METAL FRAMED MIRROR 18"X36" HORIZONTAL GRAB BAR-36" PAPER TOWEL DISPENSER PVC SHOWER CURTAIN ROD 45 GRAB BAR METAL FRAMED 2'-9" G H I J K NAPKIN DISPOSAL UNIT FEM. MECHANISMS MAX 48" A.F.F. TELEPHONE SHALL HAVE OPERATING AND WATER COOLERS, HDCP ACCESSIBLE ACTUAL LOCATIONS OF TELEPHONES SEE FLOOR PLANS FOR 3'-4" 3'-4" SHOWER TOWEL 6'-7" CURTAIN ROD. CABINET A B DISPENSER SOAP NOTE: SHOWER SEAT 15" MIN. GRAB BAR 17"-19" HCAP 2'-9" 2'-2" C 2'-3" MIN. HC LAV 1'-6 1/2" MIRROR D TOILET TISSUE DISPENSER GRAB BAR HORIZ. TOILET ACCESSORY LEGEND METAL FRAMED MIRROR 18"X36" TOILET TISSUE DISPENSER FEMININE NAPKIN DISPOSAL UNIT SOAP DISPENSER GRAB BAR-42" F. ROBE HOOK C. E. D. B. A. CABINETS TELEPHONE STANDARD L. SHOWER SEAT I K. J. G. H. 3'-4" 48" L M 3'-0" 34"MAX. 2'-0" 45 GRAB BAR 2'-0" 3'-0" E MOP RACK 3'-4" F MIRROR W/SHELF HC LAV METAL FRAMED 4'-6" HOOK ROBE H.C. TO HDCP. ACCESSIBLE COOLER MOP RACK M. TOE & KNEE CLEARANCE 8" 9" MIN. MIN. 11" MIN. 2'-3" MIN. 48" MAX. 40" SHELF TACTILE SIGNS 1'-6" 4' 5' MAX RESTROOM MIN. FROM HIGHEST TACTILE CHAR. WATER 36" SERVICE COUNTER MAX. 34" BUILT-IN WRITING SURFACE MAX. EXP. EXPANSION FIRE EXTINGUISHER IN CABINET GYPSUM HOLLOW METAL FINISHED FLOOR FACE OF STUD FIRE RETARD ANT GALVANIZED GALVANIZED IRON FIRE EXTINGUISHER EXTERIOR HORIZONTAL HORIZ. HR. HOUR GYP. H.M. G.I. F.O.S. GALV. F.R. F.E.C. F.F. FL. EXT. F.E. FLOOR CHALKBOARD OR CATCH BASIN CONSTRUCTION JOINT ABOVE FINISHED FLOOR BY OTHERS OR BY OWNERS ALUMINUM ADJUSTABLE ACOUSTICAL ELECTRICAL WATER COOLER CONCRETE MASONRY UNIT ELEVATION OR ELEVATOR CONTINUOUS EXPANSION JOINT ELECTRICAL COLUMN CONCRETE CLG. CEILING EA. EACH ELEV. E.W.C. EQ. ELEC. E.J. EQUAL CONC. CONT. DET. C.M.U. COL. DETAIL ALUM. B.O. C.B. C.J. BD. BM. BOARD BEAM A.F.F. ADJ. ACOUS. REQ'D. VINYL WALL COVERING V.W.C. VENDING VERIFY ON JOB REQUIRED SHEET SIMILAR SPECIFICATION SQUARE STRUCTURAL SUSPENDED TOILET PAPER HOLDER URINAL STRUCT. V.O.J. VEND. UR. T.P.H. SUSP. ST'L. SQ. SPECS. SIM. SH'T. STEEL MULL. MULLION REFRIGERATOR REINFORCING NATURAL NUMBER NOT TO SCALE ON CENTER OPPOSITE HAND PLASTER OR