5

B P E A D -R P 1 0 0 J A L Q P E A D -R P 1 0 0 J A L Qerp.mitsubishielectric.eu/files/library/files/erpdocs/lot10/Z-016.pdf · J A A K kW h /a 4 6 6 4 4 6 6 4 L kW 1 2 .7 1 2 .7

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: B P E A D -R P 1 0 0 J A L Q P E A D -R P 1 0 0 J A L Qerp.mitsubishielectric.eu/files/library/files/erpdocs/lot10/Z-016.pdf · J A A K kW h /a 4 6 6 4 4 6 6 4 L kW 1 2 .7 1 2 .7
Page 2: B P E A D -R P 1 0 0 J A L Q P E A D -R P 1 0 0 J A L Qerp.mitsubishielectric.eu/files/library/files/erpdocs/lot10/Z-016.pdf · J A A K kW h /a 4 6 6 4 4 6 6 4 L kW 1 2 .7 1 2 .7

B PEAD-RP100JALQ PEAD-RP100JALQC PUHZ-SHW112VHA(-BS) PUHZ-SHW112YHA(-BS)E Inside dB 63 63

F Out-side dB 69 69

G R410A GWP 1975 *14.9 4.9

J B BK kWh/a 714 714L kW 10 10

3.8 3.8J A AK kWh/a 4664 4664L kW 12.7 12.7

P kW 11.2 (-10℃) 11.2 (-10℃)

R kW 11.2 (-7℃) 11.2 (-7℃)

S kW 9.4 (-25℃) 9.4 (-25℃)

T kW 1.5 1.5

at operation limittemperature

Back up heating capacity

M

Heating(Aver-ageseason)

SCOPEnergy efficiency classAnnual electricity consumption *2Design load

NDe-claredcapacity

at reference de-sign temperatureat bivalent tem-perature

DSound power levels on coolingmode

Refrigerant

H Cooling

SEEREnergy efficiency classAnnual electricity consumption *2Design load

A ModelIndoor unitOutdoor Unit

Page 3: B P E A D -R P 1 0 0 J A L Q P E A D -R P 1 0 0 J A L Qerp.mitsubishielectric.eu/files/library/files/erpdocs/lot10/Z-016.pdf · J A A K kW h /a 4 6 6 4 4 6 6 4 L kW 1 2 .7 1 2 .7
Page 4: B P E A D -R P 1 0 0 J A L Q P E A D -R P 1 0 0 J A L Qerp.mitsubishielectric.eu/files/library/files/erpdocs/lot10/Z-016.pdf · J A A K kW h /a 4 6 6 4 4 6 6 4 L kW 1 2 .7 1 2 .7

Function (indicate if present)

If function includes heating: Indicate the heating season theinformation relates to. Indicated values should relate to oneheating season at a time. Include at least the heating seasonAverage (mandatory) Y

PRODUCT INFORMATION (*)

PACKAGED AIR CONDITIONERINDOOR MODEL PEAD-RP100JALQOUTDOOR MODEL PUHZ-SHW112VHA(-BS)

cooling Y Warmer (if designated) N

Item symbol value unitDesign load

heating Y

SEER 4.9

Colder (if designated)

Item

N

symbol value unit

SCOP/A 3.8 -

Seasonal efficiencycooling Pdesignc 10.0 kW cooling -

heating/Warmerheating/Average Pdesignh 12.7 kW heating/Averageheating/Warmer Pdesignh x kW SCOP/W x -heating/Colder Pdesignh x kW heating/Colder SCOP/C x -

Declared capacity for cooling, at indoor temperature 27(19)℃and outdoor temperature Tj

Declared energy efficiency ratio, at indoor temperature 27(19)℃ and outdoor temperature Tj

Tj=35℃ Pdc 10.0 kW Tj=35℃ EERd 3.4 -Tj=30℃ Pdc 7.3 kW Tj=30℃ EERd 4.7 -

Tj=25℃ EERd 6.3 -Tj=25℃ Pdc 5.4 kWTj=20℃ EERd 7.9 -Tj=20℃ Pdc 5.6 kW

Declared capacity for heating/Average season, at indoortemperature 20℃ and outdoor temperature Tj

Declared coefficient of performance/Average season, atindoor temperature 20℃ and outdoor temperature Tj

Tj=-7℃ Pdh 11.2 kW Tj=-7℃ COPd 2.7 -3.7 -Tj=2℃ Pdh 6.8 kW

Tj=7℃ Pdh 4.4 kWTj=2℃ COPd

Tj=12℃ COPd 5.7 -Tj=7℃ COPd 4.9 -

Tj=bivalent temperature Pdh 11.2 kWTj=12℃ Pdh 5.1 kW

1.5 -Tj=bivalent temperature COPd 2.7 -

COPd x -

Declared capacity for heating/Warmer season, at indoortemperature 20℃and outdoor temperature Tj

