Application of Static VAr Compensator in Entergy System to Address

Voltage Stability Issues – Planning and Design Considerations

Sharma Kolluri, PE, IEEE Fellow

Entergy Services, Inc.New Orleans, LA

Presentation at IEEE PES Chapter MeetingJackson, Mississippi

October 10, 2012

Page 2: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

2

Presentation Outline

I. Introduction

I. Reactive Power

II. Voltage Stability

II. Study Methodology/Results

III. Solutions Considered

IV. Design/Protection Considerations

V. External Bank Control

VI. Conclusions

Page 3: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

3

Reactive Power Reactive Power

Page 4: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

4

Page 5: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

5

Reactive Power Management/Compensation

What is Reactive Power Compensation?

• Effectively balancing of capacitive and inductive components of a power system to provide sufficient voltage support.

• Static and dynamic reactive power

• Essential for reliable operation of power system – prevention of voltage collapse/blackout

Benefits of Reactive Power Compensation:

• Improves efficiency of power delivery/reduction of losses.• Improves utilization of transmission assets/transmission capacity.• Reduces congestion and increases power transfer capability.• Enhances grid reliability/security.

Page 6: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

6

Static and Dynamic VAR Support• Static Reactive Power Devices

– Cannot quickly change the reactive power level as long as the voltage level remains constant.

– Reactive power production level drops when the voltage level drops.

– Examples include capacitors and inductors.

• Dynamic Reactive Power Devices– Can quickly change the MVAR level independent of the voltage

level.– Reactive power production level increases when the voltage level

drops.– Examples include static VAR compensators (SVC), synchronous

condensers, and generators.

Page 7: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

7

Voltage Stability Voltage Stability

Page 8: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

8

What is Voltage Instability/Collapse?

• A power system undergoes voltage collapse if post-disturbance voltages are below “acceptable limits”

• voltage collapse may be due to voltage or angular instability

• Main factor causing voltage instability is the inability of the power systems to “maintain a proper balance of reactive power and voltage control”

Page 9: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

9

Voltage Instability/Collapse• The driving force for voltage instability is

usually the load• The possible outcome of voltage instability:

– loss of loads – loss of integrity of the power system

• Voltage stability timeframe:– transient voltage instability: 0 to 10 secs– long-term voltage stability: 1 – 10 mins

Page 10: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

10

Voltage stability causes and analysis• Causes of voltage instability :

– Increase in loading

– Generators, synchronous condensers, or SVCs reaching reactivepower limits

– Tap-changing transformer action

– Load recovery dynamics

– Tripping of heavily loaded lines, generators

Page 11: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

11

P-V Curve

Page 12: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

12

Q-V Curve

200

Q-V Curve with Detailed Load ModelPeak Load with Fixed Taps

-80

-60

-40

-20

0

20

40

60

80

100

120

0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5

Voltage (p.u.)

Mva

rs

Base Case

Contingency

Page 13: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

13

Key Concerns

Minimize motor tripping

Limit UVLS activationVoltage

(pu)

Page 14: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

14

Possible Solutions for Voltage Instability

• Install/Operate Shunt Capacitor Banks

• Add dynamic Shunt Compensation in the form of SVC/STATCOM to mitigate transient voltage dips

• Add Series Compensation on transmission lines in the problem area

• Implement UVLS Scheme

• Construct transmission facilities

Page 15: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

15

Voltage Stability Study for Voltage Stability Study for Western RegionWestern Region

