lennoxemeia.com

FLEXAIR

FAC - FAG - FAH - FAM

APPLICATIONGUIDE

Air cooled rooftop packaged unit

85 230 kW

FLEXAIR-AGU-1505-E

• 1 •

1. 4

2. 14

3. 22

4. 26

5. 276

6. 42

7. 45

8. 47

9. 52

10. 54

11. 56

12. 75

www.eurovent-certifi cation.comwww.certifl ash.com

FLEXAIR

Application Guide /FLEXAIR-AGU-1505-E

APPLICATION GUIDERef : FLEXAIR-AGU-1505-E

TABLE OF CONTENTS

All the technical and technological information contained in this manual, including any drawing and technical descriptions provided by us, remain the property of Lennox and must not be utilised (except in operation of this product), reproduced, issued to or made available to third parties without the prior written agreement of Lennox.

GENERAL DESCRIPTION

OPTIONS DESCRIPTION

GENERAL DATA

OPTIONS DATA

STANDARD UNIT PERFORMANCES

FAN PERFORMANCES

HEAT RECOVERY SOLUTIONS PERFORMANCES

HEATING AUXILIARIES PERFORMANCES

ACOUSTIC DATA

ELECTRICAL DATA

DIMENSIONAL DATA

OPTIONS WEIGHTS AND ACCESSORIES PRESSURE DROPS

Product designed and manufactured under quality management systems certifi ed ISO 9001 and ISO 14001.

Our company’s products comply with European standards.

• 2 • Application Guide / FLEXAIR-AGU-1505-E

• 3 •

F FLEXAIR

F A C 3 0 0 D N M 1 M

A

W

N

S

D

T

F

C

H

G

M

X

H

S

N

M

H

N

M

T

Application Guide /FLEXAIR-AGU-1505-E

MODEL NUMBER DESCRIPTION

EXAMPLE :

Cooling capacity in kW

Revision number

Air cooled

Water cooled

No condenser

1 Circuit

2 Circuits

3 Circuits

4 Circuits

Cooling

Heat pump

gas fi red

dual fuel

heat recovery

High heat

Standard heat

No heat

R410A

HFO

No refrigerant

400V/3/50

230V/1/50

• 4 •

EPBD

ENERGY PERFORMANCE OF BUILDING DIRECTIVE

eComfort™

efficiency environment

Application Guide / FLEXAIR-AGU-1505-E

1- GENERAL DESCRIPTION

Faced with challenges relating to competitiveness and climate change, Europe has launched several initiatives for an intelligent energy strategy.

New regulations refl ect the European Union’s commitments on climate change and its determination to reach 20% effi ciency improvement in buildings by 2020.

One of the major requirements of the new EPBD is to set Energy Certifi cates for buildings which grade the energy effi ciency based on the building annual energy consumption. Soon companies will have to display their energy certifi cates to the public.

THE EXPERIENCE & COMMITMENT OF THE EUROPEAN LEADER TO DRIVE CONTINUOUS ENERGY SAVINGS

Lennox contribution to combat rising energy costs and global warming is to design innovative, effi cient and dependable products, while providing best comfort and air quality.

As a major player in the European HVAC market, Lennox is a reference in sustainable development and has been assembling its products in ISO-14001 certifi ed factories since 2007.

eComfort i l lustrates Lennox commitment towards energy efficiency and environmentally friendly solutions.

Like any other Lennox Rooftop unit, FLEXAIR is Eurovent certifi ed.

SUSTAINABLE ENERGY DEVELOPMENT CHALLENGES

FLEXAIR provides the best life cycle cost thanks to high energy effi ciency and reduced set up time and maintenance costs.

Low Energy consumption

• For a packaged air conditioner, 90% of the CO2 emissions are indirect emissions caused by the energy consumption.

• 35% energy savings with FLEXAIR when com-pared to a standard rooftop installed on a retail building.

• Innovative solutions for long lasting energy savings:. eDrive Direct transmission variable speed ventilation system. Advanced refrigeration system with multiscroll R410A com-

pressor assemblies, electronic expansion valves, extended heat exchange surface area, alternate and dynamic defrost cycles.

. Fresh air and free cooling management.. Optimized operation with eClimatic

Reduced maintenance Costs

• Fully factory tested plug and play packaged system.• eDRIVE direct transmission plug-fan with zero maintenance

and airfl ow measurement with eFlow.• eClimatic, eClimatic Wizard, unit remote management and

supervision through GPRS with ADALINK Service.

Better recycling management• Unit assembled in an ISO14001 certifi ed facility.• Refrigerant R410A to reduce refrigerant charge.• Reduced material usage with compact pac-

kaged design.

LENNOX : THE BEST LIFE CYCLE COST IN THE MARKET

• 5 •Application Guide /FLEXAIR-AGU-1505-E

1- GENERAL DESCRIPTION

1.1. GENERAL FEATURES

FLEXAIR range constitutes a packaged solution, easy to deliver and quick to install on the roof.

Operating range shall be between 46°C and minus 12°C with 4 versions : cooling, heating, cooling with gas burner or dual heat (heating with gas burner). All units are factory assembled, internally wired, fully charged with refrigerant, and 100% run-tested before leaving the factory.

EC FANS TECHNOLOGY

FLEXAIR units are fi tted with EC fans as standard, the variable speed option will save energy and reduce maintenance costs.

HIGH INDOOR AIR QUALITY

FiltrationFLEXAIR offers different fi ltration levels, ensuring the minimum pressure drop.The unit is fi tted with EU3 fi lters as standard, but it can be confi gured with :

- G4 fi lters- G4+F7 fi lter option / effi ciency > 85% / 0,4 μm particles

Free coolingSome times the thermodynamic cooling can be replaced by free cooling by introducing cold outside air into the building.FLEXAIR saves energy with automatic calibration of fresh air :

- Intelligent Fresh Air Management (patent 03 50616)- Motorised fresh air damper with enthalpy control (option)- CO2 sensor to adjust the percentage of fresh air to the Indoor

Air Quality (option)

eClimatic ADVANCED CONTROLLEReClimatic is the new generation controller that improves effi ciency and helps set up and service operations to guarantees long lasting performance

HEAT RECOVERY SOLUTIONSFLEXAIR range includes a heat recovery wheel to recovery energy from the extraction airThis heat recovery wheel is fi tted in a separated module to be installed on site

1.2. CASING

FLEXAIR indoor section is built with precoated galvanized steel panels painted in RAL 9003 color, specially designed for corrosion resistance and to ensure long operation life time.Double skin can be demanded as an option.

Condensing section mounted in a rigid base frame to ensure good support for compressors and giving rigidity to the complete structure.

1.3. ADVANCED REFRIGERANT CIRCUIT

FLEXAIR presents the most advanced design in the refrigerant pipes, optimizing pipe length and at the same time giving the best access for service and maintenance operations.The exchangers have been specially designed by Lennox for R410A operation, this copper tube and aluminum fi ns exchangers have been tested to give the best heat transfer and the best energy ratios. The refrigeration circuit is responsible for up to 40% of the annual energy consumption of a typical packaged air conditioning unit.

FLEXAIR features high effi ciency, environmentally friendly refrigeration circuits with multiscroll R410A compressors, electronic expansion valves and optimized heat exchange surface area.

• 6 • Application Guide / FLEXAIR-AGU-1505-E

SAVING ENERGY WITH ADVANCED REFRIGERATION CIRCUIT DESIGN

R410A refrigerantEffi cient systems such as FLEXAIR are designed around R410A refrigerant to achieve the best performances.

• Energy effi cient refrigerant thanks with pressure drop in the pipes: Higher evaporating pressure and lower condensing pressure improve compressor EER & COP.

• R410A compressors have a better isentropic effi ciency.• Environmentally friendly refrigerant: It contains No Chlorine (ODP =0). Signifi cant refrigerant charge

reduction (-40%) that limits the global warming potential of the system. R410A optimized heat exchangers use less material (copper, aluminum …)

1- GENERAL DESCRIPTION

1.4. MULTISCROLL COMPRESSOR TECHNOLOGY

FLEXAIR units are provided with tandem compressors, to profi t from the multiscroll compressor technology and giving the highest seasonal performance and the best SEER coeffi cients.

High effi ciency multiscroll technologyAir conditioning equipments are sized to cover the need for the most critical weather conditions which most likely will occur only a few days or even a few hours during the year.

Most of the time, in Europe, the external temperature drops below the reference value and consequently systems usually run 96% of the time at part load. It is therefore important to design system around part load performance to achieve the lowest possible annual energy consumption.

FLEXAIR provides high effi ciency and best possible part load effi ciencies year round with high effi ciency multiscroll R410A compressor technology.

Evolution of the net EER with varying capacity load

Net EER

Capacity load in % of nominal

1,5

2,0

4,0

2,5

3,0

4,5

3,5

10 20 30 40 50 60 70 80 90 100

Inverter Scroll

Single Scroll

A

BC

D

MultiScroll

MultiScroll + eDriveTM

A Multiscroll + eDRIVE C Multiscroll

B Inverter scroll D Single scroll

Source: PERSAPAC Study by Cetiat, Eurovent, Armine & EDFLennox Europe Laboratory comparative testing on rooftops

• 7 •Application Guide /FLEXAIR-AGU-1505-E

1.5. ELECTRONIC EXPANSION VALVES

The new electronic expansion valves are directly driven by the eClimatic and optimize the performances in both cooling and heating mode and provide reliable and accurate operation in all conditions all year round.This model of electronic expansion valves ensures also smooth and precise control at low capacities for improved part load performances.

Multiscroll” compressor technology with electronic expansion valves allows energy consumption reduction when compared to “inverter” solutions:

• Multiscroll compressors are always running at their best nominal operating conditions whereas compressors with inverter control usually run at 90 Hz for nominal point down to 30 Hz for low capacities.

• Energy consumption due to inverter electronics for speed variation can reduce effi ciency by up to 5%.

• Multiscroll compressor assemblies optimize heat exchanger usage during part load operation. For example, with 50% capacity load, a FLEXAIR would only start one compressor on each circuit. The running compressors would then benefi t from the whole heat exchange surface area and the whole airfl ow rate: The EER is then increased to 4.5 in some cases.

• Multiscroll compressor assemblies improve operating limits giving the possibility to unload compressors providing cooling to the building even when the outdoor temperatures are very high. With unloading, FLEXAIR can operate and supply cooling operating one compressor with outdoor temperatures reaching 50°C.

1- GENERAL DESCRIPTION

• 8 •

13

42

- 25%

1 40 %

2 18 %

3 12 %

4 30 %

Application Guide / FLEXAIR-AGU-1505-E

Fan absorbed power with variable airfl ow rate

Fan

abso

rbed

pow

er(%

of n

omin

al)

Airfl ow rate(% of nominal)

1.6- EC FANS IN SUPPLY AND EXTRACTION

Annual compressor consumption

Annual consumption of other electical systems

Remaining annual fan motor consumption

Energy savings thanks to eDRIVE

EC fan technology offers the maximum effi ciency together with the minimum power consumption. That’s why FLEXAIR provides EC fans both in indoor and exhaust section.

FLEXAIR will adapt the fan pressure to the different conditions of the unit, and will provide high pressure available in the duct even when all the options have been selected.

The EC plug-fan technology allows:- Adapting airfl ow at commissioning- Varying airfl ow during unit operation providing progressive

infl ation of smooth /textile ductworks- Easy maintenance operations, as there is not pulleys and

belts regulation

eClimatic profi ts about this EC technology by:- Monitoring the airfl ow in the service terminal- Compensating the airfl ow if the fi lters are dirty- Regulating the airfl ow to arrive to the desired set point tem-

perature.

Optimize the air-fl ow to the load demand (reduce consumption when possible)

Condensing section mounted in a rigid base frame to ensure good support for compressors and giving rigidity to the complete structure.

eDRIVE VENTILATIONeDRIVE is a standard feature of Lennox FLEXAIR units for ventilation with direct transmission, variable speed drives that saves energy and reduces maintenance costs.

SAVING ENERGY WITH eDRIVE VARIABLE SPEED, DIRECT DRIVE FAN.With a rooftop, the blower fan motor is one of the major contributors to annual energy consumption. Fans usually run 97% of the year at full speed to circulate the air inside the building. 42% of the annual energy consumption of an air conditioner is due to the fan motor, which can be more than compressors.

VARIABLE SPEED DRIVE Airfl ow reduction during part load operation and dead zone can help save on energy consumption.

There is no need to reduce airfl ow rate too much to achieve important energy savings: For example reducing airfl ow rate by only 25% will save 60% on the fan motor energy usage.

• FLEXAIR integrates the new eDRIVE which automatically adjust airfl ow rate to the needs, saving up to 30% annual rooftop energy consumption.

• Airfl ow Rate can be easily adjusted to the exact needs, thanks to eFlow the airfl ow measurement and display system.

• eDRIVE will correct power factor to reduce current.• eDRIVE integrates soft starter feature as standard, that will

reduce inrush current during fan starts and makes the unit fully compatible with fl exible ducts air diffusion systems.

1- GENERAL DESCRIPTION

• 9 •

1

2

3

4

567

Application Guide /FLEXAIR-AGU-1505-E

Our FLEXAIR range includes our New e-climatic control generation.The main features of this control are :

- Plastic cover to protect the circuit board from water entry and humidity and with all the different connection terminals correctly identifi ed.

- Two independent buses, one for display and sensors connec-tion and another one for internal components.

- Possibility of storing all parameterized conditions before an alarm is produced.

- Stronger hardware thanks to the plastic cover which protects the circuit board from water entry and humidity (and at the same time clearly identify all the different connection termi-nals)

- More reliable hardware thanks to the different communi-cation buses for internal/main devices (compressors, fans, etc.) and for the remote/accessory ones (display, probes), which preserve the regular unit operation even in case of commissioning miswirings

- Enhanced ClimaticTM regulation thanks to the better em-bedded processor and to the new Universal I/O chip, which allows to match better contacts, probes and relays to the controller board.

- Internal log memory to record unit operating trends (e.g. temperatures before alarm occurrence).

OPTIMIZED OPERATION AND SETUP SAVES ENERGY

eClimatic is designed to provide the best effi ciency throughout unit’s lifecycle while ensuring reliable and consistent operation with user-friendly interfaces .This controller monitories more machine parameters than ever to improve energy effi ciency and reliability

1 Indoor air temperature (humidity and CO2 levels as an option )

2 Outdoor air temperature (outdoor humidity as an option )

3 Return and supply air temperature

4 Filter pressure drop

5 Airfl ow rate with eFlow

6 Refrigerant pressures, temperatures & compressor monitoring

7 Power energy metering (option )

Three different platforms are available :

● End customer display DC: with basic confi gurations, set points, main temperature readings and alarms.

● Multiple display DM: graphic customer display with basic confi guration of the end customer display plus schedule programming and set of fresh air %.

● Service display DS: Specially focused to maint

Refrigeration circuit effi ciency managementClimatic control regulationThe Climatic controls the blowing air temperature to achieve the customer comfort in the most effi cient way, matching perfetctly the cooling/heating load with the optimum unit capacity staging (multiscroll compressors, heat recovery modules, freecooling, gas burners, water coils, etc.).The unit reliability is ensured by a complete set of protections as compressor envelop control, air-fl ow and pressure drops check, advanced refrigerant leakage detection, compressor anti short cycling rules.All these fetaures are designed to optimize the unit performance, but at the same time to increase its life-time and make easier its maintenance.

Dynamic defrost:It is a standard feature of all Lennox heat pumps. It limits the number and the duration of the defrost cycles in winter to maximize COP. With a smart and propietary frost-detection system, the lennox rooftops autumatically optimize the number and the durantion of the defrost cycles to get the best units perfonces in every enviromental conditions.

1.7- eCLIMATIC NEW CONTROL

1- GENERAL DESCRIPTION

• 10 •

10°C

Application Guide / FLEXAIR-AGU-1505-E

Free cooling:It is one of the most important features of this rooftop as it maximise seasonal effi ciency by reducing the use of thermodynamic cooling in mid season.

Intelligent fresh air management:With accurate percentage of fresh air the dampers are regularly calibrated to introduce just the required amount of fresh air in the building to reduce annual energy consumption. The fresh air ratio can also be controlled using the indoor CO2 level as an input.

Intelligent heating priority optimization:This unique feature on the market, allows the user to program the priority between the different heating elements (thermodynamic, electric pre-heaters or auxiliary heating). This is particularly interesting on dual fuel units or units with electrical pre-heaters. This feature maximizes energy effi ciency by optimizing heat pump operation depending on the outdoor temperature.

Full SchedulingImpressive energy savings can be done with a proper time-scheduling that optimizes the unit operation to the different load scenarios of each installation.For that reason the Climatic offers a weekly-based calendar with up to 7 time-bands per day and 4 pre-set modes (Unoccupied, Day, Day 1, Day 2).For each of this pre-set modes, plenty of unit settings can be optimized to the different moments of the day, for example during the unoccupancy periods the comforrt setpoints could be relaxed, during the energy-cost peaks hours the hot water coils or gas burners could be preferred to compressor or electrical heaters, fresh-air introduction can be reduced to warm-up the building before customer arrival, etc.

1 2

Unoccupied mode Day mode

3 4

Day1 additionnal mode Day2 additionnal mode

Start timeZ1 = 08h00

Gradient : 10 min / °C

Actual switch-onZ1 = 07h30

Actual temp.7°C

Morning anticipation and dynamic set point The unit can be programmed to switch-on in the morning to reach the occupied zone temperature set point just in time.The rooftop will start heating the building at a different time in the morning depending on the outdoor temperature: The lower the outdoor temperature, the earlier the rooftop would start to ensure that the set point is reached by the time the fi rst occupied zone (Z1) is starting. This is to avoid early start when outdoor temperature is mild.Example for a unit programmed to anticipate morning switch-on if outdoor temperature is below 10°C at a rate of 10 minutes/°C.

Dynamic set point can be used in summer to offset the ambient temperature set point according to the outdoor temperature. This is to avoid large temperature difference between indoor and outdoor. The indoor temperature set point would then increase with the outdoor temperature improving comfort and saving large amount of energy.

Communication and unit interlinkMaster/slave or cascade control is a standard feature of the FLEXAIR units. It can be used to connect up to 24 rooftops. The units can then be programmed to optimize effi ciency and improve reliability following 6 different strategies

Multi rooftops regulationIn case of multi-rooftop installations, The Climatic control of each unit can improve the unit synergies and optimize the total air-conditioning performance, without any additional cost or external dedicated "Building Manager System", but just linking the units together (up to 8) in the same network and appling any of the following smart strategies::

1: Master Slave "total": The master gives the ventilation order, its set point and its room temperature/humidity/CO2 to all other rooftops.

2: Master Slave "temperature": The master gives the ventilation order and its room temperature/humidity/CO2 to all other rooftops, but they have their own set point.

1- GENERAL DESCRIPTION

10°C

• 11 •Application Guide /FLEXAIR-AGU-1505-E

1.8. CONSTRUCTION, INSTALLATION AND SERVICE

UNIT CONSTRUCTIONFLEXAIR by Lennox is assembled with the highest standards of quality.

FLEXAIR units comply with the PED 97-23 and EN 60204 standard. It is manufactured in ISO 9001 and ISO 14001 factories.

This construction guarantees high corrosion resistance and lower the weight impact, also ensuring that the air leakages are reduced to the minimum. To improve the resistance to anticorrosion, the panels are prepainted in RAL 9003.

TRANSPORT AND HANDLINGTo facilitate handling of the unit and minimize the risk of damage, FLEXAIR units are provided with lifting lugs located in the base frame of the unit.

For transport and handling, the units are wrapped in a retractable plastic protection

PLUG AND PLAY UNITAll options are factory installed on the unit, which means that they are ready for use, optimizing the time spent on site for the installation. Bottom entry (through the base) for electrical power and hot water (if option fi tted) lines are available as standard.To make installation easier, FLEXAIR power supply does not require "neutral" connection. It is powered by 400 V, 3 phases, 50 Hz.

Circuit breakersTo improve safety and extend life time, circuit breakers protect against over-loading, over current and a disconnected supply phase. Maintenance is also improved as there is no requirement to change fuses. The electrical panel is manufactured in accordance with EN60204 electrical directive.

Numbered wiresAll wires and connectors are numbered as shown on the electrical drawing to facilitate maintenance and diagnostic

Main disconnect switchThe main switch is used as an emergency cut off.It is mandatory to guarantee a proper accessibility to this switch. Specifi c footbridges must be installed if the machine environment is requiring it.Main disconnect switch is lockable to increase safety around the rooftop unit.Switching off the unit with the disconnect switch will reset all.Disconnect switch will be sized accordingly to the options picked with the unit.

1- GENERAL DESCRIPTION

3: Master Slave "average":The master gives the ventilation order and the room temperature/humidity/CO2 used by all rooftop is the average of all rooftop, each rooftop has its own set point.

4: Master Slave "cooling/heating": All rooftop are stand-alone but the slaves have to have the same running mode as the master (Cooling or heating).

5: Master Slave “Back-up”: One rooftop is the back-up unit and will operate if any of the other rooftops is stopped due to a major problem.

6: Rolling Back-up mode: Same as above, except the "back-up" unit will change once a week on Tuesday.

Note that, the outside temperature/humidity/CO2 given to all rooftops can either be the average of all unit connected or the external humidity/temperature of the master, allowing the use of a single "weather station" for the whole site.

Faults and alarmseCLIMATIC manages more than 90 different faults and alarms codes and can store the last 32 with time and date. The stored faults and alarms can then be displayed on the DS service display and on the communication bus with the full text detail.

• 12 • Application Guide / FLEXAIR-AGU-1505-E

FILTERS As standard the unit comes with EU3 fi ltersWe can increase the capacity of fi ltration with an option of G4 and an option of G4+ F7, to arrive offering an average arrestance of synthetic dust above 90% (according to EN779:2012).

DOUBLE SKIN PANEL As an option, indoor unit of FLEXAIR, can be provided by a double skin panel, to avoid the carrying of insulation particles inside the building (25mm of thickness).

EC FANS VENTILATION SISTEM FLEXAIR is fi tted with EC fans as standard, ensuring that no belt particles can be carried away into building .This ventilation system is compliant with EN 13977 air quality norm.

ANALOGUE FILTER DETECTION Thanks to this sensor, the fi lter presence and the proper fan operation is ensured by a pressure drop above the minimum threshold, and at the same time the fi lter dirtyness is identifi ed by a pressure drop above the maximum threshold.

REMOVABLE ALUMINIUM DRAIN PAN All units are equipped with a sloped removable drain pan in aluminum which can be removed for maintenance, preventing the growth of bacteria an algae in the drain pan.

1.9. INDOOR AIR QUALITY

1- GENERAL DESCRIPTION

EASY ACCESS TO THE UNIT COMPONENTSIn FLEXAIR we keep the accessibility of all the components to the indoor unit, as well as all the internal refrigerant components

• 13 •

A

B

10 20 30 40 50 60 70 80 90 100

10

20

30

40

50

60

70

80

90

100

Application Guide /FLEXAIR-AGU-1505-E

Freecooling system is a standard feature for all Lennox rooftops, with a two sections damper made in aluminum, and connected with a proportional servomotor commanded by the control e-climatic.

New buildings that comply with EPBD will have good thermal insulation with high internal loads and will require cooling even when outdoor temperatures are low.Managing fresh air is mandatory in a building to control CO2 level and comfort.

Fresh air management and Free Cooling are standard features of FLEXAIR that can reduce annual energy consumption.

SAVING ENERGY WITH FRESH AIR & FREE COOLING

• Thermodynamic cooling can be replaced by Free Cooling when outdoor temperature is below the building set point saving up to 15% on annual energy consumption.

• Introducing just the required amount of Fresh Air in a building can reduce energy consumption.

Fres

h ai

r rat

e in

% o

f sup

ply

airfl

ow

% Damper position

Curve А : ΔP return ducts > Fresh air: Too much fresh air

Curve B : ΔP return ducts < Fresh air: Not enough fresh air

Because a fresh air damper curve is not linear, it is not accurate to assume that the percentage of opening of the damper is equal to the percentage of fresh air entering the building. However, this linear control of a damper is by far the most used in the industry

With Indoor air quality and running cost of a building being more important to our customer, FLEXAIR can manage the percentage of fresh air more accurately.

I

f the pressure drop in return air duct is high, the amount of fresh air actually introduced in the building can be higher than required. This extra fresh air will have to be cooled in summer and heated in winter, increasing energy consumption of the system.

FLEXAIR will periodically recalibrates fresh air dampers to ensure just the required amount of fresh air is introduced in the building. This recalibration is achieved using the return air, outdoor air and supply air sensors.

1.10- FRESH AIR AND FREE COOLING SYSTEM

1- GENERAL DESCRIPTION

• 14 • Application Guide / FLEXAIR-AGU-1505-E

HOT WATER COILS

A water coil made of copper pipe and aluminum fi ns can be installed to answer heating requirements. This water coil can, for example, be connected to a boiler or a heat pump. Two sizes of water coils are proposed to cope with the cooling and heating requirements. The water coil is equipped with a 3-way valve.

To check the different capacities of the water coils, please refer to the section "Heating auxiliary performances" of this application guide.

The hot water coil are protected from freezing by the Climatic, through low enviroment protections based on low supply and external temperatures, which activates safety procedures lcve pump starts, valve opening or return air damper opening.

ELECTRIC HEATERThe auxiliary electric heater is made of shielded resistance heaters, which are smooth 6 W/cm2 resistances. The heater is protected against high temperature with a thermal overload protection set at 90°C 150mm after the heating elements.For any rooftop unit size, two sizes of

electric heater are available as option, S (standard) and H (high).

F Box: 85 to 120 Kw Standard heat : 30 kW, 2 stages Medium heat : 54 kW, fully modulating (Triac) High heat : 72 kW, fully modulating (Triac)

G Box: 150 and 170 kW Standard heat : 45 kW, 2 stages Medium heat : 72 kW, fully modulating (Triac) High heat : 108 kW, fully modulating (Triac)

H Box: 200 and 230 kW Standard heat : 72 kW, 2 stages Medium heat : 108 kW, fully modulating (Triac) High heat : 162 kW, fully modulating (Triac)

GAS BURNER

FLEXAIR FAM and FAG units are fi tted with a gas burner. It is a safe and reliable atmospheric gas burner made of aluminized steel tube heat exchanger designed to offer maximum heat transfer and 92% effi ciency (PCI%). It runs with natural gas 20 mbar and an operating range of 13-26 mbar.

The standard gas module offers 2 stages of control which helps in improving space comfort by avoiding large supply air temperature deviations. Where more capacity control is required a modulating version is available with high heat burner models. With the modulating gas burner the airfl ow rate in the burner is controlled as the gas fl ow is being reduced maintaining the burner to its highest effi ciency level.

If required, an expansion device can be provided with the unit allowing it to operate with gas pressures of up to 300 mbar.

Gas fi red rooftop cannot be installed inside a technical room.

F Box: 85 to 120 Kw Standard heat (two stages): 60 kW High heat (modulating): 120 kW

G Box: 150 and 170 kW Standard heat (two stages): 120 kW High heat (modulating): 180 kW

H Box: 200 and 230 kW Standard heat (two stages) : 180 kW High heat (modulating): 240 kW

2.1- AUXILIARY HEATING OPTIONS

2- OPTIONS DESCRIPTION

• 15 •Application Guide /FLEXAIR-AGU-1505-E

2.2- HEAT RECOVERY OPTIONS

FLEXAIR RECOVERY ON EXHAUST AIR (HEAT RECOVERY WHEEL)To match Lennox commitment to a greener planet and to generate FLEXAIR savings FLEXAIR by Lennox can be equipped with one system to recover FLEXAIR from the extraction air.

Ideal for climates in which the difference between the outdoor temperature and the extraction air temperature is high. This new hybrid rotary wheel will generate very high sensible but also latent transfer.

Fresh air entry is protected with G4 fi lter.

2.3- FILTRATION OPTIONS

FLEXAIR offer several different levels of fi ltration that will allow coping with every application and any level of fi ltration demanded in the installation.

As standard the unit comes with EU3 fi lters

G4 fi lters, offered as standard can give an average arrestance of synthetic dust above 90% (according to EN779:2012).

As an option, Lennox can offer :

- G4 50 mm metallic frame with replaceable media, for those environments in which it is expected to change fi lters more frequently than usual.

- G4 50 mm + F7 100 mm with 90% opacimetric effi ciency and low pressure drop.

2- OPTIONS DESCRIPTION

• 16 • Application Guide / FLEXAIR-AGU-1505-E

2.4- ELECTRICAL OPTIONS

ENTHALPY CONTROL AND CO2 SENSOR

This option includes combined temperature and humidity sensors, to ensure that the economizer does not use 100% fresh air if the outside air has a higher enthalpy than the return air.

The CO2 sensor A VOC (Volatile Organic Component) detects the amount of CO2 in the ambient air between 0 and 2000PPM. (This obviously varies depending upon space occupancy levels). The VOC sensor sends a proportional signal (0-20mA) to the controller which will modulate the fresh air.

This option is highly reccomended in commercial installations like restaurants, shops, etc., where the CO2 level strongly varies during the day (e.g. depending on the people occupancy). In these installations in fact the energy savings coming form the correct air-renewal air-fl ow management (depending on CO2 level) can defi nitively pay back this sensor cost in a very short time.

ENERGY METER

The FLEXAIR meter option is a device that measures and displays the following parameters:

• Average, total and maximum current, voltage and frequency for each phase.• Active & reactive power.• Power factor (Cosφ).• Total active & reactive FLEXAIR consumption in Wh.

Values for FLEXAIR, current and absorbed power can be reset with password.

Some of these data will be collected by the controller and made available in the BMS tables for Modbus, BACnet and Trend protocols (not available for LonWorks).

3 PHASE CONTROL

This phase control device offers the guarantee of the correct phase connection, together with an overvoltage and under voltage protection.

FIRE DETECTOR

It is a thermostat that provides a signal to switch off the unit, close the fresh air damper and open the return damper when the temperature in the return air stream is above an adjustable set point (Factory setting: 70°C).

SMOKE DETECTOR

Located downstream of the fi lter, the optical head of the smoke detector can detect any type of smoke. When this occurs the unit will stop operating, the return air damper will be fully closed and the fresh air damper will fully open while sending an alarm signal to the unit.In accordance with the European norm, it is also compliant with the French regulation on public buildings.

2- OPTIONS DESCRIPTION

• 17 •Application Guide /FLEXAIR-AGU-1505-E

DC™ COMFORT DISPLAY

This is a remote controller for non-technical customer. It is designed to fi t aesthetically inside a room and be very easy to use. It has a 24V supply to be connected to the rooftop and can be installed at maximum 30 meters away from the unit.

