8
BC-BAS

BC-BAS Brochure:Layout 1 - Dwyer Instruments, Inc

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

BC-BAS

©Copyright 2010 Dwyer Instruments, Inc.

Printed in U.S.A. 12/10

DIRTY FILTER ALARMThe differential pressure loss across the filter is monitored.

• Products used: ADPS Pressure Switch and 616KD Differential Pressure Transmitter

FAN VALIDATIONProving a fan is operating can be done in several ways:

1. Monitor the differential pressure between upstream and downstream of the fan.

• Product used: ADPS Pressure Switch

2. Monitor the air flow or velocity exiting the fan.• Products used: DH, DHII, DH3, MS, AVU, VTT, 641 Transmitter or 616KD

Differential Pressure Transmitter

3. Monitor the current usage of the fan.• Product used: SCS Current Switch

DUCT STATIC PRESSUREA pressure transmitter is used with a static pressure tip or optional inherentstatic probe to monitor discharge or mixing air duct static pressures.

• Products used: MS Pressure Transmitter with A-302 Static Pressure Tip or MS with integral static pressure probe

DUCT HUMIDITY SENSORA humidity transmitter is inserted into the duct to monitor the zone dischargehumidity.

• Product used: RHP Humidity Transmitter

DUCT HUMIDITY/TEMPERATURE SENSORA dual humidity and temperature transmitter is inserted into the duct tomonitor the exhaust air humidity and temperature.

• Product used: RHP Humidity/Temperature Transmitter

DUCT TEMPERATURE SENSORA temperature sensor is inserted into the duct to monitor the supply air, mixair, and exhaust air temperature.

• Products used: TE-D Series Temperature Sensor or TE-A Averaging Temperature Sensor

FILTERA pleated filter offers better protection against dust and other airborneparticulate, protecting your HVAC equipment and helps clean the indoorenvironment.

• Product used: DF Pleated Filters

FROZEN COIL ALARMA differential pressure loss across the cooling coil indicates ice build up on thecoil.

• Products used: ADPS Pressure Switch or EDPS UL508 listed Pressure Switch

DWYER INSTRUMENTS, INC.P.O. Box 373

Michigan City, IN 46361-9986

Return Service Requested

PRODUCTS APPLIED FORAIR HANDLER APPLICATION AIR HANDLER APPLICATION

BC-BAS Brochure:Layout 1 2/9/11 11:12 AM Page 1

ProductsLevel, Flowmeter, ValvesLevel, Flowmeter, ValvesLevel, Flowmeter, ValvesPressure Handheld, Velocity Handheld, Pitot Tube, Test EquipmentPressure Handheld, Velocity Handheld, Pitot Tube, Test EquipmentAir Velocity Transmitter, Air Flow Station, Pitot Tube, Differential Pressure Transmitter, Gage/Switch - Digital, Valve ActuatorDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure Gage CO2, Air Velocity Transmitter, Air Flow Station, Differential Pressure Transmitter, Gage/Switch - DigitalCO2, Air Velocity Transmitter, Air Flow Station, Differential Pressure Transmitter, Gage/Switch - DigitalDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure Gage, Humidity TransmitterDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure GageHumidity Transmitter, CO2, Differential PressureTransmitter, Zone Valve, Level IndicatorHumidity Transmitter, CO2 Transmitter, Differential PressureTransmitter, Zone Valve, Level Indicator Handheld Humidity, Handheld Pressure, Handheld Velocity, Humidity Transmitter, Differential Pressure Transmitter, CO2 TransmitterHumidity Transmitter, Water Detector

ROOM TEMPERATURE AND HUMIDITYA wall mounted temperature and humidity transmitter isplaced in the zone to monitor the zone conditions anddetermine demand.

• Product used: RHP-W Humidity and Temperature Transmitter

WATER FLOW CONTROLVAV systems can include heating coils of hot water thatthe air flows past. A zone valve is used to change theamount of hot water added to the heating coil. Zonesystems can include radiant heating systems. A zone valveis used to change the amount of hot water added to theradiator in the zone.

