BCA SECTION 'J' COMPLIANCE (J1) BUILDING FABRIC. ALL INSTALLED INSULATOIN TO COMPLY WITH AS4859.1 ALL SKY LIGHTS TO WAREHOUSE TO COMPLY WITH PART J1.4 AND TO MANUFACTURER'S SPECIFICATION ALL EXTERNAL OFFICE WALLS TO BE FITTED WITH WALL INSULATION WITH MIN. R1.0 VALUE AND IN ACCORDANCE WITH PART J1.5 OF BCA. (J2) EXTERNAL GLAZING. CONCRETE WALLS TO BE BATTENED OUT (20 TO 30mm GAP) LINED WITH 10mm PLASTERBOARD WALL AND INSULATED TO MIN. R1.0 VALUE INTERNAL WALL - NIL REQUIREMENT FIRST FLOOR OPEN TO FRESH AIR - PROVIDE R1.5 INSULATION FIRST FLOOR CLOSED UNDERSIDE - NIL REQUIREMENT ALL EXTERNAL OFFICE GLAZING TO BE SINGLE LEAF WITH GREY TINTING, 6.38mm THICKNESS GREY 40 COMFORTPLUS GLASS. U VALUE 3.6 AND SHGC VALUE 0.50 ALL EXTERNAL GLAZING TO BE IN ACCORDANCE WITH BCA SECTION 'J' AND AS1288-1999 AND AS2047 CONTRACTOR'S TO PROVIDE CERTIFICATE OF COMPLIANCE STATING THAT ALL WORKS COMPLIES WITH BCA VOLUME 1, 2007 PART J2. (J3) BUILDING SEALING ALL OPENINGS TO A BUILDING SUCH AS ROOF, WALLS, DOORS, WINDOWS AND SERVICE PENETRATIONS TO BE SEALED BY MEANS OF SEALER, CAULKING OR SIMILAR APPROVED (J4) AIR MOVEMENT N/A (J5) MECHANICAL VENTILATION & AIR CONDITIONING MECHANICAL VENTILATION AND AIR-CONDITIONING TO COMPLY WITH PART J5 OF BCA 2007. CONTRACTORS TO PROVIDE CERTIFICATE OF COMPLIANCE STATING AIR CONDITIONING AND MECHANICAL VENTILATION TO OFFICES AND TOILETS HAS BEEN COMPLY WITH BCA VOLUME 1, 2007 PART J5. (J6) ARTIFICIAL LIGHTING AND POWER ARTIFICIAL LIGHTING AND POWER TO COMPLY WITH PART J6 OF THE BCA 2007. CONTRACTOR'S TO PROVIDE CERTIFICATE OF COMPLIANCE STATING ALL LIGHTS AND POWER HAS BEEN INSTALLED IN ACCORDANCE TO PART J6.1 TO J6.6 AND J6 OF THE BCA. (J7) HOT WATER SUPPLY CONTRACTOR'S TO PROVIDE COMPLIANCE CERTIFICATE STATING HWS HAS BEEN INSTALLED IN ACCORDANCE WITH AS/NZS 3500 AND BCA VOLUME 1, 2007, PART J7 (J8) ACCESS FOR MAINTENANCE ALL SERVICES LOCATED IN THE ROOF MUST BE ACCESSIBLE WITH SUITABLE MEANS. ALL WORKS MUSH COMPLY WITH PART J8.0 TO J8.2 OF THE BCA CLIENT: LOT 45 EFFICIENT DRIVE TRUGANINA PROPOSED WAREHOUSE SITE: PROJECT: SCALE: AVC CONSTRUCTION PROJECT NO. ISSUE DATE 25.01.2017 AS SHOWN PTY. LTD. 6/469 KING STREET, WEST MELBOURNE 3003 T. (03) 9329 6691 F. (03) 9329 2015 e. [email protected] group DWG NO. AVC15250-A DATE JUL. 2015 REV. STATUS: BP-5 DATE DESCRIPTION No. APPROVAL REVISIONS DATE No. DEVELOPMENT

BCA SECTION 'J' COMPLIANCE...grey tinting, 6.38mm thickness grey 40 comfortplus glass. u value 3.6 and shgc value 0.50 all external glazing to be in accordance with bca section 'j

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: BCA SECTION 'J' COMPLIANCE...grey tinting, 6.38mm thickness grey 40 comfortplus glass. u value 3.6 and shgc value 0.50 all external glazing to be in accordance with bca section 'j

BCA SECTION 'J' COMPLIANCE

(J1) BUILDING FABRIC.ALL INSTALLED INSULATOIN TO COMPLY WITH AS4859.1ALL SKY LIGHTS TO WAREHOUSE TO COMPLY WITH PART J1.4 AND TO MANUFACTURER'S SPECIFICATION

ALL EXTERNAL OFFICE WALLS TO BE FITTED WITH WALLINSULATION WITH MIN. R1.0 VALUE AND IN ACCORDANCEWITH PART J1.5 OF BCA.

