Upload
others
View
6
Download
0
Embed Size (px)
Citation preview
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2Contents
19.1 Circuit interrupters 19/72319.1.1 Surges during a switch closure 19/72319.1.2 Surges during a switch interruption 19/723
19.2 Theory of circuit interruption with different switching mediums (theoryof deionization) 19/723
19.3 Theory of arc plasma 19/725
19.4 Circuit breaking under unfavourable operating conditions 19/726
19.5 Circuit interruption in different mediums 19/72619.5.1 Bulk Oil Circuit Breakers (BOCBs) 19/72619.5.2 Minimum Oil Circuit Breakers (MOCBs or LOCBs) 19/72719.5.3 Air Circuit Breakers (ACBs) 19/72819.5.4 Air Blast Circuit Breakers (ABCBs) 19/73219.5.5 Sulphur hexafluoride gas circuit breakers (SF6) 19/73319.5.6 Vacuum circuit interrupters 19/740
(i) Vacuum circuit breakers (VCBs) 19/740(ii) HV vacuum contactors (HVCs) 19/743(iii) LV vacuum contactors (LVCs) 19/745
19.6 Phenomenon of current chopping 19/74519.6.1 Influence of frequency on the system 19/746
19.7 Virtual current chopping 19/746
19.8 Containing the severity of switching surges 19/74719.8.1 Theory of energy balancing 19/747
19.9 Comparison of circuit breakers using different interrupting devices 19/748
19.10 Gas insulated switchgears (GIS) 19/748
19.11 Retrofitting old installations with vacuum and SF6 breakers 19/757
Relevant Standards 19/758
Further Reading 19/758
19Circuitinterrupters andtheir applications
19/721
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/723
19.1 Circuit interrupters
An interrupter is the electrical part and constitutes theswitching device of a breaker. The operation of this devicecauses switching surges when closing or opening a circuit.Details of such surges and causes of their generation arediscussed in chapter 17.
Surges that may appear on the LV side of a powersystem as a result of transference from the HV side of atransformer (Section 18.5.2) are different and not relatedto switching. Surges on the LV side due to switching ofstatic devices (Section 6.13) are not related to the switchingof the circuit but to the static devices themselves.
In this chapter we discuss the types of insulating andquenching mediums, their switching characteristics andmerits and demerits of their use. We also consider thebasic interrupting devices developed over the years, usingsuch mediums, keeping switching surges as the basiccriteria in mind. The theory of arc interruption is the samefor all switching devices. The following types of breakershave been developed for the purpose of switching andthey mostly relate to the HV systems, except where noted:
1 Bulk Oil Circuit Breakers (BOCBs)2 Minimum Oil or Low Oil Content Circuit Breakers
(MOCBs or LOCBs)3 Air Circuit Breakers (ACBs) – generally for an LV
system only4 Air Blast Circuit Breakers (ABCBs)5 Sulphur Hexafluoride Circuit Breakers (SF6 breakers)6 Vacuum Circuit Breakers (VCBs)7 HV and LV Vacuum Contactors (VCs). Contactors
are not breakers but covered here to comprehend theapplications of vacuum interrupters as the contactorstoo embody an interrupting device.
It is for the user to choose the most appropriate circuitbreaker to suit his requirements, application and cost.Some of the breakers in the HV range like BOCBs,MOCBs and ABCBs are now out dated in the face ofmore advanced technologies available in the form ofvacuum and SF6 breakers. Installations where old breakersare still installed, are fast getting retrofitted with the newgeneration advanced technology breakers. But to retainthe historical significance of the old breakers we havediscussed briefly these breakers also for a general referenceto the readers, to be more abreast with the evolution ofnew technologies that has taken place over the years inthe techniques of arc extinction. Here we discuss brieflythe philosophy of circuit interruption and the effect ofinsulating and quenching mediums on the arc extinctionof these breakers. We also deal briefly with theconstructional features and applications of such breakers.For more details one may refer to the manufacturers’catalogues and literature available on the subject.
To begin our discussions, let us first have a briefreview of switching surges discussed in Chapter 17.
19.1.1 Surges during a switch closure
• Switching surges may develop during a closingoperation just before the contacts are able to make. It
may occur at a stage when the gap (i.e. the dielectric)between the contacts becomes incapable ofwithstanding the impressed voltage and breaks down.When this occurs, it causes an arc between the contactsleading to such surges.
• Switching surges also develop when all the threepoles of a switching device do not make at the sameinstant. (Refer to Section 17.7.2(ii).) The surges mayhave a peak value up to 3–5 p.u. at a surge frequencyof 5–100 kHz or more, depending upon the closingcircuit constants L and C. They may exist in the systemfor a very short duration of much less than even onehalf of a cycle, i.e. up to the closure of the switchonly. Typical speeds of interrupters may fall in therange of 1–1.5 mm/ms. Extremely steep (fast-rising)transient surges, up to 3.5 p.u. have been noticed incertain switching circuits, with a front time as low as0.2 ms.
19.1.2 Surges during a switch interruption
These surges develop when interrupting a highly inductiveor capacitive circuit, such that the current phasor lags orleads the voltage phasor by so much that up to a near fullsystem voltage may appear across the parting contactson a current zero and cause re-ignition of the arc plasma.(Refer to Section 17.7.4.) These surges may also have apeak value up to 3–5 p.u. at a surge frequency of 5–100kHz or more, depending upon the interrupting circuitconstants L and C. They may exist in the system for aslightly longer duration of one half to one-and-a-halfcycles (10–30 ms for a 50 Hz system), i.e. up to circuitinterruption. Extremely steep transient surges, up to 5 p.u.in certain interrupting circuits, have been noticed with afront time as low as 0.2 ms and even less.
The phenomenon of a switching surge is related tothe performance of the switching device, i.e. its speed ofoperation and ability to quickly rebuild its dielectricstrength (deionization of the arc plasma) between theparting contacts after a current zero.
19.2 Theory of circuit interruptionwith different switchingmediums (theory ofdeionization)
When a live circuit is interrupted, an arc is invariablyformed between the parting contacts, the intensity andmagnitude of which would depend upon the quantumand the quality (p.f.) of the current being interrupted.The arc, due to its excessive heat, under high pressure orvacuum (the medium in the interrupter is maintainedthus), forms a plasma in the medium which causesdecomposition of the insulating and the quenching mediumto a few gases and vapours. The gases so formed thenionize into electrons and protons, which are chargedparticles conducting in nature, and make the arc conductingas well. How to disperse the heat of the arc plasma quicklyfor a successful interruption of the circuit is the theoryof arc extinction. The types of gases produced and their
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/724 Electrical Power Engineering Reference & Applications Handbook
behaviour, as a consequence of ionization of the insulatingand quenching mediums are as follows:
• Oil in BOCB or MOCB This decomposes intovapourized and dissociated hydrocarbon, which in turnionizes into H2 and other gases and vapours. H2constitutes around 70% of all the gases and vapoursproduced.
• Air in ACB or ABCB This ionizes into N2, O2 andvapours; N2 constitutes most of it.
• SF6 in SF6 circuit breakers This ionizes into sulphurand fluorine.
• In a VCB This is not the vacuum but the metal ofthe parting contacts that becomes vapourized.
The main problem of circuit breaking arises out offormation of the arc and its prolonged extinction, whichmay delay the circuit interruption and lead to a restrikeof the arc plasma after a current zero. The basic conceptof a circuit breaking thus leads to the quickest extinctionof the arc plasma. It has caused many engineers andscientists to undertake extensive research and developmenton the subject over the past 50 years or so to find moresuitable mediums and to evolve better techniques toextinguish the arc plasma. The present-day hightechnology, adopted by the various manufacturers in thefield of arc quenching, is the result of these long years ofconsistent and continuous research and developmentwork.
To achieve a quicker extinction of the arc it isimperative to create one or more of the followingconditions:
1 To quench the arc plasma caused during theinterruption, quickly and continuously, is to ensurethat by the next current zero, the arc path is devoid ofany traces of arcing. In other words, the contact gapmust restore its dielectric strength before the nextcurrent zero.
2 To lengthen the arc as shown in Figures 19.11 and19.12. This is an effort to render the restriking voltage(TRV*) insufficient to re-establish an arc across theparting contacts after a current zero. The processincreases the resistance of the arc plasma that helpsto absorb a part of the TRV by causing a voltage dropacross the resistance so created, besides improvingthe p.f. of the interrupting circuit and thus dampingthe restriking voltage (TRV) to far below its peakvalue by the next current zero. Damping of TRV atimproved p.f. may be observed from curves a and bof Figure 17.11.
3 Splitting the arc into a number of series arcs (Figure19.11) so that the input power to the arc becomes lessthan the heat dissipated during the process ofdeionization. The more efficient the process of cooling,the better will be the chances of avoiding a restrikeand achieving a quicker extinction of the arc.
4 A forced interruption before a current zero, as mayoccur in an ABCB or VCB, may cause current chopping
(Section 19.6, Figure 19.27) giving rise to high TRVs,is not desirable. It is therefore important that the designof the interrupting device be such that a live circuitinterrupts only at a natural current zero, as far aspossible, to avoid generation of voltage surges. Thefollowing techniques have been developed to achievethis:• Use of high pressure at the arc plasma to drive
away the same.• Adopting forced cooling to quench the arc plasma.• Use of such constructions that can elongate arc
length and reduce the concentration of ions in thearc plasma and hence enhance the dielectric strengthbetween the parting contacts.
• Pre-inserting a resistor in the interrupter unit tocause a voltage (TRV) drop across it and to alsoimprove the p.f. of the interrupting circuit andmaking arc extinction easy. The mechanism is madesuch that a resistance commensurate with the systemparameters and switching conditions (which theuser has to stipulate to the manufacturer) is insertedinto the switching circuit. Insertion is made throughthe interrupting mechanism immediately, say, byhalf a cycle before the contacts make or open andis shortened or disconnected immediately on closingor opening of the contacts.
These techniques have been successfully implementedin interrupting devices as noted in Section 19.1.2, beingcommercially produced by various manufacturers fordifferent voltage systems and applications.
The dielectric properties of different mediums atdifferent contact gaps are illustrated in Figure 19.1. Itmay be observed, that except the medium of vacuum,which has a near constant or very little rise in dielectric
Figure 19.1 Dielectric strength of different mediums as a functionof contact gap
High vacuum
Die
lect
ric s
tren
gth
(kV
)
250
200
150
100
50
0 5 10 15 20Contact gap (mm)
Air, 1 bar
OilSF 6
, 1 b
ar
*TRV–Transient recovery or impressed voltage (Section 17.6.2)
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/725
strength above a gap of 10 mm and pressure about 10–3
Torr or less, all other mediums, even air, have a near-linear rise in their dielectric strength with the contact gap.
The dielectric strength can also be enhanced with therise in pressure of the medium, except oil, which cannotbe compressed, and can be considered as having a near-constant dielectric properties. The characteristic of air atvery low pressures is illustrated in Figure 19.2. Thebehaviour of air at very low pressures (below 10–4 Torr)is extensively utilized in vacuum interrupters.
19.3 Theory of arc plasma
The arc plasma is caused during an interruption of thelive contacts, and also just before closing the contacts,when the contact gap falls short of the required dielectricstrength to withstand the impressed voltage. When anarc is caused the gases present in the arcing chamber,under the influence of high temperature of the arc plasmaand the high pressure or high vacuum maintained withinthe arcing chamber, become ionized. They liberate protons(positive ions, positively charged, heavier particles) andneutrons (uncharged particles) surrounded by electrons(negatively charged lighter particles (Figure 19.3)). Thetheory of arc extinction relates to the physics and behaviourof these electrically charged particles that are responsiblefor a restrike of the TRV even after a current zero. Theeffectiveness of the medium and the design of the arcchamber to diffuse these electrically charged particles toneutrons as quickly as possible determines the ability ofone type of breaker over others. In fact, the theory of arcextinction is the theory of deionization (neutralization)of the electrically charged protons and electrons. Thetheory may be briefly explained as follows.
The positive ions (protons) present in the arc plasmamove to the cathode (negative pole) and neutralize(deionize) the electrons there. Similarly, the negativeions (electrons) move to the anode (positive pole) andbecome absorbed there. Thus the process continues untilall the plasma is neutralized and contains only neutrons
to extinguish the arc. In fact, the concentration of ionsbetween the parting contacts gradually becomes dilutedby the deionization of protons and the absorption ofelectrons at the anode, and a stage is reached whenadequate dielectric strength between the parting contactsis restored to extinguish the arc. It is not necessary forall the ions present in the plasma to be deionized toextinguish the arc, rather a stage when they are not ableto hold the arc. This process also increases the resistanceof the arc plasma as a result of reduced contact pressureand arc contact area.
A proton, being 1835 times heavier than an electron,moves sluggishly compared to an electron since
m m1 12
2 22 = = constantv v
where m is the mass of an ion and v its velocity. Then,for the mass of electron as m, the velocity of the protonwill be
1835 = p2
e2◊ ◊ ◊m V m V
If Vp = velocity of the proton and Ve = velocity of the electron
then VV V
pe e =
1835 =
43, which is too slow compared to
an electron. The conductance of the arc plasma is thusthe result of the movement of electrons, rather thanprotons, which contribute only a little.
Figure 19.2 Dielectric strength of air at different pressures ata uniform contact gap of 10 mm (1 Torr � 1 mm head of Hg)
1000
0.1
1
10
100
�240
10–6 10–5 10–4 10–3 10–2 10–1 1 10 102 103 104
Die
lect
ric s
tren
gth
(kV
)
Pressure (Torr) 760 Torr �1 bar (1 atm.)
N +
A molecule of gas, underhigh temperature andpressure or vacuum
Neutron is surroundedby very lightweightelectrons
Moves towards anode and allelectrons get absorbed there.The leftout neutrons comeback to plasma uncharged
Moves towards cathode, collectsan electron and gets neutralized.The neutrons so resulted, comeback to the plasma uncharged
Proton
Return to plasma
uncharged
Ionization
Note: The mass of a nucleon (proton or neutron) is 1835 timesheavier than an electron and moves much slower than an electronsince, m v m v1 1
22 2
2= = constant. Where m is the mass and v, thevelocity of an electron or a proton. The bulk of the arc is thereforecaused by electrons rather than protons.
Figure 19.3 Theory of ionization and deionization of gas atomsto extinguish the arc plasma
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/726 Electrical Power Engineering Reference & Applications Handbook
19.4 Circuit breaking underunfavourable operatingconditions
Long years of experience in the field of circuit breakingwith interrupting devices have revealed that under adverseconditions of circuit parameters, interruption may not besmooth. It may result in excessive voltage surges, as aconsequence of restriking of the parting contacts. A wrongchoice of interrupting device may result in insulationfailure of the terminal equipment, such as a powertransformer, an induction motor or inter-connecting cables.This situation may arise when:
1 Interrupting small magnetizing currents, such asinterrupting an induction motor or a transformer onno-load, a situation, when the current may lag theimpressed voltage by nearly 90∞.
