58
AMENDMENT No. 2 TO TENDER DOCUMENTS Tender No.: RITES/CO/B&A/EE/DTEH-Rohtak –Air Cooled Chiller System of HVAC work S.No. Clause of tender Page No. Description Amended & to be read as 1 Part –I Annexure –I Similar work (a) 25 a) Similar works shall mean the work of: “Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.” a) Similar works shall mean the work of: “Supply, Installation, and Testing & Commissioning of HVAC work with air cooled/ water cooled chilled system. 2 Part-I Compressor Capacity Control 98 Microprocessor activated slide valve, controlled by external solenoid valves via micro-computer control panel, fully modulating control from 100% to 15% of the capacity for Chillers less than 70 TR capacity and 100% to 7.5% for Chillers more than 70 TR capacity. Microprocessor activated slide valve, controlled by external solenoid valves via micro-computer control panel, fully modulating control from 100% to 25% of the capacity for Chillers 3 Part-I Part –II BOQ Item No. 1.a & 1.b 97-100 11-12 Technical Specifications A. HELICAL ROTARY SCREW TYPE WATER CHILLER The technical specification of air cooled screw chiller machine / Scroll machine given in the tender are for the reference of the bidders. However the air cooled machine/scroll machine is acceptable as per manufacturer standard of approved make specified in the tender. 4 Part- I 7 2. Scope of work -Building Management System complete with Automatic controls and instruments. 2. Scope of work -All HVAC equipments shall be BMS compatible. Provision of BMS System is not covered in scope of work. 5 Part-II 11- 53 Bill of quantities Revised Bill of quantities as per Annexure – “A” to this amendment.

AMENDMENT No. 2 TO TENDER DOCUMENTS Tender No.: RITES…€¦ · Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film

Embed Size (px)

Citation preview

AMENDMENT No. 2 TO TENDER DOCUMENTS Tender No.: RITES/CO/B&A/EE/DTEH-Rohtak –Air Cooled Chiller System of HVAC work S.No. Clause of tender Page No. Description Amended & to be read as 1 Part –I Annexure

–I Similar work (a)

25 a) Similar works shall mean the work of: “Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.”

a) Similar works shall mean the work of: “Supply, Installation, and Testing & Commissioning of HVAC work with air cooled/ water cooled chilled system.

2 Part-I Compressor Capacity Control

98 Microprocessor activated slide valve, controlled by external solenoid valves via micro-computer control panel, fully modulating control from 100% to 15% of the capacity for Chillers less than 70 TR capacity and 100% to 7.5% for Chillers more than 70 TR capacity.

Microprocessor activated slide valve, controlled by external solenoid valves via micro-computer control panel, fully modulating control from 100% to 25% of the capacity for Chillers

3 Part-I Part –II BOQ Item No. 1.a & 1.b

97-100 11-12

Technical Specifications A. HELICAL ROTARY SCREW TYPE WATER CHILLER

The technical specification of air cooled screw chiller machine / Scroll machine given in the tender are for the reference of the bidders. However the air cooled machine/scroll machine is acceptable as per manufacturer standard of approved make specified in the tender.

4 Part- I 7 2. Scope of work -Building Management System complete with Automatic controls and instruments.

2. Scope of work -All HVAC equipments shall be BMS compatible. Provision of BMS System is not covered in scope of work.

5 Part-II 11- 53 Bill of quantities Revised Bill of quantities as per Annexure –“A” to this amendment.

6 The following has been added to the tender:

1 . The several documents forming the contract are to be taken as mutually explanatory on one another, detailed drawings being followed in preference to small scale drawings.

1.1 In case of discrepancy between Bill of quantities , the specification and/ or the drawings, the following order of preference shall be observed: i) Description of Bill of Quantities ii) Specific Conditions and technical specifications and special condition if any iii) Drawings iv) CPWD specification v) Indian Standard Specification of BIS

7 As per

amendment No.1 Date of tender submission: 1400 Hrs. on

23.12.2010 Date of tender Opening : 1430 Hrs. on 23.12.2010

Date of tender submission: 1400 Hrs. on 10.01.2011 Date of tender Opening : 1430 Hrs. on 10.01.2011

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

1.a

i)

ii)

iii)

QUOTED

UNIT RATE

Chiller CHW IN - 12.2 º C / 54.0 º F CHW OUT - 6.67 º C / 44.00 º F Fouling Factor - 0.0001 FPS

IkW/ TR of the Air cooled screw chiller at full loadshall not be more than 1.4

Condenser Air Temp. - 43.3º C./ 110.0 º F

Supply, installation, testing and commissioningof Air CooledScrew Water Chilling M/C following capacity at belowmentioned operating conditions with R-134a refrigerant,Multiple semihermetic/Open compressors & circuits, drivenby suitable KW Sq. Cage induction motor complete with aircooled condenser,Electronic ExpansionValve, insulated shelland tube flooded chiller with victaulic coupling, DP flowswitches in chiller, refrigerant piping, Refrigerant and gas andOil (First Charge), Microprocessor based control panel,factory mounted, motor starter & accessories etc. all mountedon M.S. frame. Motor shall be highly efficient and suitablefor 415 volts ± 10%,50Hz ± 5 %, three phase A.C. supply.

SUB HEAD 'A' MACHINERY

ITEM OF WORK

FASHION DESIGN

As the performance of the chillers mentioned hereindoes not fall under the ARI/Eurovent certificationprogram so the chiller shall be tested in the factors andthe performance test shall be witnessed byRITES/DTHrepresentatives as per procedure laid downby ARI/Eurovent at four point loads at tender designconditions.

The chiller shall be able to provide 25% to 100%stepless capacity control

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

iv)

v)

vi)

Nos 3

1.b

i)

ii)

CHW OUT - 6.67 º C / 44.00 º F

Condenser Air Temp. - 43.3º C./ 110.0 º F Chiller CHW IN - 12.2 º C / 54.0 º F

a) 529200 Kcal/hr (175 TR) (2W + 1S)

The Chiller shall be able to provide mimimun 3 stepscapacity control.

The System should be compatible with the BMS systemand having the facility to perform the function thruBMS viz remote chiller start and stop, remote leavingchiller liquid temperature adjustment, remote currentlimit setpoint, remote ready to start contacts, safetyshutdown contacts, run contacts

Supply, installation, testing and commissioningof Air CooledScroll Water Chilling M/C following capacity at belowmentioned operating conditions with R410a refrigerant,hermetic, Multiple Scroll compressor unit(s), Air cooledcondenser, insulated evaporator, Electronic Expansion Valve,integral refrigerant piping and wiring, flow swtiches,accessories as required and called for, automatic and safetycontrols mounted in central control panel and all mounted onframe complete. Motor shall be suitable for 415±10% volts,50 cycles/second, 3 phase AC supply.

The chilling machine as described above shall be asper specifications.

(The system shall be complete in all respects vizlubrication sytem, evaporator, condenser coil,refrigerent sytem, controller, communication port forBMS).

Fouling Factor - 0.0001 FPSIkW/ TR of the Air cooled screw chiller at full loadshall not be more than 1.7.

