PAGE TM VERTIV FOR 1 of 11 10770, REVISION 3/1/2017 Vertiv Copyright © 2017 KIRKLAND AND ELLIS TESTED BY: Taylor, Stephen Battery Maintenance Report Quarterly TICKET # 112836 CITY CUSTOMER STREET SITE ID KIRKLAND AND ELLIS DATE CHICAGO IL 60654 POSTAL CODE 300 NORTH LASALLE STREET TAG # STATE / PROVINCE COUNTRY 3/9/2017 UPS Mod-11 SYSTEM IDENTIFIER USA ATTENTION Robert Frytz 3366272 1443971 VLA C&D BATTERY: MODEL: MANUFACTURER: DATE CODE: 08/2008 NO OF JARS: FIXTURE: 240 4 60 BATTERY TYPE: STRING INSTALL DATE: 08/2008 RACK NUMBER OF CELLS PER JAR: CELLS PER STRING: MEASUREMENT POINTS: MANUFACTURER ORDER #: 240 INTERCELL MEASUREMENTS: EMERSON ORDER #: 0 XT4LC-09 SERIAL #: MANUFACTURER: BATTERY MONITORING SYSTEM: MODEL: Alber BDS-256 TAG #: RTM256-08-0505 1444164 UPS / CHARGER: MODEL: MANUFACTURER: SERIAL #: TAG #: U39MM301A0AD050 Liebert D08F5B0014 1433675 MODEL: X4TLC-09 TAG #: # CELLS/JARS LIEBERT SPARE BATTERIES: DATE CODE 09/2008 6 INSPECTION TYPE: Quarterly SYSTEM READINGS: 537.8 V Amps V 54 .806 7.2 FLOAT VOLTAGE: FLOAT CHARGING CURRENT: AC RIPPLE CURRENT: AC RIPPLE VOLTAGE: SYSTEM LOAD: Amps V, Hrs Duration KVA SYSTEM VOLTAGE: V/C FRESHENING/EQUALIZE CHARGE VOLTAGE (Volts/Cell rate): 0.2 GENERAL SITE & SAFETY EQUIPMENT OBSERVATIONS: ROOM TEMP: 74 RACK CONDITION: OK F Present Present Present Present Present Present Present Present FIRE SUPPRESSION Present EMERGENCY GENERATOR HYDROGEN DETECTOR EYE WASH STATION ADEQUATE LIGHTING SHOWER PRESENT SPILL CONTAINMENT SPILL KIT VENTILATION FAN OK INSPECT THE APPEARANCE AND CLEANLINESS OF THE BATTERY AND BATTERY ROOM: N/A VERIFY NO GROUND FAULT EXISTS: Issues Found VISUALLY INSPECT JARS AND COVERS FOR CRACKS AND LEAKAGE: OK INSPECT ELECTROLYTE LEVELS: OK VISUALLY INSPECT FOR EVIDENCE OF CORROSION: # Manufacturer Model Equipment Inventory # Type Calibration Date 1 INSTRUMENTS USED: 1

Battery Maintenance Report Quarterly

  • Upload
    others

  • View
    10

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Battery Maintenance Report Quarterly

PAGETM

VERTIV FOR 1 of 1110770, REVISION 3/1/2017 VertivCopyright © 2017KIRKLAND AND ELLIS

TESTED BY: Taylor, Stephen

Battery Maintenance ReportQuarterly

TICKET #

112836

CITY

CUSTOMER

STREET

SITE IDKIRKLAND AND ELLIS DATE

CHICAGO IL

60654POSTAL CODE

300 NORTH LASALLE STREETTAG #

STATE / PROVINCE

COUNTRY

3/9/2017

UPS Mod-11SYSTEMIDENTIFIER

USA ATTENTION Robert Frytz

3366272

1443971

VLA

C&DBATTERY:

MODEL:

MANUFACTURER:

DATE CODE: 08/2008

NO OF JARS:

FIXTURE:

240

4

60

BATTERY TYPE:

STRING INSTALL DATE: 08/2008

RACK

NUMBER OF CELLS PER JAR:

CELLS PER STRING:

MEASUREMENT POINTS:

MANUFACTURER ORDER #:

240

INTERCELL MEASUREMENTS:

EMERSON ORDER #:

0

XT4LC-09

SERIAL #:MANUFACTURER:

BATTERY MONITORING SYSTEM:

MODEL:

Alber

BDS-256 TAG #:

RTM256-08-0505

1444164

UPS / CHARGER:

MODEL:

MANUFACTURER: SERIAL #:

TAG #:U39MM301A0AD050

Liebert D08F5B0014

1433675

MODEL: X4TLC-09 TAG #:

# CELLS/JARSLIEBERT SPARE BATTERIES:

DATE CODE 09/20086

INSPECTION TYPE: Quarterly

SYSTEM READINGS:

537.8 V

Amps V

54

.806

7.2FLOAT VOLTAGE:

FLOAT CHARGING CURRENT:

AC RIPPLE CURRENT:

AC RIPPLE VOLTAGE:

SYSTEM LOAD:

Amps

V, Hrs Duration

KVA

SYSTEM VOLTAGE:V/CFRESHENING/EQUALIZE CHARGE VOLTAGE (Volts/Cell rate):

0.2

GENERAL SITE & SAFETY EQUIPMENT OBSERVATIONS:

ROOM TEMP: 74

RACK CONDITION: OK

F

Present

Present

Present

Present Present

Present

Present

Present

FIRE SUPPRESSION Present

EMERGENCY GENERATOR HYDROGEN DETECTOR

EYE WASH STATION ADEQUATE LIGHTING

SHOWER PRESENT

SPILL CONTAINMENT

SPILL KIT

VENTILATION FAN

OKINSPECT THE APPEARANCE AND CLEANLINESS OF THE BATTERY AND BATTERY ROOM:

N/AVERIFY NO GROUND FAULT EXISTS:

Issues FoundVISUALLY INSPECT JARS AND COVERS FOR CRACKS AND LEAKAGE:

OKINSPECT ELECTROLYTE LEVELS:

OKVISUALLY INSPECT FOR EVIDENCE OF CORROSION:

# Manufacturer Model Equipment Inventory # Type Calibration Date1

INSTRUMENTS USED:

1

Page 2: Battery Maintenance Report Quarterly

PAGE

PAGETM

VERTIV FOR 2 of 1110770, REVISION 3/1/2017 VertivCopyright © 2017KIRKLAND AND ELLIS

Site 112836, Tag 1443971

Battery Maintenance ReportQuarterly

OUT OF LIMIT CELLS IN CURRENT INSPECTION

None

COMMENTS: All battery readings are within specifications. Typical life span of the battery system is 9 to 12 years. DEFICIENCIES: Cracks were found on the lid on some of the batteries.

Page 3: Battery Maintenance Report Quarterly

PAGE

PAGETM

VERTIV FOR 3 of 1110770, REVISION 3/1/2017 VertivCopyright © 2017KIRKLAND AND ELLIS

Site 112836, Tag 1443971

Battery Maintenance ReportQuarterly

LIMITSMonitor (Min/Max)Critical (Min/Max)

MiscDATE CODEMODEL#

//1.2751.3

SPECIFIC GRAVITY

1.21.195/

2.182.15

/ 2.292.32

/ 7262

/ 8088

JAR DATA

(V)TEMP.

°F

FLOATVOLTAGE

CELL

2.247XT4LC-09 08/200812.248XT4LC-09 08/200822.251XT4LC-09 08/200832.251XT4LC-09 08/200842.237XT4LC-09 08/200852.229XT4LC-09 08/200862.236XT4LC-09 08/200872.235XT4LC-09 08/200882.237XT4LC-09 08/200892.249 1.246 74XT4LC-09 08/2008102.248XT4LC-09 08/2008112.250XT4LC-09 08/2008122.242XT4LC-09 08/2008132.228XT4LC-09 08/2008142.258XT4LC-09 08/2008152.247XT4LC-09 08/2008162.229XT4LC-09 08/2008172.235XT4LC-09 08/2008182.240XT4LC-09 08/2008192.233 1.239 74XT4LC-09 08/2008202.245XT4LC-09 08/2008212.243XT4LC-09 08/2008222.243XT4LC-09 08/2008232.249XT4LC-09 08/2008242.257XT4LC-09 08/2008252.244XT4LC-09 08/2008262.252XT4LC-09 08/2008272.246XT4LC-09 08/2008282.2324XTHC-9 11/2015292.245 1.242 744XTHC-9 11/2015302.2404XTHC-9 11/2015312.2414XTHC-9 11/2015322.2554XTHC-9 11/2015332.2734XTHC-9 11/2015342.2574XTHC-9 11/2015352.2624XTHC-9 11/2015362.2424XTHC-9 11/2015372.2314XTHC-9 11/2015382.2414XTHC-9 11/2015392.244 1.251 744XTHC-9 11/2015402.2424XTHC-9 11/2015412.2394XTHC-9 11/2015422.2374XTHC-9 11/2015432.230XT4LC-09 08/2008442.243XT4LC-09 08/2008452.245XT4LC-09 08/2008462.245XT4LC-09 08/2008472.239XT4LC-09 08/2008482.241XT4LC-09 08/2008492.245 1.244 74XT4LC-09 08/2008502.249XT4LC-09 08/2008512.241XT4LC-09 08/2008522.249XT4LC-09 08/2008532.245XT4LC-09 08/2008542.245XT4LC-09 08/2008552.243XT4LC-09 08/2008562.234XT4LC-09 08/2008572.226XT4LC-09 08/2008582.224XT4LC-09 08/2008592.234 1.262 74XT4LC-09 08/200860 IR2.244XT4LC-09 08/2008612.237XT4LC-09 08/2008622.240XT4LC-09 08/200863