2 Interrupting a charged capacitor bank, when the currentwill lead the impressed voltage by nearly 90∞.
3 Interrupting an unloaded transmission or distributionline or a cable, i.e. interrupting a line charging current,which is capacitive and may lead the system voltageby nearly 90∞.
4 Interrupting an induction motor immediately after aswitch on, when the current is large and highlyinductive.
5 Interrupting fault currents that are mostly inductive(Section 13.4.1(5)) and occur at very low power factors.They are excessive in magnitude, and cause highthermal effects and electromagnetic* forces on thearc chamber, the contacts and the contact mountingsupports.
Under the above conditions, the arc, as usual, willextinguish at the first current zero but will have a tendencyto re-establish immediately again, after the current zero(Figure 17.11(c)) while the contacts are still parting. Thisis because the TRV across the parting contacts may exceedthe dielectric strength of the contact gap achieved sofar.
Restoration of the dielectric strength will depend uponthe speed of the moving contact and the insulating mediumof the arc chamber. There may be a number of arc restrikesbefore a final extinction is achieved. The frequency ofarc restrikes may be extremely high (Equation (17.1)),depending upon the L and C of the interrupting circuit,which would have the characteristics of a surge circuiton formation of an arc. In terms of actual rated frequency( f ), restoration of the dielectric strength may not takemore than one half to one and a half cycles, i.e. 10–30ms (for a 50 Hz system). The behaviour of circuit breakingthus depends upon the design and the quenching mediumof the interrupting device.
* The breaker will interrupt only during a transient state (Figure13.20) by which time the d.c. component responsible for the dynamicforces, has subsided.
Figure 19.4 Rear view of a bulk oil circuit breaker assemblyshowing single-break contacts, self aligning cluster isolatingcontacts, terminal bushing and arc control pots (Courtesy:GEC-Alsthom)
Tulipcontacts
Terminalbushings
Arc controlpots
Movingcontacts
Oil tank
19.5 Circuit interruption in differentmediums
19.5.1 Bulk Oil Circuit Breakers (BOCBs)
Refer to the general arrangement of this breaker in Figure19.4. In this device the moving contacts make and breakin an oil bath. When the arc is formed during an interruption,the oil becomes decomposed due to excessive heat, andproduces a few gases and vapours such as H2 (70%), C2H4(20%), CH4 (10%) and free carbon, say, 3 g per 10 litresof oil decomposed at a very high pressure of 100–150bars, in the shape of a bubble around the arc (Figure19.5). H2 is an extremely good medium for quenchingand does most of the cooling of the arc plasma,extinguishing it while passing through it. The gases thusproduced also cause turbulence in the oil in theneighbourhood, causing rapid replacement of the oil withcool oil from around the contacts, thus achieving a doublecooling effect. At each current zero, it almost recoversits dielectric strength and also increases its post-arcresistance as a result of cooling and arc extinction, makingthe interruption all the more easier and complete.
Simultaneously the bubble also pushes the oil awayfrom around it and reduces the cooling. Proper design,however, can ensure adequate cooling during interruption
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/727
(arcing) by adjusting the speed of the parting contact,supplementing the cooling of oil through an additionaloil chamber, such as a side-vented explosion pot or crossjet pot, by adjusting the gap between the fixed and themoving contacts.
While breaking smaller currents, the formation of gasmay not be adequate to provide the desired cooling effect.This is, however, immaterial because of less intensivearc formation requiring much less cooling. Extinctionmay be slightly prolonged but may be achieved by thenext current zero.
The circuit tends to interrupt at a normal current zeroand causes no current chopping. A BOCB is generallydesigned with two breaks per pole that help in restoringthe dielectric strength promptly during an arc interruption.
This is the oldest version of HV circuit breakers andwas the most extensively used breaker up to 1970. Inmodern systems of power distribution, however,application of this breaker is quickly becoming outdateddue to the higher maintenance of oil that requires constantchecking. It becomes carbonized on every switching andloses its dielectric strength, leading to the possibility ofa fire hazard. Poor availability of such breakers for higherfault levels to match the complexity and a much higherfault level (Table 13.10) demand of modern transmissionand distribution networks has also rendered themunsuitable for all such applications. They are, however,still in use at many old installations that have a low faultlevel and voltages 3.6–12 kV until they too are retrofittedwith advanced technology vacuum or SF6 breakers.
Role of oil
• To insulate the live contacts from the grounded metal
tank. The dielectric strength of oil is nearly twice thatof air.
• To provide an insulating barrier between the opencontacts after the arc is extinguished.
• To produce hydrogen, a good medium for quenching,during the arcing period.
Shortcomings
1 Oil causes carbonization and sludging.2 A hydrogen–air mixture is highly explosive and fire
hazardous.3 Oil coalescing (fusion) with the tank walls may cause
an ignition and explosion. This limitation requires alarge oil tank, which becomes rather impracticable tohandle beyond a certain range of voltage and currentrating. For instance, for a 245 kV system almost20 000 litres of oil tank per phase will be essential. Thearc interruption, although highly efficient and almostautomatic as the size of the gas bubble and the gaspressure is directly related to the size of the arc plasmaor the current it is interrupting, is highly susceptible toexplosion by fusion with the tank metal or highcarbonization of oil.
4 The arc energy produced during an interruption ishigh compared to the mediums of SF6 and vacuum.Figure 19.6 makes a comparison of the arc energyproduced during interruption of a breaker in differentmediums.
The improvised version of a BOCB is achieved throughan MOCB by arranging separate and insulated arcchambers to interrupt each phase separately, thuseliminating the element of fusion with the tank wall.
19.5.2 Minimum Oil Circuit Breakers (MOCBsor LOCBs)
Refer to the general arrangement of this breaker in Figure19.7. The theory of arc extinction is the same as for
Arc
ene
rgy
(kW
h)
600
500
400
300
200
100
00 10 20 30 40
Symmetrical breakingcurrent (kA)
Oil
SF6
Vacuum
Figure 19.6 Comparison of arc energy produced duringinterruption of a breaker in different mediums
Fixed contactOil
Arc
Gas bubble
Moving contact
Oil tank
(1) Formation of gas bubble.(2) When the dimensions of the tank are inadequate, the bubbles
may communicate amongst themselves and also with thetank and cause fusion which may lead to explosion.
Figure 19.5 Interruption of circuit in oil
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/728 Electrical Power Engineering Reference & Applications Handbook
Figure 19.8 Cross-sectional view of a typical pole assembly ofan 11 kV MOCB (Courtesy: NGEF Ltd.)
Oil level indicator
Vent liberated gases in the breaker
Oil filling vent
Upper pole head
Contact tube
Connecting terminals
Spring supported tulip contacts(fixed contacts)
Arc quenching device
Arc chamber
Moving contact rod
Contact roller guide
Connecting terminals
Contact rollers
Lower pole head
Oil drain plug
Level connecting operatingmechanism
Figure 19.7 Minimum oil content circuit breaker (MOCB)(Courtesy: NGEF Ltd.)
BOCBs. Here also the circuit interrupts at a normal currentzero and generally causes no current chopping. In viewof their construction which houses each arcing contactin a separate insulated cylindrical body (Figure 19.8) ithas space limitations to provide two breaks per pole. Asa result, it has a slightly delayed extinction of arc comparedto a BOCB.
However, this is an improvised version of the bulk oilcircuit breaker. Here, the oil is used only for the purposeof quenching the arc. It became the most sought-afterbreaker during the late 1960s and onwards. Their rupturingcapacity is also much higher than that of a BOCB andthey are extremely suitable for distribution systems withmoderate fault levels. MOCBs are available from 6 kVto 420 kV and have a rupturing capacity of 250–25 000MVA. The trend, however, has tilted in favour of moreadvanced technologies, now available in the form ofvacuum and SF6 breakers.
Though applications of MOCBs are rare, they maystill be preferred in the range of 72.5kV–145kV purelyon cost consideration.
19.5.3 Air Circuit Breakers (ACBs)
Refer to the general arrangement of this breaker in Figures19.9(a) and (b).
The moving contacts make and break in air as shownin Figure 19.10. During interruption, the arc is formed(Figure 19.11) producing N2 (80%) and O2 (20%) and
metallic vapours. The quenching and extinction of arcplasma is achieved through the elongation of arc, whichincreases the area of cooling, on the one hand and requiresa higher TRV to cause a restrike, on the other. To obtainthis, arc chutes are provided on the top of the interruptingcontacts, as illustrated in Figures 19.12(a) and (b). Thedesign of the arc chutes is such that it drives the arcplasma upwards and elongates it to provide the requiredcooling effect. This is achieved by constructing the arcchute housing of some insulating material, such as glass,asbestos, ceramic or Bakelite, suitable to withstand thevery high temperature of the arc plasma. Metallic arcsplitter plates (fins) made of magnetic material are fixedinside the arc chute housing so that the arc plasma producesa magnetic field through these splitters, splits into a numberof shorter arcs and rises upwards, to lose all its heatthrough convection. This renders the TRV insufficient tocause a restrike. The long arc length and subsequentcooling increases the resistance of the arc plasma andimproves the p.f. of the interrupting circuit. It thus helpsto bring the current phasor closer to the voltage, andmake interruption on a current zero less severe as a resultof low TRV. (Refer to curves a and b of Figure 17.11.)The gradual rise of arc resistance after a current zero
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/729
Figure 19.9(b) Drawout ACB (Ir – 400–6300A, Isc – 100 kA) (Courtesy: L&T)
dampens the TRV and makes such breakers almostimmune to switching surges. For higher currents, the arcsplitter plates may be altered to have a variety of designs,such as with offset slots, serpentine splitter plates orsimilar features to effectively arrest the arc plasma withinthe arc chutes, rendering it incapable of causing a restrikeafter a current zero.
Such breakers are normally produced for use on an
LV system only. At higher voltages, while interruptingheavy currents (such as on a fault) the arc energy may beso high that a disproportionate size of arc chutes may berequired to arrest and extinguish the arc, leading todisproportionate size of ACB.
ACBs were the first to be produced commercially.They are simple to operate and cause no fire hazards.But at atmospheric pressure, they possess a low dielectric
Figure 19.9(a) Views of air circuit breakers
(Courtesy: Siemens) (Courtesy: GE Power Controls)
A Safety shutter F Secondary isolatingB Microswitch for contacts (fixed)
position indication G Grounding terminal at rearC Racking screw H Scraping ground (fixed)D Racking interlock I Telescopic railE Door interlock J Interlock support
A
B
C
D
E
F
G
H
I
J
Cradie – front view
A
B
C
D
Rear view
A Current transformer C Secondary isolatingB Scraping ground (moving) contacts (moving)
D Contact jaws
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/730 Electrical Power Engineering Reference & Applications Handbook
strength and are therefore normally manufactured onlyin low voltages. Air has less contamination and thereforethese breakers require negligible maintenance, comparedto oil. They require no contact cleaning. Since there is alimit to producing these breakers for HV systems, theirnormal application is for LV systems alone, where theyare used extensively. In fact, they are the only breakersto meet the needs of an LV distribution system and are
available for current ratings 400 A-6300 A and interruptingcapacity 100 to 150 kA.
Protection releases
Modern breakers are available with various protectionconfigurations such as,
– Conventional thermo-magnetic over-current (OC) andshort-circuit (SC) releases
Figure 19.9(c) Microprocessor based and communicationcapable protection release (Courtesy: L&T)
Figure 19.9(d) Coordination of releases
Note Times shown for illustration indicatetotal tripping times
A
B
340 ms
B1 B2
240 ms 240 ms
C
C1
140 ms
C2
140 ms
F
Figure 19.10 Typical contact arrangement of an LV air circuitbreaker
Figure 19.11 Process of arc formation and quenching in anACB using splitter plates
Arc runner(Horn shaped)
Fixed & movingarcing contacts
Arc movinginto arc chute
Lengthening ofarc
Metallic arc splitters orquenching plates ofmagnetic material
Housing of insulatingmaterial (asbestos,Bakelite, FRP or DMCetc)
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/731
– Solid state OC and SC releases– State-of-the-art microprocessor based and communica-
tion capable releases.
Microprocessor based releasesFigure 19.9(c) shows a typical release of this kind of aparticular manufacturer. This is an intelligent electronicdevice (IED) and can be incorporated with many featuressuch as,
• Display r.m.s current.• Store trip data and display trip history.
• Can be hooked up with PCs (personal computers).• Pick-up current settings can be as low as 200% Ir or
so for phase faults and short-circuits and up to 10%Ir or so for ground faults. Trip time settings can be aslow as 0.1–0.5s.
• With the application of these fast operating (£ 0.5s)protective devices it is possible to contain the faultseverity (heating µ Isc
2 . t) of a system to a low leveland enable choose power equipment and components(busbars, connecting links) with lower cross-sectionsto cut on cost.
• The electromagnetic forces ‘Fm’ may still reach theirmaximum as the protective device is fast acting notcurrent limiting and will allow the fault current ‘Isc’reach its peak. (Also see fault level of an LV system,Section 13.4.1(5))
• Being digital can use MODBUS RTU model (Section24.11.5) for serial port communication like breakercontrol through RS485 or any other port.
• Using telemetry software as noted above it is nowpossible to make a substation remotely controlledand fully automatic.
• Blocking capabilities to achieve intelligentdiscrimination and zone selective interlocking: Theycan be co-ordinated for desired discrimination betweenupstream and downstream breakers. Such as in adistribution network as shown in Figure 19.9(d), toisolate only the faulty circuit on a fault (phase orground fault) retaining the continuity of the healthycircuits upstream. Each breaker trips as per its owntrip threshold value and sends out a logic waitcommand to the next trip unit upstream to prevent itstripping. This command is automatically bypassedwhen the upstream breaker directly experiences afault current reaching its trip threshold value andtrips at its original default setting. For instance for afault in circuit C2 only breaker C2 will trip and for afault in circuit B2 only breaker B2 will trip etc. andnot the upstream breakers. In case of fault in theupstream circuits such as in circuit B2, the breakerB2 will trip quickly at a default setting which may be
a
bb5e2
e5e7
n3n4 p
e1
d
d2
d4
Arc plasma risingto the arc splitters
e9
g2
f2
h4h5
h8
d5
g1
n2
a Top terminalb Moulded–plastic baseb5 Fixed contactd Arc chuted2 Arc runnerd4 Metallic arc splittersd5 Leaf springe1 Moving contacte2 Contact carriere5 Tension springe7 Flexible connector
e9 Compression springf2 Operating shaftg1 Insulating barrierg2 Insulating barrierh4 Bimetal striph5 Intermediate shafth8 Current transformern3 Intermediate shaftn4 Magnet corep Bottom terminal
Figure 19.12(a) Operating mechanism of an LV ACB showingthe arc chute with splitter plates (Courtesy: Siemens)
Figure 19.12(b) Arc chamber with splitter plates in a powercontactor
Arc chute with arcsplitter plates
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/732 Electrical Power Engineering Reference & Applications Handbook
of the order of 90–110 ms or so and not the commanddelay of 240 ms for faults in down-stream as chosenin Figure 19.9(d).