(J2) EXTERNAL GLAZING.

CONCRETE WALLS TO BE BATTENED OUT (20 TO 30mm GAP)LINED WITH 10mm PLASTERBOARD WALL AND INSULATEDTO MIN. R1.0 VALUE

INTERNAL WALL - NIL REQUIREMENT

FIRST FLOOR OPEN TO FRESH AIR - PROVIDE R1.5 INSULATION

FIRST FLOOR CLOSED UNDERSIDE - NIL REQUIREMENT

ALL EXTERNAL OFFICE GLAZING TO BE SINGLE LEAF WITHGREY TINTING, 6.38mm THICKNESS GREY 40 COMFORTPLUSGLASS. U VALUE 3.6 AND SHGC VALUE 0.50

ALL EXTERNAL GLAZING TO BE IN ACCORDANCE WITH BCASECTION 'J' AND AS1288-1999 AND AS2047

CONTRACTOR'S TO PROVIDE CERTIFICATE OF COMPLIANCESTATING THAT ALL WORKS COMPLIES WITH BCA VOLUME 1,2007 PART J2.

(J3) BUILDING SEALING

ALL OPENINGS TO A BUILDING SUCH AS ROOF, WALLS, DOORS,WINDOWS AND SERVICE PENETRATIONS TO BE SEALED BY MEANSOF SEALER, CAULKING OR SIMILAR APPROVED

(J4) AIR MOVEMENT

N/A

(J5) MECHANICAL VENTILATION & AIR CONDITIONING

MECHANICAL VENTILATION AND AIR-CONDITIONING TO COMPLY WITHPART J5 OF BCA 2007. CONTRACTORS TO PROVIDE CERTIFICATE OF COMPLIANCE STATING AIR CONDITIONING AND MECHANICAL VENTILATIONTO OFFICES AND TOILETS HAS BEEN COMPLY WITH BCA VOLUME 1, 2007 PART J5.

(J6) ARTIFICIAL LIGHTING AND POWER

ARTIFICIAL LIGHTING AND POWER TO COMPLY WITH PART J6 OF THE BCA 2007. CONTRACTOR'S TO PROVIDE CERTIFICATE OF COMPLIANCESTATING ALL LIGHTS AND POWER HAS BEEN INSTALLED IN ACCORDANCETO PART J6.1 TO J6.6 AND J6 OF THE BCA.

(J7) HOT WATER SUPPLY

CONTRACTOR'S TO PROVIDE COMPLIANCE CERTIFICATE STATINGHWS HAS BEEN INSTALLED IN ACCORDANCE WITH AS/NZS 3500 ANDBCA VOLUME 1, 2007, PART J7

(J8) ACCESS FOR MAINTENANCE

ALL SERVICES LOCATED IN THE ROOF MUST BE ACCESSIBLE WITHSUITABLE MEANS.

ALL WORKS MUSH COMPLY WITH PART J8.0 TO J8.2 OF THE BCA

CLIENT:

LOT 45 EFFICIENT DRIVETRUGANINA

PROPOSED WAREHOUSE

SITE:PROJECT:

SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE

25.01.2017 AS SHOWN

PTY. LTD.

6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]

group DWG NO.

AVC15250-A

DATE

JUL. 2015

REV. STATUS:

BP-5

DATEDESCRIPTIONNo. APPROVAL

REVISIONS

DATENo.

DEVELOPMENT

Page 2: BCA SECTION 'J' COMPLIANCE...grey tinting, 6.38mm thickness grey 40 comfortplus glass. u value 3.6 and shgc value 0.50 all external glazing to be in accordance with bca section 'j

25436

1635

062

0030

00

3000

1025

012

300

1190018986

1234 30886

55005000

1000

5000

4697

PROPOSEDWAREHOUSE

3000

2600

5835

1000

6400

4900

2600 2600 2400 2400 2600 2600

2600

1000

21620

1485

3

321201500147121

2555

0

2555

0

21685

47121

4990

1756

0

2690 10696

94°42' 32.12M

184°

42'

25.5

5M

4°42

'10

.70M

49°5

9'21

.11M

94°42' 47.12M

VOID49

00

150mm

DP 150m

m

DP

150m

m

DP

150m

m

DP 150m

m

DP 150m

m

DP

GROUND LEVEL

SITE COVERAGE

SITE AREA

OFFICE

WAREHOUSE

(GROUND & FIRST FL)TOTAL FLOOR AREA

FIRST FLOOR

TOTAL GROUND FLOOR

485 SQ.M.

OFFICE

1,093 SQ.M.