The graphical display gives information such as running mode of the unit, status of the fan, set point, % of fresh air, outside air temperature.

Customer can set the temperature set point for a given time zone, switch the unit “On” or “Off” and adjust the clock. DC can display fault codes with a reset possibility, ambient, supply and outdoor temperature, fresh air damper position (%), time zone and operating mode pictogram, heating or cooling status.It is also able to display supply fan airfl ow rate (0-33-66-100%) and component status for compressors, defrost, condenser fans and auxiliary heaters.

DC™ comfort display is equipped with a temperature sensor that can be used as room temperature sensor.

DM™ MULTI-ROOFTOP DISPLAY

This display gives access to more functionality than the DCTM and allows managing up to 8 rooftops on a single Bus-wire. Customer will be able to change the operating time zone and mode. The rooftops can be connected to operate on a Master/Slave principle. Installation up to 1000m from the unit.

DS™ SERVICE DISPLAYThis new plug and play service display and controller allows service personal to set up to read and modify all unit parameters (Unit settings, operating time and number of compressor starts, low and high pressure reading, airfl ow rate of supply fan, and read the history of last 32 faults...).

This controller has been designed to be very user friendly, with 6 different keys and graphic display. It includes scrolling menus and full text (no codes) explanation. It is available in English or another alternate language.

2.5- CONTROL OPTIONS

2- OPTIONS DESCRIPTION

COMMUNICATION INTERFACES AND SUPERVISION:The CLIMATIC ModBus interface is required to connect the unit to a BMS using "ModBus protocol". No other hardware than this board is required to have ModBus communication. One board required per rooftop. The ModBus interface is available in two versions to be connected with RS485 or TCP/IP depending on site requirements.

This board is also mandatory for any connection between one or several FLEXAIR units and Lennox ADALINK II, Lennox OneWeb, Lennox Cloud service 3G or LennoxVision supervision solutions. One BMS interface required per rooftop.

ADALINK II™Adalink II™ is Lennox’s simplest solution for HVAC installation supervision to better control the system and improve reliability and energy effi ciency. One ADALINK II™ can control up to 32 Lennox units on the same site (Chillers, rooftop or any other unit using controller and above). It displays a site picture with the status of each unit and allows the user to change set points, access alarm history and plot charts. It is the ideal tool to save time and money on maintenance with an expert mode giving access to all the parameters and set point of the unit.

• Easy local management of important settings• Possibility to create macro commands to simplify setting and

better control the installation• Easy scheduling by unit or by zone with a smart user friendly

drag and drop system• Preventive maintenance to reduce downtime and improve

comfort and energy effi ciency at all time.• Remote connection via LAN or 3G • Site maintenance planning

ADALINK II™ can also act as a real gateway to the unit, as it can be used locally or via LAN network with ModBus TCP/IP protocol.

Any BMS can read and write information in the rooftops units using ADALINK II™ network. Both systems can run at the same time.

• 18 • Application Guide / FLEXAIR-AGU-1505-E

As managing fresh air is becoming mandatory in most buildings economiser is now fi tted as standard with the FLEXAIR.

Advanced control packWhere a higher level of controllability is required to make theFLEXAIR even more fl exible, LENNOX have compiled a pack that includes two advanced control features.

• "Enthalpy control on economiser". The eCLIMATIC and its humidity sensors (return air and fresh

air) ensures that the economiser does not use 100% fresh air if the outside air has a higher enthalpy than the return air. This feature is relevant in regions where the relative humidity is high or when the desired room air condition is very dry.

• "Humidity control" The eCLIMATIC and its humidity sensors, analyze dry and

wet bulb temperatures to control dehumidifi cation. Humidity control is only available if ambient temperature is in cooling or dead zone. The dehumidifi cation algorithm can dry the air by passing it through the coil in cooling mode.

A specifi c function in the program can be activated to control the minimum supply air temperature, by maintaining it equal to the heating set point, using auxiliary heaters (Electric, Hot water coil or gas burner).

A proportional 0-10V contact is also available to control an external humidifi er.

Indoor air quality sensorIndoor air quality is controlled from the eCLIMATIC main controller. A VOC (Volatile Organic Component) sensor detects the amount of CO2 in the ambient air between 0 and 2000PPM. (This obviously varies depending upon space occupancy levels). The VOC sensor sends a proportional signal (0-20mA) to the eCLIMATIC controller which will then modulate the fresh air.

Low Noise Option As rooftops are often installed in a noise sensitive area, LENNOX proposes a low noise option on FLEXAIR. To achieve low noise level, FLEXAIR receives a quieter fan, a compressor jacket and is fully equipped with acoustic isolation in the refrigerating box.

Anti corrosion protectionWhen the units are installed in potentially aggressive environments, which can often be the case for example in coastal environments, it is often a requirement that the coils are specially treated to protect them against the corrosive effects.LenGuard™ anti-corrosion treatment is available for condensers, evaporators and hot water coil.

2.6- REFRIGERATION OPTIONS

2.7- FRESH AIR OPTIONS

2- OPTIONS DESCRIPTION

• 19 •

50

5%5%

Application Guide /FLEXAIR-AGU-1505-E

Standard

BASIC AIRFLOW CONFIGURATIONS

Unless specifi ed otherwise when ordered, FLEXAIR rooftops are shipped with downfl ow supply and return confi guration. Units can be confi gured before shipment with the required airfl ow confi gurations to suit the building needs.

AIR SOCK CONTROLA standard feature in FLEXAIR, EC fan regulation allow the air socks to be progressively fi lled with air on start up. It takes one minute to go from 0% of air to Nominal airfl ow rate

Rooftop

Sealing

Roo

fcur

b

Thermal insulation

400

mm

min

imum

2.8- AIRFLOW CONFIGURATIONS AND ROOFCURBS

2- OPTIONS DESCRIPTION

ROOFCURBS

Non adjustable non assembled roofcurb.A sturdy mounting frame designed for single package units providing an automatic weatherproof sealed rooftop installation.This roofcurb is shipped knocked down and must be assembled on site.

Adjustable roofcurb.This adjustable and assembled roofcurb is made of galvanized steel with 2.5 mm. This adjustable roofcurb is designed to be installed in roofs with slopes up to 4 to 5% in all directions, enabling FLEXAIR to be compatible with most roof profi les.

Downfl ow roofcurbs are the easiest and the cheapest way to install packaged air conditioning systems to a single volume building.

The frame can be secured directly to the roof structure thanks to its built in adjustable fl anges and sealing liner returns

Multidirectional roofcurbThis option is a required when customer wants to have horizontal return and horizontal supply on the same side.It is also required with the power exhaust fan or gravity exhaust damper options combined with horizontal return fl ow confi guration.

• 20 •

1

1

2

2

Application Guide / FLEXAIR-AGU-1505-E

UNIT WITH NO EXHAUST AIR OPTION

1 → 2 : ESP (external static pressure) given in eLencal (LENNOX units selection tool) corresponds to the static pressure between inlet and outlet of the unit and includes all options and accessories delivered with the unit with the exception of the ductwork. This external static pressure will be used to push the air through the supply and the return ductwork installed on site.

ESP = Supply duct pressure drop + return duct pressure drop

Example : With an eLencal ESP = 350 Pa and a return ductwork pressure drop of 150 Pa ▬► Remaining available static pressure for the supply ductwork = 200 Pa

In any case, on a basic unit, the return ductwork pressure drop should be lower than 150 Pa.

The airfl ow is usually set during start up for a given fresh air rate. During normal operation the fresh air ratio will change and eventually the unit will go to full fresh air during free cooling operation. If the pressure drop in the return ductwork is high, the fan may trip on over current protection when it operates with full fresh air where the pressure drop is much lower.

If the return ductwork pressure drop is higher than 150 Pa :• Select an extraction roofcurb which will include an extraction

fan and the appropriate drive kit for the given airfl ow and pressure drop.

• FLEXAIR with eDRIVE includes constant airfl ow operation that can control and limit the airfl ow as the pressure drop reduces.

Building air tightness Low air tightness

Fresh air & Free cooling Medium fresh air rateFree cooling possible

Pressure drop in the return ductwork Medium < 150 Pa

Building pressure control NO control

Typical applications Existing hypermarkets and supermarkets (old buildings with high leakage rates)

GRAVITY EXHAUST DAMPER

1 → 2: ESP “Supply” in eLencalGravity exhaust dampers are used to relief pressure when outside air is being introduced in a building with good air tightness.

Building air tightness Medium

Fresh air & Free cooling High fresh air rateFree cooling

Pressure drop in the return ductwork Low < 50 Pa

Building pressure control Low control

Typical applications Warehouses

2- OPTIONS DESCRIPTION

2.9- EXTRACTION OPTIONS

• 21 •

12

2 1

Application Guide /FLEXAIR-AGU-1505-E

2- OPTIONS DESCRIPTION

POWER EXHAUST FAN

1 → 2: ESP “Supply” in eLencal.Power exhaust axial fans with gravity exhaust dampers provide exhaust air pressure relief when high levels of outside air are being introduced in the building with good air tightness.It is interlocked to run when return air dampers are being closed and supply air blower is in operation. The power exhaust fan runs when outdoor air dampers are at least 50% open (adjustable by set point). It is also overload protected. A gravity exhaust damper is supplied with this option to prevent air from entering the unit when fan is off.

Building air tightness Medium

Fresh air & Free cooling High fresh air rateFree cooling

Pressure drop in the return ductwork Medium 50 Pa to 150 Pa

Building pressure control Low control

Typical applications Light commercial, petrol stations...

EXTRACTION ROOFCURB

1 → 3: ESP Return in eLencal 3 → 2: ESP Supply in eLencalWhere system balancing is critical and return ductwork pressure drop is high, it is recommended to use extraction fan such as the one located in the extraction roofcurb.A plug fan installed with a 3rd damper (1 inside the Roofcurb + 2 inside the rooftop), is able to extract up to 300 Pa with the Nominal airfl ow rate of the unit. This roof curb can be used in either horizontal or downfl ow applications.

Building air tightness High

Fresh air & Free cooling High fresh air rateFree cooling

Pressure drop in the return ductwork High > 150 Pa

Building pressure control Pressure balance possible

Typical applications Theatres, cinemas, data centres, new air tight buildings with long return ductworks

• 22 •

FAC FAHFAG FAM

FLEXAIR 085 100 120

15000 18500 20500

86,0 101,3 119,320,1 27,1 31,4

FAC 2,71 4,08 5,28FAG 3,26 5,14 6,65

67,5 75,5 103,2209,3 252,3 293,9

FAC 3,56 3,30 3,29FAC 3,24 2,92 2,85FAG 3,15 2,80 2,73

85,0 100,0 117,520,6 27,1 31,3

FAH 2,71 4,08 5,28FAM 3,26 5,14 6,65

FAH 3,52 3,26 3,24FAH 3,20 2,88 2,81FAM 3,11 2,76 2,69

FAH 78,4 94,7 109,018,3 22,9 28,6

FAH 2,71 4,08 5,28FAM 3,26 5,14 6,65

FAH 3,60 3,58 3,26FAH 3,39 3,32 3,01FAM 3,34 3,24 2,94

S (4) 55,2H (4) 110,4S (4) 60H (4) 120

92S (4) 6,3H (4) 12,5

2FAC-FAG 9 / 9 9,1 / 9,1 9,1 / 9,1FAH-FAM 9,1 / 9,1 9,2 / 9,2 9,2 / 9,2

15000 18500 2050012000 14000 1500023000 23000 23000

150 / 800 150 / 800 150 / 800

Application Guide / FLEXAIR-AGU-1505-E

3- GENERAL DATACooling only Heat pumpCooling only with gas fi red heating Heat pump rooftop with gas fi red heating

(1) All data are at Eurovent conditions (400V/3Ph/50Hz at nominal airfl ow rate), nominal external static pressure.

Cooling :• Outdoor temperature = 35°C DB• Entering coil temperature 27°C DB / 19°C WB

Heating :• Outdoor temperature = 7°C DB / 6°C WB• Indoor temperature = 20°C DB

(2) Including compressor + outdoor axial fan + indoor centrifugal fan(3) Net COP = Net cooling capacity/Total absorbed power(4) S = Standard heat / H = High heat(5) At nominal airfl ow rate

Casing F BOXNominal airfl ow rate m3/h

Cooling mode (FAC - FAG)Gross cooling capacity (1)

kWCompressor gross power input

Indoor fan absorbed power

Full load amps (1)

ADirect start up amps ratio Id/IaGross EER (2)

Global net EER (3)

Cooling mode (FAH - FAM)Gross cooling capacity (1)

kWCompressor gross power input

Indoor fan absorbed power

Gross EER (2)

Global net EER (3)

Heating mode (FAH - FAM)Net heating capacity

kWCompressor gross power input

Indoor fan absorbed power

Gross COP (2)

Global net COP (3)

Heating - Gas fi red

Heating capacity kW

Power input kW

Thermal effi ciency %

Gas fl ow (for natural gas at 20 mbar and 15 °C) m3/h

Refrigeration circuitNumber of circuits

1 scroll + 1 scrollCompressor type and numberExpansion valve number

Refrigerant charge per circuit 1/2 kg

Ventilation dataNominal airfl ow rate

m3/hMinimum airfl ow rateMaximum airfl ow rateExternal static pressure / Maximum (5) Pa

• 23 •

FAC FAHFAG FAM

FLEXAIR 085 100 120

15000 18500 2050012000 14000 15000

23000150 / 800

2

235150 35150 440003,12 3,12 4,5

80-85% / G38

625 x 500 x 50

80,2 81,7 88,7

78,1 78,1 85,3

86,3 80,7 84,6

48

50

10

38

-15

-15

7

A2-s1-d0 / M0

33481750

2290 / 2657

966 1055 1054

1083 1187 1178

Application Guide /FLEXAIR-AGU-1505-E

(1) All data are at Eurovent conditions (400V/3Ph/50Hz at nominal airfl ow rate), nominal external static pressure.

Cooling :• Outdoor temperature = 35°C DB• Entering coil temperature 27°C DB / 19°C WB

Heating :• Outdoor temperature = 7°C DB / 6°C WB• Indoor temperature = 20°C DB

(2) Cooling and heating operating limits are given for steady operation with specifi c temperature conditions.

(3) Below this value, "Low ambient kit" option is required(4) Down return air and down supply air confi gurations(5) S = Standard heat / H = High heat

3.- GENERAL DATACooling only Heat pumpCooling only with gas fi red heating Heat pump rooftop with gas fi red heating

Indoor fan (FAG - FAM)Nominal airfl ow rate

m3/hMinimum airfl ow rateMaximum airfl ow rate External static pressure / maximum PaFan number

Outdoor fan (axial fan)NumberNominal airfl ow rate m3/hMotor power kW

Filter (standard)Effi ciency / Filter classNumber of fi ltersFilter size mm

Acoustic data (150 Pa)Outdoor sound powerStandard unit (1)

dB(A)Outdoor sound power Low noise unit (1)

Indoor blower outlet sound power

Operating limits - Cooling modeMaxi. outdoor temperatureIndoor 27 °C DB / 19°C WB (2)

°CMaxi. outdoor temperature with unloading

Mini. outdoor temperatureIndoor 20°C DB (3)

Maxi. outdoor temperatureDB/WB with 100% fresh air

Operating limits - Heating modeMini. outdoor temperatureIndoor 20 °C DB (2)

°CMini. outdoor temperature with unloading

Mini. entering indoor coil temperatureOutdoor 7°C DB

ConstructionCasing material AluminiumPainting Polyester / RAL 9003Insulation class

DimensionsLength

mmHeight

Width with/without fresh air hood (4)

WeightStandard unit (FAC) kgWeightGas unit (FAG-H) (5)

• 24 •

FLEXAIR™ 150 170 200 230

28000 30000 35000 39000

147,2 164,6 190,8 230,744,5 49,5 51,4 61,5

FAC 5,60 8,20 8,74 10,81FAG 6,76 10,00 10,24 12,95

109,8 137,4 155,5 194,5296,1 283,6 341,4 398,6

FAC 3,08 3,04 3,29 3,26FAC 2,77 2,65 2,89 2,84FAG 2,69 2,54 2,80 2,73

141,9 161,8 188,1 227,944,3 49,4 51,4 61,5

FAH 5,60 8,20 8,74 10,81FAM 6,76 10,00 10,24 12,95

FAH 2,98 3,00 3,24 3,22FAH 2,68 2,61 2,85 2,80FAM 2,60 2,50 2,76 2,70

FAH133,7 155,5 185,2 223,833,5 38,6 43,1 57,9

FAH 5,60 8,20 8,74 10,81FAM 6,76 10,00 10,24 12,95

FAH 3,63 3,60 3,73 3,33FAH 3,38 3,29 3,43 3,09FAM 3,31 3,21 3,37 3,03

S (4) 110,4 110,4 165,6 165,6H (4) 165,6 165,6 220,8 220,8S (4) 120 120 180 180H (4) 180 180 240 240

92 92 92 92S (4) 12,5 12,5 18,8 18,8H (4) 18,8 18,8 25 25

2FAC-FAG 14,7 / 14,2 14,7 / 14,3 18,5 / 18,5 19,8 / 19,8FAH-FAM 15 / 14,5 15,1 / 14,5 18,5 / 18,5 19,8 / 19,8

28000 30000 35000 3900018000 21000 24000 2700035000 35000 43000 43000

150 / 800

FAC FAHFAG FAM

Application Guide / FLEXAIR-AGU-1505-E

3- GENERAL DATA

Casing G BOX H BOXNominal airfl ow rate m3/h

Cooling mode (FAC - FAG)Gross cooling capacity (1)

kWCompressor gross power input

Indoor fan absorbed power

Full load amps (1)

ADirect start up amps ratio Id/IaGross EER (2)

Global net EER (3)

Cooling mode (FAH - FAM)Gross cooling capacity (1)

kWCompressor gross power input

Indoor fan absorbed power

Gross EER (2)

Global net EER (3)

Heating mode (FAH - FAM)Net heating capacity

kWCompressor gross power input

Indoor fan absorbed power

Gross COP (2)

Global net COP (3)

Heating - Gas fi red

Heating capacity kW

Power input kW

Thermal effi ciency %

Gas fl ow (for natural gas at 20 mbar and 15 °C) m3/h

Refrigeration circuit

Number of circuits 1 scroll + 2 scroll 2 scroll + 2 scroll

Compressor type and numberExpansion valve number

Refrigerant charge per circuit kg

Ventilation dataNominal airfl ow rate

m3/hMinimum airfl ow rateMaximum airfl ow rateExternal static pressure / Maximum (5) Pa

Cooling only Heat pumpCooling only with gas fi red heating Heat pump rooftop with gas fi red heating

(1) All data are at Eurovent conditions (400V/3Ph/50Hz at nominal airfl ow rate), nominal external static pressure.

Cooling :• Outdoor temperature = 35°C DB• Entering coil temperature 27°C DB / 19°C WB

Heating :• Outdoor temperature = 7°C DB / 6°C WB• Indoor temperature = 20°C DB

(2) Including compressor + outdoor axial fan + indoor centrifugal fan(3) Net COP = Net cooling capacity/Total absorbed power(4) S = Standard heat / H = High heat(5) At nominal airfl ow rate

• 25 •

FLEXAIR™ 150 170 200 230

28000 30000 35000 3900018000 21000 24000 2700035000 35000 43000 43000

Pa 150 / 8003

2 2 4 438950 49400 69350 880002,96 4,16 6,24 8,96

80-85% / G312 12 10 + 5 10 + 5

625 x 500 x 50 500 x 500 + 800 x 500

87,3 91,6 85,0 89,1

84,9 88,6 82,2 88,6

92,8 83,8 92,5 96,5

46 46 48 48

45

10

38

-15

-15

7

A2-s1-d0 / M0

4385 4385 5230 52301885 1885 2235 2235

2290 / 2753

1454 1550 2027 2143

1599 1704 2297 2411

FAC FAHFAG FAM

Application Guide /FLEXAIR-AGU-1505-E

3- GENERAL DATA

Indoor fanNominal airfl ow rateMinimum airfl ow rate m3/hMaximum airfl ow rate External static pressure / maximumFan number

Outdoor fan (axial fan)NumberNominal airfl ow rate m3/hMotor power kW

Filter (standard)Effi ciency / Filter classNumber of fi ltersFilter size mm

Acoustic data (150 Pa)Outdoor sound powerStandard unit (1)

dB(A)Outdoor sound powerLow noise unit (1)

Indoor blower outlet sound power

Operating limits - Cooling modeMaxi. outdoor temperatureIndoor 27 °C DB / 19°C WB (2)

°CMaxi. outdoor temperature with unloading

Mini. outdoor temperatureIndoor 20°C DB (3)

Maxi. outdoor temperatureDB/WB with 100% fresh air

Operating limits - Heating modeMini. outdoor temperatureIndoor 20 °C DB (2)

°CMini. outdoor temperature with unloading

Mini. entering indoor coil temperatureOutdoor 7°C DB

ConstructionCasing material AluminiumPainting Polyester / RAL 9003Insulation class

DimensionsLength

mmHeight

Width with/without fresh air hood (4)

WeightStandard unit (FAC) kgWeightGas unit (FAG-H) (5)

Cooling only Heat pumpCooling only with gas fi red heating Heat pump rooftop with gas fi red heating

(1) All data are at Eurovent conditions (400V/3Ph/50Hz at nominal airfl ow rate), nominal external static pressure.

Cooling :• Outdoor temperature = 35°C DB• Entering coil temperature 27°C DB / 19°C WB

Heating :• Outdoor temperature = 7°C DB / 6°C WB• Indoor temperature = 20°C DB

(2) Cooling and heating operating limits are given for steady operation with specifi c temperature conditions.

(3) Below this value, "Low ambient kit" option is required(4) Down return air and down supply air confi gurations(5) S = Standard heat / H = High heat

• 26 •

FLEXAIR 085 100 120 150 170 200 23015000 18500 20500 28000 30000 35000 39000

S (2) 30 30 30 45 45 72 72

M (2) 54 54 54 72 72 108 108

H (2) 72 72 72 108 108 162 162

42/75/99 42/75/99 99/149/196

S (2) 114 126 133 145 156 177 186

H (2) 177 201 212 254 275 295 313

H (2) % 40-100 20-100

3

2146 2330 2516

1796 2170 2418

1422 / 1055 1518 / 1055 1676 / 623

525 635 730

1500 1800 2050

3 / 3 8 / 8 10 / 10

90% / G4 / EU4

85% / F7 / EU7

8 12 10 + 5

625 x 500 x 50 625 x 500 x 50 500x500 + 800x500

M1

3 3

450 560

FAC FAHFAG FAM

Application Guide / FLEXAIR-AGU-1505-E

(1) Conditions : entering water temperature 90°C, leaving water temperature 70°C, entering air temperature 20°C, S = standart heat, H = high heat(2) not available with FAG and FAM versions

4- OPTIONS DATA

Nominal airfl ow rate m3/h

Heating - electricType of modulation m3/h Staged on S / Triac on M & H

Available heating capacity kW

Amps S / M / H

Heating - hot water coil

Available heating capacity (1) kW

Gas modulatingModulation range

Axial exhaust fanNumber of fans

Heat recovery moduleType of exchanger Wheel exchanger

Protection against frosting on exhaust air Air differential pressure switch 20 to 300 Pa

Lenght

mmHeight

Width with/without fresh air hood

Weight kg

Wheel diameter mmNumber of fi ltersFresh air / Return air

Filter G4 and G4+F7

Effi ciency (gravimetric) / class EN779 / Eurovent G4

Effi ciency (opacimetric) / class EN779 / Eurovent F7

Number of fi lters

Filter size mm

Fire class

Power exhaust fan (axial fan)Number of fans

Diameter

Cooling only Heat pumpCooling only with gas fi red heating Heat pump rooftop with gas fi red heating

• 27 •

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 80,6 53,0 16,9 77,4 51,4 18,7 73,8 49,7 20,6 69,8 48,0 22,8 65,2 46,2 25,224°C 81,3 65,2 17,0 78,1 63,7 18,7 74,5 62,0 20,7 70,4 60,1 22,9 65,9 58,0 25,327°C 82,2 77,0 17,0 79,0 75,6 18,8 75,4 74,0 20,7 71,4 71,3 23,0 67,4 67,4 25,530°C 85,1 85,1 17,1 82,4 82,4 18,9 79,2 79,2 21,0 75,5 75,5 23,2 71,4 71,4 25,8

19°C

24°C 88,1 52,6 17,4 84,6 50,9 19,1 80,6 49,2 21,1 76,1 47,4 23,2 71,2 45,6 25,727°C 88,8 64,9 17,4 85,3 63,3 19,1 81,3 61,6 21,1 76,8 59,7 23,3 71,8 57,7 25,830°C 89,7 76,7 17,5 86,2 75,3 19,2 82,2 73,6 21,2 77,7 71,8 23,4 72,7 69,5 25,833°C 90,8 88,1 17,5 87,3 86,9 19,3 83,9 83,9 21,3 80,1 80,1 23,5 75,7 75,7 26,1

22°C

27°C 96,1 52,2 17,8 92,1 50,3 19,6 87,7 48,5 21,5 82,8 46,8 23,7 77,5 45,1 26,330°C 96,7 64,4 17,9 92,8 62,7 19,6 88,4 61,0 21,6 83,5 59,2 23,8 78,2 57,3 26,333°C 97,6 76,1 17,9 93,7 74,6 19,7 89,3 73,0 21,6 84,4 71,2 23,9 79,1 69,2 26,436°C 98,7 87,3 18,0 94,8 86,1 19,7 90,4 84,7 21,7 85,5 82,9 23,9 80,2 80,2 26,5

16°C

21°C 84,3 58,6 17,2 80,9 57,0 18,9 77,1 55,3 20,8 72,8 53,5 23,0 68,0 51,5 25,424°C 85,2 73,2 17,2 81,8 71,6 19,0 78,0 69,9 20,9 73,6 67,8 23,1 68,9 65,5 25,527°C 86,4 86,4 17,3 83,5 83,5 19,1 80,1 80,1 21,1 76,3 76,3 23,3 72,1 72,1 25,830°C 91,4 91,4 17,6 88,3 88,3 19,4 84,8 84,8 21,4 80,9 80,9 23,6 76,4 76,4 26,1

19°C

24°C 92,0 58,1 17,6 88,2 56,4 19,3 83,9 54,7 21,3 79,2 52,9 23,4 74,0 51,0 25,927°C 92,9 72,9 17,7 89,1 71,2 19,4 84,8 69,5 21,3 80,1 67,5 23,5 74,9 65,3 26,030°C 94,0 87,4 17,7 90,2 85,8 19,5 85,9 84,0 21,4 81,1 81,1 23,6 76,6 76,6 26,133°C 96,8 96,9 17,9 93,6 93,6 19,7 89,8 89,8 21,7 85,6 85,6 23,9 80,9 81,0 26,5

22°C

27°C 100,0 57,5 18,1 95,8 55,7 19,8 91,2 53,9 21,7 86,1 52,2 23,9 80,5 50,4 26,530°C 100,9 72,4 18,1 96,7 70,7 19,8 92,1 68,9 21,8 86,9 67,0 24,0 81,3 64,9 26,533°C 102,0 86,8 18,2 97,8 85,2 19,9 93,1 83,5 21,9 88,0 81,5 24,1 82,4 79,1 26,636°C 103,3 100,8 18,3 99,0 99,0 20,0 95,0 95,0 22,0 90,6 90,6 24,3

16°C

21°C 90,7 71,4 17,5 86,6 69,7 19,2 82,1 67,9 21,1 77,1 65,9 23,3 71,6 63,5 25,724°C 91,9 91,8 17,6 88,2 88,2 19,3 84,2 84,1 21,3 79,6 79,6 23,5 74,6 74,6 26,027°C 97,3 97,3 17,9 93,5 93,5 19,6 89,3 89,3 21,6 84,6 84,6 23,8 79,4 79,4 26,430°C 103,1 103,1 18,2 99,2 99,2 20,0 94,8 94,8 22,0 90,0 90,0 24,3

19°C

24°C 98,6 70,7 18,0 94,2 69,0 19,7 89,2 67,3 21,6 83,8 65,4 23,8 78,0 63,2 26,327°C 100,0 92,4 18,1 95,6 90,5 19,8 90,6 88,4 21,7 85,0 85,0 23,9 79,7 79,8 26,430°C 103,4 103,4 18,2 99,4 99,4 20,0 94,9 94,9 22,0 90,0 90,0 24,233°C 109,2 109,3 18,6 105,1 105,1 20,4

22°C

27°C 106,9 69,8 18,5 102,1 68,2 20,2 96,8 66,5 22,1 91,0 64,7 24,330°C 108,3 92,0 18,5 103,5 90,1 20,3 98,2 88,1 22,233°C 109,7 109,7 18,6 105,4 105,5 20,436°C

20°C 15°C 10°C 7°C 5°C 0°C -5°C -10°C -15°C

PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA8°C 108,9 18,3 97,2 17,3 97,2 17,3 80,2 15,7 76,2 15,4 67,0 14,5 58,6 13,7 51,0 13,0 48,2 12,711°C 107,3 19,4 95,8 18,3 95,8 18,3 79,1 16,7 75,2 16,3 66,2 15,4 58,0 14,6 50,6 13,9 47,9 13,614°C 105,6 20,5 94,3 19,4 94,3 19,4 78,0 17,6 74,2 17,2 65,4 16,3 57,4 15,5 50,2 14,8 47,6 14,517°C 103,9 21,7 92,8 20,5 92,8 20,5 76,8 18,7 73,1 18,3 64,5 17,3 56,7 16,4 49,8 15,7 47,3 15,520°C 102,1 23,0 91,3 21,7 91,3 21,7 75,6 19,8 72,0 19,4 63,6 18,3 56,1 17,4 49,3 16,7 46,9 16,523°C 100,3 24,4 89,7 23,0 89,7 23,0 74,3 21,0 70,8 20,5 62,7 19,4 55,3 18,5 48,8 17,7 46,4 17,526°C 98,5 26,0 88,1 24,4 88,1 24,4 73,1 22,2 69,7 21,7 61,7 20,5 54,6 19,5 48,3 18,8 46,0 18,58°C 111,0 17,1 99,0 16,2 99,0 16,2 81,5 14,8 77,5 14,4 68,0 13,7 59,4 12,9 51,5 12,3 48,6 12,011°C 109,3 18,0 97,6 17,1 97,6 17,1 80,5 15,6 76,5 15,3 67,3 14,5 58,8 13,7 51,2 13,1 48,4 12,914°C 107,7 19,0 96,1 18,0 96,1 18,0 79,4 16,5 75,5 16,1 66,5 15,3 58,2 14,6 50,8 13,9 48,1 13,717°C 106,0 20,1 94,6 19,0 94,6 19,0 78,2 17,4 74,5 17,1 65,6 16,2 57,6 15,5 50,4 14,8 47,8 14,620°C 104,2 21,2 93,1 20,1 93,1 20,1 77,1 18,4 73,4 18,1 64,7 17,2 56,9 16,4 50,0 15,8 47,4 15,623°C 102,5 22,4 91,6 21,2 91,6 21,2 75,8 19,5 72,2 19,1 63,8 18,2 56,2 17,4 49,5 16,8 47,0 16,626°C 100,7 23,7 90,0 22,5 90,0 22,5 74,6 20,6 71,1 20,2 62,9 19,2 55,5 18,4 49,0 17,8 46,6 17,68°C 114,7 15,2 102,1 14,5 102,1 14,5 83,6 13,3 79,3 13,1 69,2 12,4 59,9 11,8 51,4 11,3 48,2 11,111°C 113,2 16,0 100,7 15,2 100,7 15,2 82,6 14,1 78,4 13,8 68,5 13,2 59,4 12,6 51,1 12,1 48,0 11,914°C 111,6 16,8 99,4 16,0 99,4 16,0 81,6 14,9 77,4 14,6 67,7 14,0 58,9 13,4 50,8 13,0 47,8 12,817°C 109,9 17,7 97,9 16,9 97,9 16,9 80,5 15,7 76,5 15,5 67,0 14,8 58,3 14,3 50,5 13,9 47,5 13,820°C 108,2 18,7 96,5 17,8 96,5 17,8 79,4 16,7 75,4 16,4 66,1 15,8 57,7 15,3 50,1 14,9 47,2 14,923°C 106,5 19,7 95,0 18,8 95,0 18,8 78,2 17,6 74,3 17,4 65,3 16,8 57,0 16,3 49,6 16,0 46,9 16,026°C 104,8 20,8 93,4 19,9 93,4 19,9 77,0 18,7 73,2 18,4 64,4 17,9 56,4 17,4 49,2 17,2 46,5 17,2

FAH

FAH

085

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 3,17FC/FD 4,0

1,8

FAC FAH FAH

Application Guide /FLEXAIR-AGU-1505-E

COOLING CAPACITY AND ABSORBED POWER

HEATING CAPACITY AND ABSORBED POWER

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

12 0

00 m

3 /hN

omin

al a

irfl o

w ra

te15

000

m3 /h

Max

imum

airfl

ow

rate

23 0

00 m

3 /h

Ente

ring

air t

empe

ratu

reDr

y bu

lb

Min

imum

airfl

ow

ra

te12

000

m3 /h

Nom

inal

airfl

ow

rate

15 0

00 m

3 /h

Max

imum

airfl

ow

ra

te23

000

m3 /h

Outdoor air temperature

Wet bulb Dry bulb

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

Absorbed power by control device(kW)

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Cooling only Heat pump

Outdoor air temp.

