  • ANSI/TIA-606-BTh U d t d L b l St d dThe Updated Label Standard

    Todd Fries

  • CHANGES FROM LAST REVISION

    Adopts identification scheme specified in TIA-606-A Addendum 1

    Allows existing TIA 606 A identifier formats to continue to be used where they are already in use Allows existing TIA-606-A identifier formats to continue to be used where they are already in use.

    NOTE: An identifier is simply the printed text that will appear on a label as related to the standard.

    Harmonized with ISO/IEC 14763-2-1

    Creates new identification format for Cabling Subsystem 1 link identifiers (Horizontal links), Cabling Subsystem 2 and 3 links (Backbone cables) as well as telecommunications outlets, equipment outlets, splices, consolidation points and outdoor telecommunication spaces.

    Extends administration to all inter-building telecommunications cablingExtends administration to all inter building telecommunications cabling

    Creates new identifiers for telecommunications outlets, equipment outlets, splices, consolidation points and outdoor telecommunication spaces (maintenance holes, pedestals, hand holes, etc.)

    Administers Cabling Subsystem 2 and 3 links by pair groups, corresponding to ports (Pairs, strands g y y p g p p g p (and grouping identifiers) rather than copper pairs or single fibers. See clause 6.1.2.

    Administration of grounding and bonding systems beyond the TMGB and TGB

    Provides information on implementing automated infrastructure management systems.

  • LEGACY IDENTIFIERS

    The standard specifies two formats

    1. One fully backward compatible to TIA-606-A

    2. One based on TIA-606-A , addendum 1, but modified to be compatible with ISO/IEC TR14763-2-1 identifiers. This is meant for administration systems that are meant yto be deployed internationally.

    3 Voted to publish 2/7/20123. Voted to publish 2/7/2012

  • VISIBILITY AND DURABILITY 11.1

    The size color and contrast of all labels should beThe size, color, and contrast of all labels should be selected to ensure that the identifiers are easily read. Labels should be visible during normal maintenance of th i f t tthe infrastructure.

    Labels should be resistant to the environmental conditions at the point of installation (such as moisture, heat, or ultraviolet light), and should have a design life equal to or greater than that of the labeled component.equal to or greater than that of the labeled component.

  • LABELING 4.4

    Labels DO NOT need to include full identifiersLabels DO NOT need to include full identifiers. Only a portion of the identifiers needed to identify the component within the space it is located are requiredcomponent within the space it is located are required.

  • 11.2 MECHANICAL GENERATION

    The text on labels shall be machine generated.

  • CONVENTIONS AND SYMBOLS

    + sign in front of an identifier specifies that the+ sign in front of an identifier specifies that the next portion of the identifier is a location aspect for ISO/IEC TR 14763-2-1 compatible identifiers. Plus only needs to appear in the records section andPlus only needs to appear in the records section and not on the actual label.

    = sign in front of an identifier specifies a function aspect. (Example: =XO for telecommunications outlet)

  • CONVENTIONS AND SYMBOLS [[[+c]+b][f]s.][x]y

    Anything in square brackets [ ] may not be present depending on class.

    Characters in italics k,l,m,o,u are variable fields, , , ,

    The period . separates the portion of the identifier for the space from the identifier for the portion of the rack or frame

    The colon : is used as a prefix to port identifiersThe colon : is used as a prefix to port identifiersThe underscore _ character separates the vertical and horizontal coordinates of a closure in a cabinet, frame or wall section or to separate a range of ports, pairs or fiber numberspairs or fiber numbers.

    The forward slash / is used between near end/far end identifiers on a horizontal cable, backbone cable or telecommunications pathway.

    The backward slash \ is used between near end/far end identifiers on a patch cord or jumper.

    The hyphen - is used to prefix portion of equipment identifiers (e.g. switch name and switch port.

  • SELECT YOUR CLASS

    Class 1 FEWER THAN 100 users single TS roomClass 1 - FEWER THAN 100 users, single TS room

    Class 2 - HUNDREDS OF USERS multiple TSS in a single building

    Class 3 - 1000+ USERSClass 3 1000 USERS

    Class 4 - 1000s AND MULTIPLE LOCATIONS

  • 4 CLASSES OF COMPLEXITY

    CLASS 1

    An organization whose needs are served by a single E i t R Th ER i th l TSEquipment Room. The ER is the only space TS administered. There are no TRs and no Cabling S bs stem 2 and 3 cable labeling or o tside plantSubsystem 2 and 3 cable labeling or outside plant cabling systems to administer.