• Protective settings can be varied through PC whilethe breaker is in service.
19.5.4 Air Blast Circuit Breakers (ABCBs)
Refer to the general arrangement of this breaker in Figure19.13(a).
These are similar to ACBs, except that the process ofinterruption is accelerated by impinging a high pressureaxial air blast through the arc plasma, when the contactshave just begun to separate. (See Figure 19.13(b).) Thecompressed air has greater dielectric strength and thermalproperties than ordinary air at atmospheric pressure.
The conventional pressure of air blast is generally218 to 900 lb/in2 (1.5 to 6.2 MN/m2) up to 110 kV, up to3000 lb/in2 (20.7 MN/m2) for voltages up to 400 kV, and
still higher pressures for higher voltages. The pressurerequirement will change from one manufacturer to another,depending upon contact design, interrupting mechanismand design and value of resistors. Since most quenchingis through a predetermined force of an air blast, the forceof arc plasma quenching and extinction (deionization)remains the same for a particular size of breaker,irrespective of the amount of current the interruptingdevice may have to break. This factor inherits a tendencyto break small currents, even before their natural currentzeros, causing current chopping (Section 19.6). Currentchopping may raise the TRV up to 2.5–3 p.u. However,it is possible to design these breakers to contain the valueof a TRV to a non-striking level.
The damping of a TRV is achieved through low andhigh-resistance units provided across the contacts. Thelow unit will short at higher TRVs and the higher unit atlower TRVs. The arc interruption is fast and generally atthe first current zero due to damping. When the breakeris in the closed position, the resistors are open circuited.As soon as the main contacts begin to interrupt, thecontacts of resistor make first, before the main contactsseparate and provide the required damping. Afterextinction of the arc, the resistor circuit opens againautomatically and restores to the original position.
Until a few years ago these breakers had been quitecommon for medium voltages, up to 33 kV. Since theyrequire a powerful blast of air at high pressure and velocityinto the arcing region, they require a reliable source ofair supply. Air should be clean and dry and at the correctpressure and volume at all times. This requires an elaboratearrangement for air compression, an air storage facility,a network of feed pipes, valves and safety devices besidestheir regular maintenance and upkeep. All this is costly
Figure 19.13(a) One pole of ABCB 72.5–420 kV with verticalcompressed air tank (Courtesy: ABB)
Internal electricalconnection
Capacitor
Control valve andblast valve
Controlinsulator
Doubleinterruptingchamber
Interrupting chamberdriving mechanism
Control box
Control cubicle
Bifurcation housing
Supporting insulator
Compressed air tank
Pneumaticpressure lines
ControlwiringYR B
Figure 19.13(b) Process of arc formation and quenching in anair blast circuit breaker
Arc probeTerminal
Arc in initial andfinal positions
Low pressure
High pressure
Air flow
Terminal
Blast tube
Exhaust
Nozzle
Movingcontact
Slidingconact
Piston
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/733
particularly when only a few breakers are installed at aparticular installation.
Moreover, compressed air is released through an orificeat the exhaust point at a high velocity and causes a soundlike thunder. This may be frightening to people in thevicinity. Substations involving a number of such breakersare a nuisance to residents nearby. The higher the kVlarger is the breaker and greater is the pressure of the airblast and its sound. Silencers, however, are provided tocontain such sound hazards. ABCBs are more appropriatefor large installations which require a large number ofbreakers to be installed in the same system to economizeon the compressed air supply arrangement. In light ofthe above impediments these breakers are now almostobsolete except for old installations or replacements.
19.5.5 Sulphur hexafluoride gas circuit breakers(SF6)
Refer to general arrangements of such breakers in differentratings as shown in Figures 19.14–19.16.
This is the latest technology in the field of arcextinction. It was introduced in the 1960s and attemptsto achieve a high dielectric strength between the contacts.At room temperature SF6 is a chemically inert, non-toxicand non-inflammable, colourless, odourless gas, havinga molecular weight of 146 and provides excellent arcquenching as a result of electronegative behaviour.
At atmospheric pressure, its dielectric strength is twoFigure 19.14 11 kV SF6 circuit breaker (Courtesy: Voltas)
(a) Exploded view of a pole (b) Breaker in a draw-out position
Figure 19.15 General arrangement of a 3–12 kV, SF6 circuit breaker in a housing (Courtesy: Voltas)
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/734 Electrical Power Engineering Reference & Applications Handbook
to three times that of air, as illustrated in Figure 19.1,and its arc-quenching ability many times more than air.This gas undergoes no chemical change at hightemperatures, except small decomposition into SF2 andSF4 gases and some metallic fluorine in the form of aninsulating powder while interrupting and quenching anarc. These gases and powder, however, are readilyabsorbed by activated alumina placed in the filters in theclosed-loop circuit of the gas, as discussed later. The gascycle is such that after every interruption the consumedgas is replenished through a reservoir filled with SF6 gasat a high pressure, say, sixteen times that of the atmosphereand connected to the main interrupting chamber throughpressure valves and filters. As soon as the pressure in theinterrupting chamber falls below a preset value, the valvein the reservoir opens and builds up the lost pressure. Dueto the very high pressure in the reservoir, compared to onlyalmost three times the atmosphere in the chamber, it ispossible that the pressure inside the interrupting chambermay sometimes exceed the required value. In the interruptingchamber, therefore, are also provided high-pressure releasevalves to pump the excess gas back to the reservoir througha compressor and a filter. The total gas circuit is a closedcycle without any venting to the atmosphere.
This gas is electronegative and its molecules quicklyabsorb the free electrons in the arc path between the
Figure 19.16(b) SF6 circuit breakers 300–550 kV (Courtesy: Alstom)
1 – Breaking chamber2 – Central housing3 – Insulating column4 – Insulating rod5 – Opening spring6 – Lower housing7 – SF6 monitoring block8 – Operating mechanism9 – Closing spring
1
12
3
4
56
7
8
9
Figure 19.16(a) An SF6 circuit breaker 123–145 kV, 31.5 kA.(Courtesy: BHEL)
1. Interrupter unit 5. Operating mechanism2. Multi-shed insulator 6. Coupler3. base tube 7. Operating rod*4. Hydraulic storage cylinder 8. Control unit
(a)
*Note: The tripping mechanism can be pneumatic, hydraulic orspring operated, depending upon the arc quenching techniqueadopted and energy required to extinguish the arc.
1
2783
5
46
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/735
contacts to form negatively charged ions. This apparenttrapping of the electrons results in a rapid buildup ofdielectric strength after a current zero. The detailedsequence of arc extinction may be summarized asfollows.
The contacts begin to compress a quantity of SF6 gasas soon as they start opening. This opening also causesarc plasma between the contacts. The temperature of thearc plasma ionizes the gas into sulphur and fluorine atomsand quickly becomes quenched through the turbulence ofthe compressed gas through a very strange process ofnegative ion formation. At higher temperatures, the S atomsbecome ionized into S+ protons and SN neutrons. The Se
electrons of the neutrons are immediately absorbed by thefluorine atoms to form fluorine ions (F –) which are heavyand are sluggish. They contribute little to maintaining theconductivity of the arc plasma. (See also Section 19.3.)This quickly immunizes the free electrons, quenches thearc plasma, extinguishes the arc and builds up the dielectricstrength after a current zero. After a current zero, theprocess quickly quenches the arc in the beginning itselfby sweeping away the arc plasma, thus improving thedielectric strength between the parting contacts andachieving successful extinction of the arc. The arc extinctionprocess may be slightly delayed when the contacts openvery close to the next current zero, and the quenchingmedium blows it out with force, before the current zero,leading to a case of current chopping. But with continuousimprovement in the techniques of arc extinction, it hasbeen possible to achieve an interruption devoid of a currentchopping or a restrike of the arc plasma.
As noted above, to quench the arc plasma successfully
it is essential to create a turbulence in the SF6 gas aroundthe arc plasma to destabilize and blow it out. This can beachieved in two ways:
1 Puffer technique (a puffer identifies the exhaling ofgas forcibly by compression)
2 Rotating arc technique
1 Puffer technique
Destabilization of the arc plasma is achieved by forcedconvection of gas created by the movement of the mainand arcing contacts through a puffer piston. This is anintegral part of the moving main and arcing contacts (bothbeing concentric).
Sequence of arc quenchingRefer to Figure 19.17. On a trip signal the main movingcontacts start separating a little ahead of the movingarcing contact and compress gas through the puffer pistoninside the tubular chamber. On separation the main fixedand moving contacts are transferred to the fixed and themoving arcing contacts as shown. As soon as the movingarcing contact starts separating, an arc is formed betweenthe fixed and the moving arcing contacts and the alreadymoderately compressed gas is compressed further. Thiscompressed gas is impinged with full force through theblast nozzle (Figures 19.18(a) and (b)) at right angles tothe arc plasma from all sides to achieve instantdestabilization of the arc.
Through radiation also, the arc plasma dissipates apart of its heat which supplements the quenching. But
1
4
2
3
5
6
7
8
Pole in closed position. Mainand arcing contacts closed
Pole at the moment ofseparation of arching contacts
Pole duringarc quenching
Pole after arcquenching
123
– Fixed arcing contact– Tubular gas (blast) chamber– Puffer piston
456
– Main fixed contact– Main moving contact– Fixed contact assembly
78
– Arc chute– Moving contact assembly
Figure 19.17 Sequence of arc extinction through the puffer technique in an SF6 breaker through the cross-section of a pole(Courtesy: NGEF Ltd.)
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/736 Electrical Power Engineering Reference & Applications Handbook
this is too meagre a contribution, as heat dissipationoccurs only through the outer surface of the arc plasma.Nevertheless, it is the major cause of gas impedimentgiving rise to the phenomenon of clogging, discussedlater, and which helps in arc extinction.
The events are so fine-tuned and the size of chamber,pressure of gas, travel, distance of the moving contactand the size of blast nozzle are so designed and minutelyadjusted that a near-strike-free interruption can be achievedfor low reactive currents (inductive or capacitive) as wellas full-load and very heavy fault currents. The advancecompression of gas through the movement of main contactplays an important role by storing a part of the gas evenbefore opening of the arcing contacts.
At high instantaneous currents the arc may occupymost of the contact area between the arcing contacts andmay impede the flow of gas through the arc plasma. Thisphenomenon is termed the clogging effect, but it assistsarc extinction in the following manner.
The SF6 gas around the arc plasma takes away a part ofits surface heat by radiation. At high temperatures, the gasloses its specific gravity, becomes light weight and diminishesin momentum (µ mu2). As a result, the gas is renderedincapable of penetrating through the arc plasma to quenchit. The flow of gas through the thick of the arc plasma isthus impeded (restrained).
As the moving contact moves away, so the arc plasmaelongates, losing its initial intensity, and as it approachesthe current zero, it loses the most of it. The gas, on theother hand, cools and regains its lost mass, while itspressure in the chamber continues to build to its optimumlevel, making it more capable of extinguishing a lesssevere arc plasma. The interrupter can thus be adjustedto blow out the arc at the first current zero, while clearingheavy to very heavy fault currents.
Similarly, at lower currents, the volume of arc plasmais too small (µ I2) and so is the clogging effect. Thepressure and volume of the quenching gas can be adjustedto interrupt the current now also at current zero. All theseadjustments are preset and sealed by the manufacturer.
Since the arc extinction technique is highly effectiveand quick and occurs when the arcing contact is stillmoving, arc length and hence contact travel, can bereduced as can the arc energy and the excessive heatingand the erosion of the arcing contacts. An extended contactlife can thus be achieved by this technique.
For MV and HV systems the normal puffer techniquehas been quite prevalent and adopted by all leadingmanufacturers. For constructional details and moreinformation on this mechanism, refer to the manufacturers’catalogues. Figure 19.18(a) illustrates a typical poleassembly of a 12 kV and Figure 19.18(b) up to 420 kV,SF6 circuit breaker.
Further developments
The operating energy requirement in the natural form ofpuffer technique was high as the tripping mechanismwas also required to supply the energy to compress thegas. Normal puffer in its natural form was thereforeincapable to interrupt the arc plasma at higher voltagessay, above 145 kV. Initially these breakers were therefore
1. Fibre glass arc chamber tube2. Lower pole head3. Cap4. Gas filling valve5. Main fixed contact6. Fixed arcing contact7. Moving contact arrangement8. Moving arcing contact9. Blast nozzle
10. Expansion chamber11. Lower contact12. Lower terminal13. Top terminal14. Spline shaft lever15. Switching lever16. Two level pressure switch
– 1st level contact for alarm– 2nd level contact for trip and lockout
17. Enclosure for alumina18. Explosionproof safety valve
Figure 19.18(a) Cross-sectional view of a pole of a 12–36 kVSF6 breaker (Courtesy: NGEF Ltd.)
3
18
1
10
13
5
6
8
7
9
12
11
15
14
2
4
17
16
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/737
produced only up to 145 kV or so. But with continuousresearch and improvisation in tripping mechanism andarc quenching techniques it has now been possible tosubstantially reduce the earlier arc energy as discussedbelow,
As we can see there are two main factors responsible forthe arc extinction,
– Compression of SF6 gas in the arc chamber. The gasis used for the thermal blast
– Elongation and weakening of the arc plasma with themovement of the arcing contact. A thin and weak arcassists its extinction.
This the manufacturers have achieved by optimizing theuse of arcing heat through,– Thermal blast– Arc assisted and– Double volume or double motion techniquesThese techniques are briefly noted below.
Thermal blast and arc assisted technique
The design of the arc chamber is improvised to assist thearc-quenching capability of the arcing chamber, by furthercompressing the gas that has already expanded duringarcing and impinging this on the arc with a greater blast.The blast also helps the main moving contacts to movefarther away with a greater force, elongate the arc andreduce the energy requirement by the moving mechanismto interrupt the breaker. This makes the whole process ofarc extinction easy and smooth. This technique, instead of
equalizing the arc heat, reduces the arc energy itself,facilitating a quicker and smoother extinction of the arc.The moving mechanism that in a normal puffer is usuallyhydraulically or pneumatically operated (Figure 19.16(a))due to the higher energy requirement by the movingmechanism can now be achieved through a simple springmechanism (Figure 19.16(b)).