5.1- UNIT PERFORMANCES5- STANDARD UNITS PERFORMANCES

• 28 •

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 81,2 53,3 16,9 78,2 51,8 18,7 74,7 50,2 20,6 70,8 48,5 22,8 66,4 46,8 25,324°C 82,0 65,6 17,0 79,0 64,1 18,7 75,5 62,5 20,7 71,6 60,7 22,9 67,2 58,6 25,327°C 82,9 77,3 17,0 79,9 75,9 18,8 76,4 74,4 20,7 72,3 72,3 22,9 68,5 68,5 25,430°C 85,6 85,6 17,1 83,0 83,0 18,9 79,9 79,9 21,0 76,4 76,4 23,2 72,4 72,4 25,8

19°C

24°C 88,7 52,9 17,4 85,3 51,2 19,1 81,5 49,5 21,1 77,2 47,9 23,3 72,4 46,1 25,727°C 89,5 65,2 17,4 86,1 63,6 19,1 82,2 62,0 21,1 77,9 60,2 23,3 73,1 58,2 25,830°C 90,5 77,0 17,5 87,0 75,6 19,2 83,2 74,0 21,2 78,8 72,1 23,4 74,0 70,0 25,933°C 91,6 88,3 17,5 88,1 87,0 19,3 84,6 84,7 21,3 80,9 80,9 23,5 76,7 76,7 26,1

22°C

27°C 96,6 52,3 17,8 92,8 50,5 19,6 88,5 48,8 21,5 83,8 47,1 23,7 78,7 45,4 26,330°C 97,4 64,7 17,9 93,6 63,0 19,6 89,3 61,3 21,6 84,6 59,6 23,8 79,4 57,7 26,333°C 98,4 76,4 17,9 94,5 74,9 19,7 90,3 73,3 21,6 85,5 71,5 23,9 80,3 69,5 26,436°C 99,5 87,5 18,0 95,6 86,2 19,7 91,3 84,8 21,7 86,6 83,0 23,9 81,4 80,9 26,5

16°C

21°C 85,0 58,9 17,2 81,8 57,4 18,9 78,1 55,7 20,9 73,9 54,0 23,0 69,3 52,1 25,424°C 86,0 73,5 17,2 82,7 71,9 19,0 79,0 70,2 20,9 74,8 68,2 23,1 70,1 66,0 25,527°C 87,0 87,0 17,3 84,3 84,2 19,1 81,0 81,0 21,1 77,4 77,4 23,3 73,2 73,2 25,830°C 92,0 92,0 17,6 89,1 89,1 19,4 85,7 85,7 21,4 81,8 81,8 23,6 77,5 77,5 26,1

19°C

24°C 92,7 58,4 17,6 89,0 56,7 19,3 84,9 55,0 21,3 80,4 53,3 23,5 75,4 51,5 25,927°C 93,6 73,2 17,7 90,0 71,5 19,4 85,8 69,8 21,3 81,3 67,9 23,5 76,2 65,7 26,030°C 94,7 87,5 17,7 91,0 85,9 19,5 86,9 84,1 21,4 82,3 82,0 23,6 77,7 77,7 26,133°C 97,5 97,5 17,9 94,3 94,3 19,7 90,6 90,7 21,7 86,6 86,6 23,9 82,0 82,0 26,5

22°C

27°C 100,7 57,8 18,1 96,6 56,0 19,8 92,1 54,3 21,7 87,2 52,6 24,0 81,8 50,8 26,530°C 101,6 72,7 18,1 97,6 71,0 19,9 93,1 69,2 21,8 88,1 67,3 24,0 82,7 65,3 26,633°C 102,8 87,0 18,2 98,7 85,4 19,9 94,1 83,6 21,9 89,2 81,6 24,1 83,7 79,3 26,636°C 104,0 100,7 18,3 99,9 99,3 20,0 95,8 95,8 22,0 91,5 91,5 24,3

16°C

21°C 91,5 71,5 17,5 87,5 69,9 19,2 83,1 68,1 21,2 78,3 66,1 23,3 73,0 63,8 25,824°C 92,8 92,2 17,6 88,9 88,8 19,3 85,0 84,9 21,3 80,6 80,6 23,5 75,8 75,7 26,027°C 98,0 98,0 17,9 94,3 94,3 19,6 90,2 90,2 21,6 85,7 85,7 23,9 80,7 80,7 26,430°C 103,8 103,8 18,2 100,0 100,0 20,0 95,8 95,8 22,0 91,1 91,1 24,3 85,9 85,9 26,9

19°C

24°C 99,5 71,0 18,0 95,2 69,3 19,7 90,4 67,6 21,6 85,1 65,7 23,8 79,5 63,6 26,327°C 100,8 92,3 18,1 96,5 90,4 19,8 91,7 88,3 21,7 86,4 85,8 23,9 80,8 80,8 26,430°C 104,0 104,1 18,2 100,2 100,2 20,0 95,8 95,8 22,0 91,0 91,1 24,3 85,8 85,8 26,933°C 110,0 110,0 18,6 105,9 105,9 20,4

22°C

27°C 107,8 70,3 18,5 103,1 68,6 20,2 97,9 66,9 22,1 92,3 65,1 24,4 86,2 63,2 26,930°C 109,2 92,1 18,6 104,4 90,2 20,3 99,2 88,2 22,2 93,6 85,8 24,433°C 110,3 110,3 18,6 106,2 106,2 20,436°C

FAC

085FACFAC FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 3,17FC/FD 4,0

1,8

Application Guide / FLEXAIR-AGU-1505-E

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

12 0

00 m

3 /hN

omin

al a

irfl o

w ra

te15

000

m3 /h

Max

imum

airfl

ow

rate

23 0

00 m

3 /h

Temperatura de aire exterior

Wet bulb Dry bulb

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 29 •

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 90,4 60,1 20,3 86,8 58,2 22,2 82,7 56,3 24,3 78,2 54,3 26,6 73,1 52,2 29,124°C 91,2 74,1 20,4 87,6 72,3 22,3 83,5 70,4 24,4 79,0 68,3 26,7 74,0 65,9 29,227°C 92,2 87,6 20,5 88,6 86,0 22,3 84,6 84,1 24,4 80,3 80,3 26,8 75,9 75,9 29,530°C 95,5 95,5 20,7 92,5 92,4 22,6 88,9 88,9 24,8 84,8 84,8 27,2 80,3 80,3 29,9

19°C

24°C 98,6 59,6 20,9 94,5 57,5 22,8 90,0 55,6 24,9 85,0 53,6 27,2 79,5 51,5 29,827°C 99,4 73,7 21,0 95,4 71,9 22,9 90,8 69,9 25,0 85,8 67,9 27,3 80,4 65,6 29,930°C 100,4 87,2 21,1 96,4 85,6 23,0 91,9 83,8 25,0 86,9 81,7 27,4 81,4 79,2 30,033°C 101,7 100,0 21,2 97,9 97,9 23,0 94,1 94,1 25,2 89,7 89,7 27,7 84,9 84,9 30,4

22°C

27°C 107,1 58,9 21,5 102,6 56,7 23,4 97,6 54,7 25,5 92,1 52,7 27,9 86,2 50,8 30,530°C 107,9 73,0 21,6 103,4 71,1 23,5 98,5 69,2 25,6 93,0 67,2 28,0 87,1 65,0 30,633°C 109,0 86,4 21,7 104,5 84,8 23,6 99,5 83,0 25,7 94,1 81,0 28,1 88,2 78,7 30,736°C 110,3 99,0 21,8 105,8 97,7 23,7 100,8 96,2 25,8 95,4 94,3 28,2 89,8 89,8 30,9

16°C

21°C 95,3 68,0 20,7 91,3 66,1 22,6 86,9 64,2 24,6 82,0 62,2 26,9 76,6 59,9 29,524°C 96,4 85,5 20,8 92,4 83,6 22,7 88,0 81,6 24,7 83,1 79,3 27,0 77,7 76,6 29,627°C 98,5 98,4 20,9 95,1 95,0 22,9 91,1 91,1 25,0 86,7 86,7 27,4 81,8 81,8 30,030°C 104,1 104,1 21,3 100,5 100,5 23,3 96,4 96,4 25,4 91,8 91,8 27,9 86,7 86,7 30,6

19°C

24°C 103,6 67,3 21,3 99,2 65,4 23,2 94,3 63,4 25,2 88,9 61,5 27,6 83,1 59,3 30,227°C 104,8 85,1 21,4 100,3 83,2 23,3 95,5 81,2 25,3 90,1 79,0 27,7 84,3 76,4 30,330°C 106,1 102,3 21,5 101,7 100,5 23,4 96,6 96,6 25,5 91,9 91,9 27,9 86,7 86,8 30,633°C 110,1 110,1 21,8 106,2 106,3 23,7 101,9 101,9 25,9 97,0 97,0 28,3 91,6 91,6 31,1

22°C

27°C 112,2 66,3 21,9 107,4 64,4 23,8 102,0 62,5 25,9 96,2 60,6 28,2 89,9 58,6 30,930°C 113,4 84,3 22,0 108,6 82,4 23,9 103,2 80,5 26,0 97,4 78,4 28,3 91,1 76,0 31,033°C 114,8 101,6 22,1 109,9 99,9 24,0 104,6 97,9 26,1 98,8 95,7 28,5 91,9 91,9 31,136°C 116,5 116,5 22,2 112,3 112,3 24,2 107,6 107,6 26,4

16°C

21°C 98,7 74,8 20,9 94,4 73,1 22,8 89,6 71,2 24,8 84,3 69,0 27,1 78,5 66,6 29,724°C 100,1 95,8 21,1 95,8 93,9 22,9 90,7 90,7 24,9 85,9 85,9 27,3 80,7 80,7 29,927°C 104,6 104,5 21,3 100,6 100,6 23,3 96,2 96,2 25,4 91,2 91,2 27,8 85,8 85,8 30,530°C 110,6 110,6 21,8 106,5 106,5 23,7 101,9 101,9 25,9 96,8 96,7 28,3 91,1 91,1 31,1

19°C

24°C 107,2 74,0 21,5 102,4 72,2 23,4 97,1 70,4 25,5 91,4 68,4 27,8 85,2 66,1 30,427°C 108,6 95,4 21,7 103,9 93,6 23,5 98,6 91,5 25,6 92,9 89,0 27,9 86,7 86,2 30,630°C 110,9 110,9 21,8 106,7 106,7 23,7 102,0 102,0 25,9 96,7 96,8 28,3 91,0 91,0 31,133°C 117,0 117,0 22,2 112,6 112,6 24,2 107,7 107,7 26,4

22°C

27°C 116,0 72,9 22,2 110,7 71,1 24,0 105,0 69,4 26,1 98,8 67,5 28,5 92,1 65,4 31,230°C 117,4 94,7 22,3 112,2 92,9 24,2 106,5 90,9 26,3 100,3 88,6 28,6 93,7 86,0 31,433°C 119,1 115,9 22,4 113,0 113,0 24,2 108,0 108,0 26,436°C 123,7 123,7 22,7

20°C 15°C 10°C 7°C 5°C 0°C -5°C -10°C -15°C

PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA8°C 121,7 21,2 108,6 19,9 96,5 18,7 89,6 18,0 85,3 17,5 75,0 16,4 65,6 15,4 57,2 14,4 54,1 14,111°C 119,9 22,3 107,0 21,0 95,1 19,7 88,4 19,0 84,1 18,5 74,1 17,4 65,0 16,3 56,8 15,4 53,8 15,014°C 118,1 23,5 105,4 22,1 93,8 20,8 87,2 20,0 83,0 19,5 73,2 18,4 64,3 17,3 56,4 16,4 53,4 16,017°C 116,2 24,7 103,8 23,3 92,4 21,9 85,9 21,1 81,8 20,6 72,3 19,4 63,6 18,3 55,9 17,4 53,1 17,020°C 114,4 26,0 102,2 24,5 91,0 23,0 84,7 22,2 80,7 21,7 71,3 20,4 62,9 19,3 55,4 18,4 52,7 18,123°C 112,5 27,3 100,5 25,7 89,5 24,2 83,4 23,4 79,5 22,8 70,3 21,5 62,1 20,4 54,9 19,4 52,2 19,126°C 110,5 28,7 98,8 27,0 88,1 25,4 82,0 24,5 78,2 23,9 69,3 22,6 61,4 21,4 54,3 20,4 51,8 20,18°C 124,6 19,6 111,1 18,5 98,5 17,4 91,5 16,7 86,9 16,3 76,3 15,3 66,5 14,4 57,7 13,5 54,5 13,211°C 122,8 20,6 109,5 19,4 97,2 18,3 90,3 17,6 85,8 17,2 75,4 16,2 65,9 15,3 57,3 14,4 54,2 14,114°C 121,0 21,6 107,9 20,4 95,9 19,2 89,1 18,6 84,7 18,2 74,5 17,1 65,2 16,2 56,9 15,4 53,8 15,117°C 119,1 22,7 106,3 21,4 94,5 20,3 87,8 19,6 83,6 19,1 73,6 18,1 64,6 17,2 56,5 16,4 53,5 16,120°C 117,3 23,8 104,7 22,5 93,1 21,3 86,6 20,6 82,4 20,2 72,7 19,1 63,9 18,2 56,0 17,4 53,1 17,123°C 115,4 25,0 103,1 23,7 91,7 22,4 85,3 21,7 81,2 21,2 71,7 20,2 63,1 19,2 55,5 18,5 52,7 18,226°C 113,5 26,2 101,4 24,8 90,2 23,5 84,0 22,8 80,0 22,3 70,7 21,2 62,4 20,3 55,0 19,5 52,3 19,38°C 126,8 18,5 112,9 17,5 100,0 16,5 92,7 15,9 88,0 15,5 76,9 14,6 66,8 13,8 57,6 13,0 54,2 12,711°C 125,0 19,4 111,4 18,3 98,7 17,3 91,5 16,8 86,9 16,4 76,1 15,5 66,2 14,6 57,2 13,9 53,9 13,614°C 123,2 20,4 109,8 19,3 97,3 18,3 90,3 17,7 85,8 17,3 75,2 16,4 65,5 15,6 56,8 14,8 53,6 14,617°C 121,4 21,4 108,2 20,3 96,0 19,3 89,1 18,7 84,7 18,3 74,3 17,4 64,9 16,6 56,4 15,9 53,3 15,620°C 119,6 22,4 106,6 21,3 94,6 20,3 87,9 19,7 83,5 19,3 73,4 18,4 64,2 17,6 55,9 17,0 52,9 16,723°C 117,7 23,6 105,0 22,4 93,2 21,4 86,6 20,7 82,4 20,4 72,5 19,5 63,5 18,7 55,5 18,1 52,5 17,926°C 115,8 24,7 103,3 23,6 91,8 22,5 85,3 21,9 81,2 21,5 71,5 20,6 62,8 19,8 55,0 19,3 52,1 19,2

FAH

FAH

100FAC FAH

FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 4,97FC/FD 6,15

1,8

Application Guide /FLEXAIR-AGU-1505-E

HEATING CAPACITY AND ABSORBED POWER

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

14 0

00 m

3 /hN

omin

al a

irfl o

w ra

te18

500

m3 /h

Max

imum

airfl

ow

rate

23 0

00 m

3 /h

Ente

ring

air t

empe

ratu

reDr

y bu

lb

Min

imum

airfl

ow

ra

te14

000

m3 /h

Nom

inal

airfl

ow

rate

18 5

00 m

3 /h

Max

imum

airfl

ow

ra

te23

000

m3 /h

Outdoor air temperature

Wet bulb Dry bulb

Outdoor air temp.

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 30 •

FAC 25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 91,2 60,5 20,3 87,7 58,7 22,2 83,8 56,8 24,3 79,5 54,9 26,6 74,6 52,9 29,124°C 92,1 74,6 20,4 88,6 72,8 22,3 84,7 70,9 24,3 80,3 68,9 26,7 75,5 66,6 29,227°C 93,1 88,1 20,4 89,7 86,5 22,3 85,7 84,6 24,4 81,4 81,4 26,8 77,1 77,1 29,430°C 96,5 96,4 20,7 93,5 93,4 22,6 90,0 90,0 24,8 86,0 86,0 27,2 81,6 81,6 29,9

19°C

24°C 99,4 60,0 20,9 95,5 58,0 22,8 91,1 56,1 24,9 86,3 54,2 27,2 81,0 52,2 29,827°C 100,3 74,1 21,0 96,4 72,3 22,9 92,0 70,4 25,0 87,2 68,4 27,3 81,9 66,2 29,930°C 101,4 87,6 21,0 97,4 86,0 22,9 93,1 84,1 25,0 88,2 82,1 27,4 82,9 79,7 30,033°C 102,6 100,5 21,1 98,9 98,9 23,0 95,2 95,2 25,2 90,9 90,9 27,6 86,2 86,2 30,4

22°C

27°C 107,9 59,2 21,5 103,6 57,1 23,4 98,8 55,2 25,5 93,5 53,3 27,9 87,8 51,4 30,630°C 108,9 73,4 21,6 104,5 71,5 23,5 99,7 69,6 25,6 94,4 67,7 28,0 88,7 65,6 30,733°C 110,0 86,8 21,7 105,6 85,1 23,6 100,7 83,3 25,7 95,5 81,4 28,1 89,7 79,1 30,836°C 111,2 99,4 21,8 106,9 98,0 23,7 102,0 96,4 25,8 96,7 94,6 28,2 91,1 91,1 30,9

16°C

21°C 96,2 68,4 20,7 92,4 66,5 22,6 88,1 64,6 24,6 83,3 62,7 26,9 78,1 60,5 29,524°C 97,3 85,9 20,8 93,5 84,0 22,7 89,2 82,0 24,7 84,4 79,7 27,0 79,2 77,1 29,627°C 99,4 99,3 20,9 96,1 96,0 22,9 92,3 92,2 25,0 88,0 88,0 27,4 83,2 83,2 30,030°C 105,0 105,0 21,3 101,5 101,5 23,3 97,5 97,5 25,4 93,0 93,0 27,8 88,1 88,1 30,6

19°C

24°C 104,6 67,6 21,3 100,3 65,7 23,2 95,5 63,9 25,3 90,3 61,9 27,6 84,7 59,8 30,227°C 105,7 85,4 21,4 101,4 83,5 23,3 96,7 81,5 25,3 91,5 79,4 27,7 85,8 76,9 30,330°C 107,1 102,6 21,5 102,8 100,8 23,4 97,7 97,7 25,4 93,2 93,2 27,8 88,1 88,1 30,533°C 111,0 111,0 21,8 107,2 107,3 23,7 103,0 103,0 25,9 98,3 98,3 28,3 93,0 93,0 31,1

22°C

27°C 113,3 66,7 21,9 108,6 64,8 23,8 103,4 62,9 25,9 97,7 61,0 28,3 91,6 59,1 30,930°C 114,5 84,7 22,0 109,7 82,8 23,9 104,5 80,8 26,0 98,9 78,8 28,4 92,7 76,4 31,133°C 115,8 101,9 22,1 111,1 100,2 24,0 105,8 98,2 26,1 100,2 96,0 28,5 94,1 93,3 31,236°C 117,4 117,4 22,2 113,3 113,3 24,2 108,8 108,8 26,4 103,8 103,8 28,9

16°C

21°C 99,8 75,2 21,0 95,5 73,4 22,8 90,8 71,5 24,9 85,7 69,4 27,1 80,1 67,0 29,724°C 101,2 96,1 21,1 96,9 94,2 22,9 92,2 92,0 25,0 87,2 87,1 27,3 82,1 82,1 29,927°C 105,4 105,4 21,3 101,6 101,6 23,3 97,3 97,3 25,4 92,5 92,6 27,8 87,3 87,3 30,530°C 111,5 111,5 21,8 107,5 107,5 23,7 103,0 103,0 25,9 98,1 98,1 28,3 92,6 92,6 31,1

19°C

24°C 108,3 74,4 21,6 103,6 72,5 23,4 98,5 70,7 25,5 92,9 68,7 27,8 86,9 66,5 30,527°C 109,7 95,8 21,7 105,0 93,8 23,5 99,9 91,7 25,6 94,3 89,3 27,9 88,2 86,5 30,630°C 111,7 111,7 21,8 107,7 107,7 23,7 103,1 103,1 25,9 98,0 98,1 28,3 92,5 92,5 31,133°C 117,8 117,9 22,2 113,6 113,6 24,2 108,8 108,9 26,4 103,6 103,6 28,8

22°C

27°C 117,2 73,3 22,2 112,1 71,5 24,1 106,5 69,7 26,2 100,5 67,9 28,5 94,0 65,9 31,330°C 118,6 95,1 22,3 113,5 93,2 24,2 107,9 91,2 26,3 101,9 88,9 28,7 95,4 86,3 31,433°C 120,2 116,3 22,4 115,1 114,4 24,3 109,2 109,2 26,4 103,8 103,8 28,936°C 124,5 124,5 22,7

100FACFAC FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 4,97FC/FD 6,15

1,8

Application Guide / FLEXAIR-AGU-1505-E

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

14 0

00 m

3 /hN

omin

al a

irfl o

w ra

te18

500

m3 /h

Max

imum

airfl

ow

rate

23 0

00 m

3 /h

Outdoor air temperature

Wet bulb Dry bulb

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 31 •

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 105,1 68,5 26,6 100,6 65,8 29,4 95,4 63,3 32,6 89,5 60,7 36,0 82,9 58,0 39,724°C 106,2 83,8 26,7 101,6 81,2 29,5 96,3 78,7 32,6 90,4 75,9 36,1 83,8 72,8 39,827°C 107,3 98,3 26,7 102,7 96,0 29,6 97,4 93,4 32,7 91,5 90,5 36,1 85,2 85,1 40,030°C 109,5 109,4 26,9 105,6 105,6 29,8 101,1 101,1 33,0 95,9 95,9 36,5 89,9 89,9 40,4

19°C

24°C 114,4 67,8 27,3 109,2 64,9 30,1 103,5 62,3 33,2 97,0 59,7 36,6 89,9 57,1 40,327°C 115,5 83,2 27,4 110,3 80,5 30,2 104,5 77,9 33,3 98,0 75,2 36,7 90,9 72,2 40,430°C 116,7 97,7 27,5 111,5 95,3 30,3 105,7 92,8 33,4 99,2 90,0 36,8 92,0 86,8 40,533°C 118,0 111,4 27,6 112,8 109,3 30,4 106,9 106,9 33,5 101,3 101,3 37,0 95,0 95,0 40,9

22°C

27°C 124,0 66,9 28,0 118,3 63,9 30,8 112,0 61,2 33,9 105,0 58,7 37,3 97,3 56,2 41,130°C 125,2 82,3 28,1 119,5 79,5 30,9 113,1 76,9 34,0 106,1 74,3 37,4 98,4 71,5 41,233°C 126,5 96,7 28,2 120,7 94,3 31,0 114,3 91,8 34,1 107,3 89,2 37,5 99,6 86,2 41,336°C 127,9 110,1 28,3 122,1 108,1 31,1 115,7 105,9 34,2 108,6 103,4 37,7 100,9 100,2 41,5

16°C

21°C 111,8 78,0 27,1 106,7 75,4 29,9 100,9 72,9 33,0 94,4 70,2 36,4 87,3 67,3 40,124°C 113,2 97,6 27,2 108,0 95,0 30,0 102,2 92,3 33,1 95,7 89,2 36,5 88,5 85,7 40,127°C 114,7 114,7 27,3 110,3 110,2 30,2 105,1 105,1 33,3 99,2 99,2 36,8 92,7 92,7 40,630°C 120,8 120,8 27,8 116,1 116,1 30,6 110,8 110,8 33,8 104,8 104,8 37,3 98,0 98,0 41,1

19°C

24°C 121,3 77,0 27,8 115,6 74,3 30,6 109,2 71,8 33,6 102,2 69,3 37,0 94,5 66,5 40,827°C 122,7 96,9 27,9 117,0 94,3 30,7 110,6 91,6 33,8 103,5 88,7 37,2 95,8 85,3 40,930°C 124,4 116,0 28,1 118,6 113,5 30,8 112,1 110,7 33,9 105,1 105,1 37,3 98,2 98,2 41,133°C 127,7 127,7 28,3 122,7 122,7 31,2 117,0 117,0 34,3 110,6 110,6 37,8 103,5 103,5 41,7

22°C

27°C 131,1 75,8 28,6 124,8 73,1 31,3 117,9 70,6 34,4 110,3 68,1 37,8 102,1 65,6 41,630°C 132,7 95,9 28,7 126,4 93,2 31,4 119,4 90,6 34,5 111,8 87,9 37,9 103,5 84,8 41,733°C 134,3 115,1 28,8 128,0 112,6 31,6 121,0 110,0 34,6 113,4 107,0 38,1 105,1 103,5 41,936°C 136,2 133,4 28,9 129,5 129,5 31,7 123,4 123,4 34,9 116,7 116,7 38,4

16°C

21°C 114,2 81,8 27,3 108,7 79,3 30,0 102,7 76,8 33,1 95,9 74,1 36,5 88,5 71,1 40,224°C 115,7 103,4 27,4 110,3 100,8 30,2 104,2 98,0 33,2 97,4 94,8 36,6 89,8 89,8 40,427°C 118,5 118,5 27,6 113,7 113,7 30,4 108,1 108,1 33,5 101,9 101,9 37,0 95,0 95,0 40,930°C 124,8 124,8 28,1 119,8 119,8 30,9 114,1 114,1 34,1 107,7 107,7 37,6 100,6 100,6 41,5

19°C

24°C 123,7 80,7 28,0 117,7 78,2 30,8 111,1 75,7 33,8 103,8 73,2 37,2 95,8 70,4 41,027°C 125,4 102,7 28,1 119,3 100,1 30,9 112,7 97,4 33,9 105,3 94,3 37,3 97,3 90,8 41,130°C 127,1 124,0 28,3 120,4 120,4 31,0 114,5 114,6 34,1 108,0 108,0 37,6 100,7 100,7 41,433°C 131,9 131,9 28,6 126,5 126,5 31,5 120,5 120,5 34,6 113,7 113,7 38,1 106,3 106,3 42,1

22°C

27°C 133,6 79,4 28,7 127,1 76,8 31,5 119,9 74,4 34,6 112,0 72,1 38,0 103,5 69,5 41,830°C 135,4 101,7 28,9 128,8 99,1 31,6 121,6 96,5 34,7 113,7 93,6 38,1 105,1 90,4 42,033°C 137,2 123,1 29,0 130,6 120,6 31,8 123,4 117,9 34,9 115,4 114,7 38,3 106,6 106,6 42,136°C 139,2 139,2 29,2 133,5 133,5 32,0 127,1 127,0 35,2

20°C 15°C 10°C 7°C 5°C 0°C -5°C -10°C -15°C

PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA PS PA8°C 142,5 29,3 128,2 27,6 114,8 26,0 107,1 25,1 102,2 24,6 90,6 23,2 79,8 21,9 70,0 20,8 66,3 20,311°C 140,4 31,0 126,3 29,2 113,2 27,6 105,7 26,6 100,9 26,0 89,6 24,6 79,1 23,3 69,5 22,1 66,0 21,714°C 138,1 32,9 124,4 31,0 111,5 29,2 104,2 28,2 99,6 27,6 88,5 26,1 78,3 24,7 69,1 23,6 65,6 23,217°C 135,9 34,9 122,4 32,8 109,8 31,0 102,7 29,9 98,2 29,2 87,4 27,6 77,5 26,2 68,6 25,0 65,2 24,620°C 133,5 37,0 120,4 34,8 108,1 32,8 101,2 31,7 96,7 30,9 86,2 29,3 76,7 27,8 68,0 26,6 64,8 26,123°C 131,2 39,3 118,3 36,9 106,3 34,7 99,5 33,5 95,2 32,7 85,0 30,9 75,7 29,4 67,3 28,1 64,2 27,626°C 128,7 41,8 116,1 39,2 104,5 36,7 97,9 35,4 93,7 34,6 83,8 32,6 74,8 30,9 66,7 29,5 63,7 29,18°C 146,9 26,2 131,9 24,8 117,8 23,5 109,7 22,8 104,6 22,3 92,3 21,1 80,9 20,0 70,4 19,0 66,4 18,711°C 144,8 27,7 130,1 26,2 116,3 24,9 108,4 24,1 103,3 23,6 91,3 22,4 80,2 21,3 70,0 20,4 66,2 20,014°C 142,6 29,2 128,2 27,7 114,7 26,3 107,0 25,5 102,1 25,0 90,4 23,8 79,5 22,7 69,6 21,8 65,9 21,417°C 140,4 30,9 126,3 29,3 113,1 27,9 105,6 27,0 100,7 26,5 89,3 25,3 78,8 24,2 69,1 23,2 65,5 22,920°C 138,1 32,7 124,3 31,0 111,4 29,5 104,1 28,6 99,3 28,1 88,2 26,8 78,0 25,7 68,6 24,8 65,2 24,523°C 135,8 34,6 122,3 32,8 109,6 31,2 102,5 30,3 97,9 29,7 87,1 28,4 77,1 27,3 68,1 26,4 64,7 26,126°C 133,4 36,7 120,2 34,8 107,9 33,0 100,9 32,1 96,4 31,5 85,9 30,1 76,2 28,9 67,5 28,0 64,2 27,78°C 148,4 25,2 133,1 24,0 118,7 22,7 110,5 22,0 105,2 21,6 92,6 20,5 80,9 19,5 70,1 18,5 66,1 18,211°C 146,3 26,6 131,3 25,3 117,2 24,0 109,2 23,3 104,0 22,9 91,7 21,8 80,3 20,7 69,8 19,8 65,8 19,514°C 144,2 28,1 129,5 26,7 115,7 25,4 107,8 24,7 102,8 24,2 90,8 23,1 79,6 22,1 69,4 21,3 65,6 21,017°C 142,0 29,7 127,6 28,3 114,1 26,9 106,4 26,2 101,5 25,7 89,8 24,6 78,9 23,6 69,0 22,8 65,3 22,520°C 139,8 31,4 125,7 29,9 112,4 28,5 104,9 27,8 100,1 27,3 88,7 26,1 78,2 25,2 68,5 24,4 64,9 24,123°C 137,5 33,2 123,7 31,7 110,7 30,2 103,4 29,4 98,7 28,9 87,6 27,8 77,3 26,8 68,0 26,1 64,5 25,926°C 135,2 35,2 121,6 33,5 109,0 32,0 101,8 31,2 97,2 30,7 86,4 29,5 76,4 28,5 67,4 27,8 64,0 27,6

FAH

FAH

120FAC FAH

FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 5,99FC/FD 7,87

2,0

Application Guide /FLEXAIR-AGU-1505-E

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

15 0

00 m

3 /hN

omin

al a

irfl o

w ra

te20

500

m3 /h

Max

imum

airfl

ow

rate

23 0

00 m

3 /h

Outdoor air temp.