  • REQUIRED IDENTIFIERS

    (R) Cabling Subsystem 1 link identifier. (Horizontal Link)

    (R) Patch panel port and patch panel termination point identifiers

    (S) (R) TS Identifier

    (R) Cabinet, rack, enclosure, wall segment identifier

    (R) Patch panel or block identifier(R) Patch panel or block identifier

    (R) TMG Identifier + from object

    (R) TGB Identifier + from object

    Object is optional when the corresponding elements are present

    (R) TGB Identifier + from object

    (R) BCT Identifier (bonding conductor telecommunications)

  • TS IDENTIFIER5.1.1.1

    F = Numeric character(s) identifying the floor of aF Numeric character(s) identifying the floor of a building occupied by the TS.

    S Al h h t ( ) i l id tif i th TSS = Alpha character(s) uniquely identifying the TS or computer room on floor f.

    1A +fs if compatible with 1A pISO/IEC TR14763-2-1

  • RACK, CABINET, FRAME & WALL SEGMENTS5 1 2 2 1

    Add identifiers for racks and cabinets that can be applied to f

    5.1.2.2.1

    any space. fs.xy

    XY may use

    Grid Coordinates (e.g. AG54) or

    Row/Rack in large spaces (e.g. RAR05) orRow/Rack in large spaces (e.g. RAR05) or

    Rack # for small spaces (e.g. R4 for Rack 4)

    +fs.xy if compatible with ISO/IEC TR14763-2-1

  • SAMPLE CABINET IDENTIFIER

    X CoordinateAA AD AE AF AG AH AI AJ AK AL AM ANACAB

    0101

    03

    04

    02

    Sample

    Right Front Corner

    06

    07

    08

    05

    pCabinet

    08

    09

    10

    11

    1A.AJO5Y Coordinate

    12

    13

  • RACK/CABINET LOCATION EXAMPLE

  • IDENTIFICATION SCHEME FOR RACKS AND CABINETS 5.1.2.6

    All racks and cabinets should be labeled front and back. This should be on a permanent part of the cabinet or rack?

    For rooms with access floors, each rack and cabinet toFor rooms with access floors, each rack and cabinet to have a unique identifier based on floor tile coordinates. The location of the floor space grid where the right front corner of the cabinet is located determines the identifier.of the cabinet is located determines the identifier.

    If cabinet rests on more than one tile, the same corner of each cabinet can be used to identify the grid locationeach cabinet can be used to identify the grid location.

    Example: Right front corner

  • CABINET & RACK LABELING

  • NON-GRID COORDINATE EXAMPLE5 1 2 4

    There is no need for the row portion of the identifier if

    5.1.2.4

    (as example) the TS has only a single row of cabinets.

    2C.1, 2C.2, 2C.3, 2C.42C.1, 2C.2, 2C.3, 2C.4

    Each rack marked as 1, 2, 3 and 4 in room 2C.

  • PATCH PANEL IDENTIFIER 5.1.3.1.1

    fs.x1y-r1 or AD02-45

    5.1.3.1.1

    r1 = One or two characters designating the patch panel location beginning at the bottom. The quantity of characters shall be the same for all patch panels in the cabinet or rackshall be the same for all patch panels in the cabinet or rack.

    Horizontal cable managers are not included when sequencing patch panelssequencing patch panels.

    ___ ___ ___ eg., AD02-45 would be the topmost patchAD 02 - 45 panel in rack units from the bottom at location AD02

    X coordinate

    Y coordinatePanel

    +fs.x1y1+r1

    ISO/IECY coordinate ISO/IEC compatible

  • PATCH PANELIDENTIFIER

  • PATCH PANEL IDENTIFIER (Option #2) 5.1.3.1.1

    fs.x1y-r1 or AD02-F27

    ( p ) 5.1.3.1.1

    r1 = ann - One or two characters designating the patch panel location, within cabinet/rack fs.x1Y1, beginning at the bottom of the cabinet or rack. The letter indicating thethe bottom of the cabinet or rack. The letter indicating the side may be A, B, C, D or N, S, E, W from the North, South, East or West, or F and R for the front and rear.

    Horizontal cable managers are not included when sequencing patch panels.

    eg AD02 F27 would be the front patch___ ___ ___ eg., AD02-F27 would be the front patchAD 02 - F27 panel in rack/cabinet at location AD02

    X coordinatePanelY coordinate Panel

  • PATCH PANEL IDENTIFIER5.1.3.1.3.1

    Where cables are diversely routed between patch panels, l b l l th f f id tifi ti h ll b d t

    5.1.3.1.3.1

    label colors or other forms of identification shall be used to reflect cable route diversity.