• Products used: ZV1 or ZV2 Zone Valves

WATER MIXING VALVEThree-way valves are used to mix return and supply water and chilled and hotwater together.

• Products used: GV Globe Valve with EVA Electric Actuator, or 3ABV Ball Valve with Electric Actuator

WATER TEMPERATURE MONITORA temperature sensor is inserted into the water pipeline to monitor thesystem supply, system return, condenser return, condenser supply, andboiler supply water temperature.

• Product used: TE-I RTD Temperature Sensor with Thermowell

OUTSIDE AIR SENSORA dual humidity and temperature transmitter is outside the building tomonitor the outdoor air humidity and temperature.

• Product used: RHP Humidity/Temperature Transmitter with optional RHRS radiation shield

PUMP VALIDATION/FLOW PROVINGProving a pump is operating can be done in several ways:

1. Monitor the differential pressure between upstream and downstream of the pump.

• Product used: DX Pressure Switch

2. Monitor the water flow exiting the pump.• Products used: FS-2, V8 or V7 Flow Switch

3. Monitor the current usage of the pump.• Product used: SCS Current Switch

4. Ensure proper differential pressure is created from sufficient flow through chiller.

• Product used: 629 Differential Pressure Transmitter

LEAK DETECTION/DRIP PAN MONITORA conductivity sensor is used to detect leaks of fluids around equipmentand valves or to detect full drip pans.

• Products used: WD or WD2 Leak Detectors

AIR VOLUME CONTROLThe amount of air added to the zone is controlled by opening andclosing the air duct via a damper with a damper actuator whichreceives a feedback signal from a differential pressuretransmitter.

• Products used: DDA Damper Actuator and 616KD Differential Pressure Transmitter

ROOM TEMPERATURE AND CARBON DIOXIDEThe amount of air flow to a zone is varied based on occupancy ina zone. The occupancy is determined by the concentration ofcarbon dioxide in the zone.

• Product used: CDT Carbon Dioxide and Temperature Transmitter

PRODUCTS APPLIED FORVARIABLE-AIR-VOLUME APPLICATION

The following chart shows where Dwyer Instruments products have the potential to help buildings acquire LEED®. TheLEED (Leadership in Energy and Environmental Design) Green Building Rating System is the nationally acceptedbenchmark for design, construction, and operation of high performance green buildings. Dwyer is proud to be amember of the U.S. Green Building Council and to be helping build a greener future. To find out more about LEED goto www.usgbc.org.

LEED StandardSS 6.1WE 1WE 2EA Prerequisite 1EA Prerequisite 3IEQ Prerequisite 1

IEQ Prerequisite 2IEQ 1

IEQ 2

IEQ 3.2

IEQ 5

IEQ 6.2

IEQ 7.1

IEQ 7.2

IEQ 10

DescriptionStormwater ControlWater Efficient LandscapingInnovative Wastewater TechnologiesFundamental Commissioning of Building Energy SystemsEnhanced Commissioning

Minimum Indoor Air Quality Performance

Environmental Tobacco Smoke (ETS) ControlOutdoor Air Delivery Innovation

Increased Ventilation

Construction Indoor Air Quality Management Plan - Before Occupancy

Indoor Chemical and Pollution Control

Controllability of Systems - Thermal ComfortThermal Comfort - Design

Thermal Comfort - Ventilation

Mold Prevention

NC12-42Required

Required

Required

Required

1

1

1

1

1

1

1

N/A

School12-42Required

Required

Required

Required

1

1

1

1

1

1

1

1

CS12-42Required

Required

Required

Required

1

1

N/A

1

1

1

N/A

N/A

Credit Weighting (Points) byBuilding Classification

See more at www.dwyer-inst.com/leed/leed_profile.cfm

LEED® is a registered trademark of the U.S. Green Building Council.