Ente

ring

air t

empe

ratu

reDr

y bu

lb

Min

imum

airfl

ow

ra

te15

000

m3 /h

Nom

inal

airfl

ow

rate

20 5

00 m

3 /h

Max

imum

airfl

ow

ra

te23

000

m3 /h

Outdoor air temperature

Wet bulb Dry bulb

HEATING CAPACITY AND ABSORBED POWER

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 32 •

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 106,3 69,0 26,6 101,9 66,4 29,4 96,8 63,9 32,6 91,1 61,3 36,0 84,8 58,6 39,724°C 107,3 84,3 26,7 102,8 81,8 29,5 97,8 79,3 32,6 92,0 76,5 36,1 85,7 73,5 39,827°C 108,4 98,8 26,7 103,9 96,5 29,6 98,8 94,1 32,7 93,1 91,2 36,2 86,9 86,8 40,030°C 110,4 110,4 26,9 106,7 106,7 29,8 102,4 102,4 33,0 97,3 97,3 36,6 91,6 91,6 40,4

19°C

24°C 115,6 68,3 27,3 110,7 65,6 30,1 105,1 62,9 33,2 98,8 60,4 36,6 91,9 57,8 40,427°C 116,7 83,7 27,4 111,7 81,2 30,2 106,0 78,6 33,3 99,7 75,9 36,7 92,8 72,9 40,530°C 117,9 98,2 27,5 112,8 95,9 30,3 107,2 93,4 33,4 100,9 90,7 36,8 93,9 87,5 40,633°C 119,2 111,8 27,6 114,1 109,8 30,4 108,4 107,5 33,5 102,6 102,6 37,0 96,5 96,6 40,9

22°C

27°C 125,4 67,4 28,0 119,9 64,5 30,8 113,7 61,8 33,9 106,8 59,3 37,4 99,4 56,8 41,130°C 126,5 82,8 28,1 120,9 80,1 30,9 114,7 77,6 34,0 107,9 75,0 37,5 100,3 72,2 41,233°C 127,7 97,1 28,2 122,1 94,8 31,0 115,9 92,4 34,1 109,0 89,8 37,6 101,5 86,8 41,436°C 129,1 110,4 28,3 123,5 108,5 31,1 117,2 106,3 34,2 110,3 103,8 37,7 102,8 100,8 41,5

16°C

21°C 113,2 78,5 27,1 108,2 76,0 29,9 102,5 73,5 33,0 96,2 70,9 36,4 89,2 68,0 40,124°C 114,5 98,1 27,2 109,4 95,6 30,0 103,7 92,9 33,1 97,4 89,9 36,5 90,4 86,4 40,227°C 115,8 115,7 27,3 111,4 111,4 30,2 106,4 106,4 33,3 100,7 100,7 36,8 94,3 94,3 40,630°C 121,9 121,9 27,8 117,4 117,4 30,6 112,2 112,2 33,8 106,3 106,3 37,3 99,7 99,7 41,2

19°C

24°C 122,9 77,5 27,9 117,3 74,9 30,6 111,0 72,4 33,7 104,1 69,9 37,1 96,6 67,2 40,827°C 124,2 97,4 28,0 118,6 94,8 30,7 112,3 92,2 33,8 105,4 89,3 37,2 97,8 86,0 40,930°C 125,6 116,4 28,1 120,0 114,0 30,8 113,7 111,3 33,9 106,6 106,6 37,3 99,9 99,9 41,233°C 128,8 128,8 28,3 123,9 123,9 31,2 118,3 118,4 34,3 112,1 112,1 37,8 105,2 105,2 41,7

22°C

27°C 132,9 76,1 28,6 126,7 73,6 31,4 119,9 71,1 34,4 112,4 68,8 37,9 104,3 66,2 41,630°C 134,3 96,2 28,7 128,1 93,7 31,5 121,2 91,2 34,6 113,7 88,5 38,0 105,6 85,4 41,833°C 135,8 115,4 28,8 129,6 113,0 31,6 122,7 110,5 34,7 115,2 107,5 38,1 107,0 104,0 42,036°C 137,4 133,5 29,0 130,6 130,6 31,7 124,7 124,7 34,9 118,1 118,1 38,4 110,8 110,8 42,3

16°C

21°C 115,6 82,3 27,3 110,3 79,9 30,1 104,3 77,4 33,1 97,7 74,7 36,5 90,4 71,7 40,224°C 117,0 103,8 27,4 111,6 101,3 30,2 105,6 98,5 33,2 99,0 95,4 36,6 91,7 91,6 40,327°C 119,6 119,6 27,6 114,9 114,9 30,4 109,5 109,5 33,6 103,4 103,4 37,0 96,6 96,7 40,930°C 126,1 126,1 28,1 121,2 121,2 30,9 115,6 115,6 34,1 109,3 109,3 37,6 102,4 102,3 41,5

19°C

24°C 125,3 81,1 28,0 119,4 78,7 30,8 112,9 76,3 33,8 105,7 73,8 37,2 97,9 71,0 41,027°C 126,8 103,1 28,1 120,8 100,6 30,9 114,3 97,9 34,0 107,1 94,9 37,4 99,2 91,4 41,130°C 128,3 124,3 28,3 122,4 121,8 31,0 116,0 116,0 34,1 109,6 109,6 37,6 102,4 102,5 41,433°C 133,2 133,2 28,6 127,9 127,9 31,5 122,0 122,0 34,6 115,4 115,4 38,1 108,1 108,0 42,1

22°C

27°C 135,5 79,7 28,8 129,0 77,2 31,5 121,9 74,9 34,6 114,1 72,6 38,0 105,7 70,1 41,930°C 137,0 101,9 28,9 130,5 99,5 31,7 123,3 96,9 34,7 115,6 94,2 38,2 107,1 91,0 42,033°C 138,6 123,3 29,0 132,1 120,9 31,8 124,9 118,2 34,9 117,1 115,1 38,3 108,4 108,4 42,136°C 140,5 140,5 29,2 134,9 134,9 32,0 128,6 128,6 35,2 121,6 121,6 38,8

FAC

120FACFAC FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 5,99FC/FD 7,87

2,0

Application Guide / FLEXAIR-AGU-1505-E

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

15 0

00 m

3 /hN

omin

al a

irfl o

w ra

te20

500

m3 /h

Max

imum

airfl

ow

rate

23 0

00 m

3 /h

Outdoor air temperature

Wet bulb Dry bulb

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 33 •

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 120,5 79,8 31,7 115,0 76,6 35,1 108,7 73,6 38,8 101,6 70,5 42,8 93,7 67,3 47,324°C 121,5 98,1 31,8 116,0 95,1 35,1 109,7 92,1 38,8 102,6 88,8 42,9 94,7 85,1 47,327°C 122,8 115,6 31,9 117,3 113,0 35,2 111,0 110,0 38,9 104,2 104,2 43,1 97,3 97,2 47,730°C 127,0 127,0 32,2 122,3 122,3 35,6 116,7 116,7 39,5 110,2 110,2 43,7 102,9 102,9 48,3

19°C

24°C 131,3 78,9 32,7 125,1 75,5 36,0 118,1 72,4 39,6 110,2 69,4 43,6 101,6 66,3 48,127°C 132,3 97,3 32,7 126,1 94,2 36,0 119,0 91,1 39,7 111,2 87,9 43,7 102,6 84,4 48,230°C 133,5 114,9 32,8 127,3 112,1 36,1 120,3 109,2 39,8 112,4 105,9 43,9 103,8 102,0 48,333°C 135,0 131,7 33,0 129,4 129,4 36,3 123,3 123,3 40,1 116,4 116,4 44,3 108,6 108,7 48,9

22°C

27°C 142,5 77,8 33,6 135,5 74,3 36,9 127,8 71,1 40,5 119,3 68,2 44,6 109,9 65,2 49,030°C 143,4 96,3 33,7 136,5 93,1 37,0 128,7 90,0 40,6 120,2 86,9 44,7 110,9 83,6 49,233°C 144,6 113,7 33,8 137,7 111,0 37,1 129,9 108,1 40,8 121,4 105,0 44,8 112,0 101,3 49,336°C 146,1 130,3 33,9 139,2 128,0 37,2 131,4 125,5 40,9 122,8 122,4 45,0 114,6 114,5 49,7

16°C

21°C 128,8 93,6 32,5 122,6 90,6 35,8 115,6 87,5 39,4 107,8 84,3 43,4 99,2 80,8 47,724°C 130,2 118,3 32,6 124,0 115,2 35,9 117,0 111,9 39,5 109,2 108,1 43,5 101,1 101,0 48,127°C 133,8 133,7 32,9 128,4 128,4 36,3 122,2 122,1 40,0 115,0 115,0 44,2 107,0 107,0 48,730°C 141,5 141,5 33,6 135,8 135,8 37,0 129,1 129,1 40,7 121,6 121,6 44,9 113,2 113,3 49,4

19°C

24°C 139,8 92,5 33,4 132,8 89,3 36,7 125,1 86,3 40,3 116,6 83,2 44,3 107,3 79,9 48,627°C 141,2 117,6 33,5 134,3 114,4 36,8 126,5 111,2 40,4 118,0 107,6 44,4 108,7 103,4 48,830°C 142,9 142,0 33,7 136,0 136,0 37,0 129,3 129,3 40,7 121,7 121,7 44,8 113,3 113,3 49,433°C 149,6 149,6 34,3 143,3 143,4 37,7 136,3 136,3 41,4 128,3 128,3 45,6 119,5 119,5 50,2

22°C

27°C 151,1 91,1 34,4 143,5 87,9 37,6 135,1 84,9 41,2 125,8 82,0 45,3 115,8 78,9 49,730°C 152,5 116,6 34,5 144,9 113,4 37,8 136,5 110,3 41,4 127,2 106,8 45,4 117,2 102,9 49,933°C 154,2 141,2 34,7 146,6 138,2 37,9 138,1 135,0 41,6 128,6 128,6 45,6 119,7 119,7 50,236°C 157,8 157,8 35,0 151,1 151,1 38,4 143,6 143,6 42,2

16°C

21°C 134,7 107,0 33,0 127,7 104,1 36,2 119,9 101,0 39,7 111,3 97,6 43,7 102,0 93,5 48,124°C 136,5 136,5 33,1 130,3 130,3 36,4 123,3 123,3 40,1 115,4 115,4 44,2 106,6 106,6 48,727°C 144,6 144,6 33,8 138,1 138,1 37,1 130,7 130,7 40,8 122,3 122,4 44,9 113,2 113,2 49,430°C 153,0 153,0 34,5 146,0 146,1 37,9 138,2 138,2 41,6 129,5 129,5 45,7 120,0 120,0 50,3

19°C

24°C 145,9 105,7 33,9 138,2 102,8 37,1 129,7 99,9 40,7 120,4 96,7 44,7 110,3 92,9 49,127°C 147,9 138,5 34,1 140,2 135,2 37,3 131,6 131,6 40,9 122,6 122,6 44,9 113,4 113,4 49,530°C 153,3 153,3 34,6 146,2 146,3 37,9 138,3 138,4 41,6 129,6 129,6 45,7 120,0 120,0 50,333°C 161,6 161,6 35,3 154,2 154,2 38,7 145,9 145,9 42,4

22°C

27°C 157,5 104,2 34,9 149,1 101,3 38,1 139,9 98,6 41,7 129,8 95,6 45,8 119,0 92,2 50,330°C 159,4 137,7 35,1 151,0 134,5 38,3 141,8 131,1 41,9 131,8 127,2 46,0 120,3 120,3 50,433°C 162,1 162,1 35,3 154,6 154,6 38,7 146,2 146,3 42,436°C

20°C 15°C 10°C 7°C 5°C 0°C -5°C -10°C -15°C

PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA8°C 171,7 32,4 153,5 30,6 136,7 28,9 127,2 28,0 121,2 27,4 107,1 25,9 94,4 24,5 83,0 23,3 78,8 22,911°C 169,3 34,3 151,4 32,4 134,9 30,7 125,7 29,7 119,8 29,0 106,0 27,5 93,6 26,1 82,6 24,9 78,5 24,514°C 166,8 36,4 149,3 34,4 133,1 32,5 124,1 31,5 118,3 30,8 104,9 29,2 92,8 27,7 82,1 26,5 78,2 26,117°C 164,3 38,6 147,1 36,5 131,3 34,5 122,5 33,4 116,8 32,7 103,7 31,0 92,0 29,5 81,6 28,2 77,9 27,820°C 161,7 41,1 144,9 38,8 129,4 36,7 120,8 35,5 115,3 34,7 102,5 32,9 91,1 31,3 81,1 29,9 77,4 29,523°C 159,1 43,8 142,6 41,3 127,5 39,0 119,1 37,6 113,7 36,8 101,3 34,8 90,2 33,1 80,5 31,7 77,0 31,226°C 156,5 46,7 140,3 43,9 125,5 41,4 117,3 39,9 112,1 39,0 100,0 36,9 89,2 35,0 79,9 33,5 76,5 32,98°C 176,7 28,8 157,9 27,3 140,3 25,9 130,5 25,1 124,2 24,5 109,4 23,3 95,9 22,2 83,9 21,1 79,4 20,811°C 174,4 30,3 155,8 28,8 138,7 27,3 129,0 26,5 122,8 26,0 108,4 24,7 95,3 23,6 83,5 22,6 79,2 22,214°C 172,0 32,0 153,8 30,4 136,9 28,9 127,5 28,0 121,4 27,5 107,3 26,2 94,5 25,0 83,1 24,1 78,9 23,717°C 169,5 33,8 151,6 32,2 135,1 30,6 125,9 29,7 120,0 29,1 106,2 27,8 93,7 26,6 82,7 25,7 78,6 25,420°C 167,0 35,8 149,5 34,0 133,3 32,4 124,2 31,4 118,5 30,9 105,0 29,5 92,9 28,3 82,2 27,3 78,3 27,023°C 164,5 37,9 147,3 36,0 131,4 34,3 122,6 33,3 116,9 32,7 103,8 31,2 92,1 30,0 81,7 29,1 77,9 28,826°C 161,9 40,2 145,0 38,2 129,5 36,3 120,9 35,3 115,4 34,6 102,6 33,1 91,2 31,8 81,1 30,8 77,4 30,58°C 180,9 26,4 161,2 25,1 142,9 23,9 132,6 23,2 126,0 22,8 110,4 21,7 96,2 20,7 83,3 19,9 78,5 19,611°C 178,6 27,8 159,2 26,5 141,3 25,3 131,1 24,6 124,7 24,1 109,4 23,1 95,5 22,1 83,0 21,3 78,4 21,114°C 176,2 29,3 157,2 28,0 139,6 26,7 129,7 26,0 123,3 25,6 108,4 24,5 94,9 23,6 82,7 22,9 78,2 22,717°C 173,8 30,9 155,2 29,6 137,9 28,3 128,1 27,6 121,9 27,2 107,4 26,1 94,1 25,2 82,3 24,6 77,9 24,420°C 171,4 32,6 153,1 31,3 136,1 30,0 126,6 29,3 120,5 28,8 106,3 27,8 93,4 27,0 81,8 26,4 77,6 26,223°C 168,9 34,5 150,9 33,1 134,3 31,8 125,0 31,1 119,0 30,6 105,1 29,6 92,6 28,8 81,4 28,3 77,3 28,226°C 166,4 36,6 148,7 35,1 132,4 33,8 123,3 33,0 117,5 32,6 103,9 31,5 91,7 30,8 80,9 30,4 76,9 30,3

FAH

FAH

150FAC FAH

FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 6,40FC/FD 7,81

4,6

Application Guide /FLEXAIR-AGU-1505-E

Outdoor air temperature

Wet bulb Dry bulb

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

18 0

00 m

3 /hN

omin

al a

irfl o

w ra

te26

000

m3 /h

Max

imum

airfl

ow

rate

35 0

00 m

3 /h

Outdoor air temp.

Ente

ring

air t

empe

ratu

reDr

y bu

lb

Min

imum

airfl

ow

ra

te18

000

m3 /h

Nom

inal

airfl

ow

rate

26 0

00 m

3 /h

Max

imum

airfl

ow

ra

te35

000

m3 /h

HEATING CAPACITY AND ABSORBED POWER

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 34 •

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 124,6 81,8 31,8 119,0 78,5 35,2 112,7 75,5 38,9 105,6 72,4 43,0 97,8 69,1 47,424°C 125,6 99,8 31,9 120,1 96,9 35,2 113,7 93,8 39,0 106,6 90,6 43,1 98,8 86,9 47,527°C 126,9 117,3 32,0 121,4 114,7 35,4 115,0 111,8 39,1 107,7 107,7 43,2 100,8 100,8 47,830°C 130,7 130,6 32,2 125,9 125,9 35,7 120,3 120,3 39,6 113,8 113,8 43,8 106,5 106,5 48,4

19°C

24°C 135,6 80,9 32,8 129,3 77,4 36,1 122,3 74,2 39,7 114,4 71,1 43,8 105,8 68,0 48,227°C 136,6 99,1 32,8 130,3 96,0 36,2 123,3 92,9 39,8 115,4 89,6 43,9 106,8 86,1 48,330°C 137,9 116,6 32,9 131,6 113,9 36,3 124,6 111,0 40,0 116,7 107,7 44,0 108,1 103,9 48,533°C 139,5 133,6 33,1 133,2 131,3 36,4 127,0 127,0 40,2 120,1 120,1 44,4 112,3 112,3 49,0

22°C

27°C 147,1 79,8 33,8 140,0 76,2 37,0 132,2 72,9 40,7 123,6 69,8 44,8 114,3 66,8 49,230°C 148,1 98,0 33,8 141,1 94,8 37,1 133,2 91,6 40,8 124,6 88,5 44,9 115,3 85,1 49,433°C 149,4 115,4 33,9 142,4 112,6 37,3 134,5 109,7 40,9 125,9 106,6 45,0 116,5 103,0 49,536°C 151,0 132,1 34,1 143,9 129,8 37,4 136,1 127,3 41,1 127,5 124,2 45,2 118,3 118,3 49,8

16°C

21°C 133,6 95,8 32,6 127,3 92,7 35,9 120,2 89,6 39,6 112,3 86,3 43,6 103,6 82,7 47,924°C 135,0 120,3 32,8 128,7 117,2 36,1 121,6 113,8 39,7 113,7 110,1 43,7 104,9 104,9 48,227°C 137,9 137,9 33,0 132,5 132,4 36,4 126,2 126,2 40,2 119,1 119,1 44,3 111,1 111,1 48,830°C 145,8 145,8 33,7 140,0 140,0 37,1 133,3 133,3 40,8 125,7 125,7 45,0 117,3 117,3 49,5

19°C

24°C 144,8 94,7 33,6 137,8 91,4 36,8 129,9 88,3 40,5 121,3 85,1 44,5 111,9 81,7 48,827°C 146,3 119,6 33,7 139,2 116,4 37,0 131,3 113,1 40,6 122,7 109,4 44,6 113,3 105,2 49,030°C 148,0 144,1 33,9 140,2 140,2 37,1 133,5 133,5 40,8 125,9 125,9 45,0 117,4 117,4 49,533°C 154,0 154,0 34,4 147,7 147,7 37,8 140,5 140,6 41,5 132,5 132,6 45,7 123,7 123,7 50,3

22°C

27°C 156,5 93,3 34,6 148,7 89,9 37,8 140,1 86,8 41,4 130,7 83,7 45,5 120,6 80,5 49,930°C 158,0 118,6 34,7 150,1 115,3 38,0 141,5 112,0 41,6 132,1 108,5 45,6 122,0 104,5 50,133°C 159,7 143,2 34,8 151,9 140,1 38,1 143,2 136,8 41,8 133,8 132,9 45,836°C 162,4 162,4 35,1 155,6 155,7 38,5 148,0 148,0 42,3

16°C

21°C 140,0 109,3 33,2 132,8 106,2 36,4 124,8 103,0 40,0 116,1 99,5 43,9 106,6 95,4 48,324°C 141,9 141,1 33,3 134,6 134,5 36,5 127,5 127,5 40,2 119,5 119,5 44,3 110,7 110,7 48,827°C 149,3 149,3 33,9 142,6 142,6 37,3 135,1 135,1 41,0 126,8 126,8 45,1 117,6 117,6 49,630°C 157,8 157,9 34,7 150,8 150,8 38,0 142,9 142,9 41,7 134,1 134,1 45,9

19°C

24°C 151,5 108,0 34,1 143,6 104,9 37,3 134,9 101,8 40,9 125,3 98,5 44,9 115,1 94,6 49,327°C 153,5 140,6 34,3 145,5 137,2 37,5 136,7 133,5 41,1 126,9 127,0 45,1 117,7 117,7 49,630°C 158,1 158,1 34,7 151,0 151,0 38,0 143,0 143,0 41,8 134,2 134,2 45,933°C 166,7 166,7 35,4 159,1 159,2 38,8

22°C

27°C 163,5 106,4 35,1 154,8 103,3 38,4 145,3 100,4 42,0 135,0 97,3 46,030°C 165,4 139,7 35,3 156,7 136,4 38,6 147,2 132,9 42,2 136,9 128,8 46,233°C 167,1 167,1 35,5 159,5 159,5 38,836°C

FAC

150FACFAC FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 6,40FC/FD 7,81

4,6

Application Guide / FLEXAIR-AGU-1505-E

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

18 0

00 m

3 /hN

omin

al a

irfl o

w ra

te26

000

m3 /h

Max

imum

airfl

ow

rate

35 0

00 m

3 /h

Outdoor air temperature

Wet bulb Dry bulb

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 35 •

20°C 15°C 10°C 7°C 5°C 0°C -5°C -10°C -15°C

PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA8°C 205,3 38,1 183,2 35,8 162,8 33,6 151,3 32,4 144,0 31,6 126,8 29,7 111,3 28,0 97,4 26,5 92,3 26,011°C 202,4 40,3 180,7 37,9 160,7 35,6 149,4 34,3 142,2 33,4 125,5 31,5 110,3 29,7 96,8 28,3 91,9 27,814°C 199,5 42,7 178,1 40,1 158,5 37,7 147,4 36,3 140,4 35,4 124,0 33,4 109,3 31,6 96,1 30,1 91,4 29,617°C 196,4 45,2 175,5 42,5 156,2 39,9 145,4 38,5 138,5 37,5 122,5 35,4 108,2 33,6 95,4 32,1 90,8 31,620°C 193,3 48,0 172,8 45,0 153,9 42,3 143,3 40,8 136,6 39,8 121,0 37,6 107,0 35,6 94,6 34,1 90,1 33,623°C 190,1 51,0 170,0 47,8 151,4 44,8 141,1 43,2 134,6 42,1 119,3 39,8 105,7 37,8 93,7 36,2 89,4 35,726°C 186,9 54,2 167,1 50,7 149,0 47,5 138,9 45,7 132,5 44,6 117,6 42,1 104,4 40,0 92,8 38,3 88,6 37,78°C 211,9 33,8 188,8 31,9 167,4 30,1 155,3 29,0 147,6 28,4 129,5 26,8 113,0 25,3 98,1 24,1 92,6 23,611°C 209,1 35,6 186,4 33,6 165,4 31,7 153,5 30,7 146,0 30,0 128,2 28,4 112,1 26,9 97,6 25,7 92,3 25,314°C 206,2 37,5 183,9 35,4 163,3 33,5 151,7 32,4 144,2 31,7 126,9 30,1 111,2 28,7 97,1 27,5 91,9 27,117°C 203,2 39,5 181,3 37,4 161,1 35,4 149,7 34,3 142,5 33,6 125,5 31,9 110,1 30,5 96,4 29,3 91,4 29,020°C 200,2 41,8 178,7 39,5 158,8 37,4 147,7 36,3 140,6 35,5 124,0 33,8 109,0 32,4 95,7 31,3 90,9 31,023°C 197,1 44,1 176,0 41,8 156,5 39,6 145,6 38,4 138,7 37,6 122,5 35,9 107,9 34,5 94,9 33,4 90,2 33,126°C 194,0 46,7 173,2 44,2 154,1 41,9 143,4 40,6 136,7 39,8 120,8 38,1 106,6 36,6 94,1 35,6 89,5 35,38°C 214,7 32,2 191,1 30,5 169,1 28,8 156,7 27,9 148,8 27,2 130,1 25,8 113,1 24,4 97,7 23,3 92,0 22,811°C 211,9 33,9 188,7 32,1 167,2 30,4 155,0 29,4 147,2 28,8 128,9 27,3 112,3 26,0 97,3 24,9 91,7 24,514°C 209,1 35,7 186,3 33,8 165,1 32,1 153,2 31,1 145,6 30,5 127,7 29,0 111,4 27,7 96,8 26,7 91,4 26,317°C 206,2 37,6 183,8 35,7 163,0 33,9 151,3 32,9 143,8 32,3 126,3 30,8 110,4 29,6 96,2 28,6 90,9 28,320°C 203,3 39,7 181,2 37,7 160,8 35,9 149,3 34,9 142,0 34,2 124,9 32,8 109,4 31,6 95,5 30,7 90,4 30,423°C 200,2 41,9 178,6 39,9 158,5 38,0 147,3 36,9 140,1 36,3 123,4 34,8 108,3 33,7 94,8 32,9 89,9 32,726°C 197,1 44,3 175,8 42,2 156,2 40,2 145,2 39,2 138,2 38,5 121,8 37,0 107,1 35,9 94,0 35,2 89,2 35,1

FAH

FAH

170FAC FAH

FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 8,99FC/FD 10,56

4,6

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 145,7 95,5 36,2 139,6 91,8 40,0 132,6 88,3 44,3 124,6 84,7 49,0 115,7 81,0 54,324°C 147,0 116,6 36,3 140,9 113,3 40,1 133,9 109,8 44,4 125,9 106,1 49,1 116,9 101,9 54,527°C 148,4 137,0 36,4 142,4 134,1 40,2 135,3 130,8 44,5 127,3 127,0 49,3 119,1 119,1 54,930°C 152,1 152,0 36,6 147,0 147,0 40,6 140,9 140,9 45,0 133,8 133,8 50,0 125,6 125,6 55,6

19°C

24°C 159,0 94,7 37,3 152,1 90,8 41,1 144,2 87,1 45,3 135,4 83,6 50,1 125,6 80,0 55,527°C 160,4 116,0 37,4 153,5 112,4 41,2 145,6 108,9 45,5 136,7 105,3 50,2 126,9 101,3 55,630°C 161,9 136,3 37,5 155,0 133,3 41,3 147,1 130,0 45,6 138,2 126,4 50,4 128,4 122,1 55,833°C 163,6 155,9 37,7 156,6 153,4 41,5 149,3 149,3 45,8 141,7 141,7 50,8 133,0 133,0 56,5

22°C

27°C 172,7 93,6 38,5 165,0 89,4 42,2 156,3 85,7 46,5 146,7 82,2 51,3 136,0 78,7 56,830°C 174,2 114,7 38,6 166,4 111,0 42,4 157,7 107,5 46,6 148,0 104,0 51,5 137,4 100,2 57,033°C 175,8 134,8 38,7 168,0 131,7 42,5 159,3 128,6 46,8 149,6 125,1 51,7 138,9 121,1 57,236°C 177,5 154,0 38,8 169,7 151,5 42,7 161,0 148,8 47,0 151,2 145,5 51,8 140,7 140,7 57,5

16°C

21°C 156,3 111,0 37,1 149,3 107,5 40,9 141,4 104,0 45,1 132,5 100,4 49,8 122,6 96,4 55,124°C 158,0 139,5 37,2 151,0 136,1 41,0 143,1 132,4 45,2 134,2 128,2 49,9 124,3 123,3 55,227°C 161,1 161,0 37,5 155,1 155,0 41,4 148,1 148,0 45,8 140,0 140,0 50,7 130,9 130,9 56,230°C 170,1 170,1 38,2 163,7 163,8 42,1 156,4 156,4 46,5 148,0 148,0 51,5 138,5 138,5 57,1

19°C

24°C 169,9 109,8 38,2 162,1 106,1 42,0 153,4 102,7 46,2 143,6 99,2 50,9 132,9 95,4 56,327°C 171,7 138,7 38,4 163,9 135,2 42,1 155,1 131,6 46,4 145,3 127,6 51,1 134,6 123,0 56,630°C 173,7 167,0 38,5 165,8 163,7 42,3 156,9 157,0 46,6 148,3 148,4 51,5 138,7 138,8 57,133°C 180,0 180,0 39,1 173,1 173,2 43,0 165,2 165,3 47,4 156,3 156,3 52,4 146,3 146,3 58,2

22°C

27°C 184,0 108,0 39,4 175,4 104,3 43,2 165,8 100,9 47,4 155,2 97,6 52,2 143,6 94,1 57,830°C 185,9 137,3 39,5 177,2 133,8 43,3 167,6 130,3 47,6 157,0 126,5 52,5 145,4 122,2 58,033°C 187,9 165,7 39,7 179,2 162,5 43,5 169,5 158,9 47,8 158,9 154,9 52,7 146,9 146,9 58,236°C 190,2 190,2 39,9 182,8 182,9 43,9 174,4 174,4 48,4 165,0 165,0 53,5

16°C

21°C 160,4 118,6 37,4 152,9 115,2 41,2 144,5 111,8 45,3 135,0 108,0 50,0 124,7 103,8 55,424°C 162,4 151,2 37,6 154,8 147,7 41,3 146,4 143,8 45,5 137,0 136,9 50,3 127,5 127,5 55,727°C 168,2 168,2 38,0 161,5 161,5 41,9 153,8 153,8 46,2 145,0 145,0 51,1 135,2 135,2 56,730°C 177,9 177,9 38,9 170,8 170,8 42,8 162,7 162,7 47,2 153,6 153,6 52,1 143,5 143,4 57,9

19°C

24°C 174,2 117,2 38,6 165,9 113,8 42,3 156,6 110,4 46,5 146,3 106,9 51,3 135,1 102,9 56,727°C 176,2 150,5 38,7 167,9 147,0 42,5 158,6 143,2 46,7 148,3 138,9 51,5 137,0 133,9 57,030°C 178,4 178,4 38,9 171,2 171,2 42,8 162,9 162,9 47,1 153,6 153,6 52,1 143,3 143,3 57,833°C 188,0 188,1 39,7 180,5 180,5 43,6 171,9 171,9 48,1 162,2 162,2 53,2 151,5 151,5 59,0

22°C

27°C 188,5 115,2 39,7 179,3 111,8 43,5 169,2 108,6 47,8 158,1 105,3 52,6 146,0 101,7 58,330°C 190,6 149,0 39,9 181,4 145,6 43,7 171,2 142,0 48,0 160,1 138,1 52,9 148,0 133,4 58,633°C 192,8 182,1 40,1 183,6 178,8 43,9 172,4 172,4 48,1 162,6 162,6 53,1 151,7 151,7 59,036°C 198,5 198,5 40,6 190,4 190,4 44,6 181,3 181,3 49,1

Application Guide /FLEXAIR-AGU-1505-E

Outdoor air temperature

Wet bulb Dry bulb

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

21 0

00 m

3 /hN

omin

al a

irfl o

w ra

te30

000

m3 /h

Max

imum

airfl

ow

rate

35 0

00 m

3 /h

Ente

ring

air t

empe

ratu

reDr

y bu

lb

Min

imum

airfl

ow

ra

te21

000

m3 /h

Nom

inal

airfl

ow

ra

te30

000

m3 /h

Max

imum

airfl

ow

ra

te35

000

m3 /h

HEATING CAPACITY AND ABSORBED POWER

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

Outdoor air temp.