71 SQ.M.

556 SQ.M.

94 SQ.M.

650 SQ.M.

E.P

T.P

S.P

SE

SW

STREET FIRE HYDRANT

STORMWATER PIT

STORMWATER GRATE

ELECTRICAL PIT

SEWER PIT

TELSTRA PIT

STREET LIGHT POLE

S.SSTREET SIGNAGE

STORMWATER PIT (SIDE ENTRY)SW

EXISTING LEVEL

PROPOSED LEVEL24.11

E.PL ELECTRICAL POLE

EXISTING TREE TO BE RETAINED

EXISTING TREE TO BE REMOVED

2100MM HEIGHT - BLACK PLASTIC COATED CHAIN WIRE MESH FENCE

PROPOSED FENCING

2100MM HEIGHT - BLACK PAINTED STEEL PICKET FENCE

CARPARKING REQUIRE7 SPACES

@1.3/100 SQ.M

CARPARKING SPACESPROVIDED ON SITE 8 SPACES

CARPARKING +1 SPACESSURPLUS OR SHORTFALL

CAR PARKING ANALYSIS

(GROUND & FIRST FL)TOTAL FLOOR AREA

650 SQ.M.

SUBTRACT30.4 SQ.M.LOADING BAY

SUBTRACT44.6 SQ.M.STAIRCASE/VOID

TOTAL NET FLOOR AREA 555.29 SQ.M.

SUBTRACT19.71 SQ.M.

TOILETS

@1.4/100 SQ.M

CLIENT:

LOT 45 EFFICIENT DRIVETRUGANINA

PROPOSED WAREHOUSE

SITE:PROJECT:

SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE

25.01.2017 AS SHOWN

PTY. LTD.

6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]

group DWG NO.

AVC15250-A

DATE

JUL. 2015

REV. STATUS:

BP-5

DATEDESCRIPTIONNo. APPROVAL

REVISIONS

DATENo.

DEVELOPMENT

Page 3: BCA SECTION 'J' COMPLIANCE...grey tinting, 6.38mm thickness grey 40 comfortplus glass. u value 3.6 and shgc value 0.50 all external glazing to be in accordance with bca section 'j

1000

(TILE)

UP.

3 D

EG

. F

ALL

.047m

m T

RIM

DE

K H

I-T

EN

R

OO

FIN

G

3 D

EG

. F

ALL

.047m

m T

RIM

DE

K H

I-T

EN

R

OO

FIN

G

3 D

EG

. F

ALL

.047m

m T

RIM

DE

K H

I-T

EN

R

OO

FIN

G

3 D

EG

. F

ALL

.047m

m T

RIM

DE

K

HI-T

EN

R

OO

FIN

G

RIDGE LINE ABOVE

760MM WIDE FIBREGLASSROOFLIGHTS WITHSAFETY MESH UNDER

760MM WIDE FIBREGLASSROOFLIGHTS WITHSAFETY MESH UNDER

150mm

DP 150m

m

DP

150m

m

DP

150m

m

DP

150m

m

DP

150m

m

DP 150m

m

DP 150m

m

DP

900

900

VO

ID

REFER TO ENG. PLAN FOR MORE DETAILS

100mm THICK RC CONCRETE SLAB

SINK

6693

FRDG.

16

35

0

5450

150

18686

150

5525 6693 5913 6062

11750

30886

150

18986 11900

15

0

11

27

5

16

05

0

15

0

60

50

15

0

62

00

11

27

5

22

55

0

12

30

0

25136

150150

5913

5300

150

60626693 6693

25436

5525

30886

15

0

99

50

15

0

12

15

0

15

0

10

25

0

11

27

51

12

75

22

55

0

10

00

21

00

10

00

150

5700

W

920

ST

EE

L RO

OF

BE

AM

RE

FE

R T

O

EN

G. P

LAN

FO

R M

OR

E D

ET

AIL

920

T. H.B

870

920

920(TILE)

H.BT.

(TILE)

TOILET

LEGEND

EXIT

DISABLE

W

B

W.C DOORS

HINGES TO ALL

MUST BE PROVIDED

PROVIDE LIFT-OFF

NOTE:

OF DISPOSAL OF

ADEQUATE MEANS

NOTE:

FRL. WITH SOLID CORE

EXIT DOORS MUST BE

SANITARY TOWELS

NOTE:

ALL EXTERNAL WINDOW

DOOR AND SELF CLOSER

FIRE RATED TO 60/60/60

UNLESS ENCLOSED WITH

WHICH IS LOCATED BETWEEN

FACES A PERSON SEEKING

NO STORAGE UNDER STAIR

ACTION ON A SINGLE DEVICE

DOWNWARD ACTION OR PUSHING

EGRESS BY A SINGLE HAND

A KEY FROM THE SIDE THAT

0.9m-1.2m FROM THE FLOOR

NOTE:

READILY OPENABLE WITHOUT

ACCORDANCE WITH

AUSTRALIAN STANDARD

NOTE:

& BCA SECTION (J)

GLAZING TO BE

NOTE:

OUTSIDE AIR.

25 L/S DUCTED THRU

AIR-LOCK AT THE RATE OF

TO BE PROVIDED TO W.C &

MECHANICAL VENTILATION

SPECIFICATIONS REQUIRED PRIOR

TO INSTALLATION

AIR CONDITIONING TO ALL OFFICES

TO BE PROVIDED. TECHNICAL

NOTE:

CLIENT:

LOT 45 EFFICIENT DRIVETRUGANINA

PROPOSED WAREHOUSE

SITE:PROJECT:

SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE

25.01.2017 AS SHOWN

PTY. LTD.