VARIABLE-AIR-VOLUME APPLICATION ASK HOW WE CAN HELP YOU WITH LEEDHEATING & COOLING APPLICATIONPRODUCTS APPLIED FOR

HEATING & COOLING APPLICATION

BC-BAS Brochure:Layout 1 2/9/11 11:13 AM Page 2

ProductsLevel, Flowmeter, ValvesLevel, Flowmeter, ValvesLevel, Flowmeter, ValvesPressure Handheld, Velocity Handheld, Pitot Tube, Test EquipmentPressure Handheld, Velocity Handheld, Pitot Tube, Test EquipmentAir Velocity Transmitter, Air Flow Station, Pitot Tube, Differential Pressure Transmitter, Gage/Switch - Digital, Valve ActuatorDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure Gage CO2, Air Velocity Transmitter, Air Flow Station, Differential Pressure Transmitter, Gage/Switch - DigitalCO2, Air Velocity Transmitter, Air Flow Station, Differential Pressure Transmitter, Gage/Switch - DigitalDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure Gage, Humidity TransmitterDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure GageHumidity Transmitter, CO2, Differential PressureTransmitter, Zone Valve, Level IndicatorHumidity Transmitter, CO2 Transmitter, Differential PressureTransmitter, Zone Valve, Level Indicator Handheld Humidity, Handheld Pressure, Handheld Velocity, Humidity Transmitter, Differential Pressure Transmitter, CO2 TransmitterHumidity Transmitter, Water Detector

ROOM TEMPERATURE AND HUMIDITYA wall mounted temperature and humidity transmitter isplaced in the zone to monitor the zone conditions anddetermine demand.

• Product used: RHP-W Humidity and Temperature Transmitter

WATER FLOW CONTROLVAV systems can include heating coils of hot water thatthe air flows past. A zone valve is used to change theamount of hot water added to the heating coil. Zonesystems can include radiant heating systems. A zone valveis used to change the amount of hot water added to theradiator in the zone.

• Products used: ZV1 or ZV2 Zone Valves

WATER MIXING VALVEThree-way valves are used to mix return and supply water and chilled and hotwater together.

• Products used: GV Globe Valve with EVA Electric Actuator, or 3ABV Ball Valve with Electric Actuator

WATER TEMPERATURE MONITORA temperature sensor is inserted into the water pipeline to monitor thesystem supply, system return, condenser return, condenser supply, andboiler supply water temperature.

• Product used: TE-I RTD Temperature Sensor with Thermowell

OUTSIDE AIR SENSORA dual humidity and temperature transmitter is outside the building tomonitor the outdoor air humidity and temperature.

• Product used: RHP Humidity/Temperature Transmitter with optional RHRS radiation shield

PUMP VALIDATION/FLOW PROVINGProving a pump is operating can be done in several ways:

1. Monitor the differential pressure between upstream and downstream of the pump.

• Product used: DX Pressure Switch

2. Monitor the water flow exiting the pump.• Products used: FS-2, V8 or V7 Flow Switch

3. Monitor the current usage of the pump.• Product used: SCS Current Switch

4. Ensure proper differential pressure is created from sufficient flow through chiller.

• Product used: 629 Differential Pressure Transmitter

LEAK DETECTION/DRIP PAN MONITORA conductivity sensor is used to detect leaks of fluids around equipmentand valves or to detect full drip pans.

• Products used: WD or WD2 Leak Detectors

AIR VOLUME CONTROLThe amount of air added to the zone is controlled by opening andclosing the air duct via a damper with a damper actuator whichreceives a feedback signal from a differential pressuretransmitter.

• Products used: DDA Damper Actuator and 616KD Differential Pressure Transmitter

ROOM TEMPERATURE AND CARBON DIOXIDEThe amount of air flow to a zone is varied based on occupancy ina zone. The occupancy is determined by the concentration ofcarbon dioxide in the zone.

• Product used: CDT Carbon Dioxide and Temperature Transmitter

PRODUCTS APPLIED FORVARIABLE-AIR-VOLUME APPLICATION

The following chart shows where Dwyer Instruments products have the potential to help buildings acquire LEED®. TheLEED (Leadership in Energy and Environmental Design) Green Building Rating System is the nationally acceptedbenchmark for design, construction, and operation of high performance green buildings. Dwyer is proud to be amember of the U.S. Green Building Council and to be helping build a greener future. To find out more about LEED goto www.usgbc.org.

