  • SALIENT FEATURES OF IS:13920 - 1993.CODE OF PRACTICE FOR DUCTILE DETAILING OF RC STRUCTURES

    SUBJECTED TO SEISMIC FORCES.

    BEAM DESIGN:

    DESCRIPTION

    1 Ductile detailing is a must for structures in Zone IV & V. However it should also

    be followed in zone III, when Importance factor is > 1.0 OR Structure is > 5.0 Storey high OR the structure is industrial in nature.

    2 Minimum longitudinal reinforcement on any face/section shall be :

    0.24 * sqrt (fck)/fy

    3 The factored axial stress shall not be > 0.1 fck, else the beam should be designed as column.

    4 B/D > 0.30 preferably.

    5 B should not be < 200 MM.

    6 The maximum steel ratio should not be > 2.5 % per face.

    7 Beam should not be a DEEP beam.

    8 +ve reinforcement should not be < 50 % of -ve steel at that joint.

    9 Minimum steel at any section face shall not be < 25 % of maximum -ve steel at any joint.

    10 Re-distribution of support moments are not allowed for seismic moments at

    joints.

    11 Development length {Ld} = Ld + 10 x at end joints of column/beam.

    12 Top & bottom reinforcements shall be continuous at column joints.

    13 All links shall be closed type, having a 135 hook with a 10 extension, but

    not less than 75 mm at each end.

    14 The longitudinal bars shall be spliced, only if links are provided over the entire splice length at spacing not > 150 MM.

    15 All splice shall have Ld in tension.

    16 Lap splice shall not be at :

    Column Joints.2 x d from column face.Within 0.25 x span.

    17 Not > 50 % of bars shall be spliced at any section.

    18 The Minimum link shall be 6 MM for span < 5.0 M.Use 8 MM links for span > 5.0 M.

    19 The Links shall be designed for :Factored SF as per Analysis.

    SF due to formation of plastic hinges at both ends + gravity loads as per analysis.

    20

    Page 1 of 2Beam design as per IS-13920-1993 Limitations & INFO:

  • Spacing of Links within 2 x d from supports shall be minimum of :

    d/48 x of smallest longitudinal bar.

    21 Spacing of links shall not be < 100 MM.

    22 1st link shall start 50 mm away from support.

    23 Spacing of links away from 2 x d from support shall not be > d 2.

    24 Link spacing shall not be > 300 MM. { As per IS-456-2000 }.

    25 The top as well as bottom reinforcement shall atleast have 2 bars continuous throughout the whole member.