Page 4: Battery Maintenance Report Quarterly

PAGE

PAGETM

VERTIV FOR 4 of 1110770, REVISION 3/1/2017 VertivCopyright © 2017KIRKLAND AND ELLIS

Site 112836, Tag 1443971

Battery Maintenance ReportQuarterly

LIMITSMonitor (Min/Max)Critical (Min/Max)

MiscDATE CODEMODEL#

//1.2751.3

SPECIFIC GRAVITY

1.21.195/

2.182.15

/ 2.292.32

/ 7262

/ 8088

JAR DATA

(V)TEMP.

°F

FLOATVOLTAGE

CELL

2.245XT4LC-09 08/2008642.2444XTHC-9 11/2015652.2574XTHC-9 11/2015662.2504XTHC-9 11/2015672.2504XTHC-9 11/2015682.238XT4LC-09 08/2008692.223 1.235 74XT4LC-09 08/2008702.241XT4LC-09 08/2008712.244XT4LC-09 08/2008722.256XT4LC-09 08/2008732.250XT4LC-09 08/2008742.257XT4LC-09 08/2008752.257XT4LC-09 08/2008762.249XT4LC-09 08/2008772.251XT4LC-09 08/2008782.256XT4LC-09 08/2008792.254 1.236 74XT4LC-09 08/2008802.251XT4LC-09 08/2008812.245XT4LC-09 08/2008822.249XT4LC-09 08/2008832.247XT4LC-09 08/2008842.2474XTHC-9 11/2015852.2504XTHC-9 11/2015862.2504XTHC-9 11/2015872.2494XTHC-9 11/2015882.253XT4LC-09 08/2008892.251 1.257 74XT4LC-09 08/2008902.255XT4LC-09 08/2008912.249XT4LC-09 08/2008922.229XT4LC-09 08/2008932.229XT4LC-09 08/2008942.256XT4LC-09 08/2008952.234XT4LC-09 08/2008962.233XT4LC-09 08/2008972.233XT4LC-09 08/2008982.236XT4LC-09 08/2008992.228 1.238 74XT4LC-09 08/20081002.238XT4LC-09 08/20081012.242XT4LC-09 08/20081022.240XT4LC-09 08/20081032.238XT4LC-09 08/20081042.238XT4LC-09 08/20081052.245XT4LC-09 08/20081062.241XT4LC-09 08/20081072.233XT4LC-09 08/20081082.2204XTHC-9 11/20151092.219 1.232 744XTHC-9 11/20151102.2224XTHC-9 11/20151112.2174XTHC-9 11/20151122.241XT4LC-09 08/20081132.242XT4LC-09 08/20081142.240XT4LC-09 08/20081152.237XT4LC-09 08/20081162.244XT4LC-09 08/20081172.241XT4LC-09 08/20081182.246XT4LC-09 08/20081192.225 1.247 74XT4LC-09 08/2008120 IT2.250XT4LC-09 08/20081212.235XT4LC-09 08/20081222.239XT4LC-09 08/20081232.243XT4LC-09 08/20081242.236XT4LC-09 08/20081252.231XT4LC-09 08/20081262.228XT4LC-09 08/20081272.234XT4LC-09 08/20081282.228XT4LC-09 08/20081292.236 1.248 74XT4LC-09 08/20081302.223XT4LC-09 08/2008131

Page 5: Battery Maintenance Report Quarterly

PAGE

PAGETM

VERTIV FOR 5 of 1110770, REVISION 3/1/2017 VertivCopyright © 2017KIRKLAND AND ELLIS

Site 112836, Tag 1443971

Battery Maintenance ReportQuarterly

LIMITSMonitor (Min/Max)Critical (Min/Max)

MiscDATE CODEMODEL#

//1.2751.3

SPECIFIC GRAVITY

1.21.195/

2.182.15

/ 2.292.32

/ 7262

/ 8088

JAR DATA

(V)TEMP.