LEED StandardSS 6.1WE 1WE 2EA Prerequisite 1EA Prerequisite 3IEQ Prerequisite 1

IEQ Prerequisite 2IEQ 1

IEQ 2

IEQ 3.2

IEQ 5

IEQ 6.2

IEQ 7.1

IEQ 7.2

IEQ 10

DescriptionStormwater ControlWater Efficient LandscapingInnovative Wastewater TechnologiesFundamental Commissioning of Building Energy SystemsEnhanced Commissioning

Minimum Indoor Air Quality Performance

Environmental Tobacco Smoke (ETS) ControlOutdoor Air Delivery Innovation

Increased Ventilation

Construction Indoor Air Quality Management Plan - Before Occupancy

Indoor Chemical and Pollution Control

Controllability of Systems - Thermal ComfortThermal Comfort - Design

Thermal Comfort - Ventilation

Mold Prevention

NC12-42Required

Required

Required

Required

1

1

1

1

1

1

1

N/A

School12-42Required

Required

Required

Required

1

1

1

1

1

1

1

1

CS12-42Required

Required

Required

Required

1

1

N/A

1

1

1

N/A

N/A

Credit Weighting (Points) byBuilding Classification

See more at www.dwyer-inst.com/leed/leed_profile.cfm

LEED® is a registered trademark of the U.S. Green Building Council.

VARIABLE-AIR-VOLUME APPLICATION ASK HOW WE CAN HELP YOU WITH LEEDHEATING & COOLING APPLICATIONPRODUCTS APPLIED FOR

HEATING & COOLING APPLICATION

BC-BAS Brochure:Layout 1 2/9/11 11:13 AM Page 2

BC-BAS

©Copyright 2010 Dwyer Instruments, Inc.

Printed in U.S.A. 12/10

DIRTY FILTER ALARMThe differential pressure loss across the filter is monitored.

• Products used: ADPS Pressure Switch and 616KD Differential Pressure Transmitter

FAN VALIDATIONProving a fan is operating can be done in several ways:

1. Monitor the differential pressure between upstream and downstream of the fan.

• Product used: ADPS Pressure Switch

2. Monitor the air flow or velocity exiting the fan.• Products used: DH, DHII, DH3, MS, AVU, VTT, 641 Transmitter or 616KD

Differential Pressure Transmitter

3. Monitor the current usage of the fan.• Product used: SCS Current Switch

DUCT STATIC PRESSUREA pressure transmitter is used with a static pressure tip or optional inherentstatic probe to monitor discharge or mixing air duct static pressures.

• Products used: MS Pressure Transmitter with A-302 Static Pressure Tip or MS with integral static pressure probe

DUCT HUMIDITY SENSORA humidity transmitter is inserted into the duct to monitor the zone dischargehumidity.

• Product used: RHP Humidity Transmitter

DUCT HUMIDITY/TEMPERATURE SENSORA dual humidity and temperature transmitter is inserted into the duct tomonitor the exhaust air humidity and temperature.

• Product used: RHP Humidity/Temperature Transmitter

DUCT TEMPERATURE SENSORA temperature sensor is inserted into the duct to monitor the supply air, mixair, and exhaust air temperature.

• Products used: TE-D Series Temperature Sensor or TE-A Averaging Temperature Sensor

FILTERA pleated filter offers better protection against dust and other airborneparticulate, protecting your HVAC equipment and helps clean the indoorenvironment.

• Product used: DF Pleated Filters

FROZEN COIL ALARMA differential pressure loss across the cooling coil indicates ice build up on thecoil.

• Products used: ADPS Pressure Switch or EDPS UL508 listed Pressure Switch

DWYER INSTRUMENTS, INC.P.O. Box 373

Michigan City, IN 46361-9986

Return Service Requested

PRODUCTS APPLIED FORAIR HANDLER APPLICATION AIR HANDLER APPLICATION

BC-BAS Brochure:Layout 1 2/9/11 11:12 AM Page 1

BC-BAS

©Copyright 2010 Dwyer Instruments, Inc.

