TEMPERATURE CONTROLLER User's ManualRESTRICTIONS ON USEWhen using this product in applications that require particular safety or when using this product in important facilities, please pay attention to the safety of the overall system and equipment. Install failsafe mechanisms, perform redundancy checks and periodic inspections and adopt other appropriate safety measures when it is necessary. AT-502
AT02 SERIES PID
Names and Functions of Parts
Upper Displayo
LEDsAT: Lit when the auto tuning is ON. OUT: Lit when the control output is ON. ALM: Lit when the alarm output is ON. LOCK: Lit when the key is locked.
PV
C
Displays PV values (current temperature, etc.) or setup items.
SVAT OUT ALM LOCK
Lower DisplayDisplays SV values (set temperature, etc.) and other parameter values.
SETATTENTION !1.Please read the SAFETY PRECAUTION section on reverse side before use of this product. 2.Please read this user's manual before use for proper operation. 3.Please safe guard this user's manual.
Key :Used to change numeric values.
Key :Switches the display. Hold down for 3 seconds to switch modes.
Key :Used to shift setup items or parameter digits.
Function SettingWarning! Please make sure the power is off, before making any changes on the DIP switch.ON 1 2 3 4 5 6
User Level Setting1 Power ONPVo
PID Control SettingEnsure the DIP switch is set to PID control mode before proceed further.1 Start with
DIP Switch 1O
C
2
3
4
5
6
The initial screen is displayed for about 3 seconds.
SVAT OUT ALM LOCK
operation mode.
K Type J Type
0~1200 C 0~500 CO
ON OFF OFF ON ON OFF ON OFF ON 2 The IC version
PV
o
C
Current PV value Current SV value
SV PVo
Input type
R Type PT-100
0~1700 CO O
is displayed for about 6 seconds.
C
tic IC version 2 Press
AT
OUT
ALM
LOCK
Reserved
-50~400 C OFF ON ONOFF ON OFF ON
SVAT OUT ALM LOCK
ON/OFF CONTROL
Control Mode
key for 3 seconds to the parameter mode.
PV
o
C
LVL uSr
PID CONTROL RELAY
3 The operation
SV PVo
Output
mode is displayed.
C
Current PV value Current SV value 3 Press
AT
OUT
ALM
LOCK
DC 24V(for SSR driven)
SVAT OUT ALM LOCK
List of Alarm Mode :
1 2 3 4 5 6 7 8 9 10 11 12
Deviation High Alarm Deviation Low Alarm Process High Alarm Process Low Alarm Deviation High/Low Alarm Band Alarm Deviation High Alarm (Standby) Deviation Low Alarm (Standby) Process High Alarm (Standby) Process Low Alarm (Standby) Deviation High/Low Alarm (Standby) Band Alarm (Standby)
4 Press
key for 3 seconds to the Alarm range setting mode.
key once and key once to the PID level.
PV
o
C
LVL Pid
SVAT OUT ALM LOCK
PV
o
C
AS1: Alarm range setting
SVAT OUT ALM LOCK
Temperature range varies with Input typeAt: Auto Tunning YES / no
4 Press
key for 3 seconds to the P mode.
PV
o
C
P1: Proportional band (P)
5 Press
key once to the Auto Tunning switch mode
SV PVo
0.1~300.0 COUT ALM LOCK
O
C
AT
SVAT OUT ALM LOCK
5 Press
key once to the I mode.
PV
o
C
i1: Integral time (I) 0~7200sec (Set 0 for P Control)
6 Press
key once to the PV Offset mode.
SV PVo
C
PoF: PV Offset
AT
OUT
ALM
LOCK
SVAT OUT ALM LOCK
-200.0~200.0 C
O
6 Press
key once to the D mode.
PV
o
C
Key Lock SettingPVo
7 Press
key once to the SV Offset mode.
SV PVo
C
SoF: SV Offset
d1: Derivative time (D) 0~1800sec (Set 0 for P Control)
AT
OUT
ALM
LOCK
C
SVAT OUT ALM LOCK
Under uSr level, press key for 3 seconds to enter Key Lock mode. Set Lock mumber according to the level of protection.8 Press
SVAT OUT ALM LOCK
-200.0~200.0 C
O
7 Press
key once to the operation mode.
key once to the Relay output cycle mode.
PV
o
C
Ct1: Output cycle 1 0~65sec
SVAT OUT ALM LOCK
PV
o
C
Current PV value Current SV value 8 Press
List of Key Lock Mode : usr Pid SEt ArG Others 0022 0 111 11 2 2Symbol : Can display and can be set : Can't display nor can't be setPVo
SVAT OUT ALM LOCK
SV Lock SettingC
key once to the SSR output cycle mode.
PV
o
C
Ct2: Output cycle 2 0~65sec
SVAT OUT ALM LOCK
SVAT OUT ALM LOCK
Under operation mode, press key for 3 seconds to lock the SV value. And press key for 3 seconds again to unlock the SV value.
9 Press
key for 3 seconds to the operation mode.
ON/OFF Control SettingEnsure the DIP switch is set to ON/OFF control mode before proceed further.1 Start with 1 Start with
Set Level Settingoperation mode.PVo
Argument Level SettingCurrent PV value Current SV value
C
This is used to display or hide arguments under user level. Arguments can be arranged in any order, but may not repeated.1 Start with
SV PVo
operation mode.
C
Current PV value Current SV value 2 Press
AT
OUT
ALM
LOCK
operation mode.
