drawings(1) for FCU-4
Product Drawing Unit Tag: FCU-4 Sales Office: Norman Wright Mech. Equip. Corp.
13600 Industrial Park Blvd. Minneapolis, MN 55441
www.DaikinApplied.com Software Version: 06.70
Product: Project Name: Spalding Hall 2nd Floor Renovation
Sales Engineer:
Model: FCHH210 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
Item Summary for FCU-4
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 19 of 37 www.DaikinApplied.com
Item Summary for FCU-4
Job Information Item Summary
Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018
Model FCHH210 Software Version 06.70
Unit Tag FCU-4
Unit Options
Code Item
Code Value
Description
1 FC Unit Type; Fan Coil
2 HH Product Identifier; Horizontal Hideaway
3 2 Design Series; Design 2
4 10 Unit Size; 1000 CFM
5 A Voltage - Primary and Secondary; 115/60/1
6 A Coils - Fin Type; Aluminum
7 G Coils - Casing Material; Galvanized
8 M Coils - Air Vent; Manual
9 Y Coils - Coating; None
10 06 Coil Circuiting - Primary Coil; 6 Circuits
11 C Primary Coil Type; Chilled Water Only
12 4 Rows Primary Coil; 4-Row
13 12 Fins Per Inch - Primary Coil; 12 FPI
14 L Connection Location - Primary Coil; Left Hand
15 Y Piping Package - Primary Coil; None
16 S Connection Type - Primary Coil; Sweat
17 YY Preheat Coil Type; None
18 00 Fins Per Inch - Preheat Coil; None
19 Y Connection Location - Preheat Coil; None
20 Y Piping Package - Preheat Coil; None
21 Y Connection Type - Preheat Coil; None
22 YY Coil Circuiting - Secondary Coil; None
23 YY Reheat Coil Type; None
24 00 Fins Per Inch - Reheat Coil; None
25 Y Connection Location - Reheat Coil; None
26 Y Piping Package - Reheat Coil; None
27 Y Connection Type - Reheat Coil; None
28 Y Electric Heat Power Supply; None
29 000 Electric Heat Wattage; None
30 YY Future Use - Secondary Heating; None
31 S Drain Pan Material; Stainless Steel
32 VSP Blower Motor Type; Field Adjustable ECM
33 H Discharge Conditions; High Static
34 3 Motor Speed; 3 Speed
35 Q Motor Connections; Quick Connect
36 CC ECM Blower Motor Type; Constant CFM
37 YY Fresh Air Damper; None
38 YYY Cabinet Length; Standard Cabinet
39 D Unit Disconnect Switch; Disconnect Switch, Toggle
40 L Control Voltage; 24V control voltage
41 L Control Type; LV interface board, 3 sp switch
42 Y Network Communication Card; None
43 Y Changeover Type; None
44 Y Programmability; None
45 YY Setpoint Adjustment; None
Item Summary for FCU-4
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 20 of 37 www.DaikinApplied.com
Code Item
Code Value
Description
46 YBY Fan Speed Control; Off/Low/Med/High
47 Y Timed Override; None
48 YYYY Primary Coil Valve; None
49 YYYY Preheat Coil Valve; None
50 YYYY Reheat Coil Valve; None
51 Y Future Use - Controls; None
52 Y Low Temperature Protection; None
53 Y Condensate Overflow Protection; None
54 Y Discharge Air Thermistor; None
55 Y Smoke Input; None
56 Y Occ / Vacant Control Input; None
57 Y Filter Status; None
58 Y Fan Status; None
59 Y Entering Water Thermistor; None
60 Y Control Panel Revision; None
61 Y Cabinet Style; None
62 18 Cabinet Gauge; 18 Gauge
63 Y Cabinet Coating Type; None
64 Y Cabinet Color; None
65 00 Cabinet Depth Extension; None
66 S Unit Lineup Position; Standalone
67 00 Left Hand End Pocket Extension; None
68 00 Right Hand End Pocket Extension; None
69 YYY Subbase; None
70 FD Discharge Air - Outlet; Front Discharge, Duct Collar
71 RD Return Air - Inlet; Rear Return Air, Duct Collar
72 1 Filter; 1" Throwaway MERV 4 Filter
73 YYY Special Options; None
74 F Cabinet/Plenum; 1/2 inch Fiberglass
75 A Agency Listing; ETL, CETL, ARI
76 S Packaging; Standard
77 L Extended Warranty; 1st Year Labor Allowance
78 C Shipping Options; Standard
Technical Data Sheet for FCU-4
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 21 of 37 www.DaikinApplied.com
Technical Data Sheet for FCU-4
Job Information Technical Data Sheet
Job Name Spalding Hall 2nd Floor Renovation
Date 12/21/2018
Submitted By Thomas Miske
Software Version 06.70
Unit Tag FCU-4
Unit Overview
Model Number Unit Size Voltage V/Hz/Phase
Air Flow CFM
External Static Pressure
inH₂O
Unit Configuration
FCHH210 10 115/60/1 509.0 0.20 Horizontal
Unit
Model Number: FCHH210 Type: Fan Coil
Orientation: Horizontal
Size: 10
Cabinet: Hideaway
Approval ETL, CETL, AHRI
Physical
Unit
Depth Width Height Shipping Weight
20.2 in 63.5 in 9.9 in 134 lb
Filters
Type (Quantity) Height x Width x Depth
1" Throwaway MERV 4 Filter (2) 9.38 in x 26.00 in x 1 in
Electrical
Unit
Voltage Fan Motor Amps Unit MCA Unit MROPD
115/60/1 V/Hz/Phase 8.5 A 10.6 A 15 A
Chilled Water Coil
Physical
Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity
12 4 6 3.1 ft² 162.1 ft/min
Performance
Capacity Air Temperature
Total Btu/hr
Sensible Btu/hr
Entering Leaving
Dry Bulb °F
Wet Bulb °F
Dry Bulb °F
Wet Bulb °F
22369 15175 80.0 67.0 52.7 52.5
Fluid
Temperature Type Flow rate gpm
Pressure Drop ft H₂O Entering
°F Leaving
°F
45.0 55.0 Water 4.5 3.65
Technical Data Sheet for FCU-4
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 22 of 37 www.DaikinApplied.com
Supply Fan
Fan
Fan Height Fan Width Quantity
8.00 in 6.00 in 4
Motor
Type Horsepower Quantity
Field Adjustable ECM (2) 1/4 hp 2
Sound
Casing Radiated Sound Power (db)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
56 56 58 57 53 46 47
Options
General
Cabinet Plenum Insulation: 1/2 inch Fiberglass
Cabinet Gauge: 18 Gauge
Return Air Plenum: Plenum
Return Air Location: Rear
Disconnect Switch: Disconnect Switch
Warranty
Warranty: Standard
AHRI Certification
All equipment is rated and certified in accordance with AHRI 440.
