Data Sheet It is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to. All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation. All connections should be inspected periodically to ensure correct tightness. DO NOT USE POWER TOOLS ON THESE PRODUCTS Europa Helpline: email: [email protected] / tel: 01582 692 444 Page 1 of 12 Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440 e-mail: [email protected] website: www.europacomponents.com EDS1331-001 Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three phase 415V A T S PME CON _ Maximum Cable size mm² 10 16 25 35 50 Operational Current AC1 A 40 60 80 100 125 Compliance / Approvals Low Voltage Control Gear & Switch Gear British / European / International Standard BS/EN/IEC 60947-6-1

Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data SheetIt is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to.

All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation.All connections should be inspected periodically to ensure correct tightness.

DO NOT USE POWER TOOLS ON THESE PRODUCTS

Europa Helpline: email: [email protected] / tel: 01582 692 444

Page 1 of 12

Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440

e-mail: [email protected] website: www.europacomponents.com

EDS1331-001

Automatic Transfer Switch (ATS)Amperage:40, 60, 80, 100, 125

Number of poles:2 = Single phase 230V4 = Three phase 415V

A T S P M EC O N_

Maximum Cable size mm² 10 16 25 35 50Operational Current AC1 A 40 60 80 100 125Compliance / Approvals Low Voltage Control Gear & Switch GearBritish / European / International Standard BS/EN/IEC 60947-6-1

Page 2: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data Sheet

Page 2 of 12EDS1331-001

Mains Failure Relay (MFR)Set the overvoltage and undervoltage thresholds, hysteresis and time delay in accordance with the phase failure relay datasheet.

Delay On Start Timer (DOST) Set the time for how long you want to delay the generator start signal following the loss or under/over voltage of the mains supply. Reference ECTDOFF datasheet. Please see footnote.

Mains Return Timer (MRT)Set the time for how long you want to delay the ATS from returning the load back to the mains supply following the mains supply being available. Reference ECMFT datasheet.

Cool Down Timer (CDT)Set the time for how long you want to delay the generator stop signal following the load beingtransfered back to the mains supply. Reference ECTDOFF datasheet.

Changeover Timer (DOCT)Set the time for how long you want to delay the ATS unit switching to the generator supply.Reference ECTON datasheet. Please see footnote.

Footnote:The Changeover timer (DOCT) setting will determine delay before the ATS unit switches the load from mains to generator. The delay on start timer (DOST) will determine the delay before the generator start signal is given after the mains fails. Therefore the changeover timer (DOCT) must be set to incorporporate the start-up time required for the generator to reach full speed and deliver the correct output voltage and frequency.

Time required for generator to reach required output = Changeover timer - Start timer 2 = 7 - 5

Wiring Diagram:

L L L NKM1 KM2

LOADMAINS SUPPLY

GENERATOR SUPPLY

L L L NTHREE PHASE

L L L N

Parameter Settings:

SINGLE PHASEL N L N L N

SINGLE PHASE

L L L NTHREE PHASE

Page 3: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data Sheet

Page 3 of 12EDS1331-001

Single Phase Circuit Diagram

Page 4: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data Sheet

Page 4 of 12EDS1331-001

Three Phase Circuit Diagram

Page 5: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data Sheet

Page 5 of 12EDS1331-001

Data SheetIt is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to.

All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation.All connections should be inspected periodically to ensure correct tightness.

DO NOT USE POWER TOOLS ON THESE PRODUCTS

Europa Helpline: 01582 692 444 / Email: [email protected]

Page 1 of 2

Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440

e-mail: [email protected] website: www.europacomponents.com

EDS1210-101

Data ECPF02Function Monitoring voltage

Supply terminals A1-A2

Rated supply voltage AC/DC110-240V

Rated supply frequency 45-65Hz

Hysteresis 5% - 20%

Supply indication Green LED

Time delay Adjustable 0.1-10s, 10%

Measurement error ≤ 1%

Run up delay at power up 0.5s time delay

Knob setting accuracy 1% of scale value

Reset time 1000msTemperature coecient 0.05%/°C, at-20°C(0.05%°F, at-68°F)

Output 1 x SPDT

Current rating 10A / AC1

Switching voltage 250VAC / 24VDC

Minimum breaking capacity 500mW

Output indication Red LED

Mechanical life 1 x 107

Electrical life (AC1) 1 x 106

Operating temperature -20°C to +55°C (-4°F to 131°F)

Storage temperature -35°C to +75°C (-22°F to 158°F)

Mounting / din rail Din rail EN/IEC 60715

Protection degree IP40 for front panel / IP20 terminals

Operating position Any

Overvoltage category III.

