 Apache Loads (ASHRAE) User Guide IES Virtual Environment Copyright © 2014 Integrated Environmental Solutions Limited. All rights reserved. No part of the manual is to be copied or reproduced in any form without the express agreement of Integrated Environmental Solutions Limited.

Apache Loads

  • Upload
    brian

  • View
    215

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Apache Loads

7/23/2019 Apache Loads

http://slidepdf.com/reader/full/apache-loads 1/11

 

Apache Loads (ASHRAE) 

User Guide 

IES Virtual Environment

Copyright © 2014 Integrated Environmental Solutions Limited. All rights reserved.

No part of the manual is to be copied or reproduced in any form without the express agreement

of Integrated Environmental Solutions Limited.

Page 2: Apache Loads

7/23/2019 Apache Loads

http://slidepdf.com/reader/full/apache-loads 2/11

 

VE2014 Apache Loads (ASHRAE) 2

Contents

1 Introduction ........................................................................................................................... 3

2 Analysis type and results file name ....................................................................................... 4

2.1 Analysis type .......................................................................................................................... 42.2 Results file (for both .htg and .clg files) ................................................................................. 5

3 Heating Loads ........................................................................................................................ 6

3.1 Interface for Heating Loads Calculation ................................................................................ 6

3.1.1 Heating Loads Calculation ................................................................................................. 6

3.1.2 Auxiliary ventilation air exchange ..................................................................................... 6

3.1.3 Natural ventilation air exchange ....................................................................................... 7

3.1.4 Include local and (when link ticked opposite) SunCast sky shielding ................................ 7

3.1.5 Include DHW? .................................................................................................................... 7

3.1.6 Time settings for profiles ................................................................................................... 7

3.1.7 Calculate ............................................................................................................................ 7

3.1.8 Save & exit ......................................................................................................................... 7

3.1.9 Close .................................................................................................................................. 7

4 Cooling Loads......................................................................................................................... 8

4.1 Interface for Cooling Loads Calculation ................................................................................. 8

4.1.1 Cooling Loads Calculation .................................................................................................. 8

4.1.2 Auxiliary ventilation air exchange ..................................................................................... 8

4.1.3 Natural ventilation air exchange ....................................................................................... 9

4.1.4 SunCast Link? ..................................................................................................................... 9

4.1.5 Design Day (for profiles) .................................................................................................... 9

4.1.6 Calculation Period.............................................................................................................. 9

4.1.7 Save & exit ......................................................................................................................... 9

4.1.8 Calculate ............................................................................................................................ 9

4.1.9 Cancel ................................................................................................................................ 9

5 Simulation (Heat Balance Method) settings ........................................................................ 10

5.1.1 Simulation Options .......................................................................................................... 10

5.1.2 Output Options ................................................................................................................ 10

5.1.3 Simulation time step........................................................................................................ 10

5.1.4 Preconditioning ............................................................................................................... 10

6 Autosizing settings ............................................................................................................... 11

6.1 Interface for Autosizing settings.......................................................................................... 11

6.1.1 Re-zero autosized parameters ........................................................................................ 11

6.1.2 Undo last autosize ........................................................................................................... 11

Page 3: Apache Loads

7/23/2019 Apache Loads

http://slidepdf.com/reader/full/apache-loads 3/11

 

VE2014 Apache Loads (ASHRAE) 3

1  Introduction

ASHRAE Loads (also known as Apache Loads or ASHRAE Heat Balance Method) performs

heating and cooling load calculations according to the ASHRAE Heat Balance Method, as

described in the ASHRAE Handbook of Fundamentals.

Results from ASHRAE Loads are displayed by Vista.

For an account of calculation methods used in ASHRAE Loads see ASHRAE Heat Balance

Method Calculation Methods.

Page 4: Apache Loads

7/23/2019 Apache Loads

http://slidepdf.com/reader/full/apache-loads 4/11

 

VE2014 Apache Loads (ASHRAE) 4

2  Analysis type and results file name

2.1 

Analysis type

ASHRAE Loads offers two types of analysis which you can select using the ‘Analysis type’

option. Select ‘Room and Apache system loads’ to perform an analysis of room heating and

cooling loads and the associated loads on Apache Systems.