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

iii)

iv)

As the performance of the chillers mentioned hereindoes not fall under the ARI/Eurovent certificationprogram so the chiller shall be tested in the factors andthe performance test shall be witnessed by customersrepresentatives as per procedure laid down byARI/Eurovent at four point loads at tender designconditions.

The System should be compatible with the BMS systemand having the facility to perform the function thruBMS viz remote chiller start and stop, remote leavingchiller liquid temperature adjustment, remote currentlimit setpoint, remote ready to start contacts, safetyshutdown contacts, run contacts

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

v)

vi)

Nos 2

2

i)

ii)

iii)

iv)

v)

vi)

Nos. 3

Nos. 2

b) 136080 Kcal/hr (45 TR) (1W + 1S)

(The system shall be complete in all respects vizlubrication sytem, evaporator, condenser coil,refrigerent sytem, controller, communication port forBMS).

The chilling machine as described above shall be asper specifications.

b) Flow rate 410 LPM/head 20 m (1W+1SB)

Supply, installation, testing and commissioning of chilled water pump set each capable of delivering the specified flow rate comprising the following and complete as per specifications.

Lot, thermal insulation on the pump.

a) Flow rate 1820 LPM/head 25 m (2W+1SB)

Lot, concrete foundation for the pump.

2 Nos. 150 mm dia dial type pressure gauges.

Lot, anti-vibration pads, channel base, coupling,coupling guard, suction guide, etc.

1 No. suitable HP TEFC induction motor with class `F'insulation operating on 415 + 10% volts, 3 phase, 50cycles AC supply.

1 No. end section, vertical split casing, centrifugalpump.

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

2.A

a No. 3.00

b No. 2.00

Hot Water PumpsSupply, installation, testing and commissioning of Hotwater pump set each capable of delivering the specifiedflow rate comprising the following and complete as perspecifications.I) 1 No. monoblok pump.II) 1 No. suitable HP TEFC induction motor with class`F' insulation operating on 415 + 10% volts, 3 phase, 50cycles AC supply.III) Lot, thermal insulation on the pump.IV) 2 Nos. 150 mm dia dial type pressure gauges.V) Lot, anti-vibration pads, channel base, coupling,coupling guard, suction guide, etc.VI) Lot, concrete foundation for the pump.

Flow rate 100 LPM/head 20 m 2 Nos. (1W+1SB)

Flow rate 450 LPM/head 25 m 3 Nos. (2W+1SB)

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

3.0

S.No. Tag No. Cooling Load (TR) Each De-humidified Air Qty. (CFM)

Chilled water coil (Row)

3.1 AHU-1.1-A&B 8.8 5000 4 Nos. 2

3.2 AHU-2.1-A&B 7.3 4050 4 Nos. 2

3.3 AHU-3.1-A&B 7.3 4050 4 Nos. 2

3.4 AHU-4.1-A&B 13.5 7000 4 Nos. 2

GROUND FLOOR

The face velocity across cooling coil shall be limited to 152MPM maxm. The capacity of Air-handlers shall be as follows:

Supply, installation, testing and commissioning offactory built, cabinet type, horizontal/vertical, floormounted/ceilingsuspendedbelt driven air handling unitsin double skin construction of following capacity atrequired static pressure of 40 mm complete with factoryfabricated independent sections, housing the variouscomponents e.g. blower, TEFC blower motor suitablefor operation on 415 + 10% volts, 3 phase, 50 Hz ACsupply, copper tube, aluminium finned chilled watercooling coil, thermostat and control wiring etc., prefilter sets, drain connections and concrete foundationwith anti-vibration mountingsetc. as required and as per"Schedule of equipment" and specifications.

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

3.5 AHU-1.2-A&B 8.4 4700 4 Nos. 2

3.6 AHU-2.2-A&B 6.8 3700 4 Nos. 2

3.7 AHU-3.2-A&B 6.8 3700 4 Nos. 2

3.8 AHU-4.2-A&B 5.9 3200 4 Nos. 2

3.9 AHU-5.2-A&B 5.9 3200 4 Nos. 2

3.10 AHU-1.3-A&B 8.4 4700 4 Nos. 2

3.11 AHU-2.3-A&B 9.2 5125 4 Nos. 2

3.12 AHU-3.3-A&B 8.9 4925 4 Nos. 2

3.13 AHU-4.3-A&B 9.3 5225 4 Nos. 2

3.14 AHU-5.3-A&B 6.8 3700 4 Nos. 2

3.15 AHU-6.3-A&B 6.8 3700 4 Nos. 2

3.16 AHU-7.3-A&B 5.9 3200 4 Nos. 2

SECOND FLOOR

FIRST FLOOR

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

3.17 AHU-8.3-A&B 5.9 3200 4 Nos. 2

3.18 AHU-9.3-A&B 6.1 3400 4 Nos. 2

3.19 AHU-1.4-A&B 21.6 12000 4 Nos. 2

3.20 AHU-2.4-A&B 7.9 4425 4 Nos. 2

3.21 AHU-3.4-A&B 8.5 4825 4 Nos. 2

3.22 AHU-4.4-A&B 8.3 4650 4 Nos. 24.0 Supply and installation and commissioning of ceiling

concealed fan coil units including air - filter ball valveset with strainer, 2 way diverting valve with snap actingheat-cool thermostat as per drawing flexible electricalwiring necessaryconnection for chilled hot water supplyand return line coling heating coil with mechanicallyexpanded copper tube and aluminiumfins statically anddynamically balanced centrifugal forward curvealuminium blower 3 speed mortor suitable for 220(±.)10% V supply complete with stainless steel drain panduly insulated sheet metal casing of heavy gauge steelincluding flanges canvas connection as required. FCU'sare to be powder coated and the noice level shall lessthan 40 Db at AC unit outlet and as per specification.

THIRD FLOOR

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

S.No. TAG No. Cooling Load (TR) Each

4.1 FCU-1.1-6.1 1.5 Nos. 6

5.0

i) Nos. 24

6.0

a i) Nos. 1

b i) Nos. 1

Supply, installation, testing and commissioningof long casingtube axial fan with adjustable pitched aluminium alloyimpeller, TEFC squirrel cage induction motor with class 'H/F'insulation high temprature resistance and flame proof, directdrive arrangement, variable frequency drive, sheet metalcasing, rubber isolator mounts and other accessories as perspecified and of following capacities as per Schedule ofEquipment.

Smoke spill application (exhaust fans) suitable for 250ºCoperating temperature for 120 minutes as per standard BS7346 Part-II-1990, Class-B and tested by an independent firelaboratory.

Supply air fan with class 'F' insulation with PR-12 epoxycoating suitable for normal application and AMCA certifiedfor air and sound levels.

