Siemens Smart Generation Solutions Unrestricted © Siemens AG 2014 All rights reserved.
Benefit of Offgrid Hybrid Power Plants with maximum renewable penetration Cost and emission reduction by integrating renewables into diesel plants
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 2
Offgrid Hybrid Power Plants
1. What are the major challenges?
2. How can high renewable penetration be beneficial?
3. How does Siemens support this?
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 3
Opposing trends, new opportunities
Challenges of fuel based generation
Logistic Emissions
Fuel costs Weak / no grids
Shift in technology
Hybrid Power Plants
RE systems
Oil
Time
Cost
Today
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 4
What is a hybrid diesel plant?
PV plant
Storage
Control Center
Wind Plant
Diesel generators
Industrial Load
Residential Load
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 5
$22 mio.
How can high renewable penetration be beneficial?
Diesel generators 11 x 2MW
Diesel price1.09 $/l
Off-grid, e.g. Mine Load Average: 14,47 MW
Lifetime: 13 years
$58 mio.
$11 mio.
$76 mio.
Capex
High Penetration (160%) Low penetration (30%) Medium penetration (100%) Diesel only
PV plant 4,5 MW
30% of load
Control center
Storage
PV plant 15 MW
100% of load
PV plant 24 MW
160% of load
$145 mio.
Cumulated savings (13 years)
$32 mio. $88 mio.
5,2 years 4,6 years
Payback period
3,8 years
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 6
Why to go for highest renewable penetration Standard Test Condition
Even if PV plant installed capacity is designed equal to average load it‘s only possible to achieve 100% renewable penetration if:
Laboratory conditions (STC)
AND
At noon time
0,00
5,00
10,00
15,00
20,00
25,00
00:0
0 01
:00
02:0
0 03
:00
04:0
0 05
:00
06:0
0 07
:00
08:0
0 09
:00
10:0
0 11
:00
12:0
0 13
:00
14:0
0 15
:00
16:0
0 17
:00
18:0
0 19
:00
20:0
0 21
:00
22:0
0 23
:00
Power [MW]
Time
Power output under STC condition
load PV 15 MW STC PV 24 MW STC
Additional production on early and late hours of the day.
Balance to find between additional investment and increase of production.
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 7
Why to go for highest renewable penetration real weather conditions
0,00
5,00
10,00
15,00
20,00
25,00
00:0
0
01:3
0
03:0
0
04:3
0
06:0
0
07:3
0
09:0
0
10:3
0
12:0
0
13:3
0
15:0
0
16:3
0
18:0
0
19:3
0
21:0
0
22:3
0
Power [MW]
Time
100% RE
0,00
5,00
10,00
15,00
20,00
25,00
00:0
0
01:3
0
03:0
0
04:3
0
06:0
0
07:3
0
09:0
0
10:3
0
12:0
0
13:3
0
15:0
0
16:3
0
18:0
0
19:3
0
21:0
0
22:3
0
Power [MW]
Time
160% RE
Power output under real weather conditions
Standard Test Condition Low irradiation Medium irradiation
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 8
Why to go for highest renewable penetration impact of clouds
With a PV plant sized at 160% of average load mostly sufficient RE power can be provided even if clouds covering the plant partially.