Printed in U.S.A. 12/10

DIRTY FILTER ALARMThe differential pressure loss across the filter is monitored.

• Products used: ADPS Pressure Switch and 616KD Differential Pressure Transmitter

FAN VALIDATIONProving a fan is operating can be done in several ways:

1. Monitor the differential pressure between upstream and downstream of the fan.

• Product used: ADPS Pressure Switch

2. Monitor the air flow or velocity exiting the fan.• Products used: DH, DHII, DH3, MS, AVU, VTT, 641 Transmitter or 616KD

Differential Pressure Transmitter

3. Monitor the current usage of the fan.• Product used: SCS Current Switch

DUCT STATIC PRESSUREA pressure transmitter is used with a static pressure tip or optional inherentstatic probe to monitor discharge or mixing air duct static pressures.

• Products used: MS Pressure Transmitter with A-302 Static Pressure Tip or MS with integral static pressure probe

DUCT HUMIDITY SENSORA humidity transmitter is inserted into the duct to monitor the zone dischargehumidity.

• Product used: RHP Humidity Transmitter

DUCT HUMIDITY/TEMPERATURE SENSORA dual humidity and temperature transmitter is inserted into the duct tomonitor the exhaust air humidity and temperature.

• Product used: RHP Humidity/Temperature Transmitter

DUCT TEMPERATURE SENSORA temperature sensor is inserted into the duct to monitor the supply air, mixair, and exhaust air temperature.

• Products used: TE-D Series Temperature Sensor or TE-A Averaging Temperature Sensor

FILTERA pleated filter offers better protection against dust and other airborneparticulate, protecting your HVAC equipment and helps clean the indoorenvironment.

• Product used: DF Pleated Filters

FROZEN COIL ALARMA differential pressure loss across the cooling coil indicates ice build up on thecoil.

• Products used: ADPS Pressure Switch or EDPS UL508 listed Pressure Switch

DWYER INSTRUMENTS, INC.P.O. Box 373

Michigan City, IN 46361-9986

Return Service Requested

PRODUCTS APPLIED FORAIR HANDLER APPLICATION AIR HANDLER APPLICATION

BC-BAS Brochure:Layout 1 2/9/11 11:12 AM Page 1

ProductsLevel, Flowmeter, ValvesLevel, Flowmeter, ValvesLevel, Flowmeter, ValvesPressure Handheld, Velocity Handheld, Pitot Tube, Test EquipmentPressure Handheld, Velocity Handheld, Pitot Tube, Test EquipmentAir Velocity Transmitter, Air Flow Station, Pitot Tube, Differential Pressure Transmitter, Gage/Switch - Digital, Valve ActuatorDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure Gage CO2, Air Velocity Transmitter, Air Flow Station, Differential Pressure Transmitter, Gage/Switch - DigitalCO2, Air Velocity Transmitter, Air Flow Station, Differential Pressure Transmitter, Gage/Switch - DigitalDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure Gage, Humidity TransmitterDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure GageHumidity Transmitter, CO2, Differential PressureTransmitter, Zone Valve, Level IndicatorHumidity Transmitter, CO2 Transmitter, Differential PressureTransmitter, Zone Valve, Level Indicator Handheld Humidity, Handheld Pressure, Handheld Velocity, Humidity Transmitter, Differential Pressure Transmitter, CO2 TransmitterHumidity Transmitter, Water Detector

ROOM TEMPERATURE AND HUMIDITYA wall mounted temperature and humidity transmitter isplaced in the zone to monitor the zone conditions anddetermine demand.

• Product used: RHP-W Humidity and Temperature Transmitter

WATER FLOW CONTROLVAV systems can include heating coils of hot water thatthe air flows past. A zone valve is used to change theamount of hot water added to the heating coil. Zonesystems can include radiant heating systems. A zone valveis used to change the amount of hot water added to theradiator in the zone.

• Products used: ZV1 or ZV2 Zone Valves

WATER MIXING VALVEThree-way valves are used to mix return and supply water and chilled and hotwater together.

