Figure 2: Patient Room Cooling with Active Chilled Beam System
1 3 4 5
LEGEND1.) Heat recovery wheel (optional)3.) Cooling/dehumidifying coil4.) Heating coil5.) MERV 13 filter6.) Active chilled beam
Constant 6 ACH
2 ACH (100% OA)
2 ACH (100% exhaust)
T
PATIENT ROOM
71% cooling reduction before reheat
6
Space SensibleCooling Load(BTUH/FT )2
Ducted AirflowRate
(ACH )-1 (BTUH/FT )2
Water SideSensible Cooling
(BTUH/FT )2
25 (100%)
20 (80%)
15 (60%)
10 (40%)
5 (20%)
2.0
2.0
2.0
7.2
7.2
7.2
7.2
7.2
17.8
12.8
7.8
2.8
0
Airside SensibleCooling
2.0
2.0
Total SensibleCooling
(BTUH/FT )2
Space ReheatRequirement(BTUH/FT )2
0
5.2
25
20
15
10
22
0
0
0
T
Min. 6 ACH
1
2
3 4 5
12% cooling reduction before reheat
PATIENT ROOM
LEGEND1.) Heat recovery wheel (optional)2.) Mixing section3.) Cooling/dehumidifying coil4.) Heating coil5.) MERV 13 filter6.) VAV terminal with reheat
6
Space SensibleCooling Load(BTUH/FT )2
Ducted AirflowRate
(ACH )-1 (BTUH/FT )2
Space ReheatRequirement(BTUH/FT )2
25 (100%)
20 (80%)
15 (60%)
10 (40%)
5 (20%)
6.9
6.0
6.0
6.0
6.0
25
22
22
22
22
0
2
7
12
17
SensibleCooling Delivery
Figure 1: Patient Room Cooling with All-air System
Constant 6 ACH