    Colors may be used for labels, modular jacks, twisted pair patch cables, to indicate different applications (e.g. production, test, development, Internet)

    Use manufacturer provided labels and mounting surfaces wherever possible.p

  • PATCH PANEL LABELING [F1S1.][X1Y1-r1] Ports PN1 to[F2S2.]X2Y2-r2 Ports PN2 5 1 3 1 3 1[ ][ ] [ ]

    f1s1 = Space identifier optional.

    5.1.3.1.3.1

    p p

    X1Y1-r1 = Near end patch panel identifier and near end room name may be omitted. (Near end / Far end room can be omitted if within the same space.

    PN = Port number range near end and or far end.

    AJ05-35 p 01-24 to AQ03-35 p 01-24

    Use of word Ports (P) is acceptable for clarification on patch panel labels

  • TWISTED PAIR PATCH PANEL IDENTIFIER(Without Subpanels)

    Near end patch panel location and panel identifier to be followed by (if space permits) the far end panel locationfollowed by (if space permits) the far end panel location and panel identifier + port numbers

    AD02 35 p 01 06 to AG03 35 p 01 06AD02-35 p 01-06 to AG03-35 p 01-06

  • TWISTED PAIR PATCH PANEL IDENTIFIER

  • OPTIONAL

    PANEL FZ54-45

    Ports 01-24 to HDA01 AJ17-45 Ports 01-24

    The Far end telecommunication space name MDA (Main Distribution Area) or HDA (Horizontal Distribution Area)(Main Distribution Area) or HDA (Horizontal Distribution Area)can be added for additional information.

  • PATCH PANEL PORT IDENTIFIERS(Single port 5.1.4.1)

    f1s1.x1y1-r1:P1 or 1A.AJ05-35:01

    ___ ___ ___ ___ ___ eg., 1A.AJ05-35:01 would be data

    1A. AJ 05 - 35:01 center on floor 1 in space A withrack/cabinet at grid location AJ05

    Patch panel B and port 01 in the rack/cabinet. Data center(optional)

    X coordinate

    Y di t

    (optional)

    Panel Port

    Y coordinate

    :B01 for subpanels:B01 for subpanels

    :01-06 range of ports

  • POWER/DATA(Labeling 5.1.4.4)

    Power and Data over balanced pairs may use th f ll i b lthe following symbol.

  • PATCH PANEL PORT IDENTIFIERS (For patch panels that include sub panels) 5.1.4.1

    f1s1.x1y1-r1:P1 pn or 1A.AJ05-35:B06

    5.1.4.1

    ___ ___ ___ - ___ ___ eg.: 1A.AJ05-35:B6 would be data

    1A. AJ 05 - 35:B06

    Data center(optional)

    center on floor 1 in space A withrack/cabinet at grid location AJ05

    Patch panel B and port 6 in the rack/cabinet I O and Q excluded

    X coordinate

    (optional)

    PanelPort

    rack/cabinet. I , O and Q excluded.

    Y coordinate Sub panel

  • PATCH PANEL PORT IDENTIFIERS(Range of ports)

    f1s1.x1y1-r1:PN1 or 1A.AJO5-35:01-06

    ___ ___ ___ ___ ___ e.g.., 1A.AJ05-35:01-06 would be data

    1A. AJ 05 - 35:01-06 center on floor 1 in space A withrack/cabinet at grid location AJ05

    Patch panel B and ports 1-6 in the rack/cabinet. Data center

    X coordinate

    Y di t

    (optional)

    Panel

    PortY coordinate

    Port

  • CABLE BETWEEN PATCH PANELS/BLOCKS F1S1.X1Y1-r1:P1[-P2] / F2S2.X2Y2-r2:P3[-P4] 5 1 5 1

    f1s1 = Space identifier optional.

    5.1.5.1

    X1Y1-r1 = Near end patch panel identifier (Near end/Far end space ID can be omitted if within the same spaceend space ID can be omitted if within the same space. 5.1.5.3)

    P P t b d d f dP = Port number range near end and or far end.