• Products used: GV Globe Valve with EVA Electric Actuator, or 3ABV Ball Valve with Electric Actuator

WATER TEMPERATURE MONITORA temperature sensor is inserted into the water pipeline to monitor thesystem supply, system return, condenser return, condenser supply, andboiler supply water temperature.

• Product used: TE-I RTD Temperature Sensor with Thermowell

OUTSIDE AIR SENSORA dual humidity and temperature transmitter is outside the building tomonitor the outdoor air humidity and temperature.

• Product used: RHP Humidity/Temperature Transmitter with optional RHRS radiation shield

PUMP VALIDATION/FLOW PROVINGProving a pump is operating can be done in several ways:

1. Monitor the differential pressure between upstream and downstream of the pump.

• Product used: DX Pressure Switch

2. Monitor the water flow exiting the pump.• Products used: FS-2, V8 or V7 Flow Switch

3. Monitor the current usage of the pump.• Product used: SCS Current Switch

4. Ensure proper differential pressure is created from sufficient flow through chiller.

• Product used: 629 Differential Pressure Transmitter

LEAK DETECTION/DRIP PAN MONITORA conductivity sensor is used to detect leaks of fluids around equipmentand valves or to detect full drip pans.

• Products used: WD or WD2 Leak Detectors

AIR VOLUME CONTROLThe amount of air added to the zone is controlled by opening andclosing the air duct via a damper with a damper actuator whichreceives a feedback signal from a differential pressuretransmitter.

• Products used: DDA Damper Actuator and 616KD Differential Pressure Transmitter

ROOM TEMPERATURE AND CARBON DIOXIDEThe amount of air flow to a zone is varied based on occupancy ina zone. The occupancy is determined by the concentration ofcarbon dioxide in the zone.

• Product used: CDT Carbon Dioxide and Temperature Transmitter

PRODUCTS APPLIED FORVARIABLE-AIR-VOLUME APPLICATION

The following chart shows where Dwyer Instruments products have the potential to help buildings acquire LEED®. TheLEED (Leadership in Energy and Environmental Design) Green Building Rating System is the nationally acceptedbenchmark for design, construction, and operation of high performance green buildings. Dwyer is proud to be amember of the U.S. Green Building Council and to be helping build a greener future. To find out more about LEED goto www.usgbc.org.

LEED StandardSS 6.1WE 1WE 2EA Prerequisite 1EA Prerequisite 3IEQ Prerequisite 1

IEQ Prerequisite 2IEQ 1

IEQ 2

IEQ 3.2

IEQ 5

IEQ 6.2

IEQ 7.1

IEQ 7.2

IEQ 10

DescriptionStormwater ControlWater Efficient LandscapingInnovative Wastewater TechnologiesFundamental Commissioning of Building Energy SystemsEnhanced Commissioning

Minimum Indoor Air Quality Performance

Environmental Tobacco Smoke (ETS) ControlOutdoor Air Delivery Innovation

Increased Ventilation

Construction Indoor Air Quality Management Plan - Before Occupancy

Indoor Chemical and Pollution Control

Controllability of Systems - Thermal ComfortThermal Comfort - Design

Thermal Comfort - Ventilation

Mold Prevention

NC12-42Required

Required

Required

Required

1

1

1

1

1

1

1

N/A

School12-42Required

Required

Required

Required

1

1

1

1

1

1

1

1

CS12-42Required

Required

Required

Required

1

1

N/A

1

1

1

N/A

N/A

Credit Weighting (Points) byBuilding Classification

See more at www.dwyer-inst.com/leed/leed_profile.cfm

LEED® is a registered trademark of the U.S. Green Building Council.