Pollution degree 2

Maximum cable size (mm2) Solid wire maximum 1x2.5 or 2x1.5 / With sleeve maximum 1x2.5 (AWG 12)

Dimensions 90 x 18 x 64mm

Weight 59g

Standards IEC/EN 60255-6, IEC/EN61010-1

Technical Data: ECPF02 Single Phase Failure Relay

Page 6: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data Sheet

Page 6 of 12EDS1331-001

Data Sheet

Page 2 of 2EDS1210-101

Panel DiagramPanel Diagram:

-1-

Instruction Manual

Panel Diagram

Supply indication(green)

Supply indication(green)

Output indication(red)

Output indication(red)

Operating function selector

Overvoltage threshold setting

Voltage threshold setting

Hysteresis setting

Undervoltage threshold setting

Time delay setting

Time delay setting

GEYA ELECTRICAL CO.,LTDAdd:Wenzhou Brige Industrial Zone,Beibaixiang Town,Yueqing,Zhejiang,China 325603

Tel:0086-577-62711079Fax:0086-577-62711751Mobile:0086-13567770207E-mail:[email protected]:www.geya.net

Monitoring voltage relay GRV8-01.02

■Applications -Protect electrical equipment and motors from over-voltage and under-voltage. -Normal/emergency power supply switching.■ Function Features -Controls its own supply voltage(True RMS measurement) -.User may select operation mode through knob. - Voltage measurement accuracy<1%. - Relay status is indicated by LED. - 1-MODULE,DIN rail mounting.

General

GRV8

GRV8 Series

■Model and connotation

Function

Supply terminals

DC12V,AC/DC24V-48V,AC/DC110V-240V,AC220V

A1-A2

Rated supply voltage

5%-20%

Supply indication

Time delay

green LED

Adjustable 0.1s-10s,10%

0.5s time delayRun up delay at power up

Reset time

Konb setting accuracy 1% of scale value

0.05%/℃,at=20℃(0.05%℉,at=68℉)

1×SPDT

10A/AC1

250VAC/24VDC

Temperature coecient

Output

500mW

red LED

1×10

1×10

Min.breaking capacity DC

Switching voltage

Current rating

Output indication

Mechanical life

Electrical life(AC1)

-20℃ to +55℃(-4℉ to 131℉)

-35℃ to +75℃(-22℉ to 158℉)

Din rail EN/IEC 60715

IP40 for front panel/IP20 terminals

any

solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)

90×18×64mm

64g

IEC/EN 60255-6,IEC/EN61010-1

Operating temperature

Storage temperature

Mounting/DIN rail

Protection degree

Operating position

Overvoltage cathegory

Pollution degree

Dimensions

Weight

Standards

Monitoring voltage

GRV8-01 GRV8-02

Rated supply frequency 45Hz-65Hz,0

Hysteresis 3%fixed

Measurement error ≤1%

1000ms

Technical parameters

GRV8-01

Un R

U> U<

20

30

4050

60

70

80V

AC/DC

U

5

810

12 1416

20%H6

18

0.1 10s

2

4 6

8

GRV8-02

Un R

20

30

4050

60

70

80V

AC/DC

0.1 10s

2

4 6

8

20

30

40 60

70

80V

AC/DC50

U>

T

U<

Tt

Dimensions:

Dimensions(mm) Wiring Diagram

-2-

Functions Diagram

http://www.geya.net

Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.

CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.

GRV8-01

GRV8-02

Wrong setting of GRV8-01 Wrong setting of GRV8-02

U> U< U<

20

U>

30

4050 60

70

80V 20

30

4050 60

70

80V

As shown in the figure above,they are wrong settings.In that cases , LED-Un and LED-R will flash at the same time, which indicate the setting error. Normal operation will be resumed through resetting after power-off. If the operating function is changed after power-on, the two LED indicatorswould flash while the relay operates based on original operating functions;the LED would resume the normal indication after the original setting is recovered.

The set overvoltage threshold value must be larger than undervoltage thresholdvalue. Otherwise, all LEDs would flash and the output relay would be disconnected.

Locking Modes

Dimensions(mm) Wiring Diagram

-2-

Functions Diagram

http://www.geya.net

Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.

CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.

GRV8-01

GRV8-02

Wrong setting of GRV8-01 Wrong setting of GRV8-02

U> U< U<

20

U>

30

4050 60

70

80V 20

30

4050 60

70

80V

As shown in the figure above,they are wrong settings.In that cases , LED-Un and LED-R will flash at the same time, which indicate the setting error. Normal operation will be resumed through resetting after power-off. If the operating function is changed after power-on, the two LED indicatorswould flash while the relay operates based on original operating functions;the LED would resume the normal indication after the original setting is recovered.