Page 16: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

16

Western Region – Overview

138 kV Tie Lines

230 kV Tie Lines

Generation

Load Center

Woodlands Network

New Caney Network

Conroe Network

Page 17: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

17

Study Objective• Assess the nature of the Western Region voltage

instability problem • Analyze and recommend reactive compensation

measures (size, type, location) to mitigate system problems

Page 18: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

18

Key Concerns• Transient Problem

– Minimize motor tripping• Steady State Problem

– Return 138 kV buses post contingency to voltages above 0.92 pu

• Thermal Issues– Avoid thermal

violations

Page 19: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

19

Load Modeling

120 MW0.96 pf

138 kV

Non-Detailed Detailed

59.4 MW 0.95 pf

19.8 MW 0.90 pf

H=0.5

19.8 MW 0.90 pf

H=1.5

19.8 MW 0.90 pf

H=0.5

Power Factor adjustment capacitor

138 kV

13.8 kV

Static load

Trip motor

Fan motor

Pump motor

120 MW 0.96 pf

Page 20: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

20

Critical Contingencies Studied• Lewis Creek Unit 1 out-of-service

• Fault and trip– China – Jacinto 230 kV line– Grimes – Crockett 345 kV line– Lewis Creek Unit 2 – Oakridge – Tamina 138 kV line– Jacinto – Peach Creek 138 kV line

Page 21: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

21

ResultsWithout motor tripping being simulated

Oakridge - Tamina Fault

Voltage = 0.7 pu

LegendGrimesRivtrinNavasotaConroeGoslinOakridge

Voltage (pu)

Page 22: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

22

System recovers to healthy voltages

• Criterion for motor trip : Voltage < 0.7 pu for > 20 cycles

ResultsWith motor tripping being simulated

Oakridge - Tamina Fault

Motors Trip

Voltage (pu)

LegendGrimesRivtrinNavasotaConroeGoslinOakridge

Page 23: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

23

Solutions Considered• System reinforcements to mitigate the

voltage instability with the proposed China-Porter 230 kV series compensated line were:– SVC– STATCOM – Distributed VAR

Page 24: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

24

What is a SVC?• The SVC typically consists of a

– Coupling Transformer– TCR (Thyristor Controlled Reactor) – TSC (Thyristor Switched Capacitor)– ACF (AC Filters)

• TCR continuously controls reactive power by varying the current amplitude flowing through the reactors

• TSC switches the capacitors on and off • AC filters provide fixed reactive power

and absorb the harmonic current generated by TCR

• Output can be asymmetric, e.g. +300 MVAR, -100 MVAR• TCR+ACF is the most basic configuration of the SVC • TCR+TSC+ACF, the more advanced configuration, can be tuned to minimize the

losses at the most frequent operation point• Reactive power control is fast

Page 25: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

25

What is a STATCOM?

• STATCOM consists of – Coupling Transformer– Inverter Bridge – DC capacitor

• Output is always symmetric, e.g. ±100 MVAR

• Reactive power control is fast and continuous from inductive to capacitive through the adjustment of the inverter AC voltage output

Page 26: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

26

What are Distributed VARs?• They are smaller size of SVC or STATCOM at

the distribution level– DVAR: Distribution level STATCOM– AVC (Adaptive VAR Compensator): Distribution

level SVC• Distributing VAR support where it is needed – closer

to loads

Page 27: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

27

Recommendation• SVC was the most suitable solution for the problem in

the Western Region• Reasons

– Total dynamic and steady state VAR requirement for this area is very large

– Traditionally SVCs are applied to address voltage problem in large area whereas distributed solutions are applied to provide local voltage support

– SVC has a proven track record (> 1,000 installations) – matured technology

– SVC is capable of damping power system oscillation– SVC can be used under light load conditions for voltage regulation,

thereby avoiding capacitor switching

Page 28: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

28

Details of SVC Solution

• Full dynamic range required– SVC must be normally at zero output during

peak load conditions• Size

– Dynamic: 300 MVAR– Steady State: 210 MVAR

• Location – Porter 138 kV station

Page 29: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

29

Typical SVC Configuration

LV bus bar

Fixed filter circuit

Thyristor controlledreactor

Thyristor switchedcapacitor

Control

Step-down transformer

HV

LV

Page 30: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

30

Porter Static VAR Compensator(SVC)

• Main Components– Step Down Transformers– Capacitors– Cooling System– Thyristors

