ATS l AU AUTOMATIC TRANSFER SWITCH
MASCHINENBAU HALBERSTADT GmbH, building on its 60 year legacy in power generation, introduces a novel design of Automatic Changeover Switch ideally suited for quick, safe and reliable transfer of load between two energy supply sources automatically.
AU AUTOMATIC TRANSFER SWITCH
ATS CONTROL
ENCLOSURES
INSTALLATION & DIMENSIONS
CATALOG NO.
3
11
19
23
31
INDEX
AU AUTOMATICTRANSFER SWITCH
MBH ELECTRIC | AU AUTOMATIC TRANSFER SWITCH
4
Several decades of experience and contribution to power generation technology have allowed Maschinenbau Halberstadt GmbH to conceptualize and tailor the ideal low Several decades of experience and contribution to power generation technology have voltage transfer switch that enables:
■ Quick, safe and reliable transfer. ■ Secure isolation. ■ Minimum energy consumption. ■ Minimizing downtime and service continuity.
POWER GENERATIONEXPERTISE
www.MBHelectric.de
5
The transfer switch serves as an equipment to transfer load supply service between two sources.
■ Utility to GeneratorFor application with single utility feeder and a standby generator source. The transfer switch senses loss or abnormality in utility voltage then issues a remote start signal to the standby generator and transfers the load. Load is transferred back under normal utility conditions.
■ Generator to GeneratorFor application in a power system with multiple site generators. Load is transferred to secondary generation in the events of failure or scheduled maintenance.
■ Utility to UtilityFor application with multiple utility feed. Transfer from one source to another is enabled in case of scheduled maintenance of source failure.
■ Multiple Source SystemMultiple Source Systems may include multiple redundant utility feeds and/or multiple standby generators.
Load is transferred to standby source in the event of utility (ies) failure in the case of multiple utility feeds.
Load transfer to secondary generator is accomplished following the failure of both utility and standby generators.
MAIN APPLICATIONS
LOAD
LOAD
LOAD
LOAD
MBH ELECTRIC | AU AUTOMATIC TRANSFER SWITCH
6
GENERAL CHARACTERISTICS
The ATS is intended for use in low voltage power networks in order to reduce and virtually eliminate outage periods of critical loads. The ATS ratings range from 100A to 3000A to cover the widest range of industrial, commercial and residential needs.
■ Extended product lifetime through minimization of arcing time. ■ On-Load Switching. ■ 3 Stable switch positions (Main Source, Neutral, Emergency Source). ■ Manual Bypass Capabilities. ■ Dual switching strategies: Main ←→ Emergency or Main ←→ Neutral ←→ Emergency.
■ Individual phase enclosure and arc chamber to improve breaking capacity. ■ Enhanced main contact protection & breaking capacity. ■ Easy to maintain. ■ High transfer capabilities for inductive and motor loads.
Arc Chamber
www.MBHelectric.de
7
AUT FEATURES100~3000A
MBH AU’s unique design is optimized to ensure personnel safety, equipment protection and virtually eliminating outages thus combining safety, reliability and fast response. It is widely trusted to maintain service of critical and non-critical processes online at all time to enhance our client’s manufacturing capabilities.
Safety
■ All phases are fully insulated, each in its unique structure. ■ The breaking chambers are fully enclosed to prevent contact with any live parts caused by insulation degradation following an arcing event.
■ Safe conductive performance is ensured by applying adequate contact pressure at all times during operation.
Compact Design
Each phase is fully insulated and is in an independent 1-phase structure. According to the convenience of users, the conduction parts of 3-phase and 4-phase can be combined depending on the capacity and the number of phases.
■ The compact and unique design allows for switching between main source and emergency source through the use of one coil.
■ The uniquely structured arc shute reduces the arc breaking time leading to longer contact lifetime.
■ Stable breaking is ensured by the use of a breaking spring for tripping operations. ■ Low loss and low energy consumption due to the application of instantaneous excitation mode.
■ Both direct source transfer and transfer through neutral stable position are possible.