The set overvoltage threshold value must be larger than undervoltage thresholdvalue. Otherwise, all LEDs would flash and the output relay would be disconnected.

Wiring Diagram:Dimensions(mm) Wiring Diagram

-2-

Functions Diagram

http://www.geya.net

Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.

CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.

GRV8-01

GRV8-02

Wrong setting of GRV8-01 Wrong setting of GRV8-02

U> U< U<

20

U>

30

4050 60

70

80V 20

30

4050 60

70

80V

As shown in the figure above,they are wrong settings.In that cases , LED-Un and LED-R will flash at the same time, which indicate the setting error. Normal operation will be resumed through resetting after power-off. If the operating function is changed after power-on, the two LED indicatorswould flash while the relay operates based on original operating functions;the LED would resume the normal indication after the original setting is recovered.

The set overvoltage threshold value must be larger than undervoltage thresholdvalue. Otherwise, all LEDs would flash and the output relay would be disconnected.

Functions Diagram:

Dimensions(mm) Wiring Diagram

-2-

Functions Diagram

http://www.geya.net

Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.

CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.

GRV8-01

GRV8-02

Wrong setting of GRV8-01 Wrong setting of GRV8-02

U> U< U<

20

U>

30

4050 60

70

80V 20

30

4050 60

70

80V

As shown in the figure above,they are wrong settings.In that cases , LED-Un and LED-R will flash at the same time, which indicate the setting error. Normal operation will be resumed through resetting after power-off. If the operating function is changed after power-on, the two LED indicatorswould flash while the relay operates based on original operating functions;the LED would resume the normal indication after the original setting is recovered.

The set overvoltage threshold value must be larger than undervoltage thresholdvalue. Otherwise, all LEDs would flash and the output relay would be disconnected.

Page 7: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data Sheet

Page 7 of 12EDS1331-001

Data SheetIt is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to.

All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation.All connections should be inspected periodically to ensure correct tightness.

DO NOT USE POWER TOOLS ON THESE PRODUCTS

Europa Helpline: 01582 692 444 / Email: [email protected]

Page 1 of 2

Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440

e-mail: [email protected] website: www.europacomponents.com

EDS1238-001

ECTDOFF - Single Function True Delay OFF TimerTechnical Parameters ECTDOFF

Supply terminals A1-A2Voltage range AC/DC 12-240V(50-60Hz)Burden AC 0.7-3VA/DC 0.5-1.7WSupply voltage tolerance -15%;+10%Supply indication green LEDTime ranges 0.1s-10minTime setting potentionmeterTime deviation 5%-mechanical settingRepeat accuracy 0.2%-set value stabilityMininum power time 200msTemperature coecient 0.05%/°C, at=20°C (0.05%/°C at=68°C)Output 1×SPDTCurrent rating 16A / AC1Switching voltage 250VAC / 24VDCMin.breaking capacity DC 500mWOutput indication red LEDMechanical life 1×10Electrical life(AC1) 1×10Reset time max.200msOperating temperature -20°C to +55°C -4°C to 131°CStorage temperature -35°C to +75°C -22°C to 158°CMounting/DIN rail Din rail EN/IEC 60715Protection degree IP40 for front panel/IP20 terminalsOperating position anyOvervoltage category solid wire max.1×2.5 or 2×1.5/with sleeve max.1×2.5(AWG 12)Pollution degree 2Dimensions 90×18×64mmWeight 66gStandards IEC/EN 61812-1,IEC/EN61010-1

Panel Diagram

Supply indication(green)

Output indication(red)

Time setting

Wiring Diagram

Time range setting

General

■Applications

-Back-up source for Delay OFF in case of voltage failure (emergency lighting, emergency respirator,or protection of el. controlled doors - in case of fire).

■Function Features

-Time range (adjustable by rotary switch and fine setting by potentiometer): -0.1 s - 10 min.-Voltage range: AC/DC12-240V , clamp terminals.-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.

