90
ANALYSIS OF ELECTRICAL SURGES IN AJAOKUTA POWER SYSTEM NETWORK, NIGERIA By ROTIMI, Makanjuola Shola AAU/SPS/FET/ELE/M.Eng/11/03767 DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING, SCHOOL OF POSTGRADUATE STUDIES, AMBROSE ALLI UNIVERSITY, EKPOMA, NIGERIA. AUGUST, 2018

ANALYSIS OF ELECTRICAL SURGES IN AJAOKUTA POWER …

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

ANALYSIS OF ELECTRICAL SURGES IN AJAOKUTA POWER SYSTEM

NETWORK, NIGERIA

By

ROTIMI, Makanjuola Shola

AAU/SPS/FET/ELE/M.Eng/11/03767

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING,

SCHOOL OF POSTGRADUATE STUDIES,

AMBROSE ALLI UNIVERSITY,

EKPOMA, NIGERIA.

AUGUST, 2018

i

ANALYSIS OF ELECTRICAL SURGES IN AJAOKUTA POWER SYSTEM

NETWORK, NIGERIA

By

ROTIMI, Makanjuola Shola

AAU/SPS/FET/ELE/M.Eng/11/03767

HND (Kwara Poly), PGD Eng (Unizik)

A THESIS IN THE DEPARTMENT OF ELECTRICAL AND ELECTRONICS

ENGINEERING, SUBMITTED TO THE SCHOOL OF POSTGRADUATE STUDIES,

IN PARTIAL FULFILMENT OF THE REQUIREMENTS FOR THE AWARD OF

MASTERS DEGREE (M.Eng) IN ELECTRICAL POWER/MACHINES, AMBROSE

ALLI UNIVERSITY, EKPOMA, NIGERIA.

AUGUST, 2018

ii

DECLARATION

I hereby declare that this research work was done by ROTIMI, Makanjuola Shola and to the

best of my knowledge, this research work has not been submitted elsewhere for the award of

Masters of Engineering or any other degree or diploma.

…….………………………………….. ………………………………..

ROTIMI, Makanjuola Shola Date

AAU/SPS/FET/ELE/M.Eng/11/03767

iii

CERTIFICATION

This is to certify that this study was carried out by ROTIMI, Makanjuola Shola with

Matriculation number AAU/SPS/FET/ELE/M.Eng/11/03767, in the Department of Electrical

and Electronics Engineering, School of Postgraduate Studies, Ambrose Alli University,

Ekpoma.

…………………………….. …………………………

Engr. Dr. Osahenvemwen, O. A. Date

Supervisor

Department of Electrical and Electronics Engineering,

Faculty of Engineering and Technology,

Ambrose Alli University,

Ekpoma, Nigeria.

…………………………….. …………………………

Engr. Dr. Okundamiya, M. S. Date

Head of Department

Department of Electrical and Electronics Engineering,

Faculty of Engineering and Technology,

Ambrose Alli University,

Ekpoma, Nigeria.

..............Signed.................... ………………………

External Examiner Date

iv

DEDICATION

This work is dedicated to the glory of Almighty God for his unmerited favour throughout the

programme

v

ACKNOWLEDGEMENT

I am highly grateful to the Almighty God for the successful completion of this project work,

which is the climax of the M.Eng degree programme. My gratitude goes to my supervisor:

Engr. Dr. A. O Osahenvemwen, the present Head of Department: Engr. Dr. M. S. Okundamiya,

and the Postgraduate Coordinator Engr. Dr. O. Omorogiuwa, for their brotherly support and

counselling throughout the period of putting this project together.

I am also grateful for the encouraging role played by Engr. Dr. M. J. E. Evbogbai,

Engr. Dr. C. E. Ojeabu and Engr. J. K. Yeboah for their input cannot be overemphasized. Also,

I wish to acknowledge all the staff of the Department of Electrical and Electronics Engineering,

Ambrose Alli University Ekpoma.

I thank the organization and management staff of Ajaokuta Steel Company Limited and PHCN

for the rare privilege and support given to me for the successful completion of the project work.

I am grateful to my wife and children for their patient and support given to me till completion

of this course.

Thank be to God Almighty for his infinite mercies and protection throughout the period of this

programme.

vi

ABSTRACT

The study investigates the electrical surge effects and remedy in Ajaokuta Power System

Network located in Kogi State in the North Central of Nigeria, to identify various causes of

lightning strokes and highlight various associated effects and to determine surge intensity and

magnitude, collection of surge data on distribution and transmission network. The approaches

adopted is to develop a preliminary data collection that will address the identified data gap and

to review comprehensively the electrical surge related losses and address the potential impact

of electrical surge protective devices in mitigating these losses. Experimental investigations will

be carried out and collation of available data associated with electrical surges and their impacts.

The result of the data recording based on existing power system network revealed that the vast

majority of the lightning strikes were less than 30kA. In the three years of monitoring six

residences with 15 lightning surge events, only two lightning strikes were severe enough to

cause damage at current values of 1.27kA and 1.09kA in 2013 and 2015 respectively. In this

thesis causes of over voltages in Ajaokuta power system network are internal and external.

Instances of extended high voltages are rare, but when they occurred significant damages are

done. Therefore to maintain high quality power, wiring, grounding, bonding and installation of

surge protective devices are necessary to prevent over voltages from this power system network.

vii

CONTENTS

Page

DECLARATION ii

CERTIFICATION iii

DEDICATION iv

ACKNOWLEDGEMENT v

ABSTRACT vi

CONTENTS vii

LIST OF TABLES xi

LIST OF FIGURES xii

LIST OF PLATES xiv

LIST OF ABBREVIATIONS xv

CHAPTER ONE: INTRODUCTION 1

1.1 Background to the Study 1

1.2 Justification for the Study 2

1.3 Objectives of the Study 5

1.4 Scope and Limitation 5

1.5 Research Methodology 6

1.6 Thesis Arrangement 7

CHAPTER TWO: LITERATURE REVIEW 8

2.1 Surge Protection Fundamentals 8

2.2 Sources of Surges 8

2.3 Lightning Surges 12

2.4 Schneider Electric Surge Experimental Investigation. 13

viii

2.5 Utility Switching 14

2.6 Facility Internal Switching 16

2.7 Surge Effects 16

2.8 The Benefits of Power Quality and Protection Products 19

2.9 The Importance of Protecting the Power Network. 19

2.10 Practice for Powering and Grounding Electronic Equipment 19

2.11 Potential impact of Electromagnetic Interference (EMI) 20

2.12 Electrical System Surge Protection 21

2.13 Surge Arresters 22

2.14 The difference Between the Terms “Surge Arrester” and “Transient Voltage Surge

Suppressor (TVSS) 24

2.15 Protective Devices 25

2.15.1 One-Port Parallel-Connected Devices 25

2.15.2 Surge Protective Device (SPD) 25

2.15.3 Integral SPD Issues 25

2.15.4 Hybrid Design 26

2.15.5 Two-Port (Series-Connected) Devices 27

2.16 Active Tracking Filter (ATF) 27

2.16.1 Harmonic Filter 28

2.17 Surge Protection with Filtering 28

2.18 Attenuation in an SPD 28

2.19 Using Active Tracking Filters To Control Low- And High-Voltage Transients 29

2.20 CWG 1.2/50 μs Voltage Open-circuit Surge Waveform 30

ix

2.21 Filters with Air Cored Inductors 31

2.22 Voltage Regulator 32

2.23 Line Conditioner 32

2.24 The difference between series connected filters and parallel connected SPDs 32

2.25 Using Surge Suppression to Control High-Voltage Transients 34

2.26 DC Low Voltage Surge Protection 34

2.26.1 DC Power Protection 35

2.26.2 Video Line Protection 35

2.26.3 Data Line Protection 35

2.26.4 Signal Line Protection 35

2.26.5 Silicon Avalanche Diode (SAD) 35

2.26.6 Fuse 36

2.26.7 PTC (Positive Temperature Coefficient) 36

2.27 Comparisons – Fuse Vs. PTC 37

2.28 Surge Protective Devices (SPDs) 37

2.29 SPD Classification 38

2.30 SPD Ratings 40

2.31 Residential Surge Protection 40

2.32 Power Quality Standards 41

2.33 Surge Suppression Standards Overview 41

2.34 Standard for Transient Voltage Surge Suppressors (SPDs) 42

2.35 National Electrical Code (NEC) and National Fire Protection Association (NFPA) 44

2.36 Research Focus 44

x

CHAPTER THREE: MATERIALS AND METHODS 45

3.1 Site and location of the Study 45

3.2 Experimental Methods 52

3.3 Experimental Procedure 52

3.3.1 Experimental Procedure No. 1 53

3.4 Data presentation 54

3.5 Data Bank Presentation from 2013 - 2015 54

3.6 Experimental Procedure NO. 3 58

CHAPTER FOUR: RESULTS AND DISCUSSION 61

4.1 Lightning Surge Stroke Data obtained for Six Residences 61

4.2 Lightning Stroke Data Characteristics 63

4.3 Arresters Failure Rates on Transmission Lines and their Effects 64

4.4 Findings of the study 68

4.5 Contributions to Knowledge 69

CHAPTER FIVE: CONCLUSION AND RECOMMENDATIONS 70

5.1 Conclusion 70

5.2 Recommendations 70

REFERENCES 72

xi

LIST OF TABLES

Page

Table 2.1 Sources of Surges 10

Table 3.1 Technical Characteristics of the used surge Arresters 48

Table 3.2 Surge data; April to October, 2013 50

Table 3.3 Surge data; March to October, 2014 50

Table 3.4 Surge data; March to October, 2015 51

Table 3.5 Positive Lightning from 2013 to 2015 52

Table 3.6 Negative Stroke from 2013 to 2015 53

Table 3.7 F.F.R% July – August, 2013 55

Table 3.8 F.F.R% August – September, 2014 55

Table 3.9 F.F.R% August – September, 2015 55

Table 3.10 Average F.R.R. for Regional Interval 56

xii

LIST OF FIGURES

Page

Figure 2.1 Nature of Lightning Strokes 9

Figure 2.2 Typical utility capacitor switching transient Characteristics

reaching 134% voltage, observed up line from the capacitor 10

Figure 2.3 Feeder current characteristics associated with Capacitor switching event 11