°F

FLOATVOLTAGE

CELL

2.239XT4LC-09 08/20081322.229XT4LC-09 08/20081332.239XT4LC-09 08/20081342.245XT4LC-09 08/20081352.227XT4LC-09 08/20081362.245XT4LC-09 08/20081372.235XT4LC-09 08/20081382.251XT4LC-09 08/20081392.239 1.256 74XT4LC-09 08/20081402.238XT4LC-09 08/20081412.246XT4LC-09 08/20081422.248XT4LC-09 08/20081432.236XT4LC-09 08/20081442.232XT4LC-09 08/20081452.224XT4LC-09 08/20081462.234XT4LC-09 08/20081472.230XT4LC-09 08/20081482.239XT4LC-09 08/20081492.233 1.251 74XT4LC-09 08/20081502.247XT4LC-09 08/20081512.229XT4LC-09 08/20081522.244XT4LC-09 08/20081532.241XT4LC-09 08/20081542.238XT4LC-09 08/20081552.245XT4LC-09 08/20081562.237XT4LC-09 08/20081572.234XT4LC-09 08/20081582.241XT4LC-09 08/20081592.232 1.257 74XT4LC-09 08/20081602.261XT4LC-09 08/20081612.246XT4LC-09 08/20081622.251XT4LC-09 08/20081632.247XT4LC-09 08/20081642.259XT4LC-09 08/20081652.266XT4LC-09 08/20081662.256XT4LC-09 08/20081672.262XT4LC-09 08/20081682.248XT4LC-09 08/20081692.234 1.251 74XT4LC-09 08/20081702.254XT4LC-09 08/20081712.267XT4LC-09 08/20081722.255XT4LC-09 08/20081732.254XT4LC-09 08/20081742.258XT4LC-09 08/20081752.228XT4LC-09 08/20081762.254XT4LC-09 08/20081772.249XT4LC-09 08/20081782.248XT4LC-09 08/20081792.251 1.244 74XT4LC-09 08/2008180 IR2.234XT4LC-09 08/20081812.227XT4LC-09 08/20081822.234XT4LC-09 08/20081832.228XT4LC-09 08/20081842.237XT4LC-09 08/20081852.251XT4LC-09 08/20081862.243XT4LC-09 08/20081872.250XT4LC-09 08/20081882.252XT4LC-09 08/20081892.252 1.243 74XT4LC-09 08/20081902.257XT4LC-09 08/20081912.255XT4LC-09 08/20081922.243XT4LC-09 08/20081932.249XT4LC-09 08/20081942.246XT4LC-09 08/20081952.236XT4LC-09 08/20081962.238XT4LC-09 08/20081972.246XT4LC-09 08/20081982.243XT4LC-09 08/2008199

Page 6: Battery Maintenance Report Quarterly

PAGE

PAGETM

VERTIV FOR 6 of 1110770, REVISION 3/1/2017 VertivCopyright © 2017KIRKLAND AND ELLIS

Site 112836, Tag 1443971

Battery Maintenance ReportQuarterly

LIMITSMonitor (Min/Max)Critical (Min/Max)

MiscDATE CODEMODEL#

//1.2751.3

SPECIFIC GRAVITY

1.21.195/

2.182.15

/ 2.292.32

/ 7262

/ 8088

JAR DATA

(V)TEMP.