    AJ05 35:01 06 / AQ03 35:01 06AJ05-35:01-06 / AQ03-35:01-06

  • PRE-TERMINATED CABLE LABELING

  • MULTI FIBER TRUNK WITH MPO & LC CONNECTORS

    Free t distanding

    equipment no patch panel

  • PRE-TERMINATED CABLE LABELING P1n/P2n 5 1 5 3

    A 12-strand multi-fiber trunk cable equipped with MPO (multi fiber) connectors on one end and LC connectors on the other

    5.1.5.3

    fiber) connectors on one end and LC connectors on the other end.

    Example of a label wrapped around a 12 strand subgroup:Example of a label wrapped around a 12 strand subgroup:

    FD12- 42-B Ports 01-06 / FG08-01- Ports 01-06

    Grid Location One MPO MPO/LC cablesSequential 2 digit Grid Location

    Panel

    One MPO Connection

    MPO/LC cables are always 12 strand

    q gID for each 12 strand cable

    Sub Panel

  • PRE-TERMINATED CABLE LABELING

  • PRE-TERMINATED CABLE LABELING

  • PRE-TERMINATED CASSETTE LABELING

  • CABLING SUBSYSTEM 1 LINK IDENTIFIER5.1.7.3

    All elements of the horizontal link shall be labeled at the time they are installed with the horizontal link identifier.

  • WALL OUTLET/HORIZONTAL LINK

    Example: Showing simple floor 1, Space A, Rack .1 with panel 35 Rack units from bottom, port 08, 09, etc.p , p , ,

  • CABLING SUBSYSTEM 1 LINK (ANSI/TIA-606-B) 5 1 6 1

    a

    t

    c

    h

    #

    t

    #

    a

    c

    k

    #

    1

    k

    #

    2

    c

    h

    #

    o

    r

    t

    #

    5.1.6.1

    e

    a

    r

    e

    n

    d

    p

    a

    a

    r

    e

    n

    d

    p

    o

    r

    t

    e

    a

    r

    e

    n

    d

    r

    a

    a

    r

    E

    n

    d

    r

    a

    c

    a

    r

    e

    n

    d

    p

    a

    t

    c

    e

    a

    r

    e

    n

    d

    p

    o

    N

    e

    F

    a

    x1y1 -

    N

    e

    r1 : p1 / x2y2 - r2 : p2

    F

    a

    F

    a

    N

    e

    Class 1

    AG09-27:01 / AJ06-27:01

    y p y p

    AG09-27:01 / AJ06-27:01Format recommended for links that terminate on panels or

    blocks that are not in the same space.

  • EQUIPMENT ROOM OUTLET AND TELECOMMUNICATIONS OUTLET IDENTIFIERS (Horizontal Link Suffix) 5 1 8 1

    AG04-35:01 / AD06-35:01=XL:05

    (Horizontal Link Suffix) 5.1.8.1

    XO = (OPTIONAL) Equipment Room Outlet

    XC (OPTIONAL) C lid ti P i tXC = (OPTIONAL) Consolidation Point

    XL = (OPTIONAL) ZDA Port

    XSz = (OPTIONAL) Splice where z is the appropriate distance along the cable of the splice from the termination point in the telecomm nications room or HDApoint in the telecommunications room or HDA.

    NOTE: The :05 is the optional port on a consolidation point.

  • TMGB IDENTIFIERR

    a

    #

    f

    l

    o

    o

    r

    #

    T

    S

    a

    l

    p

    h

    T

    M

    G

    B

    TMGBf s -

    Class 1

    1A-TMGB

  • TMGB MAIN GROUNDING BUSBAR

  • MULTIPLE ELEMENT BONDING & GROUNDING IDENTIFIER

    5.1.13.1

    RBONDING & GROUNDING IDENTIFIER

    2A-TGB1i = optional sequence if more G

    a

    #

    2A-TGB1than 1 TGB in a space.

    T

    G

    B

    f

    l

    o

    o

    r

    #

    T

    S

    a

    l

    p

    h

    a

    TGBf s - i[ ]

    Class 1

  • IDENTIFIER FOR BONDING CONDUCTOR ATTACHED TO TMGB

    5.1.19

    R

    a

    #

    CONDUCTOR ATTACHED TO TMGB

    Applicable bonding identifiers

    T

    M

    G

    B

    f

    l

    o

    o

    r

    #

    T

    S

    a

    l

    p

    h

    a

    Applicable bonding identifiers allow the / Object suffix. TMGB, TGB, MBN, RGB

    TMGBf s - / object

    Class 1

    1TER=TMGB/A12

  • IDENTIFIER FOR BONDING CONDUCTOR ATTACHED TO TGB R

    #

    CONDUCTOR ATTACHED TO TGB

    T

    G

    B

    f

    l

    o

    o

    r

    #

    T

    S

    a

    l

    p

    h

    a

    #

    O

    b

    j

    e

    c

    t

    Applicable bonding identifiers allow the / Object suffix. TGB,

    TGBf sTf T

    - / object

    O TBB, MBN, RGB

    Class 1

    2C=TGB/acpanel

  • REQUIRED RECORDS CLASS 1

    Cabling Subsystem 1 LinkCabling Subsystem 1 Link

    Can be done with a paper based system or non-proprietary software.