Figure 2.4 Dynamic overvoltage characteristics during transformer switching 12

Figure 2.5 Lightning Flash Density Map 13

Figure 2.6 Typical Lightning Surge Current 14

Figure 2.7 Voltage Waveform for Capacitor Switching Transient 15

Figure 2.8 CWG 8/20 μs Current Waveform 29

Figure 2.9 Protected Equipment 29

Figure 2.10 Parallel Connected SPD 31

Figure 2.11 Series Connected Filter 31

Figure 2.12 Protected Equipment 32

Figure 2.13 Silicon Avalanche Diode 34

xiii

Figure 2.14 Number of Test Occurrences before Failure 35

Figure 2.15 Three-Stage Hybrid Signature Circuit 35

Figure 3.1 Basic Structure of the Power System Network in Ajaokuta 44

Figure 3.2 Location of SPD in the switchboard (in parallel) 48

Figure 3.3 Cross-section drawing view of a polymer housed Surge arrester 48

Figure 3.4 Schematic Diagram of Experiment No 1 49

Figure 4.1 Stroke Peak Current; April to October 2013 57

Figure 4.2 Stroke Peak Current; March to October 2014 58

Figure 4.3 Stroke Peak Current: March to October 2015 58

Figure 4.4 Stroke Peak Current Percentage (Positive lightning stroke) 59

Figure 4.5 Stroke Peak Current Percentage (Negative Polarity) 60

Figure 4.6 Region 1 %FFR July to August 2013 61

Figure4.7 Region 2 %FFR August to September 2014 61

Figure4.8 Region3 %FFR August to September 2015 61

Figure 4.9 Tower Footing Resistance (OHM) 62

Figure 4.10 Arrester Interval (KM) 63

xiv

LIST OF PLATES

Page

Plate 1.1 Ajaokuta Nigeria Latitude and Longitude 6

Plate 2.1 Circuit Breaker Failure Caused by surge Voltage 16

Plate 2.2 Copper Busbar Melted by Surge Current 17

Plate 2.3 Circuit Board Damaged Caused by Surge Voltage 17

Plate 2.4 Micro Circuit Damage Caused by Surge Voltage 17

Plate 3.1 Ajaokuta Nigeria latitude longitude 43

Plate 3.2 Step for grid Lines 44

Plate 3.3 Main Step –Down Substation I 44

Plate 3.4 Surge Protector 45

Plate 3.5 Earth Ground Tester (Fluke 1625) 45

Plate 3.6 Meter Board of Transmission Station 46

Plate 3.7 Main control Board of Transmission Station 47

Plate 3.8 Export and Import Power at Transmission Station 47

xv

LIST OF ABBREVIATIONS

µsec Micro-second

EMI Electromagnetic Interference

FPRF Fire Protection Research Foundation

GDT Gas Discharge Tube

GPR Ground Potential Rise

Hz Hertz

IEC International Electro-technical Commission

III Insurance Information Institute

kA Kilo-Amperes

khz Kilo-hertz

L-G Line to Ground

L-L Line to Line

MCOV Maximum Continuous Operating Voltage

MOV Metal Oxide Varistor

NEC National Electrical Code

NEMA National Electrical Manufacturers Association

xvi

NFPA National Fire Protection Association

N-G Neutral to Ground

NIST National Institute of Standards and Technology

NLDN National Lightning Detection Network

PU Per Unit

SAD Silicon Avalanche Diode

SCCR Short Circuit Current Rating

SPD Surge Protective Device

TOV Temporary Overvoltage

TVS Transient Voltage Surge Suppressor

UL Underwriter’s Laboratories

VPR Voltage Protection Rating

1

CHAPTER ONE

INTRODUCTION

1.1 Background to the Study

Degradation, disruption and destruction are three “Ds” that affect power quality. Electrical

power disturbances may be called a surge, sag, spike, swell, transient, fluctuation, interruption,

or electrical line noise. All these electrical power disturbances are abnormalities and deviations

from normal performance of voltage sources (Gustavo et al, 2003; Sukhdeo, 2013). These

Electrical power disturbances may last for a short period or a long time (continuous).

In general, a surge is a transient wave of current, voltage or power in an electric circuit. In power

systems in particular this is likely the most common context that we relate surges to a surge, or

transient is a sub cycle over-voltage with duration of less than a half-cycle of the normal voltage

waveform. A surge can be either positive or negative polarity, can be additive or subtractive

from the normal voltage waveform, and is often oscillatory and decaying over time. Surges or

transients are brief over-voltage spikes or disturbances on a power waveform that can damage,

degrade, or destroy electronic equipment, industrial, or manufacturing facility, commercial

building. Transient can reach amplitudes of tens of thousands of volts. Surges are generally

measured in microseconds and can be internal over voltages or external over-voltages (Khalid,

2011; Teru, 2010).

Internal over voltages originate in the system itself and may be transient, dynamic or stationary.

Those of a transient nature will have a frequency unrelated to the normal system frequency and

will persist a few cycles only. They can be caused by the operation of circuit breakers when

switching inductive or capacitive loads, “current chopping” when interrupting very small

2

currents or by the sudden grounding of one phase of a system operating with insulated neutral

(Hasssan, 2017 and Makinde et al, 2014).

Approximately 70% of electrical threats are internally generated and the remaining 30% of

issues are external over voltages that can be caused by atmospheric discharges such as static

charges or lightning strokes and are therefore not related to the system (Nema, 2014). They are

often of such magnitude as to cause considerable stress on the insulation and, in the case of

lightning will vary in intensity depending on how directly the line is struck , i.e., directly by the

main discharge, directly by branch or streamer, or by induction due to a flash passing near to

but not touching the line. Power quality is measured by the interaction of electric power with

electrical equipment (Dharmender, 2014; Mehdi et al, 2014).

This thesis is to ensure an uninterrupted supply of electricity that is (power quality) in Ajaokuta

power system network. High quality power can be achieved by ensuring that wiring, grounding

and bonding are up to standards. Once this is verified then the right power quality device is

selected such as Surge Protective Devices (SPDs), low-pass filters, data and signal line

protectors to prevent damage from surges and electrical line noise.

1.2 Justification for the Study

Surges or over voltages have caused stresses, disruption and damages to numerous equipment

and gadgets in Ajaokuta power system network, such as high and low voltage induction motors,

synchronous motors, transformers, circuit breakers, reactors, capacitor banks, generators,

contactors, relays, etc. Khalid (2011) presents the power quality problems, issues, such as power

surge related international standard, effect of power quality problem in different apparatuses

and methods for its correction. Iit-Bhu (2014) presents investigation of different types of

premature failures that are observed during various full-scale testing of transmission line towers

and their results are discussed in detail.

3

Importance of design assumptions and connection detailing in overall performance of towers

were studied (MCoy, 2013). Due to the opening or closing of circuit breakers and disconnect

switches in Gas Insulated Substations (GIS), especially in the pumped storage power stations,

Very Fast Transient Over-Voltages (VFTO) are generated (Sukhdeo, 2013). The main causes

of over voltages in power system are switching and lightning. The over voltages can damage

the insolation of lines and equipment connected to the power system. In other to protect

insulations and equipment of the power systems from the damaging effects of lightning over

voltages, metal oxide surge arresters have been used.

Because of dynamic behaviour of the surge arresters, they cannot be simulated using non-linear

resistors. Therefore, several models are proposed to simulate the dynamic properties of surge

arresters. IEEE and pinceti models are the main models proposed that are for the simulation of

the dynamic behaviour of surge arresters. In this thesis, for identification of surge arrester

parameters and a novel algorithm have been proposed and then a comparison among IEEE

model and pinceti model has been investigated (Mehdi et al, 2014). Mungkung et al. (2007)

investigated the temporary increase in voltage in the transmission line system. Lightning is the

most harmful for destroying the transmission line and setting devices so it is necessary to study

and analyze the temporary increase in voltage for designing and setting the surge arrester. This

analysis describes the lightning wave in transmission line with 115 kV voltage level in Thailand

by using ATP/EMTP program to create the model of the transmission line and lightning surge.

Because of the limit of this program, it must be calculated for the geometry of the transmission

line and surge parameter and calculation in the manual book for the closest value of the

parameter.

On the other hand, for the effects on surge protector when the lightning comes, the surge arrester

model must be standardized as metropolitan electrical authority’s standard. The researcher

4

compared the real information to the result from calculation Shehab (2013) presents an

overview of how the lightning strikes and their effects on power distribution systems can be

modeled, where the results gave an understanding of how to eliminate the devastating impact,

caused by lightning, by using lightning arresters.

Many conventional protective devices installed for protection of excessive fault current in

electric power systems, especially at the power stations are the circuit breakers, tripped by over-

current protection relay (Okundamiya et al., 2009). These devices the response-time delay that

allows initial two or three fault current cycles to pass through before getting activated.

Superconducting Fault Current Limiter (SFCL) is innovative electric equipment which has the

capability to reduce fault current level within the first cycle of fault current. The application of

the Fault Current Limiter (FCL) would not only decrease the stress on network devices, but also

can offer a connection to improve the reliability of the power system (Makinde et al., 2014).

This research is investigate the effects of electrical surge and the possible remedy in Ajaokuta

power system network. Consideration of three basic approaches which includes; experimental

investigation would be carried out on lightning surges in the distribution lines in some

residences of Ajaokuta Power System Network, to develop data bank for lightning stroke and

magnitude of cloud to earth lightning strokes to be used as a factor in determining the required

maximum surge current of SPDs. For this reason, the maximum surge current of an SPD could

be selected based on perceived lightning stroke levels. In addition, a test would be carried out

on the three 132kV transmission lines of Ajaokuta power interconnected system to determine

the variation of surge arresters failure probability with tower footing resistance for each of the

three case studies to be analyzed.

5

1.3 Objectives of the Study

The overall aim of this study is to investigate the effects of electrical surge and the possible

remedy in Ajaokuta power system network.

The specific objectives are to:

(a) identify various causes of lightning stroke and highlight various associated effect in

electrical equipment;

(b) determine the lightning stroke intensity and magnitude;

(c) analyse the data obtained base on set time duration and area under investigation;

(d) determine the variation of surge arresters failure probability with Tower Footing

Resistance (TFR) at 132kV operation transmission lines of Ajaokuta and;

(e) design a surge protection scheme (mechanism) for equipment.