Notes
Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.
Job
Nam
e:
Job
Nu
mb
er:
Draw
ings(1
) for FC
U-5
Spald
ing H
all 2n
d Flo
or
Ren
ovatio
n
E21
UYZ
23
of 3
7
Page
Pre
pare
d D
ate:
ww
w.D
aikinA
pp
lied.co
m
12
/21
/20
18
Drawings(1) for FCU-5
Product Drawing Unit Tag: FCU-5 Sales Office: Norman Wright Mech. Equip. Corp.
13600 Industrial Park Blvd. Minneapolis, MN 55441
www.DaikinApplied.com Software Version: 06.70
Product: Project Name: Spalding Hall 2nd Floor Renovation
Sales Engineer:
Model: FCHH204 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
Item Summary for FCU-5
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 24 of 37 www.DaikinApplied.com
Item Summary for FCU-5
Job Information Item Summary
Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018
Model FCHH204 Software Version 06.70
Unit Tag FCU-5
Unit Options
Code Item
Code Value
Description
1 FC Unit Type; Fan Coil
2 HH Product Identifier; Horizontal Hideaway
3 2 Design Series; Design 2
4 04 Unit Size; 400 CFM
5 A Voltage - Primary and Secondary; 115/60/1
6 A Coils - Fin Type; Aluminum
7 G Coils - Casing Material; Galvanized
8 M Coils - Air Vent; Manual
9 Y Coils - Coating; None
10 04 Coil Circuiting - Primary Coil; 4 Circuits
11 C Primary Coil Type; Chilled Water Only
12 4 Rows Primary Coil; 4-Row
13 12 Fins Per Inch - Primary Coil; 12 FPI
14 L Connection Location - Primary Coil; Left Hand
15 Y Piping Package - Primary Coil; None
16 S Connection Type - Primary Coil; Sweat
17 YY Preheat Coil Type; None
18 00 Fins Per Inch - Preheat Coil; None
19 Y Connection Location - Preheat Coil; None
20 Y Piping Package - Preheat Coil; None
21 Y Connection Type - Preheat Coil; None
22 YY Coil Circuiting - Secondary Coil; None
23 YY Reheat Coil Type; None
24 00 Fins Per Inch - Reheat Coil; None
25 Y Connection Location - Reheat Coil; None
26 Y Piping Package - Reheat Coil; None
27 Y Connection Type - Reheat Coil; None
28 Y Electric Heat Power Supply; None
29 000 Electric Heat Wattage; None
30 YY Future Use - Secondary Heating; None
31 S Drain Pan Material; Stainless Steel
32 VSP Blower Motor Type; Field Adjustable ECM
33 H Discharge Conditions; High Static
34 3 Motor Speed; 3 Speed
35 Q Motor Connections; Quick Connect
36 CC ECM Blower Motor Type; Constant CFM
37 YY Fresh Air Damper; None
38 YYY Cabinet Length; Standard Cabinet
39 D Unit Disconnect Switch; Disconnect Switch, Toggle
40 L Control Voltage; 24V control voltage
41 L Control Type; LV interface board, 3 sp switch
42 Y Network Communication Card; None
43 Y Changeover Type; None
44 Y Programmability; None
45 YY Setpoint Adjustment; None
Item Summary for FCU-5
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 25 of 37 www.DaikinApplied.com
Code Item
Code Value
Description
46 YBY Fan Speed Control; Off/Low/Med/High
47 Y Timed Override; None
48 YYYY Primary Coil Valve; None
49 YYYY Preheat Coil Valve; None
50 YYYY Reheat Coil Valve; None
51 Y Future Use - Controls; None
52 Y Low Temperature Protection; None
53 Y Condensate Overflow Protection; None
54 Y Discharge Air Thermistor; None
55 Y Smoke Input; None
56 Y Occ / Vacant Control Input; None
57 Y Filter Status; None
58 Y Fan Status; None
59 Y Entering Water Thermistor; None
60 Y Control Panel Revision; None
61 Y Cabinet Style; None
62 18 Cabinet Gauge; 18 Gauge
63 Y Cabinet Coating Type; None
64 Y Cabinet Color; None
65 00 Cabinet Depth Extension; None
66 S Unit Lineup Position; Standalone
67 00 Left Hand End Pocket Extension; None
68 00 Right Hand End Pocket Extension; None
69 YYY Subbase; None
70 FD Discharge Air - Outlet; Front Discharge, Duct Collar
71 RD Return Air - Inlet; Rear Return Air, Duct Collar
72 1 Filter; 1" Throwaway MERV 4 Filter
73 YYY Special Options; None
74 F Cabinet/Plenum; 1/2 inch Fiberglass
75 A Agency Listing; ETL, CETL, ARI
76 S Packaging; Standard
77 L Extended Warranty; 1st Year Labor Allowance
78 C Shipping Options; Standard
Technical Data Sheet for FCU-5
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 26 of 37 www.DaikinApplied.com
Technical Data Sheet for FCU-5
Job Information Technical Data Sheet
Job Name Spalding Hall 2nd Floor Renovation
Date 12/21/2018
Submitted By Thomas Miske
Software Version 06.70
Unit Tag FCU-5
Unit Overview
Model Number Unit Size Voltage V/Hz/Phase
Air Flow CFM
External Static Pressure
inH₂O
Unit Configuration
FCHH204 04 115/60/1 225.0 0.20 Horizontal
Unit
Model Number: FCHH204 Type: Fan Coil
Orientation: Horizontal
Size: 04
Cabinet: Hideaway
Approval ETL, CETL, AHRI
Physical
Unit
Depth Width Height Shipping Weight
20.2 in 36.0 in 9.9 in 76 lb
Filters
Type (Quantity) Height x Width x Depth
1" Throwaway MERV 4 Filter (1) 9.38 in x 24.75 in x 1 in
Electrical
