Andover Controls - CMX 240 Series Controller Installation Guide

Embed Size (px)

Citation preview

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    1/49

    Andover Controls Corporation i

    TOC

    CMX 240 Series Controller

    Installation Guide

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    2/49

    ii CMX 240 Installation Guide

    Version D

    Reproduction or distribution forbidden.Copyright1997 by Andover Controls.

    Subject to change without notice.

    Order No. 30-3001-391

    Copyright 1997

    Andover Controls Corporation

    300 Brickstone Square

    Andover, Massachusetts 01810

    All Rights Reserved.

    Published by the Engineering Department at Andover Controls Corporation.

    IMPORTANT NOTICE

    This product is subject to change without notice. This document does not con-

    stitute any warranty, express or implied. Andover Controls Corporation re-

    serves the right to alter capabilities, performance, and presentation of this

    product at any time.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    3/49

    Andover Controls Corporation iii

    TOC

    Preface

    TheInfinity CMX Installation Guide presents instructions for installing

    thevariousCMX controllers. It first presents site preparation informa-

    tion and then step-by-step installation instructions.

    We recommend you readInfinityNetwork Configuration Guide to plan

    your entire network before installing a single controller.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    4/49

    iv CMX 240 Installation Guide

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    5/49

    Andover Controls Corporation v

    TOC

    Contents

    Installing the CMX 240 ControllerSite/System Setup Requirements .............................................................2

    Cabinet Dimensions .......................................................................3

    Controller Dimensions ...................................................................3

    Power Requirements ......................................................................4

    Modem ...........................................................................................4

    Infinet Cables .................................................................................4

    Number of Infinet Controllers on CMX Infinet ............................5

    TankNet and Probe Power Supply Cables .....................................6

    Lightning Protection ......................................................................6

    Building Ground Requirements .....................................................6

    Inspecting the Ground ....................................................................7

    Environmental Requirements ........................................................8

    Laying Out the Site Setup ..............................................................8

    Installing the CMX 240 Series Controller ...............................................9

    Unpacking ......................................................................................9

    Parts Required ................................................................................9

    Mounting and Wiring ..................................................................10

    Connecting the AC Power Cable to the Power Supply ...............13

    Selecting the AC Input Voltage ...................................................14

    Finding Ports for Connecting Other Cables .................................15

    Connecting the Terminal Screen .................................................17

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    6/49

    vi CMX 240 Installation Guide

    Connecting to the Infinity Modem ..............................................17

    Wiring Infinet to the CMX 240 ...................................................18

    Wiring the TankNet and Probe Power Supply ............................19

    About the Safety Barriers ............................................................21

    Powering Up CMX 240 Series Controller .............................................23Connecting the Battery ................................................................24

    Interpreting Status Lights Inside Cabinet ...............................................25

    Custom Port Status Lights ...........................................................25

    Communication Status Lights ......................................................25

    Infinet Status Lights .....................................................................26

    Modem Power Light ....................................................................27

    System Activity Status Lights .....................................................27

    Using the CLEAR MEMORY Button .........................................28Connecting the Andover Controls Service Tool ..........................28

    Appendix ARS-232 Port Pinouts

    Appendix BProbe Switch Settings

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    7/49

    Andover Controls Corporation vii

    TOC

    Figures

    Figure 1. Backplate with Dimensions and Eyelets for Mounting

    CMX 240 ..............................................................................11

    Figure 2. Cabinet with Dimensions and Eyelets for Mounting

    CMX 240 ..............................................................................12

    Figure 3. Metal Plate and Screw for Power Supply Wire .........................13

    Figure 4. Locations of Ports and Connectors on the

    CMX 240 Face Plate ............................................................16

    Figure 5. Jumpering P1 Pins for CMX 240, Top View .............................18

    Figure 6. Infinet Cable Wiring ....................................................................19

    Figure 7. Attaching the TankNet and Probe Power Supply Cables .....20

    Figure 8. Diagram of Safety Barrier Connection ................................22

    Figure 9. Custom Port Status Lights ...........................................................25

    Figure 10. Communication Status Lights for Comm1 .................................26

    Figure 11. Communication Status Lights for Infinet ...................................26

    Figure 12. System Activity Status Lights .....................................................27

    Figure A-1. Pinouts for Cables Connecting to RS-232 Ports on

    Controller................................................................................... A-3

    Figure B-1. Switch Settings for Switches 2 and 3 on Tank Probe ..............B-2

    Figure B-2. Switch Settings for Tank Probes on Channels 1 through 6......B-3

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    8/49

    viii CMX 240 Installation Guide

    Tables

    Table 1. Number of Infinet Controllers Allowed on

    Various CMX 240s ................................................................5

    Table 2. AC Input Voltage Selection .................................................14

    Table A-1 Pinouts for RS-232 Comm Port with Male DB25

    Connector to Terminal .......................................................A-1

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    9/49

    CMX 240 Series Installation Guide 1

    Installing theCMX 240 Controller

    TheInfinityCMX 240(with or without a modem) is a unique controller.

    You can connect a terminal to it and program it just as you would an

    Infinity CX 9000controller, yet it belongs on theInfinet. You can connect

    32 or 64 controllers to the CMX 240, depending on which particular

    model number you have. From the CMXyou can program theInfinet

    controllers.