1.4 Scope and Limitation

This research focuses on the effects of electrical surge and it remedy in Ajaokuta power system

network in Kogi State, Nigeria. It involves recent surge data collection and analysis in the

distribution and transmission units to determine the SPDs locations and ratings required in

facilities and residences.

6

1.5 Research Methodology

Experimental investigation will be carried out in this study in order to achieve the desired

objectives of this study as follows:

(a) an experimental investigation would be carried out on lightning surges that flow in the

distribution lines in some residences of Ajaokuta Power System Network. Lightning

surge detectors shall be installed in six (6) residences and monitored for three years,

2013 to 2015 to ascertain the effects of lightning surge on the distribution lines;

(b) data Bank Presentation From 2013 – 2015: This data Bulletin would provide objective

data about lightning stroke intensity based on a scientific study. Since 1995 the power

system network of Ajaokuta has set up the lightning data bank to collect data on the total

number and magnitude of cloud to earth lightning strokes to be used as a factor in

determining the required maximum surge current of Surge Protective Devices (SPDs).

For this reason, the maximum surge current of an SPD could be selected based on

perceived lightning stroke levels; and

(c) tests would be carried out on the three 132kV operation transmission lines of Ajaokuta

power interconnected system to determine the variation of surge arresters failure

probability with Tower Footing Resistance (TFR) for each of the three case studies to

be analysed; and to determine the arrester failure probability interval based on the

transmission line, these lines shall be carefully selected due to: their high rate of failure

during thunderstorms, their sufficient sufficient time in service and the significant

different characteristics, such as ground flash density and the tower footing resistance

which exist through their lengths, since they run through the same region.

7

1.6 Thesis Arrangement

Chapter one is Introduction, which consist of Background to the study, justification of the study,

objectives of the study, scope and limitation, research methods. Chapter two is the Literature

Review, chapter three contains Materials and Method, which consist of three experimental

procedures. Chapter four contains Result and Discussion, findings, contributions to the

knowledge, and chapter five contains conclusion and recommendations.

8

CHAPTER TWO

LITERATURE REVIEW

2.1 Surge Protection Fundamentals

This section provides an overview of electrical surges and protection against the effects of these

destructive surges.

2.2 Sources of Surges

A surge is a transient wave of voltage or current (Khalid, 2011). The duration is not tightly

specified but is usually less than a few milliseconds. The following are typical sources of

surges:

(a) Lightning (External to the network).

(b) Utility switching, including capacitor switching (Internal to the network).

(c) Equipment switching and switching inductive loads within a facility (Internal to the

network).

Table 2.1 summarizes the effects of these various surge sources while Figure 2.1 shows positive

and negative Lightning Strokes.

9

Table 2.1: Sources of Surges

Source of Surge Peak Voltage Magnitude Frequency of Occurrence Comments

Lightning <1,000 volts to > 40,000

volts with average of about

20,000 volts

Weekly to rarely,

depending on location

Magnitude depends on proximity of

stroke to facility and coupling of

stroke to facility electrical system.

Voltages within a facility above

6,000 volts are unlikely due to

flashover.

Utility Capacitor and

System Switching

Up to 1,300 volts on a 480

volt system

Never to several times a day,

depending on utility

Capacitors might or might not be

installed nearby.

Facility Equipment

Switching

Up to 2,000 volts on a 480

volt system

Many times a day Magnitude is small compared to

lightning-induced transients, but

switching can occur frequently.

Source: (NEMA, 2014)

10

Figure 2.1: Positive and Negative Lightning Strokes.

The capacitor switch contacts closed at a point near the system voltage peak. This is a common

occurrence for many types of switches because the insulation across the switch contacts tends

to break down when the voltage across the switch is at maximum value. The voltage across the

capacitor at this instant is zero, since the capacitor voltage cannot change instantaneously, the

system voltage at capacitor location is briefly pulled down to zero and rises as the capacitor

begins to charge toward the system voltage. Because the power system source is inductive, the

capacitor overshoots and rings at natural frequency of the system (Dharmender, 2014).

Figure 2.2 to Figure 2.4 shows typical transient characteristics

11

Figure 2.2: Typical utility capacitor switching transient characteristic reaching 134% voltage,

observed up line from the capacitor (Emerson, 2013).

Figure 2.3: Feeder current characteristic associated with capacitor-switching event.

12

Figure 2.4: Dynamic overvoltage characteristic during switching.

This form of dynamic overvoltage problem (shown in Figure 2.4) can often be eliminated

simply by not energising the capacitor and transformer together. Energizing the transformer

first and not energizing the capacitor until load was about to be connected to the transformer

(Shehab, 2013).

The devices used to protect against surges are referred to as Surge Protection Devices (SPDs).

A surge of duration longer than a few milliseconds is referred to as a swell or Temporary

Overvoltage (TOV) and requires a different type of protection design; SPDs can fail if exposed

to long duration TOVs.

2.3 Lightning Surges

Lightning-induced surges into an electrical system are caused by lightning strokes to the ground,

towers, or structures. A lightning stroke can produce peak discharge currents ranging from a

few thousand amperes to 200,000 amperes, or higher. This lightning discharge current is

developed within a few microseconds and typically discharges most of its energy within a

13

millisecond. The location where a lightning stroke will occur is not completely predictable;

cloud-to-ground strokes have been recorded almost 20 miles from the base of the source cloud.

The frequency of lightning strokes varies with geographical location. Figure 2.5 shows the

Vaisala lightning flash density map for the United States. Lightning strokes are a rare

occurrence in Portland Oregon while they can be a routine event in Orlando Florida (Emerson,

2014).

Figure 2.5: Lighting Flash Density Map. (Emerson Power Network)

2.4 Schneider Electric Surge Experimental Investigation.

A single intense storm can produce thousands of lightning strokes. Schneider Electric Data

Bulletin DB03A, Surge Protection: Measured Lightning Stroke data, describes a July 2000

storm in Tampa Florida that recorded 33,863 lightning strokes during a 14 hour period. Both

positive and negative polarity strokes were detected (Teru, 2010).

For this Tampa Florida storm, 2% of the lightning strokes produced surge currents greater than

60 kA. A few lightning strokes approached 200 kA. But, over 80% of the lightning strokes

produced surge currents less than 60 kA. This data correlates reasonably well with a report

14

from the IEEE Lightning and Insulator Subcommittee of the T&D Committee that showed a

50% probability of less than about 20 kA, a 95% probability of less than about 60 kA, and a

99% probability of less than about 100 kA. A lightning-induced surge is a high magnitude

impulsive transient of very short duration, typically measured in microseconds or milliseconds.

But, during this short period, significant system damage can occur, Figure 2.6 shows an

example.

Figure 2.6: Typical Lightning Surge Current (Schneider, 2011)

2.5 Utility Switching

Utility switching is a broad term that applies to how utility configurations are occasionally

changed. Each switching operation can produce a transient that can momentarily exceed

equipment voltage ratings. Although the transients are not as large in magnitude as a nearby

lightning stroke, switching transients can cause cumulative damage to electrical equipment.

And, if switching results in a Temporary Overvoltage (TOV), it can also cause SPD failure

(Mungkung et al, 2007).

Time (usec)

C

urre

nt (

kA )

0 12030 60 90

0

20

10

15

Capacitor switching is a special case of utility switching. Capacitors might also be switched

periodically by large industrial power customers. Capacitor switching can be a common

everyday event, occurring several times each day in some locations, as the utility adjusts system

voltage and compensates for inductive loads (Kostas, 2007; Osahenvemwen et al., 2018).

Capacitor switching causes a surge voltage by the following process. The voltage across a

capacitor is zero before it is switched into the circuit. As a capacitor is switched, there is a

momentary short circuit across the capacitor as the system voltage is applied to the zero voltage

of the capacitor. At the capacitor location, the bus voltage momentarily experiences a step

change to zero volts. After the initial step change, the voltage recovers and then overshoots as

the system eventually return to its steady state value. Thereafter, the system oscillates until

damping returns the voltage to its steady-state value (Okundamiya and Nzeako, 2010). During

the initial oscillation period, the peak transient voltage can approach 200 percent of the normal

peak system voltage (common peak surge voltages can range from 150 percent to 180 percent

of normal).

Another factor contributing to the transient is the inrush current as the capacitor energizes; this

inrush current IEEE C62.41.1,Guide On The Surge Environment In Low- Voltage (1000V and

Less) AC Power Circuit, uses the terms “direct flash”, “near flash”, and “far flash” to distinguish

between lightning strokes and how they induce a surge on a facility can have a resonant

frequency anywhere from 300 Hz to 1,000 Hz depending on the installed inductance and

capacitance, which adds to the system oscillations. Figure 2.7 shows an example of a capacitor

switching transient (Gustavo et al, 2003)

16

Figure 2.7: Voltage Waveform for Capacitor Switching Transient

Capacitors inside a facility can resonate with the switching-induced oscillations, thereby

magnifying the peak voltage and extending the period until the voltage returns to normal.

Magnification of the switching transient can occur if the utility switched capacitor bank is much

larger than the facility capacitor bank and there is little resistive load (mostly motor load) to

provide a damping mechanism (Gustavo et al, 2003).

2.6 Facility Internal Switching

Switching equipment in an electrical system resulted in inductive energy that creates a

momentary voltage surge. Even minor switching can cause a significant inductive surge in the

system. This type of switching accounts for the overwhelming majority of switching transients.

However, the magnitude of this type of surge is much smaller than for lightning-induced surges

(Makinde et al, 2014).

2.7 Surge Effects

Surges can cause equipment damage. Large surges damage equipment and other components

in the electrical distribution system. Smaller surges can cumulatively damage equipment and

can cause nuisance equipment tripping. Both surge voltage and current can be damaging. In

the case of lightning strokes, the surge can be carried into a facility via all of the connected

1.5 to 1.8 pu (150 to 180% )

17

conductive paths. The following Plates show examples of damage caused by surges (Emerson,

2014).