6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]

group DWG NO.

AVC15250-A

DATE

JUL. 2015

REV. STATUS:

BP-5

DATEDESCRIPTIONNo. APPROVAL

REVISIONS

DATENo.

DEVELOPMENT

Page 4: BCA SECTION 'J' COMPLIANCE...grey tinting, 6.38mm thickness grey 40 comfortplus glass. u value 3.6 and shgc value 0.50 all external glazing to be in accordance with bca section 'j

(TILE)

UP.

150m

m

DP

900

900

VO

ID

SINK

FRDG.

1150 3360 3780

90150

5360 2600

90

8290

1000

2180

1000

1890

1000

2180

1000

150

3500

90

6360

150

150

3690

90

6170

150

10250

400

5300

1000

2100

1000

1200

150

4070

90

1200

90

5600

90

1670

90

2000

150

150

4750

90

4990

W

920

920

T. H.B

870

920

920

90

900

(TILE)

H.BT.

(TILE)

530

530

1245

4265

5000

5405

VO

IDDWN.

T.S

INK

ROOF HATCH900x900

6420

300

3530

1000

2100

1000

1200

125

15300

125

15550

300

7020

6210

5910

125

5785

90

12004585

7503835

6000

5850

125

3535

90

2100

150

125

5725

150

6000

125

8775

1200

90

900

90

900

90

3255

125

125

5025

4950

90

900

90

900

90

3255

125

15550

300

W

870

870

475

195

6570

150m

m

DP

150m

m

DP

150m

m

DP

150m

m

DP

600Wx200D BOX GUTTER

600Wx200D BOX GUTTER

600Wx200D BOX GUTTER

ROOF HATCH900x900

3 D

EG

. F

AL

L

.0

47

mm

T

RIM

DE

K H

I-T

EN

R

OO

FIN

G

3 D

EG

. F

AL

L

.0

47

mm

T

RIM

DE

K H

I-T

EN

R

OO

FIN

G

3 D

EG

. F

AL

L

.0

47

mm

T

RIM

DE

K H

I-T

EN

R

OO

FIN

G

3 D

EG

. F

AL

L

.0

47

mm

T

RIM

DE

K H

I-T

EN

R

OO

FIN

G

3 D

EG

. F

AL

L

.0

47

mm

T

RIM

DE

K H

I-T

EN

R

OO

FIN

G

3 D

EG

. F

AL

L

.0

47

mm

T

RIM

DE

K

HI-T

EN

R

OO

FIN

G

3 D

EG

. F

AL

L

.0

47

mm

T

RIM

DE

K

HI-T

EN

R

OO

FIN

G

3 D

EG

. F

AL

L

.0

47

mm

T

RIM

DE

K

HI-T

EN

R

OO

FIN

G

760MM WIDE FIBREGLASSROOFLIGHTS WITHSAFETY MESH UNDER

760MM WIDE FIBREGLASSROOFLIGHTS WITHSAFETY MESH UNDER

760MM WIDE FIBREGLASSROOFLIGHTS WITHSAFETY MESH UNDER

REQUIREMENTS

AS PER BCA SECTION 'J'

PROVIDE ROOF INSULATION

150m

m

DP 150m

m

DP

150m

m

DP

150m

m

DP150m

m

DP

TOILET

LEGEND

EXIT

DISABLE

W

B

W.C DOORS

HINGES TO ALL

MUST BE PROVIDED

PROVIDE LIFT-OFF

NOTE:

OF DISPOSAL OF

ADEQUATE MEANS

NOTE:

FRL. WITH SOLID CORE

EXIT DOORS MUST BE

SANITARY TOWELS

NOTE:

ALL EXTERNAL WINDOW

DOOR AND SELF CLOSER

FIRE RATED TO 60/60/60

UNLESS ENCLOSED WITH

WHICH IS LOCATED BETWEEN

FACES A PERSON SEEKING

NO STORAGE UNDER STAIR

ACTION ON A SINGLE DEVICE

DOWNWARD ACTION OR PUSHING

EGRESS BY A SINGLE HAND

A KEY FROM THE SIDE THAT

0.9m-1.2m FROM THE FLOOR

NOTE:

READILY OPENABLE WITHOUT

ACCORDANCE WITH

AUSTRALIAN STANDARD

NOTE:

& BCA SECTION (J)

GLAZING TO BE

NOTE:

OUTSIDE AIR.

25 L/S DUCTED THRU

AIR-LOCK AT THE RATE OF

TO BE PROVIDED TO W.C &

MECHANICAL VENTILATION

SPECIFICATIONS REQUIRED PRIOR

TO INSTALLATION

AIR CONDITIONING TO ALL OFFICES

TO BE PROVIDED. TECHNICAL

NOTE:

1. CONTRACTOR SHALL HAVE A PLUMBER'S LICENSE WITH WORKMANSHIP WARRANTY AS PER THE PLUMBING INDUSTRY BOARD & MINISTERIAL ACT REQUIREMENTS.