Page 5: Apache Loads

7/23/2019 Apache Loads

http://slidepdf.com/reader/full/apache-loads 5/11

 

VE2014 Apache Loads (ASHRAE) 5

Alternatively, select ‘ApacheHVAC system loads’ to analyse loads on a specified ApacheHVAC

system. Then select the ApacheHVAC system using the drop-down menu in the frame headed

‘Simulation (Heat Balance Method) settings’. If you tick the box labelled ‘Update ApacheHVAC

system sizes?’ the equipment sizes calculated by the analysis will be assigned to components in

the ApacheHVAC system.

2.2  Results file (for both .htg and .clg files)

Here you can specify the name given to the two files where the results will be stored. The

Heating Loads and Cooling Loads results are stored in files with extension .htg and .clg,

respectively.

Page 6: Apache Loads

7/23/2019 Apache Loads

http://slidepdf.com/reader/full/apache-loads 6/11

 

VE2014 Apache Loads (ASHRAE) 6

3  Heating Loads

Heating Loads implements ASHRAE Heat Balance Method procedures for the calculation of

room heating requirements and the sizing of heating equipment.

Steady-state room heat losses are calculated in the absence of casual and solar heat gains. The

calculation optionally includes the effects of mechanical and natural ventilation air exchanges.

The time, day and month of the heating loads calculation can be chosen. Ensure that the time

chosen matches a heated period in the modelled building.

Results are presented (in the program Vista as tables or graphs of room or zone heat loss,

broken down by heat loss mechanism. Losses can be expressed on a floor area or room volume

basis. Room temperatures are also displayed. The data may be exported to other applications

such as spreadsheets and word processors.

For a description of the calculation methods used in ApacheLoads see ASHRAE Heat Balance

Method Calculation Methods.

3.1 

Interface for Heating Loads Calculation

3.1.1  Heating Loads Calculation

Tick this box to include a Heating Loads calculation when you click on Calculate.

3.1.2 

Auxiliary ventilation air exchange

Air exchanges specified in Room Data are divided into three categories: infiltration, auxiliary

ventilation and natural ventilation. Any infiltration air exchanges are included unconditionally,

but auxiliary and natural ventilation air exchanges may be switched on or off at calculation

time.

Tick this box if you wish to include Room Data auxiliary ventilation air exchanges in the Heat

Loss calculation.

Air exchanges are specified in Room Data in terms of a Maximum Value and a Variation Profile.

In Heat Loss the Variation Profile requires interpretation because the calculation does not

involve the time variable. The assumption is that the exchange rate takes the Maximum Value

Page 7: Apache Loads

7/23/2019 Apache Loads

http://slidepdf.com/reader/full/apache-loads 7/11

 

VE2014 Apache Loads (ASHRAE) 7

unless the profile is ‘Off continuously’ or a formula profile (which is not supported by Heating

Loads), when it takes the value zero.

3.1.3  Natural ventilation air exchange

Tick this box if you wish to include Room Data natural ventilation air exchanges in the Heating

Loads calculation.

Variation Profiles for natural ventilation are interpreted as for mechanical ventilation.

3.1.4  Include local and (when link ticked opposite) SunCast sky shielding

Tick this box if you wish the analysis to make allowance for the sky shielding effects of local

shades and shading objects analysed by SunCast. Under heating design conditions the sky

temperature will be below the ambient air temperature, and shielding surfaces from the sky

therefore has the effect of reducing heat loss.

3.1.5 

Include DHW?

If you tick this box the heating loads calculated for Apache Systems will include the Domestic

Hot Water demand for each room.

Select ‘Use peak values’ to set DHW demand to the peak value in the room, or ‘Use time

settings below’ to set it according to the demand at the indicated time of day and year. 

3.1.6  Time settings for profiles

The profile settings determine whether heating is available in each room. If the heating profile

is off at the specified hour, week day and month there is assumed to be no heating. In the case

of annual profiles the profile is evaluated for the indicated weekday in the central week of the

month.

3.1.7  Calculate

Click on this button to start the ASHRAE Loads Calculation.

3.1.8  Save & exit

Click on this button to leave the ASHRAE Loads dialog and save the data.

3.1.9  Close

Click on this button to leave the ASHRAE Loads interface.

Page 8: Apache Loads

7/23/2019 Apache Loads

http://slidepdf.com/reader/full/apache-loads 8/11

 

VE2014 Apache Loads (ASHRAE) 8

4  Cooling Loads

Cooling Loads calculates room cooling loads and free-floating temperatures using the ASHRAE

Heat Balance Method.