• Switching Logic– Voltage Control– Reactive Power Control

• Coordinated Remote Capacitor Switching– Issues – Implementation

Page 31: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

31

Porter SVC Configuration

SN = 300 MVA, uk = 9.5 %

3AC 60Hz 230kV

3AC 60Hz 15.5kV

CTSC2

LTSC2

TSC 2

V2

VR2

TSC 1

CTSC3

LTSC3

TSC 3

V3 VR3

CTSC1

LTSC1

V1

VR1

= 75 MVAr = 75 MVAr = 150 MVAr

138kV

Page 32: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

32

SVC Performance Dynamic Rating

Jacinto – Peach Creek Fault

VAR output of the SVC

Voltage (pu)

LegendGrimesRivtrinNavasotaConroe

Page 33: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

33

SVC Performance Steady State Rating Two Lewis Creek Units Out

Voltage (pu)

VAR output of the SVC

210 MVAR

LegendGrimesRivtrinNavasotaConroeCorrigan

Page 34: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

34

Switching Steps of the SVCOperation Mode

# TSC 3

TSC 2

TSC 1

Reactive Power (Q)

8 0 0 0 0 MVAr

7 0 0 1 75 MVAr

6 0 1 0 75 MVAr

5 0 1 1 150 MVAr

4 1 0 0 150 MVAr

3 1 0 1 225 MVAr

2 1 1 0 225 MVAr

1 1 1 1 300 MVAr

Page 35: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

35

External Device ControlSingle line diagram of SVC and MSC

Porter 138 kV

as

Page 36: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

36

Porter

Metro

Conroe

Tamina

Goslin

Oak Ridge

SV

C

BM TOCSCADA

Host

•kV•CB Status•Availability

Cap Banks to Operate

Coordinated Cap bank Control

Page 37: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

37

SVC Operation Modes• Manual Mode or Fixed Susceptance mode

(FS mode) - Qreg is given by the fixed susceptance reference setting FSref

• Automatic Mode – Reactive Power control mode (Q mode) -

Adjust the voltage reference (Vref) setpoint to maintain the Qreg = Qref

– Voltage mode (V mode) - fast voltage control mode that can override the Q-control mode

Page 38: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

38

SVC Operation• SVC operates in the automatic mode • Vref of the SVC set at 141 kV (1.02 pu)

– This enables the SVC to dispatch itself so that the voltage doesn’t drop much below the Vref (remember 2% slope)

• Qref will be a function of the western region load– This will let the SVC switch the externally

controlled capacitor banks and maintain adequate VAr reserve at the SVC

Page 39: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

39

VACT

VREF

VQSlow Q control(when enabled)

Qsvc Slope adjustment

Stability controller

Gain controller

Dead-band controller

QSVC

Susceptance calculator

Mode select

BSVC

V

Simplified Primary Voltage Controller Schematic

Page 40: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

40

SVC Control

• Voltage Control

– Responds to voltage fluctuations– Fast response, restoring voltage within 3

cycles– Employs stability controller– Unaffected by the QREF setting

Page 41: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

41

SVC Control

• Q Control– Used to maintain the dynamic range of the

SVC and to maintain an efficient operating point

– Unaffected by the VREF Setting– Slow response– Controls the operating point of the SVC– Controls the coordinated switching of the

remote capacitor banks

Page 42: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

42

Porter SVC

Page 43: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

43

SVC Panel HMI

Page 44: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

44

Ninemile SVCSVC Site

Ninemile Switchyard

Page 45: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

45

Ninemile SVC

Coupling Transformers

Page 46: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

46

Ninemile SVC

Thyristor Switched Capacitor Bank

Page 47: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

47

Ninemile SVC

Page 48: Application of Static VAr Compensator in Entergy …...Thyristor switched capacitor Control Step-down transformer HV LV 30 Porter Static VAR Compensator (SVC) • Main Components –

48