76500 CMH at SP at 20mm WG, 1440 rpm, (Forbasment Fr. Air supply)

76500 CMH at SP at 10mm WG, 1440 rpm,(Forbasment exhaust)

Supply, installation, testing and commissioning, of ductmounted Inline fans complete with direct driven centrifugalfan, TEFC squirrel cage induction motor, direct drivearrangement, heavy gauge sheet metal casing, rubber isolatormounts and other accessories. Inline fans shall be of followingcapacities:

400 CFM at SP of 20 mm WG

GROUND FLOOR

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

ii) Nos. 1

7.0

a Nos. 3

bNos. 2

1.0

5100 CMH at SP at 10mm WG, 1440 rpm, (For lift wellpressurisation)

TOTAL OF SUB HEAD `A’ MACHINERY CARRIED OVER TO SUMMARY

SUB-HEAD 'B' PIPING

Capacity 35 KW 2 No. (1W+1SB)

Exposed Pipes

Supply, laying/fixing,testing and commissioning of followingsizes of chilled water MS ERW heavy class piping confirmingto IS code with necessary clamps, supports, anti-vibrationmountings, hangers and fittings such as bends, tees, reducersetc. (but excluding valves, strainers, gauges, etc.) dulyinsulated with factoryremoulded section of polyurethanefoamwith wire mesh and coated with sand and cement plaster as perspecifications.

Capacity 150 KW 3 Nos. (2W+1SB)

Supply, Installation, testing and commissioning of outdoor type Electric Hot Water Generator of following capacity conforming to BIS standards and hot water in let/ out let temperature of 45/50oC complete as per specifications with following accessories.i) Matching electrical immersion heater banks.ii) All automatic and safety controls such as manual reset, high temperature cut off, step controller and recycling relay, thermostats, pilot light, low water cut off and other controls.iii) Electrical panel mounted on generator frame complete with internal wiring, contractors, switches, etc.iv) Interconnecting cables between panel and heaterv) Concrete foundation for Hot Water Generatorvi) Water Temp. in °C 45 Water Temp. Out °C50

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

i) 200 mm dia M 70

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

ii) 150 mm dia M 35

iii) 125 mm dia M 50

iv) 100 mm dia M 150

v) 80 mm dia M 650

vi) 65 mm dia M 370

vii) 50 mm dia M 390

viii) 40 mm dia M 270

ix) 32 mm dia M 350

x) 25 mm dia M 50

xi) 20 mm dia M 70

2.0

a)

i) 125 mm dia No 3

Supply, installation, testing and commissioning of followingvalves, strainers, in the chilled water piping complete withcompanionflanges, nuts, bolts, gaskets, supports, etc. and dulyinsulated and painted as per specifications.

Motorised Butterfly Valve

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

ii) 80 mm dia No 2

b)

i) 65 mm dia No 2

ii) 50 mm dia No 2

iii) 40 mm dia No 32

iv) 32 mm dia No 10

v) 20 mm dia No 6

c)

i) 200 mm dia No 2

ii) 125 mm dia No 12

iii) 80 mm dia No 8

iv) 65 mm dia No 4

v) 50 mm dia No 4

2 way Chilled water Dynamic cum modulating Valve

Butterfly Valves

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

vi) 40 mm dia No 64

d)

i) 125 mm dia No 6i) 80 mm dia No 4

e)

i) 125 mm dia No 3ii) 80 mm dia No 2

f)

i) 65 mm dia No 2

ii) 50 mm dia No 2iii) 40 mm dia No 32

g)

i) 10 mm dia No 50

h)

i) 32 mm dia No 12

Balancing Valves

Non Return Valves

Y'-Strainer

Auto Air Vent Valves

G M Gate Valve

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

ii) 25 mm dia No 30

i)

i) 32 mm dia No 10

ii) 20 mm dia No 6

j)

i) 32 mm dia No 10

ii) 20 mm dia No 6

k)

i) 9.4 mm Bulb Dia) No 108

l)

i) 100 mm dial No 108

Dial type pressure gauge Range: (0 - 7 Kg/cm2)

Ball Valve without Strainer

Stem typeTemperature gauge Range (0 - 500C)

Ball Valve with Strainer

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

3.0 No 1

1.0

i) Sqm 25

ii) Sqm 30

iii) Sqm 272

iv) Sqm 1686

2.0 Sqm 175

Supply, installation, testing and balancing of factory fabricated rectangular GSS ducting of following thicknessincluding necessary supports, hangers, nut bolts, gaskets,splitter dampers, vanes, canvas connections etc. complete asper specifications.

Supply and fixing acoustic lining of 15 mm thick engineeredestastomeric open cell nitrile rubber slab on the inner side ofducting as per specifications for ducts are required.

0.63 mm

TOTAL OF SUB HEAD 'B' PIPING CARRIED OVER

1.25 mm

SUB-HEAD 'C' DUCTING AND GRILLES

0.8 mm

Supply, installation, testing and commissioning, of MSexpansion tank of size 1.2m x 1.2 m x 1.2 m height, made of3 mm thick mild steel sheet complete with insulation, vent andcontrol valves, air vent, manhole cover, final painting etc.

1.00 mm

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

3.0 Sqm 2000

4.0 Sqm 7

5.0 Sqm 5

6.0 Sqm 4

7.0 Sqm 1

8.0 Sqm 160

9.0 Sqm 2

10.0 Sqm 2

11.0 Sqm 994

Supply, installation, testing and commissioning of powdercoated extruded aluminium supply air Continuous grilles ofvarious sizes, with vcd complete as per specifications .

Supply, installation, testing and commissioning of GI multi-leaf motorised fire dampers complete with chrome platedspindles in self lubricated bronze bushes, linkages, actuatormotor, limit switch, wiring etc. complete as per specifications.

Supply, installation, testing and commissioning ofsquare/rectangularpowder coated extruded aluminium supply air jet diffusers of various sizes with volume controldampers, and complete as per specifications.

Supply, installation, testing and balancing of box type GIvolume control damper complete as per specifications

Supply, installation, testing and commissioning of powdercoated extruded aluminium fresh air louvers with aluminiumbird screen and volume control damper as per specifications.

Supply and installation of powder coated extruded aluminiumlouvers complete with bird screen as per specifications.

Supply and fixing of underdeck roof insulation and thermalinsulation on wall with 40mm thick polyisocyanuratemachinecut shiplap joint slabs prelaminated with 0.05mm aluminiumfoil etc.as per specifications

Supply, installation, testing and commissioning ofsquare/rectangular powder coated extruded aluminiumreturn/exhaust air diffusers of various sizes completewithout volume control dampers, and as per specifications.

Supply and fixing of 15 mm thick chemically crosslinked,closed cell polyethylene FR-XPE retardant gradeinsulation on supply/return air duct as per specifications.

SR. NO.

UNIT QUANTITY

AMOUNTIn Figures (Rs.) In Words (Rs.) In Figures(Rs.)

QUOTED

UNIT RATE

ITEM OF WORK

FASHION DESIGN

TOTAL OF SUB HEAD `C’ DUCTING & GRILLES CARRIED OVER TO SUMMARY

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

1.0 CABLES1.1 Supply, storing, handling, laying, testing and commissioning

of 1100 Volt grade XLPE insulated and sheathed aluminiumconductor armoured cables including the cost of providingrequired gap between adjacent cables (minimum one cabledia.) and including the cost of providing identification tags inshaft/ cable trays etc. complete as per specification, asrequired (Low losses).

a 3.5 C x 240 Sq.mm cable RM 500

b 3.5 C x 150 Sq.mm cable RM 50

c 3.5 C x 120 Sq.mm cable RM 300

d 3.5 C x 35 Sq.mm cable RM 300

e 4C x 25 Sq.mm cable RM 300

f 4C x 16 Sq.mm cable RM 700

g 4c x 6 sqmm RM 50

h 4c x 4 sqmm RM 50

1.2 Cable Termination

QUOTED

UNIT RATE

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

Supply, storing, handling, laying, testing and commissioningof 1100 Volt grade PVC insulated and sheathed aluminiumconductor unarmoured cables including the cost of providingrequired gap between adjacent cables (minimum one cabledia.) and including the cost of providing identification tags inshaft/ cable trays etc. complete as per specification, asrequired (Low losses).