Unit
Voltage Fan Motor Amps Unit MCA Unit MROPD
115/60/1 V/Hz/Phase 4.2 A 5.3 A 15 A
Chilled Water Coil
Physical
Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity
12 4 4 1.4 ft² 157.3 ft/min
Performance
Capacity Air Temperature
Total Btu/hr
Sensible Btu/hr
Entering Leaving
Dry Bulb °F
Wet Bulb °F
Dry Bulb °F
Wet Bulb °F
9995 6753 80.0 67.0 52.6 52.4
Fluid
Temperature Type Flow rate gpm
Pressure Drop ft H₂O Entering
°F Leaving
°F
45.0 55.0 Water 2.0 1.80
Technical Data Sheet for FCU-5
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 27 of 37 www.DaikinApplied.com
Supply Fan
Fan
Fan Height Fan Width Quantity
8.00 in 6.00 in 2
Motor
Type Horsepower Quantity
Field Adjustable ECM 1/8 hp 1
Sound
Casing Radiated Sound Power (db)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
53 54 51 49 44 35 33
Options
General
Cabinet Plenum Insulation: 1/2 inch Fiberglass
Cabinet Gauge: 18 Gauge
Return Air Plenum: Plenum
Return Air Location: Rear
Disconnect Switch: Disconnect Switch
Warranty
Warranty: Standard
AHRI Certification
All equipment is rated and certified in accordance with AHRI 440.
Notes
Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.
Job
Nam
e:
Job
Nu
mb
er:
Draw
ings(1
) for FC
U-6
Spald
ing H
all 2n
d Flo
or
Ren
ovatio
n
E21
UYZ
28
of 3
7
Page
Pre
pare
d D
ate:
ww
w.D
aikinA
pp
lied.co
m
12
/21
/20
18
Drawings(1) for FCU-6
Product Drawing Unit Tag: FCU-6 Sales Office: Norman Wright Mech. Equip. Corp.
13600 Industrial Park Blvd. Minneapolis, MN 55441
www.DaikinApplied.com Software Version: 06.70
Product: Project Name: Spalding Hall 2nd Floor Renovation
Sales Engineer:
Model: FCHH204 Dec. 21, 2018 Ver/Rev: Sheet: 1 of 1 Scale: NTS Tolerance: +/- 0.25” Dwg Units: in
No change to this drawing may be made unless approved in writing by Daikin Applied. Purchaser must determine that the equipment is fit and sufficient for the job specifications.
Item Summary for FCU-6
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 29 of 37 www.DaikinApplied.com
Item Summary for FCU-6
Job Information Item Summary
Job Name Spalding Hall 2nd Floor Renovation Date 11/14/2018
Model FCHH204 Software Version 06.70
Unit Tag FCU-6
Unit Options
Code Item
Code Value
Description
1 FC Unit Type; Fan Coil
2 HH Product Identifier; Horizontal Hideaway
3 2 Design Series; Design 2
4 04 Unit Size; 400 CFM
5 A Voltage - Primary and Secondary; 115/60/1
6 A Coils - Fin Type; Aluminum
7 G Coils - Casing Material; Galvanized
8 M Coils - Air Vent; Manual
9 Y Coils - Coating; None
10 04 Coil Circuiting - Primary Coil; 4 Circuits
11 C Primary Coil Type; Chilled Water Only
12 4 Rows Primary Coil; 4-Row
13 12 Fins Per Inch - Primary Coil; 12 FPI
14 L Connection Location - Primary Coil; Left Hand
15 Y Piping Package - Primary Coil; None
16 S Connection Type - Primary Coil; Sweat
17 YY Preheat Coil Type; None
18 00 Fins Per Inch - Preheat Coil; None
19 Y Connection Location - Preheat Coil; None
20 Y Piping Package - Preheat Coil; None
21 Y Connection Type - Preheat Coil; None
22 YY Coil Circuiting - Secondary Coil; None
23 YY Reheat Coil Type; None
24 00 Fins Per Inch - Reheat Coil; None
25 Y Connection Location - Reheat Coil; None
26 Y Piping Package - Reheat Coil; None
27 Y Connection Type - Reheat Coil; None
28 Y Electric Heat Power Supply; None
29 000 Electric Heat Wattage; None
30 YY Future Use - Secondary Heating; None
31 S Drain Pan Material; Stainless Steel
32 VSP Blower Motor Type; Field Adjustable ECM
33 H Discharge Conditions; High Static
34 3 Motor Speed; 3 Speed
35 Q Motor Connections; Quick Connect
36 CC ECM Blower Motor Type; Constant CFM
37 YY Fresh Air Damper; None
38 YYY Cabinet Length; Standard Cabinet
39 D Unit Disconnect Switch; Disconnect Switch, Toggle
40 L Control Voltage; 24V control voltage
41 L Control Type; LV interface board, 3 sp switch
42 Y Network Communication Card; None
43 Y Changeover Type; None
44 Y Programmability; None
45 YY Setpoint Adjustment; None
Item Summary for FCU-6
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 30 of 37 www.DaikinApplied.com
Code Item
Code Value
Description
46 YBY Fan Speed Control; Off/Low/Med/High
47 Y Timed Override; None
48 YYYY Primary Coil Valve; None
49 YYYY Preheat Coil Valve; None
50 YYYY Reheat Coil Valve; None
51 Y Future Use - Controls; None
52 Y Low Temperature Protection; None
53 Y Condensate Overflow Protection; None
54 Y Discharge Air Thermistor; None
55 Y Smoke Input; None
56 Y Occ / Vacant Control Input; None
57 Y Filter Status; None
58 Y Fan Status; None
59 Y Entering Water Thermistor; None
60 Y Control Panel Revision; None
61 Y Cabinet Style; None
62 18 Cabinet Gauge; 18 Gauge
63 Y Cabinet Coating Type; None
64 Y Cabinet Color; None