Double volume or double motion technique
The improvisation of the above techniques and makingthe main fixed contact also moving (double volume) havefurther enhanced the compression of gas. Elongation ofarc has reduced the arc energy requirement. All thesehave made the arc extinction easier, smoother and quicker.It has resulted in minimizing the arc energy to as low asabout 15% of the normal puffer. Most manufacturersadapt to all or some of such techniques. Figure 19.18(c)illustrates a comparison of energy requirements betweenthe various techniques developed so far.
Since all parameters as noted above like pressure andvolume of gas and elongation of arc can be fine-tunedthe latest SF6 breakers can be made restrike-free andsuitable for all applications. With these improvisationsSF6 breakers are now capable of interrupting any voltageand are produced up to 1100 kV. As SF6 breakers can bedesigned to provide a very smooth interruption of arc,devoid of current chopping or restrike of the arc plasma,they may also be termed soft break interrupters. SF6breakers are most extensively used breakers and aresuitable for practically all applications and voltage systems.The other advantage with SF6 switchgear is space saving
Figure 19.18(b) Cross-sectional view of a pole of SF6 breaker without pre-insertion resistor (up to 420 kV)(Source: GEC-Alsthom)
1. Support insulators 7. Coupling contact 13. Insulating rod2. Fixed contact 8. Moisture absorber 14. Safety diaphragm3. Moving contact 9. Density switch 15. Oil pump4. Nozzle 10. Hydraulic ram 16. Accumulators5. SF6 compression piston 11. Driving rod 17. HP pipe6. Arcing contact 12. Valve block
8 6 2 4 3 5 7 1 9 13 11 10 12 15
1 14 17 16
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/738 Electrical Power Engineering Reference & Applications Handbook
up to 70–90% over the conventional type of switchgears(Table 19.2). Since these breakers are totally enclosedand sealed from the atmosphere, they are also the mostrecommended choice for all installations that are hazardousand prone to explosions.
2 Rotating arc technology
The process of arc quenching can be enhanced byincreasing the turbulence by ionizing more gas atoms, toincrease the gas pressure and therefore turbulence. Thisis possible by bringing more gas into contact with thearc plasma, and this can be achieved by rotating the arcplasma between the contacts and displacing the arc by amagnetic blowout. A general method of achieving this isby providing an electromagnetic field around the fixedcontact, which gives the required rotating motion to thearc plasma, when the moving contact moves away fromthe fixed contact, as illustrated in Figure 19.19, similarto a motoring action. Figure 19.20 illustrates one pole ofsuch a breaker, provided with a magnetic coil. The breakersbased on this principle are known as rotating arc circuitbreakers. Figure 19.21 illustrates the rotating arc formationand the direction of a magnetic field during an interruption.As the arc is made rotating over the arcing contacts, theheating and thus the erosion of the contacts is low in thesebreakers, and they have an extended contact life.
This technique, although good, is cumbersome and istherefore generally not practised now by themanufacturers.
1
3
2
64
5
Pole duringarc quenching
1 Fixed contact assembly 4 Arc chute
2 Magnetic field coil 5 Moving arcing contact
3 Fixed arcing contact 6 Arc
Figure 19.20 Typical design of one pole of a rotating arc SF6circuit breaker
Figure 19.19 Making the arc rotate in a magnetic field
Mag
netic
flu
x
Arc current
Motion
Arc currentMagnetic flux
Magnetic flux
Motion
Rotationof arc
Contact bar
Field coil assembly(Replica of left-hand rule, Figure 1.1)
Figure 19.18(c) Comparison of energy requirement for arcextinction in an SF6 breaker, using different techniques (Courtesy:Alstom)
100%
60%
30%
20%
15%
Normal Improvised Thermal Arc Double puffer puffer blast assisted volume
(or doublemotion)
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/739
Operating mechanism
Because of optimization of arc energy and less energyrequirement for arc extinction, it is now possible to usea low energy spring mechanism requiring littlemaintenance (in absence of air for pneumatic and oil forhydraulic mechanism) and is more reliable in operation.It can also be used in conjunction with a synchronizingrelay. Perfect timing of operation is mandatory whenoperating in association with a synchronizing relay andthat is possible with spring operated mechanism.
Pre-insertion resistorSF6 breakers, when used for switching long transmissionlines at 420 kV and above, are provided with a preinsertionresistor across each interrupting contact to limit over-voltages that may occur during a closing or openingsequence, as a result of heavy charging currents as notedin Table 24.2. The value of the resistor may be around400 W for the line parameters, considered in Table 24.2and may vary with line parameters. The resistors areconnected so that during a closing sequence they short-circuit the making contacts before closing the maincontacts for, say, 8–10 milliseconds, and open immediatelyafter the contacts are made. The same happens during anopening sequence. See also Section 17.6.2. By adjustingthe value of this resistor a restrike-free switching can beachieved while switching large capacitors or reactors atany voltage. See Figure 19.22.
Advantages of SF61 Low gas velocity and pressure minimizes the tendency
towards current chopping.2 A closed recycling of gas causes no noise or
contamination of the atmosphere.3 There is no carbonization and therefore no tracking.
(conduction of the insulating medium).4 Because of the extremely good dielectric properties
of SF6 gas, the arc gap and the contact travel andhence the arcing time are low, requiring less energyto interrupt (Figure 19.6).
Figure 19.22 Cross-sectional view of a pole of SF6 breaker with pre-insertion resistor (up to 420 kV) (Source: GEC-Alsthom)
1. Support insulators 9. Density switch 16. Accumulators2. Fixed contact 10. Hydraulic ram 17. HP pipe3. Moving contact 11. Driving rod 18. Moving contact for4. Nozzle 12. Valve block insertion resistor5. SF6 compression piston 13. Insulating rod 19. Semi-moving contact for6. Arcing contact 14. Safety diaphragm insertion resistor8. Moisture absorber 15. Oil pump 20. Insertion resistor
17 16
19 1814
8 9 1 20 6 2 4 3 5 1 13 11 10 12 15
Successive arcpositions
Contact
Cylindricalelectrode
The arrows indicate the direction of magnetic forcesMagnetic forces on the spiral arc
Figure 19.21 The spiral arc in a rotating arc SF6 circuit breaker(Source: South Wales Switchgear Ltd.)
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/740 Electrical Power Engineering Reference & Applications Handbook
5 As the arcing time is very low, it causes no or only asmall amount of contact erosion.
6 It is highly suitable for hazardous locations.
19.5.6 Vacuum circuit interrupters
(i) Vacuum circuit breakers (VCBs)
Refer to the general arrangement of a loose breaker shownin Figure 19.23(a), and in housing Figure 19.23(b). Figure19.23(c) shows a 36 kV outdoor vacuum circuit breaker.The electrical breaking capacity in vacuum has beenlong known. But it was not until 1970, that it was usedin the making and breaking of currents at high voltages.It has been a greatly recognized and well accepted breaker,leaving behind all other techniques of arc breaking andextinction in its voltage range. In vacuum, a 10 mm gapat about 1/106 mm vacuum of mercury is capable ofwithstanding a peak voltage up to around 245 kV (Figure19.1). These breakers therefore, are very compact andrequire very low maintenance.
Unlike other mediums, the dielectric strength ofvacuum increases only marginally with the gap, which isthe limiting factor in producing such breakers above 36kV. These breakers are therefore used only for medium-
voltage systems (2.4–36 kV). Some manufacturers haveattempted to produce them up to 72.5 kV but they havenot shown the desired results. The application of thesebreakers therefore continues to be up to 36 kV only.
A comparison of dielectric strength of high vacuumwith the other available mediums is shown in Figure19.1. The very high dielectric strength of vacuum makesit possible to quench an arc with a very small contactgap and breakers with very compact dimensions can bedesigned.
Because of the low contact gap, low arc resistanceand fast clearance, the arc energy dissipated in vacuumfor a particular current is 1/10 that of oil and 1/4 that ofSF6, and is illustrated in Figure 19.6.
Vacuum is finally judged to be the best medium toquench the arc plasma and interrupt a circuit under themost adverse conditions. Figure 19.24 gives cross-sectional view of a vacuum interrupter and typicalconstruction of the arcing contacts. Figure 19.25 showsits assembly.
Advantages
Some advantages of vacuum circuit breakers aresummarized below:
Meteringand
relay chamberExplosion covers
Handle tomove the
trolleyR Y B
InsulatorsPlug-incontacts
Busbarchamber
C.T.
Circuitbreaker F
ront
P.T.
Cable chamber
Groundingswitch
Trolley Base frame Rollers
Figure 19.23(b) General arrangement of the breaker in a housing
7.2–36 kV vacuum circuit breaker (Courtesy: Siemens)
Figure 19.23(a) General arrangement of the breaker on a trolley
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/741
applied voltage and the TRV approaches a full appliedvoltage (Figure 19.27) and hence, a tendency to causea restrike. A VCB is devoid of a restrike after a currentzero, as explained later.
Because of short duration of arc they have an extremelylow energy requirement to actuate the operatingmechanism and an equally short breaking time.
Disadvantages
Vacuum breakers have a few disadvantages also as notedbelow:
1 They may inherit current chopping tendencies at verylow currents of 3–5 A, varying from one manufacturerto another and depending upon the contact materialused (some manufacturers have been able to improveit to 2–3A). This is due to their extremely fast operationas a result of a high vacuum pressure of the order of10–6 Torr (1.333 ¥ 10–4 N/m2) or more (one Torr beingthe pressure equivalent to hold a column of mercury1 mm high). Thus they cause a high TRV, particularlywhen interrupting a highly inductive or capacitivecircuit (Figure 17.11(d)).
2 Very high vacuum may have a tendency to cold weldingof the making contacts. Two pure metals, when joinedhave a tendency to stick together under high vacuum.This phenomenon is termed cold welding. The contactson closing may require a lot of force to separate themwhich may prove to be detrimental in clearing a faultpromptly.
3 At no-load, opening of contacts may lead to rougheningof the surface, due to the breaking of the cold weldingthat takes place.
4 Since a very small gap in vacuum can withstand a
– Since the contacts make and break in vacuum there isno oxidation of the contacts. The contacts do notdeteriorate nor lose their dielectric properties withswitchings and provide a longer working life.
– They cause no fire hazard and are highly suitable forchemically aggravated and hazardous locations.
– They require extremely low maintenance and littledown-time.
– They make no noise during making or breaking ofcontacts as it takes place inside a hermetically sealedarc chamber.
– They do not emit any gases.– They are the only devices that are independent of the
operating system, as the breaking capacity is dependentmainly on the material and contour of the contactstructure and the quality of the vacuum.
– At lower current, say, up to 1 kA, the maximumduration of arc even at low p.fs. is of the order of justone-half to one cycle of the natural frequency of thesystem, as against nearly two cycles for an MOCB.[The low exciting currents, at low p.fs. are moredifficult to interrupt rather than large currents at highp.fs. due to an extremely adverse voltage-current phasordisposition at low p.fs.] For more clarity refer to Section17.6.2. The current now is nearly 90º lagging the
Figure 19.23(c) 36 kV outdoor vacuum circuit breaker(Courtesy: Jyoti Ltd.)
Figure 19.24 Sectional view of a 12 kV up to 2500 A, 40 kAvacuum interrupter (Courtesy: BHEL Ltd.)
Fixed contact stem
Fixed terminal pad
Glass ceramichousing
Arc chamberFixed contact
Movingcontact
Glass ceramichousing
Metallic bellowsMoving contactguide
Moving contactstem
Blown-up view of arcingcontacts. Also seeFigure 19.26.
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/742 Electrical Power Engineering Reference & Applications Handbook
very high voltage, a larger gap than required will notincrease its dielectric strength. This is the limitingfactor for a VCB to exceed a certain voltage system,presently 36 kV.
5 They may cause contamination of the vacuum due togas produced by arcing.
6 They may lead to deterioration of the insulation ofthe insulating container due to condensing of the metalvapour on the inner surface of the container (more intransverse magnetic field type breakers).
7 They also have a tendency to melting and welding ofthe contacts while making or carrying large currents.However, this is overcome by suitably designing andcontouring the contacts so that the arc impinges overa large area of contacts rather than at one point onlyto prevent melting of contacts. The material of thecontact is chosen so that it will produce less gas content,have good anti-weld properties and low current-chopping tendencies (high contact resistance). Thenormal metal alloys in use are:
• Low resistance – high kA alloy (high melting point):copper – bismuth has a good resistance to coldwelding but has a higher probability of currentchopping. Refer to curve 4 of Figure 17.8.
• High resistance – low kA alloy (low melting point):copper–chromium (CuCr) which also has a goodresistance to cold welding and a lower probability
of current chopping, similar to in OCBs. Refer tocurve 2 of Figure 17.8.
Limitation of using AgW or CuW contactmaterials in VCBsThe properties of vacuum interrupters depend largely onthe material and contour of the arcing contacts.Experiments have shown (Further Reading, ref. 9) thatcontact materials AgW and CuW as used for vacuumcontactors and can limit chopping current (Ic) havelimitations in interrupting large arc energies because ofvery high melting temperature (3370∞C) of tungsten (W)compared to Ag (960∞C) or Cu (1083∞C). During an arcinterruption particularly on faults, it is only Ag or Cuthat melts and on solidification shows cracks on the contactsurface. They are thus suitable for low arc energies only.At low arc energies ( )c
2µ I AgW or CuW contacts haveshown excellent results with very low chopping currents.They are therefore ideally suited for LV and HV vacuumcontactors but not vacuum circuit breakers. On the otherhand Cu and Cr (1615∞C) jell very well with each otherat all currents and make a good contact material forVCBs. During melting they are soluble into each otherand on solidification leave a smooth contact surface.CuCr is thus ideal for all ratings of vacuum circuit breakers(VCBs) until at least a better contact material is developed.
