Approved Connector Installation Guide Presentation

Embed Size (px)

Citation preview

Page 1: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 1/35

Connector Installation Guide For

Compression and Mechanical Connectors

Page 2: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 2/35

Connector Installation Guide For

Compression and Mechanical Connectors

Page 3: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 3/35

Typical Cross Section of a

Compression Connector Before

Installation 

Before compression, a

typical cross section ofcable consists of 75%

metal and 25% air

Connector Installation Guide For

Compression Connectors

Page 4: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 4/35

Typical Cross Section of a

Compression Connector After

Installation After compression, little

air is left.

Connector Installation Guide For

Compression Connectors

Page 5: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 5/35

1 - 2 hole lug 

H-Taps

C-Taps Narrow Tongue Belled-End 

Grid Grounding  BatteryTerminals 

Splices

Connector Installation Guide For

Compression Connectors

Connector Types

Page 6: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 6/35

1. Determine Proper Connector For Cable* Conductor size and CU = Copper conductors only

* Conductor size and “AL9” = Aluminum conductors only 

* Conductor size and “AL9CU” = Aluminum or Copper

conductors

* Match size and type of conductor to proper lug

Note: Consult manufacturers instructions on whether fine

stranded conductors or welding cable conductor types may be

used.

Connector Installation Guide For

Compression Connectors

Page 7: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 7/35

 

* Manufacturer

* Wire Size

* Wire material- CU, AL, or

AL9CU (indicates Dual Rating and 90° C)

* Optional Crimp Indicator Bands

* Listing Information

Marking Information on Connectors: 

Connector Installation Guide For

Compression Connectors

Page 8: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 8/35

2. Strip and Properly Prepare Cable*Strip insulation carefully to avoid nicking strands.

*Strip to proper length so conductor can be fully inserted.

*Refer to manufacturers instructions for strip length.

*Most connectors are suitable for one conductor. Never installmore than one conductor unless specifically allowed by the

manufacturer’s instructions. 

*Aluminum Conductor – 

*Brush the stripped portion of the conductor to remove oxide

film using a stainless steel wire brush.

*Apply oxide inhibitor compound and wire brush into thestranding. Do not remove pre-filled inhibitor from the barrel.

Connector Installation Guide For

Compression Connectors

Page 9: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 9/35

Connector Installation Guide For

Compression Connectors

Page 10: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 10/35

3. Select proper installing die tool 

*Always refer to the connector manufacturer’s instructions for the

proper compression die that is intended for the connector.*Manufacturers may use colored bands or dots that correspond to

color markings on dies.

*Manufacturers may use die code number marked or stamped on

the connector.

*Knurls may be used in place of colored bands.

Connector Installation Guide For Compression ConnectorsConnector Installation Guide For

Compression Connectors

Page 11: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 11/35

4. Locate tool with correct die in proper position

on connector and activate tool

*Connectors that are banded with colored stripes to indicatenumber and location of each crimp.

*Connectors may also be marked with the die code number

at each compression location.

*Follow manufacturers instructions whether to crimp on the

colored bands or between the colored bands.

Connector Installation Guide For

Compression Connectors

Page 12: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 12/35

4. Continued…. 

When crimped, the die code number or other marking will be

embossed on connector for easy inspection to determine if correct

die and connector combination were used.

Connector Installation Guide For

Compression Connectors

Page 13: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 13/35

Select proper installing die-less tool 

* Crimp as directed by the manufacturer’s

instructions.

4a. Die-less Tools

Connector Installation Guide For

Compression Connectors

Page 14: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 14/35

Use a 2-hole connector if there is a

concern for twisting the connection.

5. Connector Securement

Connector Installation Guide For

Compression Connectors

Page 15: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 15/35

Connector Installation Guide For

Mechanical Connectors

Page 16: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 16/35

 

Overhead

Transformer

Single

Conductor

Lug

Stud Type Transformer

Double

Conductor

Lug

Double

Conductor

Lug, NEMA

Pad

Copper

SingleConductor

Lug

Connector Installation Guide For

Mechanical Connectors

Connector Types

Page 17: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 17/35

 

* Manufacturer’s name or Symbol 

* Wire Size or range

* Wire material- CU, AL, or Both* Temperature Rating if applicable

* AL9CU Shows Dual Rating (Al & Cu) and 90°C

* UL and/or CSA if it is a listed connector

Marking Information on Connectors: 

Connector Installation Guide For

Mechanical Connectors

Page 18: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 18/35

1. Unlike Compression connectors, mechanical connectors typicallytake a range of conductors. It is important to check that the cablefalls within the cable range listed on the connector.