PLASTIC PLASTIC OUNCE REF. REINF. RE. PL. PLAS. OZ. REFER O.C. O.H. N.T.S. NAT. NO. MASONRY OPENING METAL INSULATION LAMINATE LAVATORY MAXIMUM MECHANICAL MINIMUM METAL LATH MAX. M.L. M.O. MTL. MECH. MIN. INSUL. LAM. LAV. FIRE ALARM SYSTEM SUBMITTAL: SUBMITTAL SHALL INCLUDE THE FOLLOWING INFORMATION: 1. DRAWINGS SHALL BE SIGNED AND SEALED BY A LICENSED ENGINEER REGISTERED IN THE STATE WHERE PROJECT IS LOCATED. 2. DRAWINGS SHALL INDICATE REQUIRED CODES FOR COMPLIANCE. 3. FLOOR PLANS LOCATING ALL DEVICES AND EQUIPMENT 4. ALARM CONTROL AND TROUBLE SIGNALING DEVICES 5. ANNUNCIATION 6. POWER CONNECTION 7. BATTERY CALCULATIONS 8. CONDUCTOR TYPES AND SIZES 9. VOLTAGE DROP CALCULATIONS 10. MANUFACTURERS, MODEL NUMBERS AND LISTING INFORMATION FOR EQUIPMENT DEVICES AND MATERIALS 11. DETAILS OF CEILING HEIGHT AND CONSTRUCTION 12. THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS 13. ALL DETAILS NECESSARY TO PROPERLY INSTALL SYSTEM 14. SUBMIT DRAWINGS TO FIRE MARSHAL, BUILDING DEPT. OR OTHER GOVERNING AUTHORITIES AS REQUIRED BY EACH 15. SUBMIT ONE SET TO ARCHITECT FOR THEIR RECORDS FIRE SUPPRESSION SYSTEM SUBMITTAL: SUBMITTAL SHALL INCLUDE THE FOLLOWING INFORMATION: 1. DRAWINGS SIGNED AND SEALED BY A LICENSED ENGINEER REGISTERED IN THE STATE WHERE PROJECT IS LOCATED. 2. CALCULATIONS SIGNED AND SEALED BY A LICENSED ENGINEER REGISTERED IN THE STATE WHERE PROJECT IS LOCATED. 3. DRAWINGS SHALL INDICATE REQUIRED CODES FOR COMPLIANCE. 4. FLOOR PLANS LOCATING ALL SPRINKLER HEADS AND PIPING LAYOUT 5. DRAWING SHALL INCLUDE COMPLETE SEISMIC SUPPORT DETAILS 6. ALL DETAILS NEEDED TO INSTALL SYSTEM 7. IDENTIFICATION METHOD FOR ALL ROOMS AND EQUIPMENT. 8. FLOOR PLANS. ASCENSION PARISH DPW BUILDING RETROFIT ASCENSION PARISH COUNCIL MEMBERS: KENNY MATASSA: PARISH PRESIDENT COUNCIL MEMBERS Oliver Joseph, District 1 Bill Dawson, District 2 Travis Turner, District 3 Fcpkgn ÐFqeÑ Ucvvgtngg. Fkuvtkev 6 Dempsey Lambert, District 5 Randy Clouatre, District 6 Aaron Lawler, District 7 Teri Casso, District 8 Todd Lambert, District 9 John Cagnolatti, District 10 Benny Johnson, District 11