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

a 3.5 C x 240 Sq.mm cable Nos 16

b 3.5 C x 150 Sq.mm cable Nos 4

c 3.5 C x 120 Sq.mm cable Nos 12

d 3.5 C x 35 Sq.mm cable Nos 16

e 4C x 25 Sq.mm cable Nos 12

f 4C x 16 Sq.mm cable Nos 24

g 4c x 6 sqmm Nos 70

h 4c x 4 sqmm Nos 21.3 Control Cables :

Supplying, receiving, storing, laying, effecting proper

connections, testing and commissioning of the following

sizes of 1.1 KV grade PVC insulated and sheathed copper

conductor armoured stranded control cable complete with

saddles, clamps etc. as required and as per specifications.a 2 Core x 2.5 Sq.mm Cable RM 1500

b 4 Core x 2.5 Sq.mm Cable RM 200

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

c 7 Core x 2.5 Sq.mm Cable RM 100

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

1.4 Control Cables termination:Supplying and making of control cable terminations for

control cables as per item 8.0 above complete with brass

plated single compression glands, copper lugs etc. as

required:2 Core x 2.5 Sq.mm Cable Nos. 60

4 Core x 2.5 Sq.mm Cable Nos. 8

7 Core x 2.5 Sq.mm Cable Nos. 4

1.5 Cable Trays (Ladder Type):Supply, fabrication and installation of Hot dip galvanized factory fabricated ladder type cable trays complete with all fabricated bends, tees,nuts bolts ,dash fasteners, elbows, reducers, offsets etc & required hardware. with rungs at every250 mm spacing (c/c) of various width in two tier/three/five tier fashion either on one side of the wall or on two sides of the wall or at other places and paint afterward if required. (All bends & tees shall be of factory built-in of same make as that of tray)

a 75mm x 1200mm x 75mm x 3mm wide cable tray with rungs

of 20mm x 40mm x 20mm

RM 10

b 75mm x 750mm x 75mm x 3mm wide cable tray with rungs

of 20mm x 40mm x 20mm

RM 50

c 50mm x 600mm x 50mm x 2mm wide cable tray with rungs of 15mm x 30mm x 15mm

RM 200

d 50mm x 300mm x 50mm x 2mm wide cable tray with rungs of 15mm x 30mm x 15mm

RM 30

e 50mm x 150mm x 50mm x 2mm wide cable tray with rungs of 15mm x 30mm x 15mm

RM 50

1.6 Cable Trays (Perforated Type)

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

Supplying and fixing cable trays of the following sizes (in

one/two/ three tier fashion either on one side of the wall or on

two sides of the wall) of GI/MS perforated type including

grouting supports/hangers, nuts, bolts, dash fasteners and

required hardwares etc. as specified in the drawings.a 75mm x 1000mm x 75mm x 3mm wide cable tray RM 10b 50mm x 300mm x 50mm x 2mm wide cable tray RM 50c 50mm x 150mm x 50mm x 2mm wide cable tray RM 100

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

1.7 Steel SupportsSupplying and fixing of additional length of MS rod/angle

hangers duly painted with 2 coats of spray paint for

supporting the cable trays, complete for extension of the

supports.

Kgs. 2500

1.8 Providing and fixing 6 SWG dia GI wire on surface or inrecess for loop earthing as required.

Mtr 500

1.9 Providing and fixing 25mm x 5mm GI strip on surface or inrecess for connection etc. as required.

Mtr 1000

2.0 HVAC PANELS

Design, fabrication, Supply, Installation, loading, unloading as per site condition, Installation, testing and commissioning of HVAC Panels fabricated out of 2mm thick for structural members (Load bearing members) and 1.6mm thick for door and covers (Non load bearing members) CRCA sheet in cubicle compartmentalize free standing floor mounted, dust and vermin proof with reinforcement of suitable size angle iron, channel 'T' irons and / or flats wherever necessary, 16 gauge CRCA sheet steel shall be used for final distribution panels. Cable gland plates shall be provided on top as well as at the bottom of the panels. Panels shall be treated with all anticorrosive process before painting as per specifications with 2 coats of zinc chromate primer and final approved shade of enamelled paint. 2 Nos. earthing terminals shall be provided for all distribution panels. Panels shall be suitable for 415V, 3-phase, 4-wire, 50Hz supply system and with 15%spare space, lifting hooks shall also be provided in case of large panels. The Panel shall be suitable for installion in Outdoor conditions IP rating of panel shall be IP 54.

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

Approval shall be taken for each panel before fabrication.Galvanized hardwares with zinc passivation shall be used infabrication of panels. The panels to confirm to IP-43 forindoor & for IP-55 for outdoor installation.

2.1 AC PANEL-1

Incoming

Two (2) Nos. 1000 A, TPN EDO ACB, 50 KA

Metering, Indication and Protection

Two (2) Sets of (0-1000 Amps) 96 x 96mm CT operated Ammeter with 3 way selector switch and 1000/5A, CL-1, 10VA CT.

Two (2) Sets of (0-500 Volt) 96 x 96mm Voltmeter with control MCB and 3 way selector switch.

Two (2) Sets of phase indicating lamps with control MCBs.

Bus Bar:

1500A, TPN aluminium, colour coded bus bar suitable for 415V, 50Hz with heat shrinkable insulation sleeves.

Outgoing:

Three (3) Nos. 630 Amp TP MCCB (35 KA)Three (3) Nos. 400 Amp TP MCCB (35 KA)Four (4) Nos. 100 Amp TP MCCB (15 KA)Three (3) Nos. 40 Amp TP MCB ( 10 KA)Three (3) Nos. Star Delta starters for Chilled Water Pumpswith O/L relay suitable for 15 KW motor and single phasepreventor.

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

Three (3) Nos. DOL Starters for hot water pumps with overload relay suitable for 3.7 KW motor and single phasepreventor.

Set 1

2.2 AC PANEL-2

Incoming

One (1) Nos. 400A, TPN MCCB, 35 KA

Metering, Indication and Protection

One (1) Sets of (0-400 Amps) 96 x 96mm CT operated Ammeter with 3 way selector switch and 400/5A, CL-1, 10VA CT.

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

Two (2) Sets of (0-500 Volt) 96 x 96mm Voltmeter with control MCB and 3 way selector switch.

Two(2) Sets of phase indicating lamps with control MCBs.

Bus Bar:

600A, TPN aluminium, colour coded bus bar suitable for 415V, 50Hz with heat shrinkable insulation sleeves.

