17
Model COMMERCIAL S1-TBEU22P7S HVAC SERVICE PARTS TM Installation Instructions Installation Instructions BACKLIT DISPLAY Use with most Heat Pump Systems: 2-Heat, 2-Cool Digital Thermostat Digital Thermostat Heat/Cool & Heat Pump 7-Day Programmable Heat/Cool & Heat Pump 7-Day Programmable Stages: 2-Heat, 2-Cool Backlit Digital Display Aux Heat Indicator System Powered Fahrenheit or Celsius Auto-Changeover Clock Backup in the Event Up to 4 hour Override Keypad Lockout of Power Failure

BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Model

COMMERCIALS1-TBEU22P7S

HVAC SERVICE PARTSTM

I ns t a l l a t io n I n s t ruc t io nsIn s ta l l a t i on I ns t ru c t io n s

BACKLIT DISPLAY

Use with most Heat Pump Systems:

2-Heat, 2-CoolDigital ThermostatDigital Thermostat

Heat/Cool & Heat Pump7-Day Programmable

Heat/Cool & Heat Pump7-Day Programmable

• Stages: 2-Heat, 2-Cool

• Backlit Digital Display

• Aux Heat Indicator

• System Powered

• Fahrenheit or Celsius

• Auto-Changeover

• Clock Backup in the Event

• Up to 4 hour Override

• Keypad Lockout

of Power Failure

Page 2: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 2

ContentsPage #

Remove Old Thermostat

Safety Warnings

Preparation

Warranty

Test Operation

Troubleshooting

Wire Connections

INSTALLATION INSTRUCTIONS S1-TBEU22P7S

Page 3: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

CAUTION Follow Installation Instructions carefully.

DISCONNECT POWER TO THE HEATER - AIR CONDITIONER BEFORE REMOVINGTHE OLD THERMOSTAT AND INSTALLINGTHE NEW THERMOSTAT.

WARNING

Page 3

Safety WarningsP/N S1-TBEU22P7S

INSTALLATION INSTRUCTIONS

This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:(1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

S1-TBEU22P7S

Page 4: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 4

These tools will be required:

Flat BladeScrewdriver

Wire cutter& Stripper

Make sure your Heater/Air Conditioneris working properly before beginninginstallation of the thermostat.

Carefully unpack the thermostat.Save the screws and instructions.

Proper installation of the thermostat will beaccomplished by following these stepby step instructions. If you are unsureabout any of these steps, call a qualifiedtechnician for assistance.

Preparation

Turn off the power to the Heat Pump system at the main fuse panel.

INSTALLATION INSTRUCTIONS S1-TBEU22P7S

Page 5: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Remove the cover of the old thermostat.If it does not come off easily check forscrews.

Loosen the screws holding the thermostatbase or subbase to the wall, and lift away.

Disconnect the wires from the oldthermostat. Tape the ends of the wiresas you disconnect them, and mark themwith the letter of the terminal for easyreconnection to the new thermostat.

Keep the old thermostat for referencepurposes, until your new thermostat isfunctioning properly.

Remove & Replace Old Thermostat

Page 5

INSTALLATION INSTRUCTIONS S1-TBEU22P7S

Page 6: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 6

Wire ConnectionsIf the terminal designations on your oldthermostat do not match those on the new thermostat, refer to the chart belowor the wiring diagrams that follow.

Thermal Insulating Sheet

Fig. 1Wire Slots

A label is provided on the backplate that prevents drafts originating inside the wall from entering the thermostat. These drafts, left unchecked, may cause incorrect room temperature readings. Please do not remove this label from the thermostat. Insert the wires through the slots provided in the label as shown in Fig. 1.

MO

DEL:

S1-TBEU22P7S

MA

DE IN

CH

INA

LIS

TED

4Z9

52

4V.

60

HZ

NEC

CLA

SS

2

CRY1W1/O/bGW2Y2

INSTALLATION INSTRUCTIONS

Wire from theold thermostat

terminal markedFunction

Install on thenew thermostat

connector marked

W1/O/BB Rev. Valve (Energize to Heat)

W1, W or H Gas Furnace W1/O/B

C Common C

PowerRh, R, M, Vr, A R

G or F Fan G

W2 Aux. Heat W2

W1/O/BRev. Valve(Energize to Cool)

O

Y2 Electric Cool Y2

Y1 or Y Electric Cool Y1

ENC

LOS

EDEN

ERG

Y M

AN

AG

EMEN

TEQ

UIP

MEN

T

THER

MA

L INS

ULATIO

N B

AR

RIER

LEA

VE

TH

I LA

BE

L IN

P

LAC

EA

ND

P

US

H

THE

TH

ERM

OS

TAT

WIR

ES TH

RO

UG

H TH

ESE S

LOTS

.