65 00 Cabinet Depth Extension; None
66 S Unit Lineup Position; Standalone
67 00 Left Hand End Pocket Extension; None
68 00 Right Hand End Pocket Extension; None
69 YYY Subbase; None
70 FD Discharge Air - Outlet; Front Discharge, Duct Collar
71 RD Return Air - Inlet; Rear Return Air, Duct Collar
72 1 Filter; 1" Throwaway MERV 4 Filter
73 YYY Special Options; None
74 F Cabinet/Plenum; 1/2 inch Fiberglass
75 A Agency Listing; ETL, CETL, ARI
76 S Packaging; Standard
77 L Extended Warranty; 1st Year Labor Allowance
78 C Shipping Options; Standard
Technical Data Sheet for FCU-6
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 31 of 37 www.DaikinApplied.com
Technical Data Sheet for FCU-6
Job Information Technical Data Sheet
Job Name Spalding Hall 2nd Floor Renovation
Date 12/21/2018
Submitted By Thomas Miske
Software Version 06.70
Unit Tag FCU-6
Unit Overview
Model Number Unit Size Voltage V/Hz/Phase
Air Flow CFM
External Static Pressure
inH₂O
Unit Configuration
FCHH204 04 115/60/1 225.0 0.20 Horizontal
Unit
Model Number: FCHH204 Type: Fan Coil
Orientation: Horizontal
Size: 04
Cabinet: Hideaway
Approval ETL, CETL, AHRI
Physical
Unit
Depth Width Height Shipping Weight
20.2 in 36.0 in 9.9 in 76 lb
Filters
Type (Quantity) Height x Width x Depth
1" Throwaway MERV 4 Filter (1) 9.38 in x 24.75 in x 1 in
Electrical
Unit
Voltage Fan Motor Amps Unit MCA Unit MROPD
115/60/1 V/Hz/Phase 4.2 A 5.3 A 15 A
Chilled Water Coil
Physical
Fins per Inch Number of Rows Coil Circuits Face Area Face Velocity
12 4 4 1.4 ft² 157.3 ft/min
Performance
Capacity Air Temperature
Total Btu/hr
Sensible Btu/hr
Entering Leaving
Dry Bulb °F
Wet Bulb °F
Dry Bulb °F
Wet Bulb °F
9995 6753 80.0 67.0 52.6 52.4
Fluid
Temperature Type Flow rate gpm
Pressure Drop ft H₂O Entering
°F Leaving
°F
45.0 55.0 Water 2.0 1.80
Technical Data Sheet for FCU-6
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 32 of 37 www.DaikinApplied.com
Supply Fan
Fan
Fan Height Fan Width Quantity
8.00 in 6.00 in 2
Motor
Type Horsepower Quantity
Field Adjustable ECM 1/8 hp 1
Sound
Casing Radiated Sound Power (db)
125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz
53 54 51 49 44 35 33
Options
General
Cabinet Plenum Insulation: 1/2 inch Fiberglass
Cabinet Gauge: 18 Gauge
Return Air Plenum: Plenum
Return Air Location: Rear
Disconnect Switch: Disconnect Switch
Warranty
Warranty: Standard
AHRI Certification
All equipment is rated and certified in accordance with AHRI 440.
Notes
Sound Power (dB) measured in accordance with ANSI/AHRI Standard 260-2008.
Specification for DST Vertical Fancoil ALL
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 33 of 37 www.DaikinApplied.com
Specificati on for DST Verti cal Fancoil A LL
PART 1: GENERAL
1.01 SECTION INCLUDES
A. Horizontal Fan Coil
1.02 REFERENCES
A. Load Ratings and Fatigue Life for Ball Bearings.
B. Standards Handbook.
C. Laboratory Methods of Testing Fans for Rating Purposes.
D. Test Code for Sound Rating Air Moving Devices.
E. Test Methods for Louver, Dampers, and Shutters.
F. Room Fan Coil Unit.
G. Standard Practice for Operating Salt Spray Apparatus.
H. Motors and Generators.
I. National Electrical Code.
J. HVAC Duct Construction Standards - Metal and Flexible
K. Test for Surface Burning Characteristics of Building Materials.
L. Test Performance of Air Filter Units.
M. Standard for Heating and Cooling Equipment.
N. Test for Flammability of Plastic Materials for Parts in Devices and Appliances.
1.03 SUBMITTALS
A. Shop Drawings: Indicate assembly, unit dimensions, weight loading, required clearances, construction details, field
connection details, and electrical characteristics and connection requirements.
B. Product Data
1. Provide literature that indicates dimensions, weights, capacities, ratings, fan performance, gauges and finishes
of materials, and electrical characteristics and connection requirements.
1.04 OPERATION AND MAINTENANCE DATA
A. Maintenance Data: Include instructions for lubrication and filter replacement.
1.05 QUALIFICATIONS
A. Manufacturer: Company specializing in manufacturing Air Handler products specified in this section must show a
minimum five years documented experience and complete catalog data on total product.
1.06 DELIVERY, STORAGE, AND HANDLING
A. Deliver, store, protect and handle products to site.
B. Accept products on site wrapped in protective cardboard wrap. Inspect for damage.
C. Store in a clean dry place and protect from weather and construction traffic. Handle carefully to avoid damage.
1.07 ENVIORMENTAL REQUIREMENTS
A. Do not operate units for any purpose, temporary or permanent, until ductwork is clean, filters are in place,
bearings lubricated, and fan has been test run under observation.