VARIABLE-AIR-VOLUME APPLICATION ASK HOW WE CAN HELP YOU WITH LEEDHEATING & COOLING APPLICATIONPRODUCTS APPLIED FOR

HEATING & COOLING APPLICATION

BC-BAS Brochure:Layout 1 2/9/11 11:13 AM Page 2

ProductsLevel, Flowmeter, ValvesLevel, Flowmeter, ValvesLevel, Flowmeter, ValvesPressure Handheld, Velocity Handheld, Pitot Tube, Test EquipmentPressure Handheld, Velocity Handheld, Pitot Tube, Test EquipmentAir Velocity Transmitter, Air Flow Station, Pitot Tube, Differential Pressure Transmitter, Gage/Switch - Digital, Valve ActuatorDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure Gage CO2, Air Velocity Transmitter, Air Flow Station, Differential Pressure Transmitter, Gage/Switch - DigitalCO2, Air Velocity Transmitter, Air Flow Station, Differential Pressure Transmitter, Gage/Switch - DigitalDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure Gage, Humidity TransmitterDifferential Pressure Transmitter, Differential Pressure Switch, Differential Pressure GageHumidity Transmitter, CO2, Differential PressureTransmitter, Zone Valve, Level IndicatorHumidity Transmitter, CO2 Transmitter, Differential PressureTransmitter, Zone Valve, Level Indicator Handheld Humidity, Handheld Pressure, Handheld Velocity, Humidity Transmitter, Differential Pressure Transmitter, CO2 TransmitterHumidity Transmitter, Water Detector

ROOM TEMPERATURE AND HUMIDITYA wall mounted temperature and humidity transmitter isplaced in the zone to monitor the zone conditions anddetermine demand.

• Product used: RHP-W Humidity and Temperature Transmitter

WATER FLOW CONTROLVAV systems can include heating coils of hot water thatthe air flows past. A zone valve is used to change theamount of hot water added to the heating coil. Zonesystems can include radiant heating systems. A zone valveis used to change the amount of hot water added to theradiator in the zone.

• Products used: ZV1 or ZV2 Zone Valves

WATER MIXING VALVEThree-way valves are used to mix return and supply water and chilled and hotwater together.

• Products used: GV Globe Valve with EVA Electric Actuator, or 3ABV Ball Valve with Electric Actuator

WATER TEMPERATURE MONITORA temperature sensor is inserted into the water pipeline to monitor thesystem supply, system return, condenser return, condenser supply, andboiler supply water temperature.

• Product used: TE-I RTD Temperature Sensor with Thermowell

OUTSIDE AIR SENSORA dual humidity and temperature transmitter is outside the building tomonitor the outdoor air humidity and temperature.

• Product used: RHP Humidity/Temperature Transmitter with optional RHRS radiation shield

PUMP VALIDATION/FLOW PROVINGProving a pump is operating can be done in several ways:

1. Monitor the differential pressure between upstream and downstream of the pump.

• Product used: DX Pressure Switch

2. Monitor the water flow exiting the pump.• Products used: FS-2, V8 or V7 Flow Switch

3. Monitor the current usage of the pump.• Product used: SCS Current Switch

4. Ensure proper differential pressure is created from sufficient flow through chiller.

• Product used: 629 Differential Pressure Transmitter

LEAK DETECTION/DRIP PAN MONITORA conductivity sensor is used to detect leaks of fluids around equipmentand valves or to detect full drip pans.

• Products used: WD or WD2 Leak Detectors

AIR VOLUME CONTROLThe amount of air added to the zone is controlled by opening andclosing the air duct via a damper with a damper actuator whichreceives a feedback signal from a differential pressuretransmitter.

• Products used: DDA Damper Actuator and 616KD Differential Pressure Transmitter

ROOM TEMPERATURE AND CARBON DIOXIDEThe amount of air flow to a zone is varied based on occupancy ina zone. The occupancy is determined by the concentration ofcarbon dioxide in the zone.

• Product used: CDT Carbon Dioxide and Temperature Transmitter

PRODUCTS APPLIED FORVARIABLE-AIR-VOLUME APPLICATION

The following chart shows where Dwyer Instruments products have the potential to help buildings acquire LEED®. TheLEED (Leadership in Energy and Environmental Design) Green Building Rating System is the nationally acceptedbenchmark for design, construction, and operation of high performance green buildings. Dwyer is proud to be amember of the U.S. Green Building Council and to be helping build a greener future. To find out more about LEED goto www.usgbc.org.