S1-TBEU22P7S

Page 7: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

HP

O

ELECJP 1

JP 2

JP 3

GAS

GAS

B

Page 7

Sample Wiring Diagrams

5 Conductor 18 to 22 gauge unshielded cable from the thermostat to the equipment.

FAN G

COMPRESSOR Y

5 Wire, Single Stage Heat Pump (O reversing valve)

Residential Heat Pumps, split systems & package units, with no auxiliary heat.

INSTALLATION INSTRUCTIONS

MO

DEL:

S1-TBEU22P7S

MA

DE IN

CH

INA

LIS

TED

4Z9

52

4V.

60

HZ

NEC

CLA

SS

2

CRY1W1/O/bGW2Y2

ENC

LOS

EDEN

ERG

Y M

AN

AG

EMEN

TEQ

UIP

MEN

T

POWER R

COMMON COREVERSING VALVE

JUMPER SETTINGS

With Demand1st Stage Cooling

1st Stage Heating

Y, G, O

Y, G

ACTIVE OUTPUTS

S1-TBEU22P7S

Page 8: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 8

Sample Wiring Diagrams

6 Conductor 18 to 22 gauge unshielded cable from the thermostat to the equipment.

FAN G

POWER RW

2

AUXILIARY HEAT

COMPRESSOR Y

REVERSING VALVE O

6 Wire, Single Stage Heat Pump with Auxiliary Heat (O reversing valve)

Residential Heat Pumps, split systems & package units, with auxiliary heat.

INSTALLATION INSTRUCTIONS

MO

DEL:

S1-TBEU22P7S

MA

DE IN

CH

INA

LIS

TED

4Z9

52

4V.

60

HZ

NEC

CLA

SS

2

CRY1W1/O/bGW2Y2

ENC

LOS

EDEN

ERG

Y M

AN

AG

EMEN

TEQ

UIP

MEN

T

COMMON C

With DemandHP

O

ELECJP 1

JP 2

JP 3

GAS

GAS

B

JUMPER SETTINGS

ACTIVE OUTPUTS

1st Stage Cooling

1st Stage Heating

Y, G, O

Y, G2nd Stage Heating W2, Y2, Y, G

S1-TBEU22P7S

Page 9: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 9

Sample Wiring Diagrams

7 Conductor 18 to 22 gauge unshielded cable from the thermostat to the equipment.

FAN G

POWER RW

2

AUXILIARY HEAT

COMPRESSOR Y

REVERSING VALVE O

7 Wire, Two Stage Heat Pump with Auxiliary Heat (O reversing valve)

Residential Heat Pumps, split systems & package units, with auxiliary heat.

INSTALLATION INSTRUCTIONS

MO

DEL:

S1-TBEU22P7S

MA

DE IN

CH

INA

LIS

TED

4Z9

52

4V.

60

HZ

NEC

CLA

SS

2

CRY1W1/O/bGW2Y2

ENC

LOS

EDEN

ERG

Y M

AN

AG

EMEN

TEQ

UIP

MEN

T

COMMON C

2ND STAGE COOL Y2

With Demand

HP

O

ELECJP 1

JP 2

JP 3

GAS

GAS

B

JUMPER SETTINGS

ACTIVE OUTPUTS

1st Stage Cooling

1st Stage Heating2nd Stage Heating

2nd Stage CoolingY, G, O

Y, G

Y2, Y, G, O

W2, Y2, Y, G

S1-TBEU22P7S

Page 10: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 10

Sample Wiring Diagrams

5 Conductor 18 to 22 gauge unshielded cable from the thermostat to the equipment.

FAN G

COMPRESSOR Y

5 Wire, Single Stage Gas Furnace

Residential Gas Heat, Electric Cool, split systems & package units.

INSTALLATION INSTRUCTIONS

MO

DEL:

S1-TBEU22P7S

MA

DE IN

CH

INA

LIS

TED

4Z9

52

4V.

60

HZ

NEC

CLA

SS

2

CRY1W1/O/bGW2Y2

ENC

LOS

EDEN

ERG

Y M

AN

AG

EMEN

TEQ

UIP

MEN

T

POWER R

COMMON CWGAS HEAT

*In this application 24v will not be present at the ‘G’ terminal. The fan will be controlled by the Gas Furnace.