Technical parameters

Function

Supply terminals

AC/DC 12-240V(50-60Hz)

A1-A2

Voltage range

Burden AC 0.7-3VA/DC 0.5-1.7W

-15%;+10%Supply voltage tolerance

Supply indication

Time ranges

green LED

0.1s-10min

potentionmeterTime setting

Time deviation

Repeat accuracy

5%-mechanical setting

0.2%-set value stability

0.05%/℃,at=20℃(0.05%℉,at=68℉)

1×SPDT

16A/AC1

250VAC/24VDC

Temperature coecient

Output

500mW

red LED

1×10

1×10

max.200ms

Min.breaking capacity DC

Switching voltage

Current rating

Output indication

Mechanical life

Electrical life(AC1)

Reset time

-20℃ to +55℃(-4℉ to 131℉)

-35℃ to +75℃(-22℉ to 158℉)

Din rail EN/IEC 60715

IP40 for front panel/IP20 terminals

any

solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)

90×18×64mm

66g

IEC/EN 61812-1,IEC/EN61010-1

Operating temperature

Storage temperature

Mounting/DIN rail

Protection degree

Operating position

Overvoltage cathegory

Pollution degree

Dimensions

Weight

Standards

ECTDOFF

Mininum power time 200ms

Un R

10

20

3040 50 60 70

80

90

10m

1m10s

1s

ECTDOFF | single function true delay OFF time relay

Page 8: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data Sheet

Page 8 of 12EDS1331-001

Data Sheet

Page 2 of 2

Dimensions

Wiring Diagram

EDS1238-001

Functions Diagram

Dimensions(mm)

Un R

10

20

3040 50 60 70

80

90

10m

1m10s

1s

16

1815

A1 A2

95

4.2

Panel Diagram

Panel Diagram

Supply indication(green)

Output indication(red)

Time setting

Wiring Diagram

Time range setting

General

■Applications

-Back-up source for Delay OFF in case of voltage failure (emergency lighting, emergency respirator,or protection of el. controlled doors - in case of fire).

■Function Features

-Time range (adjustable by rotary switch and fine setting by potentiometer): -0.1 s - 10 min.-Voltage range: AC/DC12-240V , clamp terminals.-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.

Technical parameters

Function

Supply terminals

AC/DC 12-240V(50-60Hz)

A1-A2

Voltage range

Burden AC 0.7-3VA/DC 0.5-1.7W

-15%;+10%Supply voltage tolerance

Supply indication

Time ranges

green LED

0.1s-10min

potentionmeterTime setting

Time deviation

Repeat accuracy

5%-mechanical setting

0.2%-set value stability

0.05%/℃,at=20℃(0.05%℉,at=68℉)

1×SPDT

16A/AC1

250VAC/24VDC

Temperature coecient

Output

500mW

red LED

1×10

1×10

max.200ms

Min.breaking capacity DC

Switching voltage

Current rating

Output indication

Mechanical life

Electrical life(AC1)

Reset time

-20℃ to +55℃(-4℉ to 131℉)

-35℃ to +75℃(-22℉ to 158℉)

Din rail EN/IEC 60715

IP40 for front panel/IP20 terminals

any

solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)

90×18×64mm

66g

IEC/EN 61812-1,IEC/EN61010-1

Operating temperature

Storage temperature

Mounting/DIN rail

Protection degree

Operating position

Overvoltage cathegory

Pollution degree

Dimensions

Weight

Standards

ECTDOFF

Mininum power time 200ms

Un R

10

20

3040 50 60 70

80

90

10m

1m10s

1s

ECTDOFF | single function true delay OFF time relay

Panel Diagram

Supply indication(green)

Output indication(red)

Time setting

Wiring Diagram

Time range setting

General

■Applications

-Back-up source for Delay OFF in case of voltage failure (emergency lighting, emergency respirator,or protection of el. controlled doors - in case of fire).

■Function Features

-Time range (adjustable by rotary switch and fine setting by potentiometer): -0.1 s - 10 min.-Voltage range: AC/DC12-240V , clamp terminals.-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.

Technical parameters

Function

Supply terminals

AC/DC 12-240V(50-60Hz)

A1-A2

Voltage range

Burden AC 0.7-3VA/DC 0.5-1.7W

-15%;+10%Supply voltage tolerance

Supply indication

Time ranges

green LED

0.1s-10min

potentionmeterTime setting

Time deviation

Repeat accuracy

5%-mechanical setting

0.2%-set value stability

0.05%/℃,at=20℃(0.05%℉,at=68℉)

1×SPDT

16A/AC1

250VAC/24VDC

Temperature coecient

Output

500mW

red LED

1×10

1×10

max.200ms

Min.breaking capacity DC

Switching voltage

Current rating

Output indication

Mechanical life

Electrical life(AC1)

Reset time

-20℃ to +55℃(-4℉ to 131℉)

-35℃ to +75℃(-22℉ to 158℉)

Din rail EN/IEC 60715

IP40 for front panel/IP20 terminals

any

solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)