Reference Standards
The AU Automatic Transfer Switches are designed, manufactured and tested incompliance with the following standards:
■ IEC EN 60947-6-3 ■ IEC EN 60947-6-6
MBH ELECTRIC | AU AUTOMATIC TRANSFER SWITCH
8
■ AU Technical Description
www.MBHelectric.de
9
ATS CONTROL
MBH ELECTRIC | AU AUTOMATIC TRANSFER SWITCH
12
AU CONTACT TIME CHART& CIRCUIT DIAGRAM
■ AU Contact Time Chart
■ AU Internal Circuit
www.MBHelectric.de
13
■ AU Operating Circuit
MBH ELECTRIC | AU AUTOMATIC TRANSFER SWITCH
14
Features
■ DIN Rail mounted. ■ No DC supply required. ■ Adjustable MCB and GCB delays. ■ 10A/250VAC MCB and GCB outputs. ■ 10A/28VDC/250VAC remote start output. ■ Isolated mains and genset inputs.
Inputs
■ R-S-T: Mains phase voltages. ■ NEUT-MN: Mains neutral terminal. ■ G: Generator phase voltage. ■ NEUT-GN: Generator neutral terminal.
Outputs
■ MCB-MAINS Contactor: Normally open relay output connecting the phase-R voltage to the terminal. (10A@250V-AC) ■ GCB-Generator Contactor: Normally open relay output connecting the phase-G voltage to the terminal. (10A@250V-AC) ■ Remote Start: Normally open engine start request relay output. (10A@28V-DC/250V-AC)
Technical Specifications
■ Alternator Voltage: 170-300 V-AC (Ph-N). ■ Mains Voltages: 170-300 V-AC (Ph-N). ■ Generator Contactor Delay: 1 to 40 sec. adjustable. ■ Mains Return Delay: 1 to 40 sec. adjustable. ■ MCB Relay Output: 10A @ 250V-AC. ■ GCB Relay Output: 10A @ 250V-AC. ■ Remote Start Relay Output: 10A @250V-AC/28V-DC. ■ Operating temp.: -30°C (-22°F) to 70 °C (158°F). ■ Storage temp.: -30°C (-22°F) to 80 °C (176°F). ■ Maximum humidity: 95% noncondensing. ■ Dimensions: 70x115x66mm (WxHxD). ■ Weight: 180g (approx.). ■ Installation: DIN Rail mounted. ■ Case Material: High Temp. ABS/PC (UL94-V0). ■ IP Protection: IP20. ■ Conformity (EU directives).
■ 2006/95/EC (low voltage). ■ 2004/108/EC (EMC).
■ Norms of reference: ■ EN 61010 (safety requirements). ■ EN 61326 (EMC requirements).
AUC 173DIN RAIL MOUNTED
www.MBHelectric.de
15
MBH ELECTRIC | AU AUTOMATIC TRANSFER SWITCH
16
Features
■ Automatic contactor control. ■ Synchroscope & check synch. ■ No break transfer & no break load test. ■ Multiple genset system support. ■ Electrical protections for genset. ■ Built in alarms and warnings. ■ Load shedding, dummy load. ■ Periodic maintenance request indicator. ■ Built in daily / weekly / monthly exerciser. ■ Event logging with time stamp and measurements. ■ Statistical counters. ■ Battery backed-up real time clock. ■ Weekly operation schedule programs. ■ 3 level password system. ■ Field adjustable parameters. ■ RS-232 serial port. ■ Firmware downloadable from serial port. ■ Free MS-Windows Remote monitoring SW:
■ Local and modem connection. ■ Monitoring, download of parameters. ■ Modem networking.
■ GSM and PSTN modem support. ■ GSM SMS message sending on fault. ■ MODBUS communications. ■ Graphic LCD display (128x64 pixels). ■ User friendly graphic indicators. ■ Triple language support. ■ Customer logo display capability. ■ Configurable digital inputs: 7. ■ Configurable digital outputs: 2. ■ Total digital outputs: 6. ■ I/O expansion capability. ■ Survives cranking dropouts. ■ Sealed front panel. ■ Plug-in connection system for easy replacement.