ASCENSION PARISH DPW BUILDING RETROFITascensionparish.net/downloads/purchasing/042816drawings2.pdf · 2016. 4. 28. · rr160 jan161 rr163 vest.162 148 office 139 rr135 rr136 corridor

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ASCENSION PARISH DPW BUILDING RETROFITascensionparish.net/downloads/purchasing/042816drawings2.pdf · 2016. 4. 28. · rr160 jan161 rr163 vest.162 148 office 139 rr135 rr136 corridor

METAL FRAMED MIRROR 18"X36"

HORIZONTAL GRAB BAR-36"

PAPER TOWEL DISPENSER

PVC SHOWER CURTAIN ROD

45 GRAB BAR

METAL FRAMED

2'-9"

G H I J K

NAPKIN

DISPOSAL

UNIT

FEM.

MECHANISMS MAX 48" A.F.F.

TELEPHONE SHALL HAVE OPERATING

AND WATER COOLERS, HDCP ACCESSIBLE

ACTUAL LOCATIONS OF TELEPHONES

SEE FLOOR PLANS FOR

3'-4"

3'-4"

SHOWER TOWEL

6'-7"

CURTAINROD.

CABINET

A B

DISPENSERSOAP

NOTE:

SHOWERSEAT

15" MIN.

GRAB BAR

17"-19" HCAP

2'-9"

2'-2"

C

2'-3" MIN.

HC LAV

1'-6 1/2"

MIRROR

D

TOILET

TISSUE

DISPENSER

GRAB BAR

HORIZ.

TOILET ACCESSORY LEGEND

METAL FRAMED MIRROR 18"X36"

TOILET TISSUE DISPENSER

FEMININE NAPKIN DISPOSAL UNIT

SOAP DISPENSER

GRAB BAR-42"

F.

ROBE HOOK

C.

E.

D.

B.

A.

CABINETSTELEPHONESTANDARD

L.

SHOWER SEAT

I

K.

J.G.

H.

3'-4"48"

L M

3'-0"34"MAX.

2'-0"

45 GRAB BAR

2'-0"3'-0"

E

MOP RACK

3'-4"

F

MIRROR W/SHELF

HC LAV

METAL FRAMED

4'-6"

HOOK ROBE

H.C.

TO HDCP.ACCESSIBLE

COOLER

MOP RACKM.

TOE & KNEE CLEARANCE

8"

9"

MIN.

MIN

.

11"MIN.

2'-3"

MIN

.

48" MAX.

40"

SHELF

TACTILE SIGNS

1'-6"

4'

5' M

AX

RESTROOM

MIN

.

FR

OM

HIG

HE

ST

TA

CT

ILE

CH

AR

.

WATER

36"

SERVICE COUNTER

MAX. 34"

BUILT-IN WRITING SURFACE

MAX.

EXP. EXPANSION

FIRE EXTINGUISHER IN CABINET

GYPSUM

HOLLOW METAL

FINISHED FLOOR

FACE OF STUD

FIRE RETARD ANT

GALVANIZED

GALVANIZED IRON

FIRE EXTINGUISHER

EXTERIOR

HORIZONTALHORIZ.

HR. HOUR

GYP.

H.M.

G.I.

F.O.S.

GALV.

F.R.

F.E.C.

F.F.

FL.

EXT.

F.E.

FLOOR CHALKBOARD OR CATCH BASIN

CONSTRUCTION JOINT

ABOVE FINISHED FLOOR

BY OTHERS OR BY OWNERS

ALUMINUM

ADJUSTABLE

ACOUSTICALELECTRICAL WATER COOLER

CONCRETE MASONRY UNIT

ELEVATION OR ELEVATOR

CONTINUOUS

EXPANSION JOINT

ELECTRICAL

COLUMN

CONCRETE

CLG. CEILING

EA. EACH

ELEV.

E.W.C.

EQ.

ELEC.E.J.

EQUAL

CONC.

CONT.

DET.

C.M.U.

COL.

DETAIL

ALUM.

B.O.

C.B.

C.J.

BD.BM.

BOARD

BEAM

A.F.F.

ADJ.

ACOUS.

REQ'D.

VINYL WALL COVERINGV.W.C.

VENDING

VERIFY ON JOB

REQUIRED

SHEET

SIMILAR

SPECIFICATION

SQUARE

STRUCTURAL

SUSPENDED

TOILET PAPER HOLDER

URINAL

STRUCT.

V.O.J.

VEND.

UR.

T.P.H.

SUSP.

ST'L.

SQ.

SPECS.

SIM.

SH'T.

STEEL

MULL. MULLION

REFRIGERATORREINFORCING

NATURAL

NUMBER

NOT TO SCALE

ON CENTER

OPPOSITE HAND PLASTER OR PLASTIC

PLASTIC OUNCE

REF.REINF.

RE.

PL.

PLAS.

OZ.

REFER

O.C.

O.H.

N.T.S.

NAT.

NO.

MASONRY OPENING

METAL

INSULATION

LAMINATE

LAVATORY

MAXIMUM

MECHANICAL

MINIMUM

METAL LATH

MAX.

M.L.

M.O.

MTL.

MECH.

MIN.

INSUL.