ALL STORMWATER

4. ALL PIPE MATERIALS SHALL BE D.W.V (SEWER GRADE) AND NOMINATED SIZES USED IN

5. CRUSHED ROCK CLASS 2 - 20mm AGGREGATE SHALL BE USED FOR ALL TRENCH BEDDING

9. A ROAD OPENING PERMIT SHALL BE OBTAINED BY CONTRACTOR PRIOR TO WORKS COMMENCING.8. STAND-OFF BRACKETS SHALL BE USED AT 2-0m INTERVALS FOR ALL DOWNPIPES.

6. ALL TRENCHES TO BE BACKFILLED WITH CLASS 2-20mm AGGREGATE IN COMPACTED LAYERS.

2. ALL STORMWATER WORKS SHALL BE CARRIED OUT IN ACCORDANCE WITH AUSTRALIAN

7. ALL GRATED TRENCHES SHALL BE OF HEAVY DUTY MATERIAL.

3. ALL SURFACE R.L'S AND INVERT PIPES LEVELS SHALL BE VERIFIED BY THE CONTRACTOR

ACCORDANCE WITH THE HYDRAULIC PLAN PROVIDED.

OF DISCHARGETO LEGAL POINT

NOTE:

TO BE CONNECTED

ENERGY EFFICIENCY REQUIREMENTS

STANDARDS AS.3500 3.2/1998.

PRIOR TO WORKS COMMENCING

WALLS - EXTERNAL

INSULATED TO R3.2ROOF / CEILING

BUILDING FABRIC 'R' RATING

LINED WITH PLASTER BOARD

OUT (20mm TO 35mm GAP)

CONCRETE WALLS BATTENED

NIL REQUIREMENTS

(OPEN TO UNDERSIDE)

WALLS - INTERNAL

INSULATED TO R1.0

GLAZING NEEDS TO COMPLY

FIRST FLOOR INSULATED R1.5

FIRST FLOOR

1, 2007.

(CLOSED TO UNDERSIDE)

NIL REQUIREMENTS

EXTERNAL GLAZING

VOL. 1, 2007 PART J2"

CERTIFICATE OF COMPLIANCE

GLAZIER TO PROVIDE

STATING THAT "EXTERNAL

WITH SECTION 'J' OF BCA VOL.

ACCESSIBLE WITH SUITABLE

GLAZING COMPLIES WITH BCA

CERTIFICATE OF COMPLIANCE

IN THE ROOF MUST BE

AIR CONDITIONING

CONDITIONING PROVIDES

STATING THAT "AIR

PLUMBER TO PROVIDE

VENTILATION TO THE OFFICES

MEANS.

LIGHTS & POWER HAS BEEN

LIGHTS & POWER HAS BEEN

VENTILATION TO THE OFFICES

PROVIDED TO COMPLY WITH

BCA VOL. 1, 2007 PART J5"

AS REQUIRE REFER TO NATURAL

PLUMBER TO PROVIDE

CERTIFICATE OF COMPLIANCE

STATING THAT "HWS

COMPLIES WITH AS/NZS

3500 AND BCA VOL. 1, 2007

PART J7

HOT WATER SUPPLY

ALL SERVICES LOCATEDACCESS FOR

MAINTENANCE

PROVIDE ROOF VENTILATION

VENTILATION ANANYSIS

NOTE:

CLIENT:

LOT 45 EFFICIENT DRIVETRUGANINA

PROPOSED WAREHOUSE

SITE:PROJECT:

SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE

25.01.2017 AS SHOWN

PTY. LTD.

6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]

group DWG NO.

AVC15250-A

DATE

JUL. 2015

REV. STATUS:

BP-5

DATEDESCRIPTIONNo. APPROVAL

REVISIONS

DATENo.

DEVELOPMENT

Page 5: BCA SECTION 'J' COMPLIANCE...grey tinting, 6.38mm thickness grey 40 comfortplus glass. u value 3.6 and shgc value 0.50 all external glazing to be in accordance with bca section 'j