    This manual covers the following:

    Site/System Setup Requirements

    Installing the CMX 240 series controller

    Connecting to theInfinet

    Connecting to the TankNet

    Connecting to the Modem

    Powering Up the Controller

    Interpreting Status Lights inside Cabinet

    Appendix A gives the pinouts for the RS-232 port cables.

    Appendix B shows you how to set some probe switches.

    Warranty Registration

    Your warranty is effective for 18 months starting on the date the system

    is shipped.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    10/49

    2 CMX 240 Series Installation Guide

    Site/System Setup Requirements

    Before you proceed to install the system, you should map out where you

    plan to install each controller, terminal/workstation, and modem. When

    planning the sites, be aware of any electrical interference that may oc-cur. You also need to be aware of cabinet dimensions, power

    requirements, cable limitations, and environmental requirements.

    Warning

    This equipment has been tested and found to comply with the limits for

    a Class A digital device, pursuant to Part 15 of the FCC Rules. These

    limits are designed to provide reasonable protection against harmful

    interference when the equipment is operated in a commercialenvironment. This equipment generates, uses, and can radiate radio

    frequency energy and, if not installed and used in accordance with the

    instructions in this manual, may cause harmful interference to radio

    communications. Operation of this equipment in a residential area is

    likely to cause harmful interference in which case the user will be

    required to correct the interference at his own expense.

    NoteThis digital apparatus does not exceed the Class A limits for radio noise

    emissions from digital apparatus set out in the Radio Interference

    Regulations of the Canadian Department of Communications.

    Avis

    Le prsent appareil numrique nmet pas de bruits radiolectriques

    dpassant les limites applicables aux appareils numriques de la class A

    prescrites dans le Rglement sur le brouillage radiolectrique dict par

    le ministre des Communications du Canada.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    11/49

    CMX 240 Series Installation Guide 3

    Warning

    All wiring and installations must comply with local, state, and national

    electrical codes.

    Warning about Telephone Service

    Refer to theInfinity Modem Installation Guidefor safety warnings and

    installation instructions.

    In the event repairs are ever needed on anyInfinity CMX 240controller,

    they should be performed by Andover Controls Corporation or an

    authorized representative of Andover Controls Corporation. Forinformation contact Andover Controls at 300 Brickstone Square,

    Andover, Massachusetts 01810.

    Cabinet Dimensions

    EachInfinity CMX 240 cabinet is approximately 15 19 4.75 in.

    You can order the CMX 240with or without the cabinet.

    Controller DimensionsEachInfinity CMX 240 controller without a cabinet is approximately

    12.54 14.25 2.75 in.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    12/49

    4 CMX 240 Series Installation Guide

    Power Requirements

    Warning

    Be sure your installation complies with local, state, and national

    electrical codes.

    Caution

    TheCMX 240 series controller should receive power from its own

    independent, unswitched circuit.

    The CMX 240requires 24/115/230 VAC +/-20%, 50/60 Hz rated at30 VA with a modem and 20 VA without a modem.

    Modem

    You can use theInfinitymodem with any CMX 240, but the modem is

    not required.

    If you order any CMX 240with theInfinitymodem, the modem is

    already installed.

    If you order anyCMX 240without a modem and then add theInfinity

    modem later, refer to theInfinity Modem Installation Guidefor instruc-

    tions on how to install the modem.

    Infinet Cables

    The maximum cable length forInfinetis 4,000 ft. at 19,200 baud (up to

    32Infinetcontrollers). You can extendInfinetbeyond 4,000 ft. or put

    more than 32Infinetcontrollers on less than 4,000 ft. by using theIn-fiLink 200amplification module.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    13/49

    CMX 240 Series Installation Guide 5

    Cables that formInfinetare 24-gauge, single-twisted-pair, tinned,

    shielded copper wire. Use the following cables1or their equivalents:

    Note

    You must use shielded cables forInfinetto ensure compliance with the

    Class A FCC limits and to communicate reliably.

    Brand Rex # H 9002 (single-pair)

    Anixter # 9J2401021 (single-pair plenum cable)

    The cable should have a nominal impedance of 100 and a nominal

    velocity of propagation of 78%.

    The capacitance of theInfinetcable should be smaller than or equal to

    12.5 pF/ft between conductors and smaller than or equal to 22 pF/ft

    between the conductor connected to ground and the next conductor.

    Number of Infinet Controllers on CMX Infinet

    You can have up to 64Infinetcontrollers on a single CMX Infinet.

    Table 1 shows the various model numbers and the number ofInfinet

    controllers you can have on each.

    The differences between the CMX 240/241and the CMX 245/246are

    differences in what you can program them to do. The CMX 245and 246

    allow you to choose Command mode on a terminal connected to

    COMM2. For details, see theInfinity Controller Programmers Guide.