°F

FLOATVOLTAGE

CELL

2.247 1.255 74XT4LC-09 08/20082002.228XT4LC-09 08/20082012.228XT4LC-09 08/20082022.228XT4LC-09 08/20082032.228XT4LC-09 08/20082042.252XT4LC-09 08/20082052.251XT4LC-09 08/20082062.254XT4LC-09 08/20082072.248XT4LC-09 08/20082082.249XT4LC-09 08/20082092.254 1.251 74XT4LC-09 08/20082102.258XT4LC-09 08/20082112.256XT4LC-09 08/20082122.228XT4LC-09 08/20082132.228XT4LC-09 08/20082142.228XT4LC-09 08/20082152.235XT4LC-09 08/20082162.228XT4LC-09 08/20082172.228XT4LC-09 08/20082182.231XT4LC-09 08/20082192.229 1.260 74XT4LC-09 08/20082202.234XT4LC-09 08/20082212.225XT4LC-09 08/20082222.233XT4LC-09 08/20082232.232XT4LC-09 08/20082242.242XT4LC-09 08/20082252.246XT4LC-09 08/20082262.243XT4LC-09 08/20082272.236XT4LC-09 08/20082282.208XT4LC-09 08/20082292.224 1.236 74XT4LC-09 08/20082302.235XT4LC-09 08/20082312.235XT4LC-09 08/20082322.237XT4LC-09 08/20082332.237XT4LC-09 08/20082342.234XT4LC-09 08/20082352.242XT4LC-09 08/20082362.225XT4LC-09 08/20082372.224XT4LC-09 08/20082382.227XT4LC-09 08/20082392.223 1.237 74XT4LC-09 08/2008240

CriticalNormal MonitorCELL VOLTAGE (1-60) ON 3/9/2017

Page 7: Battery Maintenance Report Quarterly

PAGE

PAGETM

VERTIV FOR 7 of 1110770, REVISION 3/1/2017 VertivCopyright © 2017KIRKLAND AND ELLIS

Site 112836, Tag 1443971

Battery Maintenance ReportQuarterly

CriticalNormal MonitorCELL VOLTAGE (61-120) ON 3/9/2017

CriticalNormal MonitorCELL VOLTAGE (121-180) ON 3/9/2017

CriticalNormal MonitorCELL VOLTAGE (181-240) ON 3/9/2017

Page 8: Battery Maintenance Report Quarterly

PAGE

PAGETM

VERTIV FOR 8 of 1110770, REVISION 3/1/2017 VertivCopyright © 2017KIRKLAND AND ELLIS

Site 112836, Tag 1443971

Battery Maintenance ReportQuarterly

CELL SPECIFIC GRAVITY (Cells 1-60) ON 3/9/2017 Normal Monitor Critical

CELL SPECIFIC GRAVITY (Cells 61-120) ON 3/9/2017 Normal Monitor Critical

CELL SPECIFIC GRAVITY (Cells 121-180) ON 3/9/2017 Normal Monitor Critical

Page 9: Battery Maintenance Report Quarterly

PAGE

PAGETM

VERTIV FOR 9 of 1110770, REVISION 3/1/2017 VertivCopyright © 2017KIRKLAND AND ELLIS

Site 112836, Tag 1443971

Battery Maintenance ReportQuarterly

CELL SPECIFIC GRAVITY (Cells 181-240) ON 3/9/2017 Normal Monitor Critical

Normal Monitor CriticalCELL TEMPERATURE (Cells 1-60) ON 3/9/2017

Normal Monitor CriticalCELL TEMPERATURE (Cells 61-120) ON 3/9/2017

Page 10: Battery Maintenance Report Quarterly

PAGE

PAGETM

VERTIV FOR 10 of 1110770, REVISION 3/1/2017 VertivCopyright © 2017KIRKLAND AND ELLIS

Site 112836, Tag 1443971

Battery Maintenance ReportQuarterly

Normal Monitor CriticalCELL TEMPERATURE (Cells 121-180) ON 3/9/2017

Normal Monitor CriticalCELL TEMPERATURE (Cells 181-240) ON 3/9/2017

LEGEND

ALL TESTS VOLTAGE GRAPH

3/9/2017

12/11/2016

9/8/2016

8/23/2010

3/25/2010

Page 11: Battery Maintenance Report Quarterly

PAGE

PAGETM

VERTIV FOR 11 of 1110770, REVISION 3/1/2017 VertivCopyright © 2017KIRKLAND AND ELLIS

Site 112836, Tag 1443971

Battery Maintenance ReportQuarterly

ALL TESTS SPECIFIC GRAVITY GRAPH

LEGEND

3/9/2017

12/11/2016

9/8/2016

8/23/2010

3/25/2010

ALL TESTS TEMPERATURE GRAPH

LEGEND

3/9/2017

12/11/2016

9/8/2016

8/23/2010

3/25/2010