The theory of arc extinction, as related to vacuum, is
ON position OFF position
1. Upper interrupter support2. Top terminal
3,7. Glass ceramic housing4. Arc chamber5. Fixed contact6. Moving contact8. Metallic bellows9. Moving contact stem
10. Bottom terminal11. Lower interrupter support12. Lever13. Insulated coupler14. Contact pressure spring15. Release pawl
2
1
3
45
6
78
9
11 1012
1314
15
Figure 19.25 A pole assembly of a vacuum circuit breaker
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/743
typical. No arc can take place in the absence of a gas. Themolecules of the gas alone under heat and pressure causeionization, responsible for the arc plasma and subsequentdeionization, which extinguishes it. In vacuum, the contentof gas is missing. In fact it should have been an idealcondition to interrupt a circuit without the formation of anarc and thus make the interruption devoid of high TRVsand the phenomenon of arc restrikes. But it is not so, as theheat generated at the parting contacts causes boiling of thecontact material (generally alloy of copper as mentionedabove). This boiling produces metal vapour, usually ofcopper atoms (copper, of all the other alloy metals, has thelowest melting point). Most of the metallized vapour isthus formed of copper atoms only. An electric field withinthe contacts quickly generates free electrons of this metalvapour and a constricted localized plasma is established.Beyond a certain current value, the behaviour of the arc issuddenly modified and the constricted form of the arcplasma transforms to a diffused form. The cathode spotbecomes divided into several very small spots, which thenmove very rapidly, repelling each other continually. Thisphenomenon is used in current breaking in vacuum. Inother mediums and conventional interrupters, the currentmaintains only a single arc column. These spots have anextremely high current density which can reach millionsof amperes per square centimetre. The result is that veryhigh density streams of electrons are emitted without acommensurate quantity of metal vapour. As the currentfalls to zero, at the next current zero the metal vapoursolidifies, leaving behind no medium to hold the arc andthe electrons cease to cross the contact gap. The dielectricstrength reaches its maximum. The anode, being cool isno longer able to emit more electrons, hence it is not ableto restrike after a current zero. Arc extinction in such amedium is therefore extremely quick. The arc plasmadepends largely upon the alloy being used as the contactmaterial. It is of vital importance to limit the excessiveboiling of the contacts due to the arc heat. It is possible toachieve this by suitably designing the contour of the contactsto increase their area. Depending upon the design of thecontacts’ contours, the breaker may be
• Axial magnetic field type or• Transverse magnetic field type
In axial magnetic field type the shape of the contactsmay be as shown in Figure 19.26(a). With this design ofcontacts the arc plasma will spread out axially and increasethe contact area whereas in transverse magnetic fieldtype breakers (Figure 19.26(b)) the contacts are like spiralslits in the form of petals. The design of contacts causesthe current to flow radially outward along the contact,and gives it a rotational movement under the influenceof electrodynamic forces (similar to a rotating arc SF6interrupting device, Section 19.5.5 and Figure 19.21).The rotational movement adds to the contact area andprotects the contacts from damage and a reduced life.But in this case the arc will fall perpendicularly to themagnetic field. It is possible that it may impinge on theinside insulating lining of the contact chamber and rupturethe interrupter. Axial magnetic field type contacts aretherefore generally adopted by manufacturers.
(ii) HV vacuum contactors (HVCs)
This technology (interruption in vacuum) has also beenmade use of in designing contactors. Presently vacuumcontactors are being produced by some manufacturerseven up to 24 kV and 800 A. Figure 19.26(c) shows theviews of an HVC. The use of these contactors can bemade in the switching of MV motors (Section 12.12),HV transformers, capacitors and reactors.
Magnitude of chopping current (Ic) in HVCs
With continuous researches around the world, it has beenpossible to contain it within 0.5 A to 1.2 A, even less inVCs by using AgW (silver tungsten) or CuW (coppertungsten) contacts instead of copper chromium (CuCr)contacts used in VCBs (Further Reading, ref. 9). Some
Arcing with contrate or slotted cup contact
(a) Slotted cup type contacts of a 7.2 kV, 25 kA vacuum interrupter(Axial magnetic field type) (Courtesy: Siemens)
Figure 19.26 Magnetic arc control to increase the contactarea of the arcing contacts in a VCB
(b) Arcing with spiral petal contact(Transverse magnetic field type)
CurrentArc
trajectory
Arc
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/744 Electrical Power Engineering Reference & Applications Handbook
manufacturers like Toshiba have achieved it up to 0.3 A.This is against 2–3 A in a VCB noted earlier. It has alsobeen possible to contain the arc duration within one cycle(< 20 ms), closing time 3–4 cycles and interrupting time1.5–3 cycles and even less. The low Ic also helps extinguishthe arc plasma safely by the immediate current zero,point ‘a’ (low Ic makes ‘a1’ approach closer to ‘a’, Figure19.27) and reduce the TRVs making them safe for theterminal equipment. The parting contacts recoveringdielectric strength is so rapid that the arc is safely quenchedeven when the interruption occurs just before a currentzero and full recovery voltage may appear across theparting contacts (Section 19.6). VCs are therefore capableof interrupting low inductive (highly lagging) or highcapacitive (highly leading) currents with little likelihoodof an arc restrike.
Consequently, these contactors cause low arc voltages(Ic.Zs) incapable of causing a restrike of the arc plasma(Figure 19.27). Referring to Example 17.0 the arc voltagein case of VC having an Ic of 0.5 A will be only 0.5 ¥4000 or 2.0 kV for a 350 kW and 0.5 ¥ 2400 or 1.2 kVfor a 500 kW, 6.6 kV motor. These arc voltages areharmless. Also arc voltage falling in phase with TRVdoes not aggravate the situation.
NoteAt the instant of arc interruption, it is the arc voltage that may bemore severe and the terminal equipment should be capable towithstand the same. But gradually as the restrikes take place andstriking voltage builds up, it is the TRV that may become moresevere and defining surge voltage, which the terminal equipmentshould be capable to withstand or means provided to mitigate itsseverity.
AgW has proved to be the most ideal material for arcextinction in vacuum contactors except for high cost ofsilver. Varying content of Ag can vary the arccharacteristics. So is with the change in copper contentwith W for CuW contacts. Performance with Ag is foundto be far more satisfactory than with Cu. Differentmanufacturers however adopt to different mix of Ag orCu with W to meet the functional requirements.
It is noticed that Ic also varies with the surge impedance(Zs) of the interrupting circuit. Higher the Zs (as for lowerratings and higher voltage machines (Figures 17.7 a, b,c)) lower is the Ic and vice-versa, which is a redeemingfactor for the safety of the terminal equipment.
The other merits and demerits of a VC remain generallythe same as discussed for a VCB. However the followingmay be noted as additional features for vacuum contactors;
• Low arc energy helps enhance the contacts’ life andprevents contact welding.
• There being no contact bounce, which further enhancestheir contact life compared to an air-break contactor.
• Low coil consumption – Typically pick up about 300–1500 VA and run 30–50 VA or so depending uponrating of the contactor and may vary from manufacturerto manufacturer.
• Very high contact life say, over 1–3 million mechanicaland 0.5–1 million electrical operations depending uponcurrent rating of the contactor, is more than enoughfor a lifetime operation.
• High operating rate suitability, say up to 1200 ormore operations per hour (it may reduce at higherratings) as against about 150 operations in conventional
1
1
4
3
2
5
1 – Auxiliary switch2 – Closing solenoid3 – On/off indicator4 – Mechanical off-push button5 – Operation counter6 – Mechanical latching device7 – Trip coil8 – Metallic base frame
1 – Upper contact terminal2 – Epoxy cast armature assembly3 – Vacuum interrupter4 – Lower contact terminal5 – Epoxy resin moulded body
Figure 19.26c 6.6kV vacuum contactor (Courtesy: Jyoti Ltd.)
2
4
3
5
6
7
8
Front view Rear view
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/745
air break contactors. This makes them ideal for motorswitchings and controls and suitable for applicationsrequiring frequent switchings, brakings and reversals.
• Very high making and breaking currents.• They are very compact and lightweight. The size
may be up to one-fourth that of conventional air-break contactors.
NoteValues mentioned above are just for reference. For exact valuesone must contact the manufacturer.
Applications: Specially at steel plants, power stations,fertilizers, chemicals, petrochemicals, mines and all firehazardous and corrosive locations besides normalapplications.
(iii) LV vacuum contactors (LVCs)
The advantage of vacuum interruption is now being madeuse of in LV contactors also. Some manufacturers havealready developed this in the current capacity of 160–1200 A or so and many others are in the offing to launchthis product in the market. Because of cost considerationit may have constraints of using them in still lower ratingsuntil at least it is possible to produce the LV vacuuminterrupters such as shown in Figure 19.24, in lowerratings at reasonable cost.
Vacuum contactors in LV would extend the sameadvantages as noted for HV VCs. They are speciallyuseful for applications demanding frequent switchingsand reversals. For LV motors above 100 HP they areideal interrupters.
19.6 Phenomenon of currentchopping
With advances in technology in the field of circuitinterruption, fast to extremely fast interrupting deviceshave been developed, aided by high-performing arcquenching and extinguishing mediums, as discussedabove. While such techniques have helped in theinterruption of system currents, particularly on faults (atvery low p.fs.), they have also posed some problems incertain types of circuit breaking. For instance, an airblast circuit breaker and a vacuum circuit breaker areboth extremely fast operating. When interrupting on afault, their operation is as desired but at much lowercurrents than rated, such as at no-load, they may operaterather faster than desired and interrupt the circuit beforea natural current zero. Premature interruption of a circuitsuch as this is termed current chopping and may occurjust before a natural current zero when the current issmall. In a VCB it is of the order of 3–5 A (now achievedup to 2–3 A).
When the p.f. of the interrupting circuit is low, aswhen interrupting an induction motor or a transformer,running on no-load and drawing a small but highlyinductive current, and when interrupting a highlycapacitive circuit, such as a live but unloaded cable oroverhead line carrying a high capacitive charging current,in all such cases during a circuit interruption the currentmay interrupt before a natural current zero and cause anear peak system voltage across the parting contacts.Figure 17.11(d) has been redrawn in Figure 19.27 formore clarity. Under the cumulative influence of thereflected wave (arc voltage = Ic.Zs) and the equipment’sback e.m.f., it may attain a value of high TRV, capable ofbreaking the dielectric strength across the parting contactsof the interrupting device. It may cause yet higher TRVs,until at least the immediate first natural current zero ofthe interrupting current. See TRV at current zero (Figure19.27). Thus it would endanger the terminal equipmentand the inter-connecting cable. Such surge voltages (TRVs)may rise up to 2.5–3 p.u. in normal operation. It is possiblethat the arc does not extinguish at the first current zero,point ‘a’ on the current wave. If a sufficiently highdielectric strength between the contacts is not attained,even by the next natural current zero (point ‘b’) by virtueof an extremely low contact gap or an inadequate insulationlevel in the arc chamber of the interrupting device, thearc may restrike again and cause higher TRVs. This shallfurther complicate the process of interruption andextinction of the arc. See Blower et al. (1979), Telanderet al. (1986) and IEEE transactions (1977).
Significance of chopping current (Ic)
Lower the Ic, closer will move the point ‘a1’ to current
Figure 19.27 Approximate representation of assumed voltageand current waveforms illustrating a current-chopping effect andits attenuation while interrupting a circuit having 0.3 p.f.
TRV = 2.5 pu.
* 0.95Vm Vm
Contacts break andarc extinguishes here
Voltage wave
0.02 part of one halfcycle of the current wave(enlarged for clarity)
(Ic) current choppedat this pointa1
a b
Surge current ceasesat the immediatecurrent zero ‘a ’
Current wave
* Parting contacts are subject to this voltage which they are notable to withstand and cause an arc raising the TRV up to 2.5 pu
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/746 Electrical Power Engineering Reference & Applications Handbook
zero ‘a’ (Figure 19.27) during a circuit interruption. Itwill reduce the TRV and make it easier to extinguish thearc and interrupt the circuit by the immediate currentzero (point ‘a’), besides making it safer for the terminalequipment.
NoteThe surge frequency at which the TRV will restrike will be extremelyhigh. It may be of the order of 10–100 kHz, depending upon thecircuit constants L and C. To interrupt such high-frequency currentsis difficult for an ordinary breaker. But with the use of high technologies,such as adopted in SF6 and VCB interrupting devices, which makethem fast operating (for arcing time see, Table 19.1), it is possible tointerrupt, such high-frequency TRVs promptly.
19.6.1 Influence of frequency on the system
An a.c. current waveform passes through a natural zeroevery one half of a cycle. This is a highly redeemingfactor in an a.c. system. It helps to extinguish an arcpromptly, which is not so in a d.c. system. A higherpower frequency than rated would in fact support theextinction of an arc, irrespective of its other magnetizingeffects, while a lower power frequency than rated willdelay and add to the complications of extinguishing anarc. At surge frequencies the situation becomes different,as the zeros occur so frequently that the contacts aresubject to frequent restrikes of the arc and are vulnerableto damage, while the actual extinction of an arc will takeplace only at a natural current zero. To cope with suchsituations the interrupters must be fast operating. Figure19.27 illustrates the restriking phenomenon of the partingcontacts during current chopping that is assumed to occurat point ‘a1’, on the current wave. The actual current andvoltage waveforms may differ from assumptions,depending upon the speed of the breaker, rate ofdeionization, current being interrupted, its p.f. and theinstant at which the interruption initiates. In addition,the surge impedance of the circuit being interrupted. Weassume that the TRV may rise to 2.5 p.u. and is interruptedby the immediate first current zero (i.e. at point ‘a’ inFigure 19.27) in about 0.02 part of one half of a cycle ofa 50 Hz wave. During this period, if we consider thesurge frequency of the interrupting circuit to be of theorder of 13 kHz* the arc may restrike for nearly 2.6cycles or 5 times before a final interruption as determinedbelow.
Time for 0.02 part of one-half of a cycle of a normalfrequency wave of 50 Hz, during which current choppingoccurs:
= 12
150
0.02 second¥ ¥
\ Number of completed cycles of the TRV at the surgefrequency of 13 kHz
= 13 10 12
150
0.02 cycles3¥ ¥ ¥ ¥
� 2.6 cycles (approximately 5 restrikes)
*It is seen that the surge frequency during current chopping mayrarely exceed 20 kHz and which, in the context of switching surges,may be considered as low-frequency oscillations, easy to handleand interrupt.
R
Y
B
I� I� I�
iy i r i b
Arcrestrikes
(R pole opening)
i b i r i y
i b
i r
i y
C1 C2 C3
Gi g i b
i r
Gi rMotor
windings
I � = Load current i r, i y, i b = Charging or restriking currents
C1, C2, C3 = Interphase dielectric leakage lumped capacitances
Figure 19.28 One pole opening.Restriking phenomenon in phase ‘R’ causing charging currentsin phases ‘Y ’ and ‘B ’ which are still closed
By the immediate first current zero it is assumed thatthe contacts have travelled sufficiently apart to achievethe required deionization and have built up adequatedielectric strength to withstand at least 0.95 Vm. If thecircuit does not interrupt at the immediate current zeroat ‘a’, which is so near to the point of chopping ‘a1’, theinterruption will take place only by the next current zeroat point ‘b’ and result in another 260 strikes by then. Tostudy more accurate behaviour of an interrupter, withthe number of restrikes and the formation of the actualtransient voltage waveforms on current chopping,oscillograms similar to those during a short-circuit testmay be obtained (Section 14.3.6).