Outgoing:

Two(2) Nos. 250 Amp TP MCCB (25 KA)Two(2) Nos. 125 Amp TP MCCB (15 KA)Three (3) Nos. 40 Amp TP MCB ( 10 KA)Three (3) Nos. 25 Amp TP MCB ( 10 KA)Two (2) Nos. DOL starters for Chilled Water Pumps withO/L relay suitable for 5.5 KW motor and single phasepreventor.

Two (2) Nos. DOL starters for Hot Water Pumps with O/Lrelay suitable for 1.0 KW motor and single phase preventor.

Set 1

2.3 AHU AND VENTILATION PANELS

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

Incoming One (1) No. 1000A, EDO ACB, 50 KA Metering, Indication and Protection One (1) Set of (0-1000 Amps) 96 x 96mm CT operatedAmmeter with 3 way selector switch and 400/5A, CL-1,10VA CT. One (1) Set of (0-500 Volt) 96 x 96mm Voltmeter withcontrol MCB and 3 way selector switch. Two(2) Sets of phase indicating lamps with control MCBs. Bus Bar: 1200A, TPN aluminium, colour coded bus bar suitable for415V, 50Hz with heat shrinkable insulation sleeves. Outgoing:One (1) No. 630 Amp TP MCCB (35 KA)Two (2) Nos. 125 Amp TP MCCB (15 KA)Two (2) Nos. 63 Amp TP MCB ( 10 KA)Two (2) Nos. 40 Amp TP MCB ( 10 KA)Forty One (41) Nos. 25 Amp TP MCB ( 10 KA)

Set 1

3.0 AHU'S STARTER PANEL3.1 Supply, installation, testing and commissioning of One

no.63A TPN MPCB (10kA) with 5.5 KW DOL Starter

including single phasing prevention arrangement, O/L relays,

ammeters with CTs, ON/OFF / Trip indication lamps and

push buttons, potential free contacts for remote / local

operations, indication, interlocking. and Auto Manual

Selector Switch as required.

Set 2

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

3.2 Supply, installation, testing and commissioning of One no.

40A TPN MPCB (10kA) with 3.7 KW DOL Starter

including single phasing prevention arrangement, O/L relays,

ammeters with CTs, ON/OFF / Trip indication lamps and

push buttons, potential free contacts for remote / local

operations, indication, interlocking. and Auto Manual

Selector Switch as required.

Set 2

3.3 Supply, installation, testing and commissioning of One no.

25A TPN MPCB (10kA) with 2.2 KW DOL Starter

including single phasing prevention arrangement, O/L relays,

ammeters with CTs, ON/OFF / Trip indication lamps and

push buttons, potential free contacts for remote / local

operations, indication, interlocking. and Auto Manual

Selector Switch as required.

Set 40

4.0 LIFT WELL PRSSURIZATION AND BASEMENT VENTILATION STARTOR PANEL

4.1 Supply, installation, testing and commissioning of One no.

125 A TPN MPCB (10kA) with 30 KW Star Delta Starter

including single phasing prevention arrangement, O/L relays,

ammeters with CTs, ON/OFF / Trip indication lamps and

push buttons, potential free contacts for remote / local

operations, indication, interlocking. and Auto Manual

Selector Switch as required. (Basement Ventilation)

Set 2

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

ITEM OF WORK UNIT QTY.

AMOUNT (In words)

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)SUB-HEAD 'D' ELECTRICALS

QUOTED

UNIT RATE

4.2 Supply, installation, testing and commissioning of One no.

25A TPN MPCB (10kA) with 1.1 KW Direct-On-Line

Starter including single phasing prevention arrangement, O/L

relays, ammeters with CTs, ON/OFF / Trip indication lamps

and push buttons, potential free contacts for remote / local

operations, indication, interlocking. and Auto Manual

Selector Switch as required. (Lift Well Pressurization)

Set 1

TOTAL SUB-HEAD 'D' ELECTRICALS CARRIED OVER TO SUMMARY

Note : Qty. of cables or tentative, vendor should make the cable schedule and get it approved before procurement.

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)

1.0

i)

ii)

iii)

Condenser Air Temp. - 43.3º C./ 110.0 º F

Supply, installation, testing and commissioning of Air CooledScrew Water Chilling M/C following capacity at below mentionedoperating conditions with R-134a refrigerant, Multiplesemihermetic/Open compressors & circuits, driven by suitable KWSq. Cage induction motor complete with air cooled condenser,Electronic Expansion Valve, insulated shell and tube floodedchiller with victaulic coupling, DP flow switches in chiller,refrigerant piping, Refrigerant and gas and Oil (First Charge),Microprocessor based control panel, factory mounted, motorstarter & accessories etc. all mounted on M.S. frame. Motor shallbe highly efficient and suitable for 415 volts ± 10%,50Hz ± 5%, three phase A.C. supply.

FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

SUB HEAD 'A' MACHINERY

Chiller CHW IN - 12.2 º C / 54.0 º F CHW OUT - 6.67 º C / 44.00 º F Fouling Factor - 0.0001 FPS

As the performance of the chillers mentioned herein doesnot fall under the ARI/Eurovent certification program sothe chiller shall be tested in the factors and the performancetest shall be witnessed by customers representatives as perprocedure laid down by ARI/Eurovent at four point loads at tender design conditions.

IkW/ TR of the Air cooled screw chiller at full load shallnot be more than 1.3 at Std. Design Conditions

The Chiller shall be able to provide 25% to 100% steplesscapacity control.

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

iv)

v)

vi)

Nos. 3

2

i)

ii)

iii)

iv)

v)

vi)

Chilled Water Pumps

(The system shall be complete in all respects viz Drive,lubrication sytem, evaporator, condenser coil, refrigerentsytem, controller, communication port for BMS).

The chilling machine as described above shall be as perspecifications.

The System should be compatible with the BMS systemand having the facility to perform the function thru BMSviz remote chiller start and stop, remote leaving chillerliquid temperature adjustment, remote current limitsetpoint, remote ready to start contacts, safety shutdowncontacts, run contacts

2 Nos. 150 mm dia dial type pressure gauges.

a) 302400 Kcal/hr (100 TR) (2W + 1S)

1 No. end section, vertical split casing, centrifugal pump.

1 No. suitable HP TEFC induction motor with class `F'insulation operating on 415 + 10% volts, 3 phase, 50 cyclesAC supply.

Supply, installation, testing and commissioning of chilled water pump set each capable of delivering the specified flow rate comprising the following and complete as per specifications.

Lot, thermal insulation on the pump.

Lot, anti-vibration pads, channel base, coupling, couplingguard, suction guide, etc.

Lot, concrete foundation for the pump.

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

Nos. 3

2.A

3.0

a) Flow rate 910 LPM/head 25 m (2W+1SB)

Supply, installation, testing and commissioning of factorybuilt, cabinet type, horizontal/vertical, floor mounted/ceilingsuspended belt driven air handling units in double skinconstruction of following capacity at required static pressureof 40 mm complete with factory fabricated independentsections, housing the various components e.g. blower, TEFCblower motor suitable for operation on 415 + 10% volts, 3phase, 50 Hz AC supply, copper tube, aluminium finnedchilled water cooling coil, thermostat and control wiring etc.,pre filter sets, drain connections and concrete foundation withanti-vibrationmountings etc. as required and as per "Scheduleof equipment" and specifications.

