1
Figure 2: Patient Room Cooling with Active Chilled Beam System 1 3 4 5 LEGEND 1.) Heat recovery wheel (optional) 3.) Cooling/dehumidifying coil 4.) Heating coil 5.) MERV 13 filter 6.) Active chilled beam Constant 6 ACH 2 ACH (100% OA) 2 ACH (100% exhaust) T PATIENT ROOM 71% cooling reduction before reheat 6 Space Sensible Cooling Load (BTUH/FT ) 2 Ducted Airflow Rate (ACH ) -1 (BTUH/FT ) 2 Water Side Sensible Cooling (BTUH/FT ) 2 25 (100%) 20 (80%) 15 (60%) 10 (40%) 5 (20%) 2.0 2.0 2.0 7.2 7.2 7.2 7.2 7.2 17.8 12.8 7.8 2.8 0 Airside Sensible Cooling 2.0 2.0 Total Sensible Cooling (BTUH/FT ) 2 Space Reheat Requirement (BTUH/FT ) 2 0 5.2 25 20 15 10 22 0 0 0 T Min. 6 ACH 1 2 3 45 12% cooling reduction before reheat PATIENT ROOM LEGEND 1.) Heat recovery wheel (optional) 2.) Mixing section 3.) Cooling/dehumidifying coil 4.) Heating coil 5.) MERV 13 filter 6.) VAV terminal with reheat 6 Space Sensible Cooling Load (BTUH/FT ) 2 Ducted Airflow Rate (ACH ) -1 (BTUH/FT ) 2 Space Reheat Requirement (BTUH/FT ) 2 25 (100%) 20 (80%) 15 (60%) 10 (40%) 5 (20%) 6.9 6.0 6.0 6.0 6.0 25 22 22 22 22 0 2 7 12 17 Sensible Cooling Delivery Figure 1: Patient Room Cooling with All-air System Constant 6 ACH

ANSI-ASHRAE+170+Brief+Diagrams

  • Upload
    lim

  • View
    18

  • Download
    0

Embed Size (px)

DESCRIPTION

Ashrae Brief

Citation preview

Page 1: ANSI-ASHRAE+170+Brief+Diagrams

Figure 2: Patient Room Cooling with Active Chilled Beam System

1 3 4 5

LEGEND1.) Heat recovery wheel (optional)3.) Cooling/dehumidifying coil4.) Heating coil5.) MERV 13 filter6.) Active chilled beam

Constant 6 ACH

2 ACH (100% OA)

2 ACH (100% exhaust)

T

PATIENT ROOM

71% cooling reduction before reheat

6

Space SensibleCooling Load(BTUH/FT )2

Ducted AirflowRate

(ACH )-1 (BTUH/FT )2

Water SideSensible Cooling

(BTUH/FT )2

25 (100%)

20 (80%)

15 (60%)

10 (40%)

5 (20%)

2.0

2.0

2.0

7.2

7.2

7.2

7.2

7.2

17.8

12.8

7.8

2.8

0

Airside SensibleCooling

2.0

2.0

Total SensibleCooling

(BTUH/FT )2

Space ReheatRequirement(BTUH/FT )2

0

5.2

25

20

15

10

22

0

0

0

T

Min. 6 ACH

1

2

3 4 5

12% cooling reduction before reheat

PATIENT ROOM

LEGEND1.) Heat recovery wheel (optional)2.) Mixing section3.) Cooling/dehumidifying coil4.) Heating coil5.) MERV 13 filter6.) VAV terminal with reheat

6

Space SensibleCooling Load(BTUH/FT )2

Ducted AirflowRate

(ACH )-1 (BTUH/FT )2

Space ReheatRequirement(BTUH/FT )2

25 (100%)

20 (80%)

15 (60%)

10 (40%)

5 (20%)

6.9

6.0

6.0

6.0

6.0

25

22

22

22

22

0

2

7

12

17

SensibleCooling Delivery

Figure 1: Patient Room Cooling with All-air System

Constant 6 ACH