F.L

80

00

30

00

N.G.L

C.L

F.L

C.L3

00

06

00

14

00

PARAPET

4

0

0

0

W

x

4

8

0

0

H

R

O

L

L

E

R

D

O

O

R

SCALE 1:100

WEST ELEVATIONA A1

A1A1C C

F

D D D D D

E E EB

B

B

D D

F.L

80

00

30

00

N.G.L

C.L

F.L

C.L

30

00

60

01

40

0

PARAPET

4

0

0

0

W

x

4

8

0

0

H

R

O

L

L

E

R

D

O

O

R

SCALE 1:100

NORTH ELEVATIONA A1 A A

A1 A1 A1A A C

B

B

B

D D

E

A1

D

D

F

F.L

80

00

30

00

N.G.L

C.L

F.L

C.L

30

00

60

01

40

0

PARAPET

SCALE 1:100

EAST ELEVATION

A1 A1 A1 A1

F.L

80

00

30

00

N.G.L

C.L

F.L

C.L

30

00

60

01

40

0

PARAPET

SCALE 1:100

SOUTH ELEVATION

A1 A1 A1

A

D D

E

C

A1

A1

A1

C

MATERIAL & COLOUR FINISHES SCHEDULE

A1

LEGEND

A

EWOODLAND GREY

COLOURBOND

BLACK

DARK GREY TINTED

COLOUR

DOOR

DSPANDREL GLAZING

COLOURBOND ROLLER

TO COMPLY WITH ENERGY RATINGTINTED WINDOW GLAZING

EXTERNAL MATERIAL

CONCRETE WALLTEXTURE PAINTED

TEXTURE PAINTEDCONCRETE WALL

DULUX, SMOKEBUSH

B

F

ALUMINIUM CLADDING

COLOURBOND CLADDING

SILVER

BLACK

DULUX, HOMEBUSH

COLOURBOND

CLIENT:

LOT 45 EFFICIENT DRIVETRUGANINA

PROPOSED WAREHOUSE

SITE:PROJECT:

SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE

25.01.2017 AS SHOWN

PTY. LTD.

6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]

group DWG NO.

AVC15250-A

DATE

JUL. 2015

REV. STATUS:

BP-5

DATEDESCRIPTIONNo. APPROVAL

REVISIONS

DATENo.

DEVELOPMENT

Page 6: BCA SECTION 'J' COMPLIANCE...grey tinting, 6.38mm thickness grey 40 comfortplus glass. u value 3.6 and shgc value 0.50 all external glazing to be in accordance with bca section 'j

80

00

30

00

30

00

60

01

40

0

PARAPET

C.L

F.L

C.L

F.L

N.G.L

AS REQUIREDPROVIDE CAPPING3 DEG. FALL

.047mm TRIMDEK HI-TEN ROOFING

STEEL MESH SUPPORTOVER ALUMINIUM SISALATION

PROVIDE FLASHING& CAPPINGAS REQUIRED

LINE OF WALL BEYOND

REFER TO ENG DWG FOR DETAILSROOF BEAM & PURLINS

ON STEEL BRACKETS, FLASHING & CAPPINGAS REQUIRED

600Wx150D BOX GUTTER

REFER TO ENG. DETAILSRC FOOTINGS & SLAB

REFER TO ENG. DETAILSRC FOOTINGS & SLAB

CONCRETE150mm THICK

PANEL WALL

150mm DIA DOWNPIPE

CONCRETE150mm THICK

PANEL WALL

150mm DIA DOWNPIPE

REFER TO ENG DWG FOR DETAILSROOF BEAM & PURLINS

SECTION A-ASCALE 1:100

PROVIDE FLASHING& CAPPINGAS REQUIRED

8000

3000

3000

600

1400

PARAPET

C.L

F.L

C.L

F.L

N.G.L

16. LANDING

1.

20. LANDING

AS REQUIRED

PROVIDE FLASHING& CAPPING

REFER TO ENG. PLANSTEEL FASCIA TRUSS

FOR FURTHER DETAILS

TO BCA SECTION (J) &AS STANDARDS

ALUMINIUM FRAMED WINDOW IN ACCORDANCE

ALUMINIUM FRAMEDSPANDREL GLAZING

COLOURBOND CLADDING REFER TO MATERIAL & FINISHES SCHEDULE

FLASHING & CAPPING AS REQUIREDON STEEL BRACKETS, 600Wx150D BOX GUTTER

AS REQUIREDPROVIDE CAPPING

LINE OF WALL BEYOND

OVER ALUMINIUM SISALATION0.47mm TRIMDEK HI-TEN ROOFING3 DEG. FALL

STEEL MESH SUPPORT BLANKET TO OFFICE ROOF AREA PROVIDE 50mm INSULATION

PROVIDE R3.2 ROOFINSULATION TO ALL OFFICEROOF AREAS FLASHING & CAPPING

ON STEEL BRACKETS, 600Wx150D BOX GUTTER

AS REQUIRED

AS REQUIRED

PROVIDE FLASHING& CAPPING

COLOURBOND CLADDING REFER TO MATERIAL & FINISHES SCHEDULE

PROVIDE WATERPROOFSILICONE

REFER TO ENG. PLANSTEEL FASCIA TRUSS

FOR FURTHER DETAILS

TO BCA SECTION (J) &AS STANDARDS

ALUMINIUM FRAMED WINDOW IN ACCORDANCE

ALUMINIUM CLADDING REFER TO MATERIAL & FINISHES SCHEDULE

FEATURE BOXING

PROVIDE WATERPROOFSILICONE

SPANDREL GLAZINGALUMINIUM FRAMED

ALUMINIUM CLADDING REFER TO MATERIAL & FINISHES SCHEDULE

FEATURE BOXING

CONCRETE PANEL150mm THICK

REFER TO ENG. DETAILSRC FOOTINGS & SLABREFER TO ENG. DETAILS

RC FOOTINGS & SLAB

90x45 MGP10 TIMBER

WITH PAINTED 10mm THICK P'BOARD

FRAME WALL @ 450 CTRS.