19.7 Virtual current chopping
This may occur during the interrupting process of aswitching device when not all the three poles will interruptsimultaneously. It is corollary to a closing phenomenon(Section 17.7.2(ii)) when not all the three poles make atthe same instant. This will also endanger the insulation ofthe other two phases. The interphase dielectric leakagecapacitances, as illustrated in Figure 19.28, are the cause.
When one of the poles, say of phase R, starts openingfirst and faces a restrike of the arc, leading to surgefrequency currents, similar (balancing) currents will beinduced in the other two phases that are still closed, inaddition to the normal current, II, that these poles willstill be carrying. The result will be that when these two
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/747
poles also open the charging currents at a surge frequencymay virtually force a faster or premature current zero inphase B, as illustrated in Figure 19.29. This is termedvirtual current chopping and may cause an additional TRV.
The amplitude of this TRV, however, may not be largedue to a generally low surge impedance of the interruptingcircuit during an interruption. It may achieve a level ofonly 0.6–0.7 p.u. (see Telander et al., 1986), which maysometimes prove fatal for the insulation of the terminalequipment due to its steepness. Charging currents woulddevelop in phase Y also (at point ‘y’, but not shown toavoid overlapping of curves). But current chopping is notpossible in this phase because point ‘y’ will fall furtheraway from a current zero, on the one hand, and the Y-phase would carry a near-maximum current at this instant,on the other. Current chopping is a phenomenon of smallcurrents.
19.8 Containing the severity ofswitching surges
19.8.1 Theory of energy balancing
From the above we can deduce that at the instant ofcurrent chopping the arc extinguishes for a moment andre-establishes as soon as the TRV reappears. At the instantof arc extinction, it may be considered that the arc energyis transferred to the dielectric medium of the partingcontacts. This energy reappears in the form of a TRV
across them, and tends to cause a restrike of the arcplasma once again. We can generally consider the arcenergy as the magnetic energy caused by the magnetizingcurrent of the interrupting circuit and the energy receivedby the dielectric medium as the capacitive energy.
If Inl is the inductive current in amperes (no-load currentof the motor or the transformer, Figure 1.15) and L theinductance of the circuit being interrupted in henry, thenthe electromagnetic energy, J, initially contained by thearc plasma
J L I = Joules1
22n◊ ◊ �
NoteIn fact, this energy should be less by the hysteresis loss component(Section 1.6.2A.(iv)) which has been ignored in the present analysis.
If Vt is the prospective peak surge voltage (TRV) in voltsand C the dielectric capacitance of the contact gap infarad at the instant of restrike, then the capacitive energyJ, received across the contact gap is
J C V = Joules12 t
2◊ ◊
For successful interruption of the arc plasma it isessential that the energy emitted by the arc plasma is atleast equal to the capacitive energy received by thedielectric medium. At the instant of arc extinction, thisphenomenon is termed energy balancing, when
12 n
2 12 t
2 ◊ ◊ ◊ ◊L I C V� �
or V I L
Ct2
n2 � � ◊
or V I L
CI Zt s n n� �� � ◊
We represent this through a circuit diagram (Figure 19.30)where
L C/ is the surge impedance, Z s, L and C the circuitconstants of the interrupting circuit, as discussed in(Section 17.6.4). C represents the dielectric capacitancebetween the parting contacts of the interrupter. Vt mustbe prevented, as far as practicable, from reachingdangerous levels with the use of surge arresters.
Inl of equipment cannot be altered once it ismanufactured. The surge voltage Vt, that will appear acrossthe contacts therefore becomes a function of theinductance, L, of the circuit being interrupted. L is theinductance of the motor or the transformer windings upto the terminals of the interrupting device, including theinductance of the inter-connecting cables or the bus system.The dielectric strength is the capacitance, C, betweenthe contacts. The C of the contacts will change with thetravel of the contacts and the deionization of the arcplasma. The influence of the inductance of the circuit L,can be reduced by introducing some capacitance orresistance into the circuit. Capacitance can be introducedby installing a few p.f. correction capacitor banks acrossthe motor or the transformer terminals and the resistancecan be introduced temporarily across the moving contactof the interrupting device through its closing mechanism.This is a practice adopted by leading manufacturers toprovide a resistance where the interrupter is required tooperate under adverse switching conditions.
Figure 19.29 An approximate illustration of a virtual currentchopping in phase ‘B ’ as a consequence of restrike of arc inphase ‘R ’
Location, r – Interruption commencesr ¢ – Restrike of arc occurs in phase ‘R ’ causing a charging
current ‘i r’y – Charging current ‘iy ’ develops in phase ‘Y ’ (Not shown
to avoid overlapping)b – Charging current ‘i b’ develops in phase ‘B ’
b ¢ – Charging current i b causes a virtual forced current zeroor virtual current chopping at this point
Virtual current chopping in phase ‘B ’
I
R Y
y
B
i b
r b ¢
r ¢b
i r
w t
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/748 Electrical Power Engineering Reference & Applications Handbook
19.9 Comparison of circuit breakersusing different interruptingdevices
To assist in making an easy selection of a breaker for aparticular application, we have provided a comparisonbetween the various circuit breakers as in Table 19.1.
19.10 Gas insulated switchgears(GIS)
This is discussed only briefly to give an idea of theadvantages and applications of SF6 gas technology inHV and EHV switchgears compared to conventional airinsulated switchgears. For finer details one must consultthe manufacturer.
The advantages of SF6 gas noted in Section 19.5.5prompted its application into development of gas insulatedswitchgears even complete GIS based substations. VCBsand SF6 breakers comprising SF6 gas insulated motorizeddisconnectors and grounding switches, CTs, VTs andCVTs make a complete gas insulated substation extendingthe following advantages over conventional air insulatedswitchgears. Use of VCBs or SF6 breakers would dependupon the system voltage. Usually VCBs are used up to36 kV and SF6 breakers for 72.5 kV and above (Table19.2). A few diagrams showing VCB based GISsubstations are shown in Figures 19.31 and 19.32. Figure19.33 shows the layout of a SF6 breaker based GIS powerhouse switchyard, while Figures 19.34 and 19.35 illustratethe cross-sectional and sectional views of a SF6 breakerbased GIS with non-isolated double busbar system. Figure
19.36 illustrates sectional view of an isolated doublebusbar GIS.
Special Features
– VCBs and SF6 breakers are essentially maintenancefree. Gas insulated switchgears are therefore highlyreliable and almost maintenance free.
– The enclosure of the switchgear is at ground potentialand extends total safety to operators.
– All components are housed in hermetically sealedmetal enclosures filled with SF6 gas.
– They are environment friendly and corrosion resistantand can be installed in humid and saline (coastal)areas or industrial areas that are prone to dust andpollution and may also be fire hazardous or chemicallyaggravated.
– The plug-in or cable sealing-ends or busbar terminationsare at ground potential and safe to touch.
– It is possible to provide LEDs on the outer surface ofthe modules to ensure safe touch leakage voltage.The LEDs would glow when the leakage capacitancevoltage to ground would exceed the safe touch voltage.
– Each equipment and component is encapsulated in acompact module which occupies only a small spacecompared to if it was air insulated. Also each modulebeing at ground potential needs only small clearancesfor maintenance. GIS substations are thereforeextremely compact (see Table 19.2) and can be installedindoors or outdoors as per the site requirement.
– They extend an easy solution to space problem andare ideal for densely populated areas. VCB based GIShave extensive applications at airports, commercialbuildings, hotels, hospitals, residential colonies andpower distribution centres (substations) while SF6
j
Interrupter
Junction
Interconnectingcable
Transformer say,11 kV/6.6 kV
Interrupter
Interconnectingcable
M Motor 6.6 kV
Arc duringinterruptionor a restrike
Interruptingdevice
Contact gap having adielectric capacitance‘C ’ which is subject toa TRV of Vt during arestrike
I n�
I m ¢ Im
Interconnectingcable
Circuitinductance ‘L’
C
Vt
Figure 19.30(a) Figure 19.30(b) An energy-balancing phenomenon whileinterrupting a highly inductive circuit as shown in (a)
No-load magnetizing circuit of aninduction motor or a transformer
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/749Ta
ble
19.
1C
ompa
riso
n of
circ
uit
brea
kers
usi
ng d
iffer
ent
inte
rrup
ting
devi
ces
Mai
n fe
atur
es
1 1S
peci
fica
tion
s(i
)M
ediu
m o
fin
sula
tion
and
quen
chin
g of
arc
plas
ma
(ii)
Des
ign
volt
age
(Vm
)H
V LV
(iii
)N
omin
al c
urre
ntra
ting
s
(iv)
Clo
sing
tim
e(b
etw
een
the
inst
ant
of a
ppli
cati
on o
fvo
ltag
e to
the
clos
ing
coil
and
the
inst
ant
whe
n th
eco
ntac
ts t
ouch
)c
(v)
Ope
ning
tim
e(b
etw
een
the
inst
ant
of a
ppli
cati
on o
fvo
ltag
e to
the
tri
pco
il a
nd t
he i
nsta
ntof
sep
arat
ion
of t
hear
cing
con
tact
s)c
(vi)
Max
imum
dur
atio
nof
arc
pla
sma
(arc
ing
tim
e)c
(vii
)To
tal
brea
king
tim
e(b
etw
een
the
inst
ant
of a
ppli
cati
on o
fvo
ltag
e to
the
tri
pco
il a
nd i
nsta
nt o
ffi
nal a
rc e
xtin
ctio
n)c
2T
heor
y of
arc
pla
sma
(ion
izat
ion
of g
ases
at
high
tem
pera
ture
s)
BO
CB
2 Oil
3.6–
245
kV
690
V
Man
ufac
ture
d in
all
poss
ible
cur
rent
rat
ings
5 cy
cles
4–5
cycl
es
0.75
–1.2
5 cy
cles
4.75
–6.2
5 cy
cles
AC
Bb
AB
CB
a
45
Air
Air
bla
st
Up
to 2
4 kV
12–7
65 k
V(n
ot i
n pr
acti
ce i
n li
ght
of b
ette
r te
chno
logi
es i
nV
CB
s an
d S
F6)
690
VN
ot a
ppli
cabl
e
Up
to 6
300
AU
p to
400
0 A
and
hig
her
1–2
cycl
es2–
3 cy
cles
1 2–1
cyc
le1–
2 cy
cles
1 2–1
cyc
le1 2–1
cyc
le
1–2
cycl
es1
1 2–3
cyc
les
Em
its
ions
of
N2
(80%
) an
d O
2 (2
0%)
and
met
alli
cva
pour
s
MO
CB
a
3 Oil
3.6–
420
kV a
nd a
bove
Not
eco
nom
ical
Onl
y on
e br
eak
per
pole
,th
eref
ore
curr
ent
rati
ngs
in h
ighe
r ra
nges
are
rest
rict
ed4–
6 cy
cles
2–3
cycl
es
2 cy
cles
4–5
cycl
es
SF6a
VC
Ba
67
Sul
phur
hex
aflu
orid
eV
acuu
m
7.2–
765
kV a
nd a
bove
3.6
kV t
o 36
kV
Not
app
lica
ble
Not
app
lica
ble
Up
to 4
000
A a
nd h
ighe
rA
s re
quir
ed
4–5
cycl
es2–
3 cy
cles
12–
cyc
les
1 21–
2 cy
cles
11–
cyc
le1 2
1 2–1
cyc
le
2–4
cycl
es1
–3 c
ycle
s1 2
Em
its
ions
of
S+ (
prot
ons)
,Em
its m
etal
lic v
apou
r fro
mS
N (
neut
rons
), a
ccom
-th
e co
ntac
t mat
eria
l. Si
nce
pani
ed b
y el
ectr
ons
Se
the
cont
acts
are
ess
entia
llyan
d F
– and
met
alli
cm
ade
of c
oppe
r al
loy,
vapo
urs
copp
er h
avin
g th
e lo
wes
t
Em
its
ions
of
H2
arou
nd 7
0% a
nd r
emai
ning
as a
cety
lene
and
met
alli
c va
pour
s
(Con
td)
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/750 Electrical Power Engineering Reference & Applications Handbook
12
34
56
7
3T
heor
y of
arc
quen
chin
g an
dex
tinc
tion
, th
roug
hde
ioni
zati
on o
f ar
cpl
asm
a
4N
umbe
r of
no-
load
oper
atio
ns (
depe
nds
upon
the
arc
ene
rgy:
the
low
er th
e ar
cen
ergy
, the
hig
her
will
be th
e nu
mbe
r of
ope
-ra
tions
and
vic
e ve
rsa)
.
5M
aint
enan
ce
6D
iele
ctri
c st
reng
thco
mpa
red
to a
ir
7A
rc e
nerg
y co
mpa
red
to o
il
8W
heth
er s
uita
ble
toin
terr
upt
smal
lin
duct
ive
(mag
neti
zing
) or
capa
citi
ve c
urre
nts,
wit
hout
cau
sing
curr
ent
chop
ping
Coo
ling
of
arc
plas
ma
is b
ased
on
the
bubb
le t
heor
y,H
2 co
olin
g it
by
the
turb
ulen
ce c
ause
d by
H2
bubb
le
Min
. 10
00M
in.
1000
Dei
oniz
atio
n of
N2
(O2
havi
ng a
sm
all c
onte
nt, h
asno
sig
nifi
cant
inf
luen
ce)
by l
engt
heni
ng o
f th
e ar
cpl
asm
a th
roug
h th
e ar
cch
utes
, as
a re
sult
of m
ag-
neti
c fi
eld
indu
ced
in t
hem
etal
lic s
plitt
ers
of th
e ar
cch
ute
by th
e in
duct
ive
arc
plas
ma
Min
. 10
00
boil
ing
poin
t, th
e va
pour
is l
arge
ly c
ompo
sed
ofco
pper
ion
s
Dei
oniz
atio
n o
f N
2 an
dO
2 by
a s
tron
g bl
ast
ofai
r. T
he d
eion
izat
ion
forc
e re
mai
ns t
he s
ame
for
one
size
of
brea
ker,
irre
spec
tive
of
the
curr
ent
Min
. 10
00
Dei
oniz
atio
n of
fre
esu
lphu
r el
ectr
ons
Se ,ta
kes
plac
e th
roug
h th
eir
abso
rpti
on b
y th
efl
uori
ne i
ons
F–
(ele
ctro
nega
tive
the
ory)
Min
. 50
00
Req
uire
s ve
ry l
ittl
em
aint
enan
ce,
exce
ptpe
riod
ic c
heck
s of
pres
sure
and
con
diti
onof
the
con
tact
s
2–3
Rou
ghly
1 3 (
Figu
re 1
9.6)
Dei
oniz
atio
n of
cop
per
ions
is
natu
ral
and
extr
e-m
ely
fast
Min
. 10
000
–20
000
Req
uire
s ve
ry l
ittl
em
aint
enan
ce,
exce
ptpe
riod
ic c
heck
s of
vacu
um a
nd c
ondi
tion
of
the
cont
acts
. M
axim
umco
ntac
t er
osio
n 2–
3 m
m
Nea
rly
10 t
imes
(5
tim
esof
oil
)
Rou
ghly
1 10
(Fi
gure
19.