PART 2: PRODUCTS
2.01 ACCEPTABLE MANUFACTURERS
A. The following manufacturers are approved for use. No substitutions.
1. Daikin Applied - 'ThinLine 3G' Fan Coil is the basis of design, including standard product features and all special
features required per plans and specifications.
Specification for DST Vertical Fancoil ALL
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 34 of 37 www.DaikinApplied.com
2. ETI
3. Greenheck
2.02 FAN COIL TYPE AND ARRANGEMENT
A. The fan coil shall be furnished as a draw-through cooling coil with a heating coil in preheat/reheat position.
2.03 GENERAL CONSTRUCTION
A. The units shall include a chassis, coil(s), fan deck with blower(s)/blower housing and motor(s). Steel parts exposed
to moisture shall be galvanized and insulated to prevent condensation. The complete fan assembly shall be easily
removable for service and maintenance. A quick-connect motor electric plug shall be provided.
B. Hideaway
1. Unit shall be supplied with return plenum complete with filter frame and filter. The plenum shall be fabricated
of 18 gauge galvanized steel. The inside plenum surface shall be insulated with 1/2" matt-faced fibergalss
insulation. Plenum insulation shall meet minimum K value of 0.24 (BTU-in)/(hr-ft2-F) and rated for maximum air
velocity of 5000 fpm. Fiberglass insulation conforms to:
a. a. ASTM C1071 (including C665)
b. b. UL 181 for erosion
c. c. 25/50 rating for flame spread/smoke developed per ASTM E-84, UL 723 and NFPA 90A
2.04 SUPPLY FAN
A. Supply fans shall be a DWDI forward-curved type. Fan assemblies including fan, motor and sheaves shall be
dynamically balanced by the manufacturer on all three planes at all bearing supports. Manufacturer must ensure
maximum fan RPM is below the first critical speed.
B. The complete fan assembly, including motor and main drain pan shall be easily removable.
C. Units shall be certified in accordance with the Room Fan Coil Unit certification program that is based on ARI
Standard 440.
D. An ECM blower motor shall be provided on all units. Factory motor wiring shall be set for optimum fan
performance. The unit shall be shipped at one fixed setting. The ECM motor shall utilize a permanent magnet rotor,
which is connected to the shaft through resilient rings to absorb high frequency torque ripple. ECM motor shall be
programmed for constant CFM or constant torque.
E. ECM blower motor shall be 3 speeds, single phase with means for proportional field adjustment of each speed.
2.05 ELECTRICAL
A. Supply fans shall be driven by permanent split-capacitor motors that are run-tested in the assembled unit and
permanently lubricated. All motors shall have integral thermal overload protection with a maximum ambient
operating temperature of 104°F. Motors shall be capable of starting at 78 percent of rated voltage and operating at
90 percent of rated voltage on all speed settings. Motors can operate up to 10 percent overvoltage.
B. Motor wires shall include a quick-disconnect motor plug.
2.06 COOLING AND HEATING
A. Cooling Coils
1. Cooling performance shall be as specified on the unit schedule.
2. Water coil fins shall have full drawn collars to provide a continuous surface cover over the entire tube for
maximum heat transfer. Seamless copper tubes shall be mechanically expanded into the fins to provide a
continuous primary-to-secondary compression bond over the entire finned length for maximum heat transfer
rates. Bare copper tubes shall not be visible between fins. Coil casing shall be constructed of galvanized steel.
3. Water coils shall be provided with headers of seamless copper tubing with intruded tube holes to permit
expansion and contraction without creating undue stress or strain. Coil connections shall be copper sweat
connections with connection size to be determined by manufacturer based upon the most efficient coil circuiting.
Specification for DST Vertical Fancoil ALL
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 35 of 37 www.DaikinApplied.com
Vent and drain connections shall be furnished on the coil connection, external to the cabinet. Vent connections
provided at the highest point to assure proper venting. Drain connections shall be provided at the lowest point.
4. All steel parts exposed to moisture shall be galvanized.
5. Unit shall include a noncorrosive, ABS main drain pan, positively sloped in every plane and insulated with
closed-cell insulation. The drain pan shall be designed to ensure no pooling of condensate water per ASHRAE 62.2.
2.07 VALVE PACKAGES
A. Fan coil units shall be provided with factory-installed valve / piping package(s)available for the primary and
secondary coils. All piping packages shall be factory assembled and tested at 400 psig (2760 kPa) and re-tested for
leak when factory soldered to the coil(s) at 300 psig (2069 kPa) Maximum Working Pressure of the piping package
shall be 300 psig (2069 kPa).
B. The valve package shall be designed so that any condensation is directed into the secondary drain pan. With the
secondary drain pan provided, insulation of the piping package is not required.
C. The valve package shall be provided with:
1. Interconnecting copper piping and shut-off ball valves.
2. Connecting supply and return lines to the unit. Four-pipe packages shall include a venting valve for the preheat
or reheat coil.
3. A manual circuit setter in the supply water pipe. The circuit setter acts as both a flow-setting device and a shut-
off valve. It allows water flow through the fan coil to be set quickly and accurately. The valve shall have a memory
stop so that the correct setting can be found quickly.
4. An automatic circuit setter. The circuit setter includes a cartridge within the valve body that is sized to allow a
specific flow rate through the coil. This valve sets flow through the coil without any action required by a system
piping balancer.
5. P/T ports to measure the temperature or pressure drop across the valve. This pressure drop can be compared
to factory-supplied curves that relate the pressure drop to a specific flow rate.
6. Unions at the coil connections.
7. A 20 mesh strainer on the supply side that is easily removed for cleaning, with a blow-off valve. The strainer
shall have a pressure rating of up to 400 psig (2,758 kPa).
