BE1-11DIGITAL PROTECTIVE RELAYS

APPLICATION GUIDE

MULTIFUNCTION FLEXIBLE SOLUTIONS FOR EASY PROTECTION, CONTROL, MONITORING AND METERING

Page 2: BE1-11 - Generator control and protection systems€¦ ·  · 2013-05-17BE1-CDS240 is available. BE1-11i BE1-11g ... 47 50 51 59 60 27 32 43 46 47 48 49TC ... singaporeinfo@basler.com

BE1-11 DIGITAL PROTECTIVE RELAYSFOR RETROFIT AND NEW APPLICATIONS

KEEP CONTROL OF YOUR SYSTEM WITH BE1-11 EASY SETTINGS

The BE1-11 multifunction numeric relays are designed with many features to address reliability issues that arise due to the over complexity of programming.

Correctly setting a numeric relay has never been easier than with the BE1-11 family of relays. With BESTspace™ files, multiple BESTlogicTMPlus pre-programmed logic schemes and associated application notes, you can be confident your relay is set correctly.

Visitwww.basler.com

for technical resources.

HARDWARE

H1 Case(Half rack) J case

Size(mm)

W: 266.7H: 88.65

D: 232.92

W: 177.8H: 231.65D: 200.91

Case Fully drawout

Removable plug

Contact outputs

5+1

watchdog

8+1

watchdog

Digital inputs 4 7

CTinputs 4 4 or 8

VTinputs 4 4

User- configurable indicators

0 7

GENERATOR TRANSFORMER INTERTIESUBSTATION,

FEEDER,INDUSTRIAL PLANT

MOTOR

BE1-11g

Generator protection with optional autosynchronizer.

BE1-11t

2-winding transformer differential including extensive frequency protection.

For 3 or 4 windings, BE1-CDS240 is available.

BE1-11iBE1-11gMeets IEEE 1547-2003 Intertie Protection Standard.

Protection at the point of common coupling (PCC) between non utility distributed generation and the electric utility.

BE1-11fBE1-11iDirectional / non directional overcurrent,

Feeder management,

Load-shedding,

Recloser.

BE1-11m

Motor protection, control and management.

Options available on each BE1-11 relay:

BE1-11g specific features BE1-11t specific features BE1-11i specific features BE1-11f specific features BE1-11m specific features

M

Ethernet Modbus DNP3 IEC 61850SEF49 RTD

00 Standard feature 00 Optional feature

25A2421 25

433227 40 46

47 50 51 6059

BF6764G62

78V 78OOS 81

86 87* 87N* 101

462724 43 47

5150 5951TF

6260 BF67 81

86 87 87N 101

322524 27 43

101

4746 50 5951

6260 67 BF

8678V 8179

432725 32 46

6762 BF 8179

10186

47 50 51 6059

463227 43

47

101

49TC48

51

50

5955 60

66

62

8781BF 86

37

H Case

J Case

IEC 61850 available for all the BE1-11 family

*Options only available in J case. Only available in J case. Only available in J case.

Page 3: BE1-11 - Generator control and protection systems€¦ ·  · 2013-05-17BE1-CDS240 is available. BE1-11i BE1-11g ... 47 50 51 59 60 27 32 43 46 47 48 49TC ... singaporeinfo@basler.com

FLY_

APP

GUI_EN

_V1

BE1-11 DEVICE FUNCTIONS

*P = Programmable by logic FUNCTIONS BE1-11g BE1-11i BE1-11m BE1-11t BE1-11f

Distance 21 ■

Overexcitation - Volts per Hertz 24 ■ ■ ■

Sync Check 25 ■ ■ ■

Autosynchronizer 25A Option

Sync Check - Voltage Monitor 25VM ■ ■ ■

Undervoltage 27P ■ ■ ■ ■ ■

100% Stator Earth Fault with 3rd Harmonic Undervoltage 64G100 ■ ■ ■ ■

Directional Power 32 ■ ■ ■ Option

Undercurrent or Underpower 37 ■

Loss of Excitation (Offset Var Flow Algorithm, Dual Offset Mho Characteristic) 40Q/40Z ■

Negative Sequence Overcurrent 46 ■ ■ ■ ■ ■

Negative Sequence Overvoltage 47 ■ ■ ■ ■ ■

Incomplete Sequence 48 ■

Thermal Curve 49TC ■

Temperature Protection 49RTD Option Option Option Option Option

Instantaneous Overcurrent (Phase, Neutral or Ground, Negative Sequence) 50P/N/Q ■ ■ ■ ■ ■

Inadvertent Energizing 50/27 P*

Inverse Time Overcurrent (Phase, Neutral or Ground, Negative Sequence) 51P/N/Q ■ ■ ■ ■ ■

Time Overcurrent with Voltage Control / Restraint 51/27C, 51/27R ■ ■ ■ ■ ■

Transformer Monitor 51TF ■

Breaker Failure BF ■ ■ ■ ■ ■

Power-Factor (Motor, Out of Step) 55 ■

Phase Overvoltage 59P ■ ■ ■ ■ ■

Residual Overvoltage 59N ■ ■ ■ ■ ■

Fuse Loss 60FL ■ ■ ■ ■ ■

Current Transformer Supervision CTS P*

Logic Timer 62 ■ ■ ■ ■ ■

Starts per Time Interval, Restart Inhibit 66 ■

Directional Overcurrent (Phase, Neutral or Ground, Negative Sequence) 67P/N/Q ■ ■ ■ ■

Out of Step 78OOS ■

Vector Jump 78V ■ ■

AC Reclosing 79 ■ ■

(Over, Under, ROC) Frequency 81 ■ ■ ■ ■ ■

Lock Out 86 ■ ■ ■ ■ ■

Current Differential 87 Option Option ■

Neutral Differential 87ND Option ■

(Sensitive Earth Fault) SEF Option Option Option Option Option

(Webpage Interface) BESTnetTMPlus - Ethernet Option Option Option Option Option

ModbusTM Option Option Option Option Option

DNP3 Option Option Option Option Option

IEC 61850 Option Option Option Option Option

www.basler.com

Suzhou, P.R. ChinaTel.: +86 512 8227 [email protected]

Wasselonne, FranceTel.: +33 3 88 87 10 [email protected]

Worldwide HeadquartersHighland, Illinois USATel.: +1 618 654 [email protected]

SingaporeTel.: +65 68 44 [email protected]

For more information about BE1-11 relays, please visit our download section: www.basler.com

Basler Electric offers a standard warranty of seven years for all BE1-11 relays.