5- STANDARD UNITS PERFORMANCES

• 36 •

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 147,6 96,3 36,2 141,8 92,8 40,0 135,0 89,3 44,3 127,3 85,8 49,1 118,7 82,1 54,424°C 148,9 117,6 36,3 143,0 114,4 40,1 136,2 111,0 44,4 128,5 107,3 49,2 119,9 103,2 54,527°C 150,4 138,1 36,4 144,5 135,2 40,2 137,7 131,9 44,5 130,0 128,2 49,3 121,5 121,5 54,830°C 153,7 153,6 36,6 148,8 148,8 40,6 143,0 142,9 45,1 136,1 136,1 50,0 128,2 128,2 55,6

19°C

24°C 161,0 95,4 37,3 154,3 91,6 41,1 146,7 88,1 45,4 138,2 84,6 50,2 128,8 81,0 55,527°C 162,3 116,9 37,4 155,6 113,5 41,2 148,0 110,0 45,5 139,4 106,4 50,3 130,0 102,4 55,730°C 163,8 137,3 37,5 157,1 134,3 41,4 149,5 131,1 45,6 140,9 127,4 50,4 131,5 123,1 55,933°C 165,7 156,8 37,7 159,0 154,3 41,5 151,4 151,4 45,8 143,9 143,9 50,8 135,5 135,5 56,4

22°C

27°C 174,9 94,1 38,5 167,4 90,1 42,3 159,0 86,5 46,6 149,7 83,0 51,4 139,5 79,6 56,930°C 176,2 115,5 38,6 168,7 112,0 42,4 160,3 108,5 46,7 150,9 105,0 51,5 140,7 101,2 57,133°C 177,8 135,7 38,7 170,3 132,7 42,5 161,8 129,5 46,8 152,5 126,1 51,7 142,2 122,1 57,336°C 179,7 154,8 38,9 172,1 152,3 42,7 163,7 149,6 47,0 154,3 146,3 51,9 144,0 142,2 57,5

16°C

21°C 158,5 111,6 37,1 151,7 108,3 40,9 144,0 104,9 45,1 135,3 101,4 49,8 125,8 97,4 55,124°C 160,2 140,4 37,3 153,4 137,1 41,1 145,7 133,4 45,3 137,0 129,3 50,0 127,5 124,5 55,327°C 163,0 162,9 37,5 157,2 157,1 41,4 150,3 150,3 45,8 142,5 142,5 50,7 133,7 133,8 56,230°C 171,8 171,9 38,2 165,8 165,8 42,2 158,7 158,7 46,6 150,6 150,6 51,5 141,5 141,5 57,1

19°C

24°C 172,1 110,2 38,3 164,5 106,8 42,0 156,0 103,5 46,2 146,5 100,0 51,0 136,2 96,3 56,427°C 173,9 139,5 38,4 166,3 136,1 42,2 157,7 132,6 46,4 148,3 128,6 51,2 137,9 124,1 56,630°C 176,0 167,8 38,6 168,4 164,6 42,4 159,4 159,4 46,6 151,0 151,0 51,6 141,6 141,6 57,133°C 181,9 182,0 39,1 175,2 175,3 43,0 167,6 167,6 47,4 158,9 158,9 52,4 149,2 149,2 58,1

22°C

27°C 186,4 108,3 39,4 178,0 104,8 43,2 168,6 101,5 47,5 158,3 98,3 52,3 147,1 94,9 57,930°C 188,2 137,9 39,6 179,7 134,5 43,4 170,4 131,1 47,7 160,1 127,4 52,5 148,9 123,2 58,133°C 190,3 166,4 39,8 181,8 163,2 43,6 172,4 159,8 47,9 162,1 155,7 52,8 149,8 149,8 58,236°C 192,4 192,4 39,9 185,1 185,1 43,9 176,8 176,8 48,4 167,5 167,5 53,4

16°C

21°C 162,8 119,2 37,5 155,5 116,0 41,2 147,2 112,6 45,4 138,1 109,0 50,1 128,0 104,8 55,424°C 164,8 152,0 37,6 157,5 148,7 41,4 149,2 144,9 45,6 139,9 139,8 50,4 130,7 130,6 55,827°C 170,2 170,1 38,0 163,7 163,7 41,9 156,2 156,2 46,3 147,7 147,7 51,2 138,2 138,2 56,730°C 179,6 179,6 38,8 172,9 172,9 42,8 165,1 165,1 47,2 156,3 156,3 52,2 146,5 146,5 57,8

19°C

24°C 176,6 117,5 38,6 168,5 114,3 42,3 159,4 111,1 46,6 149,5 107,7 51,3 138,6 103,8 56,827°C 178,7 151,1 38,8 170,5 147,8 42,5 161,5 144,2 46,8 151,5 140,0 51,6 140,6 135,0 57,130°C 180,7 180,7 38,9 173,6 173,6 42,8 165,5 165,5 47,2 156,4 156,5 52,2 146,3 146,4 57,833°C 190,0 190,0 39,7 182,6 182,6 43,6 174,2 174,2 48,1 164,9 164,9 53,2 154,5 154,5 59,0

22°C

27°C 191,1 115,3 39,8 182,1 112,1 43,6 172,2 109,1 47,8 161,4 105,9 52,7 149,7 102,5 58,430°C 193,1 149,5 40,0 184,2 146,2 43,8 174,3 142,8 48,1 163,5 138,9 53,0 151,7 134,4 58,733°C 195,5 182,7 40,2 186,5 179,5 44,0 176,6 175,8 48,3 165,5 165,5 53,2 154,8 154,8 59,036°C 200,7 200,7 40,6 192,7 192,7 44,6 183,8 183,7 49,1

FAC

170FACFAC FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 8,99FC/FD 10,56

4,6

Application Guide / FLEXAIR-AGU-1505-E

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

21 0

00 m

3 /hN

omin

al a

irfl o

w ra

te30

000

m3 /h

Max

imum

airfl

ow

rate

35 0

00 m

3 /h

Outdoor air temperature

Wet bulb Dry bulb

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 37 •

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 152,7 99,2 39,1 164,8 107,4 44,2 157,1 103,6 48,4 148,5 99,7 53,1 138,9 95,6 58,224°C 172,9 135,8 40,4 166,2 132,2 44,3 158,5 128,4 48,5 149,9 124,3 53,2 140,3 119,8 58,427°C 174,5 159,3 40,6 167,8 156,1 44,4 160,1 152,5 48,6 151,5 148,3 53,3 141,8 141,8 58,730°C 178,8 178,7 40,8 173,1 173,0 44,7 166,3 166,3 49,1 158,6 158,6 54,0 149,8 149,8 59,5

19°C

24°C 187,3 110,5 41,5 179,7 106,3 45,3 171,1 102,3 49,6 161,6 98,4 54,3 151,1 94,4 59,527°C 188,8 135,1 41,6 181,1 131,2 45,4 172,6 127,4 49,7 163,0 123,4 54,4 152,6 119,0 59,730°C 190,5 158,5 41,7 182,8 155,1 45,6 174,2 151,5 49,8 164,7 147,5 54,6 154,3 142,9 59,933°C 192,4 180,9 41,9 184,7 178,1 45,7 176,1 174,9 50,0 168,0 168,0 54,9 158,6 158,6 60,4

22°C

27°C 203,7 109,3 42,7 195,2 104,8 46,5 185,8 100,7 50,8 175,4 96,8 55,6 164,0 93,0 61,030°C 205,3 133,7 42,8 196,8 129,7 46,7 187,3 125,8 50,9 176,9 121,9 55,7 165,6 117,8 61,233°C 207,1 156,8 43,0 198,5 153,4 46,8 189,1 149,9 51,1 178,7 146,1 55,9 167,3 141,8 61,436°C 209,1 178,7 43,1 200,5 176,0 46,9 191,1 172,9 51,2 180,6 169,4 56,1 169,3 165,0 61,6

16°C

21°C 185,1 130,8 41,4 177,3 127,0 45,2 168,5 123,2 49,3 158,8 119,2 54,0 148,1 114,8 59,124°C 187,1 164,2 41,6 179,2 160,4 45,3 170,5 156,3 49,5 160,8 151,7 54,1 150,1 146,4 59,327°C 190,5 190,4 41,8 183,8 183,8 45,7 176,1 176,1 50,0 167,4 167,4 54,8 157,6 157,6 60,230°C 201,1 201,1 42,6 194,1 194,1 46,5 186,1 186,1 50,9 177,0 177,0 55,7 166,9 166,9 61,3

19°C

24°C 201,3 129,3 42,6 192,6 125,4 46,3 183,0 121,6 50,5 172,4 117,7 55,2 160,8 113,6 60,527°C 203,4 163,3 42,7 194,7 159,4 46,5 185,0 155,4 50,7 174,4 151,0 55,4 162,9 146,0 60,830°C 205,7 196,4 42,9 197,0 192,7 46,7 186,9 186,9 50,9 177,5 177,5 55,8 167,1 167,2 61,333°C 213,0 213,1 43,4 205,4 205,4 47,3 196,7 196,8 51,7 187,0 187,1 56,7 176,3 176,4 62,3

22°C

27°C 218,2 127,4 43,8 208,6 123,4 47,6 198,1 119,7 51,8 186,6 116,0 56,6 174,2 112,1 62,030°C 220,4 161,7 43,9 210,8 157,8 47,7 200,2 154,0 52,0 188,7 149,8 56,8 176,3 145,2 62,333°C 222,8 194,9 44,1 213,1 191,3 47,9 202,6 187,4 52,2 191,1 182,9 57,0 178,6 177,7 62,536°C 225,5 225,5 44,3 217,3 217,3 48,2 208,0 208,0 52,7 197,7 197,7 57,7

16°C

21°C 191,7 142,9 41,9 183,1 139,2 45,6 173,5 135,4 49,7 163,0 131,3 54,4 151,6 126,6 59,624°C 194,1 182,9 42,0 185,5 178,9 45,8 175,9 174,5 49,9 165,6 165,6 54,6 155,2 155,2 60,027°C 201,7 201,7 42,5 194,1 194,1 46,4 185,4 185,4 50,7 175,6 175,7 55,6 164,9 164,9 61,130°C 213,3 213,3 43,4 205,3 205,3 47,3 196,3 196,3 51,7 186,2 186,2 56,6 175,2 175,1 62,2

19°C

24°C 208,3 141,1 43,1 198,8 137,5 46,8 188,3 133,8 51,0 177,0 130,0 55,7 164,6 125,6 61,127°C 210,8 182,1 43,2 201,3 178,2 47,0 190,8 174,0 51,2 179,4 169,2 55,9 167,1 163,6 61,330°C 214,2 214,2 43,4 206,0 206,0 47,3 196,7 196,7 51,7 186,3 186,4 56,6 175,0 175,0 62,233°C 225,7 225,7 44,3 217,1 217,1 48,2 207,5 207,5 52,6 196,8 196,8 57,6

22°C

27°C 225,5 138,8 44,3 215,2 135,3 48,0 203,8 131,8 52,3 191,5 128,2 57,1 178,3 124,3 62,730°C 228,1 180,5 44,5 217,7 176,7 48,2 206,4 172,7 52,5 194,1 168,3 57,3 180,9 163,2 63,033°C 230,9 221,2 44,7 220,5 217,4 48,4 208,6 208,5 52,7 197,6 197,6 57,736°C 238,7 238,7 45,2 229,5 229,5 49,2

20°C 15°C 10°C 7°C 5°C 0°C -5°C -10°C -15°C

PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA8°C 244,4 45,3 218,5 42,4 194,5 39,6 180,9 38,0 172,3 37,0 151,9 34,6 133,2 32,3 116,5 30,2 110,2 29,511°C 240,6 47,7 215,2 44,6 191,7 41,8 178,4 40,1 169,9 39,1 150,0 36,5 131,9 34,2 115,6 32,1 109,6 31,414°C 236,7 50,2 211,8 47,0 188,8 44,0 175,8 42,3 167,5 41,2 148,1 38,6 130,4 36,2 114,6 34,1 108,8 33,417°C 232,8 52,9 208,4 49,5 185,8 46,3 173,1 44,5 165,0 43,4 146,1 40,7 128,9 38,3 113,6 36,1 107,9 35,420°C 228,8 55,6 204,9 52,1 182,8 48,8 170,4 46,9 162,5 45,7 144,0 42,9 127,3 40,4 112,5 38,2 107,0 37,523°C 224,7 58,5 201,3 54,8 179,6 51,2 167,5 49,3 159,8 48,0 141,8 45,1 125,7 42,5 111,3 40,3 106,0 39,526°C 220,5 61,5 197,6 57,5 176,4 53,8 164,6 51,7 157,1 50,3 139,6 47,2 123,9 44,5 110,0 42,3 105,0 41,58°C 253,6 40,1 226,5 37,7 201,1 35,4 186,8 34,1 177,6 33,2 155,9 31,1 136,1 29,2 118,0 27,4 111,3 26,711°C 249,9 42,1 223,2 39,6 198,4 37,3 184,4 35,9 175,4 35,0 154,2 32,9 134,8 30,9 117,2 29,1 110,7 28,514°C 246,1 44,2 219,9 41,6 195,6 39,2 181,8 37,8 173,0 36,9 152,3 34,7 133,4 32,8 116,3 31,0 110,0 30,417°C 242,2 46,3 216,6 43,7 192,7 41,2 179,2 39,8 170,6 38,9 150,4 36,7 132,0 34,7 115,4 33,0 109,2 32,420°C 238,3 48,6 213,1 45,9 189,7 43,3 176,6 41,8 168,2 40,9 148,4 38,7 130,5 36,7 114,3 35,0 108,4 34,423°C 234,3 51,0 209,6 48,2 186,7 45,5 173,8 44,0 165,6 43,0 146,3 40,8 128,9 38,8 113,2 37,1 107,5 36,626°C 230,2 53,5 206,0 50,5 183,6 47,7 171,0 46,2 163,0 45,2 144,2 42,9 127,2 40,9 112,1 39,3 106,5 38,78°C 258,7 37,8 230,6 35,6 204,4 33,5 189,5 32,3 179,9 31,5 157,3 29,6 136,5 27,8 117,5 26,1 110,4 25,511°C 255,0 39,6 227,4 37,4 201,7 35,3 187,1 34,1 177,7 33,3 155,6 31,4 135,3 29,6 116,7 27,9 109,8 27,314°C 251,3 41,5 224,2 39,3 198,9 37,1 184,6 35,9 175,5 35,1 153,8 33,2 134,0 31,4 115,9 29,8 109,2 29,217°C 247,5 43,6 220,9 41,3 196,1 39,1 182,1 37,8 173,1 37,0 151,9 35,1 132,6 33,4 115,0 31,9 108,5 31,320°C 243,6 45,7 217,5 43,4 193,2 41,2 179,5 39,9 170,7 39,1 150,0 37,2 131,1 35,5 114,1 34,0 107,8 33,623°C 239,7 48,0 214,1 45,6 190,2 43,3 176,8 42,0 168,2 41,2 148,0 39,3 129,6 37,7 113,0 36,3 106,9 35,926°C 235,7 50,4 210,5 47,9 187,2 45,6 174,0 44,3 165,6 43,4 145,9 41,5 128,0 40,0 111,9 38,7 106,0 38,4

FAH

FAH

200FAC FAH

FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 8,95FC/FD 10,81

4,1

Application Guide /FLEXAIR-AGU-1505-E

Outdoor air temperature

Wet bulb Dry bulb

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

24 0

00 m

3 /hN

omin

al a

irfl o

w ra

te35

000

m3 /h

Max

imum

airfl

ow

rate

43 0

00 m

3 /h

Outdoor air temp.

Ente

ring

air t

empe

ratu

reDr

y bu

lb

Min

imum

airfl

ow

ra

te24

000

m3 /h

Nom

inal

airfl

ow

rate

35 0

00 m

3 /h

Max

imum

airfl

ow

ra

te43

000

m3 /h

HEATING CAPACITY AND ABSORBED POWER

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 38 •

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 173,2 112,3 40,3 166,8 108,5 44,2 159,5 104,7 48,4 151,2 100,8 53,0 141,9 96,8 58,224°C 174,6 136,9 40,4 168,2 133,3 44,2 160,8 129,6 48,5 152,5 125,6 53,1 143,2 121,1 58,327°C 176,5 160,4 40,5 170,0 157,2 44,4 162,6 153,6 48,6 154,2 149,6 53,3 144,9 144,8 58,530°C 180,0 179,9 40,7 174,6 174,6 44,7 168,2 168,2 49,1 160,9 160,9 54,0 152,5 152,5 59,4

19°C

24°C 189,1 111,3 41,5 181,8 107,1 45,3 173,5 103,2 49,5 164,3 99,4 54,2 154,1 95,5 59,527°C 190,5 136,1 41,6 183,1 132,3 45,4 174,8 128,5 49,7 165,6 124,5 54,4 155,4 120,2 59,730°C 192,3 159,5 41,7 184,9 156,2 45,5 176,6 152,6 49,8 167,3 148,7 54,5 157,1 144,1 59,833°C 194,6 181,8 41,9 187,2 179,0 45,7 178,8 175,8 50,0 170,2 170,3 54,8 161,3 161,4 60,4

22°C

27°C 205,7 109,7 42,7 197,5 105,4 46,5 188,4 101,5 50,8 178,3 97,7 55,6 167,2 93,9 61,030°C 207,1 134,5 42,8 198,9 130,6 46,6 189,7 126,9 50,9 179,6 123,0 55,7 168,5 118,9 61,233°C 209,0 157,8 42,9 200,7 154,4 46,8 191,5 150,9 51,1 181,3 147,2 55,9 170,2 142,9 61,436°C 211,3 179,6 43,1 202,9 176,9 46,9 193,7 173,8 51,2 183,5 170,2 56,1 172,4 165,9 61,6

16°C

21°C 187,0 131,6 41,4 179,5 127,9 45,2 171,1 124,1 49,3 161,7 120,2 54,0 151,3 115,9 59,124°C 189,1 165,0 41,6 181,6 161,3 45,3 173,1 157,3 49,5 163,7 152,8 54,1 153,4 147,6 59,327°C 192,1 192,0 41,8 185,7 185,6 45,7 178,3 178,2 50,0 169,9 169,9 54,8 160,5 160,5 60,230°C 202,9 202,9 42,5 196,1 196,1 46,5 188,4 188,4 50,8 179,6 179,6 55,7 169,8 169,8 61,2

19°C

24°C 203,4 129,9 42,6 195,0 126,1 46,3 185,6 122,4 50,5 175,3 118,6 55,2 164,1 114,5 60,527°C 205,5 164,0 42,7 197,1 160,3 46,5 187,7 156,3 50,7 177,4 152,0 55,4 166,1 147,1 60,830°C 208,0 197,0 42,9 199,6 193,4 46,7 190,2 189,4 50,9 180,0 180,0 55,7 170,0 170,1 61,233°C 214,7 214,7 43,4 207,4 207,4 47,3 199,0 199,1 51,7 189,8 189,8 56,7 179,5 179,5 62,3

22°C

27°C 220,6 127,7 43,8 211,3 123,9 47,6 201,0 120,3 51,8 189,8 116,7 56,6 177,7 112,9 62,130°C 222,7 162,3 43,9 213,4 158,5 47,7 203,1 154,7 52,0 191,9 150,6 56,8 179,7 146,1 62,333°C 225,2 195,5 44,1 215,9 191,9 47,9 205,6 188,1 52,2 194,3 183,7 57,0 182,2 178,5 62,536°C 228,2 227,4 44,3 218,9 218,9 48,2 210,0 210,0 52,7 200,2 200,2 57,7 189,4 189,4 63,4

16°C

21°C 193,7 143,8 41,9 185,4 140,2 45,6 176,1 136,4 49,7 166,0 132,3 54,4 154,8 127,7 59,624°C 196,3 183,7 42,1 188,0 179,8 45,8 178,7 175,5 50,0 168,5 168,4 54,6 158,5 158,5 60,027°C 203,6 203,5 42,5 196,1 196,1 46,4 187,7 187,7 50,7 178,3 178,4 55,5 167,9 168,0 61,030°C 215,3 215,3 43,4 207,5 207,5 47,3 198,8 198,7 51,7 189,0 189,0 56,6 178,2 178,2 62,2

19°C

24°C 210,4 141,9 43,1 201,2 138,3 46,8 191,1 134,7 51,0 180,0 130,9 55,7 168,0 126,6 61,127°C 213,0 182,8 43,3 203,8 179,0 47,0 193,7 174,8 51,2 182,6 170,1 56,0 170,5 164,6 61,430°C 215,8 215,8 43,4 207,9 207,9 47,3 198,9 199,0 51,6 189,0 189,0 56,6 178,1 178,1 62,233°C 227,7 227,7 44,3 219,4 219,4 48,2 210,0 210,1 52,6 199,7 199,7 57,6 188,4 188,4 63,4

22°C

27°C 228,0 139,3 44,3 217,9 135,8 48,1 206,8 132,4 52,3 194,9 128,9 57,1 182,0 125,1 62,730°C 230,6 181,0 44,5 220,5 177,3 48,3 209,4 173,5 52,5 197,4 169,1 57,4 184,5 164,1 63,033°C 233,7 221,6 44,7 223,6 217,9 48,5 210,4 210,4 52,6 200,0 200,0 57,6 188,5 188,5 63,436°C 240,3 240,3 45,2 231,5 231,4 49,1 221,6 221,6 53,6

FAC

200FACFAC FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 8,95FC/FD 10,81

4,1

Application Guide / FLEXAIR-AGU-1505-E

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

24 0

00 m

3 /hN

omin

al a

irfl o

w ra

te35

000

m3 /h

Max

imum

airfl

ow

rate

43 0

00 m

3 /h

Outdoor air temperature

Wet bulb Dry bulb

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 39 •

20°C 15°C 10°C 7°C 5°C 0°C -5°C -10°C -15°C

PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA PT PA8°C 289,9 62,2 261,2 58,4 234,3 54,9 219,0 52,9 209,1 51,6 185,7 48,5 163,9 45,7 143,9 43,1 136,3 42,211°C 285,0 65,8 257,0 61,8 230,8 58,1 215,8 55,9 206,2 54,6 183,4 51,4 162,2 48,5 142,9 45,9 135,6 44,914°C 280,1 69,7 252,7 65,4 227,1 61,4 212,5 59,2 203,2 57,7 181,0 54,4 160,5 51,4 141,8 48,8 134,7 47,817°C 275,1 74,0 248,4 69,3 223,4 65,0 209,2 62,6 200,1 61,1 178,5 57,6 158,7 54,4 140,6 51,7 133,8 50,820°C 270,0 78,5 243,9 73,4 219,5 68,8 205,8 66,2 196,9 64,6 176,0 60,8 156,8 57,5 139,3 54,8 132,8 53,823°C 264,8 83,4 239,4 77,8 215,6 72,8 202,2 70,0 193,6 68,2 173,4 64,2 154,8 60,7 138,0 57,8 131,7 56,826°C 259,5 88,6 234,7 82,5 211,6 76,9 198,6 73,9 190,3 71,9 170,6 67,6 152,7 63,8 136,5 60,7 130,5 59,78°C 302,5 53,9 272,0 51,0 243,2 48,2 226,8 46,5 216,1 45,5 190,8 43,0 167,2 40,6 145,3 38,4 137,0 37,611°C 297,8 56,8 267,9 53,7 239,8 50,8 223,7 49,2 213,3 48,1 188,6 45,5 165,6 43,2 144,4 41,0 136,3 40,214°C 293,0 59,9 263,7 56,7 236,2 53,7 220,5 52,0 210,4 50,9 186,4 48,3 164,0 45,9 143,4 43,8 135,6 43,117°C 288,1 63,3 259,5 59,9 232,6 56,8 217,3 55,0 207,4 53,8 184,0 51,2 162,3 48,8 142,3 46,8 134,8 46,120°C 283,1 66,9 255,1 63,3 228,9 60,0 214,0 58,2 204,4 57,0 181,6 54,3 160,5 51,9 141,2 49,9 133,9 49,223°C 278,0 70,8 250,7 67,0 225,1 63,5 210,6 61,5 201,2 60,3 179,1 57,5 158,7 55,1 139,9 53,1 132,9 52,526°C 272,9 75,0 246,2 70,9 221,2 67,1 207,1 65,1 198,0 63,8 176,5 60,9 156,7 58,4 138,6 56,5 131,9 55,98°C 305,9 52,1 274,7 49,3 245,3 46,7 228,5 45,1 217,6 44,1 191,7 41,7 167,4 39,5 144,9 37,4 136,4 36,611°C 301,2 54,9 270,7 52,0 241,9 49,3 225,5 47,7 214,9 46,7 189,5 44,3 165,9 42,0 144,0 40,0 135,8 39,314°C 296,4 57,8 266,6 54,9 238,4 52,1 222,4 50,5 212,0 49,4 187,3 47,0 164,4 44,8 143,1 42,8 135,1 42,117°C 291,6 61,1 262,4 58,0 234,9 55,1 219,2 53,4 209,1 52,4 185,0 49,9 162,7 47,7 142,1 45,9 134,3 45,220°C 286,6 64,5 258,0 61,3 231,2 58,3 215,9 56,6 206,1 55,5 182,6 53,0 160,9 50,8 141,0 49,1 133,5 48,523°C 281,6 68,3 253,7 64,8 227,4 61,7 212,5 59,9 202,9 58,8 180,2 56,3 159,1 54,2 139,8 52,5 132,5 52,026°C 276,5 72,3 249,2 68,6 223,6 65,3 209,1 63,5 199,7 62,3 177,6 59,8 157,2 57,6 138,5 56,1 131,5 55,6

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 200,7 129,2 52,9 192,3 124,1 58,7 182,5 119,1 65,1 171,4 114,0 72,1 158,8 108,6 79,624°C 202,5 156,6 53,0 194,1 152,0 58,8 184,2 147,2 65,2 173,0 141,9 72,2 160,3 135,9 79,727°C 204,5 183,0 53,1 195,9 178,9 58,9 186,0 174,3 65,3 174,7 168,9 72,3 161,9 161,8 80,130°C 207,8 207,7 53,3 200,4 200,4 59,2 191,6 191,6 65,8 181,6 181,6 72,9 170,1 170,2 80,7

19°C

24°C 218,8 128,2 54,2 209,3 122,7 59,9 198,4 117,5 66,3 186,0 112,4 73,3 172,3 107,2 80,827°C 220,8 155,6 54,4 211,3 150,7 60,1 200,2 145,8 66,4 187,8 140,6 73,4 174,0 134,8 81,030°C 223,0 181,9 54,5 213,3 177,6 60,2 202,2 173,0 66,6 189,7 167,8 73,6 175,8 161,6 81,233°C 225,2 206,8 54,7 215,4 203,3 60,4 204,2 199,2 66,7 192,2 192,2 73,8 179,9 179,9 81,7