8. Isolating ball valve on the supply side.
9. Balancing flow valve ( auto-fixed or manual) with isolating ball valve on the return.
10. Control valves in the supply water pipe.
11. Two-Way/Two-Position Valves that are fully open or fully closed in response to a line voltage (115 or 265-277
VAC) or a 24 VAC signal from the Daikin Applied thermostat or controller. Some means of relieving pump head
pressure should be accounted for when two-way valves are selected. Normally open or normally closed valves are
available. Both are spring-return.
12. Three-Way, Two-Position Valves that either allow full water flow through the coil or divert the flow through a
bypass line. The valves respond to a line voltage (115 or 265-277 VAC) or to a 24 VAC signal from the Daikin
Applied thermostat or controller. All standard three-way valves come with a fixed-balance orifice in the bypass line
to compensate for flow balancing in the bypass position, eliminating the need for an additional balancing valve.
Normally open or normally closed valves are available.
13. Two-Way Modulating Valves that modulate the water flow through the coil in response to a signal from the
Daikin Applied thermostat or controller. All standard Daikin Applied modulating valves are three-wire floating
point equal percentage valves. The modulating valves are factory mounted in the supply water pipe upstream of
the coil.
14. Three-Way Modulating Valves that modulate the water flow through the coil in response to a signal from the
Daikin Applied thermostat or controller. Three-way valves allow water that is directed through the coil to mix with
water that is directed through the bypass line. This mixture exits through the leaving water pipe. All modulating
valves are three-wire, floating-point equal percentage valves.
Specification for DST Vertical Fancoil ALL
Job Number: E21UYZ Page Prepared Date: 12/21/2018 Job Name: Spalding Hall 2nd Floor
Renovation 36 of 37 www.DaikinApplied.com
2.08 FILTERS
A. Filters shall be 1” (25 mm) throwaway. They shall be concealed from sight and easily removable.
2.09 CONTROLS
A. Unit shall be supplied with a DDC interface board.
B. DDC Interface board shall have three 24-volt relays with line-voltage contactors to operate the fan motor speeds.
C. DDC interface board shall have terminal connections for interfacing to:
1. Wall-Mounted Thermostat
2. Low-voltage, on-off valve actuators.
3. A return air sensor.
4. A pipe temperature sensor for changeover from heating to cooling on two-pipe systems.
5. Condensate overflow switch.
6. Room occupancy sensor.
PART 3: EXECUTION
3.01 INSTALLATION
A. The Thinline Fan Coil unit shall be installed per manufacturer's Installation & Maintenance Bulletin.
1. Selected field mounted kits shall be specified on the unit schedule and installed per manufacturer's instruction.
Document Summary Page
Fan Coils ScheduleLine
#
Tag Family Cab Size CFM ESP Motor Type HP Spec TotalFLA
C-Rws
Cool-EDB
Cool-EWB
Cool-Fluid
Cool-Temp
TotalBTU
SensibleBTU
Cool-LDB
Cool-LWB
Cool-LWT
Cool-GPM
Cool-Water
PD
KW H-Rws
Heat-EDB
Heat-Fluid
Heat-Temp
Total BTU Heat-LDB
Heat-LWT
Heat-GPM
Heat-Water
PD
1 FCU-1,4
Horizontal LH-R 006 475 0.20 ECM -Constant
Volume withUser Input
Speed Splits
1/3 120/1/60 5.0 6 80.00 67.00 Water 45.00 23,977 15,620 49.9 49.9 55.0 4.8 5.6 None 0 0.0 None 0.0 na na na na na
2 FCU-2 Horizontal LH-R 008 800 0.20 ECM -Constant
Volume withUser Input
Speed Splits
1/2 120/1/60 7.7 6 80.00 67.00 Water 45.00 33,893 23,556 53.1 53.1 55.0 6.8 2.0 None 0 0.0 None 0.0 na na na na na
3 FCU-3 Horizontal LH-R 004 300 0.20 ECM -Constant
Volume withUser Input
Speed Splits
1/3 120/1/60 5.0 6 80.00 67.00 Water 45.00 15,630 10,079 49.3 49.3 55.0 3.1 6.3 None 0 0.0 None 0.0 na na na na na
4 FCU-5,6
Horizontal LH-R 003 225 0.20 ECM -Constant
Volume withUser Input
Speed Splits
1/3 120/1/60 5.0 6 80.00 67.00 Water 45.00 9,987 6,813 52.3 52.3 55.0 2.0 0.9 None 0 0.0 None 0.0 na na na na na
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factory for current information. AHU OM-January 2012: Certified inaccordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 1 of 16
Fan Coils ScheduleSupplemental DataLine
#
Tag UOM MotCnt
BHP MinHP
RPM FLA MCA MOP MotorSpeed
MotorWatts
Velo-city
Altitude FinsPer In
TotalMCA
TotalMOP
C-CKT
EDP Cool-Delta T
Cool-%
Glycol
Refrig-erant
SST H-CKT
Heat-Delta T
Heat-%
Glycol
Heat-Flow
Heat-Conden-
sate
Elec.HeatBTU
Elec.HeatFLA
Elec.HeatMCA
Elec.HeatMOP
ShpngWt
OprWt
UserAppvl
1 FCU-1, 4 Standard 1 0.0 na 0.0 5.0 6.25 15.0 High Speed 600 284 0.0 12 6.25 15.0 3 60.4 10.0 0 None 0.0 0 0.0 0 na na na 0.0 0.0 15.0 186 154 LowLeaving
AirTemperature
Approved
2 FCU-2 Standard 1 0.0 na 0.0 7.7 9.625 15.0 High Speed 924 411 0.0 12 9.625 15.0 6 60.4 10.0 0 None 0.0 0 0.0 0 na na na 0.0 0.0 15.0 206 170 LowLeaving
AirTemperature
Approved
3 FCU-3 Standard 1 0.0 na 0.0 5.0 6.25 15.0 High Speed 600 240 0.0 12 6.25 15.0 2 60.4 10.0 0 None 0.0 0 0.0 0 na na na 0.0 0.0 15.0 167 133 LowLeaving
AirTemperature
Approved
4 FCU-5, 6 Standard 1 0.0 na 0.0 5.0 6.25 15.0 High Speed 600 240 0.0 12 6.25 15.0 3 60.4 10.0 0 None 0.0 0 0.0 0 na na na 0.0 0.0 15.0 140 105 LowLeaving
AirTemperature
Approved
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factory for current information. AHU OM-January 2012: Certified inaccordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 2 of 16
Performance Summary - Unit 1 , FCU-1, 4
84571-1 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, RightHand, 6R3C Cool (LH-R006W2R601R000) The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.