LAM.

LAV.

FIRE ALARM SYSTEM SUBMITTAL:

SUBMITTAL SHALL INCLUDE THE FOLLOWING INFORMATION:

1. DRAWINGS SHALL BE SIGNED AND SEALED BY A LICENSED ENGINEER REGISTERED IN THE

STATE WHERE PROJECT IS LOCATED.

2. DRAWINGS SHALL INDICATE REQUIRED CODES FOR COMPLIANCE.

3. FLOOR PLANS LOCATING ALL DEVICES AND EQUIPMENT

4. ALARM CONTROL AND TROUBLE SIGNALING DEVICES

5. ANNUNCIATION

6. POWER CONNECTION

7. BATTERY CALCULATIONS

8. CONDUCTOR TYPES AND SIZES

9. VOLTAGE DROP CALCULATIONS

10. MANUFACTURERS, MODEL NUMBERS AND LISTING INFORMATION FOR EQUIPMENT DEVICES AND

MATERIALS

11. DETAILS OF CEILING HEIGHT AND CONSTRUCTION

12. THE INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS

13. ALL DETAILS NECESSARY TO PROPERLY INSTALL SYSTEM

14. SUBMIT DRAWINGS TO FIRE MARSHAL, BUILDING DEPT. OR OTHER GOVERNING AUTHORITIES

AS REQUIRED BY EACH

15. SUBMIT ONE SET TO ARCHITECT FOR THEIR RECORDS

FIRE SUPPRESSION SYSTEM SUBMITTAL:

SUBMITTAL SHALL INCLUDE THE FOLLOWING INFORMATION:

1. DRAWINGS SIGNED AND SEALED BY A LICENSED ENGINEER REGISTERED IN THE STATE WHERE

PROJECT IS LOCATED.

2. CALCULATIONS SIGNED AND SEALED BY A LICENSED ENGINEER REGISTERED IN THE STATE

WHERE PROJECT IS LOCATED.

3. DRAWINGS SHALL INDICATE REQUIRED CODES FOR COMPLIANCE.

4. FLOOR PLANS LOCATING ALL SPRINKLER HEADS AND PIPING LAYOUT

5. DRAWING SHALL INCLUDE COMPLETE SEISMIC SUPPORT DETAILS

6. ALL DETAILS NEEDED TO INSTALL SYSTEM

7. IDENTIFICATION METHOD FOR ALL ROOMS AND EQUIPMENT.

8. FLOOR PLANS.

ASCENSION PARISH

DPW BUILDING RETROFIT

ASCENSION PARISH COUNCIL MEMBERS:

KENNY MATASSA: PARISH PRESIDENT

COUNCIL MEMBERS

Oliver Joseph, District 1

Bill Dawson, District 2

Travis Turner, District 3

Fcpkgn"ÐFqeÑ"Ucvvgtngg."Fkuvtkev"6Dempsey Lambert, District 5

Randy Clouatre, District 6

Aaron Lawler, District 7

Teri Casso, District 8

Todd Lambert, District 9

John Cagnolatti, District 10

Benny Johnson, District 11

Page 2: ASCENSION PARISH DPW BUILDING RETROFITascensionparish.net/downloads/purchasing/042816drawings2.pdf · 2016. 4. 28. · rr160 jan161 rr163 vest.162 148 office 139 rr135 rr136 corridor

GENERATOR

WATER FOUNTAINS

WATER FOUNTAINS

WATER HEATER

A/C UNIT

A/C UNIT

A/C UNIT

A/C UNIT

A/C UNIT

A/C UNIT

scale : 3/16"=1'-0"01.

CONDITIONED 10,664 SF

UNDER ROOF 10,954 SF

cvjmejoh"trvbsf"gppubhf

OFFICE 131RHONDA B &BOB T

OFFICE 130INSPECTORS & ANGIE C.

OFFICE 128RHONDA M.

CLOSET 129

OFFICE 127

COFFEE 137OFFICE 132

DARREL P.OFFICE 138

TRANS.ENG.

COVERED

ENTRY

145

OFFICE 126TACIE

OFFICE 125LIZ

LOBBY 101

OFFICE 123JOEY-Chief Eng.