22°C

27°C 237,6 126,8 55,6 226,9 120,9 61,3 214,9 115,6 67,6 201,4 110,5 74,6 186,5 105,5 82,330°C 239,8 154,0 55,8 229,1 148,8 61,5 216,9 143,8 67,8 203,4 138,8 74,8 188,4 133,3 82,533°C 242,2 179,7 56,0 231,3 175,4 61,6 219,1 170,9 68,0 205,4 166,0 75,0 190,4 160,2 82,736°C 244,5 204,0 56,1 233,6 200,6 61,8 221,3 196,8 68,1 207,6 192,1 75,2 192,4 186,1 83,0

16°C

21°C 217,2 150,2 54,1 207,2 145,3 59,8 195,7 140,4 66,0 182,8 135,1 72,9 168,6 129,2 80,424°C 219,6 187,7 54,3 209,5 182,9 60,0 198,0 177,6 66,2 185,0 171,5 73,1 170,7 164,3 80,627°C 222,2 222,1 54,5 213,3 213,2 60,3 203,0 202,9 66,6 191,3 191,4 73,7 178,4 178,4 81,530°C 233,3 233,4 55,3 224,2 224,2 61,1 213,7 213,7 67,5 201,9 201,9 74,7 188,7 188,7 82,5

19°C

24°C 236,0 148,3 55,5 224,8 143,2 61,1 212,2 138,3 67,3 198,1 133,3 74,2 182,7 127,7 81,827°C 238,6 186,3 55,7 227,3 181,4 61,3 214,6 176,2 67,5 200,5 170,5 74,4 185,0 163,7 82,130°C 241,3 223,2 55,9 229,9 218,6 61,5 217,1 213,3 67,7 202,9 202,9 74,7 189,1 189,1 82,533°C 247,2 247,3 56,4 237,2 237,3 62,1 225,8 225,9 68,5 213,1 213,2 75,7 199,1 199,1 83,6

22°C

27°C 255,4 145,9 56,9 243,1 140,7 62,5 229,3 135,9 68,7 214,1 131,1 75,7 197,5 125,9 83,530°C 258,2 184,1 57,1 245,8 179,2 62,7 231,9 174,2 69,0 216,7 168,8 75,9 200,0 162,6 83,733°C 261,1 221,1 57,3 248,6 216,6 62,9 234,6 211,6 69,2 219,3 205,7 76,2 202,5 198,6 84,036°C 264,0 256,7 57,6 250,9 250,9 63,2 238,6 238,7 69,6 225,1 225,1 76,8 210,2 210,2 84,8

16°C

21°C 221,1 156,3 54,4 210,5 151,5 60,0 198,5 146,6 66,2 185,1 141,2 73,1 170,2 135,0 80,624°C 223,7 197,1 54,6 213,0 192,2 60,2 200,9 186,8 66,4 187,4 180,4 73,3 172,2 172,1 81,027°C 228,3 228,2 54,9 218,8 218,7 60,6 207,9 207,9 67,0 195,7 195,7 74,1 182,2 182,2 81,930°C 240,1 240,1 55,8 230,4 230,4 61,5 219,3 219,3 68,0 206,9 206,9 75,1 193,1 193,1 83,1

19°C

24°C 240,1 154,2 55,8 228,3 149,3 61,4 215,1 144,5 67,6 200,6 139,4 74,5 184,6 133,7 82,227°C 242,9 195,7 56,0 231,0 190,8 61,6 217,8 185,6 67,8 203,1 179,5 74,7 187,0 172,4 82,430°C 245,7 236,3 56,2 233,8 231,5 61,8 220,5 220,6 68,0 207,5 207,5 75,1 193,1 193,1 83,033°C 254,2 254,3 56,9 243,6 243,6 62,6 231,7 231,7 69,0 218,4 218,4 76,2 203,8 203,8 84,2

22°C

27°C 259,7 151,5 57,2 246,8 146,6 62,8 232,5 142,0 69,0 216,8 137,2 76,0 199,6 132,0 83,930°C 262,7 193,4 57,5 249,7 188,6 63,0 235,3 183,6 69,3 219,5 178,1 76,3 202,3 171,5 84,133°C 265,8 234,2 57,7 252,7 229,6 63,3 238,2 224,4 69,5 222,3 218,2 76,5 204,7 204,7 84,236°C 269,0 269,0 58,0 257,5 257,5 63,7 244,7 244,7 70,1 230,6 230,5 77,3

FAH

FAH

230FAC FAH

FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 11,34FC/FD 14,01

4,1

Application Guide /FLEXAIR-AGU-1505-E

Outdoor air temperature

Wet bulb Dry bulb

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

27 0

00 m

3 /hN

omin

al a

irfl o

w ra

te39

000

m3 /h

Max

imum

airfl

ow

rate

43 0

00 m

3 /h

Outdoor air temp.

Ente

ring

air t

empe

ratu

reDr

y bu

lb

Min

imum

airfl

ow

ra

te27

000

m3 /h

Nom

inal

airfl

ow

ra

te39

000

m3 /h

Max

imum

airfl

ow

ra

te43

000

m3 /h

HEATING CAPACITY AND ABSORBED POWER

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 40 •

25°C 30°C 35°C 40°C 45°C

PT PS PA PT PS PA PT PS PA PT PS PA PT PS PA

16°C

21°C 202,7 129,8 52,9 194,5 124,7 58,7 185,0 119,8 65,1 174,2 114,9 72,1 162,0 109,7 79,624°C 204,4 157,4 53,0 196,2 152,8 58,8 186,6 148,0 65,2 175,7 142,8 72,2 163,5 137,0 79,727°C 206,4 183,8 53,1 198,1 179,7 58,9 188,5 175,2 65,3 177,6 169,9 72,3 165,3 163,7 79,930°C 209,5 209,4 53,3 202,2 202,2 59,2 193,7 193,7 65,8 183,9 183,9 72,9 172,9 172,9 80,7

19°C

24°C 220,9 128,6 54,3 211,6 123,2 60,0 201,0 118,1 66,3 189,0 113,1 73,3 175,7 108,1 80,827°C 222,7 156,3 54,4 213,3 151,4 60,1 202,7 146,5 66,4 190,6 141,4 73,4 177,2 135,8 81,030°C 224,8 182,6 54,5 215,4 178,3 60,2 204,7 173,8 66,6 192,6 168,7 73,6 179,1 162,7 81,233°C 227,2 207,6 54,7 217,8 204,1 60,4 207,0 200,0 66,8 194,6 194,6 73,9 182,7 182,7 81,7

22°C

27°C 240,0 126,9 55,7 229,6 121,2 61,4 217,8 116,0 67,7 204,7 111,1 74,6 190,2 106,2 82,330°C 241,8 154,5 55,8 231,3 149,3 61,5 219,5 144,4 67,8 206,3 139,5 74,8 191,8 134,2 82,533°C 244,0 180,4 56,0 233,5 176,0 61,7 221,6 171,6 68,0 208,4 166,7 75,0 193,8 161,1 82,836°C 246,5 204,8 56,2 235,9 201,3 61,8 224,0 197,4 68,2 210,7 192,8 75,2 196,1 187,1 83,0

16°C

21°C 219,1 150,6 54,2 209,4 145,8 59,8 198,3 141,0 66,1 185,9 135,9 73,0 172,1 130,2 80,424°C 221,5 188,3 54,3 211,7 183,5 60,0 200,6 178,3 66,2 188,1 172,5 73,1 174,3 165,6 80,627°C 224,0 223,8 54,5 215,2 215,1 60,3 205,1 205,1 66,7 193,8 193,8 73,7 181,3 181,3 81,530°C 235,1 235,2 55,3 226,2 226,2 61,1 215,9 216,0 67,5 204,5 204,5 74,6 191,7 191,8 82,5

19°C

24°C 238,0 148,5 55,5 227,1 143,6 61,1 214,9 138,7 67,4 201,3 133,8 74,3 186,4 128,5 81,927°C 240,4 186,8 55,7 229,5 181,9 61,3 217,2 176,8 67,6 203,6 171,2 74,5 188,6 164,8 82,130°C 243,2 223,8 55,9 232,2 219,2 61,5 219,9 214,0 67,8 205,7 205,7 74,8 192,2 192,3 82,533°C 248,9 249,0 56,4 239,1 239,2 62,1 228,0 228,1 68,5 215,7 215,7 75,7 202,1 202,1 83,6

22°C

27°C 257,6 145,8 57,0 245,6 140,8 62,6 232,2 136,0 68,8 217,5 131,4 75,8 201,5 126,5 83,630°C 260,1 184,4 57,2 248,1 179,5 62,8 234,7 174,6 69,0 219,9 169,4 76,0 203,8 163,4 83,833°C 263,0 221,5 57,4 250,9 217,0 63,0 237,4 212,1 69,3 222,6 206,4 76,3 206,4 199,6 84,136°C 266,2 257,3 57,6 254,0 253,3 63,2 240,9 240,9 69,6 227,7 227,7 76,8 213,2 213,2 84,8

16°C

21°C 223,1 156,7 54,4 212,8 152,0 60,0 201,2 147,2 66,3 188,3 142,0 73,1 174,0 136,1 80,724°C 225,7 197,7 54,6 215,4 192,9 60,2 203,7 187,6 66,5 190,7 181,4 73,4 176,4 174,1 80,927°C 230,1 230,0 54,9 220,8 220,7 60,6 210,2 210,2 67,0 198,3 198,3 74,1 185,1 185,2 81,930°C 242,0 242,1 55,8 232,5 232,5 61,6 221,7 221,7 68,0 209,7 209,7 75,1 196,4 196,3 83,1

19°C

24°C 242,1 154,4 55,8 230,7 149,6 61,4 218,0 144,9 67,6 203,9 140,0 74,5 188,4 134,5 82,227°C 244,8 196,2 56,0 233,4 191,3 61,6 220,6 186,1 67,8 206,4 180,3 74,8 190,9 173,5 82,530°C 247,8 236,9 56,3 236,3 232,1 61,8 223,0 223,0 68,1 210,3 210,3 75,2 196,3 196,4 83,033°C 256,0 256,1 56,9 245,6 245,7 62,6 234,0 234,0 69,0 221,1 221,1 76,2 206,9 206,9 84,2

22°C

27°C 262,0 151,4 57,3 249,4 146,6 62,9 235,6 142,0 69,1 220,3 137,5 76,1 203,7 132,5 84,030°C 264,7 193,7 57,5 252,1 188,9 63,1 238,2 184,0 69,3 222,9 178,6 76,4 206,3 172,3 84,233°C 267,8 234,6 57,7 255,2 230,0 63,3 241,2 224,9 69,6 225,8 218,9 76,6 208,2 208,2 84,336°C 270,8 270,8 58,0 259,5 259,5 63,7 247,0 247,0 70,2 233,3 233,2 77,4 218,3 218,2 85,5

FAC

230FACFAC FAH

PT :PS :PA :xxx :

FC/FH 0,3

FC/FD 0,5

FC/FH 11,34FC/FD 14,01

4,1

Application Guide / FLEXAIR-AGU-1505-E

Ent

erin

g ai

r tem

pera

ture

Min

imum

airfl

ow

rate

27 0

00 m

3 /hN

omin

al a

irfl o

w ra

te39

000

m3 /h

Max

imum

airfl

ow

rate

43 0

00 m

3 /h

Outdoor air temperature

Wet bulb Dry bulb

COOLING CAPACITY AND ABSORBED POWER

Cooling only Heat pump

Supply fan aborbed power(kW)

Absorbed power by outdoor fan(kW)

Absorbed power by control device(kW)

Gross total cooling/heating capacity in kWSensible heating capacity in kWCompressor absorbed powerData according to Eurovent standard conditions

5- STANDARD UNITS PERFORMANCES

• 41 •

085 100 120

FAC

15000 18500 20500

250 250 250

30 74 62,3 3,47 72,7 3,10 85,2 3,05

25 47 41,7 3,67 49,3 3,37 57,3 3,34

20 21 39,9 3,44 47,1 3,19 55,7 3,23

FAH

15000 18500 20500

250 250 250

30 74 61,5 3,44 71,8 3,06 83,9 3,01

25 47 41,3 3,63 48,9 3,33 56,7 3,30

20 21 39,6 3,41 46,7 3,16 55,2 3,19

150 170 200 230

FAC

28000 30000 35000 39000

300 350 350 350

30 74 106,1 3,35 117,5 3,43 136,7 3,49 165,0 3,54

25 47 67,4 3,55 74,6 3,82 86,9 3,82 104,8 3,88

20 21 53,1 4,09 50,7 3,75 57,8 3,72 72,4 3,81

FAH

28000 30000 35000 39000

300 350 350 350

30 74 102,1 3,26 115,4 3,40 134,7 3,46 162,9 3,51

25 47 64,9 3,58 73,3 3,79 85,6 3,77 103,5 3,85

20 21 52,6 4,03 50,4 3,72 57,3 3,69 71,9 3,78

Application Guide /FLEXAIR-AGU-1505-E

PERFORMANCES AT PART LOAD OPERATION (*)Eurovent conditions(*) Part load data according to ANSI/ARI Standard 340/360 conditionsCooling mode : Outdoor temperature = 29,7 °C DB / Indoor temperature : 26,7 °C DB / 19,4 °C WBHeating mode : Outdoor temperature = 7 °C DB / Indoor temperature = 6 °C WB / 20 °C DB

Nominal airfl ow rate at full load (m3/h)

Nominal ESP at full load (Pa)

Outdoor temperature*(°C)

Part load ratio*(%)

Cooling capacity(Kw) EER

Cooling capacity(Kw) EER

Cooling capacity(Kw) EER

Nominal airfl ow rate at full load (m3/h)

Nominal ESP at full load (Pa)

Outdoor temperature*(°C)

Part load ratio*(%)

Cooling capacity(Kw) EER

Cooling capacity(Kw) EER

Cooling capacity(Kw) EER

Nominal airfl ow rate at full load (m3/h)

Nominal ESP at full load (Pa)

Outdoor temperature*(°C)

Part load ratio*(%)

Cooling capacity

(Kw) EER

Cooling capacity

(Kw) EER

Cooling capacity

(Kw) EER

Cooling capacity

(Kw) EER

Nominal airfl ow rate at full load (m3/h)

Nominal ESP at full load (Pa)

Outdoor temperature*(°C)

Part load ratio*(%)

Cooling capacity

(Kw) EER

Cooling capacity

(Kw) EER

Cooling capacity

(Kw) EER

Cooling capacity

(Kw) EER

5.2- PERFORMANCES AT PART LOAD OPERATION

5- STANDARD UNITS PERFORMANCES

• 42 •

FAC FAHFAG FAM

FAC/FAH 80-120

F085

F100

F120

100

150

200

250

300

350

400

450

500

550

600

650

700

750

800

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

1200

0LP

1,19

LP1,

42LP

1,63

LP1,

86LP

2,11

LP2,

36LP

2,62

LP2,

90LP

3,19

LP3,

49LP

3,81

LP4,

14LP

4,46

LP4,

77LP

5,08

1300

0LP

1,39

LP1,

63LP

1,87

LP2,

11LP

2,36

LP2,

62LP

2,90

LP3,

18LP

3,48

LP3,

79LP

4,11

LP4,

44LP

4,79

LP5,

15LP

5,51

1400

0LP

1,63

LP1,

87LP

2,14

LP2,

39LP

2,65

LP2,

92LP

3,21

LP3,

50LP

3,81

LP4,

12LP

4,45

LP4,

79LP

5,14

LP5,

51H

P5,

9515

000

LP1,

89LP

2,15

LP2,

43LP

2,71

LP2,

98LP

3,26

LP3,

56LP

3,86

LP4,

18LP

4,51

LP4,

84LP

5,18

LP5,

54H

P6,

03H

P6,

3916

000

LP2,

20LP

2,47

LP2,

75LP

3,05

LP3,

35LP

3,64

LP3,

95LP

4,26

LP4,

59LP

4,92

LP5,

27LP

5,63

HP

6,16

HP

6,51

HP

6,87

1700

0LP

2,54

LP2,

82LP

3,12

LP3,

43LP

3,76

LP4,

07LP

4,38

LP4,

71LP

5,04

LP5,

39H

P5,

92H

P6,

29H

P6,

67H

P7,

05H

P7,

4218

000

LP2,

93LP

3,21

LP3,

52LP

3,85

LP4,

19LP

4,54

LP4,

86LP

5,20

LP5,

55H

P6,

06H

P6,

43H

P6,

81H

P7,

20H

P7,

59H

P8,

0019

000

LP3,

36LP

3,66

LP3,

97LP

4,31

LP4,

67LP

5,03

LP5,

40H

P5,

88H

P6,

24H

P6,

60H

P6,

98H

P7,

37H

P7,

77H

P8,

18H

P8,

6020

000

LP3,

84LP

4,15

LP4,

48LP

4,83

HP

5,34

HP

5,70

HP

6,07

HP

6,45

HP

6,83

HP

7,21

HP

7,60

HP

7,99

HP

8,40

HP

8,82

HP

9,25

2100

0LP

4,36

LP4,

69H

P5,

23H

P5,

57H

P5,

93H

P6,

29H

P6,

67H

P7,

06H

P7,

47H

P7,

87H

P8,

27H

P8,

67H

P9,

09H

P9,

52H

P9,

9622

000

HP

5,16

HP

5,49

HP

5,84

HP

6,20

HP

6,56

HP

6,94

HP

7,33

HP

7,73

HP

8,15

HP

8,58

HP

9,00

HP

9,42

HP

9,84

HP

10,2

823

000

HP

5,81

HP

6,15

HP

6,51

HP

6,88

HP

7,26

HP

7,65

HP

8,05

HP

8,46

HP

8,88

HP

9,32

HP

9,78

HP

10,2

2

FAC/FAH 150-170

F150

F170

100

150

200

250

300

350

400

450

500

550

600

650

700

750

800

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

1800

0LP

1,70

LP2,

04LP

2,37

LP2,

71LP

3,07

LP3,

45LP

3,84

LP4,

25LP

4,68

LP5,

13LP

5,60

LP6,

09LP

6,58

LP7,

04LP

7,51

1900

0LP

1,89

LP2,

24LP

2,59

LP2,

94LP

3,31

LP3,

69LP

4,10

LP4,

52LP

4,95

LP5,

40LP

5,88

LP6,

37LP

6,89

LP7,

42LP

7,92

2000

0LP

2,10

LP2,

45LP

2,84

LP3,

19LP

3,57

LP3,

96LP

4,37

LP4,

81LP

5,25

LP5,

70LP

6,18

LP6,

68LP

7,20

LP7,

74LP

8,29

2100

0LP

2,33

LP2,

69LP

3,08

LP3,

47LP

3,85

LP4,

25LP

4,67

LP5,

11LP

5,57

LP6,

03LP

6,52

LP7,

02LP

7,54

LP8,

08LP

8,64

2200

0LP

2,58

LP2,

95LP

3,35

LP3,

76LP

4,16

LP4,

57LP

5,00

LP5,

44LP

5,91

LP6,

39LP

6,88

LP7,

39LP

7,91

LP8,

46H

P9,

1723

000

LP2,

85LP

3,22

LP3,

63LP

4,07

LP4,

49LP

4,91

LP5,

35LP

5,80

LP6,

28LP

6,77

LP7,

28LP

7,79

LP8,

32H

P9,

08H

P9,

6124

000

LP3,

14LP

3,53

LP3,

95LP

4,39

LP4,

85LP

5,28

LP5,

73LP

6,19

LP6,

67LP

7,17

LP7,

69LP

8,23

HP

9,03

HP

9,55

HP

10,0

825

000

LP3,

46LP

3,85

LP4,

28LP

4,74

LP5,

21LP

5,67

LP6,

13LP

6,61

LP7,

10LP

7,61

LP8,

13H

P8,

94H

P9,

50H

P10

,05

HP

10,6

026

000

LP3,

80LP

4,21

LP4,

64LP

5,11

LP5,

60LP

6,10

LP6,

57LP

7,06

LP7,

56LP

8,08

HP

8,86

HP

9,41

HP

9,98

HP

10,5

6H

P11

,14

2700

0LP

4,17

LP4,

59LP

5,03

LP5,

51LP

6,01

LP6,

53LP

7,04

LP7,

53LP

8,05

HP

8,80

HP

9,34

HP

9,91

HP

10,4

8H

P11

,07

HP

11,6

828

000

LP4,

57LP

5,00

LP5,

45LP

5,94

LP6,

45LP

6,99

LP7,

53LP

8,04

HP

8,78

HP

9,31

HP

9,87

HP

10,4

4H

P11

,02

HP

11,6

2H

P12

,24

2900

0LP

4,99

LP5,

44LP

5,91

LP6,

40LP

6,93

LP7,

47H

P8,

21H

P8,

77H

P9,

32H

P9,

86H

P10

,42

HP

11,0

0H

P11

,59

HP

12,2

0H

P12

,83

3000

0LP

5,45

LP5,

92LP

6,39

LP6,

89LP

7,43

HP

8,20

HP

8,74

HP

9,30

HP

9,89

HP

10,4

4H

P11

,01

HP

11,6

0H

P12

,20

HP

12,8

2H

P13

,45

3100

0LP

5,94

LP6,

42LP

6,91

LP7,

42H

P8,

22H

P8,

75H

P9,

30H

P9,

87H

P10

,46

HP

11,0

6H

P11

,64

HP

12,2

4H

P12

,85

HP

13,4

8H

P14

,12

3200

0LP

6,46

LP6,

96H

P7,

76H

P8,

28H

P8,

80H

P9,

34H

P9,

89H

P10

,47

HP

11,0

7H

P11

,70

HP

12,3

1H

P12

,91

HP

13,5

3H

P14

,17

HP

14,8

233

000

LP7,

02H

P7,

85H

P8,

35H

P8,

88H

P9,

41H

P9,

96H

P10

,53

HP

11,1

1H

P11

,72

HP

12,3

5H

P13

,01

HP

13,6

3H

P14

,26

HP

14,9

0H

P15

,56

3400

0H

P7,

97H

P8,

46H

P8,

97H

P9,

51H

P10

,06

HP

10,6

2H

P11

,20

HP

11,8

0H

P12

,41

HP

13,0

5H

P13

,71

HP

14,3

9H

P15

,02

HP

15,6

835

000

HP

8,61

HP

9,11

HP

9,63

HP

10,1

8H

P10

,75

HP

11,3

2H

P11

,91

HP

12,5

2H

P13

,14

HP

13,7

9H

P14

,46

HP

15,1

5

FAC/FAH 200-230

F200

F230

100

150

200

250

300

350

400

450

500

550

600

650

700

750

800

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

2400

0LP

2,37

LP2,

79LP

3,23

LP3,

67LP

4,16

LP4,

67LP

5,16

LP5,

67LP

6,21

LP6,

76LP

7,34

LP7,

94LP

8,52

HP

9,11

HP

9,68

2500

0LP

2,59

LP3,

01LP

3,48

LP3,

91LP

4,41

LP4,

93LP

5,46

LP5,

98LP

6,52

LP7,

08LP

7,66

LP8,

27LP

8,90

HP

9,53

HP

10,1

026

000

LP2,

81LP

3,24

LP3,

72LP

4,18

LP4,

67LP

5,20

LP5,

76LP

6,30

LP6,

86LP

7,43

LP8,

01LP

8,63

HP

9,30

HP

9,96

HP

10,5

527

000

LP3,

05LP

3,50

LP3,

98LP

4,48

LP4,

96LP

5,50

LP6,

06LP

6,65

LP7,

21LP

7,79

LP8,

39H

P9,

01H

P9,

65H

P10

,31

HP

11,0

028

000

LP3,

31LP

3,77

LP4,

25LP

4,80

LP5,

27LP

5,81

LP6,

39LP

6,99

LP7,

59LP

8,18

LP8,

79H

P9,

40H

P10

,03

HP

10,7

0H

P11

,39

2900

0LP

3,59

LP4,

07LP

4,55

LP5,

10LP

5,62

LP6,

15LP

6,73

LP7,

34LP

7,97

LP8,

59H

P9,

18H

P9,

80H

P10

,45

HP

11,1

1H

P11

,80

3000

0LP

3,88

LP4,

38LP

4,87

LP5,

42LP

5,98

LP6,

51LP

7,09

LP7,

71LP

8,36

HP

8,99

HP

9,60

HP

10,2

3H

P10

,88

HP

11,5

5H

P12

,25

3100

0LP

4,21

LP4,

71LP

5,22

LP5,

76LP

6,37

LP6,

91LP

7,48

LP8,

11H

P8,

76H

P9,

40H

P10

,06

HP

10,6

9H

P11

,35

HP

12,0

3H

P12

,72

3200

0LP

4,55

LP5,

06LP

5,59

LP6,

13LP

6,74

LP7,

33LP

7,90

LP8,

52H

P9,

18H

P9,

83H

P10

,50

HP

11,1

8H

P11

,84

HP

12,5

2H

P13

,23

3300

0LP

4,92

LP5,

43LP

5,98

LP6,

53LP

7,13

LP7,

79LP

8,36

HP

9,01

HP

9,64

HP

10,2

9H

P10

,97

HP

11,6

7H

P12

,36

HP

13,0

5H

P13

,76

3400

0LP

5,31

LP5,

82LP

6,39

LP6,

95LP

7,56

HP

8,30

HP

8,88

HP

9,48

HP

10,1

2H

P10

,77

HP

11,4

6H

P12

,17

HP

12,9

0H

P13

,61

3500

0LP

5,73

LP6,

24LP

6,82

LP7,

40H

P8,

10H

P8,

74H

P9,

38H

P9,

99H

P10

,62

HP

11,2

9H

P11

,98

HP

12,6

9H

P13

,43

3600

0LP

6,17

LP6,

67LP

7,28

HP

7,95

HP

8,56

HP

9,22

HP

9,90

HP

10,5

2H

P11

,16

HP

11,8

3H

P12

,53

HP

13,2

537

000

LP6,

64LP

7,14

HP

7,82

HP

8,44

HP

9,06

HP

9,72

HP

10,4

1H

P11

,08

HP

11,7

3H

P12

,40

HP

13,1

138

000

LP7,

13H

P7,

72H

P8,

32H

P8,

95H

P9,

58H

P10

,25

HP

10,9

5H

P11

,67

HP

12,3

3H

P13

,01

3900

0H

P7,

68H

P8,

24H

P8,

84H

P9,

48H

P10

,14

HP

10,8

1H

P11

,51

HP

12,2

6H

P12

,96

4000

0H

P8,

21H

P8,

78H

P9,

39H

P10

,05

HP

10,7

2H

P11

,40

HP

12,1

1H

P12

,86

4100

0H

P8,

76H

P9,

35H

P9,

96H

P10

,64

HP

11,3

2H

P12

,02

4200

0H

P9,

35H

P9,

95H

P10

,56

HP

11,2

6H

P11

,96

4300

0H

P9,

97H

P10

,58

HP

11,2

1

Application Guide / FLEXAIR-AGU-1505-E

Cooling only Heat pumpCooling only with gas fi red heating Heat pump rooftop with gas fi red heating