Performance Calculations are at an altitude of 0.0 feet Unit Application User Approvals: Low Leaving Air Temperature Approved
Fan Performance
Motor Voltage:
120/1/60
Motor Type:
ECM - Constant Volume with User InputSpeed Splits
External Static:
0.20 InWC
Airflow at High Speed: 475 cfm
Cooling Coil Performance - 6 rows, 3 circuit, 12 fins/inch Entering Dry Bulb:Entering Wet Bulb:Fluid Type:
80.00 oF67.00 oFWater
Leaving Dry Bulb:Leaving Wet Bulb:Flow Rate:
49.9 oF49.9 oF4.8 GPM
Entering Fluid Temp:EAT Dew Point:
45.00 oF60.4 oF
Leaving Fluid Temp:Fluid Pressure Drop:
55.0 oF5.6 FtWC
Total Cooling Capacity:
23,977 BTUH
Sensible Cooling Capacity:
15,620 BTUH
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 3 of 16
Base Unit Summary - Unit 1 , FCU-1, 484571-1 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, Right Hand, 6R3C Cool (LH-R006W2R601R000)
The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.
Unit Application - Fan CoilCabinet Style (Model) - Horizontal Ceiling Concealed with Plenum(LH-R) Unit Size - 006 Sales Program - Standard System Type - Cool Only System Configuration - 2-pipe Hydronic Motor Type - ECM - Constant Volume with User Input Speed Splits Motor Voltage/Freq/Phase - 120/1/60 Motor Count - 1
Supply - Front Ducted Return - Rear Ducted Wall Type - Single Wall Insulation - 1/2" Fiberglass Finish - GalvanizedMotor Watts - 600
Filter Type - Pleated - 2 inch - MERV 8 Rated Hand - Right Electrical Hand - LeftCooling Rows Deep - 6 Cooling Circuiting - 3 Cooling Air Vent - Manual Fins Per Inch - 12 Fin/Casing Material - Aluminum/Galvanized
Drain Pan - Stainless Shipping Weight - 186 lbsOperating Weight - 154 lbs
Cooling Coil Connection Size: 1/2 Heating Coil Connection Size: na
Unit Revision Level - B
Filter Access - Bottom Circuit Wiring - Single Power Source
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 4 of 16
Standard Drawing - Unit 1 , FCU-1, 4 84571-1 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, Right Hand, 6R3C Cool (LH-R006W2R601R000)
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 5 of 16
Performance Summary - Unit 2 , FCU-2
84571-2 Horizontal Ceiling Concealed with Plenum (LH-R) - 008, 120/1/60, 6/0 Coil, RightHand, 6R6C Cool (LH-R008W2R601R000) The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.
Performance Calculations are at an altitude of 0.0 feet Unit Application User Approvals: Low Leaving Air Temperature Approved
Fan Performance
Motor Voltage:
120/1/60
Motor Type:
ECM - Constant Volume with User InputSpeed Splits
External Static:
0.20 InWC
Airflow at High Speed: 800 cfm
Cooling Coil Performance - 6 rows, 6 circuit, 12 fins/inch Entering Dry Bulb:Entering Wet Bulb:Fluid Type:
80.00 oF67.00 oFWater
Leaving Dry Bulb:Leaving Wet Bulb:Flow Rate:
53.1 oF53.1 oF6.8 GPM
Entering Fluid Temp:EAT Dew Point:
45.00 oF60.4 oF
Leaving Fluid Temp:Fluid Pressure Drop:
55.0 oF2.0 FtWC
Total Cooling Capacity:
33,893 BTUH
Sensible Cooling Capacity:
23,556 BTUH
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 6 of 16
Base Unit Summary - Unit 2 , FCU-284571-2 Horizontal Ceiling Concealed with Plenum (LH-R) - 008, 120/1/60, 6/0 Coil, Right Hand, 6R6C Cool (LH-R008W2R601R000)
The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.
Unit Application - Fan CoilCabinet Style (Model) - Horizontal Ceiling Concealed with Plenum(LH-R) Unit Size - 008 Sales Program - Standard System Type - Cool Only System Configuration - 2-pipe Hydronic Motor Type - ECM - Constant Volume with User Input Speed Splits Motor Voltage/Freq/Phase - 120/1/60 Motor Count - 1
Supply - Front Ducted Return - Rear Ducted Wall Type - Single Wall Insulation - 1/2" Fiberglass Finish - GalvanizedMotor Watts - 924
Filter Type - Pleated - 2 inch - MERV 8 Rated Hand - Right Electrical Hand - LeftCooling Rows Deep - 6 Cooling Circuiting - 6 Cooling Air Vent - Manual Fins Per Inch - 12 Fin/Casing Material - Aluminum/Galvanized
Drain Pan - Stainless Shipping Weight - 206 lbsOperating Weight - 170 lbs
Cooling Coil Connection Size: 1/2 Heating Coil Connection Size: na
Unit Revision Level - B
Filter Access - Bottom Circuit Wiring - Single Power Source
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 7 of 16
Standard Drawing - Unit 2 , FCU-2 84571-2 Horizontal Ceiling Concealed with Plenum (LH-R) - 008, 120/1/60, 6/0 Coil, Right Hand, 6R6C Cool (LH-R008W2R601R000)
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 8 of 16
Performance Summary - Unit 3 , FCU-3
84571-3 Horizontal Ceiling Concealed with Plenum (LH-R) - 004, 120/1/60, 6/0 Coil, RightHand, 6R2C Cool (LH-R004W2R601R000) The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.