    1. You can also use any cables you may already have in place for ACNET or LBUS.

    Table 1. Number of Infinet Controllers

    Allowed on Various CMX 240s

    No.Ctlrs

    CMX ModelStandard

    CMX Model withCommand Mode

    32 CMX 240 CMX 245

    64 CMX 241 CMX 246

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    14/49

    6 CMX 240 Series Installation Guide

    TankNet and Probe Power Supply Cables

    Refer to the probe documentation for information on TankNet and

    probe power supply cables. If you do not have this documentation

    contact MTS Systems Corporation at the following address:

    MTS Systems Corp.

    Sensors Division

    P.O. Box 13218

    Research Triangle Park, NC 27709

    (919) 677-0100

    Order Number0592 550164 Revision B

    Lightning Protection

    Warning

    When running cables (Infinet) between buildings you must install

    lightning arresters forInfinetto prevent electromagnetic disturbances.

    Use lightning arresters at each point whereInfinetcable enters or exits

    a building. Use the following arrester:

    Two pair gas tube arrester, Andover Controls # 01-2100-299.

    Building Ground Requirements

    Warning

    Be sure that allInfinityproducts from Andover Controls Corporation

    are grounded to true earth ground. This kind of ground protects the

    equipment from voltage transients and other power surges in the area.

    We cannot guarantee that the controller system will operate as

    documented unless you properly ground all controllers.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    15/49

    CMX 240 Series Installation Guide 7

    Warning

    Be sure to have your grounds inspected before you begin the

    installation process to be sure your municipality follows the National

    Electrical Code. Many municipalities do not and often havesubstandard electrical grounds.

    An example of a substandard ground is a galvanized steel cold water

    pipe. As the pipe corrodes, it does not act as a true ground. The corro-

    sion acts as an insulator, raising the potential of the pipe with respect to

    the ground.

    When lightning strikes in the area of the installation, it drastically

    changes the potential of the earth.

    Since properly grounded Andover Controls units respond to changes in

    potential more rapidly than poorly grounded electrical systems, a poor-

    ly grounded building tries to reach ground through the Andover

    Controls system. The surge of current can destroy electronic compo-

    nents on the controller board. Surges of much lower potential than

    lightning also impact the reliability of Andover Controls equipment.

    Inspecting the Ground

    You can check your ground as follows:

    1. Check your ground by first inspecting the building power

    distribution panel for earth ground termination. If the ground

    termination is any of the following, it is not adequate and must be

    corrected:

    Does not exist.

    Is connected to a corroded or galvanized pipe.

    Is connected using a small gauge wire (less than 14 AWG).

    2. Be sure your Andover Controls cabinet is connected to the ground

    with a copper conductor that terminates at the distribution panel.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    16/49

    8 CMX 240 Series Installation Guide

    Environmental Requirements

    TheCMX 240 controllers operate in rooms with temperatures ranging

    from 40 to 120F and with humidity between 10 and 95%, noncondensing.

    Laying Out the Site Setup

    You may want to draw a map of where you plan to put each controller

    and store it in a notebook. If you have not already done so, read the

    EnergyNet and Infinet Configuration Guidefor information on how to

    design a configuration.

    You put only one CMX240series controller on anInfinet. You connect

    a terminal to the CMX.

    Youcannotconnect an LBUS to a CMX 240series controller. Youcan-

    nothave anInfinity CX 9000controller on the sameInfinetwith any

    CMX 240.

    Find the tag attached to each controller that gives the number of the con-

    troller.Before you remove any tags, be sure the tag has all of the

    following information on it:

    Location of the controller.

    Serial number. Model name and number.

    Then collect the tags. Youll need to know where your controllers are

    located when you later assign a name to each controller and each input

    and output.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    17/49

    CMX 240 Series Installation Guide 9

    Installing theCMX 240 Series Controller

    Unpacking

    Be careful when unpacking the unit to not damage the packaging

    materialyou must reuse it if you ship the product back for repair.

    Parts Required

    To install a single controller you start with the following parts:

    CMX 240Series Controller

    Cabinet (provided or other enclosure)

    Modem (optional)

    AC Power Cable

    InfinetCable

    TankNet Cable and Intrinsic Safety Barriers (optional, for

    connecting TankNet)

    Probe Power Supply Cable and Intrinsic Safety Barriers (optional,

    for use with TankNet)

    Telephone Cable (optional, for connecting to modem)

    RS-232 Cables for Terminal, Printer, or Modem (see the Appendix A

    for specifications)

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    18/49

    10 CMX 240 Series Installation Guide

    Mounting and Wiring

    Figure 1 shows the backplate and the positions of the eyelets for

    mounting the CMX 240series controller.

    Warning

    Never drill holes in the CMXcabinet or boards. A metal shaving could

    easily short circuit the electronics.

    1. Pull the cable for a terminal or printer through the opening on the left

    side of the cabinet.

    2. Pull cables forInfinetthrough the left side opening.

    3. Pull the AC cable through the opening on the top left side of the

    cabinet.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    19/49

    CMX 240 Series Installation Guide 11

    Figure 1. Backplate with Dimensions and Eyeletsfor Mounting CMX 240

    8.550

    4.275

    .90

    6.575

    13.150

    14

    11.50

    .454 Places

    1.58

    11.72.03

    12.54.05

    .55

    .23REF

    2.000.015

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    20/49

    12 CMX 240 Series Installation Guide

    Figure 2 shows the dimensions of the cabinet, provided with the

    controller (if purchased), and the location of the mounting screw holes.