AUC 329 ATS CONTROLLER WITH MULTIPLE GENSET SUPPORT
www.MBHelectric.de
17
Inputs
The unit has 7 configutable digital inputs. Each input has following programmable parameters: ■ Alarm type: shutdown / load-dump / warning / no alarm. ■ Alarm polling: on engine running / always / on mains OK. ■ Latching / non-latching operation. ■ Contact type: NO / NC. ■ Switching: BAT+ / BAT.
Outputs
The unit provides 6 digital outputs and 2 of them have programmable functions, selectable from a list. Any function or alarm condition may be output as a relay output. Using two Relay Expansion Modules, the number of relays may be increased to 22, 16 of them being volt-free contacts.
■ Alternator voltage: 0 to 300 V-AC (Ph-N). ■ Alternator frequency: 0-100 Hz. ■ Mains voltage: 0 to 300 V-AC (Ph-N). ■ Mains frequency: 0-100 Hz. ■ DC Supply Range: 9.0 to 30.0 V-DC. ■ Cranking dropouts: survives 0 V for 100ms. ■ Typical Standby Current: 100 mA-DC. ■ Maximum Operating Current: 200 mA-DC. (Relay outputs open) ■ Generator/Mains Contactor Relay Outputs: 16 A / 250V. ■ Current inputs: from CTs, .../5A. Max load 0.7VA per phase. ■ Serial port: RS-232, 9600 bauds, no parity, 1 bit stop. ■ DC Outputs: 1A @ 28V. ■ Operating temperature: -20°C (-4°F) to 70 °C (158°F). ■ Storage temperature: -40°C (-40°F) to 80 °C (176°F). ■ Maximum humidity: 95% non-condensing. ■ Dimensions: 165 x 125 x 48 mm (WxHxD). ■ Panel Cut-out Dimensions: 151x111 mm minimum. ■ Weight: 300 g (approx). ■ Case Material: High Temperature ABS/PC (UL94-V0). ■ IP Protection: IP65 from front panel, IP30 from the rear. ■ Conformity (EU directives). ■ 2006/95/EC (low voltage). ■ 2004/108/EC (electro-magnetic compatibility). ■ Norms:
■ EN 61010 (safety requirements). ■ EN 61326 (EMC requirements).
ENCLOSURES
MBH ELECTRIC | AU AUTOMATIC TRANSFER SWITCH
20
The enclosed ATS dimensions are optimized to fit in small areas while facilitating the installation and maintenance for all its parts. The enclosed ATS line provides the user with a secure and reliable solution under a wide range of environmental and physical dangers. Enclosed ATS range can be customized to fit all your needs.
Rating(A) IP Voltage PoiesStandard Enclosures (mm)
Width Depth Height
100A, 200A 32 600V 3P, 4P 600 250 800
400A, 600A 32 600V 3P, 4P 600 250 1000
800A, 1000A 32 600V 3P, 4P 800 300 1400
1200A, 1600A 32 600V 3P, 4P Custom Design
2000A 32 600V 3P, 4P Custom Design
3000A 32 600V 3P, 4P Custom Design
www.MBHelectric.de
21
INSTALLATION& DIMENSIONS
MBH ELECTRIC | AU AUTOMATIC TRANSFER SWITCH
24
■ Manual Bypass to Source B
■ Source B: ON
■ Source A: ON
■ Manual Bypass to Source A
■ Source A: OFF
■ Source B: OFF
■ Trip
Manual operation is made feasible through the use of a handle connected to the side of the ATS and by making use of a metal pin to control source selection and tripping.
■ CAUTION: ATS Manual operation should be carried out under no load conditions and after careful inspection of live parts.
MANUAL OPERATION
www.MBHelectric.de
25
OPERATING CONDITIONS ■ Ambient Conditions
Avoid installation in humid areas, locations with risk of exposure to poisonous gas and high temperature places.
■ OrientationThe ATS is designed to be installed in a specific direction as highlighted in the figure. The ATS feature and performance may be subject to variation if the installation orientation changes. Ideally, the ATS should be installed so as the nameplate can be read properly facing the front and without any twist or bending of any ATS components.