90×18×64mm

66g

IEC/EN 61812-1,IEC/EN61010-1

Operating temperature

Storage temperature

Mounting/DIN rail

Protection degree

Operating position

Overvoltage cathegory

Pollution degree

Dimensions

Weight

Standards

ECTDOFF

Mininum power time 200ms

Un R

10

20

3040 50 60 70

80

90

10m

1m10s

1s

ECTDOFF | single function true delay OFF time relay

Panel Diagram

Supply indication(green)

Output indication(red)

Time setting

Wiring Diagram

Time range setting

General

■Applications

-Back-up source for Delay OFF in case of voltage failure (emergency lighting, emergency respirator,or protection of el. controlled doors - in case of fire).

■Function Features

-Time range (adjustable by rotary switch and fine setting by potentiometer): -0.1 s - 10 min.-Voltage range: AC/DC12-240V , clamp terminals.-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.

Technical parameters

Function

Supply terminals

AC/DC 12-240V(50-60Hz)

A1-A2

Voltage range

Burden AC 0.7-3VA/DC 0.5-1.7W

-15%;+10%Supply voltage tolerance

Supply indication

Time ranges

green LED

0.1s-10min

potentionmeterTime setting

Time deviation

Repeat accuracy

5%-mechanical setting

0.2%-set value stability

0.05%/℃,at=20℃(0.05%℉,at=68℉)

1×SPDT

16A/AC1

250VAC/24VDC

Temperature coecient

Output

500mW

red LED

1×10

1×10

max.200ms

Min.breaking capacity DC

Switching voltage

Current rating

Output indication

Mechanical life

Electrical life(AC1)

Reset time

-20℃ to +55℃(-4℉ to 131℉)

-35℃ to +75℃(-22℉ to 158℉)

Din rail EN/IEC 60715

IP40 for front panel/IP20 terminals

any

solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)

90×18×64mm

66g

IEC/EN 61812-1,IEC/EN61010-1

Operating temperature

Storage temperature

Mounting/DIN rail

Protection degree

Operating position

Overvoltage cathegory

Pollution degree

Dimensions

Weight

Standards

ECTDOFF

Mininum power time 200ms

Un R

10

20

3040 50 60 70

80

90

10m

1m10s

1s

ECTDOFF | single function true delay OFF time relay

Page 9: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data Sheet

Page 9 of 12EDS1331-001

Data SheetIt is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to.

All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation.All connections should be inspected periodically to ensure correct tightness.

DO NOT USE POWER TOOLS ON THESE PRODUCTS

Europa Helpline: 01582 692 444 / Email: [email protected]

Page 1 of 2

Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440

e-mail: [email protected] website: www.europacomponents.com

EDS1278-001

ECTOFF - Single Function Delay OFF Time RelayECTON - Single Function Delay ON Time Relay

-1-

ECTON | Single function delay ON time relay ECTOFF | Single function delay OFF time relay

Panel Diagram

Supply indication(green)

Output indication(red)

Time setting

Un R

10

20

3040 50 60 70

80

90

OFFON

10d1d

10h1h10m

1m

10s1s

It is possible to connect load between S-A2 (e.g contactor , control of light or any other device, without disturbing a correct function of relay(load is energized while the switch is ON.)

Wiring Diagram

LOAD 15

16 18

General

■Applications

-Suitable for applications where function and time requirements are know.-Time switch , possible to be used for pump decay time after switching heatingoff , switching of fans.

■Function Features

-Single-function relay with possibility of time setting by a potentiometer.-Choice of 2 functions:A:Delay ONB:Delay OFF

-Time scale 0.1 s - 10 days divided into 10 ranges..-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.

Technical parameters

Function

Supply terminals

AC/DC 12-240V(50-60Hz)

A1-A2

Voltage range

Burden

Voltage range

delay ON delay OFF

AC 0.7-3VA/DC 0.5-1.7W

AC 230V(50-60Hz)

AC max.12VA/1.3W AC max.12VA/1.9W

-15%;+10%

Power input

Supply voltage tolerance

Supply indication

Time ranges

green LED

potentionmeterTime setting

Time deviation

Repeat accuracy

5%-mechanical setting

0.2%-set value stability

0.05%/℃,at=20℃(0.05%℉,at=68℉)

1×SPDT 2×SPDT

16A/AC1

250VAC/24VDC

Temperature coecient

Output

500mW

red LED

1×10

1×10

max.200ms

Min.breaking capacity DC

Switching voltage

Current rating

Output indication

Mechanical life

Electrical life(AC1)