Plate 2.1: Circuit Breaker Failure Caused by Surge Voltage

Plate 2.2: Copper Bus-bar Melted by Surge

18

Plate 2.3: Circuit Board Damage Caused by Surge Voltage

Plate 2.4: Micro Circuit Damage Caused by Surge Voltage

Electronic equipment is susceptible to surge transients. Computers and internet-enabled

devices are not only at risk in the power supply but can be damaged by surges that propagate

into the equipment via the communications link (Mungkung et al, 2007).

19

2.8 The Benefits of Power Quality and Protection Products

To maintain high-quality power within the facility, it must start with best engineering practices

foundation. This begins by ensuring that the wiring, grounding, and bonding are up to standards.

Once this is verified, elements such as Surge Protection Devices (SPDs), can be installed, low-

pass filters, and data and signal line protectors to prevent damage from surges and electrical

line noise. To improve the facility’s uptime, Uninterruptible Power Supplies (UPS) should be

considered, voltage regulators, and generators (Teru, 2010).

2.9 The Importance of Protecting the Power Network.

Safety agencies recognize the Need for Pnwer Quality Products for Lightning/surge protection

considerations: a properly rated surge protective device should be applied to each individual or

set of electrical conductors (e.g., power, voice, and data) penetrating any of the six sides forming

a structure (Gustavo et al, 2003).

2.10 Practice for Powering and Grounding Electronic Equipment

If lightning strikes occurs on or near overhead electric power or telephone line, a large current

will be injected into or induced in the wires, and the current can do considerable damage both

to the power and telecommunications equipment and to anything else that is connected to the

system.

Surges can have many effects on equipment, ranging from no detectable effect to complete

destruction, electronic devices can have their operation upset before hard failure occurs. The

semiconductor junctions of electronic devices are particularly susceptible to progressive

deterioration, few solid state devices can tolerate much more than twice their normal rating.

Furthermore, data processing equipment can be affected by fast changes in voltage with

relatively small amplitude compared to the hardware-damaging over-voltages.

20

For large surge currents, this diversion is best accomplished in several stages. The first diversion

should be performed at the entrance to the building, a second protective device at the power

panel.

2.11 Potential impact of Electromagnetic Interference (EMI)

Depending on the severity of the surge and the susceptibility of the equipment, three types of

occurrences are possible, data disruption, hardware stress, and hardware destruction.

(a) EMI, Type I, signal-data disruption: Signal carrying circuits are susceptible to surge

interference via conduction, inductive and capacitive coupling, and electromagnetic

radiation (Kostas, 2007).

(b) EMI, Type II, gradual hardware stress and latent failures: A single lightning or

switching surge often causes immediate, but not readily apparent physical damage to

semiconductor devices. This damage then finally appears at some later time.

(c) EMI, Type III, immediate hardware destruction: The third possible impact of surges

is the immediate obvious and total destruction of hardware components in a single

incident.

(d) Surge suppressors: Effective surge protection requires the coordinated use of large-

capacity current diverting devices at the service entrance followed by progressively

lower voltage-clamping devices.

(e) Lightning/surge protection considerations: A properly rated surge protective device

should be applied to each individual or set of electrical conductors (e.g., power, voice,

and data) penetrating any of the six sides forming a structure.

21

(f) Selection: Surge protective devices for three phases, four-wire circuits are generally

recommended to be connected in all combinations of line-to-line, line-to neutral, line-

to-ground, and neutral-to-ground.

(g) Installation: Recommended installation practice is for all lead lengths to be short and

shaped to minimize open loop geometry between the various conductors by twisting all

the phase, neutral, and equipment grounding conductors together; and by avoiding any

sharp bends and coils in the conductors.

(h) Service entrance surge protection: Facilities housing electronic load equipment of

any type should have service entrances equipped with Category “C” surge protective

devices, as specified in IEEE Std. C62.41-1991 (Shehab, 2013).

2.12 Electrical System Surge Protection

Recommended that additional surge protective devices of listed Category ‘B’ or Category ‘A,’

as specified in IEEE Std. C62.41-1991, be applied to downstream electrical switchboards and

panel boards, and panel boards on the secondary side of separately derived systems if they

support communications, information technology equipment, signalling, television, or other

form of electronic load equipment.

(a) UPS system surge protection: It is recommended practice that both the input circuit

to the UPS and the associated bypass circuits (including the manual bypass circuit) be

equipped with effective Category ‘B’ surge protective device.

(b) Data/communication systems surge protection: Electronic equipment containing

both ac power and data cabling should also be properly protected via surge protective

devices on both the ac power and data cables.

22

(c) Exterior building systems and piping lightning/ surge protection: All exterior

mechanical systems (e.g., cooling towers, fans, blowers, compressors, pumps, and

motors) should be considered targets for a lightning strike.it is recommended practice

to individually provide surge protective device protection on both the power input and

data circuits connected to all such equipment.

2.13 Surge Arresters

Surge arresters are designed to be insulators for nominal operating voltage, conducting at most

a few milliamperes of current and good conductors when the voltage of the line exceeds design

specifications to pass the energy of the lightning strike to the ground (Teru, 2010).

Several different types of arresters are available (e.g. gapped silicon carbide, gapped or non-

gapped metal-oxide) and all perform in a similar manner: they function as high impedances at

normal operating voltages and become low impedances during surge conditions. Even though

a great number of arresters which are gapped arresters with resistors made of silicon carbide

(SiC) are still in use, the arresters installed today are almost all metal-oxide (MO) arresters

without gaps, something which means arresters with resistors made of metal-oxide. The

distinctive feature of a metal-oxide arrester is its extremely non-linear V–I characteristic,

rendering unnecessary the disconnection of the resistors from the line through serial spark gaps,

as it is found in the arresters with SiC resistors.

The most significant technical characteristics of surge arresters according to the IEC 60099-4

are:

(a) Continuous operating voltage (Uc): Designated rms value of power frequency

voltage that may be applied continuously between the terminals of the arrester.

23

MCOV of the arrester must be higher than the maximum continuous operating

voltage of the system.

(b) Rated voltage: Maximum permissible rms value of power frequency voltage

between arrester terminals at which is designed to operate correctly under

temporary over voltages.

(c) Discharge current: Impulse current which flows through the arrester.

(d) Residual voltage (Ures): Peak value of the voltage that appears between arrester

terminals when a discharge current is injected.

(e) Rated discharge current: Peak value of lightning current impulse, which is used

to classify an arrester.

(f) Lightning impulse protective level: Voltage that drops across the arrester when

the rated discharge current flows through the arrester.

(g) Energy absorption capability. Maximum level of energy injected into the

arrester at which it can still cool back down to its normal operating temperature.

Standards do not define energy capability of an arrester. In IEC exists the term

line discharge class, but since this is not enough information, various

manufacturers present thermal energy absorption capability in kJ/kV (Uc),

defined as the maximum permissible energy that an arrester may be subjected

to two impulses without damage and without loss of thermal stability.

24

2.14 The difference Between the Terms “Surge Arrester” and “Transient Voltage

Surge Suppressor (TVSS)

These terms are often used interchangeably and rather loosely. However, the two terms have

different meanings as determined by the National Electrical Code (NEC) (www.nfpa.org), their

UL listing, and applicable IEEE/ANSI standards.

Surge arresters less than 1000 volts have been called secondary surge arresters. Going forward

they are now considered a Type 1 SPD and listed in Article 285 of the NEC. Surge arresters

were originally developed and applied to the power distribution system to protect utility

supplied equipment and building wiring. Surge arresters were intended to protect the system

structure and not necessarily the connected equipment and loads.

Under ANSI/UL 1449-2006, the main difference between a TVSS and a secondary surge

arrester is the location within the electrical distribution system which their respective Listing

allows them to be installed. Secondary surge arresters (now known as Type 1 SPDs) are

generally intended to be installed on the line side of the main service disconnect overcurrent

device (service equipment) Their main purpose is to protect insulation levels of the electrical

system. A TVSS (now known as a Type 2 SPD), by code (NEC 2008), must be installed on the

load side of the main service disconnect overcurrent device (service equipment) and be 1000

volts or less. Their main purpose is to protect the sensitive electronics and microprocessor based

loads by limiting the transient voltage (Mehdi et al, 2014).

Under ANSI/UL 1449-2006, both Type 1 SPDs and Type 2 SPDs are marked with a Short-

Circuit Current Rating (SCCR). This rating is required by code to determine if an SPD is

suitable for installation at a given location within the electrical system. Prior to ANSI/UL 1449-

2006, there was no requirement for this rating on Type 1 SPDs. Under ANSI/UL 1449-2006,

all SPDs are tested to evaluate the suitability of their end-of-service condition given various

25

levels of available fault current when subjected to abnormal over voltages. Prior to ANSI/UL

1449-2006, only Type 2 SPDs were required to undergo this evaluation.

2.15 Protective Devices

Within the three types of protection described above, there are many devices designed for

specific applications.

2.15.1 One-Port Parallel-Connected Devices

This design is to limit high-voltage spikes to a level acceptable to most electronic equipment.

These are considered the first line of defense, using components placed in parallel with the line.

These devices are typically installed at service entrances, larger distribution panels, branch

panel boards, and motor control centres.

2.15.2 Surge Protective Device (SPD)

SPDs are parallel-connected, non-linear protective devices for limiting surge voltages on

equipment by discharging, bypassing, or diverting surge current. They prevent continued flow

of follow current and can repeat these functions as specified.

Domestically, the term SPD is used to describe both Surge Arresters and Transient Voltage

Surge Suppressors (TVSS). However, internationally, the term SPD is synonymous with the

IEC 61643-1 definition that describes a surge component, not a stand-alone device. This

component has no short-circuit current rating so it requires additional fusing and must be

mounted inside an enclosure (Khalid, 2011).

2.15.3 Integral SPD Issues

The major electrical panel manufacturers offer some form of surge protection, integrated

directly within their power distribution or branch panels. Product performance, ease of

installation, and less wall space are some of the advantages that have been touted over externally

26

mounted surge devices. While there may be some credibility to these claims, the end user should

also be aware of the risks involved with integrating SPDs directly into the power distribution

equipment (Emerson, 2014).

The first risk is the failure of the SPD within the distribution equipment. When SPDs fail and

the internal MOVs reach an end-of-life condition, they can create a significant amount of power

which is dissipated in the form of heat. This heat can be so intense that it can cause significant

collateral damage to the distribution equipment.