    Figure 2. Cabinet with Dimensions and Eyeletsfor Mounting CMX 240

    15.0012.351.33

    1.00

    19.00

    17.00

    INFINETSHLD

    ----

    AC INPUT VOLTAGE SELECTION

    TO230V

    E3

    P2

    FROM24V

    TOE3

    P2

    FROM

    E4

    TO

    P2

    FROM115V

    CMX240

    ERROR

    SCAN

    CPU

    +

    6V BATTERY

    CLEAR-

    +

    USE COPPERCONDUCTORS

    ONLY

    F23A,250V

    SLOW BLOW

    NEU

    HOT

    GND

    AC

    INPUT

    E7 E5E2 E6 E2 E2 E4

    E1 E1 E5

    MODEM POWER

    F5, 2A

    THIS DEVICE COMPLIES WITH PART 15 OF

    AC POWER

    F23A,250V

    SLOW BLOW

    +

    -

    MEMORYSHLDCOM+26V

    +26V

    RD

    TD

    RTS

    RD

    TD

    RTS

    RD

    TD

    RD

    TD

    SERVICE

    PORT

    THE FCC RULES. OPERATION IS SUBJECTTO THE FOLLOWING TWO CONDITIONS:( 1 ) THIS DEVICE MAY NOT CAUSE HARMFUL

    INTERFERENCE, AND( 2 ) THIS DEVICE MUST ACCEPT ANY

    INTERFERENCE RECEIVED, INCLUDINGINTERFERENCE THAT MAY CAUSEUNDESIRED OPERATION.

    F6, 1/8A

    COMM1

    COMM2

    CUSTOM

    PORT

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    21/49

    CMX 240 Series Installation Guide 13

    Connecting the AC Power Cableto the Power Supply

    Warning

    Be sure the controller is not receiving AC power while you are wiring

    it, or you could receive an electrical shock that is life-threatening.

    1. Open the cabinet door. Look to the upper left corner. You should see

    three screws labeled GND, NEU, and HOT. You must wire the AC

    power to the three screws.

    Caution

    Be sure to connect all three wires, GND, NEU, and HOT. Otherwise,

    the controller could malfunction.

    2. Notice that the three wires at the end of your AC cable are green,

    white, and black.

    3. Place the green wire under the metal plate behind the top screw,

    labeled GND.

    4. Tighten the screw with a flathead screw driver.

    Figure 3 shows the position of the plate, where to place the wire, and

    how the screw fits on the plate. You can see how the screw holds the

    plate in place once you tighten it.

    Figure 3. Metal Plate and Screw for Power Supply Wire

    5. Place the white wire under the metal plate behind the middle screw,

    labeled NEU.

    Insert Wire Here

    Metal Plate

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    22/49

    14 CMX 240 Series Installation Guide

    6. Tighten the screw with a flathead screw driver.

    7. Place the black wire under the metal plate behind the bottom screw,

    labeled HOT.

    8. Tighten the screw with a flathead screw driver.

    Selecting the AC Input Voltage

    The voltage is set to 115 V when shipped. To change the voltage, you

    must reset the jumpers located to the right of the AC power cord

    connection.

    Table 2 shows the input voltage selection.

    To change the voltage from 115 V to 230 V, proceed as follows:

    1. Remove the jumper from E3 to E5.

    2. Leave the jumper E2 to E4 as it is.

    3. Disconnect the jumper end from E1 and move it to E5 so it jumpers

    P2 to E5.

    To change the voltage from 115 V to 24 V, proceed as follows:

    1. Disconnect the jumper end from E5 and move it to E7 so it jumpersE3 to E7.

    2. Disconnect the jumper from E4 and connect it to E6, so it jumpers

    E2 to E6.

    3. Leave the jumper P2 to E1 as it is.

    Table 2. AC Input Voltage Selection

    24 V 115 V 230 V

    From To From To From To

    E3 E7 E3 E5

    E2 E6 E2 E4 E2 E4

    P2 E1 P2 E1 P2 E5

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    23/49

    CMX 240 Series Installation Guide 15

    Finding Ports for Connecting Other Cables

    Figure 4 shows the CMX 240 controller face plate. You see several ports

    on the unit.

    Custom Port

    The Custom Port is used for a TankNetof level sensing probes or any

    device you have ordered custom software for (see your Andover Con-

    trols representative). It is located just above COMM1, on the left side

    of the board.

    Communications Port

    Notice that the CMX 240 series controller has two RS-232 communica-

    tion ports, labeled COMM1 and COMM2 on the left side of the board.

    You can attach a cable to each port.

    COMM1 is preset for you to connect a printer to.

    COMM2 is preset for you to connect either a terminal orInfinity

    modem to.

    (COMM1 and COMM2 can be connected to a printer, terminal, com-

    puter, or modem by changing the port mode in the software.)

    COMM1 and COMM2cannotconnect to an LBUS orInfinetcable.

    Infinet Connector

    TheInfinetconnector is located below COMM2 on the left side of the

    board.

    Service Port

    The port labeled SERVICE PORT connects the Andover Controls Ser-vice Tool to the CMX 240controller. You can carry around the tool and

    plug it in as required to see how the controller system is functioning.