STEEL BEAM & PURLIN

DETAILSREFER TO ENG. DESIGN &

90x45 MGP10 TIMBER

WITH PAINTED 10mm THICK P'BOARD

FRAME WALL @ 450 CTRS.

1000

WALL @ 450 CTRS. WITH BOTH90x45 MGP10 TIMBER FRAMED

AT 1000 HIGH FROM F.F.L

SIDE P'BOARD PAINTED FINISH

T&G TIMBER19mm THICK

FLOOR BOARDST&G TIMBER19mm THICK

FLOOR BOARDS

PROVIDE COLOURBONDSOFFIT LINING TO UNDERSIDEOF CARPARK

CONCRETE PANEL150mm THICK

MANUFACTURES SPECIFICATIONS DETAILS

SUSPENDED CEILING TO19mm PLASTERBOARD

SECTION B-BSCALE 1:50

8000

3000

3000

600

1400

PARAPET

C.L

F.L

C.L

F.L

N.G.L

AS REQUIRED

PROVIDE FLASHING& CAPPING

REFER TO ENG. PLANSTEEL FASCIA TRUSS

FOR FURTHER DETAILS

COLOURBOND CLADDING REFER TO MATERIAL & FINISHES SCHEDULE

TO BCA SECTION (J) &AS STANDARDS

ALUMINIUM FRAMED WINDOW IN ACCORDANCE

ALUMINIUM FRAMEDSPANDREL GLAZING

STEEL BEAM & PURLIN

DETAILSREFER TO ENG. DESIGN &

MANUFACTURES SPECIFICATIONS DETAILS

SUSPENDED CEILING TO19mm PLASTERBOARD

19mm THICK T&G TIMBERFLOOR BOARDS

90x45 MGP10 TIMBER

WITH PAINTED 10mm THICK P'BOARD

FRAME WALL @ 450 CTRS.

1000

CONCRETE PANEL150mm THICK

REFER TO ENG. DETAILSRC FOOTINGS & SLAB

OVER ALUMINIUM SISALATION0.47mm TRIMDEK HI-TEN ROOFING3 DEG. FALL

STEEL MESH SUPPORT

PROVIDE R3.2 ROOFINSULATION TO ALL OFFICEROOF AREAS

BLANKET TO OFFICE ROOF AREA PROVIDE 50mm INSULATION

LINE OF WALL BEYOND

SECTION C-CSCALE 1:50

CLIENT:

LOT 45 EFFICIENT DRIVETRUGANINA

PROPOSED WAREHOUSE

SITE:PROJECT:

SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE

25.01.2017 AS SHOWN

PTY. LTD.

6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]

group DWG NO.

AVC15250-A

DATE

JUL. 2015

REV. STATUS:

BP-5

DATEDESCRIPTIONNo. APPROVAL

REVISIONS

DATENo.

DEVELOPMENT

Page 7: BCA SECTION 'J' COMPLIANCE...grey tinting, 6.38mm thickness grey 40 comfortplus glass. u value 3.6 and shgc value 0.50 all external glazing to be in accordance with bca section 'j

WITH LAMINEX

ABOVE BENCH TOP150H TILEPROVIDE

580 50530

600

TYPICAL KITCHEN CABINET

BENCH TOPBENCH TOP

FINISH TO DOOR

SELECTED 16MM

AND CABINET

THICK MDF OVER

WITH

FINISH

20mm

LAMINEX

SELCTED

BY OWNER

PLUMBING

MDF OVER

FIXTURES

SELECTED

900

SCALE 1:50SCALE 1:50TYPICAL VANITY UNIT

THICK MDF OVER

380

900

50

150

750

FINISH TO DOOR

450

430

WITH LAMINEX

SELECTED 16MM

BY OWNER

SELCTED AND CABINET

PLUMBINGSELECTED

20mm

FIXTURES

LAMINEXWITH MDF OVER

150H TILE

FINISH

PROVIDE

EQ

730

580

ABOVE BENCH TOP

EQ

EQ

EQ

150

THICK MDF OVER

TYPICAL CABINET ELEVATION

SELECTED 16MM

FINISH TO DOOR

1600

PLUMBING

BY OWNERFIXTURES

SELECTEDWITH LAMINEX

AND CABINET

SCALE 1:50

LAMINEX

150H TILE

SELCTED

ABOVE BENCH TOP

PROVIDE

WITH

FINISHBENCH TOP

20mm MDF OVER

150

630

EQ 150

120

900

EQ

EQ

EQEQEQ EQ

616

2216

UP.