Reset time

-20℃ to +55℃(-4℉ to 131℉)

-35℃ to +75℃(-22℉ to 158℉)

Din rail EN/IEC 60715

IP40 for front panel/IP20 terminals

any

solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)

90×18×64mm

1×SPDT:W240-60g,A230-59g

2×SPDT:W240-81g,A230-79g

IEC/EN 61812-1,IEC/EN61010-1

Operating temperature

Storage temperature

Mounting/DIN rail

Protection degree

Operating position

Overvoltage cathegory

Pollution degree

Dimensions

Weight

Standards

0.1s-10days,ON,OFF

ECTON ECTOFFFunction delay ON delay OFFSupply terminals A1-A2Voltage range AC/DC 12-240V(50-60Hz) Burden AC 0.7-3VA/DC 0.5-1.7W Voltage range AC 230V(50-60Hz)Power input AC max.12VA/1.3W AC max.12VA/1.9WSupply voltage tolerance -15%;+10%Supply indication green LEDTime ranges 0.1s-10days,ON,OFFTime setting PotentionmeterTime deviation 5%-mechanical settingRepeat accuracy 0.2%-set value stabilityTemperature coecient 0.05%/°C, at=20°C(0.05%°Cat=68°C)Output 1×SPDT 1×DPDTCurrent rating 16A / AC1Switching voltage 250VAC / 24VDCMin.breaking capacity DC 500mWOutput indication red LEDMechanical life 1×10Electrical life(AC1) 1×10Reset time max.200msOperating temperature -20°C to +55°C, -4°C to 131°CStorage temperature -35°C to +75°C, -22℉ to 158°CMounting/DIN rail Din rail EN/IEC 60715Protection degree IP40 for front panel/IP20 terminals Operating position AnyOvervoltage cathegory III.Pollution degree 2Max. Cable Size (mm2) solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12) Dimensions 90×18×64mm

Weight 1×SPDT: W240- 60g,A230-59g1×DPDT: W240- 81g,A230-79g

Standards IEC/EN 61812-1,IEC/EN61010-1Time Range

Page 10: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data Sheet

Page 10 of 12EDS1331-001

Data Sheet

Page 2 of 2

Time Range

Functions DiagramDimensions

Wiring Diagram

EDS1237-001

Functions Diagram

Dimensions(mm)

25

Time Range

95

4.2

Panel Diagram

-1-

ECTON | Single function delay ON time relay ECTOFF | Single function delay OFF time relay

Panel Diagram

Supply indication(green)

Output indication(red)

Time setting

Un R

10

20

3040 50 60 70

80

90

OFFON

10d1d

10h1h10m

1m

10s1s

It is possible to connect load between S-A2 (e.g contactor , control of light or any other device, without disturbing a correct function of relay(load is energized while the switch is ON.)

Wiring Diagram

LOAD 15

16 18

General

■Applications

-Suitable for applications where function and time requirements are know.-Time switch , possible to be used for pump decay time after switching heatingoff , switching of fans.

■Function Features

-Single-function relay with possibility of time setting by a potentiometer.-Choice of 2 functions:A:Delay ONB:Delay OFF

-Time scale 0.1 s - 10 days divided into 10 ranges..-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.

Technical parameters

Function

Supply terminals

AC/DC 12-240V(50-60Hz)

A1-A2

Voltage range

Burden

Voltage range

delay ON delay OFF

AC 0.7-3VA/DC 0.5-1.7W

AC 230V(50-60Hz)

AC max.12VA/1.3W AC max.12VA/1.9W

-15%;+10%

Power input

Supply voltage tolerance

Supply indication

Time ranges

green LED

potentionmeterTime setting

Time deviation

Repeat accuracy

5%-mechanical setting

0.2%-set value stability

0.05%/℃,at=20℃(0.05%℉,at=68℉)

1×SPDT 2×SPDT

16A/AC1

250VAC/24VDC

Temperature coecient

Output

500mW

red LED

1×10

1×10

max.200ms

Min.breaking capacity DC

Switching voltage

Current rating

Output indication

Mechanical life

Electrical life(AC1)

Reset time

-20℃ to +55℃(-4℉ to 131℉)

-35℃ to +75℃(-22℉ to 158℉)

Din rail EN/IEC 60715

IP40 for front panel/IP20 terminals

any

solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)

90×18×64mm

1×SPDT:W240-60g,A230-59g

2×SPDT:W240-81g,A230-79g

IEC/EN 61812-1,IEC/EN61010-1

Operating temperature

Storage temperature

Mounting/DIN rail

Protection degree

Operating position

Overvoltage cathegory

Pollution degree

Dimensions

Weight

Standards

0.1s-10days,ON,OFF

ECTON ECTOFF

-1-

ECTON | Single function delay ON time relay ECTOFF | Single function delay OFF time relay

Panel Diagram

Supply indication(green)

Output indication(red)

Time setting

Un R

10

20

3040 50 60 70

80

90

OFFON

10d1d

10h1h10m

1m

10s1s

It is possible to connect load between S-A2 (e.g contactor , control of light or any other device, without disturbing a correct function of relay(load is energized while the switch is ON.)