    See your Andover Controls representative about availability of the tool.

    Figure 4 shows the location of various parts inside any CMX 240. You

    may want to refer to this figure to locate parts during the installation.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    24/49

    16 CMX 240 Series Installation Guide

    Figure 4. Locations of Ports and Connectors on the CMX 240 FacePlate

    INFINETSHLD

    ----

    AC INPUT VOLTAGE SELECTION

    TO

    230V

    E3

    P2

    FROM

    24V

    TO

    E3

    P2

    FROM

    E4

    TO

    P2

    FROM

    115V

    CMX240

    ERROR

    SCAN

    CPU

    +

    6V BATTERY

    CLEAR-

    +

    USE COPPERCONDUCTORS

    ONLY

    F23A,250V

    SLOW BLOW

    NEU

    HOT

    GND

    ACINPUT

    E7 E5

    E2 E6 E2 E2 E4

    E1 E1 E5

    MODEM POWER

    F5, 2A

    THIS DEVICE COMPLIES WITH PART 15 OF

    AC POWER

    F23A,250V

    SLOW BLOW

    +

    -MEMORYSHLD

    COM+26V

    +26V

    RD

    TD

    RTS

    RD

    TD

    RTS

    RD

    TD

    RD

    TD

    SERVICEPORT

    THE FCC RULES. OPERATION IS SUBJECTTO THE FOLLOWING TWO CONDITIONS:( 1 ) THIS DEVICE MAY NOT CAUSE HARMFUL

    INTERFERENCE, AND( 2 ) THIS DEVICE MUST ACCEPT ANY

    INTERFERENCE RECEIVED, INCLUDINGINTERFERENCE THAT MAY CAUSEUNDESIRED OPERATION.

    F6, 1/8A

    COMM1

    COMM2

    CUSTOM

    PORT

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    25/49

    CMX 240 Series Installation Guide 17

    Connecting the Terminal Screen

    Connect the terminal or computer (running a terminal emulation pack-

    age such as CROSSTALK) to the CMX 240series controller as follows:

    1. Set up the terminal or computer on a table within cables length ofthe controller.

    2. Open the front of your controller cabinet.

    3. Either purchase a cable with pinouts matching those in the appendix

    or make one. Use that cable in the next step.

    4. Plug one end of the cable into the RS-232 port labeled COMM2 on

    the CMX 240.

    5. String the cable through the cable hole on the left side of the

    controller.

    6. Plug the other end of the cable into the terminal port.

    Connecting to the Infinity Modem

    If you are adding anInfinitymodem, you must install theInfinity

    modem before you connect it to the controller. Refer to theInfinity

    Modem Installation Guidefor instructions. After installing theInfinity

    modem connect it to the CMX 240 using the directions below.

    If you ordered the CMX 240controller with a modem it will already be

    installed. Follow the directions below to connect theInfinitymodem to

    the CMX 240:

    1. Find the pins and plastic jumper labeled P1on the upper left of the

    Infinity modem.

    Caution

    You must be absolutely certain P1is jumpered correctly or you may

    blow the F1 (2A picofuse) on the modem. If you have any questions

    contact your Andover Controls representative.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    26/49

    18 CMX 240 Series Installation Guide

    2. Be absolutely certainthat the left two pins are jumpered. You will

    see 5Vabove the left pin.

    Figure 5 shows how to correctly jumper the pins.

    Figure 5. Jumpering P1 Pins for CMX 240, Top View

    3. Connect the modem power cable to the CMX 240 controller port

    labeled MODEM POWER, on the left side just below COMM1.

    4. Plug the end of the RS-232 cable, hanging from the modem, into the

    COMM1 or COMM2 port on the CMX240controller.

    5. Run the telephone cable through the nearest knockout in the cabinet

    to the wall jack.

    Wiring Infinet to the CMX 240

    You wire the beginning ofInfinetto allInfinity CMX 240controllers.

    After that you wire theInfinetto eachInfinetcontroller.

    NoteYou must use shielded cables forInfinetto ensure compliance with the

    Class A FCC limits and to ensure reliable communications.

    You wire theInfinetto all CMX 240s using the following procedure:

    1. Open the front of the controller cabinet.

    Notice that to the lower left is a port labeledInfinet.

    The end of theInfinetcable has two wires and a shield. You wire

    them to the block terminal connector on theInfinetport.

    2. String the cable through the cable hole on the left side of the

    controller.

    15 V

    Jumper Pin

    5 V

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    27/49

    CMX 240 Series Installation Guide 19

    Figure 6 illustrates how to wire theInfinetcable to the removable

    terminal block connector on the lower left corner of all CMX 240s.

    Figure 6. Infinet Cable Wiring

    3. Trim back the shield over the wires.

    4. Take the first wire for the incomingInfinetand the first wire for the

    outgoingInfinetand slip both in the hole beneath the screw labeled

    with a plus sign (top).

    5. Tighten the screw down on them until the screw holds the wires in

    place.

    6. Slip the second (usually black) wire from eachInfinetcable under

    the screw labeled with a minus sign (middle) and tighten the screw

    down on them.