Airfl

ow

Airfl

ow

Airfl

ow

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

6.- FAN PERFORMANCES

6.1- INDOOR SUPPLY FAN PERFORMANCES

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

LP HPLow Pressure High Pressure

• 43 •

FAC FAHFAG FAM

FAG/FAM 80-120

F085

F100

F120

100

150

200

250

300

350

400

450

500

550

600

650

700

750

800

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

1200

0LP

1,56

LP1,

78LP

2,02

LP2,

27LP

2,53

LP2,

81LP

3,09

LP3,

39LP

3,70

LP4,

03LP

4,36

LP4,

66LP

4,98

LP5,

30LP

5,63

1300

0LP

1,86

LP2,

10LP

2,35

LP2,

61LP

2,89

LP3,

17LP

3,46

LP3,

77LP

4,09

LP4,

43LP

4,77

LP5,

13LP

5,50

LP5,

83H

P6,

1914

000

LP2,

21LP

2,46

LP2,

72LP

3,00

LP3,

28LP

3,59

LP3,

89LP

4,21

LP4,

54LP

4,88

LP5,

24LP

5,60

HP

6,04

HP

6,40

HP

6,76

1500

0LP

2,60

LP2,

87LP

3,15

LP3,

44LP

3,74

LP4,

05LP

4,37

LP4,

71LP

5,05

LP5,

40LP

5,76

HP

6,24

HP

6,60

HP

6,97

HP

7,35

1600

0LP

3,04

LP3,

34LP

3,63

LP3,

93LP

4,25

LP4,

57LP

4,91

LP5,

26LP

5,62

HP

6,15

HP

6,50

HP

6,86

HP

7,23

HP

7,61

HP

8,00

1700

0LP

3,54

LP3,

86LP

4,17

LP4,

49LP

4,82

LP5,

16LP

5,51

HP

6,04

HP

6,42

HP

6,80

HP

7,17

HP

7,54

HP

7,93

HP

8,31

HP

8,71

1800

0LP

4,10

LP4,

45LP

4,78

LP5,

12LP

5,46

HP

5,96

HP

6,33

HP

6,71

HP

7,09

HP

7,49

HP

7,90

HP

8,30

HP

8,69

HP

9,10

HP

9,51

1900

0LP

4,73

LP5,

10H

P5,

59H

P5,

94H

P6,

30H

P6,

67H

P7,

05H

P7,

44H

P7,

84H

P8,

25H

P8,

67H

P9,

10H

P9,

54H

P9,

96H

P10

,38

2000

0H

P5,

56H

P5,

93H

P6,

31H

P6,

69H

P7,

06H

P7,

45H

P7,

84H

P8,

25H

P8,

66H

P9,

09H

P9,

52H

P9,

96H

P10

,42

HP

10,8

821

000

HP

6,32

HP

6,70

HP

7,10

HP

7,51

HP

7,91

HP

8,30

HP

8,71

HP

9,13

HP

9,56

HP

10,0

0H

P10

,45

2200

0H

P7,

17H

P7,

56H

P7,

97H

P8,

40H

P8,

83H

P9,

24H

P9,

67H

P10

,10

HP

10,5

523

000

HP

8,09

HP

8,50

HP

8,93

HP

9,37

HP

9,83

HP

10,2

7no

kit

0,00

FAG/FAM 150-170

F150

F170

100

150

200

250

300

350

400

450

500

550

600

650

700

750

800

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

1800

0LP

2,19

LP2,

52LP

2,87

LP3,

23LP

3,62

LP4,

02LP

4,44

LP4,

87LP

5,33

LP5,

82LP

6,32

LP6,

78LP

7,25

LP7,

72LP

8,21

1900

0LP

2,46

LP2,

80LP

3,16

LP3,

54LP

3,94

LP4,

35LP

4,77

LP5,

22LP

5,69

LP6,

17LP

6,68

LP7,

21LP

7,73

LP8,

22H

P8,

7620

000

LP2,

75LP

3,11

LP3,

48LP

3,87

LP4,

28LP

4,71

LP5,

15LP

5,60

LP6,

07LP

6,57

LP7,

08LP

7,61

LP8,

17LP

8,74

HP

9,27

2100

0LP

3,06

LP3,

45LP

3,84

LP4,

24LP

4,65

LP5,

09LP

5,55

LP6,

01LP

6,49

LP7,

00LP

7,52

LP8,

06LP

8,62

HP

9,27

HP

9,81

2200

0LP

3,41

LP3,

82LP

4,22

LP4,

63LP

5,06

LP5,

51LP

5,98

LP6,

46LP

6,96

LP7,

46LP

7,99

LP8,

54H

P9,

24H

P9,

78H

P10

,34

2300

0LP

3,78

LP4,

22LP

4,63

LP5,

06LP

5,51

LP5,

97LP

6,45

LP6,

94LP

7,45

LP7,

97LP

8,51

HP

9,26

HP

9,80

HP

10,3

4H

P10

,91

2400

0LP

4,19

LP4,

65LP

5,08

LP5,

53LP

5,98

LP6,

46LP

6,95

LP7,

46LP

7,99

LP8,

52H

P9,

32H

P9,

85H

P10

,39

HP

10,9

5H

P11

,52

2500

0LP

4,63

LP5,

10LP

5,57

LP6,

03LP

6,50

LP6,

99LP

7,49

LP8,

01LP

8,55

HP

9,37

HP

9,93

HP

10,4

7H

P11

,02

HP

11,5

9H

P12

,17

2600

0LP

5,11

LP5,

60LP

6,10

LP6,

57LP

7,06

LP7,

56LP

8,08

HP

8,86

HP

9,41

HP

9,98

HP

10,5

6H

P11

,14

HP

11,7

1H

P12

,28

HP

12,8

727

000

LP5,

63LP

6,13

LP6,

66LP

7,15

LP7,

65LP

8,17

HP

8,93

HP

9,48

HP

10,0

4H

P10

,62

HP

11,2

2H

P11

,83

HP

12,4

3H

P13

,02

HP

13,6

228

000

LP6,

18LP

6,71

LP7,

25LP

7,78

HP

8,50

HP

9,03

HP

9,58

HP

10,1

4H

P10

,71

HP

11,3

1H

P11

,91

HP

12,5

4H

P13

,17

HP

13,8

1H

P14

,42

2900

0LP

6,78

LP7,

32LP

7,88

HP

8,62

HP

9,17

HP

9,71

HP

10,2

7H

P10

,84

HP

11,4

3H

P12

,04

HP

12,6

6H

P13

,29

HP

13,9

4H

P14

,61

HP

15,2

730

000

LP7,

43H

P8,

19H

P8,

73H

P9,

30H

P9,

88H

P10

,44

HP

11,0

1H

P11

,60

HP

12,2

0H

P12

,82

HP

13,4

5H

P14

,10

HP

14,7

6H

P15

,44

HP

16,1

331

000

HP

8,36

HP

8,89

HP

9,45

HP

10,0

2H

P10

,62

HP

11,2

1H

P11

,80

HP

12,4

0H

P13

,01

HP

13,6

4H

P14

,29

HP

14,9

5H

P15

,63

HP

16,3

232

000

HP

9,09

HP

9,64

HP

10,2

1H

P10

,80

HP

11,4

1H

P12

,04

HP

12,6

4H

P13

,25

HP

13,8

8H

P14

,52

HP

15,1

8H

P15

,86

3300

0H

P9,

87H

P10

,43

HP

11,0

2H

P11

,62

HP

12,2

5H

P12

,90

HP

13,5

3H

P14

,15

HP

14,7

9H

P15

,45

3400

0H

P10

,70

HP

11,2

8H

P11

,88

HP

12,4

9H

P13

,14

HP

13,8

0H

P14

,47

HP

15,1

1H

P15

,77

3500

0H

P11

,58

HP

12,1

8H

P12

,79

HP

13,4

2H

P14

,08

HP

14,7

6H

P15

,45

FAG/FAM 200-230

F200

F230

100

150

200

250

300

350

400

450

500

550

600

650

700

750

800

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

2400

0LP

2,98

LP3,

40LP

3,87

LP4,

37LP

4,87

LP5,

37LP

5,89

LP6,

43LP

6,99

LP7,

58LP

8,18

LP8,

77H

P9,

34H

P9,

92H

P10

,51

2500

0LP

3,25

LP3,

70LP

4,17

LP4,

68LP

5,22

LP5,

73LP

6,26

LP6,

82LP

7,39

LP7,

98LP

8,60

HP

9,26

HP

9,83

HP

10,4

1H

P11

,01

2600

0LP

3,55

LP4,

03LP

4,50

LP5,

02LP

5,57

LP6,

12LP

6,66

LP7,

23LP

7,81

LP8,

41H

P9,

07H

P9,

73H

P10

,35

HP

10,9

4H

P11

,55

2700

0LP

3,87

LP4,

38LP

4,85

LP5,

38LP

5,94

LP6,

53LP

7,09

LP7,

66LP

8,26

LP8,

87H

P9,

51H

P10

,17

HP

10,8

5H

P11

,51

HP

12,1

228

000

LP4,

21LP

4,75

LP5,

23LP

5,76

LP6,

34LP

6,94

LP7,

54LP

8,13

LP8,

74H

P9,

34H

P9,

98H

P10

,64

HP

11,3

3H

P12

,04

HP

12,7

329

000

LP4,

58LP

5,13

LP5,

65LP

6,18

LP6,

76LP

7,38

LP8,

01LP

8,62

HP

9,21

HP

9,84

HP

10,4

8H

P11

,15

HP

11,8

4H

P12

,56

HP

13,3

030

000

LP4,

98LP

5,54

LP6,

09LP

6,62

LP7,

21LP

7,84

LP8,

49H

P9,

12H

P9,

73H

P10

,36

HP

11,0

2H

P11

,69

HP

12,3

9H

P13

,11

HP

13,8

631

000

LP5,

40LP

5,97

LP6,

56LP

7,10

LP7,

70LP

8,34

HP

8,98

HP

9,63

HP

10,2

8H

P10

,92

HP

11,5

9H

P12

,27

HP

12,9

7H

P13

,70

3200

0LP

5,86

LP6,

43LP

7,07

LP7,

61LP

8,21

HP

8,87

HP

9,51

HP

10,1

7H

P10

,86

HP

11,5

1H

P12

,19

HP

12,8

8H

P13

,59

3300

0LP

6,34

LP6,

93LP

7,57

LP8,

16H

P8,

81H

P9,

42H

P10

,07

HP

10,7

4H

P11

,43

HP

12,1

4H

P12

,82

HP

13,5

234

000

LP6,

86LP

7,45

LP8,

11H

P8,

78H

P9,

38H

P10

,01

HP

10,6

6H

P11

,34

HP

12,0

5H

P12

,78

HP

13,4

935

000

LP7,

40H

P8,

10H

P8,

74H

P9,

38H

P9,

99H

P10

,62

HP

11,2

9H

P11

,98

HP

12,6

9H

P13

,43

3600

0H

P8,

06H

P8,

67H

P9,

33H

P10

,01

HP

10,6

3H

P11

,28

HP

11,9

5H

P12

,65

HP

13,3

837

000

HP

8,65

HP

9,29

HP

9,96

HP

10,6

7H

P11

,31

HP

11,9

6H

P12

,65

HP

13,3

638

000

HP

9,29

HP

9,93

HP

10,6

2H

P11

,34

HP

12,0

2H

P12

,69

3900

0H

P9,

96H

P10

,62

HP

11,3

2H

P12

,05

HP

12,7

740

000

HP

10,6

6H

P11

,34

HP

12,0

5H

P12

,80

4100

0H

P11

,40

HP

12,1

042

000

HP

12,1

843

000

LP HP

Application Guide /FLEXAIR-AGU-1505-E

6- FAN PERFORMANCESCooling only Heat pumpCooling only with gas fi red heating Heat pump rooftop with gas fi red heating

Low Pressure High Pressure

Airfl

ow

Airfl

ow

Airfl

ow

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

No

kit

• 44 •

FAC FAHFAG FAM

FAC/FAH/FAG/FAM 85-120F0

85F1

00F1

2015

020

025

030

035

040

045

050

055

060

0K

ITPa

(kw

)K

ITPa

(kw

)K

ITPa

(kw

)K

ITPa

(kw

)K

ITPa

(kw

)K

ITPa

(kw

)K

ITPa

(kw

)K

ITPa

(kw

)K

ITPa

(kw

)K

ITPa

(kw

)12

000

LP1,

02LP

1,26

LP1,

51LP

1,76

LP2,

04LP

2,33

LP2,

61LP

2,91

LP3,

23LP

3,56

1300

0LP

1,13

LP1,

37LP

1,64

LP1,

91LP

2,19

LP2,

48LP

2,79

LP3,

10LP

3,42

LP3,

7514

000

LP1,

25LP

1,51

LP1,

78LP

2,07

LP2,

36LP

2,66

LP2,

97LP

3,30

LP3,

64LP

3,97

1500

0LP

1,39

LP1,

67LP

1,93

LP2,

23LP

2,55

LP2,

86LP

3,17

LP3,

51LP

3,85

LP4,

2216

000

LP1,

55LP

1,82

LP2,

12LP

2,41

LP2,

73LP

3,07

LP3,

40LP

3,74

LP4,

09LP

4,46

1700

0LP

1,72

LP2,

00LP

2,31

LP2,

62LP

2,93

LP3,

28LP

3,64

LP4,

00LP

4,36

LP4,

7318

000

LP1,

91LP

2,21

LP2,

51LP

2,86

LP3,

16LP

3,51

LP3,

88LP

4,27

LP4,

64LP

5,03

1900

0LP

2,14

LP2,

43LP

2,74

LP3,

08LP

3,44

LP3,

77LP

4,14

LP4,

53LP

4,94

LP5,

3520

000

LP2,

38LP

2,67

LP3,

00LP

3,33

LP3,

70LP

4,07

LP4,

43LP

4,82

LP5,

24LP

5,68

2100

0LP

2,65

LP2,

94LP

3,27

LP3,

62LP

3,99

LP4,

39LP

4,76

LP5,

15LP

5,57

HP

6,00

2200

0LP

2,94

LP3,

24LP

3,57

LP3,

94LP

4,30

LP4,

70LP

5,14

LP5,

52H

P5,

95H

P6,

3723

000

LP3,

26LP

3,58

LP3,

89LP

4,27

LP4,

66LP

5,05

HP

5,53

HP

5,95

HP

6,35

HP

6,77

FAC/FAH/FAG/FAM 150-170

F150

F170

150

200

250

300

350

400

450

500

550

600

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

1800

0LP

1,61

LP1,

98LP

2,36

LP2,

75LP

3,16

LP3,

60LP

4,03

LP4,

48LP

4,97

LP5,

4719

000

LP1,

74LP

2,11

LP2,

51LP

2,91

LP3,

33LP

3,77

LP4,

23LP

4,68

LP5,

17LP

5,67

2000

0LP

1,88

LP2,

25LP

2,66

LP3,

08LP

3,50

LP3,

95LP

4,42

LP4,

90LP

5,39

LP5,

9021

000

LP2,

02LP

2,40

LP2,

82LP

3,26

LP3,

69LP

4,15

LP4,

62LP

5,13

LP5,

63LP

6,14

2200

0LP

2,16

LP2,

57LP

2,98

LP3,

44LP

3,90

LP4,

36LP

4,84

LP5,

35LP

5,88

LP6,

4123

000

LP2,

33LP

2,76

LP3,

17LP

3,63

LP4,

12LP

4,59

LP5,

08LP

5,59

LP6,

12LP

6,68

2400

0LP

2,51

LP2,

94LP

3,37

LP3,

83LP

4,33

LP4,

83LP

5,33

LP5,

85LP

6,39

LP6,

9525

000

LP2,

70LP

3,13

LP3,

60LP

4,04

LP4,

55LP

5,08

LP5,

60LP

6,13

LP6,

67LP

7,24

2600

0LP

2,90

LP3,

34LP

3,84

LP4,

28LP

4,78

LP5,

32LP

5,88

LP6,

42LP

6,98

LP7,

5527

000

LP3,

12LP

3,57

LP4,

06LP

4,55

LP5,

04LP

5,58

LP6,

15LP

6,73

LP7,

30LP

7,88

2800

0LP

3,35

LP3,

82LP

4,30

LP4,

84LP

5,32

LP5,

86LP

6,44

LP7,

04LP

7,64

LP8,

2329

000

LP3,

60LP

4,08

LP4,

57LP

5,11

LP5,

63LP

6,16

LP6,

74LP

7,35

LP7,

99LP

8,60

3000

0LP

3,86

LP4,

36LP

4,85

LP5,

39LP

5,96

LP6,

49LP

7,06

LP7,

68LP

8,33

HP

8,97

3100

0LP

4,16

LP4,

65LP

5,16

LP5,

70LP

6,30

LP6,

84LP

7,41

LP8,

03H

P8,

69H

P9,

3232

000

LP4,

47LP

4,96

LP5,

49LP

6,03

LP6,

62LP

7,23

LP7,

79LP

8,40

HP

9,07

HP

9,71

3300

0LP

4,81

LP5,

28LP

5,83

LP6,

38LP

6,97

LP7,

62LP

8,20

HP

8,85

HP

9,47

HP

10,1

234

000

LP5,

16LP

5,63

LP6,

19LP

6,76

LP7,

35LP

7,99

HP

8,68

HP

9,28

HP

9,90

HP

10,5

535

000

LP5,

53LP

6,01

LP6,

58LP

7,16

LP7,

75H

P8,

47H

P9,

13H

P9,

73H

P10

,35

HP

11,0

1

FAC/FAH/FAG/FAM 200-230

F200

F230

150

200

250

300

350

400

450

500

550

600

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

KIT

Pa (k

w)

2400

0LP

2,50

LP2,

93LP

3,37

LP3,

82LP

4,32

LP4,

83LP

5,33

LP5,

84LP

6,38

LP6,

9425

000

LP2,

70LP

3,13

LP3,

59LP

4,04

LP4,

54LP

5,07

LP5,

59LP

6,12

LP6,

67LP

7,23

2600

0LP

2,90

LP3,

33LP

3,83

LP4,

28LP

4,78

LP5,

32LP

5,88

LP6,

41LP

6,97

LP7,

5427

000

LP3,

12LP

3,56

LP4,

05LP

4,54

LP5,

03LP

5,57

LP6,

15LP

6,72

LP7,

29LP

7,87

2800

0LP

3,35

LP3,

81LP

4,29

LP4,

83LP

5,31

LP5,

85LP

6,43

LP7,

03LP

7,63

LP8,

2229

000

LP3,

59LP

4,07

LP4,

56LP

5,10

LP5,

62LP

6,15

LP6,

73LP

7,34

LP7,

98LP

8,59

3000

0LP

3,86

LP4,

35LP

4,84

LP5,

38LP

5,95

LP6,

48LP

7,05

LP7,

67LP

8,32

HP

8,95

3100

0LP

4,15

LP4,

64LP

5,15

LP5,

69LP

6,29

LP6,

83LP

7,40

LP8,

02H

P8,

67H

P9,

3132

000

LP4,

47LP

4,95

LP5,

48LP

6,02

LP6,

61LP

7,22

LP7,

78LP

8,39

HP

9,05

HP

9,70

3300

0LP

4,80

LP5,

27LP

5,82

LP6,

37LP

6,96

LP7,

61LP

8,19

HP

8,84

HP

9,46

HP

10,1

034

000

LP5,

15LP

5,62

LP6,

18LP

6,75

LP7,

33LP

7,98

HP

8,67

HP

9,26

HP

9,88

HP

10,5

335

000

LP5,

52LP

6,00

LP6,

56LP

7,15

LP7,

74H

P8,

45H

P9,

12H

P9,

71H

P10

,34

HP

10,9

936

000

LP5,

91LP

6,40

LP6,

96LP

7,56

HP

8,24

HP

8,87

HP

9,54

HP

10,1

9H

P10

,82

HP

11,4

737

000

LP6,

32LP

6,83

LP7,

38H

P8,

06H

P8,

68H

P9,

31H

P9,

98H

P10

,69

HP

11,3

3H

P11

,99

3800

0LP

6,76

HP

7,34

HP

7,88

HP

8,51

HP

9,14

HP

9,78

HP

10,4

5H

P11

,17

HP

11,8

7H

P12

,53

3900

0H

P7,

24H

P7,

79H

P8,

35H

P8,

97H

P9,

62H

P10

,27

HP

10,9

5H

P11

,67

HP

12,4

240

000

HP

7,70

HP

8,27

HP

8,85

HP

9,46

HP

10,1

2H

P10

,79

HP

11,4

8H

P12

,19

4100

0H

P8,

19H

P8,

78H

P9,

36H

P9,

97H

P10

,65

HP

11,3

4H

P12

,03

4200

0H

P8,

71H

P9,

30H

P9,

91H

P10

,52

HP

11,2

0H

P11

,90

4300

0H

P9,

24H

P9,

85H

P10

,47

HP

11,1

0H

P11

,78

Application Guide / FLEXAIR-AGU-1505-E

Cooling only Heat pumpCooling only with gas fi red heating Heat pump rooftop with gas fi red heating

Airfl

ow

Airfl

ow

Airfl

ow

No

kit

No

kit

No

kit

No

kit

No

kit

6.- FAN PERFORMANCES

6.2- EXHAUST FAN PERFORMANCES

LP HPLow Pressure High Pressure

• 45 •

085 100 120 150 170 200 230

15000 18500 20500 26000 30000 35000 39000

20%

14,2 17,1 18,8 24,2 27,4 32,4 35,7

0,18 0,18 0,18 0,18 0,18 0,18 0,18

84 82 81 83 81 82 81

60%

35,7 41,6 44,6 59,0 65,1 78,6 84,6

0,18 0,18 0,18 0,18 0,18 0,18 0,18

71 67 64 67 64 67 64

90%

47,5 54,0 57,2 76,8 83,3 101,9 108,3

0,18 0,18 0,18 0,18 0,18 0,18 0,18

62 58 55 58 55 58 55

100%

50,7 57,3 60,4 81,6 88,0 108,1 114,4

0,18 0,18 0,18 0,18 0,18 0,18 0,18

60 55 52 56 52 55 52

085 100 120 150 170 200 230

15000 18500 20500 26000 30000 35000 39000

20%

16,5 19,9 21,7 28,1 31,8 37,6 41,3

0,18 0,18 0,18 0,18 0,18 0,18 0,18

87 85 84 85 84 85 84

60%

40,8 47,2 50,5 67,0 73,6 89,2 95,7

0,18 0,18 0,18 0,18 0,18 0,18 0,18

72 67 65 68 65 67 65

90%

53,5 60,4 63,8 86,1 92,9 114,1 120,8

0,18 0,18 0,18 0,18 0,18 0,18 0,18

63 57 55 58 54 57 54

100%

57,0 63,9 67,1 91,1 97,7 120,6 127,0

0,18 0,18 0,18 0,18 0,18 0,18 0,18

60 55 52 55 51 54 51

Application Guide /FLEXAIR-AGU-1505-E

ENERGY RECOVERY MODULEHeating and cooling mode

Conditions : 27°C / 47% HR35°C / 50 % HR

Fres

h ai

r %

COOLING MODESize

Nominal airfl ow rate (m3/h)

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

7- HEAT RECOVERY SOLUTIONS PERFORMANCES

7.1- ROTARY WHEEL HEAT RECOVERY SYSTEM

Conditions :20°C / 70% HR / -7°C

Fres

h ai

r %

HEATING MODESize

Nominal airfl ow rate (m3/h)

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

• 46 •

085 100 120 150 170 200 230

15000 18500 20500 26000 30000 35000 39000

20%

32,9 39,6 43,3 55,9 63,3 75,0 82,3

0,18 0,18 0,18 0,18 0,18 0,18 0,18

88 86 85 86 85 86 85

60%

80,7 93,1 99,5 132,2 145,1 176,0 188,6

0,18 0,18 0,18 0,18 0,18 0,18 0,18

72 67 65 68 65 67 65

90%

105,4 118,7 125,0 169,1 182,0 224,1 236,7

0,18 0,18 0,18 0,18 0,18 0,18 0,18

63 57 55 58 54 57 54

100%

112,0 125,2 131,4 178,7 191,2 236,4 248,7

0,18 0,18 0,18 0,18 0,18 0,18 0,18

60 54 52 55 51 54 51

Application Guide / FLEXAIR-AGU-1505-E

7- HEAT RECOVERY SOLUTIONS PERFORMANCES

ENERGY RECOVERY MODULEHeating and cooling modes

Conditions :20°C / 70% HR / 7°C

Fres

h ai

r %

HEATING MODESize

Nominal airfl ow rate (m3/h)

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

Heat recovery cooling capacity kW

Heat recovery cooling absorbed power kW

Effi ciency %

• 47 •

90-70 80-60 70-50

85

S 12000 142 109 33 6 123 83 28 5 104 59 24 4H 217 90 50 9 189 69 44 8 160 50 37 7S 15000 160 137 30 7 138 104 26 6 116 74 22 5H 249 118 46 11 216 90 40 9 183 65 34 8S 23000 - - - - 170 156 21 7 143 111 17 6H 318 191 38 14 275 145 33 12 232 103 28 10

100

S 14000 154 127 31 7 133 97 26 6 112 69 22 5H 239 109 47 10 207 83 41 9 175 60 35 8S 18500 178 168 27 8 154 127 23 7 129 91 19 6H 282 151 42 12 244 114 37 11 206 83 31 9S 23000 - - - - 170 156 21 7 143 111 17 6H 318 191 38 14 275 145 33 12 232 103 28 10

120

S 15000 160 137 30 7 138 104 26 6 116 74 22 5H 249 118 46 11 216 90 40 9 183 65 34 8S 20500 187 185 25 8 161 140 22 7 136 100 18 6H 298 169 40 13 258 128 35 11 218 92 29 9S 23000 - - - - 170 156 21 7 143 111 17 6H 318 191 38 14 275 145 33 12 232 103 28 10

150

S 18000 172 50 26 7 148 37 23 6 123 26 19 5H 286 70 44 12 249 54 38 11 211 40 33 9S 26000 206 72 22 9 177 53 19 8 147 37 16 6H 356 107 38 15 309 82 33 13 262 60 28 11S 35000 236 94 19 10 202 69 16 9 169 49 13 7H 420 147 33 18 364 113 29 16 308 83 24 13

170

S 21000 186 59 25 8 159 43 21 7 133 30 18 6H 314 84 41 14 273 65 36 12 231 48 31 10S 30000 220 82 20 10 189 60 17 8 158 42 15 7H 386 125 36 17 335 96 31 14 283 70 26 12S 35000 236 94 19 10 202 69 16 9 169 49 13 7H 420 147 33 18 364 113 29 16 308 83 24 13

200

S 24000 208 62 24 9 178 46 21 8 149 32 17 6H 335 78 39 14 290 60 34 13 246 44 28 11S 35000 251 91 20 11 215 67 17 9 180 47 14 8H 414 118 33 18 359 91 28 15 304 66 24 13S 43000 277 110 18 12 237 81 15 10 198 57 13 9H 461 147 30 20 400 112 26 17 338 82 22 15

230

S 27000 221 70 23 10 189 52 19 8 158 36 16 7H 358 89 37 15 311 68 32 13 263 50 27 11S 39000 264 101 19 11 227 74 16 10 189 52 13 8H 438 133 31 19 380 101 27 16 322 74 23 14S 43000 277 110 18 12 237 81 15 10 198 57 13 9H 461 147 30 20 400 112 26 17 338 82 22 15

FCM FHM

(1) S H(2)

Application Guide /FLEXAIR-AGU-1505-E

Return air at 0°C

8- HEATING AUXILIARIES PERFORMANCES

SIZE

Type

(1)

Airfl

ow

rate

m3 /h

water temperature

Hea

ting

capa

city

kW Pre

ssur

e dr

op (2

)

kPa

A

ir te

mpe

ratu

re

Wat

er fl

ow ra

tem

3 /h

Hea

ting

capa

city

kW Pre

ssur

e dr

op (2

)

kPa

A

ir te

mpe

ratu

re

Wat

er fl

ow ra

tem

3 /h

Hea

ting

capa

city

kW Pre

ssur

e dr

op (2

)

kPa

A

ir te

mpe

ratu

re

Wat

er fl

ow ra

tem

3 /h

Cooling only Heat pump

Standard heat High heatPressure drop = Internal coil + 3-way valve

Water without glycolReminder : 10 kPa=1mCe = 1mH2O

8.1- HOT WATER COIL PERFORMANCES

• 48 •

90-70 80-60 70-50

85

S 12000 121 80 29 5 102 57 25 4 83 39 20 4H 185 66 44 8 157 48 38 7 129 33 31 6S 15000 137 100 26 6 115 72 22 5 94 49 18 4H 213 87 41 9 180 63 34 8 147 43 28 6S 23000 168 151 21 7 142 108 18 6 115 73 14 5H 271 140 34 12 229 101 29 10 187 68 23 8

100

S 14000 132 94 27 6 111 67 23 5 90 46 19 4H 204 80 42 9 173 58 35 7 141 39 29 6S 18500 152 123 24 7 128 88 20 6 104 60 16 4H 240 110 37 10 203 80 32 9 166 54 26 7S 23000 168 151 21 7 142 108 18 6 115 73 14 5H 271 140 34 12 229 101 29 10 187 68 23 8

120

S 15000 137 100 26 6 115 72 22 5 94 49 18 4H 213 87 41 9 180 63 34 8 147 43 28 6S 20500 160 136 22 7 134 97 19 6 109 66 15 5H 255 124 36 11 215 90 30 9 175 60 25 8S 23000 168 151 21 7 142 108 18 6 115 73 14 5H 271 140 34 12 229 101 29 10 187 68 23 8

150

S 18000 146 36 23 6 122 26 20 5 99 17 16 4H 244 52 39 11 208 38 33 9 170 26 27 7S 26000 175 52 19 8 147 37 16 6 118 24 13 5H 304 79 34 13 258 58 28 11 211 40 23 9S 35000 201 68 16 9 168 48 14 7 135 31 11 6H 358 109 29 15 304 80 25 13 248 54 20 11

170

S 21000 158 42 22 7 132 30 18 6 106 20 15 5H 268 62 37 12 228 46 31 10 187 31 26 8S 30000 187 59 18 8 157 42 15 7 126 27 12 5H 329 92 32 14 279 68 27 12 229 46 22 10S 35000 201 68 16 9 168 48 14 7 135 31 11 6H 358 109 29 15 304 80 25 13 248 54 20 11

200

S 24000 176 45 21 8 148 32 18 6 119 21 14 5H 286 58 34 12 242 42 29 10 199 29 24 9S 35000 213 65 18 9 178 46 15 8 143 30 12 6H 353 87 29 15 300 64 25 13 245 43 20 11S 43000 235 79 16 10 197 56 13 8 158 36 11 7H 394 108 26 17 334 79 22 14 273 54 18 12

230

S 27000 187 51 20 8 157 36 17 7 126 23 13 5H 306 66 33 13 259 48 28 11 213 33 23 9S 39000 225 72 17 10 188 51 14 8 151 33 11 7H 374 98 28 16 317 72 23 14 260 49 19 11S 43000 235 79 16 10 197 56 13 8 158 36 11 7H 394 108 26 17 334 79 22 14 273 54 18 12

(1) S H(2)

FCM FHM

Application Guide / FLEXAIR-AGU-1505-E

8- HEATING AUXILIARIES PERFORMANCES

Return air at 10°CTy

pe (1

)

Airfl

ow

rate

m3 /h

water temperature

SIZE

Hea

ting

capa

city

kW Pre

ssur

e dr

op (2

)

kPa

A

ir te

mpe

ratu

re

Wat

er fl

ow ra

tem

3 /h

Hea

ting

capa

city

kW Pre

ssur

e dr

op (2

)

kPa

A

ir te

mpe

ratu

re

Wat

er fl

ow ra

tem

3 /h

Hea

ting

capa

city

kW Pre

ssur

e dr

op (2

)

kPa

A

ir te

mpe

ratu

re

Wat

er fl

ow ra

tem

3 /h

Standard heat High heatPressure drop = Internal coil + 3-way valve

Water without glycolReminder : 10 kPa=1mCe = 1mH2O

Cooling only Heat pump

• 49 •

90-70 80-60 70-50

85

S 12000 101 56 25 4 83 38 20 4 64 23 16 3H 155 47 38 7 127 32 31 5 99 20 25 4S 15000 114 70 23 5 93 48 18 4 72 29 14 3H 177 61 35 8 145 41 29 6 113 26 22 5S 23000 140 106 18 6 114 71 15 5 88 43 11 4H 226 98 29 10 185 66 24 8 143 41 19 6

100

S 14000 110 65 23 5 90 44 19 4 69 27 15 3H 170 56 36 7 139 38 30 6 109 24 23 5S 18500 126 86 20 5 103 58 17 4 79 35 13 3H 201 78 32 9 164 52 26 7 127 32 20 6S 23000 140 106 18 6 114 71 15 5 88 43 11 4H 226 98 29 10 185 66 24 8 143 41 19 6

120

S 15000 114 70 23 5 93 48 18 4 72 29 14 3H 177 61 35 8 145 41 29 6 113 26 22 5S 20500 133 95 19 6 108 64 16 5 83 39 12 4H 212 87 31 9 174 59 25 7 135 36 20 6S 23000 140 106 18 6 114 71 15 5 88 43 11 4H 226 98 29 10 185 66 24 8 143 41 19 6

150

S 18000 121 25 20 5 98 17 16 4 75 10 12 3H 204 37 34 9 168 25 28 7 132 16 22 6S 26000 145 36 17 6 117 24 13 5 89 14 10 4H 254 56 29 11 209 38 24 9 163 24 19 7S 35000 167 47 14 7 135 31 11 6 102 18 9 4H 300 77 25 13 246 53 21 11 191 33 16 8

170

S 21000 131 29 19 6 106 19 15 5 81 11 11 3H 224 44 32 10 184 30 26 8 144 19 20 6S 30000 156 41 15 7 126 27 12 5 95 16 9 4H 275 65 27 12 226 45 22 10 176 28 17 8S 35000 167 47 14 7 135 31 11 6 102 18 9 4H 300 77 25 13 246 53 21 11 191 33 16 8