Additionally, when that failed SPD needs to be repaired in the field, the service technician has

two options: remove all power from the panel; or remove only the power feeding the SPD,

leaving the rest of the panel energized. The first option, which is the safest, may not be feasible

if the connected loads cannot be shut off due to their criticality. Then, considerable measures

need to be taken to work in a live panel. Special gear must be worn and tools used to protect the

technician from shock, electrical faults and potential arc flash (Mungkung et al, 2007).

Performance is another major area of concern when integrating an SPD. Even though

performance is touted as an advantage over externally mounted SPDs, in reality it may be far

worse. For safety reasons, UL dictates the location of the SPD within the gear. This can result

in the device being mounted a long distance away from the connection points. The neutral bus

bar for example may be as far as four feet away from the installed SPD. This would cause the

performance to be considerably worse than an optimally placed, externally mounted SPD.

2.15.4 Hybrid Design

Hybrid surge protection devices combine at least two types of surge components – typically

MOVs and SADs. An effective hybrid design limits the amount of surge current through the

SAD module to an acceptable level and diverts the remaining surge current through the MOV

27

module – sharing the surge. When properly designed, a hybrid SPD will outperform an SPD

that uses only MOVs. However, an effective hybrid SPD requires significant engineering.

Some of the pitfalls of a hybrid approach include:

(a) Designs with all components on line at all times can result in component failure during

surge or overvoltage events.

(b) Some components may not be appropriate for the application of the end unit.

(c) Some manufacturers may claim a capacitor constitutes a hybrid design, but this may not

be the case.

The key to a successful hybrid design is to maximize each individual component’s strengths

and transition away from the weaknesses (NEC, 2014).

2.15.5 Two-Port (Series-Connected) Devices

Filtering/line conditioning units are designed to provide clean AC power by helping to eliminate

or dramatically reduce high-voltage transients and low-voltage electrical line noise that degrade

microprocessor-based equipment. They are generally applied in front of or in series with critical

load or industrial equipment, such as PLCs and motion control systems (Dharmender, 2014).

2.16 Active Tracking Filter (ATF)

Active Tracking Filters offer a comprehensive level of protection by providing clean AC power

for highly sensitive equipment. Composed of series inductors, shunt absorbing components, and

fast-reacting surge protective components, these hybrid devices eliminate low-level noise as

well as protect against destructive high-energy events. Ideal applications include

microprocessor-based equipment such as programmable logic controllers, motion control

equipment, broadcast transmitters, and computers (NEC, 2014; Okundamiya, 2018).

28

2.16.1 Harmonic Filter

A harmonic filter is also a series-connected filter, but is designed to attenuate frequencies that

are a multiple of the fundamental 50 Hz frequency, such as the 5th, 7th, and 9th harmonic

(Kostas , 2007).

2.17 Surge Protection with Filtering

Switching pulses and subsequent re-strikes in multi-stroke lightning can produce very fast

transients, with rise times in the fraction of microseconds. These can capacitive and inductively

couple to equipment and cause induced over-voltages. To eliminate such fast spikes, it is usual

to incorporate a level of filtering in the SPD device. This can simply be a capacitor connected

in parallel across the SPD’s output, or it might be a true series LC filter, often called a two port

SPD where there are distinct sets of input and output terminals.

SPDs incorporating series LC filters generally provide superior filtering performance, however

they are more expensive and need to be sized for the continuous load current. It should be point

out that SPDs with so called “filters” would more accurately be described as wave-shaping

devices as the filter’s prime role is to slow the very fast rate of voltage rise dv/dt rather than to

“filter” (Hasssan, 2017).

2.18 Attenuation in an SPD

Generally this applies to surge protective devices (SPDs), which incorporate filters. The dB of

attenuation stated is usually the point at which the filter has reduced the incident transient by

3dB (or the voltage by a factor of 20).

A more effective surge filter will have a higher dB at a lower frequency. For example, an SPD

with 60dB attenuation at 30 kHz is more effective than a filter with 60dB at 100kHz. The

attenuation can also apply to in-line, series connected; type SPDs used in data communications.

29

In such a case the SPD should have a low attenuation (dB number) at the operating frequency

of the data system. For SPDs protecting ac power circuits, it is common for SPD manufacturers

to quote the dB result at 100kHz, rather than the frequency at which 3dB attenuation occurs.

Rather than quoting a single figure, a graph of frequency response from 10 kHz to 1MHz is

more useful. Performance above 1MHz is of little value as at these higher frequencies large

variations will occur between installations. While many specifications call for 60-80dB at 100

kHz, little practical performance benefit is obtained beyond 30 dB.

The subject of SPDs with filters is not complete without reiterating the point made in the

preceding the term “filter” when applied to a power SPD is confusing. Such “filtering” devices

would more appropriately be described as wave shaping devices and their performance

expressed by the reduction in dv/dt, which they present to the steep rising, edge of the surge,

rather than in dBs. Filters per sec are linear attenuation whilst SPDs with filtering components

exhibit a non-linear action and slope attenuation (Sukhdeo, 2013).

2.19 Using Active Tracking Filters To Control Low- And High-Voltage Transients

Low-voltage noise is caused by everyday events such as turning on appliances or motors.

Although less dramatic than high-voltage transients, the long-term effect of these frequent

disturbances can be just as damaging. Filtering systems, such as our Active Tracking FiltersTM,

provide clean AC power by eliminating lower-voltage noise (Mehdi et al, 2014).

Ideally installed at specific sensitive loads or branch panels, or on individual pieces of

equipment. This is a rather fancy term given to a Surge Protective Device (SPD) which includes

Radio-Frequency Interference (RFI)/Electromagnetic Interference (EMI) filtering. All SPDs

with capacitive RFI/EMI filtering exhibit sine wave tracking abilities (Emerson, 2014).

30

2.20 CWG 1.2/50 μs Voltage Open-circuit Surge Waveform

Open waveform characteristics:

T = Time B - Time A

T1=1.67T = 1.2 μs± 30 %

T2 = 50 μs± 20 % Undershoot ≤ 30% of the crest.

Figure. 2.8: CWG 8/20μs Current Waveform

31

T = Time B - Time C

T1=1.25T = 8 μs± 30 %

T2 = 20 μs± 20 % Undershoot ≤ 30% of the crest.

Figure 2.9: Short-Circuit Characteristics Waveform

2.21 Filters with Air Cored Inductors

Series-installed Surge Protective Devices (SPDs), which comprise LC networks with a series

ferrite inductor in the line-side conductor, can experience saturation under the high current

levels during surge activity. Air gap inductors do not suffer from problems of saturation;

however they are more expensive to produce for the same figure of inductance than ferrite

wound inductors (Sukhdeo, 2013).

32

2.22 Voltage Regulator

Voltage regulators control the output voltage, eliminating voltage sags and swells in the input

voltage that lasts from 15 milliseconds to one-half second. They are typically inexpensive

feedback-controlled transformers.

2.23 Line Conditioner

A line conditioner contains multiple protection devices in one package to provide, for example,

electrical noise isolation and voltage regulation.

2.24 The difference between series connected filters and parallel connected SPDs

Parallel devices protect equipment from high-energy transient diversion and impulse clamping

from internally and externally generated transients. These SPDs provide protection from spikes

by limiting let-through voltage that could destroy downstream equipment.

Series filter technology protects from low-voltage noise caused by everyday events, such as

turning on appliances or motors, which cause long-term degradation of equipment. Filter

products are typically SPDs combined with inductors, capacitors, and resistors.

Parallel connected and series connected Active Tracking Filters™ (ATF), both are effective

power quality devices. This illustration shows connection diagrams for both types of systems.

The parallel connected device is tapped off the load side of a service panel. Typically, a

dedicated circuit breaker in the service or branch panel is used as the means of connection. On

the other hand, the series connected filter, also wired to the load side of the service panel, is

directly in line with the protected equipment (Dharmender, 2014).

33

Figure 2.10: Parallel Connected SPD and Series Connected Filter

Parallel SPDs protect against high-energy transients by limiting or clamping the surge voltage

and diverting transient surge currents away from the load. The technologies most commonly

used are Gas Discharge Tubes (GDT), Silicon Avalanche Diodes (SADs) and Metal Oxide

Varistors (MOVs). SPDs are voltage-dependent only and are sized based on the surge current

rating on the device.

On the other hand, series connected Active Tracking Filters™ use a low-pass circuit to protect

downstream equipment from high-frequency electrical line noise. ATFs are load dependent,

which means that the series element is sized to handle the maximum current draw of the load.

Inductors, together with the capacitors and resistors, form a circuit capable of absorbing a large

bandwidth of noise.

34

2.25 Using Surge Suppression to Control High-Voltage Transients

High-voltage transients, such as those caused by lightning or grid switching, are relatively rare.

However, they get more attention than low voltage events because their ability to cause

catastrophic damage is so dramatic. Surge suppressors provide protection from spikes by

limiting let-through voltage that could destroy down-stream equipment.

2.26 DC Low Voltage Surge Protection

Low voltage surge protection devices safeguard the integrity of data networks, communication

systems, and video lines from dangerous “backdoor” transients and currents. A three-stage

hybrid design approach is one method used to mitigate surges and “sneak currents” in order to

reduce expensive equipment downtime (Gustavo, 2003).

Figure 2.11: Protected Equipment

Pro

tect

ed E

qu

ipm

ent

35

2.26.1 DC Power Protection

Surge protection designed to protect the DC power going to cameras or other sensitive

equipment generally used in the security industry (Hasssan, 2017).

2.26.2 Video Line Protection

Surge protection devices designed to protect camera, television or computer equipment from

harmful surges that may be induced on to wires or cable lines. These devices may be used in

the security, telecom or traffic industry (Emerson, 2015).

2.26.3 Data Line Protection

Surge protection devices primarily designed to protect high-speed data transmission lines used

for network communication systems. Data lines typically travel throughout a facility and

sometimes even between buildings, leaving the system vulnerable to both externally and

internally generated transients (Kostas, 2007).

2.26.4 Signal Line Protection

Surge protection devices designed to protect signal lines from harmful surges. These devices

are typically used in the telecom industry to protect analogue and digital phone lines as well as

intercom systems. Other applications may include security lines and traffic signal lines

(Dharmender, 2014).