    7. Slip the shields from the incoming and outgoingInfinet cables under

    the screw labeled SHLD (bottom) and tighten the screw down on

    them.

    Wiring the TankNet and Probe Power Supply

    You connect the TankNet and probe power supply cables to a special

    port on the CMX 240series controller called the CUSTOM PORT.

    Figure 7 illustrates how to wire TankNetand probe power supply cablesto the CUSTOM PORT.

    +

    SHLD

    Infinet Connection

    WHITE WHITE

    BLACK

    BLACK

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    28/49

    20 CMX 240 Series Installation Guide

    Figure 7. Attaching the TankNet and Probe Power Supply Cables

    Wiring TankNet

    To connect the TankNetto the CUSTOM PORT use the following

    procedure:

    1. Trim back the shield over the wires.

    2. Slip the positive wire through the hole beneath the screw labeled

    with a plus sign.

    3. Tighten the screw down on it until the screw holds the wires in place.

    4. Slip the negative wire under the screw labeled with a minus sign and

    tighten the screw down on the wire.

    5. Tie back the shield.

    6. Read the following section about safety barriers and then wire them.

    Wiring Probe Power Supply

    To connect the probe power supply cable to the CUSTOM PORT usethe following procedure:

    1. Trim back the shield over the wires.

    2. Slip the common wire through the hole beneath the screw labeled

    COM.

    COM

    +26V

    Shield

    +IN

    IN

    Stahl Enclosureand Safety Barriers

    Shield

    TankNet Cable

    Power Cable

    SHLD

    Common

    Custom Port

    Positive Wire

    Negative Wire

    +26V Wire

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    29/49

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    30/49

    22 CMX 240 Series Installation Guide

    Note

    Any CMX 240can supply 26 V at 70 mA current for up to 20 tank

    probes. Refer to the manufacturers documentation for probe

    information.

    The TankNetrequires a communications Stahl intrinsic safety barrier.

    After you connect TankNetto any CMX 240 controller, you wire the

    other end of the TankNetcable to the safety barriers.

    The probe power supply cable requires a power supply Stahl intrinsic

    safety barrier. After you connect the power supply cable to any

    CMX 240controller, you wire the other end to the safety barrier.

    Figure 8 is an illustration of the safety barrier connection.

    Figure 8. Diagram of Safety Barrier Connection

    To Probe

    Wire Safety Barriers and Probe Carefully

    To Probe

    Hazardous AreaSafe Area

    Following Manufacturers Instructions

    Stahl SafetyBarrier Enclosure

    Communications

    Intrinsic Safety Barrier

    CommunicationsIntrinsic Safety Barrier

    To Custom Port

    Shield

    Common

    Ground

    To Custom Port

    Power SupplyIntrinsic Safety Barrier

    Shield

    +26V

    TankNetPositive Wire

    Negative Wire

    Probe PowerSupply

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    31/49

    CMX 240 Series Installation Guide 23

    Powering UpCMX 240 Series Controller

    Before you proceed, be sure the following are correct:

    1. Be sure AC input voltage selection is jumpered correctly.

    2. Be sure the AC power is wired properly. Check to be sure all three

    wires have been connected.

    3. Be sure the controller has a true earth ground.

    4. Be sure you have used the proper cables and correct lengths.

    5. Be sure theInfinethas been properly wired. Double check that theground wire is under the negative screw.

    6. Be sure thatInfinetcable shields are properly connected.

    7. If you have a TankNet, be sure the TankNet, safety barriers, and

    probes are properly connected.

    If you have completed all previous sections in this manual and installed

    allInfinetcontrollers, you are now ready to power up any CMX 240

    controller.

    To start the controller, turn on the AC power source (or close the power

    connection) and the controller starts automatically.

    (The real-time clock is always running on battery power, independent

    of AC power.)

    The following occurs (also occurs when you press the CLEAR

    MEMORY button):

    1. The CPU light begins flashing and flashes every 0.2 sec.

    2. The TD lights immediately start flashing to show COMM1,

    COMM2, the CUSTOM PORT, or theInfinetis transmitting data.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    32/49

    24 CMX 240 Series Installation Guide

    3. The RD lights begins flashing only if data is being received from

    COMM1, COMM2, CUSTOM PORT, or theInfinet. This may not

    happen immediately.

    4. If the CPU light flashes every 0.1 sec, it means the CPU has failed a

    RAM or ROM test. Call your Andover Controls representative for

    assistance.

    Connecting the Battery

    Once you have closed the AC power connection, you connect the bat-

    tery. The battery (6 V lead-acid battery) is to the lower left in the

    cabinet. You must connect the red and black wires, hanging from the

    right side of the CMX 240board, to the battery as follows:

    1. Find the black and red battery wires that are already attached to the

    right side of the CMX 240series controller labeled 6V BATTERY.

    2. Take the negative black wire from the controller and slip it onto the

    black socket on the battery.

    3. Take the positive red wire from the controller and slip it onto the red

    socket on the battery.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    33/49

    CMX 240 Series Installation Guide 25

    Interpreting Status LightsInside Cabinet

    Custom Port Status LightsThree custom port status lights display to the right of the custom port.