0,00
5,00
10,00
15,00
20,00
25,00
00:0
0
01:0
0
02:0
0
03:0
0
04:0
0
05:0
0
06:0
0
07:0
0
08:0
0
09:0
0
10:0
0
11:0
0
12:0
0
13:0
0
14:0
0
15:0
0
16:0
0
17:0
0
18:0
0
19:0
0
20:0
0
21:0
0
22:0
0
23:0
0
Power [MW]
Time
Power output with clouds
load PV 15 MW cloud PV 24 MW cloud
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 9
Siemens Hybrid Power Plants – 24/7 reliable Power
Hours Minutes Seconds Milliseconds
MON
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 10
Sample case study – Philippines Base scenario: Diesel Gensets Only
Base scenario
Diesel Genset (DGS)
Description DGS Diesel Plant Size: 650+650+280kW
Fuel type: Diesel
Diesel cost (delivered) (USD/ l) 1.00
Diesel consumption (l/ yr) 1,752,336
Diesel costs (USD/ yr) 1,752,336
Maintenance costs (USD/ yr) 112,419
Total operating costs (USD/ yr) 1,864,755
CO2 emissions (kg/yr) 4,614,477
Load Profile
1: 650kW 2: 650kW 3: 280kW
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 11
PV Size: 275 kWp Irradiation: 1,622 kWh/m²
Wind Size: 990 kW Velocity: 5.8 m/s
Battery Size: 600 kW, 220 kWh Lithium-Ion
DG 650+650+250 kW (1.85MW), Diesel, Temporarily off
Sample case study – Philippines Optimization: Wind, PV, Storage & Diesel Gensets
Optimization
Hybrid
Description DGS Hybrid Saving Diesel cost (delivered) (USD/ l) 1.00 1.00 -
Diesel consumption (l/ yr) 1,752,336 1,018,981 733,355
Diesel costs (USD/ yr) 1,752,336 1,018,981 733,355
Maintenance costs (USD/ yr) 112,419 231,241 (118,822)
Total operating costs (USD/ yr) 1,864,755 1,250,222 614,533
Investment costs (USD) - 4,598,415 -
LCoE (USD/ kWh) 0.383 0.335 0.048 CO2 emissions (kg/yr) 4,614,477 2,683,313 1,931,164
~42% 6.3 yr
Payback Period
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 12
backed by performance guarantees
Siemens support Benefits from a world class turnkey supplier
Focus on customer requirements 1
Solutions covering the complete scope 2
One-stop turnkey solution 3
Worldwide experience in turnkey implementation 4
Financial strength 5
Credibility to attract financial partners 6
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 13
Published by and Copyright 2014:
Siemens AG Energy Sector Power Generation Instrumentation, Controls & Electrical
Siemensallee 84 76187 Karlsruhe, Germany
Tel.: + 49 9131 / 18 – 84105
This document contains forward-looking statements and information – that is, statements related to future, not past, events. These statements may be identified either orally or in writing by words as “expects”, “anticipates”, “intends”, “plans”, “believes”, “seeks”, “estimates”, “will” or words of similar meaning. Such statements are based on our current expectations and certain assumptions, and are, therefore, subject to certain risks and uncertainties. A variety of factors, many of which are beyond Siemens’ control, affect its operations, performance, business strategy and results and could cause the actual results, performance or achievements of Siemens worldwide to be materially different from any future results, performance or achievements that may be expressed or implied by such forward-looking statements. For us, particular uncertainties arise, among others, from changes in general economic and business conditions, changes in currency exchange rates and interest rates, introduction of competing products or technologies by other companies, lack of acceptance of new products or services by customers targeted by Siemens worldwide, changes in business strategy and various other factors. More detailed information about certain of these factors is contained in Siemens’ filings with the SEC, which are available on the Siemens website, www.siemens.com and on the SEC’s website, www.sec.gov. Should one or more of these risks or uncertainties materialize, or should underlying assumptions prove incorrect, actual results may vary materially from those described in the relevant forward-looking statement as anticipated, believed, estimated, expected, intended, planned or projected. Siemens does not intend or assume any obligation to update or revise these forward-looking statements in light of developments which differ from those anticipated.
Trademarks mentioned in this document are the property of Siemens AG, it's affiliates or their respective owners.
Subject to change without prior notice. The information in this document contains general descriptions of the technical options available which do not always have to be present in individual cases. The required features should therefore be specified in each individual case at the time of closing the contract. Smart Generation Solutions E P IE AL:N ECCN:N
To obtain further information, please contact: [email protected]
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 14
backup
Siemens Hybrid Power Solutions
Unrestricted © Siemens AG 2014 All rights reserved.
Page 15
Our solution: Fleet Control is the "brain" of distributed power plant control
Central Control & Operation
Combined solution provides highest availability, lowest OPEX and maximum earnings
Reliable and secure control
Generation optimization
Fleet Generation Optimization
Price
Capacity
Demand Optimizer
Schedules
Fleet Control