Tj=operating limit Pdh 9.4 kW Tj=operating limit COPd

Tj=7℃ Pdh x kW

Declared coefficient of performance/Warmer season, at indoortemperature 20℃ and outdoor temperature Tj

Tj=2℃ Pdh x kW Tj=2℃Tj=7℃ COPd x -Tj=7℃ Pdh x kWTj=12℃ COPd x -Tj=7℃ COPd x -

Tj=bivalent temperature Pdh x kWTj=12℃ Pdh x kW

x -Tj=bivalent temperature COPd x -

Tj=operating limit Pdh x kW Tj=operating limit COPd

Declared capacity for heating/Colder season, at indoortemperature 20℃and outdoor temperature Tj

Declared coefficient of performance/Colder season, at indoortemperature 20℃ and outdoor temperature Tj

Tj=-7℃ Pdh x kW Tj=-7℃ COPd x -Tj=2℃ COPd x -Tj=2℃ Pdh x kWTj=7℃ COPd x -Tj=7℃ Pdh x kWTj=12℃ COPd x -Tj=12℃ Pdh x kWTj=bivalent temperature COPd x -Tj=bivalent temperature Pdh x kWTj=operating limit COPd x -Tj=operating limit Pdh x kWTj=-15℃ COPd x -Tj=-15℃ Pdh x kW

Bivalent temperature Operating limit temperatureheating/Average Tbiv -7 ℃ heating/Average Tol -25 ℃

heating/Warmer Tol x ℃heating/Warmer Tbiv x ℃heating/Colder Tol x ℃heating/Colder Tbiv x ℃

Cycling interval capacity Cycling interval efficiencyfor cooling Pcycc x kW for cooling EERcyc x -

for heating COPcyc x -for heating Pcych x kWDegradion co-efficient heating Cdh 0.25 -Degradation co-efficient cooling Cdc 0.25 -

Electric power input in power modes other than 'active mode' Annual electricity consumptionoff mode POFF 15 W cooling QCE 714 kWh/a

heating/Average QHE 4664 kWh/astandby mode PSB 15 Wx kWh/athermostat - off mode PTO(c/h) 212/74 W

crankcase heater mode PCK 0 Wheating/Warmer QHE

63/69 dB(A)

heating/Colder QHE x kWh/a

staged N Global warming potential GWP

Capacity control (indicate one of three options) Other items

fixed N Sound power level(indoor/outdoor)

LWA

variable Y Rated air flow(indoor/outdoor)

- 2520/6000 m3/h

1975 kgCO2eq.

Contact details for obtaining MITSUBISHI ELECTRIC CORPORATION SHIZUOKA WORKS3-18-1, Oshika, Suruga-ku, Shizuoka 422-8528, Japan

(*) This information is based on the "product information requirement" in COMMISSION REGULATION (EU) No206/2012.

Contact details for obtainingmore information

3-18-1, Oshika, Suruga-ku, Shizuoka 422-8528, JapanE-mail: [email protected]

Page 5: B P E A D -R P 1 0 0 J A L Q P E A D -R P 1 0 0 J A L Qerp.mitsubishielectric.eu/files/library/files/erpdocs/lot10/Z-016.pdf · J A A K kW h /a 4 6 6 4 4 6 6 4 L kW 1 2 .7 1 2 .7

Function

Capacity control

ItemSeasonal efficiency (2)

Energy efficiency class

Other items

250H1400W732D (mm)OUTDOOR MODEL PUHZ-SHW112VHA(-BS) 1350H950W330D (mm)

cooling Yheating Y

TECHNICAL DOCUMENTATION (1)

PACKAGED AIR CONDITIONERINDOOR MODEL PEAD-RP100JALQ

Colder (if designated) N

fixed N

The heating seasonAverage (mandatory) Y

Warmer (if designated) N

symbol value unit

staged Nvariable Y

heating/Average SCOP/A 3.8 -cooling SEER 4.9 -

-

heating/Colder SCOP/C x -heating/Warmer SCOP/W x -

heating/Average SCOP/A A -cooling SEER B

dB(A)

heating/Colder SCOP/C x -heating/Warmer SCOP/W x -

Refrigerant - R410A -Sound power level (indoor/outdoor) LWA 63/69

Global warming potential GWP 1975 kgCO2eq.

(1) This information is based on COMMISSION DELEGATED REGULATION (EU)No626/2011.(2) SEER/SCOP values are measured based on FprEN 14825:2011: Testing and rating at part load conditions and calculation of seasonal performance.

identification and signatureof the person empowered tobind the supplier

Hideyo TamuraManager,Packaged Air Conditioners Quality Control SectionMITSUBISHI ELECTRIC CORPORATION SHIZUOKA WORKS