LEED StandardSS 6.1WE 1WE 2EA Prerequisite 1EA Prerequisite 3IEQ Prerequisite 1

IEQ Prerequisite 2IEQ 1

IEQ 2

IEQ 3.2

IEQ 5

IEQ 6.2

IEQ 7.1

IEQ 7.2

IEQ 10

DescriptionStormwater ControlWater Efficient LandscapingInnovative Wastewater TechnologiesFundamental Commissioning of Building Energy SystemsEnhanced Commissioning

Minimum Indoor Air Quality Performance

Environmental Tobacco Smoke (ETS) ControlOutdoor Air Delivery Innovation

Increased Ventilation

Construction Indoor Air Quality Management Plan - Before Occupancy

Indoor Chemical and Pollution Control

Controllability of Systems - Thermal ComfortThermal Comfort - Design

Thermal Comfort - Ventilation

Mold Prevention

NC12-42Required

Required

Required

Required

1

1

1

1

1

1

1

N/A

School12-42Required

Required

Required

Required

1

1

1

1

1

1

1

1

CS12-42Required

Required

Required

Required

1

1

N/A

1

1

1

N/A

N/A

Credit Weighting (Points) byBuilding Classification

See more at www.dwyer-inst.com/leed/leed_profile.cfm

LEED® is a registered trademark of the U.S. Green Building Council.

VARIABLE-AIR-VOLUME APPLICATION ASK HOW WE CAN HELP YOU WITH LEEDHEATING & COOLING APPLICATIONPRODUCTS APPLIED FOR

HEATING & COOLING APPLICATION

BC-BAS Brochure:Layout 1 2/9/11 11:13 AM Page 2

BC-BAS

©Copyright 2010 Dwyer Instruments, Inc.

Printed in U.S.A. 12/10

DIRTY FILTER ALARMThe differential pressure loss across the filter is monitored.

• Products used: ADPS Pressure Switch and 616KD Differential Pressure Transmitter

FAN VALIDATIONProving a fan is operating can be done in several ways:

1. Monitor the differential pressure between upstream and downstream of the fan.

• Product used: ADPS Pressure Switch

2. Monitor the air flow or velocity exiting the fan.• Products used: DH, DHII, DH3, MS, AVU, VTT, 641 Transmitter or 616KD

Differential Pressure Transmitter

3. Monitor the current usage of the fan.• Product used: SCS Current Switch

DUCT STATIC PRESSUREA pressure transmitter is used with a static pressure tip or optional inherentstatic probe to monitor discharge or mixing air duct static pressures.

• Products used: MS Pressure Transmitter with A-302 Static Pressure Tip or MS with integral static pressure probe

DUCT HUMIDITY SENSORA humidity transmitter is inserted into the duct to monitor the zone dischargehumidity.

• Product used: RHP Humidity Transmitter

DUCT HUMIDITY/TEMPERATURE SENSORA dual humidity and temperature transmitter is inserted into the duct tomonitor the exhaust air humidity and temperature.

• Product used: RHP Humidity/Temperature Transmitter

DUCT TEMPERATURE SENSORA temperature sensor is inserted into the duct to monitor the supply air, mixair, and exhaust air temperature.

• Products used: TE-D Series Temperature Sensor or TE-A Averaging Temperature Sensor

FILTERA pleated filter offers better protection against dust and other airborneparticulate, protecting your HVAC equipment and helps clean the indoorenvironment.

• Product used: DF Pleated Filters

FROZEN COIL ALARMA differential pressure loss across the cooling coil indicates ice build up on thecoil.

• Products used: ADPS Pressure Switch or EDPS UL508 listed Pressure Switch

DWYER INSTRUMENTS, INC.P.O. Box 373

Michigan City, IN 46361-9986

Return Service Requested

PRODUCTS APPLIED FORAIR HANDLER APPLICATION AIR HANDLER APPLICATION

BC-BAS Brochure:Layout 1 2/9/11 11:12 AM Page 1