Performance Calculations are at an altitude of 0.0 feet Unit Application User Approvals: Low Leaving Air Temperature Approved
Fan Performance
Motor Voltage:
120/1/60
Motor Type:
ECM - Constant Volume with User InputSpeed Splits
External Static:
0.20 InWC
Airflow at High Speed: 300 cfm
Cooling Coil Performance - 6 rows, 2 circuit, 12 fins/inch Entering Dry Bulb:Entering Wet Bulb:Fluid Type:
80.00 oF67.00 oFWater
Leaving Dry Bulb:Leaving Wet Bulb:Flow Rate:
49.3 oF49.3 oF3.1 GPM
Entering Fluid Temp:EAT Dew Point:
45.00 oF60.4 oF
Leaving Fluid Temp:Fluid Pressure Drop:
55.0 oF6.3 FtWC
Total Cooling Capacity:
15,630 BTUH
Sensible Cooling Capacity:
10,079 BTUH
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 9 of 16
Base Unit Summary - Unit 3 , FCU-384571-3 Horizontal Ceiling Concealed with Plenum (LH-R) - 004, 120/1/60, 6/0 Coil, Right Hand, 6R2C Cool (LH-R004W2R601R000)
The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.
Unit Application - Fan CoilCabinet Style (Model) - Horizontal Ceiling Concealed with Plenum(LH-R) Unit Size - 004 Sales Program - Standard System Type - Cool Only System Configuration - 2-pipe Hydronic Motor Type - ECM - Constant Volume with User Input Speed Splits Motor Voltage/Freq/Phase - 120/1/60 Motor Count - 1
Supply - Front Ducted Return - Rear Ducted Wall Type - Single Wall Insulation - 1/2" Fiberglass Finish - GalvanizedMotor Watts - 600
Filter Type - Pleated - 2 inch - MERV 8 Rated Hand - Right Electrical Hand - LeftCooling Rows Deep - 6 Cooling Circuiting - 2 Cooling Air Vent - Manual Fins Per Inch - 12 Fin/Casing Material - Aluminum/Galvanized
Drain Pan - Stainless Shipping Weight - 167 lbsOperating Weight - 133 lbs
Cooling Coil Connection Size: 1/2 Heating Coil Connection Size: na
Unit Revision Level - B
Filter Access - Bottom Circuit Wiring - Single Power Source
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 10 of 16
Standard Drawing - Unit 3 , FCU-3 84571-3 Horizontal Ceiling Concealed with Plenum (LH-R) - 004, 120/1/60, 6/0 Coil, Right Hand, 6R2C Cool (LH-R004W2R601R000)
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 11 of 16
Performance Summary - Unit 4 , FCU-5, 6
84571-5 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, RightHand, 6R3C Cool (LH-R006W2R601R000) The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.
Performance Calculations are at an altitude of 0.0 feet Unit Application User Approvals: Low Leaving Air Temperature Approved
Fan Performance
Motor Voltage:
120/1/60
Motor Type:
ECM - Constant Volume with User InputSpeed Splits
External Static:
0.20 InWC
Airflow at High Speed: 225 cfm
Cooling Coil Performance - 6 rows, 3 circuit, 12 fins/inch Entering Dry Bulb:Entering Wet Bulb:Fluid Type:
80.00 oF67.00 oFWater
Leaving Dry Bulb:Leaving Wet Bulb:Flow Rate:
52.3 oF52.3 oF2.0 GPM
Entering Fluid Temp:EAT Dew Point:
45.00 oF60.4 oF
Leaving Fluid Temp:Fluid Pressure Drop:
55.0 oF0.9 FtWC
Total Cooling Capacity:
9,987 BTUH
Sensible Cooling Capacity:
6,813 BTUH
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 12 of 16
Base Unit Summary - Unit 4 , FCU-5, 684571-5 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, Right Hand, 6R3C Cool (LH-R006W2R601R000)
The Horizontal with Return-Air Plenum fan coil is ideal for mounting above ceilings inclosets hallways and bathroom areas. The plenum conceals the unit's blower motor which iseasily accessible for service by removing the bottom panel.
Unit Application - Fan CoilCabinet Style (Model) - Horizontal Ceiling Concealed with Plenum(LH-R) Unit Size - 003 Sales Program - Standard System Type - Cool Only System Configuration - 2-pipe Hydronic Motor Type - ECM - Constant Volume with User Input Speed Splits Motor Voltage/Freq/Phase - 120/1/60 Motor Count - 1
Supply - Front Ducted Return - Rear Ducted Wall Type - Single Wall Insulation - 1/2" Fiberglass Finish - GalvanizedMotor Watts - 600
Filter Type - Pleated - 2 inch - MERV 8 Rated Hand - Right Electrical Hand - LeftCooling Rows Deep - 6 Cooling Circuiting - 3 Cooling Air Vent - Manual Fins Per Inch - 12 Fin/Casing Material - Aluminum/Galvanized
Drain Pan - Stainless Shipping Weight - 140 lbsOperating Weight - 105 lbs
Cooling Coil Connection Size: 1/2 Heating Coil Connection Size: na
Unit Revision Level - B
Filter Access - Bottom Circuit Wiring - Single Power Source
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 13 of 16
Standard Drawing - Unit 4 , FCU-5, 6 84571-5 Horizontal Ceiling Concealed with Plenum (LH-R) - 006, 120/1/60, 6/0 Coil, Right Hand, 6R3C Cool (LH-R006W2R601R000)
Company: normanwrightwaipahu Project Name: Spalding Hall 2nd floor renovations ,Honolulu ,Hawaii
Proposal: 84571 Date: 12-21-2018
Information contained herein are not express warranties nor do they constitute an agreement between the parties. Williams ® may change the design and product specifications at anytime. Contact the factoryfor current information. AHU OM-January 2012: Certified in accordance with the AHRI Central Station Air-Handling Unit Certification Program, which is based on the AHRI standard430. Certified units may befound in the AHRI Directory at www.ahridirectory.org. Rating version number: 2.01
Page 14 of 16