2. If the connector is intended to be used on a bus, pad or equipment,mount the connector and tighten the mounting hardware per themanufacturer’s specifications. 

Connector Installation Guide For

Mechanical Connectors

Page 19: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 19/35

3.Strip and Properly Prepare Cable*Strip insulation carefully to avoid nicking strands

*Strip to proper length so conductors can be fully inserted*Refer to manufacturers instructions for strip length

*Aluminum Conductor – 

Brush the stripped portion of the conductor to remove

oxide film with a stainless steel wire brush. Apply oxide

inhibitor compound and wire brush into the stranding

Connector Installation Guide For

Mechanical Connectors

Page 20: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 20/35

• 4. Insert the conductor (s) and tighten all set screws per themanufacturer’s recommendations.

* Do not retighten after properly torqued.

* Most connectors are suitable for one conductor. Never installmore than one conductor unless specifically allowed by themanufacturers instructions.

* Use the mounting bolt size as recommended by themanufacturer.

Connector Installation Guide For

Mechanical Connectors

Page 21: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 21/35

Split BoltsGenerally used as taps.

* If conductors are different materials,

a spacer bar is included. Aluminum conductorshould always be positioned on top.

Connector Installation Guide For

Mechanical Connectors

Page 22: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 22/35

* Voltage Rating (Insulated Only)

* 300 volts

* 600 volts

* 1000 volts signs/luminaires

* Note: NOT MARKED

Un-insulated listed connectors are suitable for2,000 volts. They may be used over 2,000 voltsup to 35,000 volts where the effects of coronahave been investigated.

Connector Installation Guide

Connector Ratings

Page 23: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 23/35

* Non-insulated Temperature Rating

 – 75°C -Use the connector at 75°C ampacity

 – 90°C -Use the connector at 90°C ampacity

* Higher temp rated conductors at higherambient temperatures may be used aslong as the ampacity levels are used per

the connector rating.* Use the NEC® to obtain the conductorampacity ratings.

Connector Installation Guide

Connector Ratings

Page 24: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 24/35

* Insulated Temperature Rating

* Never exceed the temperature rating of an

insulated connector. See Packaging or

Product for the marking.

Connector Installation Guide

Connector Ratings

Page 25: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 25/35

* Conductor Material

* AL 9 Aluminum 90°C

* AL9CU CU9AL Aluminum/Copper 90°C

* AL7 Aluminum 75°C

* AL7CU CU7AL Aluminum/Copper 75°C

CU9AL

Connector Installation Guide

Connector Rating Marking

Page 26: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 26/35

* Grounding

* DB Direct Burial

* The connector is suitablefor direct burial in the soil

or embedded in concrete.

Connector Installation Guide for

Grounding Connectors

Page 27: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 27/35

DB = Direct Burial

Suitable Conductor

Compression Die Information

Connector Installation Guide for

Grounding Connectors

Page 28: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 28/35

Grounding Connections

* Look for the product markings for suitability

for attachment to rods, pipe, and concrete

encased reinforcement steel.

Connector Installation Guide For

Compression and Mechanical ConnectorsConnector Installation Guide for

Grounding Connectors

Page 29: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 29/35

Grounding Connections

Rod size

Conductor size

onnector Installation Guide

for Grounding onnectors

Page 30: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 30/35

• Grounding Connections

Connector Installation Guide For

Grounding Connectors

Direct burial

Conductor size

Rebar size

Page 31: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 31/35

SAFETY STANDARDS

Connector Installation Guide For

Compression and Mechanical Connectors

Page 32: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 32/35

Safety Standards 

Wire Connectors UL 486A-486B

CSA C22.2 No. 65

ANCE NMX-J-543

Splicing Wire ConnectorsUL 486C

CSA C22.2 No. 188

ANCE NMX-J-548

Grounding and Bonding Equipment 

UL 467

CSA C22.2 No. 41

ANCE NMX-J-567

Connector Installation Guide For

Compression and Mechanical Connectors

Page 33: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 33/35

 

Electrical Connector Section

• Connector Castings Inc.

• Connector Mfg. Co.

• Cooper Power Systems

• ERICO, Inc.

• Galvan Industries, Inc.

•Homac Mfg. Co.

• Hubbell Power Systems,

Inc.

• Ilsco

• FCI/BURNDY

• MacLean Power Systems

• Panduit Corporation

• Sicame

•South Atlantic/SouthernGrounding

• Thomas & Betts Corp.

• Tyco Electronics

Page 34: Approved Connector Installation Guide Presentation

8/10/2019 Approved Connector Installation Guide Presentation

http://slidepdf.com/reader/full/approved-connector-installation-guide-presentation 34/35