6)
Hig
h, t
o ch
eck
the
con-
diti
on o
f oi
l, co
ntac
ts a
ndar
c qu
ench
ing
fins
and
devi
ces
> 2
1 Yes
(bu
t fo
r a
lim
ited
num
ber
of s
wit
chin
gop
erat
ions
), b
ecau
se o
fdo
uble
bre
ak p
erph
ase
that
enab
les
quic
kre
stor
atio
n of
the
diel
ectr
ic s
tren
gth
Che
ckin
g th
e co
ndit
ion
ofoi
l is
mor
e fr
eque
nt,
invi
ew o
f sm
alle
r qu
anti
tyof
oil
> 2
1 No,
bec
ause
of
gene
rall
yon
e br
eak
per
pole
, fo
rbr
eake
rs 1
2 kV
and
abov
e, u
nles
s th
ebr
eake
r is
spe
cial
lyde
sign
ed w
ith
extr
aqu
ench
ing
syst
emth
roug
h a
jet
of o
il
Ve r
y lo
w m
a int
e na n
c e e
xce p
t fo
r c h
e cki
ng t
heco
ndit
ion
of t
he a
rcin
g co
ntac
ts f
or a
ny w
ear,
tear
or
pitt
ing
1C
ompr
esse
d ai
r has
bet
ter
than
1
––
(Con
tac t
ero
sion
low
and
sui
tabl
e fo
r fr
e que
ntop
erat
ions
)
On
an L
V s
yste
m, s
uch
aph
enom
enon
has
no
rele
vanc
e, b
ecau
se o
fhi
gh d
iele
ctri
c st
reng
thbe
twee
n th
e pa
rtin
gco
ntac
ts c
ompa
red
to t
hesy
stem
vol
tage
No,
bec
ause
of
forc
e of
air
blas
t ev
en a
t sm
all
curr
ents
whi
ch m
ayde
velo
p th
e te
nden
cy t
ocu
rren
t ch
oppi
ng.
On
the
othe
r ha
nd,
it i
s po
ssib
leth
at t
he b
reak
er m
ay f
ail
to i
nter
rupt
the
ste
epfr
onte
d T
RV
s
Yes
, in
all
typ
es o
f ar
c-qu
ench
ing
tech
niqu
es:
(i)
Puf
fer t
ype:
bec
ause
the
flow
of
gas
thro
ugh
the
arc
is a
func
tion
of
mag
ni-
tude
of
curr
ent
(ii)
Rot
atin
g ar
c ty
pe:
beca
use
the
mag
neti
c fi
eld
that
Gen
eral
ly n
ot,
beca
use
of e
xtre
mel
y fa
stde
ioni
zati
on.
It h
as t
hete
nden
cy t
o cu
rren
tch
oppi
ng.
How
ever
, in
view
of
cont
inuo
usde
velo
pmen
t in
thi
sfi
eld,
it
has
now
bee
npo
ssib
le t
o ac
hiev
e a
chop
ping
cur
rent
as
low
(Con
td.)
Tab
le 1
9.1
(Con
td.)
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/751
12
34
56
7
9A
ppli
cati
ons:
Sw
itch
ing
of∑
Indu
ctio
n m
otor
s∑
Gen
erat
ors
∑ T
rans
form
ers
∑ R
eact
ors
∑ In
duct
ive
circ
uits
∑ C
apac
itor
ban
ks∑
Dis
trib
utio
n li
nes
∑ H
ighe
r-sp
eed
auto
-re
clos
ing
(a)
Sui
tabl
e fo
r al
lap
plic
atio
ns,
not
requ
irin
g fr
eque
ntsw
itch
ing
oper
atio
ns.
(b)
Unt
il a
few
yea
rsag
o th
ey w
ere
bein
gex
tens
ivel
y us
ed f
or a
llLV
app
lica
tion
s
Ext
ensi
vely
use
d fo
r al
lLV
app
lica
tion
s an
dsu
itab
le f
or f
requ
ent
oper
atio
ns
driv
es t
he a
rc i
spr
oduc
ed b
y th
ein
terr
upti
ng c
urre
ntit
self
, an
d w
ill
vary
wit
h th
e cu
rren
t,an
d so
wil
l va
ryth
e co
olin
g ga
s in
dire
ct p
ropo
rtio
n.T
he s
mal
ler
the
curr
ent
to b
ein
terr
upte
d, t
hesm
alle
r w
ill
be t
hem
agne
tic
fiel
d an
dth
e co
olin
g fo
rce,
enab
ling
the
arc
to
inte
rrup
t at
ana
tura
l cu
rren
t ze
roon
ly.
But
thi
ste
chni
que
is n
owse
ldom
pra
ctis
ed(i
ii)
The
rma l
bla
st,
a rc
assi
sted
and
dou
ble
volu
me
type
:A
s (i
) ab
ove
Sui
tabl
e fo
r al
lap
plic
atio
ns. S
witc
hing
of
capa
cito
r ban
ks, h
owev
er,
may
pos
e pr
oble
mbe
caus
e of
hig
h T
RV
s.T
hese
may
cau
se a
rest
rike
of th
e ar
c pl
asm
a an
d gi
veri
se t
o sw
itch
ing
surg
es.
How
ever
, w
ith
the
use
of p
re-i
nser
tion
resi
stan
ce a
cros
s th
epa
rtin
g co
ntac
ts (
fixe
dan
d m
ovin
g)(F
igur
e19
.22)
the
se b
reak
ers
can
be m
ade
rest
rike
free
eve
n w
hen
swit
chin
g la
rge
capa
cito
rba
nks.
as 0
.5 t
o 1.
2A a
nd e
ven
less
. S
ecti
on 1
9.5.
6.T
here
fore
, ex
cept
inte
rrup
ting
cur
rent
slo
wer
tha
n th
is,
thes
ein
terr
upte
rs a
re s
uita
ble
to i
nter
rupt
suc
h cu
rren
tsw
itho
ut c
urre
nt c
hopp
ing
Sui
tabl
e fo
r al
l ty
pes
ofin
dust
rial
nee
ds a
ndfr
eque
nt o
pera
tion
s.T
heir
abi
lity
for
qui
ckin
terr
upti
on a
nd f
ast
buil
ding
up
of d
iele
ctri
cst
reng
th m
ake
them
suit
able
for
one
rous
duti
es a
nd h
igh
TR
Vs
(a)
Sui
tabl
e fo
r al
lap
plic
atio
ns n
otre
quir
ing
freq
uent
swit
chin
g op
erat
ions
Gen
eral
ly s
uita
ble
for
HV
dis
trib
utio
n on
ly,
and
at i
nsta
llat
ions
empl
oyin
g a
num
ber
ofsu
ch d
evic
es t
o m
ake
dry
com
pres
sed
air
syst
em h
andy
and
econ
omic
al
(Con
td.)
Tab
le 1
9.1
(Con
td.)
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/752 Electrical Power Engineering Reference & Applications Handbook
12
34
56
7
10W
heth
er a
sur
gear
rest
er i
s es
sent
ial
11E
ffec
t of
lea
kage
on
perf
orm
ance
:(i
)O
pera
ting
saf
ety
(ii)
Die
lect
ric
stre
ngth
(iii
)In
terr
uptin
g ca
paci
ty
No
Gen
eral
ly n
ot
(i)
Gen
eral
ly,
the
use
ofS
F6
is s
afe,
inh
alin
g is
pois
onou
s. I
f th
ere
is a
leak
age
it w
ould
be
dang
erou
s. S
F6
itse
lf i
sno
n-to
xic,
but
dec
om-
pose
d S
F6
is m
oder
atel
yto
xic
and
mus
t be
hand
led
unde
r co
ntro
lled
cond
itio
ns. T
rain
ing
and
guid
elin
es a
re e
ssen
tial
for
pers
onne
l w
orki
ngon
suc
h eq
uipm
ent.
Sit
eda
ta c
olle
cted
fro
mva
riou
s so
urce
s,ho
wev
er,
sugg
est
ale
akag
e ra
te o
f le
ss t
han
0.1%
per
ann
um
Sti
ll h
igh
In t
he e
vent
of
ale
akag
e, t
he b
reak
er w
ill
stil
l be
in
a po
siti
on t
oin
terr
upt
the
norm
alcu
rren
ts
Bet
ter
to p
rovi
de(d
epen
ding
upo
n th
ety
pe o
f eq
uipm
ent
it i
ssw
itch
ing,
the
min
imum
curr
ent
it h
as t
o in
terr
upt
and
the
like
ly a
mpl
itud
eof
TR
V)
Not
app
lica
ble
Not
app
lica
ble
Not
app
lica
ble.
But
if
the
leak
age
is in
the
com
pres
-se
d ai
r su
pply
sys
tem
, the
brea
ker
may
not
inte
rrup
ton
fau
lt,
depe
ndin
g up
onth
e ai
r pre
ssur
e th
e sy
stem
is a
ble
to m
aint
ain
on a
leak
age
No
Not
app
lica
ble
Yes
, pa
rtic
ular
ly f
or d
ryin
sula
ted
equi
pmen
t (su
chas
an
indu
ctio
n m
otor
, a
dry
type
rea
ctor
or
a dr
yty
pe t
rans
form
er),
whi
chha
ve lo
w in
sula
tion
leve
ls.
An
oil-
imm
erse
d eq
uip-
men
t (s
uch
as a
pow
ertr
ansf
orm
er),
hav
ing
are
lati
vely
muc
h be
tter
diel
ectr
ic s
tren
gth,
may
be
swit
ched
wit
hout
an
arre
ster
Gen
eral
ly a
saf
eeq
uipm
ent.
But
in
the
even
t of
vac
uum
lea
kage
whi
ch,
alth
ough
rem
ote,
may
cau
se a
fir
e ha
zard
and
X-r
ays.
X-r
ayw
arni
ng a
nd p
rope
rsh
ield
ing
may
be
esse
ntia
l
Zer
o
In t
he e
vent
of
ale
akag
e, t
he b
reak
er w
ill
not
be i
n a
posi
tion
to
inte
rrup
t ev
en n
orm
alcu
rren
ts
No
Sin
ce th
e oi
l is
fill
ed a
t atm
osph
eric
pre
ssur
e, th
ere
isge
nera
lly
no l
eaka
ge
Not
app
lica
ble
Not
app
lica
ble
Not
app
lica
ble
Not
app
lica
ble
Not
app
lica
ble
Not
app
lica
ble
(Con
td.)
Tab
le 1
9.1
(Con
td.)
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/753
Thi
s ha
s th
e la
test
tech
nolo
gy in
the
arc
inte
rrup
tion
and
sui
tabl
efo
r al
l app
lica
tion
s as
note
d ab
ove,
in v
iew
of
havi
ng a
chie
ved
a ve
rylo
w c
hopp
ing
curr
ent,
ofth
e or
der
of ju
st 0
.5–
1.2A
and
eve
n le
ss. I
nvi
ew o
f li
mit
ed v
olta
gera
nge,
how
ever
, it
isfa
cing
lim
itat
ions
in it
sex
tens
ive
appl
icat
ion.
The
dev
elop
men
t wor
kon
hig
her
rang
es is
sti
llun
der
way
and
not
man
ybr
eake
rs a
bove
36
kVha
ve b
een
prod
uced
so
far.
Tend
ency
to a
col
dw
eld,
dur
ing
clos
ing
and
chan
ge in
the
arc
cham
ber
pres
sure
, dur
ing
an in
terr
upti
on m
ayda
mag
e th
e m
etal
lic
bell
ows
(Fig
ure
19.2
4).
The
se a
re s
ome
impe
dim
ents
in th
eir
exte
nsiv
e us
e
Thu
nder
ous
nois
e du
ring
an in
terr
uptio
n, b
ecau
se o
fai
r bla
st. T
he in
tens
ity
can
be c
ontr
olle
d by
pro
vidi
ngsi
lenc
ers
In l
ower
ran
ges,
say
, up
to 7
2.5
kV,
this
bre
aker
is n
ow f
ast
losi
ng i
tsho
ld i
n fa
vour
of
SF
6,du
e to
cos
tco
nsid
erat
ions
and
the
cum
bers
ome
dry
air
pres
sure
sys
tem
. In
high
er r
ange
s, s
ay,
123–
765
kV,
how
ever
, th
eyar
e st
ill
bein
g us
ed b
uton
ly r
arel
y
Gen
eral
ly,
oil
is f
ire
haza
rdou
s, b
ut n
ot p
rone
to
itun
less
the
die
lect
ric
stre
ngth
rea
ches
a v
ery
low
leve
l an
d th
e m
ediu
m i
tsel
f be
com
es c
ondu
ctin
g.N
ever
thel
ess,
the
y ar
e no
t su
itab
le a
t lo
cati
ons
whi
ch a
re f
ire
haza
rdou
s. N
orm
al m
ake
or b
reak
,ev
en o
n fa
ult,
may
onl
y de
teri
orat
e th
e qu
alit
y of
oil,
but
yet
not
mak
e it
fir
e ha
zard
ous,
unl
ess
asno
ted
abov
e
Qui
et o
pera
tion
Qui
et o
pera
tion
The
se b
reak
ers
wer
e ex
tens
ivel
y us
ed u
ntil
abo
ut19
70s
but
are
now
fas
t lo
sing
the
ir h
old
in f
avou
rof
SF
6 an
d V
CB
s fo
r H
V a
nd A
CB
s fo
r LV
sys
tem
s
12
34
56
7
a The
se c
ompa
riso
ns r
elat
e on
ly t
o H
V i
nter
rupt
ers.
b For
LV s
yste
ms
only
.c R
efer
red
to a
t po
wer
fre
quen
cy (
50 o
r 60
Hz)
and
rat
ed c
urre
nt. T
hese
fig
ures
are
app
roxi
mat
e an
d fo
r a
gene
ral
refe
renc
e on
ly. T
hey
may
var
y w
ith
rati
ng, l
oadi
ng a
nd m
anuf
actu
rer.