Wiring Diagram

LOAD 15

16 18

General

■Applications

-Suitable for applications where function and time requirements are know.-Time switch , possible to be used for pump decay time after switching heatingoff , switching of fans.

■Function Features

-Single-function relay with possibility of time setting by a potentiometer.-Choice of 2 functions:A:Delay ONB:Delay OFF

-Time scale 0.1 s - 10 days divided into 10 ranges..-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.

Technical parameters

Function

Supply terminals

AC/DC 12-240V(50-60Hz)

A1-A2

Voltage range

Burden

Voltage range

delay ON delay OFF

AC 0.7-3VA/DC 0.5-1.7W

AC 230V(50-60Hz)

AC max.12VA/1.3W AC max.12VA/1.9W

-15%;+10%

Power input

Supply voltage tolerance

Supply indication

Time ranges

green LED

potentionmeterTime setting

Time deviation

Repeat accuracy

5%-mechanical setting

0.2%-set value stability

0.05%/℃,at=20℃(0.05%℉,at=68℉)

1×SPDT 2×SPDT

16A/AC1

250VAC/24VDC

Temperature coecient

Output

500mW

red LED

1×10

1×10

max.200ms

Min.breaking capacity DC

Switching voltage

Current rating

Output indication

Mechanical life

Electrical life(AC1)

Reset time

-20℃ to +55℃(-4℉ to 131℉)

-35℃ to +75℃(-22℉ to 158℉)

Din rail EN/IEC 60715

IP40 for front panel/IP20 terminals

any

solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)

90×18×64mm

1×SPDT:W240-60g,A230-59g

2×SPDT:W240-81g,A230-79g

IEC/EN 61812-1,IEC/EN61010-1

Operating temperature

Storage temperature

Mounting/DIN rail

Protection degree

Operating position

Overvoltage cathegory

Pollution degree

Dimensions

Weight

Standards

0.1s-10days,ON,OFF

ECTON ECTOFF

-1-

ECTON | Single function delay ON time relay ECTOFF | Single function delay OFF time relay

Panel Diagram

Supply indication(green)

Output indication(red)

Time setting

Un R

10

20

3040 50 60 70

80

90

OFFON

10d1d

10h1h10m

1m

10s1s

It is possible to connect load between S-A2 (e.g contactor , control of light or any other device, without disturbing a correct function of relay(load is energized while the switch is ON.)

Wiring Diagram

LOAD 15

16 18

General

■Applications

-Suitable for applications where function and time requirements are know.-Time switch , possible to be used for pump decay time after switching heatingoff , switching of fans.

■Function Features

-Single-function relay with possibility of time setting by a potentiometer.-Choice of 2 functions:A:Delay ONB:Delay OFF

-Time scale 0.1 s - 10 days divided into 10 ranges..-Relay status is indicated by LED.-1-MODULE,DIN rail mounting.

Technical parameters

Function

Supply terminals

AC/DC 12-240V(50-60Hz)

A1-A2

Voltage range

Burden

Voltage range

delay ON delay OFF

AC 0.7-3VA/DC 0.5-1.7W

AC 230V(50-60Hz)

AC max.12VA/1.3W AC max.12VA/1.9W

-15%;+10%

Power input

Supply voltage tolerance

Supply indication

Time ranges

green LED

potentionmeterTime setting

Time deviation

Repeat accuracy

5%-mechanical setting

0.2%-set value stability

0.05%/℃,at=20℃(0.05%℉,at=68℉)

1×SPDT 2×SPDT

16A/AC1

250VAC/24VDC

Temperature coecient

Output

500mW

red LED

1×10

1×10

max.200ms

Min.breaking capacity DC

Switching voltage

Current rating

Output indication

Mechanical life

Electrical life(AC1)

Reset time

-20℃ to +55℃(-4℉ to 131℉)

-35℃ to +75℃(-22℉ to 158℉)