PV
o
C
Current PV value Current SV value
SVAT OUT ALM LOCK
key for 3 seconds to the parameter mode.
SV PVo
C
LVL uSr 2 Press
AT
OUT
ALM
LOCK
2 Press
key for 3 seconds to the parameter mode.
SV PVo
C
LVL uSr 3 Press
AT
OUT
ALM
LOCK
key for 3 seconds to the parameter mode.
PV
o
C
LVL uSr
SVAT OUT ALM LOCK
3 Press
key once and key once to the PID level.
key once and key twice to the SET level.
SV PVo
C
LVL SEt 3 Press
AT
OUT
ALM
LOCK
SVAT OUT ALM LOCK
PV
o
C
LVL Pid 4 Press
SVAT OUT ALM LOCK
key for 3 seconds to the Alarm mode.
key once and key three times to the ARG level.
PV
o
C
LVL ArG
SVAT OUT ALM LOCK
PV
o
C
AF1: Alarm 1~12 See List of Alarm Mode. AH1: Alarm Hysteresis 4 Press
4 Press
key for 3 seconds to the Hysteresis mode.
SV PVo
C
SVAT OUT ALM LOCK
HSt: Hysteresis ON/OFF 0.0~200.0 CO
AT
OUT
ALM
LOCK
key for 3 seconds to the 1-2 mode.
PV
o
C
1-2 select 1: non, AS1, At, PoF, SoF
5 Press
5 Press
key for 3 seconds to the operation mode.
key once to the Alarm Hysteresis mode.
SV PVo
C
AT
OUT
ALM
LOCK
SVAT OUT ALM LOCK
-200.0~200.0 C
O
5 Press
key once to the 1-3 mode.
PV
o
C
1-3 select 1: non, AS1, At, PoF, SoF
6 Press
SV Value Setting1 Start with
key once to the Heater / Cooling switch mode.
SV PVo
C
SVAT OUT ALM LOCK
Act: Heater/Cooling switch Ht / CL
AT
OUT
ALM
LOCK
6 Press
operation mode.
PV
o
C
Current PV value Current SV value 7 Press
key once to the 1-4 mode.
PV
o
C
1-4 select 1: non, AS1, At, PoF, SoF
SVAT OUT ALM LOCK
2 Press
key once to the SV value change mode.
PV
o
C
key once to the Decimal point position switch mode.
SV PVo
C
SVAT OUT ALM LOCK
dP: Decimal point position switch 0 / 0.0
AT
OUT
ALM
LOCK
7 Press
Current PV value Current SV value 8 Press
key once to the 1-5 mode.
PV
o
C
1-5 select 1: non, AS1, At, PoF, SoF
SVAT OUT ALM LOCK
key once to the Low Set Point mode.
SV PVo
C
LSP: Low Set Point
AT
OUT
ALM
LOCK
3 Press
SV PVo
key for change value and press key for change to the next digit and so on. 4 Press key once to the operation mode.
C
Current PV value Current SV value 9 Press
AT
OUT
ALM
LOCK
Temperature range varies with Input typeHSP: High Set Point
8 Press
key for 3 seconds to the operation mode.
SVAT OUT ALM LOCK
key once to the High Set Point mode.
PV
o
C
SVAT OUT ALM LOCK
Temperature range varies with Input type
10 Press
key for 3 seconds to the operation mode.
TERMINAL LAYOUTAT-502100~240 VAC 50/60 Hz 12 11 1 2NO
DIMENSIONS(mm)A BDevice
AT-402 / 602 / 9021 2NO
a b Panel Cutout
AT02 series AT-402
A 48 48 96 72 96
B 96 48 48 72 96
a45.5 +0.5 -0
b91 +0.5 -0
11 12 13 14 15 16 17 18 19 20 SSR
100~240 VAC 50/60 HzCOM
6 7 8 9 10 14 13
AT-502 AT-602 AT-702 AT-902
45.5 +0.5 45.5 +0.5 -0 -0 91 +0.5 -0 67.5 91+0.5 -0
ALM
COM
3 4 5 6 7 8 9 10
45.5 +0.5 -0 67.5 +0.5 -0 91 +0.5 -0
3 4 5
A B B
OUT
NC
OUT 100~240 VAC 50/60 HzCOM
NC
+0.5 -0
SSR
A B
ALM
SAFETY PRECAUTIONThis manual uses the following symbols to ensure safe operation of this controller.
AT-7021 2NO
B
WARNING Warnings are indicated when mishandling this controller might result in death or serious injury to user. CAUTIONCautions are indicated when mishandling this controller might result in minor injury to the user, or only physical damage to the controller.
8 9 10 11 12 13 14
A B B
WARNINGNote this incorrect wiring of this controller can damage it and lead to other hazards. Make sure the controller has been correctly wired before turning the power ON. Before wiring, or removing / mounting the controller, be sure to turn the power OFF. Failure to do so might cause electric shock. Do not touch electrically charged parts such as the power terminals. Doing so might cause electric shock. Do not disassemble the controller. Doing so might cause electric shock or faulty operation.
3 4 5 6 7
OUT ALM
NC
CAUTIONUse the controller within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere and etc.). Failure to do so might cause fire or faulty operation. Do not block ventilation holes. Doing so might cause fire or faulty operation. Do not allow lead clippings, chips or water to enter the controller case. Doing so might cause fire or faulty operation.