2.26.5 Silicon Avalanche Diode (SAD)

A semiconductor device that normally acts as an open circuit, but changes to a short circuit

when the trigger voltage exceeds a certain amount. The SAD is shown in Plate 2.5.

36

Plate 2.5: Silicon Avalanche Diode (SAD)

Advantages

(a) Clamping

(b) TOV susceptibility

(c) Usability

(d) Pulse power

Disadvantages

(a) Cost

(b) Availability

(c) Surge current

2.26.6 Fuse

A current limiting device, used in an electric circuit, containing a conductor that melts under

heat produced by an excess current, thereby opening the circuit.

2.26.7 PTC (Positive Temperature Coefficient)

Thermally sensitive resistors manufactured from semiconductor material. As the temperature

approaches a predetermined value, the resistance of the part begins to rise rapidly, and

eventually levels off. Thermal expansion of the material reduces the current to a safer level.

37

2.27 Comparisons – Fuse Vs. PTC

Both provide a means of disconnect from high current.

Figure. 2.12: Number of Test Occurrences before Failure

PTC = Positive Temperature Coefficient Thermistor

Figure 2.13: Three-Stage Hybrid Signature Circuit

2.28 Surge Protective Devices (SPDs)

Most SPDs is use for the applications covered by this report use Metal Oxide Varistors (MOVs)

to accomplish surge suppression in the electrical power system. MOVs exhibit nonlinear

resistance characteristics as a function of voltage. Within the MOV voltage rating, the

38

resistance usually exceeds 10,000,000ohms, but the resistance drops to less than 0.1ohm when

the MOV is exposed to an overvoltage, such as a transient voltage spike due to a nearby

lightning stroke. It is this characteristic that makes MOVs an effective protection element

(Mungkung et al, 2007)

The MOV is essentially a matrix of zinc oxide grain boundaries that have a nonlinear resistance

characteristic. The series combination of the boundaries defines the MOV voltage rating, the

parallel combination defines the total current that can be passed, and the bulk volume

determines how much energy that it can absorb. When an MOV is energized with an AC

voltage, resistive and reactive current flows through the highly capacitive disc.

Most SPDs are connected in parallel with the circuit and operate when a transient voltage

exceeds the voltage protection rating. Parallel surge protectors have little interaction with the

circuit under normal conditions (Sukhdeo, 2013).

A different technology is commonly used for communications lines, referred to as a Gas

Discharge Tube (GDT), which is a spark gap type of surge suppression device. When subjected

to a surge voltage, the gas discharge tube sparks over, thereby causing an arc to ground. The

hermetically sealed tubes used today can have a precise and repeatable turn-on voltage. Gas

discharge tubes consist of a spark gap in series with a resistance or varistance to limit the

discharge current to safe levels (Mehdi et al, 2014).

2.29 SPD Classification

UL 1449 classifies SPDs by type depending, in part, on their location in the system and their

level of internal protection:

(a) Type 1 – Permanently connected SPDs intended for installation between the secondary

of the service transformer and the line side of the service equipment overcurrent device,

39

as well as the load side, including watt-hour meter socket enclosures and intended to

be installed without an external overcurrent protective device. They must have

overcurrent protective devices either installed internally on the SPD or included with

it. While these are primarily intended for installation before the main service

disconnect, Type 1 SPDs can be installed in Type 2 and Type 4 locations such as

distribution panels, end-use equipment. Residential installations are often Type 1,

installed near the incoming meter.

(b) Type 2 – Permanently connected SPDs intended for installation on the load side of the

service equipment overcurrent device; including SPDs located at the branch panel.

While some will have internal overcurrent protective components, Type 2 SPDs can

rely on the service entrance overcurrent disconnect device for over current protection.

These SPDs can be installed in service equipment, distribution panels, and end-use

equipment.

(c) Type 3 – Point of utilization SPDs, installed at a minimum conductor length of 10

meters (30 feet) from the electrical service panel to the point of utilization, for example

cord connected, direct plug-in, receptacle type and SPDs installed at the utilization

equipment being protected.

(d) Type 4 – Component SPDs, including discrete components as well as component

assemblies.

40

2.30 SPD Ratings

SPDs are tested and rated in accordance with UL 1449. The following ratings are normally

provided for each model and size of SPD:

(a) Nominal voltage and frequency.

(b) Maximum continuous overvoltage (MCOV) – defines the voltage at which the SPD

will start conducting to ground. Continuous operation above the MCOV will lead to

SPD failure.

(c) Voltage protection rating (VPR) – a UL 1449 rating of the limiting voltage measured

during the transient-voltage surge suppression test using the combination wave

generator at a setting of 6kV, 3kA. A lower VPR is better.

(d) Surge current rating – the maximum surge current that an SPD is rated to carry without

excessive overheating and consequent premature breakdown or combustion risk. The

surge current rating is expressed in thousands of amps (kA) and is an indicator of how

many MOVs are installed in parallel inside the device. SPDs are readily available rated

for as low as ≤20 kA up to ≥600 kA. SPD price tends to increase as surge current rating

increases.

(e) Protection modes – line-to-line, line-to-ground, line-to-neutral, neutral-to-ground.

(f) Short circuit current rating (SCCR).

(g) Surge life – expected number of surges that the SPD can withstand.

Other important attributes include monitoring and design for the environment at the installation

location (Mehdi et al, 2014).

2.31 Residential Surge Protection

Residential surge protection has long been viewed as an important safety consideration and

guidance has been issued in the past to help homeowners protect their house and its contents.

This protection has often been described as being similar to an insurance policy, partly because

41

there is not an NFPA code requirement for SPD installation in residences. Today’s residences

often contain electronic equipment throughout, including appliances, computers, security

systems, life safety equipment, automation systems for internet-enabled applications, and home

entertainment systems (Teru, 2010).

2.32 Power Quality Standards

Technical standards are developed by panels of experts, and designed to be independent of

proprietary products or specific vendors. These standards are then maintained and revised as

needed by the organization that issues them (e. g., Underwriters Laboratories).

National and international product safety standards and guidelines are created to:

(a) Reduce risks to human health and safety.

(b) Improve the quality of manufactured goods and services.

(c) Promote interoperability, making it possible for equipment from one vendor to function

efficiently in coordination with equipment from other vendors.

(d) Improve the efficiency of constructing and equipping industrial, medical, and

commercial facilities.

(e) Result in consistent products and reliable manufacturing and safety processes.

(f) Improve environmental protection where standards compliant products are installed.

2.33 Surge Suppression Standards Overview

When it comes to SPDs, specific standards are developed by Underwriters Laboratories (UL)

and the National Fire Protection Association. Over the last several years, there have been many

changes in the codes and standards for SPDs. The most significant are changes to UL 1449.

42

There is also a new standard for safety, of surge protective devices (article 285), which involves

changes to the National Electric Code (Khalid, 2011).

This standard specifies the waveforms to be used in testing American-manufactured SPDs,

defines terminology related to SPD manufacture and test procedures, establishes proper

labelling for SPD products, and specifies required testing and minimum acceptable

performance.

Previous versions of UL 1449 identified only two types of SPDs: permanently connected or

cord-connected. The third edition of UL 1449 has combined all categories into a formal

classification and identified them as four different types, each of which has consistent testing

and application requirements. The most common SPDs generally fall into Type 1 and Type 2

categories. (NFPA, 2013)

2.34 Standard for Transient Voltage Surge Suppressors (SPDs)

Type 1 SPDs are Secondary Surge Arresters and are installed between the secondary side of a

service transformer and the primary side of a service entrance disconnect. They must have

overcurrent protective devices either installed internally on the SPD or included with it. While

these are primarily intended for installation before the main service disconnect, Type 1 SPDs

can be installed in Type 2 and Type 4 locations such as distribution panels, end-use equipment,

etc.

Type 2 SPDs are intended to be connected on the secondary side of the main service disconnect.

While some will have internal overcurrent protective components, Type 2 SPDs can rely on the

service entrance overcurrent disconnect device for over current protection. These can be

installed in service equipment, distribution panels, and end-use equipment. Type 2 SPDs are

permanently connected.

43

Type 3 SPDs are intended to connect at least 33 feet from the service entrance; this does not

include the length of the SPD conductors. These devices are cord-connected devices, and

intended to be used in end-equipment locations. They can rely on external overcurrent

protective devices for overcurrent protection. Type 3 SPDs that are cord-connected are required

to comply with the leakage current requirements to ensure unwanted (objectionable) currents

are not injected on the ground conductor.

Type 4 SPDs are component or assembly drives. They are incomplete in their construction or

safety testing (e. g., limited-current abnormal overvoltage test, and intermediate current tests)

and are intended to be tested in the final assembly. Those that are incomplete in construction or

testing have the identifying information noted in the requirements section of the manufacturer’s

UL report. Unfortunately, there is no documentation of the additional testing requirements for

a Type 4 SPD on the labelling or installation instructions. These can range from single

components (MOVs, SADs) to complex devices intended for installation into distribution

equipment (panel boards, switchboards, etc).

In addition to the new categorization, ANSI/UL 1449 Third Edition specifies that surge

suppression products formerly identified as Transient Voltage Surge Suppressor (TVSS) will

be called Surge Protective Devices (SPDs). It modified the Suppressed Voltage Rating (SVR)

test from 6kV, 500A to 6kV, 3,000A, which represents six times more surge current. And let-

through voltage is now termed the Voltage Protection Rating (VPR).

There’s also a Nominal Discharge Current rating up to 20kA. This is part of the Voltage

Protection Rating test and is a measure of the SPD’s endurance capability. Manufacturers will

choose the applicable rating and show the data on literature, specifications, and products

(Gustavo, 2003).

44

2.35 National Electrical Code (NEC) and National Fire Protection Association (NFPA)

Developed by the NFPA, the NEC was established in 2002 to address electrical safety in the

workplace. While the code is updated every three years, not all states and municipalities have

adopted the same version of the NEC. The 2005 revision of the NEC had two types of SPDs:

secondary surge arrestors and transient voltage surge suppressors (now called SPDs) (NEC,

2014).

2.36 Research Focus

This research focuses on the effects of electrical surge and its remedy which is an improvement

on Paul Mccoy, 2014 research on power surges, causes and their effects in the residential

environment, using Ajaokuta power system Network in Kogi State, of Nigeria as a case study.