Hot Water PumpsSupply, installation, testing and commissioning of Hot waterpump set each capable of delivering the specified flow ratecomprising the following and complete as per specifications.I) 1 No. monoblok pump.II) 1 No. suitable HP TEFC induction motor with class `F'insulation operating on 415 + 10% volts, 3 phase, 50 cyclesAC supply.III) Lot, thermal insulation on the pump.IV) 2 Nos. 150 mm dia dial type pressure gauges.V) Lot, anti-vibration pads, channel base, coupling, couplingguard, suction guide, etc.VI) Lot, concrete foundation for the pump.a) Flow rate 450 LPM/head 25 m 3 Nos. (2W+1SB)b) Flow rate 100 LPM/head 20 m 2 Nos. (1W+1SB)

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

S.No. TAG No. Cooling Load (TR) Each

De-humidi-fied Air Qty. (CFM)

Chilled Water Coil (Row)

3.1 AHU-1.1 35.0 20000 4 No. 1

3.2 AHU-2.1 17.0 9500 4 No. 1

3.3 AHU-3.1 & 4.1 7.0 4000 4 Nos. 2

3.4 AHU-5.1 & 6.1 7.0 4000 4 Nos. 2

GROUND FLOOR

The face velocity across cooling coil shall be limited to 152 MPMmaxm. The capacity of Air-handlers shall be as follows:

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

3.5 AHU-7.1 & 8.1 7.0 4000 4 Nos. 2

3.6 AHU-9.1 & 10.1 7.0 3500 4 Nos. 2

3.7 AHU-11.1 12.0 5800 4 No. 1

3.8 AHU-1.2 5.6 2800 4 Nos. 2

3.9 AHU-2.2 & 3.2 7.0 3500 4 Nos. 1

3.10 AHU-1.3 & 2.3 8.1 4650 4 Nos. 2

3.11 AHU-3.3 & 4.3 8.1 4650 4 Nos. 2

3.12 AHU-5.3 & 6.3 6.5 3500 4 Nos. 2

FIRST FLOOR

SECOND FLOOR

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

4.0

S.No. TAG No. Cooling Load (TR) Each

4.1 FCU-1.1 1.5 No. 2

4.2 FCU-2.1 1.5 No. 2

5.0

Supply and installation and commissioning of ceilingconcealed fan coil units includingair - filter ball valve set withstrainer, 2 way diverting valve with snap acting heat-coolthermostat as per drawing flexible electrical wiring necessaryconnection for chilled hot water supply and return line colingheating coil with mechanically expanded copper tube andaluminium fins staticallyand dynamicallybalanced centrifugalforward curve aluminium blower 3 speed mortor suitable for220(±.) 10% V supply complete with stainlesssteel drain panduly insulated sheet metal casing of heavy gauge steelincluding flanges canvas connection as required. FCU's are tobe powder coated and the noice level shall less than 40 Db atAC unit outlet and as per specification.

De-humidi-fied Air Qty. (CFM)

600

GROUND FLOOR

Supply, installation, testing and commissioning, of duct mountedInline fans complete with direct driven centrifugal fan, TEFCsquirrel cage induction motor, direct drive arrangement, heavygauge sheet metal casing, rubber isolator mounts and otheraccessories. Inline fans shall be of following capacities:

600

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

i) No. 12

6.0

i) No. 1

7.0

400 CFM at SP of 20 mm WG

Supply, installation, testing and commissioning of long casing tubeaxial fan with adjustable pitched aluminium alloy impeller, TEFCsquirrel cage induction motor with class 'F' insulation hightemprature resistance and flame proof, direct drive arrangement,variable frequency drive, sheet metal casing, rubber isolator mountsand other accessories as per specified and of following capacities asper Schedule of Equipment.

Supply air fan with class 'F' insulation with PR-12 epoxy coatingsuitable for normal application and AMCA certified for air andsound levels.

5100 CMH at SP at 10mm WG, 1440 rpm, (For lift wellpressurisation)

Supply, Installation, testing and commissioning of Electric Hot Water Generator of following capacity conforming to BIS standards and hot water in let/ out let temperature of 45/50oC complete as per specifications with following accessories.i) Matching electrical immersion heater banks.ii) All automatic and safety controls such as manual reset, high temperature cut off, step controller and recycling relay, thermostats, pilot light, low water cut off and other controls.iii) Electrical panel mounted on generator frame complete with internal wiring, contractors, switches, etc.iv) Interconnecting cables between panel and heaterv) Concrete foundation for Hot Water Generator vi) Water Temp. in °C 45 Water Temp. Out °C50

Capacity 70 KW 3 Nos. (2W+1SB)

TOTAL OF SUB HEAD `A’ MACHINERY CARRIED OVER TO SUMMARY

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

1.0 A.

i) 150 mm dia M 20

ii) 125 mm dia M 100

iii) 100 mm dia M 25

iv) 80 mm dia M 275

v) 65 mm dia M 260

vi) 50 mm dia M 170

vii) 40 mm dia M 260

SUB-HEAD 'B' PIPING

Exposed Pipes

Supply, laying/fixing, testing and commissioning of following sizesof chilled water MS ERW heavy class piping with necessaryclamps, supports, anti-vibration mountings, hangers and fittingssuch as bends, tees, reducers etc. (but excluding valves, strainers,gauges, etc.) duly insulated with polyurethane foam pipe sectionprelaminated with aluminium foil and finally applying aluminiumtape at joints as per specifications.

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

viii) 32 mm dia M 185

ix) 25 mm dia M 25

x) 20 mm dia M 20

2.0

a)

i) 125 mm dia Nos. 3

b)

i) 80 mm dia Nos. 1

ii) 50 mm dia Nos. 3

iii) 40 mm dia Nos. 16

iv) 25 mm dia Nos. 4

Supply, installation, testing and commissioning of followingvalves, strainers, in the chilled water piping complete withcompanion flanges, nuts, bolts, gaskets, supports, etc. and dulyinsulated and painted as per specifications.

Motorised Butterfly Valve

2 way Chilled water Dynamic cum modulating Valve

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

c)

i) 150 mm dia Nos. 2

ii) 125 mm dia Nos. 18

iii) 80 mm dia Nos. 1

iv) 50 mm dia Nos. 6

v) 40 mm dia Nos. 32

d)

i) 125 mm dia Nos. 9

e)

i) 125 mm dia Nos. 3

f)

i) 80 mm dia Nos. 1

ii) 50 mm dia Nos. 3

Balancing Valves

Y'-Strainer

Non Return Valves

Butterfly Valves

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

iii) 40 mm dia Nos. 16

g)

i) 10 mm dia Nos. 30

h)i) 32 mm dia Nos. 12

ii) 25 mm dia Nos. 30

i)

i) 25 mm dia Nos. 4

j)

i) 25 mm dia Nos. 4

k)

Ball Valve without Strainer

G M Gate Valve

Auto Air Vent Valves

Stem typeTemperature gauge Range (0 - 500C)

Ball Valve with Strainer

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

i) 9.4 mm Bulb Dia) Nos. 60

l)

i) 100 mm dial Nos. 60

3.0 No. 1

1.0

i) Sqm. 20

ii) Sqm. 25

iii) Sqm. 190

iv) Sqm. 850

Supply, installation, testing and balancing of factory fabricatedrectangular GSS ducting of following thickness includingnecessary supports, hangers, nut bolts, gaskets, splitter dampers,vanes, canvas connections etc. complete as per specifications.