OFFICE 122

OFFICE 109BARBARA

COPY 108COPIER

OFFICE 102 OFFICE 103

OFFICE 104ALCS

OFFICE 107TAMMY M. +1

MECHANICAL

OFFICE SUPPLIES112

WAITING 119

ASSEMBLY 116

CORRIDOR 111

CORRIDOR 110

SHARED CONFERENCE

140OFFICE 144BILL ROUX

CO

RR

IDO

R

141

CORRIDOR 150

OFFICE 143

RECEP.

147BARBARADRAINAGE

LOBBY

146

OFFICE 158

CO

RR

IDO

R

157

OFFICE 156 OFFICE 155

OFFICE

154

OFFICE 151

OFFICE

152 OFFICE 153 OFFICE 120

RR105RR106

RR114

FILES 113

RR115

SERVER 121

OFFICE 149

FIL

ES

142

ELE

C 1

59

RR160

JAN161

RR163 VEST.162

148

OFFICE 139

RR136RR135

CO

RR

IDO

R 1

33

CLOSET 117CLOSET 118

CORRIDOR 124

HVAC 134

ROGER

PAULTHAD

RON S.

STEVEN B.

MIKE T.

ALLEN

HEATHER

EXISTING TO REMAIN

EXISTING TO BE REMOVED

Page 3: ASCENSION PARISH DPW BUILDING RETROFITascensionparish.net/downloads/purchasing/042816drawings2.pdf · 2016. 4. 28. · rr160 jan161 rr163 vest.162 148 office 139 rr135 rr136 corridor

WATER FOUNTAINS

WATER FOUNTAINS

WATER HEATER

A/C UNIT

A/C UNIT

A/C UNIT

A/C UNIT

scale : 3/16"=1'-0"01.

CONDITIONED 10,664 SF

UNDER ROOF 10,954 SF

trvbsf"gppubhf

OFFICE 131RHONDA B &BOB T

OFFICE 130INSPECTORS & ANGIE C.

OFFICE 128RHONDA M.

CLOSET 129

OFFICE 127

COFFEE 137OFFICE 132

DARREL P.OFFICE 138

TRANS.ENG.

COVERED

ENTRY

145

OFFICE 126TACIE

OFFICE 125LIZ

OFFICE 101

OFFICE 123JOEY-Chief Eng.

OFFICE 122TRANSCROS

OFFICE 109

COPY 108COPIER

OFFICE 102

OFFICE 104ALCS

OFFICE 107TAMMY M. +1

MECHANICAL

OFFICE SUPPLIES112

WAITING 119

ASSEMBLY 116

CORRIDOR 111

CO

RR

IDO

R 1

10

SHARED CONFERENCE

140OFFICE 144BILL ROUX

CO

RR

IDO

R

141

CORRIDOR 150

OFFICE 143

RECEP.

147BARBARADRAINAGE

LOBBY

146

OFFICE 158

CO

RR

IDO

R

157

OFFICE 156 OFFICE 155

OFFICE 151 OFFICE 152 OFFICE 120

RR105RR106

RR114

FILES 113

RR115

SERVER 121

OFFICE 149

FIL

ES

142

ELE

C 1

59

RR160

JAN161

RR163 VEST.162

148

OFFICE 139

RR136RR135CO

RR

IDO

R 1

33

CLOSET 117CLOSET 118

CORRIDOR 124

HVAC 134

ROGER

5 PERSON OFFICEANTHONY,PELE, JOHN, CHARLES +1

5 PERSON OFFICETHAD, BRIAN, TRENT,KENTRELL,DANA

PAULTHAD

RON S.

STEVEN B.

MIKE T.

DEBORAH

ALLEN

ENLOW

11'-1

1 2"

9"

10'-11"

10'-11"

3'

8'-4"

3'

3'

4'-8"

16'-5

1 2"

14'-312"

3'

NOTE:

1. PROVIDE CONT. HORIZONTAL REINFORCING @ 2'-0" o.c.

2. USE #4 VERTICAL ROD @ 2'-0"o.c. TIE TO ANCHOR ROD

3. VERIFY CMU THICKNESS ON SITE PRIOR TO BIDDING

VERTICALLY REINFORCE

WALL BY #3 BARS @ 24"o.c.