  • 4.1 GENERAL SPREADSHEETS

    Each identifier and records makes up a rowEach identifier and records makes up a row.

    Each column contains a particular item of information for the record.

  • SPREADSHEET

  • SCOPE OF ANSI-EIA-TIA-606

    Identifiers

    Pathway Space T i ti T i tiyIdentifiers

    Cable Identifiers

    pIdentifiers

    Grounding Identifiers

    Termination Hardware Identifiers

    Termination Position

    Identifiers

    Required Linkages

    Telecommunications Records

    Required

    Grounding Records Cable

    RecordsPathway Records

    Required Linkages Termination

    Position Records

    Termination Hardware Records Space

    R d

    User Codes

    Records

  • TR CABLING SUBSYSTEM 1 LINK RECORDS REQUIRED FOR THE NEEDS OF A CLASS 1 SYSTEM

    Horizontal Link Records shall contain the following i f tiinformation. Location of work area outlet connector (room, office, or grid local)

    Cabling Subsystem 1 Link Identifier (primary indexing identifier) Cabling Subsystem 1 Link Identifier (primary indexing identifier)

    Outlet connector type (8 position modular, T568B cat 6)

    Cross connect hardware (48 port modular patch panel T568A Cross connect hardware (48 port modular patch panel, T568A, category 6)

    Cable type (4 pr, UPT, Cat 6, plenum)

    Cable Length (e.g.: 51m/154ft.)

    Service Record of link (e.g. passed category 6 at install 1/12/11.

  • RECORD KEEPING METHODS

  • CLASS 2

    An organization with one or more TelecommunicationAn organization with one or more Telecommunication

    spaces, but in a single building.

    An ER with one or more TSs.

  • REQUIRED IDENTIFIERS

    Identifiers required for a class 1 administration t lsystem plus..

    Building Cabling Subsystem 2 & 3 backbone cable identifier

    Building Cabling Subsystem 2 & 3 backbone port identifier

    Fire stopping location identifier Fire stopping location identifier

  • BACKBONE CABLE IDENTIFIER

    fs1.x1y1-r1:P1[P2] / fs2.x2y2-r2:P3[P4]y [ ] y [ ]

    1A AJ06-27:01-24 / 2A AG09-27:01-24Can be a single port or range of ports 6.1.3

    1A.AJ06 27:01 24 / 2A.AG09 27:01 24

    ISO = +1A.AJ06+27:01/+2A.AG09+27:01

  • BACKBONE CABLE IDENTIFIERANSI/TIA606-B 6.1.2.3

    In the new standard, it is treated almost the same as a ,standard Cabling Subsystem 1 link identifier as described in a Class 1 installation.

    Administration of backbone cables is by pair groups (corresponding to ports) rather than copper pairs or single fibers.single fibers.

    Each port or pair on a building Cabling Subsystem 2 or 3 cable shall have a unique identifier. Individual optical q pfibers and balanced pairs are typically color coded rather than individually labeled.

  • BACKBONE CABLE PAIR GROUP IDENTIFIER(For balanced pair groups. i.e. single pair, four pairs)

    6 1 2 1

    fs1.x1y1-r1:p1 / fs2.x2y2-r2:p2

    6.1.2.1

    y p y p

    1A.AJ06-27:01 / 2A.AG09-27:01

    New format based on pair groups corresponding to ports (rather than individual fibers or pairs)

    P1 = port or termination at patch panel or block #1

    P2 = port or termination at patch panel or block #2

    p ( p )

    Terminating both ends with modular jack = 4 pair

    Terminating both ends on IDC blocks = 2 pair

  • FIRESTOPPING LOCATION IDENTIFIERCompatible with ISO/IEC 14763-2-1

    6 1 4

    [[C1-]b1-][f1]s1 / [[C2-]b2-][f2]s2=U(n[d)])= F[m]

    6.1.4

    [[ ] ][ ] [[ ] ][ ] ( [ )]) [ ]