Dial type pressure gauge Range: (0 - 7 Kg/cm2)

TOTAL OF SUB HEAD 'B' PIPING CARRIED OVER TO SUMMARY

SUB-HEAD 'C' DUCTING AND GRILLES

Supply, installation, testing and commissioning, of MS expansiontank of size 1.2m x 1.2 m x 1.2 m height, made of 3 mm thickmild steel sheet complete with insulation, vent and control valves,air vent, manhole cover, final painting etc.

0.8 mm

0.63 mm

1.25 mm

1.00 mm

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.SR. NO.

UNIT QTY.

AMOUNT (in words)In Figures(Rs.) In Words(Rs.) In Figures(Rs.)FILM & TV

ITEM OF WORK QUOTED

UNIT RATE

2.0 Sqm. 150

3.0 Sqm. 950

4.0 Sqm. 7

5.0 Sqm. 5

6.0 Sqm. 1

7.0 Sqm. 85

8.0 Sqm. 1.5

9.0 Sqm. 1.5

10.0 Sqm. 550

Supply, installation, testing and commissioning of powder coatedextruded aluminium supply air Continuous grilles of various sizes,with vcd complete as per specifications .

Supply, installation, testing and commissioning ofsquare/rectangular powder coated extruded aluminiumreturn/exhaust air diffusers of various sizes complete withoutvolume control dampers, and as per specifications.

Supply, installation, testing and commissioning of GI multi-leafmotorised fire dampers complete with chrome plated spindles inself lubricated bronze bushes, linkages, actuator motor, limitswitch, wiring etc. complete as per specifications.

Supply, installation, testing and balancing of box type GI volumecontrol damper complete as per specifications

Supply and fixing of 15 mm thick chemically cross linked,closedcell polyethylene FR-XPE retardant grade insulation onsupply/return air duct as per specifications.

Supply and fixing acoustic lining of 15 mm thick engineeredestatomeric open cell nitrile rubber slab on the inner side ofducting as per specifications for ducts as required

TOTAL OF SUB HEAD `C’ DUCTING & GRILLES CARRIED OVER TO SUMMARY

Supply, installation, testing and commissioning of powder coatedextruded aluminium fresh air louvers with aluminium bird screenand volume control damper as per specifications.

Supply and installation of powder coated extruded aluminiumlouvers complete with bird screen as per specifications.

Supply and fixing of underdeck roof insulation and thermalinsulation on wall with 40mm thick polyisocyanurate machine cutshiplap joint slabs prelaminated with 0.05mm aluminium foil etc.asper specifications

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

1.0 CABLES1.1

a RM 150

b RM 60

c RM 120

d RM 50

e RM 440

f RM 400

g RM 100

1.2 Cable Termination

3.5 C x 120 Sq.mm cable

4c x 6 sqmm

4C x 16 Sq.mm cable

4C x 25 Sq.mm cable

SR. NO.

ITEM OF WORK

SUB-HEAD 'D' ELECTRICALS

Supply, storing, handling, laying, testing and commissioningof1100 Volt grade XLPE insulated and sheathed aluminiumconductor armoured cables including the cost of providingrequired gap between adjacent cables (minimumone cable dia.)and including the cost of providing identification tags in shaft/cable trays etc. complete as per specification, as required (Lowlosses).

FILM & TV

3.5 C x 240 Sq.mm cable

3.5 C x 150 Sq.mm cable

4c x 4 sqmm

QUOTED

UNIT RATE

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

SR. NO.

ITEM OF WORK

FILM & TV

QUOTED

UNIT RATE

a Nos 4

b Nos 6

c Nos 12

d Nos 2

e Nos 2

f Nos 40

g Nos 6

Supply, storing, handling, laying, testing and commissioningof1100 Volt grade PVC insulated and sheathed aluminiumconductor unarmoured cables including the cost of providingrequired gap between adjacent cables (minimumone cable dia.)and including the cost of providing identification tags in shaft/cable trays etc. complete as per specification, as required (Lowlosses).

3.5 C x 120 Sq.mm cable

3.5 C x 150 Sq.mm cable

4C x 16 Sq.mm cable

4c x 6 sqmm

4c x 4 sqmm

3.5 C x 240 Sq.mm cable

4C x 25 Sq.mm cable

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

SR. NO.

ITEM OF WORK

FILM & TV

QUOTED

UNIT RATE

Control Cables :

RM 600

RM 200

RM 100

1.4

Nos. 30

7 Core x 2.5 Sq.mm Cable

Control Cables termination:

2 Core x 2.5 Sq.mm Cable

Supplying, receiving, storing, laying, effecting proper

connections, testing and commissioning of the following sizes of

1.1 KV grade PVC insulated and sheathed copper conductor

armoured stranded control cable complete with saddles, clamps

etc. as required and as per specifications.

4 Core x 2.5 Sq.mm Cable

Supplying and making of control cable terminations for control

cables as per item 8.0 above complete with brass plated single

compression glands, copper lugs etc. as required:2 Core x 2.5 Sq.mm Cable

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

SR. NO.

ITEM OF WORK

FILM & TV

QUOTED

UNIT RATE

Nos. 8

Nos. 4

1.5

RM 10

RM 50

RM 50

4 Core x 2.5 Sq.mm Cable

7 Core x 2.5 Sq.mm Cable

Cable Trays (Ladder Type):Supply, fabrication and installation of Hot dip galvanized factoryfabricated ladder type cable trays complete with all fabricated bends, tees,nuts bolts ,dash fasteners, elbows, reducers, offsets et& required hardware. with rungs at every 250 mm spacing (c/c) of various width in two tier/three/five tier fashion either on one side of the wall or on two sides of the wall or at other places and paint afterward if required. (All bends & tees shall be of factory built-in of same make as that of tray)

75mm x 750mm x 75mm x 3mm wide cable tray with rungs of

20mm x 40mm x 20mm50mm x 600mm x 50mm x 2mm wide cable tray with rungs of

15mm x 30mm x 15mm

75mm x 1200mm x 75mm x 3mm wide cable tray with rungs of

20mm x 40mm x 20mm

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

SR. NO.

ITEM OF WORK

FILM & TV

QUOTED

UNIT RATE

RM 150

RM 50

1.6

a RM 10b RM 50c RM 50

1.7Kgs. 1500

1.8 Mtr 500

1.9 Mtr 1000

2.0

50mm x 150mm x 50mm x 2mm wide cable tray with rungs of 15mm x 30mm x 15mm

Cable Trays (Perforated Type)Supplying and fixing cable trays of the following sizes (in one/two/ three tier fashion either on one side of the wall or on two sides of the wall) of GI/MS perforated type including grouting supports/hangers, nuts, bolts, dash fasteners and required hardwares etc. as specified in the drawings.