GAS

GASJP 1

JP 2

JP 3

ELEC

HP

O

B

JUMPER SETTINGS

With Demand1st Stage Cooling

1st Stage Heating

Y, G

W1, (G)*

ACTIVE OUTPUTS

S1-TBEU22P7S

Page 11: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 11

Sample Wiring Diagrams

6 Conductor 18 to 22 gauge unshielded cable from the thermostat to the equipment.

FAN G

POWER RW

2

AUXILIARY HEAT

COMPRESSOR Y

INSTALLATION INSTRUCTIONS

MO

DEL:

S1-TBEU22P7S

MA

DE IN

CH

INA

LIS

TED

4Z9

52

4V.

60

HZ

NEC

CLA

SS

2

CRY1W1/O/bGW2Y2

ENC

LOS

EDEN

ERG

Y M

AN

AG

EMEN

TEQ

UIP

MEN

T

COMMON C

Residential Gas, Electric Cool, split systems & package units.

WGAS HEAT

GAS

GASJP 1

JP 2

JP 3

ELEC

HP

O

B

JUMPER SETTINGS

With DemandACTIVE OUTPUTS

1st Stage Cooling

1st Stage Heating

Y, G

W1, (G)*2nd Stage Heating W2, W1, (G)*

*In this application 24v will not be present at the ‘G’ terminal. The fan will be controlled by the Gas Furnace.

6 Wire, Two Stage Gas Furnace and Single Stage Cooling

S1-TBEU22P7S

Page 12: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 12

Sample Wiring Diagrams

7 Conductor 18 to 22 gauge unshielded cable from the thermostat to the equipment.

FAN G

POWER RW

2

AUXILIARY HEAT

COMPRESSOR Y

INSTALLATION INSTRUCTIONS

MO

DEL:

S1-TBEU22P7S

MA

DE IN

CH

INA

LIS

TED

4Z9

52

4V.

60

HZ

NEC

CLA

SS

2

CRY1W1/O/bGW2Y2

ENC

LOS

EDEN

ERG

Y M

AN

AG

EMEN

TEQ

UIP

MEN

T

COMMON C

2ND STAGE COOL Y2

7 Wire, Two Stage Gas Furnace and Two Stage Cooling

Residential Gas Heat, Electric Cool, split systems & package units.

WGAS HEAT

GAS

GASJP 1

JP 2

JP 3

ELEC

HP

O

B

JUMPER SETTINGS

*In this application 24v will not be present at the ‘G’ terminal. The fan will be controlled by the Gas Furnace.

With DemandACTIVE OUTPUTS

1st Stage Cooling

1st Stage Heating2nd Stage Heating

2nd Stage CoolingY, G

W1, (G)*

Y2, Y, G

W2, W1, (G)*

S1-TBEU22P7S

Page 13: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 13

Sample Wiring Diagrams5 Wire, Single Stage Electric Heat

Residential Electric Heat units with a separately controlled fan.

INSTALLATION INSTRUCTIONS

ELEC

GAS

JP 1

JP 2

JP 3O

B

HP

GAS

5 Conductor 18 to 22 gauge unshielded cable from the thermostat to the equipment.

FAN G

COMPRESSOR Y

MO

DEL:

S1-TBEU22P7S

MA

DE IN

CH

INA

LIS

TED

4Z9

52

4V.

60

HZ

NEC

CLA

SS

2

CRY1W1/O/bGW2Y2

ENC

LOS

EDEN

ERG

Y M

AN

AG

EMEN

TEQ

UIP

MEN

T

POWER R

COMMON CWELECTRIC HEAT

JUMPER SETTINGS

With Demand1st Stage Cooling

1st Stage Heating

Y, G

W1, G

ACTIVE OUTPUTS

S1-TBEU22P7S

Page 14: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 14

Turn on the power to the HVAC unit.

Test Operation

TWO STAGE OPERATION - The 2nd stage

On the thermostat, press the Mode button until HEAT is displayed. Press the COOLER or WARMER button until the set temperature is 10 degrees above room temperature. The HVAC unit should energize in the heating mode.

INSTALLATION INSTRUCTIONS

Heat or CoolSetpoint

Deadband Deadband

db 1db 2(adj. 1-6 )

1st Stageturn on

2nd Stageturn on

Heating

(non-adj. 2 )

Deadband

db 1(adj. 1-6 )

1st Stageturn on

CoolingDeadband

db 2(non-adj. 2 )

2nd Stageturn on

of heat (auxiliary heat) is turned on when the room temperature is equal to or less than: the setpoint minus the 1st stage deadband (one degree, adjustable), minus the 2nd stage deadband (two degrees, non-adjustable).

Note: You may need to wait up to five minutes for heating to energize due to the compressor lockout feature. There is a two minute min-imum run-time for first stage heating.