The calculation is carried out for one design day in each of a user-selected range of months,using weather data provided in APlocate. The calculation takes into account the timing and

nature of each gain, applying the appropriate radiant fraction to all sources of heat and cooling.

Inter-room dynamic conduction and ventilation heat transfer is accounted for. Glazing solar

transmission properties are treated using an analysis based on the Fresnel equations. At the

user’s option the effects of ventilation air exchanges and external solar shading, as calculated

by SunCast, may be incorporated.

Vista presents the Cooling Loads results in tabular or graphical form in a variety of formats.

Gains are broken down by heat transfer mechanism and by type (sensible or latent). Results

may be displayed by room, by zone or totalled over the building and peak loads are identified.

Various measures of room temperature are displayed, together with room relative humidity.

Data may be exported to other applications.

For a description of the calculation methods used in Cooling Loads see ApacheLoads Methods.

4.1 

Interface for Cooling Loads Calculation

4.1.1  Cooling Loads Calculation

Tick this box to include a Cooling Loads calculation when you click on Calculate.

4.1.2  Auxiliary ventilation air exchange

Air exchanges specified in Room Data are divided into three categories: infiltration, mechanical

ventilation and natural ventilation. Any infiltration air exchanges are included unconditionally,

but mechanical and natural ventilation air exchanges may be switched on or off at calculation

time.

Tick this box if you wish to include Room Data mechanical ventilation air exchanges in the

Cooling Loads calculation.

Page 9: Apache Loads

7/23/2019 Apache Loads

http://slidepdf.com/reader/full/apache-loads 9/11

 

VE2014 Apache Loads (ASHRAE) 9

4.1.3  Natural ventilation air exchange

Tick this box if you wish to include Room Data natural ventilation air exchanges in the Cooling

Loads calculation.

4.1.4  SunCast Link?

Tick this box to include the effects of external solar shading, as calculated by SunCast or

SunCast Lite, in the Cooling Loads calculation. The SunCast shading data can also be applied to

the calculation of Heating Loads, where it is used to model the effects of sky shielding.

It is important to ensure that the shading data is kept up to date with any changes to the

building geometry. The shading calculations should be repeated after any such changes.

4.1.5  Design Day (for profiles)

The Cooling Loads calculation is carried out for one design day per month. Indicate which day of

the week is to be used to set the profiles used in Cooling Loads for casual gains, ventilation

rates and (if appropriate) temperature boundary conditions.

4.1.6  Calculation Period

Select the months for which Cooling Loads calculations are required.

4.1.7  Save & exit

Click on this button to leave the ASHRAE Loads dialog and save the data.

4.1.8  Calculate

Click on this button to start the Heating and Cooling Loads calculations.

4.1.9  Cancel

Click on this button to leave the ASHRAE Loads interface.

Page 10: Apache Loads

7/23/2019 Apache Loads

http://slidepdf.com/reader/full/apache-loads 10/11

 

VE2014 Apache Loads (ASHRAE) 10

5  Simulation (Heat Balance Method) settings

5.1.1  Simulation Options

Options for the simulation, see ApacheSim User Guide for details

5.1.2  Output Options

Options for output to the results viewer Vista, see ApacheSim User Guide for details.

5.1.3  Simulation time step

Specify the time step to be used in the simulation. A time step of 10 minutes is suitable for

most building simulations. For ASHRAE Loads calculations the reporting interval is fixed at 60

minutes.

5.1.4  Preconditioning

A period of preconditioning is necessary to ensure that the building enters the simulation

period in a realistic thermal state. Preconditioning is necessary because of heat storage in the

building fabric. For lightweight buildings a preconditioning period of 10 days is sufficient. For

heavyweight buildings as much as 30 days or more may be needed. The appropriate period of

preconditioning may be established by increasing the number of preconditioning days until the

effect of further increments produces a negligible change in the first day’s simulation results.

Page 11: Apache Loads

7/23/2019 Apache Loads

http://slidepdf.com/reader/full/apache-loads 11/11

 

VE2014 Apache Loads (ASHRAE) 11

6  Autosizing settings

6.1 

Interface for Autosizing settings

6.1.1  Re-zero autosized parameters

Auto-sized parameters are the parameters located in the Room Data / Apache Systems dialog

that are sized during ApacheLoads or ApacheCalc calculations. Re-zero sets the values back to

zero before a new calculation.

6.1.2  Undo last autosize

Undo last autosize resets the autosized parameters to the previous calculated value.