200

S 24000 146 31 18 6 118 20 15 5 90 12 11 4H 239 41 30 10 196 28 24 8 154 18 19 7S 35000 177 45 15 8 143 30 12 6 108 17 9 5H 295 62 25 13 242 42 21 10 189 26 16 8S 43000 195 55 14 8 157 36 11 7 119 21 8 5H 330 76 23 14 270 52 19 12 210 32 15 9

230

S 27000 156 35 17 7 126 23 14 5 96 13 11 4H 256 47 28 11 210 32 23 9 164 20 18 7S 39000 186 50 14 8 150 33 11 6 114 19 9 5H 313 69 24 14 257 47 20 11 200 29 15 9S 43000 195 55 14 8 157 36 11 7 119 21 8 5H 330 76 23 14 270 52 19 12 210 32 15 9

(1) S H(2)

FCM FHM

Application Guide /FLEXAIR-AGU-1505-E

Return air at 20°C

8- HEATING AUXILIARIES PERFORMANCES

Type

(1)

Airfl

ow

rate

m3 /h

water temperature

SIZE

Hea

ting

capa

city

kW Pre

ssur

e dr

op (2

)

kPa

A

ir te

mpe

ratu

re

Wat

er fl

ow ra

tem

3 /h

Hea

ting

capa

city

kW Pre

ssur

e dr

op (2

)

kPa

A

ir te

mpe

ratu

re

Wat

er fl

ow ra

tem

3 /h

Hea

ting

capa

city

kW Pre

ssur

e dr

op (2

)

kPa

A

ir te

mpe

ratu

re

Wat

er fl

ow ra

tem

3 /h

Standard heat High heatPressure drop = Internal coil + 3-way valve

Water without glycolReminder : 10 kPa=1mCe = 1mH2O

Cooling only Heat pump

• 50 •

2,930S

15000085

5,75,250%-->

0-100%54M10,3100%-->6,950%-->

0-100%72H13,8100%-->2,3

30S

18500100

4,64,250%-->

0-100%54M8,4100%-->5,650%-->

0-100%72H11,2100%-->2,1

30S

20500120

4,23,850%-->

0-100%54M7,6100%-->5,050%-->

0-100%72H10,1100%-->2,5

45S

26000150

5,04,050%-->

0-100%72M7,9100%-->6,050%-->

0-100%108H11,9100%-->2,2

45S

30000170

4,33,450%-->

0-100%72M6,9100%-->5,250%-->

0-100%108H10,3100%-->2,9

72S

35000200

5,94,450%-->

0-100%108M8,8100%-->6,650%-->

0-100%162H13,3100%-->2,6

72S

39000230

5,34,050%-->

0-100%108M7,9100%-->6,050%-->

0-100%162H11,9100%-->

Application Guide / FLEXAIR-AGU-1505-E

8- HEATING AUXILIARIES PERFORMANCES

8.2- ELECTRICAL HEATERS

Temp. RiseStagesType of

Modulation

Available CapacityTYPEAIRFLOW

m3/hSIZE

ºCKW

Stage 1: 2 stages

Stage 2:

Stage 1: 2 stages

Stage 2:

Stage 1: 2 stages

Stage 2:

Stage 1: 2 stages

Stage 2:

Stage 1: 2 stages

Stage 2:

Stage 1: 2 stages

Stage 2:

Stage 1: 2 stages

Stage 2:

• 51 •

20.1655.260S15000085

40%-->100%20.25110.4120H

20.1655.260S18500100

40%-->100%20.25110.4120H

20.1655.260S20500120

40%-->100%20.25110.4120H

20.25110.4120S26000150

40%-->100%20.25165.6180H

20.25110.4120S30000170

40%-->100%20.25165.6180H

20.25165.6180S35000200

40%-->100%20.25220.8240H

20.25165.6180S39000230

40%-->100%20.25220.8240H

Application Guide /FLEXAIR-AGU-1505-E

8- HEATING AUXILIARIES PERFORMANCES

8.3- GAS BURNER PERFORMANCES

Modulation Option

Number of stages

Electrical absorbed

power

Gas power input

Gas power inputTYPEAirfl ow rate

m3/h

SIZE KWKWKW

• 52 •

FAC/FAHFAG/FAM

ESP(Pa) 63 125 250 500 1000 2000 4000 8000

85 15000 125 57,0 58,1 64,4 70,9 74,7 74,6 73,7 67,2 80,1 49,2100 18500 125 60,2 67,1 72,2 82,4 82,5 86,8 79,8 87,4 91,8 60,8120 20500 125 56,8 61,9 74,7 78,4 79,4 83,8 77,4 84,4 88,8 57,8150 28000 150 52,0 57,7 68,3 76,1 77,8 82,0 79,9 82,0 87,2 56,2170 30000 175 57,1 58,8 73,3 74,1 77,6 78,8 80,8 79,4 85,9 54,9200 35000 175 59,5 63,0 69,9 75,0 79,2 80,9 76,2 73,0 84,9 53,9230 39000 175 57,3 60,3 69,2 75,7 78,2 78,5 81,0 73,4 85,2 54,2

FAC/FAHFAG/FAM

ESP(Pa) 63 125 250 500 1000 2000 4000 8000

85 15000 500 57,0 58,3 65,8 71,1 75,0 74,3 74,7 62,6 80,3 49,3100 18500 500 60,2 65,2 72,7 82,5 82,5 87,1 80,4 87,6 92,0 61,0120 20500 500 56,7 61,6 67,7 78,1 79,0 83,6 78,4 84,4 88,6 57,6150 28000 500 52,0 56,6 72,4 75,9 78,3 81,8 80,4 82,8 87,6 56,6170 30000 500 60,1 65,4 70,2 82,2 82,1 86,7 79,5 87,4 91,6 60,6200 35000 500 59,5 61,5 70,4 75,3 79,6 80,7 76,0 73,1 85,0 54,0230 39000 500 57,3 60,3 74,4 76,5 79,4 79,5 82,2 78,7 86,9 55,9

FAC/FAHFAG/FAM

ESP(Pa) 63 125 250 500 1000 2000 4000 8000

85 15000 250 53,9 56,6 64,0 69,8 70,1 71,2 73,2 67,3 78,0 47,0100 18500 250 58,9 65,7 71,4 79,2 78,0 77,4 72,9 87,4 89,0 58,0120 20500 250 55,9 59,7 74,5 76,1 75,0 74,1 72,3 83,4 85,6 54,6150 28000 300 58,0 58,6 68,4 74,2 72,8 76,3 79,0 81,2 84,9 53,9170 30000 350 54,1 57,5 73,2 73,5 74,7 76,3 80,5 79,4 85,0 54,0200 35000 350 56,5 61,7 69,5 73,6 74,1 77,4 74,0 73,0 82,0 51,0230 39000 350 56,5 59,1 68,7 74,7 74,5 76,0 80,9 73,3 84,0 53,0

FAC/FAHFAG/FAM

ESP(Pa) 63 125 250 500 1000 2000 4000 8000

85 15000 500 54,0 56,8 65,5 70,0 71,0 70,5 74,4 62,7 78,3 47,3100 18500 500 58,9 62,6 72,0 79,4 78,0 79,1 75,2 87,6 89,3 58,3120 20500 500 55,7 59,3 66,5 75,5 73,6 72,7 74,9 83,4 85,2 54,2150 28000 500 58,0 57,8 72,4 73,8 74,1 75,3 79,6 82,1 85,5 54,5170 30000 500 58,8 63,0 68,7 78,7 76,8 75,5 70,7 87,4 88,6 57,6200 35000 500 56,5 59,6 70,2 73,9 75,3 77,1 73,6 73,1 82,2 51,2230 39000 500 56,6 59,1 74,3 75,7 76,9 77,7 82,1 78,6 86,1 55,1

Application Guide / FLEXAIR-AGU-1505-E

OUTDOOR NOISE LEVEL - STANDARD

OUTDOOR NOISE LEVEL - LOW NOISE

(1) Total outdoor power levels(2) Global outdoor sound pressure levels 10 m

Spectrum per octave band

Spectrum per octave band

Spectrum per octave band

Spectrum per octave band

Sound powerdB(A) (1)

Sound powerdB(A) (1)

Sound powerdB(A) (1)

Sound powerdB(A) (1)

Sound pressure at 10 meters

dB(A) (2)

Sound pressure at 10 meters

dB(A) (2)

Sound pressure at 10 meters

dB(A) (2)

Sound pressure at 10 meters

dB(A) (2)

9- ACOUSTIC DATA IN SPECTRUM

Airfl ow rate (m3/h)

Airfl ow rate (m3/h)

Airfl ow rate (m3/h)

Airfl ow rate (m3/h)

• 53 •

FAC/FAH ESP(Pa) 63 125 250 500 1000 2000 4000 8000

85 15000 125 41,3 55,2 69,0 77,8 81,0 80,8 80,5 73,1 86,5 85100 18500 125 50,2 70,2 77,1 82,4 86,7 84,0 78,4 73,8 90,2 90120 20500 125 50,3 58,9 79,6 80,6 85,9 81,7 78,3 72,1 89,2 89150 28000 150 47,8 62,1 75,6 84,5 87,7 87,6 86,8 79,9 93,1 91170 30000 175 50,1 59,6 77,1 85,8 90,8 87,7 88,8 85,1 95,2 94200 35000 175 50,1 64,0 75,9 83,9 84,8 87,7 80,7 78,6 91,3 86230 39000 175 47,4 59,7 74,7 83,2 86,2 85,7 87,1 78,1 92,0 88

FAC/FAH 63 125 250 500 1000 2000 4000 8000

85 15000 500 44,9 57,8 71,8 78,8 82,1 80,6 82,3 70,0 87,4 87100 18500 500 48,1 60,2 75,2 83,7 87,1 86,3 80,2 78,2 91,4 89120 20500 500 41,8 54,2 68,7 76,1 79,3 78,0 79,7 67,9 84,7 90150 28000 500 50,0 59,1 76,3 85,0 90,5 87,1 87,9 83,5 94,5 92170 30000 500 44,3 62,0 71,4 78,4 81,7 79,8 74,3 69,8 85,6 95200 35000 500 49,6 61,5 76,6 85,2 88,5 87,8 81,6 79,8 92,8 91230 39000 500 50,1 58,9 76,2 84,6 90,3 86,8 87,4 82,2 94,1 92

FAG/FAM 63 125 250 500 1000 2000 4000 8000

85 15000 250 41,3 55,2 69,0 77,8 81,0 80,8 80,5 73,1 86,5 84100 18500 250 50,2 70,2 77,1 82,4 86,7 84,0 78,4 73,8 90,2 87120 20500 250 50,3 58,9 79,6 80,6 85,9 81,7 78,3 72,1 89,2 89150 28000 300 47,8 62,1 75,6 84,5 87,7 87,6 86,8 79,9 93,1 88170 30000 350 50,1 59,6 77,1 85,8 90,8 87,7 88,8 85,1 95,2 90200 35000 350 50,1 64,0 75,9 83,9 84,8 87,7 80,7 78,6 91,3 88230 39000 350 47,4 59,7 74,7 83,2 86,2 85,7 87,1 78,1 92,0 90

FAG/FAM 63 125 250 500 1000 2000 4000 8000

85 15000 500 44,9 57,8 71,8 78,8 82,1 80,6 82,3 70,0 87,4 90100 18500 500 48,1 60,2 75,2 83,7 87,1 86,3 80,2 78,2 91,4 91120 20500 500 41,8 54,2 68,7 76,1 79,3 78,0 79,7 67,9 84,7 93150 28000 500 50,0 59,1 76,3 85,0 90,5 87,1 87,9 83,5 94,5 94170 30000 500 44,3 62,0 71,4 78,4 81,7 79,8 74,3 69,8 85,6 95200 35000 500 49,6 61,5 76,6 85,2 88,5 87,8 81,6 79,8 92,8 93230 39000 500 50,1 58,9 76,2 84,6 90,3 86,8 87,4 82,2 94,1 94

Application Guide /FLEXAIR-AGU-1505-E

INDOOR NOISE LEVEL - STANDARD & LOW NOISE

INDOOR NOISE LEVEL - STANDARD & LOW NOISE

Spectrum per octave band

Spectrum per octave band

Spectrum per octave band

Spectrum per octave band

Sound power returndB(A)

Sound power supplydB(A)

9- ACOUSTIC DATA IN SPECTRUM

Airfl ow rate (m3/h)

Sound power returndB(A)

Sound power supplydB(A)

Airfl ow rate (m3/h)

Sound power returndB(A)

Sound power supplydB(A)

Airfl ow rate (m3/h)

Sound power returndB(A)

Sound power supplydB(A)

Airfl ow rate (m3/h)

• 54 •

085 100 120PA FLA SUA PA FLA SUA PA FLA SUAkW A A kW A A kW A A

0,21 0,53 0,53 0,21 0,53 0,53 0,21 0,53 0,53

31,1 50,6 183,3 34,8 58,6 226,3 46,6 75,6 252,8

3,9 7,8 16,9 3,9 7,8 16,9 5,0 10,3 23,7

3,7 5,7 5,7 3,7 5,7 5,7 4,2 6,4 6,4

5,7 8,6 8,6 5,7 8,6 8,6 5,7 8,6 8,6

11,0 16,8 16,8 11,0 16,8 16,8 11,0 16,8 16,8

S 30,0 41,2 41,2 30,0 41,2 41,2 30,0 41,2 41,2

M 54,0 74,2 74,2 54,0 74,2 74,2 54,0 74,2 74,2

H 72,0 99,0 99,0 72,0 99,0 99,0 72,0 99,0 99,0

0,16 0,40 0,40 0,16 0,40 0,40 0,16 0,40 0,40

0,25 0,63 0,63 0,25 0,63 0,63 0,25 0,63 0,63

1,0 1,8 5,1 1,0 1,8 5,10 1,0 1,8 5,1

5,7 8,6 8,6 5,7 8,6 8,6 5,7 8,6 8,6

0,09 0,29 1,16 0,09 0,29 1,16 0,09 0,29 1,16

PA SFLA MSUA H

150 170 200 230PA FLA SUA PA FLA SUA PA FLA SUA PA FLA SUAkW A A kW A A kW A A kW A A

0,30 0,75 0,75 0,30 0,75 0,75 0,30 0,75 0,75 0,30 0,75 0,75

54,4 88,4 265,6 62,2 101,2 233,9 69,5 117,2 284,9 93,2 151,2 328,4

3,9 7,8 16,9 5,0 10,3 23,7 7,8 15,6 33,8 9,9 20,6 47,5

3,7 5,7 5,7 4,2 6,4 6,4 7,4 11,4 11,4 8,4 12,8 12,8

8,49 12,9 12,9 8,49 12,9 12,9 9,0 13,8 13,8 9,0 13,8 13,8

16,5 25,2 25,2 16,5 25,2 25,2 14,1 21,9 21,9 14,1 21,9 21,9

S 45,0 61,8 61,8 45,0 61,8 61,8 72,0 99,0 99,0 72,0 99,0 99,0

M 72,0 99,0 99,0 72,0 99,0 99,0 108,0 148,5 148,5 108,0 148,5 148,5

H 108,0 148,5 148,5 108,0 148,5 148,5 162,0 195,3 195,3 162,0 195,3 195,3

0,25 0,63 0,63 0,25 0,63 0,63 0,25 0,63 0,63 0,25 0,63 0,63

0,25 0,63 0,63 0,25 0,63 0,63 0,25 0,63 0,63 0,25 0,63 0,63

1,02 1,83 5,10 1,02 1,83 5,10 1,02 1,83 5,10 1,02 1,83 5,10

8,5 12,9 12,9 8,5 12,9 12,9 9,0 13,8 13,8 9,0 13,8 13,8

0,18 0,58 2,32 0,18 0,58 2,32 0,18 0,58 2,32 0,18 0,58 2,32

Application Guide / FLEXAIR-AGU-1505-E

With (not cumulative):

Transformer

Compressor

Condensing fan

Condensing fan (EC fan)

Indoor supply kitLP

HP

ELECTRICAL

Electric heater

Gas burnerS

H

POWER AXIAL FAN VERTICAL

EXTRACTIONAxial extraction fan(Vertical or horizontal)

ENERGY RECOVERYRotary wheel motor

Absorbed power (kW) Standard heat

Full load amps (A) Medium heat

Start up amps (A) High heat

10.1- ELECTRICAL TABLES

10- ELECTRICAL DATA

With (not cumulative):

Transformer

Compressor

Condensing fan

Condensing fan (EC fan)

Indoor supply kitLP

HP

ELECTRICAL

Electric heater

Gas burnerS

H

POWER AXIAL FAN VERTICAL

EXTRACTIONAxial extraction fan(Vertical or horizontal)

ENERGY RECOVERYRotary wheel motor

• 55 •

pLan

connectionMaster/Slave

CUSTOMER CONNECTIONS

J1 J2

U1

U3

U2

GN

DG G0

J3

U4

+VdcU5

+5VR

GN

D

J4

U6

+VdcU7

+5VR

GN

D

J6

GN

D Y3Y1 Y2

J5

U8

+VdcU9

+5VR

GN

D

U10

J7

DI1

DI3

DI2

DI4

GN

D

J8

J25

DI7

H

DI7

C

DI7

DI8

DI8

H

J26

Y4 U11Y5

GN

D

U12

GN

D

DI9

DI1

0

DI9

C

J24

NO

8

C8

J12

J28

C11

NO

12

NO

11

NO

13

C11

2 1 J23

NO

7

C7

J22

NO

6

C6

J21

C2

V-IN

J20

Out

5

C2

J19

Out

4

C2

J18

Out

3

C2

J17

Out

2

C2

J16

NC

1

C1

NO

1

J27

NO

9

NC

9

C9

NO

10

C10

NC

10

J15

GN

DTx

/Rx

+Tx

/Rx

-

J14

GN

D+-

J11

GN

D+-

J29

J10BMS card

J9

GN

D+-V

out +

J13

WH

ITE

BR

OW

N

Bus

Bus

4

3 24V.E

24V.F R2

GN

D24

V

GN

DR

X+RX-

4770703RLOCAL DISPLAYMULTI UNITS

V+G

ND T- T+

MAINTENANCE DISPLAY

1243

0 1 2 3 4 5 6

3 2 1 3 2 1J14J15

24Vac

Application Guide /FLEXAIR-AGU-1505-E

10. ELECTRICAL DATA

10.2- CONTROL TERMINAL CONNECTION

Customer connections

• 56 •

FAC/FAH/FAG/FAM 85/100/120

Application Guide / FLEXAIR-AGU-1505-E

11- DIMENSIONS

G����A� A��A�G�M���� ��A���G�

11�1� ���� ��M�������

• 57 •

FAC/FAH/FAG/FAM 085/100/120

Application Guide /FLEXAIR-AGU-1505-E

11- DIMENSIONS

G����A� A��A�G�M���� ��A���G�

• 58 •

FAC/FAH/FAG/FAM 85/100/120

Application Guide / FLEXAIR-AGU-1505-E

GENERAL ARRANGEMENTS DRAWINGS

11- DIMENSIONS

• 59 •

FAC/FAH/FAG/FAM 085/100/120

Application Guide /FLEXAIR-AGU-1505-E

GENERAL ARRANGEMENTS DRAWINGS

11- DIMENSIONS

• 60 •

FAC/FAH/FAG/FAM 150/170

Application Guide / FLEXAIR-AGU-1505-E

GENERAL ARRANGEMENTS DRAWINGS

11- DIMENSIONS

• 61 •

FAC/FAH/FAG/FAM 150/170

Application Guide /FLEXAIR-AGU-1505-E

GENERAL ARRANGEMENTS DRAWINGS

11- DIMENSIONS

• 62 •

FAC/FAH/FAG/FAM 150/170

Application Guide / FLEXAIR-AGU-1505-E

GENERAL ARRANGEMENTS DRAWINGS

11- DIMENSIONS

• 63 •

FAC/FAH/FAG/FAM 150/170

Application Guide /FLEXAIR-AGU-1505-E

GENERAL ARRANGEMENTS DRAWINGS

11- DIMENSIONS

• 64 •

FAC/FAH/FAG/FAM 200/230

Application Guide / FLEXAIR-AGU-1505-E

GENERAL ARRANGEMENTS DRAWINGS

11- DIMENSIONS

• 65 •

FAC/FAH/FAG/FAM 200/230

Application Guide /FLEXAIR-AGU-1505-E

GENERAL ARRANGEMENTS DRAWINGS

11- DIMENSIONS

• 66 •

FAC/FAH/FAG/FAM 200/230

Application Guide / FLEXAIR-AGU-1505-E

GENERAL ARRANGEMENTS DRAWINGS

11- DIMENSIONS

• 67 •

FAC/FAH/FAG/FAM 200/230

Application Guide /FLEXAIR-AGU-1505-E

GENERAL ARRANGEMENTS DRAWINGS

11- DIMENSIONS

• 68 •

FAC/FAH/FAG/FAM 85/100/120

FAC/FAH/FAG/FAM 150/170

FAC/FAH/FAG/FAM 200/230

Application Guide / FLEXAIR-AGU-1505-E

11.2- AIRFLOW CONFIGURATION

11- DIMENSIONS

Supply(Option)

Supply(Option)

Supply(Option)

Supply(Option)

Supply(Standard)

Supply(Standard)

Supply(Standard)

Supply(Standard)

Supply(Standard)

Supply(Standard)

Return(Standard)

Return(Standard)

Return(Standard)

Return(Standard)

Return(Standard)

Return(Standard)

Fresh air

Fresh air

Fresh air

Fresh air

Fresh air

Fresh air

Extraction(option)

Extraction(option)

Return(option)

Return(option)

Supply(Option)

Supply(Option)

• 69 •

2059 ± 15

1956 ± 1550 ± 5

F

50 ± 550 ± 5

50 ± 5

A

B C

D

EG

HJ

K L

A B C D E F G H J K L

85-100-120 2771 614 2005 2669 410 96 207 1443 326 139 700

150-170 3466 800 2493 3365 410 95 491 1540 433 139 700

200-230 4066 1106 2493 3965 425 95 233 1830 432 89 800

FAC/FAH/FAG/FAM

Application Guide /FLEXAIR-AGU-1505-E

DIMENSIONS

NON ADJUSTABLE ROOFCURB

11.3- ROOFCOURB DIMENSIONS

11- DIMENSIONS

• 70 •

2064 ± 15

1958 ± 1514%

100 ± 5

95 ± 5

422 ± 15

100 ± 5 100 ± 5 EQ

B CA

100 ± 5

DF

GH

MN

P

J K L

A B C D E F G H J K L M N P Q

85-100-120 2771 614 2006 400 2672 237 1443 326 140 700 145 131 1747 128 10 %

150-170 3467 800 2494 400 3368 520 1540 433 140 700 146 235 1997 230 8 %

200-230 4067 1105 2494 425 3968 232 1830 432 89 800 146 235 1997 262 6,6 %

FAC/FAH/FAG/FAM

Application Guide / FLEXAIR-AGU-1505-E

DIMENSIONS

ADJUSTABLE ROOFCURB

11- DIMENSIONS

• 71 •

A

E F

2154

CD

B

200 ± 5

88 ± 52056 ± 15

980±15 780±15

40 ±

5

RS

L

M

NP88 ± 5

H JK

200 ± 5

A B C D E F H J

85-100-120 300 1335 600 60 1550 794 840 600

150-170 229 1540 600 60 1799 1241 1140 900

200-230 322 1850 700 162 2093 1572 1340 1100

K L M N P R S

85-100-120 60 2744 2005 1335 300 600 60

150-170 60 3440 2493 1540 229 600 60

200-230 100 4067 2493 1850 332 700 160

FAC/FAH/FAG/FAM

Application Guide /FLEXAIR-AGU-1505-E

DIMENSIONS

MULTIDIRECTIONAL ROOFCURB

11- DIMENSIONS

• 72 •

A

2083

1220

400

B

F

J

G

CE

120

420

700

973

800

240

120

240

2056

H50

D

120

A B C D E F G H J

85-100-120 3041 3016 - 2005 85 1525 2805 95 1525

150-170 4107 4093 800 2493 85 2013 3293 90 2013

200-230 4107 4093 800 2493 100 2013 3293 90 2013

FAC/FAH/FAG/FAM

Application Guide / FLEXAIR-AGU-1505-E

EX

HA

US

T A

IR

MAIN POWER ENTRY

MAIN POWER ENTRY

SUPPLY AIR

RETURN AIR

RETURN AIR

ACCESS TO FAN COMPARTMENT

DIMENSIONS

HORIZONTAL EXHAUST ROOFCURB

11- DIMENSIONS

• 73 •

1220

350

105

137240

240

118

700

400

390

2256

G

2056

A

B

BC

D

E 800

100 100 100100

2056

2159

2056H

J

F

A B C D E F G H J

85-100-120 2312 1525 2805 3016 211 2005 85 2805 3127

150-170 2800 2013 3293 4093 800 2493 85 3293 4193

200-230 2800 2012 3293 4093 800 2493 100 3293 4193

FAC/FAH/FAG/FAM

Application Guide /FLEXAIR-AGU-1505-E

EX

HA

US

T A

IR

MAIN POWER ENTRY

MAIN POWER ENTRY

ACCESS TO FAN COMPARTMENT

DIMENSIONS

VERTICAL EXHAUST ROOFCURB

11- DIMENSIONS

• 74 •

A

D

E

C

B 90083

A B C D E

85-100-120 2146 2063 1796 1422 367

150-170 2330 2247 2170 1676 463

200-230 2516 2497 2418 1518 623

FAC/FAH/FAG/FAM

Application Guide / FLEXAIR-AGU-1505-E

ENERGY RECOVERY OPTION

DIMENSIONS

11- DIMENSIONS

11��- HEAT RECOVERY OPTION �IMEN�ION�

• 75 •

85 100 120 150 170 200 230966 1055 1054 1454 1550 2027 2143

981 1070 1069 1484 1580 2057 2173

1013 1117 1108 1576 1681 2257 2371

1083 1187 1178 1599 1704 2297 2411

1028 1132 1123 1606 1711 2287 2401

1098 1202 1193 1629 1734 2327 2441

27 27 27 41 41 45 45

14 14 14 19 19 21 21

41 41 41 63 63 67 67

525 525 525 635 635 730 730

654 654 654 775 775 775 775

586 586 586 698 698 698 698

36 36 36 44 44 61 61

6 6 6 11 11 19 19

6 6 6 11 11 19 19

S 47 47 47 57 57 78 78

M 64 64 64 78 78 103 103

H 78 78 78 103 103 143 143

S 34 34 34 52 52 63 63

H 62 62 62 96 96 116 116

94 94 94 108 108 128 128

197 197 197 229 229 272 272

237 237 237 332 332 395 395

SMH

FAC

FAH

FAG (S)

FAG (H)

FAM (S)

FAM (H)

Application Guide /FLEXAIR-AGU-1505-E

12- OPTIONS WEIGHT AND PRESSURE DROPS

SIZE

Basic unit

Airfl ow confi gurationHigh pressure EC Plug Fan

Exhaust air options

Gravity exhaust damper for downfl ow return

Power exhaust fan axial + gravity exhaust damper (downfl ow return)

Heat recovery module (downfl ow and horizontal fl ow)

EC Low Pressure return roofcurb Downfl ow

EC Low Pressure return roofcurb Horizontalfl ow

Filtration option

G4 metallic frame, whashable fi lter

F7 Filters / G4 Prefi lters

G4 Refi lable fi lters

12.1- OPTIONS WEIGHTS

Heating options versus FAC or FAG2 steps electric heater

Modulating electric heater

Hot water coil

Other Options

Non adjustable non assembled roofcurb

Adjustable assembled roofcurb

Multi direction horizontalfl ow curb

Standard heat

Medium heat

High heat

• 76 •

G4 F7 S H

8512000 1 75 9 1515000 7 105 13 2223000 28 199 26 44

10014000 5 94 11 1918500 15 143 18 3123000 28 199 26 44

12015000 7 105 13 2220500 21 167 21 3723000 28 199 26 44

15018000 1 75 6 1026000 12 130 12 1935000 29 204 19 33

17021000 5 94 8 1430000 19 161 15 2535000 29 204 19 33

20024000 3 88 7 1135000 18 154 13 2243000 31 211 19 31

23027000 7 105 8 1439000 24 182 16 2643000 31 211 19 31

S M H H

8512000 3 5 6 14 17 22 16115000 6 7 7 23 27 33 20123000 7 9 11 53 63 73 309

10014000 6 7 8 20 23 30 18718500 8 10 11 34 41 51 24823000 11 14 16 53 63 78 309

12015000 7 8 9 23 27 35 20120500 10 12 13 42 50 62 27623000 12 15 17 53 63 78 309

15018000 4 5 7 16 30 35 16726000 9 10 13 33 62 72 24135000 15 18 23 59 112 131 325

17021000 8 9 10 21 40 49 19430000 10 13 15 44 82 95 27835000 17 19 21 59 112 131 325

20024000 16 15 14 21 53 67 17135000 22 21 20 44 112 133 25043000 24 26 29 66 169 195 307

23027000 18 18 17 26 67 84 19239000 24 24 25 55 139 163 27843000 24 26 29 66 169 195 307

FAC FAHFAG FAM

Application Guide / FLEXAIR-AGU-1505-E

SizeAirfl ow rate Filters Hot water coil

m3/h

SizeAirfl ow rate Electric heater Heating gas

fi red Adjustable roofcurb

Multidirectio-nal roofcurb

Heat recovery module

Fresh airm3/h

Cooling only Heat pumpCooling only with gas fi red heating Heat pump rooftop with gas fi red heating

12- ACCESSORIES PRESSURE DROPS

lennoxemeia.com

+7 495 626 56 53

+34 915 401 810

+38 044 585 59 10

+44 1604 669 100

+ 32 3 633 3045

+33 1 64 76 23 23

+49 (0) 211 950 79 600

+ 39 02 495 26 200

+ 31 332 471 800

+48 22 58 48 610

+351 229 066 050

LENNOX DISTRIBUTION

+33 4 72 23 20 20

RUSSIA

SPAIN

UKRAINE

UNITED KINGDOM AND IRELAND

BELGIUM AND LUXEMBOURG

FRANCE

GERMANY

ITALY

NETHERLANDS

POLAND

PORTUGAL

Due to Lennox’s ongoing commitment to quality, the specifi cations, ratings and dimensions are subject to change without notice and without incurring liability.Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.Installation and service must be performed by a qualifi ed installer and servicing agency

FLEXAIR-AGU-1505-E

SALES OFFICES :

OTHER COUNTRIES :