■ Control Circuit ConnectionUse low voltage control/power cable with sufficient length. In case of DC supply, make sure to take into consideration battery and charging characteristics.
■ Main Circuit ConnectionConnect firmly by selecting appropriate wire sizes and solderless terminals. Avoid applying excessive stress to the main circuit terminal.
■ Maintenance & InspectionConduct maintenance and inspection at regular cycles in order to maintain the ATS performance.
■ Recommended
■ NOT Recommended
MBH ELECTRIC | AU AUTOMATIC TRANSFER SWITCH
26
AU DIMENSIONS
■ AU 100A - AU 200A (Front)
■ AU 400A (Front)
Type 3P 4P
A 234 264
B 133 163
Type 3P 4P
A 287 338
B 192 243
www.MBHelectric.de
27
■ AU 600A - AU 1000A (Front)
AU600 AU800 AU1000
3P 4P 3P 4P 3P 4P
A 340 400 400 480 400 480
B 224 284 284 364 284 364
C 220 220 239 239 239 239
D 30 30 31 31 31 31
E 40 40 40 40 50 50
F 20 20 40 40 30 30
G 60 60 80 80 80 80
H 5 5 8 8 10 10
I 36 36 42 42 42 42
J 60 60 54 54 56 56
K 248 248 267 267 267 267
L 58 58 80.5 80.5 79.5 79.5
M 53 53 63 63 63 63
MBH ELECTRIC | AU AUTOMATIC TRANSFER SWITCH
28
■ AU 1200A - AU 1600A (Front)
AU1200 AU1600
3P 4P 3P 4P
A 452.7 535.7 452.7 535.7
B 328 411 328 411
C 419.4 419.4 419.4 419.4
D 534.4 534.4 534.4 534.4
E 50 50 50 50
F 27 27 27 27
G 33 33 33 33
H 83 83 83 83
I 94.5 94.5 94.5 94.5
J 25 25 25 25
K 12 12 12 12
L 69 69 69 69
M 55 55 55 55
N 153.7 153.7 153.7 153.7
www.MBHelectric.de
29
■ AU 2000A (Back)
AU1200
3P 4P
A 527.7 635.7
B 403 511
C - -
D - -
E 75 75
F 40 40
G 33 33
H 108 108
I 107 107
J - -
K 15 15
L - -
M - -
N 152.2 152.2
MBH ELECTRIC | AU AUTOMATIC TRANSFER SWITCH
30
■ AU 3000A (Back)
AU3000
3P 4P
A 602.7 735.7
B 478 611
C 25 25
D 142.2 142.2
www.MBHelectric.de
31
AUTOMATIC TRANSFER SWITCH
ModelAU Automatic Changeover Switch
Supply voltage (shunt trip)220 220V110 110V
InstallationF Front ConnectionB Back Connection
Controllerc1 AUC 329c2 AUC 173
Enclosure
** Protection Index
** Specify Protection Index
Current Rating0100 100A 1200 1200A0200 200A 1600 1600A0400 400A 2000 2000A0800 800A 2500 2500A1000 1000A 3000 3000A
Switch TypeS Standard AC
Poles3 3P4 4P
CATALOG NO.
MBH Middle East & Africa
Halat, LebanonT. +961 9 444 [email protected]
MBH Gulf
Baniyas ComplexNasser Square Al Rigga AreaDeira, Dubai, UAET. +971 4 239 5954, F. +971 4 239 [email protected]
MBH Headquarters
MASCHINENBAU HALBERSTADT GmbHRudolf –Diesel-Strasse 50Halberstadt 38820GermanyT. +49 1577 3394 113, F. +49 3941 [email protected]
© 2012 Maschinenbau Halberstadt GmbHAll rights reserved. Reproduction in whole or in part is prohibited without the prior written consent of the copyright owner. The information presented in this document does not form part of any quotation or contract, is believed to be accurate and reliable and may be changed without notice. No liability will be accepted by the publisher for any consequence of its use. Publication thereof does not convey nor imply any license under patent- or other industrial or intellectual property rights.