It’s a further move in finding the effects and remedy to power surges both in residential,

industrial and Transmission line which involves the collating of data in three environments with

two experimental procedures and to identify other parameters such as effects of tower footing

resistance and arrester intervals on arresters failure probability on transmission line.

The recent surge data recorded and would be analysed to determine the SPD ratings required

for facilities and residences.

45

CHAPTER THREE

MATERIALS AND METHODS

3.1 Site and location of the Study

Ajaokuta is located in the North-central of Nigeria popularly known as steel-city because of the

established integrated steel plant by the federal government of Nigeria. The land Area is about

1,800 hectares, (18 million square metres) and the latitude/longitude coordinates for Ajaokuta

are: 7°33'44.24"N, 6°39'17.89"E.

•Latitude position: Equator ⇐ 841km (522mi) ⇐ Ajaokuta⇒ 9166km (5696mi) ⇒ North

pole.

Plate 3.1: Step for grid lines is 15°. On second map 15° latitude and 0° longitude line is

numbered. Map pointer shows the 7.56, 6.65 lat-long coordinates.

The erection of Ajaokuta power system network commenced in 1981 and completed and

commissioned in 1987. This power Network consists of Thermal power plant (TPP) with an

installed capacity of 110MW, Two 55MW steam turbines served by three 220ton/hr high

150

46

pressure boilers. The plant output of 11.5kV is stepped up to 132kV by two 63MVA coupling

transformers for loading to the national grid and to the two 63MVA main step down transformer

stations for domestic and industrial usage.

Figure 3.1: Basic Structure of the Power System Network in Ajaokuta.

The generating, transmission and distribution stations is shown in Figure 3.2.

Source: www.nerc.com

Transmission

Lines

Transmission

to Grid (132kV) Generator Step Up

Transformer

(132kV, 63 MVA)

Generating Station

(110MW)

Substation Step-

Down Transformer

(63MVA)

Sub-transmission

Consumer (11.5kV)

Primary Consumer

(6.6kV)

Secondary

Consumer

(1000MVA, 240V)

47

Plate: 3.2 Main Step-Down Substation I

Figure 3.2: Generating Transmission and Distribution Stations is shown in Figure 3.2.

Plate 3.2: Surge Protector

48

Plate 3.3: Fluke 1625 Advanced GEO Earth Ground Tester

49

Plate 3.4: Meter Board of Transmission Station.

50

Plate 3.5: Main control Board of Transmission Station

Plate 3.6: Exports and Import Power at Transmission Station.

51

Figure 3.2: Location of SPD in the switchboard (in parallel)

Figure 3.3: Cross-section drawing view of a polymer housed surge arrester

52

Table 3.1: Technical Characteristics of the Surge Arresters in use

Continuous operating voltage (Uc) 108<Uc<115kV(rms)

Rated voltage 144kV (rms)

Rated discharge current 10kA

Residual voltage <330kV (max) for 5kA

<350kV (max) for 10kA

<390kV (max) for 20kA

Discharge energy class 3

Energy capability 8kJ/kV

3.2 Experimental Methods

The approaches adopted for the realization of the study include the following:

(a) Develop a preliminary data collection plan that will address the identified data

gaps. When implemented, the data collection plan would provide a

comprehensive review of electrical surge related losses in the power system

network of Ajaokuta and address the potential impact of electrical surge

protection devices in mitigating these losses.

(b) Experimental investigations and collation of available data associated with

electrical surges and their impacts.

3.3 Experimental Procedure

53

The experimental procedure in this paper is subdivided into three in order to achieve the desired

objectives.

3.3.1 Experimental Procedure No. 1

An experimental investigation was carried out on lightning surges that flow in the distribution

lines in some residences of Ajaokuta Power System Network;

Figure 3.4: Schematic Diagram of Experiment No 1

Lightning surge detectors were installed in six (6) residences and monitored for three years

2013 to 2015. During the three years observation period, 15 lightning stroke were recorded

(a) Damage occurred to appliances in two of the 15 events when lightning appeared to have

hit an antenna. In this case, currents of 0.2 kA or greater were recorded at all the

measurement points, and some appliances were damaged.

(b) Homes with lightning protective devices of a peak current rating of 1kA break down at

a current peak value of approximately 1 kA or higher, according to the observations.

Surge Detector

Data logger

Ground wire

54

3.4 Data presentation

The data obtained in the experiment is presented in Tables 3.2 to 3.5; Average lightning stroke

surge recorded by surge detectors installed in 6 residents and monitored for three years, 2013

to 2015 for 15 lightning stroke events

Table 3.2: April to October, 2013

Residents 1 2 3 4 5 6

Surge current (kA) 0.64 0.7 Nil 0.9 1.27 0.84

Time (µs) 12 15 Nil 22 27 20

Table 3.3: March to October, 2014

Residents 1 2 3 4 5 6

Surge current (kA) 0.5 0.46 0.72 0.44 0.2 0.42

Time (µs) 10 10 15.4 8 5 6

Table 3.4: March to October, 2015

Residents 1 2 3 4 5 6

Surge current (kA) 0.41 0.66 1.09 0.85 Nil Nil

Time (µs) 7 15 22 18 Nil Nil

3.5 Data Bank Presentation from 2013 - 2015

This data provides objective data about lightning stroke intensity based on a scientific study.

Since 1995 the 0perations of the power system Network had set up lightning data bank to collect

55

data on the total number and magnitude of cloud to earth lightning strokes to be used as a factor

in determining the required maximum surge current of SPDs.

For this reason, the maximum surge current of an SPD is often selected based on perceived

lightning stroke levels. The data collected by Ajaokuta power system network measured the

time and the current magnitude of each positive and negative lightning stroke.

The summary of the data in which the resultant lightning storms generated 19,982 separate

cloud to earth strokes is represented in the Tables 3.5 and 3.6 which indicates the count of

current magnitudes arranged in 10kA increments and their cumulative percentage.

56

Table 3.5: Positive Lightning strokes from 2013 to 2015

Low kA High kA COUNT (number

of occurrence) % of POSITIVE % Cumulative

0 10 914 50.30 50.30

10 20 715 39.35 89.65

20 30 110 6.05 95.7

30 40 31 1.71 97.41

40 50 22 1.21 98.62

50 60 7 0.39 99.01

60 70 4 0.22 99.23

70 80 5 0.28 99.51

80 90 4 0.22 99.73

90 100 2 0.11 99.84

100 110 1 0.06 99.9

110 120 1 0.06 99.9

120 130 _ _ 99.96

130 140 1 0.06 98.02

140 150 _ _ 100

Total Positive = 1817

Table 3.5 above displays the distribution of current magnitude in 10KA increment for 1,817

positive lightning strokes. A summary of this data is given as follow; 96% were less than 30kA,

while 99% were less than 60kA.

57

Table 3.6: Negative Stroke from 2013 to 2015

Low kA High kA COUNT (number of

occurrence) % of POSITIVE % Cumulative

0 10 1819 10.01 10.01

10 20 7201 39.64 49.66

20 30 5667 31.20 80.86

30 40 2011 11.07 91.93

40 50 799 4.40 96.33

50 60 324 1.784 98.11

60 70 164 0.90 99.01

70 80 65 0.36 99.37

80 90 49 0.27 99.64

90 100 31 0.17 99.81

100 110 17 0.09 99.90

110 120 9 0.05 99.95

120 130 5 0.03 99.98

130 140 2 0.01 99.9

140 150 2 0.01 100

Total Negative = 18,165

There were also 18,165 negative strokes during the same time period.

Table 3.6 above shows the measured current value of these strokes. A summary of the data is

given as follow; 81% is less than 30kA, while 98% is less than 60kA.

58

3.6 Experimental Procedure NO. 3

A test was carried out on three 132KV operation transmission lines of Ajaokuta power

interconnected system to determine the variation of surge Arresters failure probability with

Tower Footing Resistance for each of the three analysed case studies, secondly to determine the

Arrester failure probability with the Arrester interval for the transmission line. These lines were

carefully selected due to

(a) their high rate of failure during thunderstorms.

(b) their sufficient length and sufficient time in service.

(c) the significant different characteristics, such as ground flash density and the tower

footing resistance which exist through their lengths, since they run through the same

region.

Table 3.7 to 3.9 show the percentage failure reduction for all the analysed lines in each one of

the three examined case studies, using the equation. The relationship between the installation

interval and arresters failure probabilities for the line is shown in equation (3.1):

F.R.R (%) = 𝐅.𝐑.𝐨−𝐅.𝐑.𝐢

𝐅.𝐑.𝐨∗ 100% (3.1)

Where:

F.R.R = Failure Rate Reduction

F.R.O = failure rate without surge arresters.

F.R.I = failure rate with installed surge arresters.

59

Table 3.7: Failure rate reduction from July to October, 2013

Line Region Average Recorded

Fro

Computed F.R.1

For Case Study F.R.R. %

Ajaokuka to

Geregu

I 0.1 0.051 0.49

II 0.6 0.082 0.86

III 0.9 0.385 0.57

Total 1.6 0.519 1.92

.

Table 3.8: Failure rate reduction from August to September, 2014

Line Region Average

Recorded Fro

Computed

F.R.1 For Case

Study

F.R.R. %

Ajaokuta to

Geregu

I 0.613 0.425 0.31

II 1.540 0.769 0.50

III 3.207 1.005 0.69

Total 5.360 2.199 1.5

Table 3.9: Failure rate reduction from August to September, 2015

Line Region Average

Recorded Fro

Computed

F.R.1 For Case

Study

F.R.R. %

Ajaokuta to

Geregu

I 0.461 2.77 0.40

II 0.836 0.439 0.48

III 2.190 0.744 0.66

Total 3.397 1.460 1.54

60

Average F.R.R. for regional interval (ajaokuta to geregu) =

Total FRR for a region (3.2)

Total FRR for the three regions

Where:

FRR = failure rate reduction.

AV FRR = Average Failure Rate Reduction.

Total FRR. For a (1,2 or 3) region

Table 3.10:

Line Voltage

(kV)

No. Of

Tower

Arrester

Interval

(Km)

Tower

Footing

Resist.

Av. FRR

for the

three

regions.

% AV.