    Figure 9 shows how the lights appear for the custom port.

    Figure 9. Custom Port Status Lights

    The first light is yellow, the second green, the third red. These lights

    indicate the activity of the custom port. The different colored lights

    flash to indicate the following:

    TD (Yellow)Flashes when the custom port is transmitting data.

    RD (Green)Flashes when the custom port is receiving data.

    +26V (Red)Lights up to indicate power is being supplied to the

    probe. Does not light up when F4 ( A picofuse) is blown.

    Communication Status Lights

    Three communication port status lights display to the right of COMM1and COMM2.

    Figure 10 shows how the lights appear for each comm port.

    RD

    TD

    +26V

    CUSTOM (Green)

    (Yellow)

    (Red)

    PORT

    1

    8---

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    34/49

    26 CMX 240 Series Installation Guide

    Figure 10. Communication Status Lights for Comm1

    The first light is yellow, the second green, the third red. The lights to the

    right of COMM1 indicate communication activity through the COMM1

    port. The lights to the right of COMM2 indicate communication activity

    through the COMM2 port. The different colored lights flash to indicate

    the following:

    TD (Yellow)Flashes when the communication port is transmitting

    data.

    RD (Green)Flashes when the custom port is receiving data.

    RTS (Red)Lights up to indicate equipment (modem, terminal,

    printer) is on-line.

    Infinet Status Lights

    There are twoInfinetstatus lights to the right of theInfinetconnection.

    Figure 11 shows how the lights appear forInfinet.

    Figure 11. Communication Status Lights for Infinet

    The different colored lights flash to indicate the following:

    TD (Yellow)Flashes when theInfinetis transmitting data.

    RD (Green)Flashes when theInfinetis receiving data.

    RD

    TD

    RTS

    COMM 1 (Green)

    (Yellow)

    (Red)

    RD

    TD

    INFINET

    (Green)

    (Yellow)

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    35/49

    CMX 240 Series Installation Guide 27

    Modem Power Light

    On the far left middle of any CMX 240board there is a light labeled

    MODEM POWER. This lights up to indicate the controller is providing

    power for the modem. Does not light up when F5 (2A picofuse) is

    blown.

    System Activity Status Lights

    Four system activity status lights are located on the center of the board.

    Open the cabinet door and you see a string of green and red lights, some

    of them flashing.

    Figure 12 shows how the lights appear.

    Figure 12. System Activity Status Lights

    All these lights, except of course the ERROR light, turn on when the

    power comes up. The lights blink to indicate activity. The purposes of

    the four lights are as follows:

    AC POWERLights up to indicate the AC power is on. Does not

    light up when the controller is running on battery backup.

    CPUFlashes every 0.2 sec that the controller is active.

    SCANFlashes once for every scan of the controller.

    ERRORLights up if the controller fails the internal integrity

    check.

    SCAN

    AC POWER

    CPU

    ERROR

    (Green)

    (Red)

    (Red)

    (Red)

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    36/49

    28 CMX 240 Series Installation Guide

    Using the CLEAR MEMORY Button

    The CLEAR MEMORY button is the red button located near the top

    center of the controller. You press the red button only to cold start the

    controller.

    Connecting the Andover Controls Service Tool

    The SERVICE PORT, on the lower left corner of the controller, is to

    connect the Andover Controls Service Tool to anyCMX 240. The ser-

    vice tool will access allInfinetcontrollers on the sameInfinet. For

    information on availability of the Andover Controls Service Tool, con-

    tact your Andover Controls representative.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    37/49

    CMX 240 Series Installation Guide A-1

    Appendix A

    RS-232 Port

    Pinouts

    If you choose, you may use a standard 25-pin ribbon cable for connect-

    ing a modem to either a controller or a terminal. However, to connect

    any terminal to a controller, you should use a cable with the required

    pinouts.

    This appendix shows the required pinouts.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    38/49

    A-2 CMX 240 Series Installation Guide

    Table A-1 shows the pinouts for the RS-232 port on the Infinity CMX

    240 controller.

    Figure A-1 shows the required and optional pinouts for cables

    connecting a terminal to the controller, a modem to the controller, and

    a modem to the terminal.

    a. "To" and "From" are in relation to the Infinity CMX 240 controller."Modem" means it is required for the modem.

    Table A-1. Pinouts for RS-232 Comm Porta

    with Male DB25 Connector to Terminal

    Pin Number Purpose Direction Required

    1 Chassis --- NO

    2 TD From YES

    3 RD To YES

    4 RTS From MODEM

    5 CTS To MODEM

    6 DSR To MODEM7 GND --- YES

    8 DCD (CXD) To MODEM

    9 +V From NO

    10 -V From NO

    20 DTR From MODEM

    22 RI To NO

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    39/49

    CMX Series 240 Installation Guide A-3

    Figure A-1. Pinouts for Cables Connecting to RS-232 Ports

    on Controller

    Female End Female End

    23

    7

    23

    7

    or IBM PS/2 (25-pin)Connecting to VT 100 Connecting to

    Controller

    Female End Female End

    23

    5

    23

    IBM AT (9-pin)Connecting to Connecting toController

    7

    Female End Female End

    ModemConnecting to Connecting to

    Controller

    23

    7

    23

    788

    2020

    6 6

    Connected Over Modem

    45

    45

    Directly Connected Terminals or Workstations

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    40/49

    A-4 CMX 240 Series Installation Guide

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    41/49

    CMX 240 Series Installation Guide B-1

    Appendix B

    Probe Switch Settings

    This appendix shows how to set the tank probe DIP switch so that you

    can determine the point channel number for each tank probe.