75mm x 1000mm x 75mm x 3mm wide cable tray

Steel SupportsSupplying and fixing of additional length of MS rod/angle

hangers duly painted with 2 coats of spray paint for supporting

the cable trays, complete for extension of the supports.

HVAC PANELS

Providing and fixing 25mm x 5mm GI strip on surface or inrecess for connection etc. as required.

Providing and fixing 6 SWG dia GI wire on surface or in recess for loop earthing as required.

50mm x 300mm x 50mm x 2mm wide cable tray with rungs of

15mm x 30mm x 15mm

50mm x 150mm x 50mm x 2mm wide cable tray50mm x 300mm x 50mm x 2mm wide cable tray

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

SR. NO.

ITEM OF WORK

FILM & TV

QUOTED

UNIT RATE

Approval shall be taken for each panel before fabrication.Galvanized hardwares with zinc passivation shall be used infabrication of panels. The panels to confirm to IP-43 for indoor& for IP-55 for outdoor installation.

Design, fabrication, Supply, Installation, loading, unloading asper site condition, Installation, testing and commissioning ofHVAC Panels fabricated out of 2mm thick for structuralmembers (Load bearing members) and 1.6mm thick for door andcovers (Non load bearing members) CRCA sheet in cubiclecompartmentalize free standing floor mounted, dust and verminproof with reinforcement of suitable size angle iron, channel 'T'irons and / or flats wherever necessary, 16 gauge CRCA sheetsteel shall be used for final distribution panels. Cable glandplates shall be provided on top as well as at the bottom of thepanels. Panels shall be treated with all anticorrosive processbefore painting as per specifications with 2 coats of zincchromate primer and final approved shade of enamelled paint. 2Nos. earthing terminals shall be provided for all distributionpanels. Panels shall be suitable for 415V, 3-phase, 4-wire, 50Hzsupply systemand with 15% spare space, lifting hooks shall alsobe provided in case of large panels. The panel shall be suitablefor installation in outdoor conditions. IP rating of panel shall be I

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

SR. NO.

ITEM OF WORK

FILM & TV

QUOTED

UNIT RATE

2.1

One (1) No. 800A, TPN EDO ACB, 35 KA

Three (3) Nos. 160 Amp TPN MCCB (25 KA)

Three (3) Nos. 25 Amp TPN MCB with motor duty (10 KA)

One(1) Set of phase indicating lamps with control MCBs.

One (1) Set of (0-500 Volt) 96 x 96mm Voltmeter with control MCB and 3 way selector switch.

Metering, Indication and Protection

AC PANEL

Incoming

Bus Bar:

Outgoing:

Three (3) Nos. star delta starters for Chilled Water Pumps withO/L relay suitable for 7.5 KW motor and single phase preventor.

Three (3) Nos. 400 Amp TPN MCCB (35 KA)

Five (5) Nos. 63 Amp TPN MCB with motor duty (10 KA)

1000A, TPN aluminium, colour coded bus bar suitable for 415V50Hz with heat shrinkable insulation sleeves.

One (1) Set of (0-800 Amps) 96 x 96mm CT operated Ammeter with 3 way selector switch and 800/5A, CL-1, 10VA CT.

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

SR. NO.

ITEM OF WORK

FILM & TV

QUOTED

UNIT RATE

Set 1

3.03.1 Set 1

3.2 Set 1

Supply, installation, testing and commissioningof One no. 63A

TPN MPCB (10kA) with 7.5 KW Star Delta Starter including

single phasing prevention arrangement, O/L relays, ammeters

with CTs, ON/OFF / Trip indication lamps and push buttons,

potential free contacts for remote / local operations, indication,

interlocking. and Auto Manual Selector Switch as required.

Supply, installation, testing and commissioningof One no. 63A

TPN MPCB (10kA) with 5.5 KW DOL Starter including single

phasing prevention arrangement, O/L relays, ammeterswith CTs,

ON/OFF / Trip indication lamps and push buttons, potential free

contacts for remote / local operations, indication, interlocking.

and Auto Manual Selector Switch as required.

Three (3) Nos. DOLstarters for Chilled Water Pumps with O/Lrelay suitable for 1.5 kw motor and single phase preventor.

AHU'S STARTOR PANEL

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

SR. NO.

ITEM OF WORK

FILM & TV

QUOTED

UNIT RATE

3.3 Set 2Supply, installation, testing and commissioningof One no. 40A

TPN MPCB (10kA) with 3.7 KW DOL Starter including single

phasing prevention arrangement, O/L relays, ammeterswith CTs,

ON/OFF / Trip indication lamps and push buttons, potential free

contacts for remote / local operations, indication, interlocking.

and Auto Manual Selector Switch as required.

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

SR. NO.

ITEM OF WORK

FILM & TV

QUOTED

UNIT RATE

3.4 Set 9

3.5 Set 1

3.6 Set 1Supply, installation, testing and commissioningof One no. 16A

TPN MPCB (10kA) with 0.75 KW DOL Starter including

single phasing prevention arrangement, O/L relays, ammeters

with CTs, ON/OFF / Trip indication lamps and push buttons,

potential free contacts for remote / local operations, indication,

interlocking. and Auto Manual Selector Switch as required.

Supply, installation, testing and commissioningof One no. 16A

TPN MPCB (10kA) with 1.5 KW DOL Starter including single

phasing prevention arrangement, O/L relays, ammeterswith CTs,

ON/OFF / Trip indication lamps and push buttons, potential free

contacts for remote / local operations, indication, interlocking.

and Auto Manual Selector Switch as required.

Supply, installation, testing and commissioningof One no. 25A

TPN MPCB (10kA) with 2.2 KW DOL Starter including single

phasing prevention arrangement, O/L relays, ammeterswith CTs,

ON/OFF / Trip indication lamps and push buttons, potential free

contacts for remote / local operations, indication, interlocking.

and Auto Manual Selector Switch as required.

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

SR. NO.

ITEM OF WORK

FILM & TV

QUOTED

UNIT RATE

4.0 LIFT WELL PRSSURIZATION STARTOR PANEL

Supply, Installation, and Testing & Commissioning of Air Cooled chiller System HVAC work for Fashion Design & Film & TV at Institutional Campus, Rohtak.

UNIT QTY. RATE (in Rs.)

AMOUNT

In Figures (Rs.) In Words (Rs.) In Figures (Rs.)

SR. NO.

ITEM OF WORK

FILM & TV

QUOTED

UNIT RATE

4.1 Set 1

Note : Qty. of cables or tentative, vendor should make the cable schedule and get it approved before procurement.

TOTAL OF SUB HEAD `D’ MACHINERY CARRIED OVER TO SUMMARY

Supply, installation, testing and commissioningof One no. 16A

TPN MPCB (10kA) with 0.75 KW Direct On Line Starter

including single phasing prevention arrangement, O/L relays,

ammeters with CTs, ON/OFF / Trip indication lamps and push

buttons, potential free contacts for remote / local operations,

indication, interlocking. and Auto Manual Selector Switch as

required.