FRR for

Regional

Intervals

Ajaokuta to

Geregu 132kV 1 – 5 6 4.2 1.2 24.19%

Ajaokuta to

Geregu 132kV 6 – 12 4 25.8 1.84 37.10%

Ajaokuta

to Geregu 132kV 13 – 22 8 2.0 1.92 38.71%

61

CHAPTER FOUR

RESULTS AND DISCUSSION

4.1 Lightning Surge Stroke Data obtained for Six Residences

Lightning surge recorded data by surge detector installed in six residences and monitored in the

period of rainfall for three years, 2013 to 2015. Figure 4.1 shows the surge events that occurred

between April and October 2013 with peak stroke of 1.27kA which caused damage to

appliances while Figure 4.2 to Figure 4.3 shows the corresponding values for 2014 and 2015

respectively.

Figure 4.1: Five surge events that occurred between April and October 2013

with peak stroke of 1.27kA which caused damage to appliances

1.27 KA

62

Figure 4.2: Surge events that were recorded between March and October, 2014, but the surge

strokes magnitude were not severe enough to cause any damage.

Figure 4.3: Surge events recorded between March and October 2015 with peak stroke of

1.09kA which caused damage to home appliances.

63

The analysis of observation data found that in some cases a ground potential rise causes a

lightning surge to flow from ground of another residence or the ground of a distribution system

into the distribution and, in turn, to flow into another residence.

4.2 Lightning Stroke Data Characteristics

The obtained data on lighting stroke are presented in the Figure. 4.4 showing the Peak Current

Percentage (Positive Polarity)

Figure. 4.4: Distribution of positive lightning stroke in percentage and the current magnitude

in kA from 2013 – 2015

Figure 4.5 shows the distribution of negative lightning stroke in percentage and the current

magnitude in kA from 2013 – 2015, In aggregate, the data reveals that less than 1% of the

positive and 2% of negative strokes had a current magnitude greater than 60kA.The vast

majority of strokes were less than 30kA.

64

Figure 4.5: Stroke Peak Current Percentage (Negative Polarity)

4.3 Arresters Failure Rates on Transmission Lines and their Effects

Tables 3.7 to 3.9 have presented the recorded transmission line lightning failure in comparison

with the obtained surge arrester failure rates for the analysed case, considering arresters failures

as line faults. The result shows that the use of surge arresters improved the lightning

performance of the line and reduces the line outages.

Figure. 4.6: Percentage failure rates reduction of the analysed line for the three regions from

July to August, 2013

65

Figure 4.7 shows the percentage failure rates reduction of the analysed line for the three regions

between August to September, 2014 while Figure 4.8 shows the percentage failure rates

reduction of the analysed line for the three regions between August to September, 2015

Figure. 4.7: Percentage failure rates reduction of the analysed line for the three regions

between August to September, 2014

Figure 4.8: Percentage failure rates reduction of the analysed line for the three regions from

August to September, 2015

The graphic representation of the result in Figure 4.9 gives a sense of expected improvement of

the lightning performance of the line. The lightning performance of the line and computation

of the outage rate were determined for different arresters location and for regions with different

tower footing resistances and ground flash densities.

66

Surge arresters installation on every tower gives the best protection, especially for region with

high footing resistance. When tower resistance is low enough, arresters protect the line

sufficiently. Figure 4.10 shows the failure probability of arresters interval versus the tower

footing resistance for examined line. Increasing tower footing resistance leads to increasing of

arrester failure probability while arresters failure rate depend also on line length and ground

flash density.

R - Regions

Figure 4.9: The variation of surge arresters failure probability with Tower Footing

Resistance for each of the three analysed region case studies

67

T.F.R. - Tower Footing Resistance

Figure 4. 10: The variation of surge arresters failure probability with the arresters interval for

the transmission line Ajaokuta - Geregu.

It is also observed that smaller interval decreases arrester failures. In Figure 4.10 for each tower

resistance the failure probability is higher as the interval increases. Thus for each region with

high tower footing resistance, arresters installation, probably with higher withstanding capacity,

on every tower is recommended.

68

4.4 Findings of the study

(a) In the three years of monitoring of six residences with 15 lightning surge events, only

two were severe enough to cause damage to appliances at current value of 1.27kA and

1.09kA in 2013 and 2015 respectively.

(b) It was observed that there is a ground potential that caused a lightning surge to flow

from ground of one residence or distribution to another.

(c) The data collected based on existing power system network of Ajaokuta revealed the

vast majority of the lightning stroke were less than 30kA.

(d) When tower resistance is low arrester protect the line sufficiently, but with high tower

resistance the protection is not impressive.

(e) Arrester failure probability also depends on arrester interval, increasing the length

increasing the failure rate.

69

4.5 Contributions to Knowledge

(a) The real data recording regarding surges is to assist the company in determining when

SPD is required and when not required.

(b) The failure rate reduction probability revealed that surge arrester installed in every

tower will give the best result.

(c) Characterization of surge events that did not cause damage, the surge events that will

cause subsequent damage and the surge events that resulted in damage were a guide to

ascertain the ratings and positioning of protective devices.

(d) For failure rate reduction the arrester intervals should be considered to be at minimum

distance as much as possible.

70

CHAPTER FIVE

CONCLUSION AND RECOMMENDATIONS

5.1 Conclusion

In this thesis the causes of overvoltage in Ajaokuta power system Network may be internal or

external. Instances of extended high voltages are rare but when they occur significant damage

is done. To maintain high quality power within the facility, it must start with a solid foundation.

This begins by ensuring wirings, grounding and bonding are up to standard, then element such

as quality surge protectors like low-pass fitters, data and signal line protectors to prevent

damage from surges and electrical noise and lightning arresters for external over-voltage can

be installed, then over-voltages can be prevented from system Network and surge damage is

reduced or eliminated.

5.2 Recommendations

Selecting the right power quality device is the optimum remedy to power surge and this involves

several issues to be considered, like your specification should focus on the essential

performance, installation and safety requirements.

It is further recommended that:

(a) The power department should consider the value of the equipment and their data to meet

customers’ satisfaction. Surge can destroy or corrupt data so that it becomes unreliable,

and it can cause significant equipment damage. Review the equipment to be protected,

the cost of repair or replacement, loss of productivity, cost of annoyed customers and

loss of business, and inconvenience to the equipment repaired or replaced.

71

(b) The level of protection needed should be known. The more protection you need, the

greater the cost will be, but keep in mind that the cost of not protecting the power supply

could be much greater still.

(c) Where surge protection is to be installed is highly important since every facility is

different, there is no method of deciding where an SPD should be installed within your

power system. Surge protection needs for a small business differ from that of larger

ones.

The recommendation is that further research should be carried out to determine the design of

the grounding system installations to meet ground resistance requirements, because without

proper grounding the protectors are useless. The soil composition, moisture content and

temperature all impact the resistivity. Soil is rarely homogenous and the resistivity of the soil

will vary geographically and at different soil depths. Also moisture changes seasonally and

varies according to the nature of the sub-layers of the earth

72

REFERENCES

Dharmender, P. (2014). Reasons for failure of transmission lines and their prevention

strategies, International Journal of Electrical, Electronics and Data Communication,

2(1): 14-19.

Gustavo, B., Bogdan, K., and Craig W. (2003). Shunt Capacitor Bank Fundamentals and

Protection, Conference for Protective Relay Engineers - Texas A&M University, April 8-

10, College Station (TX).

Hasssan, H., El-Tamaly, Ayman Yousef Nassef (2017). Study the Integrated of Wind Farm

with Utility Grid, Journal of Scientific and Engineering Research, 4(9):122-136.

Khalid, S., and Bharti Dwived (2011). Power Quality Issues, Problems, Standards & Their

Effects in industry with corrective means, International Journal of Advances in

Engineering & Technology, 1(2):1-11

Kostas, S., and Chris J. Salmas (2007), Electrical Surge Protective Device for Industrial

Faculties- a tutorial review, IEEE Transaction Industry Application, 43(1): 1-11.

Makinde, K., Enemuoh, F. O., Lawal, O. K, Umar I, Abubakar B, and Mahmood M. (2014).

Performance Analysis of Surge Current Protection Using Superconductors, European

Scientific Journal, 10(19): 183-192

Mehdi N., Ghahraman S. and Masoud J. (2014). Comparison of IEEE and Pinceti Models of

Surge Arresters, Research Journal of Engineering Sciences, 3(5), 32-34.

Mungkung N., Wongcharoen S., Tanitteerapan Tanes, Saejao C., and Arunyasot D., (2007),

Analysis of Lightning Surge Condition Effect on Surge Arrester in Electrical Power

System by using ATP/EMTP Program World Academy of Science, Engineering and

Technology, International Journal of Energy and Power Engineering, 1(4).

NEMA, 2013, U.S. Surge Protection Damage Survey. NEMA, Surge Damage Survey Results

– Wave 2.

NFPA 780, 2014, National~ Electrical Code, Standard for the Installation of Lightening

Protection Systems.

Okundamiya, M. S. (2018). Fundamentals of Digital Signal Processing. Benin City: Sciengtex

Publishing.

Okundamiya, M. S., and Nzeako, A. N. (2010). Energy storage models for optimizing

renewable power applications, Journal of Electrical and Power Engineering, 4(2): 54-65

73

Okundamiya, M. S., Udeozor, O. S., and Imade, O. J. (2009). Investigation and evaluation of

voltage drops: A case study of Guinness and Ikpoba Dam injection substations.

International Journal of Electrical and Power Engineering, 3(2), 105–111.

Osahenvemwen, O. A., Okhuomeode, M. E. & Omatahunde, B. E. (2018). Electrical Energy

Losses Reduction using Power Factor Correction Technique, Advances in Electrical and

Telecommunication Engineering, 1(1), 9-16.

Shehab A. A., (2013). Design of Lightning Arresters for Electrical Power Systems Protection.

Power Engineering and Electrical Engineering, 11(6): 433-442.

Sukhdeo Sao, K Prasada Rao. (2013). Effect of Very Fast Transient over voltages at high

frequency in a Gas Insulated Substation during switching operations, International

Journal of Scientific and Research Publications, 3(3): 2250-3153

Teru M., (2010). Field study of lighting surges propagating into residences, IEEE transactions

on electromagnetic capability, 52(4): 211-221

.