8" CMU BLOCK

FILL ONLY CELLS REBSR

PASSES THRU WITH 2,500

PSI GROUT

SOUND BATT INSULATION

20 GAUGE, 3-5/8"

METAL STUDS @ 16" o.c.

5/8" GYPSUM BOARD EACH SIDE

5/8 GREEN GYP. BD. AT ALL WET AREAS

EXTEND WALL TO 9'-6 V.O.J.

NOTE:

1. PROVIDE JAMB EXTENSIONS FOR EXISTING DOORS AND

WINDOWSEXISTING CMU BLOCK

7/8" METAL FURRING

58" GYPSUM WALL BOARD

P1

P1

P1

P1

P1

P1

P1

3' 3'3'-1012"

3'

P2

P3

P2

P2

P2

P2

P2

P2

P2

P2

P3

P3

P3

P3

P3

P3

P3

P3

P3

P3

P3

8A3

3A3

4A3

6A3

5A3

6A-3

F-1

F-2

F-1

F-2F-2F-2

F-2

F-2

F-2

F-2

F-2

F-2

F-2

F-2

F-1

F-2

F-2

F-2

F-2

F-2

F-2

F-2

F-2 F-2

F-2

F-2

F-2

F-2

F-2

F-2

F-2

A3

2

F-2

F-2

F-2

5' 13'-012" 17'-4"

11'-11"

EXISTING CONSTRUCTION

TO REMAIN

NEW CONSTRUCTION

HW-1

HW-1 ACCESS CONTROL DOOR HARDWARE

PROVIDE ACCESS CONTROL SYSTEM

FIRMWARE AND SOFTWARE FOR A

COMPLETELY OPERATIONAL ACCESS

CONTROL & SECURITY SITE MANAGEMENT

SYSTEM. SEE SPECIFICATION

ALL OTHER DOORS SHALL RECEIVE NEW

LOCKING CORES WITH NEW KEYING

A3

1

HW-1

HW-1

HW-1

HW-1

HW-1

Page 4: ASCENSION PARISH DPW BUILDING RETROFITascensionparish.net/downloads/purchasing/042816drawings2.pdf · 2016. 4. 28. · rr160 jan161 rr163 vest.162 148 office 139 rr135 rr136 corridor

scale : 1/4"=1'-0"03.

OFFICE 131

OFFICE 158

CO

RR

IDO

R

157

OFFICE 156 OFFICE 155

ELE

C 1

59

CONFERENCE 140

OFFICE 144

OFFICE 149RM 148

OFFICE 151

OFFICE 152

scale : 1/4"=1'-0"04.

scale : 1/4"=1'-0"06.

scale : 1/4"=1'-0"05.

scale : 1/4"=1'-0"07.

scale : 1/4"=1'-0"08

fmfdusjdbm""mfhfoe

COUNTER TOP RECEPTICAL

DUPLEX RECEPTACLE 18" AFF TYP.

MATCH EXISTING RECEPTACLE COVERPLATES

FLOOR RECEPTICAL

TELEPHONE /DATA JACK

PLUG MOLD

COAX CABLE

CONDUIT RUN BELOW FLOOR

OR SLAB

CONDUIT CONCEALED IN WALL OR

CEILING

INDIVIDUAL CIRCUIT RUN DIRECTLY

TO ONE PANEL FROM THIS POINT

EXISTING

ELECTRICAL

PANELS

21'-412"

6'-11"

7'-412" 14'

7'-1" 14'-6"

11'-1

1 2"

6'-11"7'-6"7'-2"

PLASTIC LAM ON 3/4'PLYWOOD COUNTER TOP

WRAPPED

2'-2"

EDGE

scale : 1"=1'-0"16.

2"

2'-3"

1'-6"

4"

2'-6"

18X24 WORK STATION

COUNTERTOP BRACKET18" STEEL, 1000LB CAPACITY,

SPACED APPROX. 54" O.C.