VO

ID

901200

90

4950

120090

1290

1200750

3750

1200

SELECTED STEEL HANDRAILREFER TO MANUFACTURER'SFOR FURTHER DETAILS

SELECTED TIMBER STRINGER,TREAD AND RISER

TACTILE GROUND SURFACE

INDICATOR MUST BE PROVIDED

IN ACCORDANCE WITH AS 1428.4

SCALE 1:50

VO

ID

DWN.

SCALE 1:50

1200

750 1200

1950

3750

1200

4950

90

5040

1200

3750

1200

9036

6090

750

120090

660

1290660

3750

1290

SELECTED STEEL HANDRAIL REFERTO MANUFACTURER'S FOR FURTHER DETAILS

SELECTED TIMBER STRINGER, TREAD AND RISER

TACTILE GROUND SURFACE

INDICATOR MUST BE PROVIDED

IN ACCORDANCE WITH AS 1428.4

16. LANDING

1.

20. LANDING

600

3000

3600

F.L

C.L

F.L

1000

900

NOTE:

TIMBER STAIR REFER TO

MANUFACTURER'S FOR

FURTHER DETAILS &

INSTALLATION

SELECTED TIMBER STRINGER,TREAD AND RISER

TIMBER FRAMED BALUSTRADEWALL @ 1000H.

SELECTED STEEL HANDRAILREFER TO MANUFACTURER'SFOR FURTHER DETAILS

TIMBER FRAMED BALUSTRADEWALL @ 1000H.

810

920

450 - 460

1900 MIN

700

MIN

800

MIN

300

MIN

1450

MIN

330

MIN

2300

MIN

425 MIN530 MIN

850 MIN

450 MIN

1400

MIN

1400 MIN 300 250

425

50375

684 90

0

70050 850

890 170

900

MA

X

350 MIN

125 - 150

425 MIN80

0 -

830

900

- 10

001850

MIN

PLAN

870

65080

040

0

400

610-660

200

460

400

50 50

SCALE 1:50AMBULANT DISABILITIES TOILET

900

PLAN ELEVATION

38MM DIA. STAINLESS

FOR FIXING DETAILS

STEEL GRABRAIL. REFER SAFETY RAILS AUSTRALIS P/L

610

- 66

090

0

CIRCULATION SPACE(DOOR MUST NOT INTRUDE)

STANDARD PROJECTION FOR WC

900

460

- 48

0

300MAX

MAX.

HAND RAIL

STRINGER

STRINGER

BA

LUS

TR

AD

E

BA

LUS

TR

AD

E

GOING RIS

ER

CLIENT:

LOT 45 EFFICIENT DRIVETRUGANINA

PROPOSED WAREHOUSE

SITE:PROJECT:

SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE

25.01.2017 AS SHOWN

PTY. LTD.

6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]

group DWG NO.

AVC15250-A

DATE

JUL. 2015

REV. STATUS:

BP-5

DATEDESCRIPTIONNo. APPROVAL

REVISIONS

DATENo.

DEVELOPMENT

Page 8: BCA SECTION 'J' COMPLIANCE...grey tinting, 6.38mm thickness grey 40 comfortplus glass. u value 3.6 and shgc value 0.50 all external glazing to be in accordance with bca section 'j

32 AMPS 3 PHASE OUTLETS

ELECTRICAL LEGEND

MECHANICAL EXAUST FAN

HIGH BAY 400 WATT METAL HALIDE FITTING TO BE

SELECTED LED DOWN LIGHTS

80 WATT METAL HALIDE WALL MOUNTED

TELEVISION

TELEPHONE

SWITCHED IN PAIRS

WITH WIRE GUARD 1200x300 (T5-1x28W)

EXIT SIGNS

SWITCHBOARD

EMERGENCY LIGHTING

1x36W MAINTAINED)

1 x BATTEN FLUORESCENT CEILING MOUNTED

T-BAR TROFFER FLUORESCENT RECESSED CEILING 1200x300 (T5-2x28W) WITH DIFFUSER COVER

WARE HOUSE AREA (BT136NWG 1x36W

STAIRWELLS AREA (BT218MPR 2x18W)

(2x18W QUICKFIT EXIT, SUSTAINED,150mm LETTERING, NI-CAD BATTERIES)

CAT 5 DATA CABLE

DOUBLE GPO

EXTERNAL SINGLE GPO

PH3

LEGEND

CLIENT:

LOT 45 EFFICIENT DRIVETRUGANINA

PROPOSED WAREHOUSE

SITE:PROJECT:

SCALE:AVC CONSTRUCTION PROJECT NO.ISSUE DATE

25.01.2017 AS SHOWN

PTY. LTD.

6/469 KING STREET, WEST MELBOURNE 3003T. (03) 9329 6691 F. (03) 9329 2015e. [email protected]

group DWG NO.

AVC15250-A

DATE

JUL. 2015

REV. STATUS:

BP-5

DATEDESCRIPTIONNo. APPROVAL

REVISIONS

DATENo.

DEVELOPMENT