S1-TBEU22P7S

Page 15: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 15

Test Operation

On the thermostat, press the Mode button untilOFF is displayed. Press the Fan button untilFan On is displayed. The fan should turn on and run continuously.

On the thermostat, press the Mode button until COOL is displayed. Press the COOLER or WARMER button until the set temperature is 10 degrees below room temperature. The HVAC unit should energize in the cooling mode (page 7 of the Owner’s Manual).

INSTALLATION INSTRUCTIONS

TWO STAGE OPERATION - The 2nd stage

Heat or CoolSetpoint

Deadband Deadband

db 1db 2(adj. 1-6 )

1st Stageturn on

2nd Stageturn on

Heating

(non-adj. 2 )

Deadband

db 1(adj. 1-6 )

1st Stageturn on

CoolingDeadband

db 2(non-adj. 2 )

2nd Stageturn on

of cooling is turned on when the room temperature is equal to or greater than: the setpoint plus the 1st stage deadband (one degree, adjustable), plus the 2nd stage deadband (two degrees, non-adjustable).

Note: You may need to wait up to five minutes for cooling to energize due to the compressor lockout feature.

S1-TBEU22P7S

Page 16: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 16

Trouble Shooting

INSTALLATION INSTRUCTIONS

SYMPTOM: The cooling does not attempt to turn on.

CAUSE: The cooling setpoint is set too highor the thermostat is not in the Cool mode.

section in the Owner’s Manual to: Lower the cooling setpoint Place the thermostat into the Cool mode

REMEDY: Consult the Normal Operation

SYMPTOM: The heating does not attempt to turn on.

CAUSE: The heating setpoint is set too lowor the thermostat is not in the Heat mode.

section in this manual to: Raise the heating setpoint Place the thermostat into the Heat mode

REMEDY: Consult the Normal Operation

P/N 88-905Rev. 1

CcFFOR HOME OR OFFICE USE

Tested to Complywith FCC Standards

Source 1 S1-TBEU22P7S

4Z95

S1-TBEU22P7S

Page 17: BACKLIT DISPLAY Digital 2-Heat, 2-Cool 7-Day Programmable ...Save the screws and instructions. Proper installation of the thermostat will be accomplished by following these step by

Page 17

WarrantyOne-Year Warranty - This Product is warranted to be free from defects in material and workmanship. If it appears within one year from the date of original installation, whether or not actual use begins on that date, that the product does not meet this warranty, a new or remanufactured part, at the manufacturer’s sole option to replace any defective part, will be provided without charge for the part itself provided the defective part is returned to the distributor through a qualified servicing dealer.

THIS WARRANTY DOES NOT INCLUDE LABOR OR OTHER COSTS incurred for diagnosing, repairing, removing, installing, shipping, servicing or handling of either defective parts or replacement parts. Such costs may be covered by a separate warranty provided by the installer.

THIS WARRANTY APPLIES ONLY TO PRODUCTS IN THEIR ORIGINAL INSTALLATION LOCATION AND BECOMES VOID UPON REINSTALLATION.

LIMITATIONS OF WARRANTIES – ALL IMPLIED WARRANTIES (INCLUDING IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY) ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH THE LIMITED WARRANTY IS GIVEN. SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. THE EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED, ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON WHATSOEVER. ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS. ALL REPLACEMENT PARTS, WHETHER NEW OR REMANUFACTURED, ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WARRANTY.

THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR:1. Normal maintenance as outlined in the installation and servicing instructions or owner’s manual, including filter cleaning and/or replacement and lubrication.2. Damage or repairs required as a consequence of faulty installation, misapplication, abuse, improper servicing, unauthorized alteration or improper operation.3. Failure to start due to voltage conditions, blown fuses, open circuit breakers or other damages due to the inadequacy or interruption of electrical service.4. Damage as a result of floods, winds, fires, lightning, accidents, corrosive environments or other conditions beyond the control of the Manufacturer.5. Parts not supplied or designated by the Manufacturer, or damages resulting from their use. 6. Manufacturer products installed outside the continental U.S.A., Alaska, Hawaii, and Canada.7. Electricity or fuel costs or increases in electricity or fuel costs for any reason whatsoever including additional or unusual use of supplemental electric heat.8. ANY SPECIAL INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIAL DAMAGE OF ANY NATURE WHATSOEVER. Some states do not allow the exclusion of incidental or consequential damages, so the above may not apply to you.

This warranty gives you specific legal rights and you may also have other rights which may vary from state to state.

INSTALLATION INSTRUCTIONS S1-TBEU22P7S