GRAY COLOR

BLOCKING & WALL CLEATS

FOR WALL SUPPORT

P.LAM. BACKSPLASH

scale : 1/4"=1'-0"09.

scale : 1/4"=1'-0"10.

scale : 1/4"=1'-0"11.

scale : 1/4"=1'-0"12.

scale : 1/4"=1'-0"14.

scale : 1/4"=1'-0"13.

9

A-3

11

A-3

10

A-3

12

A-3

14

A-3

15

A-3

16A-3

16A-3

16A-3

16A-3

16A-3

16A-3

14A-3

PAINTED

GYP.

LAMINATE

FACED COUNTER

& BACKSPLASH

COUNTER

SIDE PANEL

NEW ELECTRICAL & DATA

OUTLET @ 40" AFF

PLUG

MOLD

2'-6"

2'-6"

2'-6"

2'-6"

NEW 6" VINYL BASE

PAINTED

GYP.

LAMINATE

FACED COUNTER

& BACKSPLASH

COUNTER

SIDE PANEL

NEW 6"

VINYL BASE

COUNTER

SIDE PANEL

COUNTER

SIDE PANEL

COUNTER

SIDE PANEL

NEW 6"

VINYL BASE

EXISTING

WINDOW

PAINTED

CMU

V.O.J.LAMINATE

FACED COUNTER

& BACKSPLASH

2'-6"

COUNTER SIDE PANEL AT

CORNERS AND ENDPIECES,

P.LAM OVER 34" PLYWOOD

NEW ELECTRICAL & DATA

OUTLET @40" AFF

PLUG

MOLD

NEW ELECTRICAL &

DATA OUTLET @40"

AFFPLUG

MOLD

NEW ELECTRICAL &

DATA OUTLET

NEW ELECTRICAL &

DATA OUTLET @ 40" AFF

PLUG MOLD

METAL

BRACKET

METAL BRACKET

KNEE SPACE 2'-3"

MIN

.

DOOR

PAINTED

GYP. PAINTED

GYP.

METAL BRACKET

KNEE SPACE 2'-3"

MIN

.

METAL BRACKET

KNEE

SPACE

2'-3"

MIN

.

METAL BRACKET

2'-3"

MIN

.

METAL BRACKET

KNEE SPACE

2'-3"

MIN

.

METAL BRACKET

KNEE SPACE

2'-3"

MIN

.

KNEE SPACE

7'-4"

NEW

COUNTER NEW FURNITURE

NEW

COUNTER

NEW

COUNTER

NEW

FURNITURE

NEW

COUNTER

TOP

NEW

WALL

NEW

WALL

7'

5'

scale : 1/4"=1'-0"15.

2'-6"

LAMINATE

FACED COUNTER

& BACKSPLASH

NEW ELECTRICAL &

DATA OUTLET @40"

AFF

PAINTED

GYP.

KNEE

SPACE

2'-3"

MOBILE

PEDESTAL

MOBILE

PEDESTALKNEE

SPACE

scale : 1/4"=1'-0"02.

OFFICE 123

NEW FURNITURE

DRY-ERASE/MAGNETIC

BOARD 9'H X19'W V.O.J.

TV EQUIPMENT SPECIFIATION

1. TELEVISION SHALL BE PANASONIC TH-50LFE7 50", LCD VA Panel/E-LED,Aspect

Ratio 16:9, OR APPROVED EQUAL, for Rooms 122,127,138,151,158 SEE EQUIPMENT

SPECIFICATION

2. TELEVISION SHALL BE PANASONIC TH-65 0LFE7U 65", LCD VA Panel/E-LED,Aspect

Ratio 16:9, OR APPROVED EQUAL, for Rooms 102,140 & 144 SEE EQUIPMENT

SPECIFICATION

3. TELEVISION MOUNTING BRACKET: Heavy-Duty Premium Swivel Full Motion

Articulating Tilting TV Wall Mount Corner Bracket for 32-60 inch Screen LCD OLED

Plasma 4K Flat Panel Screen VESA up to 750x450, 175 lb Capacity, Black. SHALL BE

COMPATIBLE WITH TV BRAND AND SIZE.

scale : 1/4"=1'-0"01.

OFFICE 101 OFFICE 102

13

A-3