Din rail EN/IEC 60715

IP40 for front panel/IP20 terminals

any

solid wire max.1×2.5or 2×1.5/with sleeve max.1×2.5(AWG 12)

90×18×64mm

1×SPDT:W240-60g,A230-59g

2×SPDT:W240-81g,A230-79g

IEC/EN 61812-1,IEC/EN61010-1

Operating temperature

Storage temperature

Mounting/DIN rail

Protection degree

Operating position

Overvoltage cathegory

Pollution degree

Dimensions

Weight

Standards

0.1s-10days,ON,OFF

ECTON ECTOFF

Functions Diagram

Dimensions(mm)

25

Time Range

95

4.2

Functions Diagram

Dimensions(mm)

25

Time Range

95

4.2

Functions Diagram

Dimensions(mm)

25

Time Range

95

4.2

Functions Diagram

Dimensions(mm)

25

Time Range

95

4.2

Page 11: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data Sheet

Page 11 of 12EDS1331-001

Data SheetIt is the responsibility of the person installing the electrical equipment to ensure that the installation meets the requirements of the IET wiring regulations and is therefore ‘fit for purpose’. Factors such as correct selection of components, cable sizing, protective devices and Earth bonding are all critical and should be checked prior to full testing and power-up. Any other regulations applicable to the equipment being installed such as the Machinery Directive and current health and safety legislation must also be adhered to.

All connections (including factory made) must be checked for the correct tightness prior to commissioning of the electrical installation.All connections should be inspected periodically to ensure correct tightness.

DO NOT USE POWER TOOLS ON THESE PRODUCTS

Europa Helpline: 01582 692 444 / Email: [email protected]

Page 1 of 2

Europa House, Airport Way, Luton, Beds, LU2 9NH Tel: 01582 692 440

e-mail: [email protected] website: www.europacomponents.com

EDS1176-001

ECMFT - Multi Function Timer 12-230V AC/DCTechnical Parameters ECMFT

Function A, B, C, D, E, F, G, H, I, JSupply Terminals A1 - A2Voltage Range AC/DC 12-240V(50-60Hz)Burden AC 0.7-3VA/DC 0.5-1.7WVoltage Range AC 230V(50-60Hz)Power Input AC max.12VA/1.3WSupply Voltage Tolerance -15%;+10%Supply Indication green LEDTime Ranges 0.1s - 10days, ON ,OFFTime Setting PotentionmeterTime Deviation 5%-mechanical settingRepeat Accuracy 0.2%-set value stabilityTemperature Coecient 0.05%/oC,at=20oC(0.05%oF, at=68oF)Output 1 × SPDTCurrent Rating 16A/ AC1Switching Voltage 250VAC / 24VDCMin Breaking Capacity DC 500mWOutput Indication red LEDMechanical Life 1×107

Electrical Life(Ac1) 1×106

Reset Time max.200msOperating Temperature -20oC to +55oC(-4oF to 131oF)Storage Temperature -35oC to +75oC(-22oF to 158oF)Mounting/Din Rail Din rail EN/IEC 60715Protection Degree IP40 for front panel / IP20 terminalsOperating Position AnyOvervoltage Category III.Pollution Degree 2Max Cable Size (mm2) Solid wire max 1×2.5 or 2×1.5 / With sleeve max.1×2.5 (AWG 12)Dimensions 90 × 18 × 64mmWeight 1 × SPDT: W240 - 62g, A230 - 60gStandards IEC / EN 61812-1, IEC / EN61010-1

Page 12: Automatic Transfer Switch (ATS) - Europa Components · 2020. 9. 21. · Automatic Transfer Switch (ATS) Amperage: 40, 60, 80, 100, 125 Number of poles: 2 = Single phase 230V 4 = Three

Data Sheet

Page 12 of 12EDS1331-001

Data Sheet

Page 2 of 2

Dimensions

Function Diagrams

EDS1176-001

-2-

http://www.geya.net

Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.

CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.

Time Range

Functions Diagram

D:

E:

F:

G:

H:

I:

J:

Dimensions(mm)

95

4.2

Time Diagrams

-2-

http://www.geya.net

Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.

CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.

Time Range

Functions Diagram

D:

E:

F:

G:

H:

I:

J:

Dimensions(mm)

95

4.2

-2-

http://www.geya.net

Disposal of Electrical WasteAll electrical waste should bedisposed of in compliance withcurrent WEEE regulations.

CautionThe products must be installed by qualified electricians. All andany electrical connections of the time relay shall comply withthe appropriate safety standards.

Time Range

Functions Diagram

D:

E:

F:

G:

H:

I:

J:

Dimensions(mm)

95

4.2