    The DIP switch is located inside the probe head. For details on how to

    access the DIP switch, refer to the MTS installation guide supplied with

    the probe.

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    42/49

    Hardware Installation

    B-2 CMX 240 Series Installation Guide

    Set the tank probe switches as follows:

    1. Set the second and third switches to ON for Andover Controls

    software. If they are not ON (enabled), you do not see error

    messages.

    Figure B-1 shows the settings for switches 2 and 3 on the probe.

    Figure B-1. Switch Settings for Switches 2 and 3 on TankProbe

    Note

    The Power Supply Override should be set to OFF because you do not

    want to override the power supply.

    2. Set the switch 1 to OFF tonotoverride the power supply.

    3. Set switches 4 through 9 to the address that corresponds to the

    channel number of the probe.

    Figure B-2 shows the address switch settings for the tank probe

    channels 1 through 6. Be sure that the probe you assign to channel 1

    in the Pointwindow is set to address 0, as shown. The otherchannels correspond to subsequent address numbers.

    Refer to the MTS Systems Corporation documentation for further

    information on how to set the address switches.

    1 2 3 4 5 6 7 8 9ON

    Data Error Detection Enabled

    Communication Time-out Timer Enabled

    Set Other Switches for Address of Probe

    Power Supply Override

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    43/49

    Hardware Installation

    CMX 240 Series Installation Guide B-3

    Figure B-2. Switch Settings for Tank Probeson Channels 1 through 6

    1 2 3 4 5 6 7 8 9ON

    1 2 3 4 5 6 7 8 9ON

    Channel 1

    Channel 2

    1 2 3 4 5 6 7 8 9ON

    1 2 3 4 5 6 7 8 9ON

    Channel 3

    Channel 4

    1 2 3 4 5 6 7 8 9ON

    1 2 3 4 5 6 7 8 9ON

    Channel 5

    Channel 6

    (Address 0)

    (Address 1)

    (Address 2)

    (Address 3)

    (Address 4)

    (Address 5)

    32 16 8 4 2 1

    Binary Value of Each Switch

    1

    0

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    44/49

    Hardware Installation

    B-4 CMX 240 Series Installation Guide

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    45/49

    CMX 240 Installation Guide Index-1

    Index

    A

    AC power

    wiring 13

    AC Power light inside 27

    AC voltage

    setting 14

    Andover Controls Service Tool

    using 28

    B

    barrier

    connection 22

    C

    cabinet

    dimensions 3

    eyelets

    measurements to 10

    cable

    connecting to modem 18

    forInfinet5

    for lightning protection 6

    Infinetport 15port for RS-232 15

    RS-232

    pinouts A-2

    circuit requirements for power 4

    codes

    complying with 4

    communication ports

    locations of 15

    communications port

    COMM1 use 15

    COMM2 15computer

    connecting 17

    configuration

    planning 8

    controller

    dimensions 3

    CPU light inside 27

    D

    dimensions

    cabinet 3controller 3

    E

    ERROR light inside 27

    F

    features

    unique to CMX 2401

    Gground

    correcting 7

    inspecting 7

    requirements 6

    I

    Infinet

    connecting 18

    lightning arrester for 6

    Infinetcableconnecting 19

    Infinetcable numbers 5

    INFINET RD light inside 26

    INFINET TD light inside 26

    intrinsic safety barrier

    TankNet20, 21

    wiring 21

    J

    jumperfor CMX 24017

    forInfinity CX 900017

    forInfinity CX 920017

    L

    lightning arrester

    forInfinet6

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    46/49

    Index-2 CMX 240 Installation Guide

    M

    modem

    baud rate of 4

    mounting

    steps to 10

    P

    parts

    inside the controller 15

    requirements 9

    power requirements 4

    circuit 4

    power surges

    preventing 6

    powerup

    executing 23

    procedure to prepare for 23

    probe

    switch settings B-2

    R

    repair

    packaging required to ship for 9

    requirementsparts 9

    RS-232 port

    pinouts A-2

    S

    safety barrier

    connection 22

    SCAN light inside 27

    service portlocation of 15

    purpose of 28

    shields

    forInfinetcable

    connecting 19

    status lights

    communication ports 25, 26

    system and network activity 27

    TTankNet

    instrinsic safety barrier 20, 21

    temperatures

    for operating 8

    terminal

    connecting 17

    V

    voltageselecting for AC power 14

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    47/49

    CMX 240 Installation Guide Index-3

    W

    wiring

    connectingInfinetcable 19

    correct wire gauge for ground 7

    intrinsic safety barriers 21

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    48/49

    Index-4 CMX 240 Installation Guide

    www.PDF-Zoo.com

  • 7/22/2019 Andover Controls - CMX 240 Series Controller Installation Guide

    49/49