    SF02-2A/3A=U(3)=FSF02 2A/3A U(3) F

    The Firestop for conduit sleeve 3 would be between pTelecom rooms 2A and 3A in building SF02

    U = Pathway

    F = Firestop

  • REQUIRED RECORDS CLASS 2

    One TS record for each TS

    Cabling Subsystem 1 link records as specified class I

    One cabling subsystem 2 or 3 cable record for eachOne cabling subsystem 2 or 3 cable record for each backbone cable

    One TMGB record for each TMGBOne TMGB record for each TMGB

    One TGB record for each TGB

    One Fire-stopping record for each location

  • CLASS 3

    A Telecommunications infrastructure serving anA Telecommunications infrastructure serving an organization or enterprise in a campus environment. This could encompass several hundred to several thousand users. There are multiple buildings and outside plant cabling systems to identify.

  • CLASS 3 REQUIRED IDENTIFIERS(Those of Class 1 and 2 plus)

    Infrastructure Identifiers

    Building Identifier

    Campus Inter building cable Identifier. Backbone

    Campus Inter building cable pair or optical fiber

    identifier. Backbone

  • INTER-BUILDING CABLE IDENTIFIER(Backbone) R

    7.1.3.1

    c1-b1-f1s1.x1y1-r1:P1[P2] / c2-b2-f2s2.x2y2-r2:P3[P4]

    A-ENG-1A AGO5-35:01-06 / B-ADM-1A AD06-35:01-06A-ENG-1A.AGO5-35:01-06 / B-ADM-1A.AD06-35:01-06

    OrOr

    ENG 1A R4 35 01 06 / ADM 1A R5 35 01 06ENG-1A.R4-35:01-06 / ADM-1A.R5-35:01-06

  • INTER-BUILDING CABLE PAIR/PORT IDENTIFIER (Backbone) R

    7.1.4.1

    ( )

    c1-b1-f1s1.x1y1-r1:P1 / c2-b2-f2s2.x2y2-r2:P3

    A-ENG-1A AGO5-35:01 / B-ADM-1A AD06-35:01A-ENG-1A.AGO5-35:01 / B-ADM-1A.AD06-35:01

    OrOr

    ENG 1A R4 35 01 / ADM 1A R5 35 01ENG-1A-R4-35:01 / ADM-1A-R5-35:01

  • REQUIRED RECORDS

    All records from a Class 2 Systemy

    One Building Record for each building

    One campus inter-building cable record for each

    campus backbone cable.

  • CLASS 4

    A Telecommunications infrastructure that extendsA Telecommunications infrastructure that extends across multiple geographic locations. Class 4 specifies multiple campus telecommunications infrastructure.p p

  • REQUIRED IDENTIFIERS

    All identifiers from a Class 3 system including:All identifiers from a Class 3 system including:

    Site or Campus Identifier

  • SITE OR CAMPUS IDENTIFIER R

    C = One or more alphanumeric characters identifying a site or campus. Additional identifiers may be added if desired in parentheses after the end of the required formatend of the required format.

  • SITE OR CAMPUS RECORD

    Site or campus name

    Site or campus location

    Contact information for local administrator of infrastructureContact information for local administrator of infrastructure

    List of all buildings at the site or campus

    Location of main cross connect, if applicable

    Access hours if applicableAccess hours, if applicable

  • AUTOMATED INFRASTRUCTURE MANAGEMENT SYSTEMS O

    Administered by paper based, proprietary, y p p p p yspreadsheets, databases.

    Systems can be software and or hardware basedSystems can be software and or hardware based.

    The system should be capable of documenting the i f t t l t d ib d i thi t d dinfrastructure elements as described in this standard.

  • COLORS(Required if color coding is used)

    Demarcation point Pantone 150C Orange

    N k i P 3 3C GNetwork connection Pantone 353C Green

    Common equipment Pantone 264C Purple

    K t P t 184C R dKey system Pantone 184C Red

    First level backbone Pantone White

    (MC IC or IC HC)Intra building backbone Pantone 422C Gray(MC-IC or IC-HC)Intra-building backbone Pantone 422C Gray

    (IC-HC) Inter-building backbone Pantone 465C Brown

    Horizontal Pantone 291C BlueHorizontal Pantone 291C Blue

    Other Pantone 101C Yellow

  • DATABASE MANAGEMENT

    SOFTWARE BASED ADMINISTRATION SYSTEM

    A Class 1 to 4 administration system may alternately be implemented by means of a simple spreadsheet in a non-proprietary software program.