For
low
er v
olta
ge r
atin
gs,
they
may
be
slig
htly
hig
her.
Arc
for
mat
ion
and
exti
ncti
on t
akes
pla
ce i
nsid
e a
seal
ed c
ham
ber,
thu
s em
itti
ng n
o ga
ses
or v
apou
rsto
the
atm
osph
ere,
whi
ch m
ay b
e a
caus
e of
fir
eha
zard
. The
y ar
e th
e m
ost
appr
opri
ate
choi
ce f
orsu
ch a
reas
The
y m
ay b
e ra
ted
as m
ore
fire
haz
ardo
us t
han
aB
OC
B o
r M
OC
B i
n vi
ew o
f ar
c fo
rmat
ion
taki
ngpl
ace
in th
e op
en, a
lthou
gh u
nder
con
trol
led
cond
ition
s.T
hey
are
not
suit
able
for
ins
tall
atio
ns p
rone
to
fire
haza
rds,
unl
ess
the
sub-
stat
ion
or t
he c
ontr
ol r
oom
whe
re t
hey
are
inst
alle
d is
iso
late
d fr
om t
he a
rea
ofha
zard
s (S
ecti
on 7
.11)
. The
y ar
e ge
nera
lly
suit
able
for
all
othe
r ar
eas
12F
ire
haza
rds
13N
oise
lev
el
14T
rend
s
Exc
ept
duri
ng a
nin
terr
upti
on,
it h
as q
uiet
oper
atio
n
Onl
y br
eake
r fo
r al
l LV
appl
icat
ions
Qui
et o
pera
tion
Qui
et o
pera
tion
Thi
s ha
s be
com
e th
em
ost
pref
erre
d br
eake
rw
ith
the
wid
est
volt
age
rang
e an
d su
itab
ilit
y fo
ral
l ap
plic
atio
ns
Tab
le 1
9.1
(Con
td.)
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/754 Electrical Power Engineering Reference & Applications Handbook
Figure 19.33 220 kV GIS at the Sendai thermal power station switchyard of Kyushu Electric Power Co., Inc, Japan (1973)(Source: Hitachi)
Figure 19.31 Non-withdrawable vacuum circuit breaker (VCB)switchgear with single busbars (Source: Siemens)
Figure 19.32 Rear view of Figure 19.31
AluminiumBusbars
SF6
Isometric view
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/755
As intelligent switchgears
It is easy to make them intelligent with the use ofmicroprocessor based relays, electronic releases andmetering. See Section 13.8.1 for details.
Constructional features
– Gas tight aluminium castings, aluminium welded orstainless steel housings are used to encapsulate VCBor SF6 interrupters.
– Disconnectors and grounding switches are alsomounted inside the enclosures.
– Busbar, interrupter and switching chambers areseparated by gas tight barriers.
– There being no contact between the arc chamber of aVCB or SF6 breaker and the bus chamber. The insulatinggas of the bus chamber is not exposed to arcing chamberand causes no deterioration of the insulating SF6 gasand permits long years of maintenance-free operation.
– Operating mechanism of breakers, disconnectors andswitches and all auxiliary components like CTs orRogowski coil transducers (Section 15.11), VTs, CVTsare mounted outside the hermetically encapsulatedhousings to maintain them at ground potential andfacilitate easy maintenance without disturbing the maincomponents.
– The VCB is usually mounted in a vertical formation inthe bottom housing, each pole housed in a separateenclosure one behind the other as shown in Figure 19.31.The upper housing encapsulates the disconnector switchthat connects the busbars. SF6 breakers can be mounted
Figure 19.35 Sectional view of a 145 kV GIS bay with non-isolated double busbar system (Source: Toshiba)
breaker based GIS are used at power stations andswitchyards. They are an ideal choice for hilly areaslike for mini and large hydel power projects.
– With the global warming and consequent rising ofsea level, shrinking of available land area and risingpopulation, every effort is being made worldwide tosave on land wherever possible for the good of themankind. Use of GIS will contribute to these efforts.
– The overall compact structure of GIS also saves onI2R loss and contributes significantly towards energysaving which too is a buzzword in today’s scenario asdiscussed already.
Figure 19.34 Cross-sectional view of a GIS substation with non-isolated double busbar configuration (up to 500 kV)(Source: Hitachi)
Circuit breaker
Local control cubicle
Maintenancegroundingswitch
Grounding switchwith makingcapacity
Voltagetransformer
Removable link
Cable headMaintenancegroundingswitch
Cable isolator
Currenttransformer
Current transformerSpacer
Operatingmechanismfor circuitbreaker
Busbarisolator
B busbars
Busbarisolator
A busbars
Circuit diagram
1
1
3
7
9
22
10
11
4
5
6
8
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/756 Electrical Power Engineering Reference & Applications Handbook
horizontally or vertically. Horizontal layouts at highervoltages facilitate easy erection and maintenance.
– Indication, measurement, protection, control and alarmdevices can be mounted separately on a central controlpanel.
– Busbars: They can be either single or double busbarsystems depending upon the number of supplysources.
• Each busbar system can be a conventional threephase system to economize on space and cost. Suchbusbars are used in trefoil formation to nullify theproximity effect and space field (Section 28.8) asalso enclosure currents (Section 31.4).
• They can also be single phase isolated phase bussystem to make the switchgear suitable for higherfault levels by limiting the internal faults to single
Dimensions Isolated bus (VCBs) Non isolated bus (SF6 breakers)
System Voltage kV Æ 7.2/36 72.5–145 170–245 245–300 360–420 525 765–800 1100Width-(W) m 0.6 1.0 2.8 3.1 3.6 5.5 6.5 7.5Height-(H) m 2.46 4.0 4.2 4.8 6.0 6.5 6.5 6.0Depth-(D) m 2.66 4.7* 5.7* 6.5* 8.0* 12* 20* 30*% floor space (W ¥ D) 30 14 8 6 5 4 – –required by GIScompared to AIS % Saving 70 86 92 94 95 96 – –
Notes1. These dimensions may vary by 10% or so.2. *For isolated bus system the depth will be slightly more.
Table 19.2 Typical floor dimensions for GIS (with double bus)
I(R)
I(Y)
I(B)
One set of busbars Second set of busbars
II(R) Phase
II(Y) Phase
II(B) Phase
3
7
4 3
6
26
5
8
4
3
1
Figure 19.36 Typical sectional view of an isolated double busbar GIS substation bay up to 420 kV (Source: GEC-Alsthom)
1. Circuit-breaker without closing resistor 5. Make-proof grounding switch2. Hydraulic mechanism 6. Current transformer3. Disconnector 7. Voltage transformer4. Maintenance grounding switch 8. HV cable connection
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
Circuit interrupters and their applications 19/757
phase faults and preventing a ground fault to developinto a phase fault.
– Each busbar system can be connected directly to atransformer.
– Gas filled in the entire enclosure forms a closed cyclesystem for easy monitoring and minimizing leakages.
– For making manufacturing simpler, cost effective andalso for ease of monitoring the gas pressure of theentire switchgear equipment is divided into separatehousings, each fitted with gas pressure monitors, fillingvalves and alarm switches. Usually an alarm is soundedwhen the pressure drops by 5% or so of the set pressure.The usual inside pressure is maintained at about 3–5kg/cm2 depending upon the system voltage.
Cable termination – Through plug-in type cabletermination or by conventional cable sealing ends.
Dimensions
Typical floor dimensions of GIS and comparativedimensions of conventional air insulated switchgears (AIS)for different interrupting devices, voltage systems andbusbar configurations are shown in Table 19.2 just forreference. For exact details the user must contact themanufacturer.
One can visualize the compact sizes of GIS andconsequently their small floor area requirement comparedto AIS. Higher the system voltage higher will be thespace saving.
Local control station
A local control panel can be provided for a complete bayof GIS and may comprise the following:
– Controls for operating ON/OFF all the switchingdevices (breakers, disconnectors and groundingswitches)
– Display of switch position– LV supply protection– Alarm display– Safety interlocks– Measuring instruments– Interface terminals for remote control– Protective relays (or the bay control unit of a substation
digital control system) as per the system requirement.– Any other requirement
Termination
The GIS can be terminated directly to cables, overheadlines, transformers or reactors through gas insulatedbusducts (GIBs). The necessary jointing kits are suppliedby the manufacturer to terminate at a bushing or aninsulator. See Section 28.2.6 for inter-connecting HVand EHV equipment.
GIS condition monitoring
Condition monitoring is sort of a preventive maintenanceand is a good service practice to enhance the reliability
of GIS that otherwise are capable to perform themselvesunattended for long years. The following monitoringdisciplines can be practised.
– SF6 breaker health monitoring: to monitor thecondition of the breaker and undertake servicing whenit is actually necessary by recording and transmittingits operating conditions such as travel curves, electricalwear and tear and other vital-parameters to a centralmonitoring station.
– Ultra high frequency (UHF) monitoring – to detectinternal partial discharges. It can be accomplishedthrough monitoring the UHF electromagnetic (EM)waves generated by partial discharges.
– SF6 gas monitoring
• Density of gas – to decide on refilling• Pressure alarm• Gas liquefaction detection• Sensor status control• Internal failure detection• Maintaining historical records• Any other vital parameter
19.11 Retrofitting old installationswith vacuum and SF6 breakers
Referring to switchgears, retrofitting aims at upgradingthe existing installations using OCBs, MOCBs or ABCBswith state-of-the-art interrupting technologies throughVCBs and SF6 breakers.
OCBs, MOCBs and ABCBs as discussed already arenow outdated at least for the new installations. But theydo exist at many old installations. In view of ever risingfault level of a system and to achieve low maintenancelevel, it is advisable to gradually changeover the oldinstallations with VCBs or SF6 breakers as per the systemvoltage and fault level. Upgradation is surely imperativefor installations undergoing renovation or expansion andall important installations like power stations, switchyardsand transformer substations, steel, automobile, chemical,petrochemical, cement and fertilizer plants. All largeindustries and other installations like airports, residentialcolonies and commercial buildings or hazardous locations.Not only to meet the fault level of the extended system,it may also be cumbersome to operate and maintainbreakers of two generations at the same installation withas many spares and maintenance experts.
Most manufacturers of switchgears and contractingcompanies are extending this service to their clients tofacilitate quick, smooth and cost-effective changeoversat most installations even without or only short shutdowns.Most switchgear structures, foundation and cabling mayremain much the same with minor modifications, savingabout half the cost of replacement by new switchgears.Replacement by new switchgear means shifting of cables,modification of foundation and other associated cost.
The normal practice is to offer new breakers in modularform (on trolley) making them matching with the oldinstallations. It is just removing the old breaker and rackingin the new one.
Auth
or: K.
C. A
graw
al
ISBN
: 81
-901
642-
5-2
19/758 Electrical Power Engineering Reference & Applications Handbook
Further Reading
1 Bettge, H., ‘Design and construction of vacuum interrupters’,Siemens Circuit, XVIII, No. 4 (1983).
2 Blower, R.W., Distribution Switchgear, Collins Professionaland Technical Books, 1986.
3 Blower, R.W., Cornick, K.J. and Reece, M.P. ‘Use of vacuumswitchgear for the control of motors and transformers in industrialsystems’, Electric Power Applications, 2, No. 3, June (1979).
4 Bouilliez, O., ‘Mastering switching voltage transients with SF6
switchgear’, Cahiers techniques Merlin Gerin, No. 125.5 ‘Current chopping phenomena of MV circuit breakers’, IEEE
Transactions, PAS –96, No. 1 (1977).6 Pelenc, Y. ‘Review of the main current interruption techniques’
Voltas Limited, Switchgear Division, India.
7 Ramaswamy, R., ‘Vacuum circuit breakers’, Siemens Circuit,XXIII, April (1988).
8 Telander, S.H., Wilhelm M.R. and Stump, K.B., ‘Surge limitersfor vacuum circuit breaker switchgear’, CH 2279–8/86/0000–003751.00, IEEE (1986).
9 XXth International Symposium on Discharges and ElectricalInsulation in Vacuum.
(i) X'ian Jiaotong University, X'ian, China, September 18–22,2000.
(ii) EIT- Ecole d’ Ing’enieurs de Tours, Tours, France, June 30–July 5, 2002.
10 Wong, S.M., Snider, L.A. and Lo, E.W.C., Over-voltages andReignition Behaviour of Vacuum Circuit Breaker, InternationalConference on Power System Transients – IPST-2003, NewOrleans, USA.
ANSI/IEEE-C37.010/1999ANSI/IEEE-C37.04/1999ANSI-C37.06/2000
ANSI-C37.16/2000NEMA/SG-3/1995NEMA/SG-4/2000NEMA/SG-6/2000
Application guide for a.c. HV circuit breakers.Rating structure for a.c. HV circuit breakers.A.C. HV circuit breakers rated on a symmetrical current basis – preferred ratings and related requiredcapabilities.Low voltage power circuit breakers – preferred ratings and application recommendations.Low voltage power circuit breakers.A.C. HV circuit breakers.Power switching equipment.
Related US Standards ANSI/NEMA and IEEE
Notes1 In the table of relevant Standards while the latest editions of the Standards are provided, it is possible that revised editions have become
available or some of them are even withdrawn. With the advances in technology and/or its application, the upgrading of Standards is acontinuous process by different Standards organizations. It is therefore advisable that for more authentic references, one may consult therelevant organizations for the latest version of a Standard.
2 Some of the BS or IS Standards mentioned against IEC may not be identical.3 The year noted against each Standard may also refer to the year it was last reaffirmed and not necessarily the year of publication.
IEC
60694/2001
60947-2/2003
62271-100/2003
62271-200/2003
62271-203/2003
–
Title
Common specifications for high voltage switchgear andcontrolgear standards.
Low voltage switchgear and controlgear, circuit breakers.
High voltage alternating current circuit breakers.
A.C. metal enclosed switchgear and controlgear for ratedvoltages above 1 kV and up to and including 52 kV.
Gas insulated metal-enclosed switchgear for rated voltagesof 72.5 kV and above.
Circuit breakers requirements and tests. Sec 1, voltages notexceeding 1000 V a.c. or 1200 d.c. (2 parts)
IS
12729/2000
13947-2/1998
13118/2002
12729/2000
–
13947-2/1998
BS
BS EN 60694/1997
BS EN 60947-2/2003
BS 5311/1996
BS EN 60298/1996
BS EN 60517/1997
–
–
–
–
–
–
–
Relevant Standards